EPM 5300 Power Metering System


Chapter 1:

Modbus Register Mappings


Software Revision: 4.5
Manual P/N: 1601-9032-A1
Manual Order Code: GEK-113399
Copyright 2007 GE Multilin

GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet: http://www.GEmultilin.com

*1601-0215-A4*

GE Multilin's Quality
Management System is
registered to ISO9001:2000
QMI # 005094

TABLE OF CONTENTS

Table of Contents
METER PROFILE BLOCK ................................................................................................................. 1
METER INFORMATION BLOCK .................................................................................................... 2
PROGRAMMING DATA BLOCK .................................................................................................... 3
PHASE REVERSAL / IMBALANCE BLOCK
...................................................................... 4
DAXI DATA BLOCK ........................................................................................................................... 5
HOUR BLOCK ..................................................................................................................................... 6
LIMIT DETECTION BLOCK
..................................................................................................... 7
RELAY STATUS BLOCK ................................................................................................................... 8
THD SUMMARY BLOCK .................................................................................................................. 9
THD DETAIL BLOCK ......................................................................................................................... 10
HARM VOLT A REGISTERS ............................................................................................... 10
HARM VOLT B REGISTERS ............................................................................................... 10
HARM VOLT C REGISTERS ............................................................................................... 10
HARM AMP A REGISTERS ................................................................................................ 10
HARM AMP B REGISTERS ................................................................................................ 10
HARM AMP C REGISTERS ................................................................................................ 11
RESET BLOCK ..................................................................................................................................... 12
COMMUNICATION PARAMETERS .............................................................................................. 13
APPENDIX A: PROGRAMMING DATA BLOCK MAP ............................................................. 14
CONFIGURATION INFORMATION ........................................................................................ 15
Interval ............................................................................................................................15
Address ...........................................................................................................................15
Baud Rate ......................................................................................................................15
Configuration ...............................................................................................................15
VOLTS Full Scale .........................................................................................................16
AMPS Full Scale ...........................................................................................................16
Decimal Placement & LILCO Configuration ...................................................17
LILCO Configuration .................................................................................................17
Set Above/Below Lim 1 ...........................................................................................17
Set Above/Below LIM 2 ...........................................................................................18
VOLTS AN Lim1-FREQ Lim2 ...................................................................................18
RLY LIM 1 .......................................................................................................................18
RLY LIM 2-RLY2 LIM2 ................................................................................................18
Delay ON RLY1-2 ........................................................................................................18
SAB THD LIM 1-2 ........................................................................................................18
RLY THD LIM 1-2 .........................................................................................................19
RLY2 THD LIM 1-2 ......................................................................................................19
THD VOLTS A LIM 1 - THD AMPS C LIM2 ..........................................................19
RLY1-2 IMB LIM 1 .......................................................................................................19
IMB LIM 1 .......................................................................................................................20
Relay 1 Mode: ..............................................................................................................20
RELAY 2 MODE ............................................................................................................20
Delay off RLY1-2 .........................................................................................................20
KYZ Map, KYZ Factor ................................................................................................21
CT/PT Ratios .................................................................................................................21
System Reset ...............................................................................................................21

APPENDIX B: LILCO MAPPING .................................................................................................... 23


SYSTEM SANITY .................................................................................................................... 23
POLLING VALUES ................................................................................................................. 23
CT/PT RATIOS ..................................................................................................................... 24
NEUTRAL CURRENT ............................................................................................................. 24

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

TOCI

TABLE OF CONTENTS

HOUR READINGS ................................................................................................................. 24


FREQUENCY .......................................................................................................................... 25
ENERGY RESET ..................................................................................................................... 25
APPENDIX C: FLOATING POINT REGISTERS .......................................................................... 26
NEGATIVE MAX/MIN BLOCK .............................................................................................. 26
FLOATING POINT DAXI DATA BLOCK .............................................................................. 26
FLOATING-POINT NEGATIVE MAX/MIN BLOCK ............................................................... 27
FLOATING-POINT THD DETAIL BLOCK ............................................................................. 28
NEGATIVE HOUR BLOCK .................................................................................................... 29
APPENDIX D: MASS MEMORY & NULL TERMINATED HOUR READINGS ................... 30
MASS MEMORY COUNTER ................................................................................................. 30
EXCEPTION FLAGS .............................................................................................................. 30
INPUT STATUS: .................................................................................................................... 31
EXCEPTION BUFFER STATUS (FUTURA+ CPU1000 ONLY) ........................................... 31
EXCEPTION BUFFER (FUTURA+ CPU1000 ONLY) ......................................................... 31

TOCII

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

GE Consumer & Industrial


Multilin

EPM 5300 Series Meters


Register Mappings for
MODBUS Protocol

Register Mappings for MODBUS Protocol

Meter Profile Block


Registers
15

14

13

12

11

10

Bits
8

VOLTS
0000

AN

BN

CN

W
0001

0002

0003

A
1

AB

BC

VA
R

---

---

VA

VA

PF

FQ

---

40001

IMB

---

---

40002

VA

---

40003

POWER
N
PF

RE
V

----

----

----

----

KF AMPS
B

THD VOLTS

HOUR

THD AMPS

LIMITS
0004

CA

KF VOLTS
B

AMPS

VAR
B

584/984
7

HARM VOLTS

RELAYS

0005+

VAR

HARM AMPS
A

---

---

40004

---

---

----

---

---

40005

KYZ
1
--3 CH
CH
RESERVED FOR FUTURE USE
2

---

40006+

Relay and KYZ:


A bit value of 1 means that the firmware supports features, but specific hardware is
necessary for those features to operate. The hardware is only installed if the appropriate
options are purchased for the meter.
THESE BITS DO NOT GUARANTEE THESE FEATURES. A bit value of 0 means the features are
not supported.
Other:
A bit value of 1 means the features are supported.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

METER INFORMATION BLOCK

REGISTER MAPPINGS FOR MODBUS PROTOCOL

Meter Information Block


Registers
0

Registers
4

584/984
5

METER NAME
0008+

40009+
METER NAME

0010+
0018+

RESERVED FOR FUTURE USE

40017+

RESERVED FOR FUTURE USE

40025+
VERSION NUMBERS

0020+

RESERVED FOR FUTURE USE

MODBUS

ANALOG

DIGITAL

40033+

Registers 0008-0011:
20 Bytes ASCII, containing the meter name, left justified and padded with ASCII SPACEs
(0x20)
Registers 0025-0027:
2 Bytes each twos complement number, representing a version number with a single
implied decimal point.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

PROGRAMMING DATA BLOCK

Programming Data Block


Registers

Registers
0

584/984
5

0028+
|

40041+
|

010C+

40269+

Registers 0028-0113:
Until written to, the Programming Data Block contains information accurate to the current
operation of the meter. Changes written to the Programming Data Block do not go into
effect until a system reset is requested through communication.
See Appendix A: Programming Data Block for specific information.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

PHASE REVERSAL / IMBALANCE BLOCK

REGISTER MAPPINGS FOR MODBUS PROTOCOL

Phase Reversal / Imbalance Block


Registers

Registers

584/984

PHASE REVERSAL
0114

40277
PHASE IMBALANCE

0115

40278

Register 0114:
A 2 Byte value of 0 x 0000 = a phase sequence of A-B-C. A 2-Byte non-zero value = a phase
sequence of C-B-A.
Register 0115:
2 Byte twos complement number, representing a percent voltage imbalance with a single
implied decimal place.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

DAXI DATA BLOCK

Daxi Data Block


Registers

584/984

Registers

INST (D)

584/984

Registers 584/984

AVE (A)

VOLT AN
VOLT BN
VOLT CN
VOLT AB
VOLT BC
VOLT CA
AMP A
AMP B
AMP C
AMP N
WATT
VAR
VA
PF
FREQ
WATT A
WATT B
WATT C
VAR A
VAR B
VAR C
VA A
VA B
VA C
PF A
PF B
PF C
KF VOLT A DM Only
KF VOLT B DM Only
KF VOLT C DM Only
KF AMP A DM Only
KF AMP B DM Only
KF AMP C DM Only
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED

0116
0117
0118
0119
011A
011B
011C
011D
011E
011F
0120
0121
0122
0123
0124
0125
0126
0127
0128
0129
012A
012B
012C
012D
012E
012F
0130
0131
0132
0133
0134
0135
0136
0137
0138
0139
013A
013B

40279
40280
40281
40282
40283
40284
40285
40286
40287
40288
40289
40290
40291
40292
40293
40294
40295
40296
40297
40298
40299
40300
40301
40302
40303
40304
40305
40306
40307
40308
40309
40310
40311
40312
40313
40314
40315
40316

013D
013E
013F
0140
0141
0142
0143
0144
0145
0146
0147
0148
0149
014A
014B
014C
014D
014E
014F
0150
0151
0152
0153
0154
0155
0156
0157
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
015E
015F
0160
0161
0162

RESERVED

013C

40317

0163

40318
40319
40320
40321
40322
40323
40324
40325
40326
40327
40328
40329
40330
40331
40332
40333
40334
40335
40336
40337
40338
40339
40340
40341
40342
40343
40344

Registers

MAX (X)

584/984

MIN (I)

40351
40352
40353
40354
40355

0164
0165
0166
0167
0168
0169
016A
016B
016C
016D
016E
016F
0170
0171
0172
0173
0174
0175
0176
0177
0178
0179
017A
017B
017C
017D
017E
017F
0180
0181
0182
0183
0184
0185
0186
0187
0188
0189

40357
40358
40359
40360
40361
40362
40363
40364
40365
40366
40367
40368
40369
40370
40371
40372
40373
40374
40375
40376
40377
40378
40379
40380
40381
40382
40383
40384
40385
40386
40387
40388
40389
40390
40391
40392
40393
40394

018B
018C
018D
018E
018F
0190
0191
0192
0193
0194
0195
0196
0197
0198
0199
019A
019B
019C
019D
019E
019F
01A0
01A1
01A2
01A3
01A4
01A5
01A6
01A7
01A8
01A9
01AA
01AB
01AC
01AD
01AE
01AF
01B0

40396
40397
40398
40399
40400
40401
40402
40403
40404
40405
40406
40407
40408
40409
40410
40411
40412
40413
40414
40415
40416
40417
40418
40419
40420
40421
40422
40423
40424
40425
40426
40427
40428
40429
40430
40431
40432
40433

40356

018A

40395

01B1

40434

Registers 0116-01B1:
2 Byte twos complement numbers. Decimal placement and scales for voltages, currents
and power readings are available from the Programming Data Block.
Power Factor reported in units of 0.001 PF, divide by 1000. Frequency reported in units of
0.01 Hz, divide by 100.
K-Factor reported in units of 0.01 KF, divide by 100.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

HOUR BLOCK

REGISTER MAPPINGS FOR MODBUS PROTOCOL

Hour Block
Registers

Registers
0

584/984
5

WATT HOUR
01B2+

40435+
VAR HOUR

01BA+

40443+
VA HOUR

01C2+

40451+

Register 501B2-01C9:
16 Bytes each ASCII, representing a 16 Byte BCD count of the base Hour function, in units
of Wh, VARh or VAh.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

LIMIT DETECTION BLOCK

Limit Detection Block


Registers
15

14

13

12

11

10

Limit 1 Bits Limit 2 for


DM Series
9
8
7
6

584/
984
5

THD VOLTS
01CA

---

01CB

A
N

01CC
+

---BN

--- --VOLTS
C
A
N
B

---

---

B
C

C
A

---

---

RE
V

IM
B

PF

FQ

---

14

13

12

11

10

--A
N

---BN

--- --VOLTS
C
A
N
B

---

---

Limit 2 Bits Limit 1 for


DM Series
9
8
7
6
---

---

VAR

VA

C
A

40460
40461
+
584/
984

THD AMPS
C

AMPS
B
C

40459

POWER

THD VOLTS

01D0
+

RESERVED FOR FUTURE USE

15

01CF

AMPS

Registers

01CE

3
THD AMPS

40463

POWER
N

VAR

VA

PF

FQ

---

RESERVED FOR FUTURE USE

40464
40465
+

Register 501CA-01CF:
A bit value of 1 means that the limit is being exceeded for the associated quantity.
A bit value of 0 means that the limit is not being exceeded for the associated quantity.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

RELAY STATUS BLOCK

REGISTER MAPPINGS FOR MODBUS PROTOCOL

Relay Status Block


Registers

Relay 1 Bits
15

14

01DA

---

----

01DB

A
N

01DC
+

BN

13

11

10

--- --VOLTS
C
A
N
B

---

---

STATUS
THD VOLTS
O
LK
A
B
C
N
AMPS

B
C

C
A

VAR

---

01DE

A
N

01DF

RE
V

IM
B

40475

PF

FQ

----

40476

THD AMPS
B
POWER

VA

13

12

11

10

----

--- --VOLTS
C
A
N
B

---

---

STATUS
THD VOLTS
O
LK
A
B
C
N
AMPS

BN

B
C

15
---

RE
V

IM
B

40479

PF

FQ

----

40480

THD AMPS
A

B
POWER

C
A
B
C
N
W
VAR
A
RESERVED FOR FUTURE USE

VA

40481+

Relay 3 Bits

Registers

A
N

40477+
584/984

14

01E0+

01E0+

Relay 2 Bits
15

01E3

RESERVED FOR FUTURE USE

Registers

01E2

584/984

12

14
---BN

13

12

--- --VOLTS
C
A
N
B

11
--B
C

584/984

10

---

STATUS
THD VOLTS
O
LK
A
B
C
N
AMPS

REV

IMB

40483

PF

FQ

----

40484

THD AMPS
A

C
A
B
C
N
W
VAR
A
RESERVED FOR FUTURE USE

B
POWER
VA

40485+

Registers 01DA-01E3:
Status: A bit value of 1 for ON means the relay is activated, 0 means not activated.
A bit of 1 for LK means the relay is locked, 0 means not locked.
Other: A bit value of 1 means the associated limit has activated the relay.
A bit value of 1 means the associated limit has not activated the relay.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

THD SUMMARY BLOCK

THD Summary Block


Registers

584/984

Registers

584/984

Registers

INST (D)

584/984
MAX (X)
40503
40504
40505
40506

Registers
01FC
01FD
01FE
01FF

584/984
MIN (I)
40509
40510
40511
40512

THD VOLT A
THD VOLT B
THD VOLT C
THD AMP A

01EA
01EB
01EC
01ED

40491
40492
40493
40494

RESERVED
RESERVED
RESERVED
RESERVED

01F6
01F7
01F8
01F9

THD AMP B

01EE

40495

RESERVED

01FA

40507

0200

40513

THD AMP C

01EF

40496

RESERVED

01FB

40508

0201

40514

Registers 01EA-0201:
2 Byte each twos complement numbers, representing a percentage with a single decimal
point.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

THD DETAIL BLOCK

10

REGISTER MAPPINGS FOR MODBUS PROTOCOL

THD Detail Block


10.1

HARM VOLT A Registers


Registers

584/984

Registers

PERCENT
HARM 0
|
HARM 31

0202
|
0240
0242+

10.2

HARM 31

0282
|
02C0
02C2+

HARM 0
|

0302
|

HARM 31

0340

HARM 0
|

0382
|

HARM 31

03C0

0241

40578
40579+

40643
|

0283
|

40705

02C1

RESERVED FOR FUTURE USE

40644
|
40706
40707+

40771
|

0303
|

40833

0341

RESERVED FOR FUTURE USE

40772
|
40834
40835+

40899
|

0383
|

40961

03C1

RESERVED FOR FUTURE USE

40900
|
40962
40963+

HARM AMP B Registers


HARM 0
|
HARM 31

0402
|
0440
0442+

10

40577

RESERVED FOR FUTURE USE

40516
|

HARM AMP A Registers

03C2+

10.5

0203
|

HARM VOLT C Registers

0342+

10.4

40515
|

HARM VOLT B Registers


HARM 0
|

10.3

584/984
PHASE

41027
|

0403
|

41089

0441

RESERVED FOR FUTURE USE

41028
|
41090
41091+

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

10.6

THD DETAIL BLOCK

HARM AMP C Registers


HARM 0
|

0482
|

41155
|

0483
|

41156
|

HARM 31

04C0

41217

04C1

41218

04C2+

RESERVED FOR FUTURE USE

41219+

Register 0202-04C1:
Percent: 2 Bytes each twos complement number, representing a percentage with a single
implied decimal point.
Phase: 2 Bytes each twos complement number, representing a phase angle with a single
implied decimal point.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

11

RESET BLOCK

11

REGISTER MAPPINGS FOR MODBUS PROTOCOL

Reset Block
Registers

Bits
15

14

1
3

A
0502

0503

0504

1
2
B

584/984
7

A
M
P

POWER

A
B

B
C
VA

C
A

---

---

---

---

VAR

V
A

PF

FQ

---

41283

---

----

----

---

41284

VAR

VA

---

41285

----

---

----

----

---

41286

PF

KF AMPS

THD VOLTS
0505

8
V-PP

VAR

KF VOLTS
B

W
B

1
0

11

RESET

HOUR

THD AMPS
C

0506+

------ -----RESERVED FOR FUTURE USE

41287+

Registers 0502-0505:
Reset: A bit of 1 for X or I will reset the MAX or MIN, respectively, of indicated features.
The bits from indicated features will be cleared as their feature is reset.
Hour: A bit value of 1 for W, VAR, or VA will reset the WATT, VAR, or VA Hour counter.
Other: A bit value will reset the MAX or MIN of the associated feature upon setting either
the X or I bit in the Reset Group.

12

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

12

COMMUNICATION PARAMETERS

Communication Parameters
Meters with the MODBUS communication option can communicate with either ASCII or
RTU framing.
ASCII framing - 7 data bits, even parity, 1 stop bit
RTU framing - 8 data bits, no parity, 1 stop bits
User selection of this parameter can be accomplished either through communication (see
Appendix A: Programming Data Block Map) or by the user through the keypad.
Keypad selection is accomplished through the Programming mode in the System
Configuration function,
Group 0, Function 3. Switch PACK 2 Position C controls which framing mode to use for
MODBUS communication.
Switch setting 0 signifies RTU framing, while switch settings 1 signifies ASCII framing.
For a detailed explanation of the Programming Mode, see the Programming Manual.
MODBUS communication is limited to 50 registers per query.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

13

APPENDIX A: PROGRAMMING DATA BLOCK MAP

13

Appendix A: Programming Data Block Map


Registers
0028+
002C+
0030+
0034+
0038+
003C+
0040+
0044+
0048+
004C+
0050+
0054+
0058+
005C+
0060+
0064+
0068+
006C+
0070+
0074+
0078+
007C+
0080+
0084+
0088+
008C+
0090+
0094+
0098+
009C+
00A0+
00A4+
00A8+
00AC+
00B0+
00B4+
00B8+
00BC+
00C0+
00C4+
00C8+
00CC+
00D0+
00D4+
00D8+
00DC+
00E0+
00E4+
00E8+
00EC+
00F0+
00F4+
00F8+
00FC+
0100+
0104+
0108+

14

REGISTER MAPPINGS FOR MODBUS PROTOCOL

0
Interval
VOLTS Full Scale
Set Above/Below Lim1
AMPS A Lim1
AMPS B Lim1
AMPS C Lim1
VOLTS BC Lim1
AMPS N Lim1
VAR Lim1
PF Lim1

Registers
1
Address
AMPS Full Scale
Set Above/Below Lim2
AMPS A Lim2
AMPS B Lim2
AMPS C Lim2
VOLTS BC Lim2
AMPS N Lim2
VAR Lim2
PF Lim2

584/984
2
Baud Rate
Decimal Placement
VOLTS AN Lim1
VOLTS BN Lim1
VOLTS CN Lim1
VOLTS AB Lim1
VOLTS CA Lim1
WATT Lim1
VA Lim1
FREQ Lim1

3
Config
LILCO
VOLTS AN Lim2
VOLTS BN Lim2
VOLTS CN Lim2
VOLTS AB Lim2
VOLTS CA Lim2
WATT Lim2
VA Lim2
FREQ Lim2

RLY2 Lim1
RLY1 THD Lim1-2
THD AMPS A Lim1
THD AMPS B Lim1
THD AMPS C Lim1
RELAY 1 MODE
Delay off RLY1-2

RLY2 Lim2
RLY2 THD Lim1-2
THD AMPS A Lim2
THD AMPS B Lim2
THD AMPS C Lim2

RESERVED
FOR
FUTURE
USE
RLY1 Lim1
Delay on RLY1-2
THD VOLTS A Lim1
THD VOLTS B Lim1
THD VOLTS C Lim1
RLY1-2 IMB Lim1
RELAY 2 MODE
KYZ MAP

RLY1 Lim2
SAB THD Lim1-2
THD VOLTS A Lim2
THD VOLTS B Lim2
THD VOLTS C Lim2
IMB Lim1
KYZ FACTOR

RESERVED
FOR
FUTURE
USE

CT Ratio

PT Ratio

KYZ MAP

40041+
40045+
40049+
40053+
40057+
40061+
40065+
40069+
40073+
40077+
40081+
40085+
40089+
40093+
40097+
40101+
40105+
40109+
40113+
40117+
40121+
40125+
40129+
40133+
40137+
40141+
40145+
40149+
40153+
40157+
40161+
40165+
40169+
40173+
40177+
40181+
40185+
40189+
40193+
40197+
40201+
40205+
40209+
40213+
40217+
40221+
40225+
40229+
40233+
40237+
40241+
40245+
40249+
40253+
40257+
40261+
40265+

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

APPENDIX A: PROGRAMMING DATA BLOCK MAP

010C+
0110+

40269+
40273+

SYSTEM RESET

13.1

Configuration Information
13.1.1

Interval

Register 0028:
2 Byte twos complement number representing the Integration Interval in seconds.

13.1.2

Address

Register 0029:
2 Byte twos complement number, which is the Address of the meter for communication
purposes.
Under MODBUS communications, this address should be between 1 and 247, inclusive.

13.1.3

Baud Rate

Register 002A:
2 Byte twos complement number, which is the Baud Rate being used for communications.
Only baud rate
valid for the meter in question should be used (e.g., 1200, 9600). Improper settings could
disable communication.

13.1.4

Configuration

Register 002B:
Register
002B

Bits
15

14

13

12

11

KV

KA

MW

REV

LZ

KV:

10
RS
T

584/984

----

DLT

AVG

----

ASCII

MOD

RLY1

RLY2

COM

DC

40044

A bit value of 1 means the meter is configured for kilovolt inputs. *

A bit value of 0 means the meter is configured for volt inputs. *


KA:

A bit value of 1 means the meter is configured for kiloamp inputs. *


A bit value of 0 means the meter is configured for amps inputs. *

MW:

A bit value of 1 means the meter is configured for megawatt inputs. *


A bit value of 0 means the meter is configured for kilowatt inputs. *

REV:

A bit value of 1 means the Phase Reversal Limits are enabled.


A bit value of 0 means the Phase Reversal Limits are not enabled.

LZ:

A bit value of 1 means leading zeros are blanked on the meter display.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

15

APPENDIX A: PROGRAMMING DATA BLOCK MAP

REGISTER MAPPINGS FOR MODBUS PROTOCOL

A bit value of 0 means leading zeros are displayed on the meter display.
RST:

A bit value of 1 means that Reset Protection is enabled. (Resetting max/min and
hour function readings from the keypad requires the entry of a password).

A bit value of 0 means that Reset Protection is disabled. (Resetting hour function readings
from the keypad requires the entry of a password).
DLT:

A bit value of 1 means the meter is set up for Open Delta.


A bit value of 0 means the meter is set up for non Open Delta configuration.

AVG:

A bit value of 1 means Limits are set by the Average Readings.


A bit value of 0 means Limits are set by the Instantaneous Readings.

ASCII MOD:
ASCII

MOD

PROTOCOL

DNP 3.0

Modbus ASCII

Modbus RTU

RLY1:

Please see the Programming Manual about PACK 3 of Function 0, Group 3 for an
explanation of the meaning of these bits.

RLY2:

Please see the Programming Manual about PACK 3 of Function 0, Group 3 for an
explanation of the meaning of these bits.

COM:

Please see the Programming Manual about PACK 3 of Function 0, Group 3 for an
explanation of the meaning of these bits.

DC:

Please see the Programming Manual about PACK 3 of Function 0, Group 3 for an
explanation of the meaning of these bits.

These features duplicate those available in the switch PACKS of Function 0, Group 3, in the
meters Programming Mode.
For further information, please see the other manuals for the meter.
* Should these features be changed, a replacement Bezel should be ordered to reflect the
new units.

13.1.5

VOLTS Full Scale

Register 002C:
2 Byte twos complement number representing the Full Scale for voltage. For decimal
placement, see Decimal Placement below.

13.1.6

AMPS Full Scale

Register 002D:
2 Byte twos complement number representing the Full Scale for current. For decimal
placement, see Decimal Placement below.

16

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

13.1.7

APPENDIX A: PROGRAMMING DATA BLOCK MAP

Decimal Placement & LILCO Configuration

Registers

Registers

584/984

0
002E+

VOLTS DP

1
AMPS DP

WATT DP

LILCO CONFIG

40047+

Registers 002E-002F:
Each of the DP bytes represents the implied number decimal places in the associated
values. Valid values are '0'-'4', withmeanings from 'no implied decimal place' to 'four
implied decimal places'. These values effect the meanings of INST,MAX, MIN, Hour
functions, Full Scales, Limits and other readings.

13.1.8

LILCO Configuration

Register

Bits
7

002F

584/984
3

VOLT

AMP

POWER

Round by 10

Current Scale

Power Scale

0
ENABLE
LILCO

40048

Register 002F:
These settings affect readings in the LILCO mapping.
Round by 10:

0=no rounding

1=round raw readings down by 10 before


scaling.

Current Scale:

00=1A Full Scale

01=2.5A Full Scale

10= 5A Full Scale

11=7.5A Full Scale

000=250W Full Scale

001=500W Full Scale

010=1000W Full Scale

011=1500W Full Scale

100=2000W Full Scale

101=2500W Full Scale

110=3000W Full Scale

111=3500W Full Scale

0=Normal Mapping

1=LILCO Mapping (Normal mapping starts at


100)

Power Scale:

LILCO Enable:

13.1.9

Set Above/Below Lim 1

Register

Bits
15

14

13

12

11

10

VOLTS
0030

AN

BN

CN

AB

584/984
7

AMPS
BC

CA

PF

FQ

---

POWER
N

VAR

VA

40049

Register 0030:
A bit value of 0 means the limit is exceeded if the associated value is greater than its Limit
1 value.
A bit value of 1 means the limit is exceeded if the associated value is less than its Limit 1
value.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

17

APPENDIX A: PROGRAMMING DATA BLOCK MAP

REGISTER MAPPINGS FOR MODBUS PROTOCOL

For functions with negative numbers, the comparisons use absolute valued values.

13.1.10 Set Above/Below LIM 2


Register 0031:
Same as Set Above/Below Lim1, but for Limit 2.

13.1.11 VOLTS AN Lim1-FREQ Lim2


Registers 0032-004F:
2 Byte twos complement numbers, representing limit thresholds for the associated
functions. Decimal placement is determined by the associated DP byte.

13.1.12 RLY LIM 1

Register

Bits
15

14

13

AN

BN

CN

12

11

10

BC

CA

VOLTS
0070

AB

584/984
7

VAR

AMPS
C

PF

FQ

---

POWER
VA

40113

Register 0070:
A bit value of 1 means that Limit 1 of the associated value will trigger Relay 1.
A bit value of 0 means that Limit 1 of the associated value will not trigger Relay 1.

13.1.13 RLY LIM 2-RLY2 LIM2


Register 0071-0073:
Same as RLY1 Lim 1, but for Relay 2 and Limit 2 where appropriate.

13.1.14 Delay ON RLY1-2

Register

Bytes

0074

584/984

Relay 1

Relay 2

40117

Register 0074:
1 Byte unsigned binary number each, representing the delay time from a relay being reset
before it could be set in seconds.
Valid numbers are 0 to 250.

13.1.15 SAB THD LIM 1-2

Register

18

Bits

584/984

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

15

14

13

APPENDIX A: PROGRAMMING DATA BLOCK MAP

12

11

10

Lim1
A

THD AMPS

---

---

Lim2

THD VOLTS
0075

THD VOLTS
---

----

THD AMPS

40118

Register 0075:
A bit value of 0 = the limit is exceeded if the associated value is greater than its Limit 1 or 2.
A bit value of 1 = the limit is exceeded if the associated value is less than its Limit 1 or 2.

13.1.16 RLY THD LIM 1-2

Register

Bits
15

14

13

12

11

10

584/984

RLY1 Lim1
THD VOLTS
0076

---

---

RLY1 Lim2

THD AMPS

THD VOLTS
----

----

THD AMPS
A

40119

Register 0076:
A bit value of 1 means that the indicated limit of the associated value will trigger a Relay.
A bit value of 0 means that the indicated limit of associated value will not trigger Relay 1.

13.1.17 RLY2 THD LIM 1-2


Register 0077:
Same as RLY THD Lim 1-2, but for Relay 2.

13.1.18 THD VOLTS A LIM 1 - THD AMPS C LIM2


Registers 0078-0083:
2 Byte twos complement numbers, representing the limit thresholds for the associated
functions, represents a percentage with a single implied decimal.

13.1.19 RLY1-2 IMB LIM 1

Register

Bits
15

14

12

11

10

----

----

---

---

---

----

REV

RLY1
0084

RE
V

IMB

584/984

13

---

---

---

---

----

---

RLY2
IMB

40133

Register 0084:
REV: A bit value of 1 means that Limit 1 for Phase Reversal will trigger the indicated Relay.
A bit value of 0 means that Limit 1 for Phase Reversal will not trigger the indicated Relay.
Phase Reversal Limit 1 is enabled by the REV bit in Config.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

19

APPENDIX A: PROGRAMMING DATA BLOCK MAP

REGISTER MAPPINGS FOR MODBUS PROTOCOL

IMB: A bit value of 1 means that Limit 1 for Phase Imbalance will trigger the indicated
Relay.
A bit value of 0 means that Limit 1 for Phase Imbalance will not trigger the indicated Relay.
Phase Imbalance Limit 1 is always enabled.

13.1.20 IMB LIM 1


Register 0085:
2 Byte twos complement number, representing the limit threshold for Imbalance. This
number represents a percentage with a single implied decimal place. The Imbalance Limit
is always set to be passed, if the Imbalance percentage is greater than this limit.

13.1.21 Relay 1 Mode:

Registers

Registers
IMB/REV
CONTROL

0086+

584/984
1
SET/ RESET
CONTROL

LOGIC CONTROL

40135+

Registers 0086-0087:
IMB/REV/CONTROL: 1 Byte twos complement number, where a value of 0 means that
Relay 1 is set by Phase Reversal or Imbalance Limits being exceeded and reset by normal
Reversal and Imbalance conditions. Non-zero values mean that Relay 1 is reset by Phase
Reversal or Imbalance Limits being exceeded and set by normal Reversal and Imbalance
conditions.
LOGIC CONTROL: 1 Byte twos complement number, where a value 0 means that all
Limits triggering Relay 1 should be added to set or reset the Relay. Non-zero values means
that all Limits triggering Relay 1 should be ORed to set or reset the Relay.
SET RESET CONTROL: 2 one Byte twos complement numbers. Two non-zero values
indicate that Relay 1 is normally reset, and exceeded limit set the Relay. Two values of zero
indicate that Relay 1 is normally set and exceeded limits reset the Relay. Other
combinations are reserved for future use.

13.1.22 RELAY 2 MODE


Registers 0088-0089:
Same as RELAY 1 MODE, but for Relay 2.

13.1.23 Delay off RLY1-2

Registers

Bytes
0

008A

Relay 1

584/984
1
Relay 2

40139+

Register 008A:

20

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

APPENDIX A: PROGRAMMING DATA BLOCK MAP

1 Byte unsigned binary number each, representing the delay time from a relay being set
before it could be reset in seconds.
Valid numbers are from 0 to 250

13.1.24 KYZ Map, KYZ Factor

Registers

Registers
0

KYZ MAP
008B+

Port 1

584/984

1
Port 2

KYZ FACTOR
Port3

Port1

Port2

Port3

40143+

Register 008B-008D:
KYZ MAP:1 Byte twos complement numbers, signifying whether which ports should be
enabled for KYZ outputs of which functions.
Valid numbers are:
0 KYZ disabled

3 -Watt Hour KYZ

1 +Watt Hour KYZ

4 +VAR Hour KYZ

2 VA Hour KYZ

5 -VAR Hour KYZ

KYZ FACTOR:1 Byte twos complement numbers, representing the KYZ change in level per
Watt for each port. Valid numbers are:
0 one unit of Full Scale

4 one unit of Full Scale

1 two units if Full Scale

5 half a unit of Full Scale

2 ten units of Full Scale

6 one tenth a unit of Full Scale

3 twenty units of Full Scale

7 one twentieth a unit of Full Scale

13.1.25 CT/PT Ratios

Registers
0108+

Registers

584/984

CT Ratio

PT Ratio

40265+

Registers 0108-0109:
2 bytes, MSB first values. Displayed in the RTU Block in user definable format.

13.1.26 System Reset


Register 0113:
2 Byte twos complement number. When the meter is reset, this register contains the value
-32, 768, (0x8000). It is recommended that communication with the meter begin with
writing another value to this register. Thus, the device communicating would know if the
meter was reset (through the keypad, power loss, etc.) by reading this register and
checking for the value -32768.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

21

APPENDIX A: PROGRAMMING DATA BLOCK MAP

REGISTER MAPPINGS FOR MODBUS PROTOCOL

Communication can request for a reset of the meter by writing the value -1 (0xFFFF) to
this register. Any changes made to the Programming Data Block through communication
will go into effect only after this reset is performed. Any other form of reset will result in the
loss of any modifications to the Programming Data since the last meter was reset.
Writing the value 0 (0x0000) to this register will reset the Programming Data Block,
permanently removing any changes made to these registers since the last communication
requested reset.

22

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

14

APPENDIX B: LILCO MAPPING

Appendix B: LILCO MAPPING


If this mapping is configured by setting the appropriate bit in the LILCO configuration
register of the Programming Block, then all the register addresses shown in the regular
mapping are moved down by 100. For example, Instantaneous Volts AN is normally
accessed in register 0116 (40279). When LILCO mapping is selected, the old register
information is now stored 100 registers lower, in register 017A (40379).
In addition to the bit which configures the mapping, the LILCO Configuration register
contains other bits which provide scaling options for readings in this alternate mapping.
This register mapping is designed in conjunction with Long Island Lighting Company a
proposed standard for utility RTUs. This is designed to give the maximum efficiency in
polling information within the blocks.

14.1

System Sanity
Registers

Registers

584/984

SYSTEM SANITY
0000

40001

Register 0000:
2-byte indication of proper operation of a meter. A value of 0x0000 indicates the meter
detects it is operating properly.
Any other value is an indication that the meter detects an internal fault.

14.2

Polling Values
Registers

584/984

Registers

POLLING
AMP A
AMP B
AMP C
VOLT AN
VOLT BN
VOLT CN
WATT
VAR

000
1
000
2
000
3
000
4
000
5
000
6
000
7
000
8

584/984

POLLING

40002

WATT A

0009

40010

40003

WATT B

000A

40011

40004

WATT C

000B

40012

40005

VAR A

000C

40013

40006

VAR B

000D

40014

40007

VAR C

000E

40015

40008
40009

Register 0001-000E:
All registers use the least significant 12 bits as signed magnitude numbers. All polling
values report their magnitude based on the secondary currents and voltage, not the
primaries. Scaling for these values should be interpreted as follows:
0x0000 (0) = negative Full Scale 0x07FF (2047) = 0 0x0FFF (4096) = positive Full Scale
Full Scale for Voltage is 150 V on the secondary.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

23

APPENDIX B: LILCO MAPPING

REGISTER MAPPINGS FOR MODBUS PROTOCOL

Full Scale for Current and Power depends on the settings of the MODBUS RTU
Configuration bits in the Programming Block.

14.3

CT/PT Ratios
Registers

Registers

584/984

CT RATIO
000F

40016
PT RATIO

0010

40017

Registers 000F - 0010:


These are two byte registers of raw binary data, stored by the meter in the Programming
Block. These registers are MSB binary.
Any value of any format may be used. These values may be modified through the CT/PT
Ratio Registers in the Programming Block.

14.4

Neutral Current
Registers

Registers

584/984

NEUTRAL CURRENT
0011

40018

Register 0011:
This register is formatted the same as registers 0001 - 000E.

14.5

Hour Readings
Registers
584/984
High
+KWatt/hour
-KWatt/hour
+KVAR/hour
-KVAR/hour

0012
0014
0016
0018

40019
40021
40023
40025

Registers
584/984
Low
0013
0015
0017
0019

40020
40022
40024
40026

Register 0012 - 0019:


2 - byte MSB binary numbers. The registers marked Low contain the values 0x0000 0x270F, or 0 - 9999, representing Kilowatt/hour. The registers marked High contain the
values 0x0000 - 0x270F, or 0 - 9999, representing 10's of MegaWatt/hour.
Together, eight digits of Kilowatt/hour may be read.

24

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

14.6

APPENDIX B: LILCO MAPPING

Frequency
Registers

Registers

584/984

FREQUENCY
001A

40027

Register 001A:
This register uses the least significant 12 bits as a signed magnitude number. Scaling for
this values should be interpreted as follows:
0x0000 (0) = 45 Hz or less 0x07FF (2047) = 60 Hz 0x0FFF (4096) = 75 Hz or greater
Register 001B - 0062
These registers are reserved for future use.

14.7

Energy Reset
Registers

Registers

584/984

ENERGY RESET
0063

40100

Register 0063:
When a value of 0x0001 is written to this register, the HOUR readings on the meter will be
reset.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

25

APPENDIX C: FLOATING POINT REGISTERS

15

REGISTER MAPPINGS FOR MODBUS PROTOCOL

Appendix C: Floating Point Registers


15.1

Negative Max/Min Block

WATT
VAR
PF
WATT A
WATT B

Registers
584/984
NEG MAX
050A
41291
050B
41292
050C
41293
050D
41294
050E
41295

Registers

584/984
NEG MIN
41303
41304
41305
41306
41307

0516
0517
0518
0519
051A

WATT C

050F

41296

051B

41308

VAR A
VAR B
VAR C
PF A
PF B

0510
0511
0512
0513
0514

41297
41298
41299
41300
41301

051C
051D
051E
051F
0520

41309
41310
41311
41312
41313

PF C

0515

41302

0521

41314

Registers 01EA-0201:
2 Byte twos complement numbers. Decimal placement and scales for appropriate
readings are available from the Programming Data Block.

15.2

26

Floating Point DAXI Data Block

VOLT AN
VOLT BN
VOLT CN
VOLT AB
VOLT BC
VOLT CA
AMP A
AMP B
AMP C
AMP N
WATT
VAR
VA
PF
FREQ
WATT A
WATT B
WATT C
VAR A
VAR B
VAR C

Registers 584/984
INST (D)
0522
41315
0524
41317
0526
41319
0528
41321
052A
41323
052C
41325
052E
41327
0530
41329
0532
41331
0534
41333
0536
41335
0538
41337
053A
41339
053C
41341
053E
41343
0540
41345
0542
41347
0544
41349
0546
41351
0548
41353
054A
41355

Registers 584/984
AVE (A)
057C
41405
057E
41407
0580
41409
0582
41411
0584
41413
0586
41415
0588
41417
058A
41419
058C
41421
058E
41423
0590
41425
0592
41427
0594
41429
0596
41431
0598
41433
059A
41435
059C
41437
059E
41439
05A0
41441
05A2
41443
05A4
41445

Registers 584/984
MAX (X)
05D6
41495
05D8
41497
05DA
41499
05DC
41501
05DE
41503
05E0
41505
05E2
41507
05E4
41509
05E6
41511
05E8
41513
05EA
41515
05EC
41517
05EE
41519
05F0
41521
05F2
41523
05F4
41525
05F6
41527
05F8
41529
05FA
41531
05FC
41533
05FE
41535

Registers 584/984
MIN (I)
0630
41585
0632
41587
0634
41589
0636
41591
0638
41593
063A
41595
063C
41597
063E
41599
0640
41601
0642
41603
0644
41605
0646
41607
0648
41609
064A
41611
064C
41613
064E
41615
0650
41617
0652
41619
0654
41621
0656
41623
0658
41625

VA A

054C

05A6

0600

065A

41357

41447

41537

41627

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

VA B
VA C
PF A
PF B
PF C

APPENDIX C: FLOATING POINT REGISTERS

054E
0550
0552
0554
0556

41359
41361
41363
41365
41367

05A8
05AA
05AC
05AE
05B0

41449
41451
41453
41455
41457

0602
0604
0606
0608
060A

41539
41541
41543
41545
41547

065C
065E
0660
0662
0664

41629
41631
41633
41635
41637

060C
060E
0610
0612
0614
0616
0618
061A
061C
061E
0620

MAX (X)
41548
41551
41553
41555
41557
41559
41561
41563
41565
41567
41569

0666
0668
066A
066C
066E
0670
0672
0674
0676
0678
067A

MIN (I)
41639
41641
41643
41645
41647
41649
41651
41653
41655
41657
41659

See next page for continuation and description.

THD VOLT A
THD VOLT B
THD VOLT C
THD AMP A
THD AMP B
THD AMP C
KF VOLT A DM Only
KF VOLT B DM Only
KF VOLT C DM Only
KF AMP A DM Only
KF AMP B DM Only

0558
055A
055C
055E
0560
0562
0564
0566
0568
056A
056C

INST (D)
41369
41371
41373
41375
41377
41379
41381
41383
41385
41387
41389

AVE (A)
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED

KF AMP C DM Only

056E

41391

RESERVED

0622

41571

067C

41661

RESERVED
RESERVED
RESERVED
RESERVED
RESERVED

0570
0572
0574
0576
0578

41393
41395
41397
41399
41401

05CA
05CC
05CF
05D0
05D2

41483
41485
41487
41489
41491

0624
0626
0628
062A
062C

41573
41575
41577
41579
41581

067E
0680
0682
0684
0686

41663
41665
41667
41669
41671

RESERVED

057A

41403

05D4

41493

062E

41583

0688

41673

Registers 0522-0689:
Every 2 registers hold a 4 byte floating-point number. The format of a pair of registers is as
follows:
Registers

0522+

15
Sign
0

15.3

14
7

Exponent

REGISTER 0
7
6
0

22

15

584/984

REGISTER 1

Fraction

41315+

Floating-point Negative Max/Min Block

WATT
VAR
PF
WATT A
WATT B

Registers
584/984
NEG MAX
068A
41675
068C
41677
068E
41679
0690
41681
0692
41683

Registers
584/984
NEG MIN
06A2
41699
06A4
41701
06A6
41703
06A8
41705
06AA
41707

WATT C

0694

41685

06AC

41709

VAR A
VAR B
VAR C
PF A

0696
0698
069A
069C

41687
41689
41691
41693

06AE
06B0
06B2
06B4

41711
41713
41715
41717

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

27

APPENDIX C: FLOATING POINT REGISTERS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

PF B

069E

41695

06B6

41719

PF C

06A0

41697

06B8

41721

584/984

Registers

Registers 068A-06B9:
Every 2 registers hold a 4-byte floating-point number.

15.4

Floating-point THD Detail Block


HARM VOLT A Registers
Registers
PERCENT

584/984
PHASE

HARM 0
|

06BA
|

41723
|

06BC
|

41725
|

HARM 31

0736

41847

0738

41849

HARM 0
|

073A
|

41851
|

073C
|

41853
|

HARM 31

07B6

41975

07B8

41977

HARM VOLT B Registers

HARM VOLT C Registers


HARM 0
|

07BA
|

41979
|

0303
|

41981
|

HARM 31

0836

42103

0838

41205

HARM AMP A Registers


HARM 0
|

083A
|

42107
|

083C
|

42109
|

HARM 31

08B6

42231

08B8

42233

HARM 0
|

08BA
|

42235
|

08BC
|

42237
|

HARM 31

0936

42359

0938

42361

HARM 0
|

093A
|

42363
|

093C
|

42365
|

HARM 31

09B6

42487

09B8

42489

HARM AMP B Registers

HARM AMP C Registers

Register 0202-04C1:
Percent: 2 registers, a 4-byte floating point number representing a percentage with a
single implied decimal point.

28

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

APPENDIX C: FLOATING POINT REGISTERS

Phase: 2 registers, a 4-byte floating point number representing a phase angle with a single
implied decimal point.

15.5

Negative Hour Block


Registers

584/984

-WATT HOUR
09BA +

42491+
-VAR HOUR

09C2+

42499+

For Description: see description for HOUR BLOCK on page 5.

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

29

APPENDIX D: MASS MEMORY & NULL TERMINATED HOUR READINGS

16

REGISTER MAPPINGS FOR MODBUS PROTOCOL

Appendix D: Mass Memory & Null Terminated Hour Readings


16.1

Mass Memory Counter


Registers 09CA-09CD:
4-byte or 2-byte 2s complement numbers representing the number of Snapshots, Events
or Waveforms stored in the mass memory of the meter.
Null-Terminated Hour Readings
Registers

584/984

WATT HOUR
09CE+

42511+

VAR HOUR
09D6+

42519+

VA HOUR
09DE+

42527+

-WATT HOUR
09E6+

42535+

-VAR HOUR
09EE+

42543+

Registers 09CE-09F5:
16 Bytes each ASCII, representing a 15-Byte BCD count of the Base Hour Function, in units
of Wh, VARh and VAh.
The least significant byte of the last register in each Hour Reading is the ASCII null
character ( 0x 00 ).

16.2

Exception Flags

09F6

15

14

13

12

11

10

L1

L2

42551

Register 09F6:
L1:

A bit value of 1 means a Limit 1 is exceeded. Cleared when Read.


A bit value of 0 means no Limit 1s are exceeded.

L2:

A bit value of 1 means a Limit 2 is exceeded. Cleared when Read.


A bit value of 0 means no Limit 2s are exceeded.

30

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

R:

APPENDIX D: MASS MEMORY & NULL TERMINATED HOUR READINGS

A bit value of 1 means a Relay is energized. Cleared when Read.


A bit value of 0 means no Relays are energized.

I:

A bit value of 1 means an Input is active.


A bit value of 0 means no Inputs are active.

W:

A bit value of 1 means at least 1 Waveform is stored.


A bit value of 0 means no Waveforms are stored.

16.3

Input Status:

09f7

15

14

13

12

11

10

I1

I2

I3

I4

42552

Register 09F7:
A bit value of 1 means the associated input is active
A bit value of 0 means the associated input is not active.

16.4

Exception Buffer Status (Futura+ CPU1000 only)


09F8
09F9

Buffer Status
Programming Status

42553
42554

Register 09F8:
[Buffer Status]

2 Bytes

0x00000

= No change in Exception Buffer since the Buffer was last read.

0x0001-0x0FFFE

= Number of update cycles where the Exception Buffer was


updated since the buffer was last read.

0x0FFFF

= 65535 or more update cycles where the Exception Buffer was


updated since the buffer was last read.

Register 09F9:

16.5

[Programming Status]

2 Bytes

0x00000

= No change in Programming since the Buffer was last read.

0x00001-0x0FFFF

= Programming was changed since the Buffer was last read.

Exception Buffer (Futura+ CPU1000 only)


Current Limit Status
Registers 09FA-09FE:
[Delta]

10 bytes

Bit = 1 means a change occurred for the appropriate condition


Bit = 0 means no change occurred for the appropriate condition
Limit 1 - 4 bytes

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

31

APPENDIX D: MASS MEMORY & NULL TERMINATED HOUR READINGS

09FA

09FB

15
7
THD VA
15
VAN
7
IC

14
6
THD VB
14
VBN
6
IN

13
5
THD VC
13
VCN
5
W

REGISTER MAPPINGS FOR MODBUS PROTOCOL

12
4
THD IA
12
VAB
4
VAR

11
3
THD IB
11
VBC
3
VA

10
2
THD IC
10
VCA
2
PF

9
1
REV
9
IA
1
FQ

8
0
IMB
8
IB
0
-

12
4
THD IA
12
VAB
4
VAR

11
3
THD IB
11
VBC
3
VA

10
2
THD IC
10
VCA
2
PF

9
1
REV
9
IA
1
FQ

8
0
IMB
8
IB
0
-

12
Input 4
4
-

11
3
-

10
2
-

9
1
-

8
0
-

42555

42556

Limit 2 - 4 bytes

09FC

09FD

15
7
THD VA
15
VAN
7
IC

14
6
THD VB
14
VBN
6
IN

Inputs

09FE

15
Input 1
7
-

13
5
THD VC
13
VCN
5
W

42557

42558

- 2 bytes

14
Input 2
6
-

13
Input 3
5
-

42559

Registers 09FF-0A02:
[Exceed]

8 bytes

Bit = 1 means this limit is being exceeded.


Bit = 0 means this limit is not being exceeded.
Limit 1 - 4 bytes

09FF

0A00

15
7
THD VA
15
VAN
7
IC

14
6
THD VB
14
VBN
6
IN

13
5
THD VC
13
VCN
5
W

12
4
THD IA
12
VAB
4
VAR

11
3
THD IB
11
VBC
3
VA

10
2
THD IC
10
VCA
2
PF

9
1
REV
9
IA
1
FQ

8
0
IMB
8
IB
0
-

12
4
THD IA
12
VAB
4
VAR

11
3
THD IB
11
VBC
3
VA

10
2
THD IC
10
VCA
2
PF

9
1
REV
9
IA
1
FQ

8
0
IMB
8
IB
0
-

42560

42561

Limit 2 - 4 bytes

0A01

0A02

15
7
THD VA
15
VAN
7
IC

14
6
THD VB
14
VBN
6
IN

13
5
THD VC
13
VCN
5
W

42562

42563

Registers 0A03-0A2B:
[Values]

0A03+
0A0B+
0A13+
0A1B+
0A23+

32

0
VAN
IC
WB
PF A
KF IC

1
VBN
IN
WC
PF B
THD VA

82 bytes

2
VCN
W
VAR A
PF C
THD VB

3
VAB
VAR
VAR B
KF VA
THD VC

Instantaneous or Average values, 2 bytes, 2s comp,


MSB
4
VBC
VA
VAR C
KF VB
THD IA

5
VCA
PF
VA A
KF VC
THD IB

6
IA
FQ
VA B
KF IA
THD IC

7
IB
WA
VA C
KF IB
Reversal

42564+
42572+
42580+
42588+
42596+

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

REGISTER MAPPINGS FOR MODBUS PROTOCOL

0A2B

APPENDIX D: MASS MEMORY & NULL TERMINATED HOUR READINGS

Imbalance

42604

Register 0A2C:
[Inputs]

0A2C

15
Input 1
7
-

2 bytes

14
Input 2
6
-

13
Input 3
5
-

12
Input 4
4
-

11
3
-

10
2
-

9
1
-

8
0
-

42605

Registers 0A2D-0A2F:
[Time Stamp]

0A2D+

Day

6 bytes

Month

Year

Serial Seconds

42606+

Day

= 1~31, Day of the month

Month

= 1~12

Year

= 0~99. The century is assumed. (example: 2002 = 02)

Serial Seconds

= Seconds after midnight

Programmed Settings (Read only)


Registers 0A30-0A36:
[FSs]

4 bytes

Full Scale Volts, 2s comp, MSB


Full Scale Current, 2s comp, MSB

[DPs]

4 bytes

Decimal Place Volts, 1byte


Decimal Place Current, 1 byte
Decimal Place Power, 1 byte
Reserved, 1 byte

[FPs]

4 bytes

Face Plate Volts, 0x000 = Volts,0x001-0x0FF = kVolts


Face Plate Currents,0x000 = Amps,0x001-0x0FF

Face Plate Power, 0x000 = kWatts,0x001-0x0FF

kAmps
MWatts
Reserved, 1 byte
[I/A]
readings

1 byte

0x000

= Limits triggered by Instantaneous

0x001-0x0FF= Limits triggered by Average readings.


1 byte

0A30+
0A34+

0
FP Volts

FS Volts
FP Amps
FP watts

Reserved byte

2
Reserved

I/A

FS Amps
Reserved

42609+
24613+

Registers 0A37-0A50:
[Limit 1]

52 bytes

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS

Limit 1 value, 2 bytes, 2s comp, MSB

33

APPENDIX D: MASS MEMORY & NULL TERMINATED HOUR READINGS

0A37+
0A3F+
0A47+
0A4F+

0
VAN
IC
-VAR
Reversal

1
VBN
IN
-PF
Imbalance

2
VCN
W
THD VA

3
VAB
VAR
THD VB

REGISTER MAPPINGS FOR MODBUS PROTOCOL

4
VBC
VA
THD VC

5
VCA
PF
THD IA

6
IA
FQ
THD IB

7
IB
-W
THD IC

42616+
42624+
42632+
42640+

Registers 0A51-0A6A:
[Limit 2]

0A51+
0A59+
0A61+
0A69+

0
VAN
IC
-VAR
Reversal

1
VBN
IN
-PF
Imbalance

52 bytes
2
VCN
W
THD VA

Limit 2 values, 2 bytes, 2s comp, MSB

3
VAB
VAR
THD VB

4
VBC
VA
THD VC

5
VCA
PF
THD IA

6
IA
FQ
THD IB

7
IB
-W
THD IC

42642+
42650+
42658+
42666+

Register 0A6B:
Set Above/Below
A bit value of 0 means the limit is exceeded if the associated value is greater than its Limit.
A bit value of 0 means the limit is exceeded if the associated value is less than its Limit.
[SAB1]

0A6B

15
VAN
7
IC

2 bytes for Limit 1

14
VBN
6
IN

13
VCN
5
W

12
VAB
4
VAR

11
VBC
3
VA

10
VCA
2
PF

9
IA
1
FQ

8
IB
0
-

42668

11
VBC
3
VA

10
VCA
2
PF

9
IA
1
FQ

8
IB
0
-

42669

Register 0A6C:
[SAB2]

0A6C

15
VAN
7
IC

2 bytes for Limit 2

14
VBN
6
IN

13
VCN
5
W

12
VAB
4
VAR

Register 0A6D:
[SAB THD]

0A6D

34

15
THD VA
7
THD VA

14
THD VB
6
THD VB

2 bytes,
13
THD VC
5
THD VC

High byte is Limit 1, Low byte is Limit 2


12
THD IA
4
THD IA

11
THD IB
3
THD IB

10
THD IC
2
THD IC

9
1
-

8
0
-

42670

EPM 5300 SERIES ADVANCED POWER METERS MODBUS REGISTER MAPPINGS