DOCUMENT
NUMBER
SLTEC1-COM-CPT-0013
TITLE
1 7
Items
Prerequisit
All commissioning activities of light fuel oil system (fuel oil pump house
and plant area) have been completed with the positive results in
2 agreement to prepared ITP. Main line of the fuel oil system air blow off
completed and is full with fuel oil.
All cold commissioning activities of Boiler Gas Fuel system have been
completed with the positive results in agreement to prepared ITP. Trail
4 running of IDF, HPFF, PAF and SAF is completed as the result of cold
commissioning.
Bed material is filled into the furnace at the static height of about
5 700mm and the bed material fluidizing test completed.
Ignition System
es
Start
fans
Check
1
Reference
documents
Description
NO
up
2 7
(Below Boiler)
Ignition/CS
Oil
1
Shut the isolating valves on the oil supply pipe and oil return pipe
between unit 1 and unit 2. Fully open the return oil manual valve
1 10HJF60AA001, return oil control valve 10HJF60AA101 and return oil
fast shutoff valve10HJF60AA005. FSSS
Start up the oil supplying pump A and control the pump outlet pressure
2 at about 4.0MPa by the pump return oil valve J0ERB50AA101.
Establish
oil pressure
of
the
system
Test Logic will automatically open the oil trip valve, oil return valve and
2 control valve to cycle the fuel oil and establish oil pressure.
Turn off the oil return valve until the fuel has circled for 15 seconds.
Determine whether the fuel oil-filled pressure to meet the test
3
requirements. Continue the test when oil pressure is right, otherwise
fail.
Close the oil trip valve. Delay 120 seconds, to determine whether the
4 rear oil pressure of the trip valve is low. If it isnt, continue the test. If
the rear pipe of the trip valve or the angle valve is leaking, test fail.
Fuel oil
leak test
3 7
Oil gun
atomizatio
n simple
test
Furnace air
purging
Open the oil return fast shutoff valve to drain, delay of 30 seconds and
5 judge the differential pressure of the trip valve. If it is high, it shows that
the pressure has fallen.
Close the oil return fast shutoff valve, delay of 30 seconds and continue
6 to judge the differential pressure of the trip valve. If the pressure alarm
maintains high, the valve can be proved that is not leaking.
Put the metal pail on the ground near the oil guns with sand or ash
1 under the pail.
2 Remove the bolts of A1 oil gun flange and pull the oil gun out.
Control the supply oil pressure to 3.2MPa and maintain this pressure.
Put the oil gun muzzle at the metal pail, manually open Oil Supply Valve
(10HJA10AA002) and Return Valve (10HJA20AA002) of A1 oil gun at
local panel and observe the atomization of oil. If there is no oil drop or
stream, then the atomization test succeed.
Drop the oil pressure to 2.5MPa, repeat steps above. If succeeding, then
continue to drop the oil pressure with the oil atomization observation
until the oil cannot be atomized. Record this pressure of un-atomization.
Conduct atomization test of A2, B1 and B2 oil guns by the same way of
A1 oil gun atomization test.
After the oil leak test completed, press the furnace purging button to
1 purge the furnace for 5 minutes.
Shutdown SAF B, adjust the SAF A inlet damper to drop the total air
2 volume at 120000 m3/h.
Oil ignition system has three control modes, which are local, remote and
automatic.
1) In local control mode, oil guns and can be operated by the START
or SHUTDOWN button on the ignition control panel respectively.
Oil Ignition
Sequence
Control
2) In remote control model, oil guns can be operated from the DCS
respectively.
3) In automatic mode, the sequence control program will run when
operator press Auto start button on DCS.
4 7
Increase
IDF
load
to
ensure
the
furnace
2 pressure(10HBK10CP107,10HBK20CP107) keep at about -150Pa.
Slowly close the oil return control valve 10HJF60AA101 according to the
supply oil pressure (10HJF10CP501) dropping, maintain the oil
4 supplying pressure at 2.5-3.0MPa. Then put the valve into automatic
control mode.
5 Check if the flame is bright at local and ensure oil is well burning.
Oil shut
down and
air purge
2
Precaution
during
ignition
the quick closing valve of supply oil header pipe shut, and
the quick closing valve of return oil header pipe shut.
2
If oil gun is not at the remote mode, or any trip signal exists, purging
2 is not permitted.
5 7
When additional oil gun put into operation, the furnace pressure shall be
keep at -50Pa~-100Pa, and the Oxygen content analysis of gas
3 (10HBK10CQ101, 10HBK20CQ101) shall be observed to decide if oil
burning well .
Control the outlet flue gas temperature of ignition air path not higher
4 than 980, air chamber temperature below 870 during ignition.
NEVER cut off the cooling air for flame scanner during ignition and
6 shutdown.
6 7
Remarks
CNTIC:
DMCI:
Signature
Date:
7 7
Owner: