ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT,

JUBAIL
(GREENFIELD PROJECT)

INSTRUMENT
INDEX
SO2 PRODUCTION PLANT
PROJECT NO.
P002429-001
DOCUMENT NUMBER:
2429.1-10-IC-INX-001-0

Issued for Design

KD

MM

SMA

6/6/2013

Issued for Client


Comments

AM

MM

SMA

5/22/2013

REV

DESCRIPTION

ORIGIN

REVIEW

L&T IES APPROVAL

DATE

CLIENT APPROVAL

DATE

DISCLAIMER:
This report has been prepared on behalf of and for exclusive use of ADDAR and is subject to and issued in accordance with the agreement between ADDAR and L&T-IES. L&T-IES accepts no liability or
responsibility whatsoever for it in respect of any use or reliance upon this report by any third party.
Copying this report without the permission of ADDAR or L&T-IES is not permitted.

APPENDIX 1: LEGEND SHEET


ABBREVIATION:
AI - ANALOGUE INPUT
AO - ANALOGUE OUTPUT
DI - DIGITAL INPUT
DO - DIGITAL OUTPUT
DCS - DISTRIBUTED CONTROL SYSTEM
REFERENCE DOCUMENT:
LEGEND & SYMBOL FOR INSTRUMENTATION - 2429.1-30-PR-LSD-003-C
1.P&ID DRG. NO.2429.1-10-PR-PID-001 -E
1.P&ID DRG. NO.2429.1-10-PR-PID-002-E
1.P&ID DRG. NO.2429.1-10-PR-PID-003-E
1.P&ID DRG. NO.2429.1-10-PR-PID-004-E
1.P&ID DRG. NO.2429.1-10-PR-PID-005-E
1.P&ID DRG. NO.2429.1-10-PR-PID-006-E
1.P&ID DRG. NO.2429.1-10-PR-PID-007-E
1.P&ID DRG. NO.2429.1-10-PR-PID-008-E
1.P&ID DRG. NO.2429.1-10-PR-PID-009-E
IPDS DOC NO. 2429.1-10-PR-DAS-016-C
IPDS DOC NO. 2429.1-10-PR-DAS-017-C
IPDS DOC NO. 2429.1-10-PR-DAS-018-C
IPDS DOC NO. 2429.1-10-PR-DAS-019-C
IPDS DOC NO. 2429.1-10-PR-DAS-020-C
IPDS DOC NO. 2429.1-10-PR-DAS-021-C
IPDS DOC NO. 2429.1-10-PR-DAS-023-C
IPDS DOC NO. 2429.1-10-PR-DAS-024-C

NOTES:

323010866.xls

07/05/2016
09:12:24

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

TAG NO.

1
2

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

Norm.

Max.

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

FLOW
(m3/hr)

DESIGN TEMP.
(OC)

Min.

Norm.

Max.

32

36

38

LEVEL
(mm)

CALIBRATION RANGE

ALARM SET POINTS


P&ID NO.

P&ID REV.
NO.

LINE NO. / EQUIPMENT NO.

2429.1-10-PR-PID001

100-CWR-10001-A4A

UNITS
Min.

Norm.

Max.

60

Min.

Norm.

Max.

Min.

Max.

14

pH

LL

HH

AT-1001

Cooling Water

Liquid

pH Analyser Transmitter

AI

Field

DCS

AI-1001

pH Analyser Indication

Soft

DCS

DCS

2429.1-10-PR-PID001

QAH-1001

pH Analyser Alarm high

Soft

DCS

DCS

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

E
E

A-1001
3
4

QAL-1001

AT-1002

Cooling Water

AI-1002

Liquid
-

pH Analyser Alarm Low


pH Analyser Transmitter
pH Analyser Indication

Soft
AI
Soft

DCS
Field
DCS

DCS
DCS

6
0

32

38

45

60

14

pH

DCS

A-1002
7

QAH-1002

pH Analyser Alarm High

Soft

DCS

DCS

QAL-1002

pH Analyser Alarm Low

Soft

DCS

DCS

FE-1001

Cooling Water

Liquid

Flow Element

Field

Field

25

32

36

60

20

24

Flow Transmitter

AI

Field

DCS

0 25

32

36

60

20

24

Flow Indication

Soft

DCS

DCS

10

FT-1001

FT-201

30

m3/hr

2429.1-10-PR-PID004

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

E
E

F-1001
11

FI-1001

12

FAL-1001

13

SO3

FE-1002

14

FT-1002

15

FI-1002

Liquid
-

Flow Alarm Low


Flow Element
Flow Transmitter
Flow Indication

Soft
AI
Soft

DCS
Field
Field
DCS

DCS
Field
DCS

5
0
0

8.6
8.6

11
11

11
11

25

25

35

35

43

100

43

100

0.01
0.01

0.2

0.3

0.2

0.3

0.5

m3/hr

DCS

0.04

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

E
E

DCS

DCS

FALL-1002

Flow Alarm Low Low

Soft

DCS

DCS

18

FDA-1002

Flow Differential Alarm

Soft

DCS

DCS

19

FE-1003

SO3

Liquid

Flow Element

Field

Field

FT-1003

Flow Transmitter

AI

Field

DCS

8.6

11
11

11
11

25

25

35

35

43

100

0.01

0.22

0.3

43

100

0.01

0.22

0.3

0.5

m /hr

Soft

8.6

Flow Alarm Low

0 0.1

20

2429.1-10-PR-PID004

FAL-1002

17

F-1002
16

F-1003
21

FI-1003

22

FAL-1003

23

FE-1004

24

Sulfur

Liquid

Flow Indication
Flow Alarm Low
Flow Element

Soft
Soft
-

DCS
DCS
Field

DCS
DCS
Field

8.7

11

11

120

125

150

200

0.01

0.05

0.1

0.1
-

2429.1-10-PR-PID004

DCS

2429.1-10-PR-PID004

DCS

DCS

0.08

2429.1-10-PR-PID004

DCS

DCS

0.03

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

E
E

FT-1004

Flow Transmitter

AI

Field

DCS

FI-1004

Flow Indication

Soft

DCS

26

FAH-1004

Flow Alarm High

Soft

27

FAL-1004

Flow Alarm Low

Soft

25

8.7

11

11

120

125

150

200

0.01

0.05

0.1

0.2

m3/hr

F-1004

28

FALL-1004

Flow Alarm Low Low

Soft

DCS

DCS

29

FE-1005

HW/CW

Liquid

Flow Element

Field

Field

32

70

90

150

30

50

60

30

FT-1005

Flow Transmitter

AI

Field

DCS

32

70

90

150

30

50

60

80

m /hr
3

0.02
-

F-1005
31

FI-1005

Flow Indication

Soft

DCS

DCS

32

FAL-1005

Flow Alarm Low

Soft

DCS

DCS

33

FE-1006

Cooling Water

Liquid

Flow Element

Field

Field

32

36

60

10

12.5

Flow Transmitter

AI

Field

DCS

32

36

60

10

12.5

Flow Indication

Soft

DCS

DCS

34

FT-1006

FT-202

30

30

40

m3/hr

35

2429.1-10-PR-PID004

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

E
E

F-1006
35

FI-1006

36

FIQ-1006

37

FE-1007

38

FT-1007

FT-203

Flow Indicator Totaliser

Soft

DCS

DCS

Cooling Water

Liquid

Flow Element

Field

Field

32

36

60

10

12.5

Flow Transmitter

AI

Field

DCS

32

36

60

10

12.5

30

30

40

m /hr
3

F-1007
39

FI-1007

Flow Indication

Soft

DCS

DCS

40

FIQ-1007

Flow Indicator Totaliser

Soft

DCS

DCS

41

FE-1008

Cooling Water

Liquid

Flow Element

Field

Field

32

36

60

10

12.5

Flow Transmitter

AI

Field

DCS

32

36

60

10

12.5

Flow Indication

Soft

DCS

DCS

42

FT-1008

FT-204

30

30

40

m3/hr

2429.1-10-PR-PID007

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

F-1008
43
323010866.xls

FI-1008

07/05/2016
09:12:24

3 of 30

80-CWR-10002-A2A

80-CWS-10001-A4A

40-P-10030+A2A-ET-IH-40

40-P-10030+A2A-ET-IH-40

25-P-10050-A2A-ET-IH-40

100-CWS-10003A4A-IH-40

80-CWS-10005-A4A

80-CWS-10006-A4A

80-CWS-10007-A4A

SR. NO.

F-1008

LOOP NO.

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
TAG NO.

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

Norm.

Max.

Min.

Date

6/6/2013

FLOW
(m3/hr)

DESIGN TEMP.
(OC)

Norm.

Max.

LEVEL
(mm)

Min.

Norm.

Max.

FIQ-1008

Flow Indicator Totaliser

Soft

DCS

DCS

45

FE-1009

Cooling Water

Liquid

Flow Element

Field

Field

32

36

60

10

12.5

30

Flow Transmitter

AI

Field

DCS

32

36

60

10

12.5

0 30

FT-1009

FT-205

CALIBRATION RANGE

ALARM SET POINTS


P&ID NO.

P&ID REV.
NO.

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

E
E

UNITS

44

46

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

Min.

Norm.

Max.

Min.

Max.

40

m3/hr

LL

HH

F-1009
47

FI-1009

48

FIQ-1009

49

SO2

FE-1010

50

FT-1010

Liquid
-

Flow Indication
Flow Indicator Totaliser
Flow Element
Flow Transmitter

Soft
Soft
AI

DCS
DCS
Field
Field

DCS

DCS
Field
DCS

4.5
4.5

8.5
8.5

10
10

12.5

35

12.5

35

40

55

40

100

55

100

5
5

7
7

8.5

8.5

15

m3/hr

F-1010
51

FI-1010

Flow Indication

Soft

DCS

DCS

2429.1-10-PR-PID008

52

FIQ-1010

Flow Indicator Totaliser

Soft

DCS

DCS

2429.1-10-PR-PID008

53

LT-1001

SO3

Liquid

Level Transmitter

AI

Field

DCS

2429.1-10-PR-PID001

54

LI-1001

Level Indication

Soft

DCS

DCS

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

E
E

55

L-1001

56

LT-204

LAH-1001

LAL-1001

57

LALL-1001

58

LT-1002

LT-203

SO3

Liquid

Level Alarm High


Level Alarm Low
Level Alarm Low Low
Level Transmitter

Soft
Soft
Soft
AI

DCS
DCS
DCS
Field

0.1

3.5

25

35

43

100

160

Variable

1280

0% =0

100% =1280

mm

DCS

DCS

215

DCS
DCS

0.1

3.5

25

35

43

100

160

Variable

1280

0% =0

100% =1280

mm

185
-

1235
-

LI-1002

Level Indication

Soft

DCS

DCS

2429.1-10-PR-PID001

LAH-1002

Level Alarm High

Soft

DCS

DCS

1235

2429.1-10-PR-PID001

61

LAL-1002

Level Alarm Low

Soft

DCS

DCS

215

2429.1-10-PR-PID001

62

LALL-1002

Level Alarm Low Low

Soft

DCS

DCS

185

2429.1-10-PR-PID001

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID002

E
E

59
60

L-1002

63

LT-1003

64

LT-205

LI-1003

65

SO3
-

LAH-1003

Liquid
-

Level Transmitter
Level Indication
Level Alarm High

AI
Soft
Soft

Field
DCS
DCS

DCS

0.1

3.5

25

40

43

100

125

Variable

1000

0% =0

100% =1000

mm

DCS

DCS

965

L-1003
66

LAL-1003

Level Alarm Low

Soft

DCS

DCS

170

67

LALL-1003

Level Alarm Low Low

Soft

DCS

DCS

145

2429.1-10-PR-PID002

68

LAHH-1003

Level Alarm High High

Soft

DCS

DCS

985

2429.1-10-PR-PID002

69

LT-1004

SO3

Liquid

Level Transmitter

AI

Field

DCS

2429.1-10-PR-PID002

70

LI-1004

Level Indication

Soft

DCS

DCS

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID002

E
E

71

LT-206

LAH-1004

Level Alarm High

Soft

DCS

0.1

3.5

25

40

43

100

125

Variable

1000

0% =0

100% =1000

mm

DCS

965

L-1004
72

LAL-1004

73

LALL-1004

74

LAHH-1004

75

LT-1005

Level Alarm Low


Level Alarm Low Low
Level Alarm High High

Soft
Soft
Soft

DCS
DCS
DCS

DCS

170

DCS

DCS

145
985

2429.1-10-PR-PID003

DCS

2429.1-10-PR-PID003

DCS

DCS

1150

2429.1-10-PR-PID003

DCS

DCS

2429.1-10-PR-PID003

2429.1-10-PR-PID003

2429.1-10-PR-PID003

2429.1-10-PR-PID003

2429.1-10-PR-PID003

E
E

Sulfuric Acid

Liquid

Level Transmitter

AI

Field

DCS

LI-1005

Level Indication

Soft

DCS

77

LAH-1005

Level Alarm High

Soft

78

LAL-1005

Level Alarm Low

Soft

76

LT-209

0.1

3.5

40

50

100

Variable

1200

0% =0

100% =1200

mm

L-1005

79

LT-1006

80

LT-210

LI-1006

25% Oleum
-

Liquid
-

Level Transmitter
Level Indication

AI
Soft

Field
DCS

DCS

0.1

3.5

40

50

100

Variable

1200

0% =0

100% =1200

mm

DCS

L-1006
81

LAH-1006

82

LAL-1006

83

LT-1007

84
85

LT-207

Level Alarm High


Level Alarm Low

Soft
Soft

DCS
DCS

DCS

DCS

1150
-

2429.1-10-PR-PID003

DCS

2429.1-10-PR-PID003

DCS

DCS

1390

2429.1-10-PR-PID003

DCS

DCS

245

2429.1-10-PR-PID003

Sulfur

Liquid

Level Transmitter

AI

Field

DCS

LI-1007

Level Indication

Soft

DCS

LAH-1007

Level Alarm High

Soft

LAL-1007

Level Alarm Low

Soft

0.2

3.5

120

125

150

200

180

1260

1440

0% =0

100% =1440

mm

L-1007
86
323010866.xls

07/05/2016
09:12:24

4 of 30

LINE NO. / EQUIPMENT NO.

80-CWS-10008-A4A

50-P-10111-A2A

On V-101A

On V-101B

On T-101A

On T-101B

On DT-101

On DT-103

On DT-102

SR. NO.

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)

L-1007

LOOP NO.

TAG NO.

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

87

LAHH-1007

Level Alarm High High

Soft

DCS

DCS

88

LDA-1007

Level Deviation Alarm

Soft

DCS

DCS

89

LT-1008

Sulfur

Liquid

Level Transmitter

AI

Field

DCS

90
91

LIC-1008
L-1008

LI-1008

92

LAH-1008

93

LAL-1008

94

LT-1009

95
96

L-1009

97
98

LT-205

Level Indication
Level Alarm High
Level Alarm Low

Soft
Soft
Soft
Soft

DCS
DCS
DCS
DCS

0% =0

Max.

P&ID NO.

P&ID REV.
NO.

2429.1-10-PR-PID003

2429.1-10-PR-PID003

100% =1440

mm

2429.1-10-PR-PID003

2429.1-10-PR-PID003

2429.1-10-PR-PID003

2429.1-10-PR-PID003

2429.1-10-PR-PID003

E
E

LL

HH

1415

245

1390
-

2429.1-10-PR-PID004

DCS

DCS

1681

2429.1-10-PR-PID004

DCS

DCS

91

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

E
E

Level Alarm High

Soft

LAL-1009

Level Alarm Low

Soft

DCS
Field
DCS

0.1

0.2

3.5

70

90

100

150

250

1750

2000

0% =0

100% =
1751

Soft

1440

Min.

Level Indication

1260

Max.

LAH-1009

180

Norm.

DCS

Min.

DCS

Soft

LI-1010

200

Max.

Level Indication

AI

150

Norm.

Level Transmitter

125

Min.

Mixed

120

ALARM SET POINTS


UNITS

LI-1009

H2SO4+SO2 Gas

CALIBRATION RANGE

2429.1-10-PR-PID004

DCS

Soft

3.5

Max.

LEVEL
(mm)

DCS

Field

Level Alarm Low Low

0.2

Norm.

FLOW
(m3/hr)

DESIGN TEMP.
(OC)

DCS

AI

Min.

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

DCS

Level Transmitter

Max.

6/6/2013

DCS

Liquid

LT-1010

100

Level Indicator Controller

Hot water

LALL-1009

99

Norm.

Date
2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

mmWC

DCS
DCS

5.6

10

60

62

75

100

147.5

1032.5

1180

0% =0

100% =1180

mm

DCS

36
-

L-1010
101

LAH-1010

Level Alarm High

Soft

DCS

DCS

1140

200

2429.1-10-PR-PID005

2429.1-10-PR-PID005

DCS

2429.1-10-PR-PID005

DCS

1140

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

E
E

102

LAL-1010

Level Alarm Low

Soft

DCS

DCS

103

LT-1011

H2SO4+SO2 Gas

Mixed

Level Transmitter

AI

Field

DCS

LI-1011

Level Indication

Soft

DCS

LAH-1011

Level Alarm High

Soft

DCS

104

5.6

10

60

62

75

100

147.5

1032.5

1180

0% =0

100% =1180

mm

L-1011
105
106

LAL-1011

107

H2SO4+SO2 Gas

LT-1012

108

LI-1012

Mixed
-

Level Alarm Low


Level Transmitter
Level Indication

Soft
AI
Soft

DCS
Field
DCS

DCS
DCS

200
0

5.6

10

60

62

75

100

147.5

1032.5

1180

0% =0

100% =1180

mm

DCS

L-1012
109

LAH-1012

110

LAL-1012

111

LT-1013

112
113

L-1013

114

116

119

120
121

123
124

2429.1-10-PR-PID006

DCS

2429.1-10-PR-PID006

DCS

1160

2429.1-10-PR-PID006

2429.1-10-PR-PID006

2429.1-10-PR-PID006

2429.1-10-PR-PID006

2429.1-10-PR-PID006

E
E

Level Transmitter

AI

Field

DCS

LI-1013

Level Indication

Soft

DCS

LAH-1013

Level Alarm High

Soft

DCS

LALL-1013

Spent Sulphuric
LT-208
Acid
-

Liquid
-

Level Alarm Low


Level Alarm Low Low
Level Transmitter
Level Indication

Soft
Soft
AI
Soft

DCS
DCS
Field
DCS

DCS

3.5

35

40

60

100

150

1050

1200

0% =0

100% =1200

mm

202.5
0

0.2

3.5

35

40

60

100

150

1050

1200

0% =0

100% =1200

mm

170
-

LAH-1014

Level Alarm High

Soft

DCS

DCS

1160

2429.1-10-PR-PID006

LAL-1014

Level Alarm Low

Soft

DCS

DCS

202.5

2429.1-10-PR-PID006

LALL-1014

Level Alarm Low Low

Soft

DCS

DCS

170

2429.1-10-PR-PID006

Hot water

Liquid

Level Transmitter

AI

Field

DCS

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

E
E

LT-208

LAH-1015

Level Alarm High


Level Alarm Low
Level Alarm Low Low

Soft
Soft
Soft
Soft

DCS
DCS
DCS
DCS

0.1

1.5

3.5

40

55

70

150

250

1750

2000

0% =0

100% =
1751

mmWC

DCS

DCS

DCS

LT-1016

Mixed

Level Transmitter

AI

Field

DCS

127

LI-1016

Level Indication

Soft

DCS

LAH-1016

Level Alarm High

Soft

LAL-1016

Level Alarm Low

Soft

LT-215

Level Indication

126

323010866.xls

0.2

DCS

129

DCS

Liq.SO2+SO2
Gas

L-1016

DCS

LALL-1015

128

1140

Liquid

200

Strong
Sulphuric Acid

LT-219

2429.1-10-PR-PID005

DCS

LAL-1015

125

DCS

DCS

LI-1015
L-1015

DCS

Soft

LT-1015

122

Soft

Level Alarm Low

LI-1014
L-1014

Level Alarm High

LT-1014

117

LAL-1013

115

118

88

DCS

36

1681
-

2429.1-10-PR-PID007

DCS

2429.1-10-PR-PID007

DCS

DCS

1158

2429.1-10-PR-PID007

DCS

DCS

202.5

2429.1-10-PR-PID007

07/05/2016
09:12:24

10

40

45

55

100

5 of 30

150

1050

1200

0% =0

100% =1200

mm

LINE NO. / EQUIPMENT NO.

On DT-102

On T-105

On T-102

On T-103

On T-104

On T-107

On T-106

On T-108

On V-102A

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

L-1016
SR. NO.

LOOP NO.

PRESSURE
(kg/cm2g)
TAG NO.

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

130

LALL-1016

131

LT-1017

132

LI-1017

133

L-1017

134

LT-216

LAH-1017

LT-1018

Level Alarm Low Low

Soft

DCS

DCS

Liq.SO2+SO2
Gas

Mixed

Level Transmitter

AI

Field

DCS

Level Indication

Soft

DCS

DCS

LALL-1017

136

LAL-1017

135

LT-217

SO2

Liquid

Level Alarm High


Level Alarm Low
Level Alarm Low Low
Level Transmitter

Soft
Soft
Soft
AI

DCS
DCS
DCS
Field

Norm.

Max.

Min.

10

40

Norm.

45

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

FLOW
(m3/hr)

DESIGN TEMP.
(OC)
Max.

55

CALIBRATION RANGE

ALARM SET POINTS

Norm.

Max.

Min.

150

Norm.

1050

Max.

1200

Min.

0% =0

Max.

100% =1200

mm

DCS

DCS
7

10

35

40

55

100

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID008

E
E

HH

170

4.5

LL

202.5

P&ID REV.
NO.

DCS

DCS

P&ID NO.

UNITS
Min.

100

LEVEL
(mm)

150

1050

1200

0% =0

100% =1200

mm

170
-

1158
-

LI-1018

Level Indication

Soft

DCS

DCS

2429.1-10-PR-PID008

LAH-1018

Level Alarm High

Soft

DCS

DCS

1160

2429.1-10-PR-PID008

139

LAL-1018

Level Alarm Low

Soft

DCS

DCS

202.5

2429.1-10-PR-PID008

140

LALL-1018

Level Alarm Low Low

Soft

DCS

DCS

170

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

E
E

137
138

L-1018

141

LT-1019

142
143

LI-1019
L-1019

144

LAL-1019

145
146

LAH-1019

147

LT-218

SO2
-

Liquid
-

Level Transmitter
Level Indication
Level Alarm High
Level Alarm Low

AI
Soft
Soft
Soft

Field
DCS
DCS
DCS

DCS

4.5

10

35

40

55

100

150

1050

1200

0% =0

100% =1200

mm

DCS

DCS

DCS

202.5

1160
-

170

2429.1-10-PR-PID008

2429.1-10-PR-PID007

DCS

2429.1-10-PR-PID007

DCS

1158

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

E
E

LALL-1019

Level Alarm Low Low

Soft

DCS

DCS

LT-1020

Liq.SO2+SO2
Gas

Mixed

Level Transmitter

AI

Field

DCS

LI-1020

Level Indication

Soft

DCS

LAH-1020

Level Alarm High

Soft

DCS

10

40

45

55

100

150

1050

1200

0% =0

100% =1200

mm

L-1020
148
149
150

151

LAL-1020

LT-1021

Liq.SO2+SO2
Gas

LI-1021

Mixed
-

Level Alarm Low


Level Transmitter
Level Indication

Soft
AI
Soft

DCS
Field
DCS

DCS
DCS

202.5
3

10

40

45

55

100

150

1050

1200

0% =0

100% =1200

mm

DCS

L-1021
152

LAH-1021

153
154

155

Level Alarm High

Soft

DCS

DCS

202.5

1158

202.5

2429.1-10-PR-PID007

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID008

DCS

1160

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

E
E

LAL-1021

Level Alarm Low

Soft

DCS

DCS

LT-1022

SO2

Liquid

Level Transmitter

AI

Field

DCS

LI-1022

Level Indication

Soft

DCS

LAH-1022

Level Alarm High

Soft

DCS

4.5

10

35

40

55

100

150

1050

1200

0% =0

100% =1200

mm

L-1022
156
157
158

LAL-1022

159

LT-1023
LI-1023

SO2
-

Liquid
-

Level Alarm Low


Level Transmitter
Level Indication

Soft
AI
Soft

DCS
Field
DCS

DCS
DCS

202.5
3

4.5

10

35

40

55

100

DCS

150

1050

1200

0% =0

100% =1200

mm

L-1023
160

LAH-1023

Level Alarm High

Soft

DCS

DCS

1160

LINE NO. / EQUIPMENT NO.

On V-102B

On V-103A

On V-103B

On V-102A

On V-102B

On V-103A

On V-103B

161

LAL-1023

Level Alarm Low

Soft

DCS

DCS

202.5

2429.1-10-PR-PID008

162

XR-101A

Motor Stopped

DI

Field

DCS

2429.1-10-PR-PID002

P-101A

XL101A

Motor Running

DI

Field

DCS

2429.1-10-PR-PID002

P-101A

HSL-101A

Stop Command

DO

DCS

Field

2429.1-10-PR-PID002

P-101A

2429.1-10-PR-PID002

P-101B

2429.1-10-PR-PID002

P-101B

2429.1-10-PR-PID002

P-101B

2429.1-10-PR-PID003

P-102A

P-102A

163

M-101A

164
165
166

XR-101B
M-101B

167

XL-101B
HSL-101B

168

XR-102A

Motor Stopped
Motor Running
Stop Command
Motor Stopped

DI
DI
DO
DI

Field
Field
DCS
Field

DCS

DCS

Field

DCS

XL102A

Motor Running

DI

Field

DCS

2429.1-10-PR-PID003

170

HSL-102A

Stop Command

DO

DCS

Field

2429.1-10-PR-PID003

P-102A

171

XR-102B

Motor Stopped

DI

Field

DCS

2429.1-10-PR-PID003

P-102B

XL-102B

Motor Running

DI

Field

DCS

2429.1-10-PR-PID003

P-102B

169

172

M-102A

M-102B

323010866.xls

07/05/2016
09:12:24

6 of 30

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

M-102B

TAG NO.

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

Norm.

Max.

Min.

Norm.

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

FLOW
(m3/hr)

DESIGN TEMP.
(OC)
Max.

LEVEL
(mm)

CALIBRATION RANGE

ALARM SET POINTS


UNITS

Min.

Norm.

Max.

Min.

Norm.

Max.

Min.

Max.

LL

HH

P&ID NO.

P&ID REV.
NO.

LINE NO. / EQUIPMENT NO.

173

HSL-102B

Stop Command

DO

DCS

Field

2429.1-10-PR-PID003

P-102B

174

XR-105A

Motor Stopped

DI

Field

DCS

2429.1-10-PR-PID004

P-105A

XL105A

Motor Running

DI

Field

DCS

2429.1-10-PR-PID004

P-105A

2429.1-10-PR-PID004

P-105A

2429.1-10-PR-PID004

P-105B

2429.1-10-PR-PID004

P-105B

2429.1-10-PR-PID004

P-105B

P-106

175

M-105A

176

HSL-105A

177
178

XR-105B
M-105B

179

XL-105B

HSL-105B

Stop Command
Motor Stopped
Motor Running
Stop Command

DO
DI
DI
DO

DCS
Field
Field
DCS

Field

DCS

DCS

Field

XR-106

Motor Stopped

DI

Field

DCS

2429.1-10-PR-PID006

XL-106

Motor Running

DI

Field

DCS

2429.1-10-PR-PID006

P-106

182

HSL-106

Stop Command

DO

DCS

Field

2429.1-10-PR-PID006

P-106

183

XR-107

Motor Stopped

DI

Field

DCS

2429.1-10-PR-PID006

P-107

2429.1-10-PR-PID006

P-107

2429.1-10-PR-PID006

P-107

2429.1-10-PR-PID007

P-108A

2429.1-10-PR-PID007

P-108A

P-108A

180
181

184

M-106

M-107

185

HSL-107

186
187

XL-107

XR-108A
M-108A

XL108A

Motor Running
Stop Command
Motor Stopped
Motor Running

DI
DO
DI
DI

Field
DCS
Field
Field

DCS

Field

DCS

DCS

188

HSL-108A

Stop Command

DO

DCS

Field

2429.1-10-PR-PID007

189

XR-108B

Motor Stopped

DI

Field

DCS

2429.1-10-PR-PID007

P-108B

XL-108B

Motor Running

DI

Field

DCS

2429.1-10-PR-PID007

P-108B

HSL-108B

Stop Command

DO

DCS

Field

2429.1-10-PR-PID007

P-108B

2429.1-10-PR-PID008

P-109A

2429.1-10-PR-PID008

P-109A

2429.1-10-PR-PID008

P-109A

2429.1-10-PR-PID008

P-109B

P-109B

190

M-108B

191
192
193

XR-109A
M-109A

194

XL-109A

HSL-109A

195

XR-109B

Motor Stopped
Motor Running
Stop Command
Motor Stopped

DI
DI
DO
DI

Field
Field
DCS
Field

DCS

DCS

Field

DCS

XL-109B

Motor Running

DI

Field

DCS

2429.1-10-PR-PID008

197

HSL-109B

Stop Command

DO

DCS

Field

2429.1-10-PR-PID008

P-109B

198

XR-AG-101A

Motor Stopped

DI

Field

DCS

2429.1-10-PR-PID004

P-AG-101

XL-AG-101A

Motor Running

DI

Field

DCS

2429.1-10-PR-PID004

P-AG-101

2429.1-10-PR-PID004

P-AG-101

2429.1-10-PR-PID003

25-LS-10016-A2A-IH-40

2429.1-10-PR-PID003

2429.1-10-PR-PID003

E
E

196

199

M-109B

M-AG-101

200

HSL-AG-101A

Stop Command

DO

DCS

Field

201

PT-1001

LP Steam

Vapor

Pressure Transmitter

AI

Field

DCS

3.5

143

147.9

152

165

10

Kg/cm (g)
2

P-1001
202

PI-1001

203

PT-1002

LP Steam

Vapor

Pressure indication
Pressure Transmitter

Soft
AI

DCS
Field

DCS
DCS

3.5

143

147.9

152

165

10

Kg/cm2 (g)

P-1002
-

2429.1-10-PR-PID003

2429.1-10-PR-PID004

DCS

2429.1-10-PR-PID004

DCS

2429.1-10-PR-PID004

2429.1-10-PR-PID004

7.2

2429.1-10-PR-PID004

2429.1-10-PR-PID004

2429.1-10-PR-PID004

E
E

204

PI-1002

Pressure indication

Soft

DCS

DCS

205

PT-1003

SO2+SO3

Gas

Pressure Transmitter

AI

Field

DCS

206

PI-1003

Pressure indication

Soft

DCS

PAH-1003

Pressure Alarm High

Soft

DCS

207

7.5

10.5

60

65

70

150

10

Kg/cm2 (g)

P-1003
208

PAL-1003

209

PAHH-1003

210

PDA-1003

211

SO2+SO3

PT-1004

Gas

Pressure Alarm Low


Pressure Alarm High High
Pressure Deviation Alarm
Pressure Transmitter

Soft
Soft
Soft
AI

DCS
DCS
DCS
Field

DCS

DCS

DCS
DCS

7.5

10.5

40

65

70

150

10

Kg/cm2 (g)

PI-1004

Pressure indication

Soft

DCS

DCS

2429.1-10-PR-PID004

213

PAH-1004

Pressure Alarm High

Soft

DCS

DCS

2429.1-10-PR-PID004

214

PAL-1004

Pressure Alarm Low

Soft

DCS

DCS

2429.1-10-PR-PID004

215

PT-1005

SO2+SO3

Gas

Pressure Transmitter

AI

Field

DCS

2429.1-10-PR-PID005

212
P-1004

323010866.xls
P-1005

PT-214

0
07/05/2016
09:12:24

7.5

10

60

65

70

100
7 of 30

10

Kg/cm2 (g)

25-LS-10017-A2A-IH-40

On R-101

On R-101

80-P-10057-A2A

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

TAG NO.

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

Norm.

Max.

Min.

Norm.

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

FLOW
(m3/hr)

DESIGN TEMP.
(OC)
Max.

LEVEL
(mm)

CALIBRATION RANGE

ALARM SET POINTS


UNITS

Min.

Norm.

Max.

Min.

Norm.

Max.

Min.

Max.

LL

HH

P&ID NO.

P&ID REV.
NO.

PI-1005

Pressure indication

Soft

DCS

DCS

2429.1-10-PR-PID005

217

PAH-1005

Pressure Alarm High

Soft

DCS

DCS

2429.1-10-PR-PID005

218

PAL-1005

Pressure Alarm Low

Soft

DCS

DCS

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

E
E

216
P-1005

219

PT-1006

220

PT-215

PI-1006

SO2+SO3
-

Gas
-

Pressure Transmitter
Pressure indication

AI
Soft

Field
DCS

DCS

7.5

10

50

65

70

100

10

Kg/cm (g)
2

DCS

P-1006
221

PAH-1006

222

PAL-1006

Pressure Alarm High


Pressure Alarm Low

Soft
Soft

DCS
DCS

DCS
DCS

7
-

DCS

2429.1-10-PR-PID005

DCS

DCS

6.5

2429.1-10-PR-PID005

DCS

DCS

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

E
E

H2SO4+SO2 Gas

Mixed

Pressure Transmitter

AI

Field

DCS

PI-1007

Pressure indication

Soft

DCS

225

PAH-1007

Pressure Alarm High

Soft

226

PAL-1007

Pressure Alarm Low

Soft

224

2429.1-10-PR-PID005

PT-1007

223

5.6

10

50

62

75

100

10

Kg/cm2 (g)

P-1007

227

H2SO4+SO2 Gas

PT-1008

228

PI-1008

Mixed
-

Pressure Transmitter
Pressure indication

AI
Soft

Field
DCS

DCS

5.6

10

50

62

75

100

10

Kg/cm (g)
2

DCS

P-1008
229

PAH-1008

230

PAL-1008

Pressure Alarm High


Pressure Alarm Low

Soft
Soft

DCS
DCS

DCS
DCS

6.5
-

DCS

2429.1-10-PR-PID005

DCS

DCS

6.5

2429.1-10-PR-PID005

Soft

DCS

DCS

2429.1-10-PR-PID005

AI

Field

DCS

2429.1-10-PR-PID006

2429.1-10-PR-PID006

2429.1-10-PR-PID006

2429.1-10-PR-PID006

E
E

H2SO4+SO2 Gas

Mixed

Pressure Transmitter

AI

Field

DCS

PI-1009

Pressure indication

Soft

DCS

233

PAH-1009

Pressure Alarm High

Soft

234

PAL-1009

Pressure Alarm Low

PT-1010

SO2 Gas+Acid
Mist+SO3 Mist

Mixed

Pressure Transmitter

232

2429.1-10-PR-PID005

PT-1009

231

5.6

10

50

62

75

100

10

Kg/cm2 (g)

P-1009

235
236

PI-1010

Pressure indication

Soft

DCS

5.1

10

45

51

70

100

10

Kg/cm (g)
2

DCS

P-1010
237

PAH-1010

238

PAL-1010

Pressure Alarm High


Pressure Alarm Low

Soft
Soft

DCS
DCS

DCS
DCS

DCS

2429.1-10-PR-PID007

DCS

DCS

6.6

2429.1-10-PR-PID007

Field

DCS

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

E
E

AI

Field

DCS

PI-1011

Pressure indication

Soft

DCS

241

PAH-1011

Pressure Alarm High

Soft

242

PT-1012

SO2

Vapor

Pressure Transmitter

AI

240

243

P-1011

P-1012

PI-1012

244

PAH-1012

245

PT-1013

246

P-1013

PT-217

PT-218

PI-1013

247

PAH-1013

248

PT-1014

Pressure indication

Soft

DCS

Pressure Alarm High

Soft

DCS

DCS

SO2

Mixed

Pressure Transmitter

AI

Field

DCS

Pressure indication

Soft

DCS

10

Kg/cm (g)

2429.1-10-PR-PID007

Field

DCS

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

E
E

Soft

251

PT-1015

SO2

Vapor

Pressure Transmitter

AI

AI

Pressure Alarm High

Pressure Transmitter

100

Vapor

55

DCS

SO2

45

DCS

PAH-1014

PT-221

40

250

PT-1016

10

2429.1-10-PR-PID007

DCS

254

Soft

Soft

6.6

Pressure indication

Pressure Alarm High

DCS

PI-1014

PAH-1015

Kg/cm2 (g)

DCS

253

10

2429.1-10-PR-PID007

Field

Soft

Kg/cm2 (g)

AI

Pressure indication

100

10

Pressure Transmitter

50

Mixed

100

SO2

PI-1015

35

50

DCS

P-1015

30

35

DCS

252

10

30

Soft

PT-220

10

Pressure Alarm High

P-1014

2429.1-10-PR-PID007

249

DCS

PT-219

DCS

Pressure Transmitter

PT-216

Vapor

PT-1011

2429.1-10-PR-PID007

SO2

239

DCS
DCS
Field

10

10

40

30

45

35

55

100

50

100

10

10

Kg/cm2 (g)

Kg/cm (g)
2

DCS

DCS
DCS

10

30

35

50

100

10

Kg/cm2 (g)

6.6
-

PI-1016

Pressure indication

Soft

DCS

DCS

2429.1-10-PR-PID008

256

PAH-1016

Pressure Alarm High

Soft

DCS

DCS

6.6

2429.1-10-PR-PID008

257

PT-1017

SO2

Liquid

Pressure Transmitter

AI

Field

DCS

2429.1-10-PR-PID008

Pressure indication

Soft

DCS

DCS

2429.1-10-PR-PID008

255

258

P-1016

P-1017

323010866.xls

PI-1017

PT-222

07/05/2016
09:12:24

4.5

10

35

40

55

100

8 of 30

10

Kg/cm2 (g)

LINE NO. / EQUIPMENT NO.

80-P-10058-A2A

On T-102

On T-103

On T-104

80-P-10070-A2A

On EX-102A

On EX-102B

On V-102A

On V-102A

On EX-103A

On EX-103B

On V-103A

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

TAG NO.

P-1017

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

PAH-1017

260

PT-1018
P-1018

PT-223

PI-1018

Pressure Alarm High

Soft

DCS

DCS

SO2

Liquid

Pressure Transmitter

AI

Field

DCS

Pressure indication

Soft

DCS

DCS

262

PAH-1018

Pressure Alarm High

Soft

DCS

DCS

263

PDT-1001

SO2 + SO3

Gas

Pressure Differential Transmitter

AI

Field

DCS

264

PDI-1001

Pressure Differential Indication

Soft

DCS

Norm.

Max.

4.5

Min.

10

35

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO
Min.

259

261

OLD TAG NO.

FLOW
(m3/hr)

DESIGN TEMP.
(OC)

Norm.

Max.

40

100

CALIBRATION RANGE

ALARM SET POINTS

Norm.

Max.

Min.

Norm.

Max.

Min.

Max.

10

60

65

70

100

P&ID REV.
NO.

2429.1-10-PR-PID008

10

Kg/cm2 (g)

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

E
E

LL

HH

P&ID NO.

UNITS
Min.

55

LEVEL
(mm)

0.8

Kg/cm (g)
2

DCS

PD-1001
265

PDAH-1001

266
267

268

Pressure Differential Alarm High

Soft

DCS

DCS

0.5

0.1

2429.1-10-PR-PID005

2429.1-10-PR-PID005

DCS

2429.1-10-PR-PID005

DCS

0.5

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

E
E

PDAL-1001

Pressure Differential Alarm Low

Soft

DCS

DCS

PDT-1002

SO2 + SO3

Gas

Pressure Differential Transmitter

AI

Field

DCS

PDI-1002

Pressure Differential Indication

Soft

DCS

PDAH-1002

Pressure Differential Alarm High

Soft

DCS

5.8

10

60

62

70

100

0.8

Kg/cm2 (g)

PD-1002
269
270

PDAL-1002

271

TE-1001

272

TT-1001

Cooling Water
TT-201

Liquid
-

Pressure Differential Alarm Low


Temperature Element
Temperature Transmitter

Soft
AI

DCS
Field
Field

DCS
Field
DCS

0.1
0
0

7
7

25

25

32

36

32

60

36

60

80

T-1001
273

TI-1001

Temperature Indication

Soft

DCS

DCS

274

TAH-1001

Temperature Alarm High

Soft

DCS

DCS

275

TE-1002

SO3

Vapor

Temperature Element

Field

Field

0.5

Temperature Transmitter

AI

Field

DCS

0.5

Temperature Indication

Soft

DCS

DCS

276

T-1002

TT-1002

277

TI-1002

278
279

SO3

TE-1003
T-1003

TT-1003

280

TT-204

TI-1003

281
282

TT-203

TE-1004
T-1004

TT-1004

Cooling Water
TT-202

Liquid
Liquid

Temperature Element
Temperature Transmitter
Temperature Indication
Temperature Element

AI
Soft
-

Field
Field
DCS
Field

Field
DCS

0
0

0
0

0.8

0.8

0.1
0.1

Field

Temperature Transmitter

AI

Field

DCS

0
0

3
3

4
4

Soft

DCS

DCS

284

TE-1005

SO3

Mixed

Temperature Element

Field

Field

0.1

3.5

285

TT-1005

Temperature Transmitter

AI

Field

DCS

0.1

3.5

287

TAH-1005

288

TAL-1005

289

SO3

TE-1006

290

Mixed

Temperature Alarm High


Temperature Alarm Low
Temperature Element

Soft
Soft
Soft
-

DCS
DCS
DCS
Field

Field

TAH-1007

Temperature Alarm High

Soft

0.1

2429.1-10-PR-PID001

80

2429.1-10-PR-PID001

2429.1-10-PR-PID001

E
E

36
36

43

60

43

60

20

35

40

100

20

35

40

100

80

80

20

40

50

100

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

2429.1-10-PR-PID001

E
E

25
-

50
-

DCS

DCS

25

2429.1-10-PR-PID001

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID002

E
E

Field
Field
DCS
DCS

Field
DCS

0.1

3.5

20

40

50

100

80

0
0
0

0
0

0.1
0.1

3.5
3.5

20

20

40
40

50

100

50

100

80

DCS

DCS

Temperature Alarm Low

Soft

DCS

DCS

299

TE-1008

SO3

Liquid

Temperature Element

Field

Field

0.1

3.5

300

TT-1008

Temperature Transmitter

AI

Field

DCS

0.1

3.5

Temperature Indication

Soft

DCS

DCS

323010866.xls

32

3.5

TI-1008

T-1008

2429.1-10-PR-PID001

TAL-1007

301

2429.1-10-PR-PID001

298

TT-208

Soft

297

2429.1-10-PR-PID001

Temperature Alarm Low

Soft

Temperature Indication

50

TAL-1006

2429.1-10-PR-PID001

293

TI-1007

DCS

Soft

DCS

Temperature Alarm High

T-1007

296

2429.1-10-PR-PID001

AI

TAH-1006

Temperature Transmitter

2429.1-10-PR-PID001

292

DCS

100

Soft

TT-207

45

DCS

Temperature Indication

TT-1007

100

295

150

38

TI-1006

Temperature Element

DCS

Liquid

45

125

2429.1-10-PR-PID001

Field

SO3

DCS

AI

TE-1007

44

110

DCS

Temperature Transmitter

294

44

DCS

T-1006

TT-206

Temperature Indication

291

TT-1006

32

Temperature Indication

35

TI-1005

90

125

2429.1-10-PR-PID001

T-1005

44

110

DCS

TI-1004

286

90

35

283

TT-205

44

07/05/2016
09:12:24

20

40

50

100

20

40

50

100

9 of 30

80

50

25

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID002

LINE NO. / EQUIPMENT NO.

On V-103B

On PLT-101A

On PLT-101B

80-CWS-10001-A4A

100-P-10001-A2A-ET-IH-40

50-P-10002-A2A-ET-IH-40

100-CWR-10001-A4A

On V-101A

On V-101B

On T-101A

On T-101B

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

TAG NO.

T-1008

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

TAH-1008

Temperature Alarm High

Soft

DCS

DCS

303

TAL-1008

Temperature Alarm Low

Soft

DCS

DCS

304

TE-1009

Sulfur

Liquid

Temperature Element

Field

Field

305

TT-1009

306

TT-209

TIC-1009

307

TI-1009

308

TAL-1009

Temperature Transmitter
Temperature Indicator Controller
Temperature Indication
Temperature Alarm Low

AI
Soft
Soft
Soft

Field
DCS
DCS
DCS

Norm.

Max.

Min.

Norm.

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO
Min.

302

OLD TAG NO.

FLOW
(m3/hr)

DESIGN TEMP.
(OC)
Max.

LEVEL
(mm)

CALIBRATION RANGE

ALARM SET POINTS

Min.

Norm.

Max.

Min.

Norm.

Max.

Min.

Max.

DCS

0
0

0.2
0.2

3.5
3.5

120

120

125
125

150
150

P&ID NO.

P&ID REV.
NO.

2429.1-10-PR-PID002

2429.1-10-PR-PID002

2429.1-10-PR-PID003

2429.1-10-PR-PID003

2429.1-10-PR-PID003

2429.1-10-PR-PID003

2429.1-10-PR-PID003

E
E

UNITS

200
200

200

DCS

LL

HH

50

25

DCS

DCS

122

T-1009

LINE NO. / EQUIPMENT NO.

On DT-102

309

TAH-1009

Temperature Alarm High

Soft

DCS

DCS

135

2429.1-10-PR-PID003

310

TDA-1009

Temperature Deviation Alarm

Soft

DCS

DCS

2429.1-10-PR-PID003

AO

DCS

Field

2429.1-10-PR-PID003

AI

Field

DCS

2429.1-10-PR-PID003

Field

Field

2429.1-10-PR-PID003

25-LS-10016-A2A-IH-40

2429.1-10-PR-PID003

On DT-102

2429.1-10-PR-PID003

2429.1-10-PR-PID003

E
E

311
TY-1009
312

313

TV-1009

314

TE-1010

315
316

Smart Positioner
-

LP Steam

Vapor

Sulfur

TT-1010
T-1010

TI-1010

Liquid
-

Temperature Control Valve


Temperature Element
Temperature Transmitter
Temperature Indication

AI
Soft

Field
Field
DCS

Field

DCS

3.5
0
0

4
0.2
0.2

143

3.5
3.5

120

120

147.9
125
125

152
150
150

165

11.175

18.02

22.35

m /hr
3

200

200

200

DCS

317

TAL-1010

Temperature Alarm Low

Soft

DCS

DCS

122

2429.1-10-PR-PID003

318

TAH-1010

Temperature Alarm High

Soft

DCS

DCS

135

2429.1-10-PR-PID003

319

TE-1011

Hot water

Liquid

Temperature Element

Field

Field

0.1

3.5

70

70

90

150

2429.1-10-PR-PID004

320

TT-1011

Temperature Transmitter

AI

Field

DCS

0.1

3.5

70

70

90

150

2429.1-10-PR-PID004

DCS

2429.1-10-PR-PID004

DCS

2429.1-10-PR-PID004

Field

2429.1-10-PR-PID004

Field

2429.1-10-PR-PID004

2429.1-10-PR-PID004

25-LS-10018-A2A-IH-40
100-CWS-10003-A4A-IH-40

321
322

T-1011

TT-210

TIC-1011

TI-1011

323

Temperature Indicator Controller


Temperature Indication

TY-1011

Soft
Soft
AO

DCS
DCS
DCS

AI

DCS

325

TV-1011

LP Steam

Vapor

Temperature Control Valve

Field

Field

326

TE-1012

CW/HW

Liquid

Temperature Element

Field

TT-1012

Temperature Transmitter

AI

TI-1012

Temperature Indication

Soft

T-1012

328
329

TE-1013

330
331

Cooling Water

TT-1013
T-1013

332

TI-1013

TAH-1013

Liquid
-

Temperature Element
Temperature Transmitter
Temperature Indication
Temperature Alarm High

AI
Soft
Soft

3.5

Field

Field

DCS

DCS

DCS

Field
Field
DCS
DCS

Field
DCS

0
0

3
3

4
4

119.62

147.9

152

165

32

70

90

150

32

70

90

150

7
7

32
32

36
36

45
45

60

E
E

150

150

2429.1-10-PR-PID004

E
E

3.9

4.62

65

70

90

150

TI-1014

Temperature Indication

Soft

DCS

DCS

120

DCS

DCS

68

5.5

6
6

7
7

10.5
10.5

60
60

65
65

70
70

42

2429.1-10-PR-PID004

2.8

5.5

DCS

2429.1-10-PR-PID004

DCS

Field

2429.1-10-PR-PID004

Field

AI

2429.1-10-PR-PID004

AI

Temperature Transmitter

Temperature Transmitter

2429.1-10-PR-PID004

80

2429.1-10-PR-PID004

TT-211

TT-1014

TT-1015

2429.1-10-PR-PID004

335

340

150

Field

2429.1-10-PR-PID004

90

Field

2429.1-10-PR-PID004

70

2429.1-10-PR-PID004

65

Temperature Element

4.62

Gas

3.9

SO2+SO3

2.8

TE-1015

339

2429.1-10-PR-PID004

Field

DCS

2429.1-10-PR-PID004

Field

Soft

Temperature Alarm Low

Temperature Element

Liquid

Hot water

TAL-1014

2429.1-10-PR-PID004

TE-1014

338

334

DCS

DCS

Soft

120

34

DCS

Temperature Alarm High

2429.1-10-PR-PID004

Soft

m3/hr

Temperature Alarm Low

14.9

DCS

TAH-1014

12.41

337

7.45

DCS

TAL-1013

T-1014

60

333

336

120

Smart Positioner

324

327

100

85
-

341

TIC-1015

Temperature Indicator Controller

Soft

DCS

DCS

2429.1-10-PR-PID004

342

TI-1015

Temperature Indication

Soft

DCS

DCS

2429.1-10-PR-PID004

TAH-1015

Temperature Alarm High

Soft

DCS

DCS

68

2429.1-10-PR-PID004

TAL-1015

Temperature Alarm Low

Soft

DCS

DCS

62

2429.1-10-PR-PID004

343

T-1015

344
323010866.xls

07/05/2016
09:12:24

10 of 30

On T-105

80-CWR-10002-A2A

100-HWR-10001-A4A-IH-40

On R-101

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

T-1015
SR. NO.

PRESSURE
(kg/cm2g)

LOOP NO.

TAG NO.

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

345

TY-1015
346

TV-1015

348

350

TT-1016
T-1016

351

Cooling Water

Liquid

SO2+SO3

TE-1016

349

Max.

Min.

Norm.

TT-216

TI-1016

TAH-1016

Max.

Norm.

Max.

Min.

Norm.

Max.

Min.

Max.

LL

Gas
-

Temperature Control Valve


Temperature Element
Temperature Transmitter
Temperature Indication
Temperature Alarm High

Field

DCS

2429.1-10-PR-PID004

Field

Field

2429.1-10-PR-PID004

80-CWR-10002-A2A

2429.1-10-PR-PID005

On PLT-101A

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

E
E

AI
Soft
Soft

Field
Field
DCS
DCS

Field
DCS

0
0
0

3
5.8
5.8

4
7
7

7
10
10

32
57
57

36
62
62

43
70
70

60

100

Field

Field

5.8

10

57

62

70

100

354

TT-1017

Temperature Transmitter

AI

Field

DCS

5.8

10

57

62

70

100

Temperature Indication

Soft

DCS

DCS

TAL-1017

H2SO4+SO2 Gas

TE-1018
TT-1018

Mixed
-

Temperature Alarm Low


Temperature Element
Temperature Transmitter

Soft
AI

DCS
DCS
Field
Field

100

100

DCS

DCS

5.6
5.6

7
7

10
10

57
57

62
62

70
70

100
100

100

68

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

E
E

60

60
0

2429.1-10-PR-PID005

DCS
Field

Temperature Element

Soft

m3/hr

DCS

Gas

Temperature Alarm High

18

SO2+SO3

15

DCS

TE-1017

10

100

353

TAH-1017

68
-

TI-1018

Temperature Indication

Soft

DCS

DCS

2429.1-10-PR-PID005

361

TAH-1018

Temperature Alarm High

Soft

DCS

DCS

70

2429.1-10-PR-PID005

362

TAL-1018

Temperature Alarm Low

Soft

DCS

DCS

60

2429.1-10-PR-PID005

363

TE-1019

H2SO4+SO2 Gas

Mixed

Temperature Element

Field

Field

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID005

E
E

360

T-1018

364
365

TT-1019
T-1019

366

TI-1019

TAH-1019

367

TAL-1019

Temperature Transmitter
Temperature Indication
Temperature Alarm High
Temperature Alarm Low

AI
Soft
Soft
Soft

Field
DCS
DCS
DCS

DCS

0
0

5.6
5.6

7
7

10
10

57
57

62
62

75
75

100
100

DCS

60

2429.1-10-PR-PID005

DCS

2429.1-10-PR-PID005

DCS

70

2429.1-10-PR-PID005

2429.1-10-PR-PID005

2429.1-10-PR-PID006

2429.1-10-PR-PID006

2429.1-10-PR-PID006

E
E

5.6

10

57

62

75

100

369

TT-1020

Temperature Transmitter

AI

Field

DCS

5.6

10

57

62

75

100

TI-1020

Temperature Indication

Soft

DCS

TAH-1020

Temperature Alarm High

Soft

DCS

373
374
375

SO2 Gas

TE-1021
TT-1021
T-1021

TT-218

TI-1021

Gas
-

Temperature Element
Temperature Transmitter
Temperature Indication

AI
Soft

DCS
Field
Field
DCS

Soft

70

Field

Temperature Alarm Low

Field

2429.1-10-PR-PID005

Temperature Element

TAL-1020

Mixed

372

DCS

H2SO4+SO2 Gas

371

100

TE-1020

T-1020

DCS

368

370

100

DCS
Field
DCS

60
0
0

5.1
5.1

7
7

10
10

45
45

51
51

70
70

100
100

100

DCS

376

TAH-1021

Temperature Alarm High

Soft

DCS

DCS

60

2429.1-10-PR-PID006

377

TAL-1021

Temperature Alarm Low

Soft

DCS

DCS

48

2429.1-10-PR-PID006

378

TE-1022

Spent Acid

Liquid

Temperature Element

Field

Field

0.2

3.5

35

40

60

100

2429.1-10-PR-PID006

379

TT-1022

Temperature Transmitter

AI

Field

DCS

0.2

3.5

35

40

60

100

2429.1-10-PR-PID006

2429.1-10-PR-PID006

2429.1-10-PR-PID006

2429.1-10-PR-PID006

2429.1-10-PR-PID007

E
E

380

T-1022

381

TT-215

TI-1022

TAH-1022

382

TAL-1022

383

TE-1023

384

Liquid

Temperature Alarm High


Temperature Alarm Low
Temperature Element

Soft
Soft
Soft
-

DCS
DCS
DCS
Field

80

DCS

DCS
Field

38
0

32

36

43

60

50
-

2429.1-10-PR-PID007

DCS

2429.1-10-PR-PID007

DCS

DCS

40

2429.1-10-PR-PID007

DCS

DCS

34

2429.1-10-PR-PID007

Temperature Transmitter

AI

Field

DCS

TI-1023

Temperature Indication

Soft

DCS

386

TAH-1023

Temperature Alarm High

Soft

387

TAL-1023

Temperature Alarm Low

Soft

323010866.xls

DCS

T-1023

TT-220

Temperature Indication

385

TT-1023

Cooling Water

LINE NO. / EQUIPMENT NO.

AI

DCS

TI-1017

P&ID REV.
NO.

DCS

TT-217

P&ID NO.
HH

2429.1-10-PR-PID004

Soft

359

ALARM SET POINTS

Field

Temperature Alarm Low

358

CALIBRATION RANGE

DCS

357

LEVEL
(mm)

AO

356

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

UNITS
Min.

TAL-1016

T-1017

FLOW
(m3/hr)

DESIGN TEMP.
(OC)

352

355

6/6/2013

Smart Positioner

347

Norm.

Date
2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

07/05/2016
09:12:24

32

36

43

11 of 30

60

80

On PLT-101B

On T-102

On T-103

On T-104

80-P-10070-A2A

On T-106

50-CWR-10003-A4A

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

TAG NO.

388

TE-1024

389

TT-1024

390

T-1024

391

OLD TAG NO.

TT-222

TI-1024
TAH-1024

392

TT-1025

I / O TYPE

FROM

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO
Min.

Norm.

Max.

Min.

Norm.

Max.

Field

Field

32

36

43

60

Temperature Transmitter

AI

Field

DCS

32

36

43

60

Temperature Indication

Soft

DCS

DCS

Liquid

Temperature Alarm High


Temperature Alarm Low
Temperature Element
Temperature Transmitter

Soft
Soft
AI

DCS
DCS
Field
Field

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

LEVEL
(mm)

CALIBRATION RANGE

ALARM SET POINTS

Norm.

Max.

Min.

Norm.

Max.

Min.

Max.

80

DCS
DCS

DCS

3
3

25

25

32
32

36
36

LINE NO. / EQUIPMENT NO.

2429.1-10-PR-PID007

50-CWR-10004-A4A

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

34

2429.1-10-PR-PID007

LL

HH

34
0

P&ID REV.
NO.

Field

P&ID NO.

UNITS
Min.

Temperature Element

6/6/2013

FLOW
(m3/hr)

DESIGN TEMP.
(OC)

Liquid

Cooling Water
TT-219

INSTRUMENT TYPE/DESCRIPTION

Date
2429.1-10-IC-INX-001-C

Cooling Water

TE-1025

394

SERVICE PHASE

TAL-1024

393

SERVICE NAME

60

60

80

40

T-1025
395

TI-1025

Temperature Indication

Soft

DCS

DCS

396

TAH-1025

Temperature Alarm High

Soft

DCS

DCS

397

TE-1026

Cooling Water

Liquid

Temperature Element

Field

Field

2429.1-10-PR-PID007

Temperature Transmitter

AI

Field

DCS

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

150

2429.1-10-PR-PID007

150

2429.1-10-PR-PID007

E
E

398

TT-1026

TT-221

25

32

36

60

25

32

36

60

80

T-1026
399

TI-1026

400

TAH-1026

401

TE-1027

402

TT-1027

Hot water
TT-231

Liquid

Temperature Indication
Temperature Alarm High
Temperature Element
Temperature Transmitter

Soft
Soft
AI

DCS
DCS
Field
Field

DCS

DCS

Field

DCS

0
0

1.5

3.5

1.5

40

3.5

40

55
55

70
70

100

34

80-CWS-10005-A4A

80-CWS-10006-A4A

On T-108

403

TIC-1027

Temperature Indicator Controller

Soft

DCS

DCS

2429.1-10-PR-PID007

404

TI-1027

Temperature Indication

Soft

DCS

DCS

2429.1-10-PR-PID007

TAH-1027

Temperature Alarm High

Soft

DCS

DCS

60

2429.1-10-PR-PID007

TAL-1027

Temperature Alarm Low

Soft

DCS

DCS

45

2429.1-10-PR-PID007

Field

2429.1-10-PR-PID007

DCS

2429.1-10-PR-PID007

2429.1-10-PR-PID007

25-LS-10019-A2A-IH-40

2429.1-10-PR-PID007

On V-102A

405

T-1027

406
407

TY-1027
408

409

TV-1027

410

DCS

SO2

Mixed

Temperature Control Valve


Temperature Element

Field
Field
Field

Field
Field

2429.1-10-PR-PID007

DCS

DCS

43

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

E
E

414

TAL-1028

Temperature Alarm Low

Soft

418

TI-1029

TAH-1029

Temperature Indication
Temperature Alarm High

Soft
Soft

Field
Field
DCS
DCS

Field
DCS

3
3

5
5

7
7

10

10

10

40

40
40

45

45
45

55

55
55

100

100

Soft

DCS

DCS

420

TE-1030

Cooling Water

Liquid

Temperature Element

Field

Field

32

36

43

60

Temperature Transmitter

AI

Field

DCS

32

36

43

60

Temperature Indication

Soft

DCS

DCS

TI-1030

423
424

TE-1031
T-1031

425

TT-1031

Cooling Water
TT-228

TI-1031

426

TE-1032

427

TT-1032

Cooling Water
TT-225

Liquid
Liquid

Temperature Element
Temperature Transmitter
Temperature Indication
Temperature Element

AI
Soft
-

Field
Field
DCS
Field

80

Field
DCS

0
0

3
3

4
4

7
7

32
32

36
36

43
43

80

60
60

80

Temperature Transmitter

AI

Field

DCS

3
3

4
4

7
7

5
5

32
32

36
36

60
60

80

50

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

E
E

43

2429.1-10-PR-PID007

DCS
Field

Temperature Alarm Low

422

DCS

TT-226

TT-1030

80

DCS

TAL-1029

T-1030

100

419

421

50

Soft

T-1029

Temperature Alarm High

417

AI

100

DCS

Temperature Transmitter

m /hr

DCS

TAH-1028

62.07

413

51.74

2429.1-10-PR-PID007

DCS

TT-224

55

31.04

Soft

TT-1029

45

165

Temperature Indication

416

40

152

10

147.9

Temperature Element

119.62

DCS

TI-1028

Mixed

DCS

SO2

Field

TE-1029

3.5

AI

415

Temperature Transmitter

2429.1-10-PR-PID007

T-1028

TT-223

Vapor

AI

412

TT-1028

LP Steam

TE-1028

411

AO
Smart Positioner

2429.1-10-PR-PID008

2429.1-10-PR-PID008

34

2429.1-10-PR-PID008

2429.1-10-PR-PID008

T-1032
428

TI-1032

Temperature Indication

Soft

DCS

DCS

429

TAH-1032

Temperature Alarm High

Soft

DCS

DCS

430

TE-1033

Cooling Water

Liquid

Temperature Element

Field

Field

323010866.xls
T-1033

0
07/05/2016
09:12:24

32

36
12 of 30

60

On V-102B

80-CWR-10006-A4A

80-CWR-10007-A4A

80-CWS-10007-A4A

80-CWS-10008-A4A

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

431

TAG NO.

TT-1033

OLD TAG NO.

TT-227

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Temperature Transmitter

AI

Field

DCS

Min.

Norm.

Max.

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

FLOW
(m3/hr)

DESIGN TEMP.
(OC)

Min.

Norm.

Max.

32

36

LEVEL
(mm)

CALIBRATION RANGE

ALARM SET POINTS


P&ID NO.

P&ID REV.
NO.

2429.1-10-PR-PID008

2429.1-10-PR-PID008

34

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

2429.1-10-PR-PID008

E
E

UNITS
Min.

Norm.

Max.

60

Min.

Norm.

Max.

Min.

Max.

80

LL

HH

T-1033
432

TI-1033

Temperature Indication

Soft

DCS

DCS

433

TAH-1033

Temperature Alarm High

Soft

DCS

DCS

434
435

T-1034

436

TT-1034

TT-229

TI-1034

437
438

SO2

TE-1034

SO2

TE-1035
T-1035

TT-1035

439

TI-1035

440

XV-1001

441

TT-230

LCV-203

XY-1001

Liquid
Liquid

Temperature Element
Temperature Transmitter
Temperature Indication
Temperature Element

AI
Soft
-

Field
Field
DCS
Field

Field
DCS

3
3

4.5
4.5

7
7

10
10

35
35

40
40

55
55

100

100

ZSC-1001

Field

4.5

10

35

40

55

100

443

ZSO-1001

2429.1-10-PR-PID008

2429.1-10-PR-PID001

Field

2429.1-10-PR-PID001

DCS

2429.1-10-PR-PID001

DCS

2429.1-10-PR-PID001

Field

2429.1-10-PR-PID001

Field

2429.1-10-PR-PID001

E
E

DCS

Temperature Indication

Soft

DCS

DCS

SO3

Liquid

ON/OFF Valve

Field

Field

Solenoid Valve

DO

DCS

444

XV-1002

445

LCV-204

XY-1002

SO3
-

Liquid
-

Valve Open Indication


ON/OFF Valve
Solenoid Valve

DI
DO

Field
Field
DCS

Field

Field

AI

DI

Temperature Transmitter

Valve Close Indication

2429.1-10-PR-PID008

DCS

4.5

By Gravity

10

By Gravity

35

30

40

35

55

45

100

100

0.5

0.88

X-1001
442

80

By Gravity

By Gravity

30

35

45

100

0.5

0.88

X-1002

80

446

ZSC-1002

Valve Close Indication

DI

Field

DCS

2429.1-10-PR-PID001

447

ZSO-1002

Valve Open Indication

DI

Field

DCS

2429.1-10-PR-PID001

448

XV-1003

SO3

Liquid

ON/OFF Valve

Field

Field

2429.1-10-PR-PID002

Solenoid Valve

DO

DCS

Field

2429.1-10-PR-PID002

DCS

2429.1-10-PR-PID002

DCS

2429.1-10-PR-PID002

Field

2429.1-10-PR-PID002

Field

2429.1-10-PR-PID002

E
E

449

LCV-205

XY-1003

1.5

3.5

30

35

45

100

0.01

0.22

0.3

X-1003
450

ZSC-1003

451

ZSO-1003

452

XV-1004

453

LCV-206

XY-1004

SO3
-

Liquid
-

Valve Close Indication


Valve Open Indication
ON/OFF Valve
Solenoid Valve

DI
DI
DO

Field
Field
Field
DCS

1.5

3.5

30

35

45

100

0.01

0.22

0.3

X-1004
454

ZSC-1004

Valve Close Indication

DI

Field

DCS

2429.1-10-PR-PID002

455

ZSO-1004

Valve Open Indication

DI

Field

DCS

2429.1-10-PR-PID002

456

XV-1005

SO2

Liquid

ON/OFF Valve

Field

Field

2429.1-10-PR-PID007

Solenoid Valve

DO

DCS

Field

2429.1-10-PR-PID007

DCS

2429.1-10-PR-PID007

DCS

2429.1-10-PR-PID007

Field

2429.1-10-PR-PID007

Field

2429.1-10-PR-PID007

E
E

457

UV-01

XY-1005

4.3

10

30

36

45

100

0.1

0.17

0.2

X-1005
458

ZSC-1005

459

ZSO-1005

460

SO2

XV-1006

461

XY-1006

Liquid
-

Valve Close Indication


Valve Open Indication
ON/OFF Valve
Solenoid Valve

DI
DI
DO

Field
Field
Field
DCS

4.3

10

30

36

45

100

0.1

0.17

0.2

X-1006
462

ZSC-1006

Valve Close Indication

DI

Field

DCS

2429.1-10-PR-PID007

463

ZSO-1006

Valve Open Indication

DI

Field

DCS

2429.1-10-PR-PID007

464

XV-1007

SO2

Gas

ON/OFF Valve

Field

Field

2429.1-10-PR-PID007

Solenoid Valve

DO

DCS

Field

2429.1-10-PR-PID007

DCS

2429.1-10-PR-PID007

DCS

2429.1-10-PR-PID007

Field

2429.1-10-PR-PID007

Field

2429.1-10-PR-PID007

E
E

465

UV-02

XY-1007

10

30

36

45

100

135

222.03

265

X-1007
466

ZSC-1007

467

ZSO-1007

468

XV-1008

469

UV-04

XY-1008

SO2
-

Gas
-

Valve Close Indication


Valve Open Indication
ON/OFF Valve
Solenoid Valve

DI
DI
DO

Field
Field
Field
DCS

10

30

36

45

100

135

222.03

265

X-1008
470

ZSC-1008

Valve Close Indication

DI

Field

DCS

2429.1-10-PR-PID007

471

ZSO-1008

Valve Open Indication

DI

Field

DCS

2429.1-10-PR-PID007

472

XV-1009

SO2

Liquid

ON/OFF Valve

Field

Field

2429.1-10-PR-PID008

Solenoid Valve

DO

DCS

Field

2429.1-10-PR-PID008

473

XY-1009

UV-05

4.5

10

30

36

45

X-1009
323010866.xls

07/05/2016
09:12:24

13 of 30

100

0.1

0.18

0.2

LINE NO. / EQUIPMENT NO.

On V-103A

On V-103B

40-P-10010-A2A-ET-IH-40

40-P-10011-A2A-ET-IH-40

40-P-10020-A2A-ET-IH-40

40-P-10021-A2A-ET-IH-40

40-P-10086-A2A

40-P-10084-A2A

80-P-10087-A2A

80-P10088-A2A

40-P-10103-A2A

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

TAG NO.

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

Norm.

Max.

Min.

Norm.

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

FLOW
(m3/hr)

DESIGN TEMP.
(OC)
Max.

LEVEL
(mm)

CALIBRATION RANGE

ALARM SET POINTS


UNITS

Min.

Norm.

Max.

X-1009

Min.

Norm.

Max.

Min.

Max.

LL

P&ID NO.

P&ID REV.
NO.

474

ZSC-1009

Valve Close Indication

DI

Field

DCS

2429.1-10-PR-PID008

475

ZSO-1009

Valve Open Indication

DI

Field

DCS

2429.1-10-PR-PID008

476

XV-1010

SO2

Liquid

ON/OFF Valve

Field

Field

2429.1-10-PR-PID008

Field

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID008

Field

2429.1-10-PR-PID008

E
E

477

XY-1010

Solenoid Valve

DO

DCS

4.5

10

30

36

45

100

0.1

0.18

0.2

X-1010
478

ZSC-1010

479

ZSO-1010

480

XV-1011

UV-06

SO2

Liquid

Valve Close Indication


Valve Open Indication
ON/OFF Valve

DI
DI
-

Field
Field
Field

4.5

10

35

40

55

100

4.2

8.4

XY-1011

Solenoid Valve

DO

DCS

Field

2429.1-10-PR-PID008

482

ZSC-1011

Valve Close Indication

DI

Field

DCS

2429.1-10-PR-PID008

483

ZSO-1011

Valve Open Indication

DI

Field

DCS

2429.1-10-PR-PID008

484

XV-1012

SO2

Liquid

ON/OFF Valve

Field

Field

2429.1-10-PR-PID008

Field

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID008

Field

2429.1-10-PR-PID008

E
E

481
X-1011

485

XY-1012

UV-08

Solenoid Valve

DO

DCS

4.5

10

35

40

55

100

4.2

8.4

X-1012
486

ZSC-1012

487

ZSO-1012

488

XV-1013

SO2

Liquid

Valve Close Indication


Valve Open Indication
ON/OFF Valve

DI
DI
-

Field
Field
Field

9.25

9.5

10.13

35

40

55

70

4.2

8.4

XY-1013

Solenoid Valve

DO

DCS

Field

2429.1-10-PR-PID008

490

ZSC-1013

Valve Close Indication

DI

Field

DCS

2429.1-10-PR-PID008

491

ZSO-1013

Valve Open Indication

DI

Field

DCS

2429.1-10-PR-PID008

492

XV-1014

SO2

Liquid

ON/OFF Valve

Field

Field

2429.1-10-PR-PID008

Field

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID008

Field

2429.1-10-PR-PID008

E
E

489
X-1013

493

XY-1014

Solenoid Valve

DO

DCS

9.25

9.5

10.13

35

40

55

70

4.2

8.4

X-1014
494

ZSC-1014

495
496

ZSO-1014
XV-1015

Hot Water

Liquid

Valve Close Indication


Valve Open Indication
ON/OFF Valve

DI
DI
-

Field
Field
Field

4.5

10

40

70

80

100

30

50

60

LINE NO. / EQUIPMENT NO.

HH

40-P-10101-A2A

50-P-10107-A2A

50-P-10108-A2A

50-P-10129-A2A

50-P-10111-A2A

80-HWS-10015-A4A-IH-40

XY-1015

Solenoid Valve

DO

DCS

Field

2429.1-10-PR-PID008

498

ZSC-1015

Valve Close Indication

DI

Field

DCS

2429.1-10-PR-PID008

499

ZSO-1015

Valve Open Indication

DI

Field

DCS

2429.1-10-PR-PID008

XV-1016

Hot Water

Liquid

ON/OFF Valve

Field

Field

2429.1-10-PR-PID008

Field

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID008

DCS

2429.1-10-PR-PID001

DCS

DCS

497
X-1015

500

501

XY-1016

Solenoid Valve

DO

DCS

4.5

10

40

70

80

X-1016
502

ZSC-1016

503
504

ZSO-1016
-

HS-1001

Valve Close Indication


Valve Open Indication
Hand Switch

DI
DI
Soft

Field
Field
DCS

100

30

50

60

80-HWS-10016-A4A-IH-40

505

HS-1002

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID001

506

HS-1003

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID002

DCS

507

HS-1004

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID002

DCS

508

HS-1005

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID007

DCS

DCS

2429.1-10-PR-PID007

DCS

DCS

2429.1-10-PR-PID007

DCS

DCS

2429.1-10-PR-PID007

DCS

DCS

2429.1-10-PR-PID008

DCS

DCS

509
510
511
512

HS-1006
HS-1007
HS-1008
HS-1009

Hand Switch
Hand Switch
Hand Switch
Hand Switch

Soft
Soft
Soft
Soft

DCS
DCS
DCS
DCS

513

HS-1010

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID008

514

HS-1011

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID008

DCS

515

HS-1012

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID008

DCS

516

- 0

HS-1013

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID008

DCS

323010866.xls

07/05/2016
09:12:24

14 of 30

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

TAG NO.

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

Norm.

Max.

Min.

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

FLOW
(m3/hr)

DESIGN TEMP.
(OC)

Norm.

Max.

LEVEL
(mm)

CALIBRATION RANGE

ALARM SET POINTS


UNITS

Min.

Norm.

Max.

Min.

Norm.

Max.

Min.

Max.

LL

P&ID NO.

P&ID REV.
NO.

LINE NO. / EQUIPMENT NO.

HH

517

- 0

HS-1015

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID007

DCS

518

- 0

HS-1016

Hand Switch

Soft

DCS

DCS

2429.1-10-PR-PID007

DCS

519

LG-1001

Hot water

Liquid

Level Gauge

Field

Field

2429.1-10-PR-PID004

On T-105

2429.1-10-PR-PID007

2429.1-10-PR-PID001

2429.1-10-PR-PID001

100-P-10001-A2A-ET-IH-40

2429.1-10-PR-PID001

V-101A

V-101B

520

521

522

523

LG-1002
PG-1001
PG-1002
PG-1003

Hot water
PI-201
PI-202
PI-203

Cooling Water
SO3
SO3

Liquid
Liquid
Vapor
Mixed

Level Gauge
Pressure Gauge
Pressure Gauge
Pressure Gauge

Field
Field
Field
Field

Field
Field
Field
Field

0
0
0
0
0

0.1

0.2

0.1

1.5

3
0.1
0.2

0.8
0.3

3.5
3.5
7
1

PG-1004

PI-204

SO3

Mixed

Pressure Gauge

Field

Field

0.2

0.3

3.5

525

PG-1005

PI-213

SO3

Liquid

Pressure Gauge

Field

Field

8.6

11

11

526

PG-1006

SO3

Liquid

Pressure Gauge

Field

Field

8.6

11

11

527

PG-1007

Sulfur

Liquid

Pressure Gauge

Field

Field

8.7

11

11

PG-1008

529

PG-1009

530

531

Liquid

Pressure Gauge

Field

Field

8.7

11

11

Hot water

Liquid

Pressure Gauge

Field

Field

2.8

3.9

Hot water

PG-1011

SO2 Gas+Acid
Mist+SO3 Mist

PG-1012

533

PG-1013

534

PG-1014

535

PG-1015

536

PG-1016

537

538

Sulfur

PG-1010

532

539

PI-205

Liquid
Mixed

Pressure Gauge
Pressure Gauge

Field
Field

Field
Field

0
0

2.8
5.1

3.9
7

70

150

25

32

36

60

44

90

0
0

25
25

40

45

40

0
0

35
35

110

0
0

125
100

250

1750
1750

2000
2000

250

2000

mm

250

2000

mm

Kg/cm (g)

0
0

1
1

Kg/cm2 (g)
Kg/cm2 (g)

43

100

16

Kg/cm2 (g)

2429.1-10-PR-PID002

40-P-10025-A2A-ET-IH-40

43

100

16

Kg/cm2 (g)

2429.1-10-PR-PID002

40-P-10026-A2A-ET-IH-40

2429.1-10-PR-PID003

25-P-10044-A2A

2429.1-10-PR-PID003

25-P-10045-A2A

2429.1-10-PR-PID004

100-HWS-10004-A4A-IH-40

2429.1-10-PR-PID004

100-HWS-10005-A4A-IH-40

2429.1-10-PR-PID006

80-P-10069-A2A

PH-101

16

Kg/cm2 (g)

120

125

150

200

16

Kg/cm (g)

70

90

100

150

Kg/cm (g)

100
70

150
100

0
0

6
10

Kg/cm2 (g)
Kg/cm2 (g)

SO2 GAS

Gas

Pressure Gauge

Field

Field

10

45

55

75

100

10

Kg/cm2 (g)

Strong Sulfuric
Acid

Liquid

Pressure Gauge

Field

Field

5.1

6.7

35

40

60

70

10

Kg/cm2 (g)

2429.1-10-PR-PID006

40-P-10077-B5A

PI-206

Spent Sulfuric
Acid

Liquid

Pressure Gauge

Field

Field

3.8

4.5

5.1

35

40

60

70

10

Kg/cm2 (g)

2429.1-10-PR-PID006

50-P-10080-A7A

PI-208

Cooling Water

Liquid

Pressure Gauge

Field

Field

25

32

36

60

Kg/cm2 (g)

2429.1-10-PR-PID007

25

32

36

60

Kg/cm (g)

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID007

2429.1-10-PR-PID008

PI-212

PI-209

0
0

PG-1017

Hot water

Liquid

Pressure Gauge

Field

Field

4.8

40

55

70

150

Kg/cm (g)

PG-1018

Hot water

Liquid

Pressure Gauge

Field

Field

4.8

40

55

70

150

Kg/cm (g)

PI-210
PI-211

Cooling Water

Liquid

Pressure Gauge

Field

Field

60

Kg/cm2 (g)

12.5

35

40

55

100

16

Kg/cm2 (g)

2429.1-10-PR-PID008

50-P-10110-A2A

10

12.5

35

40

55

100

16

Kg/cm2 (g)

2429.1-10-PR-PID008

50-P-10111-A2A

9.5

10

10.5

60

65

70

150

16

Kg/cm2 (g)

2429.1-10-PR-PID004

9.5

10

34

36

40

100

16

Kg/cm (g)

2429.1-10-PR-PID007

Field

9.5

10

34

36

40

100

16

Kg/cm (g)

2429.1-10-PR-PID007

Field

9.5

10

34

36

40

100

16

Kg/cm (g)

2429.1-10-PR-PID008

2429.1-10-PR-PID008

E
E

T-101A
T-101B

PG-1021

SO2

Liquid

Pressure Gauge

Field

Field

4.5

8.5

10

PG-1022

SO2

Liquid

Pressure Gauge

Field

Field

4.5

8.5

543

PG-1028

SO2+SO3

Gas

Pressure Gauge

Field

Field

544

PG-1029

SO2

Vapor

Pressure Gauge

Field

Field

545

PG-1030

SO2

Vapor

Pressure Gauge

Field

546

PG-1031

SO2

Vapor

Pressure Gauge

Field

Field

9.5

10

34

36

40

100

16

Kg/cm2 (g)

E
E
E

PG-1033

SO3

Vapor

Pressure Gauge

Field

Field

0.5

3.5

25

40

43

100

Kg/cm2 (g)

2429.1-10-PR-PID002

PG-1034

SO3

Vapor

Pressure Gauge

Field

Field

0.5

3.5

25

40

43

100

Kg/cm2 (g)

2429.1-10-PR-PID002

550

PSV-1001

Pressure Safety Valve

Field

Field

2429.1-10-PR-PID003

551

PSV-1002

Pressure Safety Valve

Field

Field

2429.1-10-PR-PID003

Field

2429.1-10-PR-PID004

Field

2429.1-10-PR-PID004

Field

2429.1-10-PR-PID004

Field

2429.1-10-PR-PID005

E
E

553
554
555

PSV-1003
PSV-1004
PSV-1005
PSV-1006

Pressure Safety Valve


Pressure Safety Valve
Pressure Safety Valve
Pressure Safety Valve

Field
Field
Field
Field

556

PSV-1007

Pressure Safety Valve

Field

Field

2429.1-10-PR-PID005

557

PSV-1008

Pressure Safety Valve

Field

Field

2429.1-10-PR-PID005

558

PSV-1009

Pressure Safety Valve

Field

Field

2429.1-10-PR-PID007

559

PSV-1010

Pressure Safety Valve

Field

Field

2429.1-10-PR-PID007

323010866.xls

80-CWS-10007-A4A

552

100-HWS-10014-A2A-IH-40

Kg/cm2 (g)

549

100-HWS-10013-A2A-IH-40

548

80-CWS-10006-A4A

Field

Field

36

60

Field

32

36

Pressure Gauge

25

80-CWS-10005-A4A

32

Pressure Gauge

Vapor

25

Liquid

SO2

2429.1-10-PR-PID008

Cooling Water

PG-1032

2429.1-10-PR-PID006

542

Field

80-CWS-10001-A4A

Kg/cm2 (g)

Field

541

On T-108

PG-1019

200

51

100

150

45

45

125

90

2429.1-10-PR-PID001

120

70

10

250

Pressure Gauge

PG-1020

55

35

150

40

35

100

Liquid

90

Cooling Water

540

547

3.5

524

528

70

07/05/2016
09:12:25

15 of 30

80-CWS-10008-A4A

80-P-10053-A2A

0
0
0
0

40-SV-10028-A2A
40-SV-10030-A2A
40-SV-10033-A2A
40-SV-10035-A2A

Doc. Title

INSTRUMENT INDEX - SO2 PRODUCTION PLANT

Rev.

Project No.

P002429-001

Doc No.

PRESSURE
(kg/cm2g)
SR. NO.

LOOP NO.

TAG NO.

OLD TAG NO.

SERVICE NAME

SERVICE PHASE

INSTRUMENT TYPE/DESCRIPTION

I / O TYPE

FROM

Min.

Norm.

Max.

Min.

Norm.

Date

6/6/2013

ADDAR SPECIALITY CHEMICAL PRODUCTION PLANT, JUBAIL

2429.1-10-IC-INX-001-C

TEMPERATURE
(OC)

DESIGN PRES.
(kg/cm2g)

TO

FLOW
(m3/hr)

DESIGN TEMP.
(OC)
Max.

LEVEL
(mm)

CALIBRATION RANGE

ALARM SET POINTS


UNITS

Min.

Norm.

Max.

Min.

Norm.

Max.

Min.

Max.

LL

P&ID NO.

P&ID REV.
NO.

LINE NO. / EQUIPMENT NO.

HH

560

PSV-1011

Pressure Safety Valve

Field

Field

2429.1-10-PR-PID007

561

PSV-1012

Pressure Safety Valve

Field

Field

2429.1-10-PR-PID007

562

PSV-1013

Pressure Safety Valve

Field

Field

2429.1-10-PR-PID008

Field

2429.1-10-PR-PID008

Field

2429.1-10-PR-PID004

80-P-10053-A2A

Field

2429.1-10-PR-PID007

80-P-10089-A2A

Field

2429.1-10-PR-PID007

80-P-10091-A2A

80-P-10114-A2A

563
564
565
566

PSV-1014

RD-1001

RD-1002

RD-1003

Pressure Safety Valve


SO2+SO3
SO2
SO2

Gas
Gas
Gas

Rapture Disc
Rapture Disc
Rapture Disc

Field
Field
Field
Field

567

RD-1004

SO2

Vapor

Rapture Disc

Field

Field

2429.1-10-PR-PID008

568

RD-1005

SO2

Vapor

Rapture Disc

Field

Field

2429.1-10-PR-PID008

80-P-10116-A2A

569

TW-1001

LP Steam

Vapor

Thermowell

Field

Field

3.5

143.6

147.9

151.8

170.4

2429.1-10-PR-PID003

25-LS-10016-A2A-IH-40

570

TW-1002

LP Steam

Vapor

Thermowell

Field

Field

3.5

143.6

147.9

151.8

170.4

2429.1-10-PR-PID003

25-LS-10017-A2A-IH-40

150

2429.1-10-PR-PID005

T-102

150

2429.1-10-PR-PID005

T-103

150

2429.1-10-PR-PID005

T-104

571
572
573

323010866.xls

0
0
0

TW-1003
TW-1004
TW-1005

Hot Water
Hot Water
Hot Water

Liquid
Liquid
Liquid

Thermowell
Thermowell
Thermowell

Field
Field
Field

Field
Field
Field

0
0
0

07/05/2016
09:12:25

2.8
2.8
2.8

3.9
3.9
3.9

4
4
4

65
65
65

70
70
70

90
90
90

16 of 30

ION PLANT, JUBAIL

REMARKS

pH Min. = 0
pH Normal =7
pH Max. = 14

pH Min. = 0
pH Normal = 7
pH Max. = 14

323010866.xls

07/05/2016
09:12:25

17 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

18 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

19 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

20 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

21 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

22 of 30

ION PLANT, JUBAIL

REMARKS

DP Min. = 0.1
kg/cm2(g)
DP Normal = 0.2
kg/cm2(g)
DP Max. = 0.5
kg/cm2(g)

DP Min. = 0.1
kg/cm2(g)
DP Normal = 0.2
kg/cm2(g)
DP Max. = 0.5
kg/cm2(g)

323010866.xls

07/05/2016
09:12:25

23 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

24 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

25 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

26 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

27 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

28 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

29 of 30

ION PLANT, JUBAIL

REMARKS

323010866.xls

07/05/2016
09:12:25

30 of 30