INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS
(With Draw-out Cradle and Type AGR-11 Overcurrent Protective Device)
Types: AR208S
AR212S
AR216S
AR220S
AR325S
AR332S
AR440S
AR212H
AR216H
AR316H
AR220H
AR320H
AR325H
AR332H
KRB-5237e
TABLE OF CONTENTS
1. SAFETY NOTICES
3. GENERAL
10
14
4. OPERATION
18
18
18
19
19
20
22
4-2-1. General
22
23
46
47
50
6-2-1. Preparation
50
53
54
56
57
58
59
62
63
7. TROUBLESHOOTING FLOWCHARTS
65
4-2-3. Putting the breaker body back into the draw-out cradle 24
4-2-4. Contact status of auxiliary and position switches
27
27
28
28
29
29
30
5-1. Specifications
30
31
32
32
35
40
45
KRB-5237e
1. SAFETY NOTICES
Thank you for purchasing the TERASAKI AR-series Air Circuit Breaker (TemPower2).
This chapter contains important safety information.
Be sure to carefully read these safety notices, instruction in this manual, and other documents accompanying the Air Circuit
Breaker (hereinafter referred to as the ACB) to familiarize yourself with safe and correct procedures or practices before installing,
operating, or servicing the ACB.
In this manual, safety notices are divided into DANGER and CAUTION according to the hazard level:
DANGER : A danger notice with this symbol indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION : A caution notice with this symbol indicates a potentially hazardous situation which, if not avoided, may result
in minor or moderate injury and/or property damage.
Note that failure to observe a caution notice could result in serious injury/damage in some situations. Because safety notices
contain important information, be sure to read and observe them.
Transportation Precaution
DANGER
z Never stand under the ACB that has been lifted or suspended by a lifter or lifting attachments. The weight of the ACB may
cause serious injury.
Installation Precautions
CAUTION
z Electrical work must be done by competent persons.
z Do not place the ACB in such an area that is subject to high temperatures, high humidity, dusty air, corrosive gases, strong
vibration and shock, or other unusual conditions. Mounting the ACB in such an area could cause a fire or malfunction.
z Be careful to prevent foreign objects (such as debris, concrete powder, dust, chippings, and iron powder) and oil or
rainwater from entering the ACB. These materials inside the ACB could cause a fire or malfunction.
z Prior to commencing any work on the ACB, open an upstream circuit breaker or the like to isolate all sources of
power/voltage. Otherwise, electric shock may result.
z Fix the draw-out cradle of the ACB firmly on a flat, level surface using mounting screws. Otherwise, the draw-out
operation may cause the breaker body or the draw-out cradle to fall, resulting in damage to the ACB or personal injury.
z Take care not to deform or bend protrusions in the bottom face of the draw-out cradle when fixing the draw-out cradle with
mounting screws. Deformation of the protrusions may cause a malfunction.
z When terminating conductors to the ACB, tighten terminal screws to the torque specified in this manual. Otherwise, a fire
could result.
z For 4-pole ACBs, be sure to connect a 3-phase, 4-wire neutral conductor to the N-phase pole (on the right end). Otherwise,
an overcurrent may hinder the ACB from tripping, resulting in a fire.
Operation Precautions
DANGER
z Never touch live terminal parts. Doing so will result in electric shock.
z Do not leave the ACB body in the draw-out position. If the ACB body is accidentally dropped, its weight may cause
serious injury.
CAUTION
z Do not force down the charging handle after completion of manual charging operation. Doing so may cause a malfunction.
z The permissible operating voltage of the spring charging motor is 85 to 110% of the rated ac voltage or 75 to 110% of the
rated dc voltage. Be sure to supply a voltage within the above ranges to the motor. Otherwise, a malfunction, burnout, or fire
may result.
KRB-5237e
continuous open/close operation is inevitable, a pause of at least 20 minutes should be provided after the repetitions of 15
times. Otherwise, a spring charging motor may be burnt out.
Do not bring your hand or face close to arc gas vent of the arc chamber while the ACB is closed. Otherwise, a burn may
result from high-temperature arc gas blowing out of the arc gas vent when the ACB trips open.
If the ACB trips open automatically, remove the cause of tripping operation before re-closing the ACB. Otherwise, a fire
could result.
If the ACB has the breaker fixing bolts, be sure to loose the fixing bolts before draw-out operation. Otherwise, damage to
the ACB may result.
Make sure the draw-out cradle is secured with mounting screws before inserting or drawing out the breaker body.
Otherwise, the insertion or draw-out operation may cause the breaker body or the draw-out cradle to fall, resulting in
damage to the ACB or personal injury.
When retracting the draw-out rail into the draw-out cradle, be sure to push the rail end. Do not hold the hook pin, body
stopper, or body stopper shaft. Doing so may cause your fingers to be pinched, resulting in injury.
Do not forcedly turn the draw-out handle clockwise when the breaker body is in the CONN. position. Doing so may
cause a malfunction.
If the ACB has the breaker fixing bolts, make sure the bolts on both sides are securely tightened before using the ACB.
Loosened fixing bolts may cause a malfunction of the ACB, in particular when it is installed in such an area that is subject
to strong vibrations.
z After completion of OCR tests, be sure to return the setting switches to the original positions. Failure to do so may cause a
fire or burnout.
z Prior to commencing any work on the ACB, open an upstream circuit breaker or the like to isolate all sources of
power/voltage from the main and control circuits. Otherwise, electric shock may result.
z Take care to avoid adhesion of dust to main and control circuit contacts. Dust on the contacts may result in a fire.
z Prior to commencing maintenance, inspection, or parts replacement, make sure that the closing springs are released and the
z
z
z
z
z
ACB is open. Otherwise, unintentional open/close operation may lead to fingers or tools to be pinched by the open/close
mechanism, resulting in injury.
Retighten the terminal screws periodically to the specified torque. Otherwise, a fire could result.
When grinding a contact tip, be careful to prevent grinding dust from entering the breaker operating mechanism. Wipe the
tip clean after grinding. Otherwise, a malfunction or fire could result.
Do not perform dielectric withstand tests under other conditions than specified. Doing so may cause a malfunction.
Be sure to reinstall the arc chamber if removed. Failure to do so or incorrect installation of the arc chamber may result in a
fire or burn.
When charging the closing springs or performing open/close operation of the ACB with the arc chamber, front cover and/or
side covers removed during maintenance or inspection work, do not touch parts other than those required for the above
operation (charging handle, ON/OFF buttons, moving core and the like). Doing so may cause fingers or tools to be pinched,
resulting in injury.
When replacing an auxiliary, do not damage the control wire for the auxiliary or pinch the wire between the auxiliary and
the breaker body. Doing so may cause a malfunction.
KRB-5237e
z Check that the ACB received is as ordered and that the accessories are as specified.
z Check that the ACB is not damaged during shipment.
DANGER
z Never stand under the ACB that has been lifted or suspended by a lifter or lifting attachments. If the ACB body is
accidentally dropped, its weight may cause serious injury.
z When lifting the ACB, hold it using lifting attachments or wire ropes through the lifting holes. Take care that the position
switches, control circuit terminals, auxiliary switches, arc gas barrier and control terminal block cover which are shown in
figure 1 are not damaged by the lifting rope. Lift the ACB carefully and gently. For transportation, place the ACB on a pallet
and carry slowly and carefully.
z When transporting the ACB while it is installed in a switchboard, you should fix the breaker body in the draw-out cradle with
the breaker fixing bolts (optional).
Position switches
Control circuit terminals
Auxiliary switches
Lifting attachment
Control terminal block cover
Lifting hole (20mm)
Breaker body
Front view
Rear view
KRB-5237e
Lifting plate
Control circuit
contact
Front cover
Front view
Rear view
Position switches
Control circuit terminals
Auxiliary switches
Lifting attachment
Control terminal block cover
Lifting hole (20mm)
Arc gas barrier
Draw-out arm
Front view
Rear view
z Store the ACB in a dry indoor location to prevent condensation due to sudden changes in ambient temperature. Condensation
has a harmful effect on the ACB insulation.
z Store the ACB in a clean place free of corrosive gases and dust. In particular, exposure to a mixture of moisture and cement
dust may cause corrosion damage to metal parts of the ACB.
z Place the ACB on a flat, level surface in its normal position (Do not lay the ACB).
z Do not place the ACB directly on the floor. Do not stack the ACBs during storage.
KRB-5237e
CAUTION
z Electrical work must be done by competent persons.
z Do not place the ACB in such an area that is subject to high temperatures, high humidity, dusty air, corrosive gases, strong
vibration and shock, or other unusual conditions. Mounting the ACB in such an area could cause a fire or malfunction.
z Be careful to prevent foreign objects (such as debris, concrete powder, dust, chippings, and iron powder) and oil or
rainwater from entering the ACB. These materials inside the ACB could cause a fire or malfunction.
z Prior to commencing any work on the ACB, open an upstream circuit breaker or the like to isolate all sources of
power/voltage. Otherwise, electric shock may result.
z Fix the draw-out cradle of the ACB firmly on a flat, level surface using mounting screws. Otherwise, the draw-out
operation may cause the breaker body or the draw-out cradle to fall, resulting in damage to the ACB or personal injury.
Take care not to deform or bend protrusions in the bottom face of the draw-out cradle when fixing the draw-out cradle with
mounting screws. Deformation of the protrusions may cause a malfunction.
z When terminating conductors to the ACB, tighten terminal screws to the torque specified in this manual. Otherwise, a fire
could result.
z For 4-pole ACBs, be sure to connect a 3-phase, 4-wire neutral conductor to the N-phase pole (on the right end). Otherwise,
an overcurrent may hinder the ACB from tripping, resulting in a fire.
Protrusion
Draw-out cradle
mounting screw hole
z Do not install the ACB in such an area that is exposed to direct sunlight.
z Make sure that the mounting base has a sufficient capacity of bearing the weight of the ACB (see Table 3 on page 7). The
mounting base must be protected against vibration. Take appropriate measures to provide a perfect protection to the mounting
base against resonance. Otherwise, open/close operation of the ACB may cause a malfunction of other devices in the
switchboard or vibrations of the switchboard may cause a malfunction of the ACB.
z Use the following screws with appropriate length for the main circuit terminals.
Main circuit terminal screws: Hex head M10, with flat washers (2), spring washer (1) and nut (1) per screw
Tightening torque: 22.5 - 37.2 Nm
Table 1 Number of main circuit terminal screws required
ACB type
AR220S,
AR212H, AR216H, AR220H
AR325S, AR332S
AR316H, AR320H, AR325H, AR332H
AR440S
18/24
24/32
48/64
18/24
12/16
z Use the following screw for the ground terminal. The screw must have a length that allows it to be inserted 4 - 9 mm into the
ground terminal M8 tapped hole.
Ground terminal screw: M8 (1) with spring washer and flat washer
Tightening torque: 11.8 - 14.7 Nm
KRB-5237e
z Use the receptacles shown in Table 2 to make connections with plug-in tab terminals (#187) of position switches, control
circuit terminals, and auxiliary switches.
Table 2 Receptacles for #187 tab terminals
AWG
Recommended terminals
Wire thickness (mm2)
0.75 - 1.25
18 - 16
TMEDN480509-FA
2
14
TMEDN480520-FA
Manufacturer
NH-32
NICHIFU
z The following procedure makes it easy to make connections with plug-in tab terminals (#187) of position switches, control
circuit terminals, and auxiliary switches.
(1) Draw out the breaker body to the removed position, and remove it using an optional lifter or lifting plate. Refer to
sections 4-2-2 and 2-1-2.
(2) If the ACB is equipped with the control terminal block cover, loosen both the cover fixing screws and remove the cover.
(3) Remove the terminal block fixing screws shown in Fig. 5.
Auxiliary switches
z If any work is done near the ACB that have been installed, protect the openings of the ACB with appropriate covers to prevent
spatters, metal chips, wire cuttings or other foreign objects from entering the ACB.
KRB-5237e
3. GENERAL
3-1. Types and Descriptions
TemPower2 is available in types shown in Tables 3 and 4.
Table 3 Standard types
Frame size (A)
Type
Max. rated current [In] (A)
*1, *2
IEC, EN, AS
JIS
Marine use
800
AR208S
1250
AR212S
1600
AR216S
2000
AR220S
2500
AR325S
3200
AR332S
800
1250
1600
2000
2500
3200
1250
3
1000
690
Control power
Operation power
1600
3
1000
690
2000
3
1000
690
2500
3
1000
690
3200
3
1000
690
4000
AR440S
4000
3700
4000
4000
3
4
1000
690
50/105
65/143 *11
50/105
65/143
85/187 *11
65/143
75/165
100/220
75/165
65/143
85/195.5
100/230
50/115
65/153 *11
65/153
85/201 *11
75/179
100/245
40/40
65
65
30000
15000
30000
15000
25000
12000
20000
10000
20000
10000
100
100
15000
8000
12000
12000
10000
7000
7000
3000
10000
10000
7000
5000
5000
2500
86
85
85
76
90
79
94
105
125
105
125
139
176
360
445
360
445
360
445
360
445
466
586
466
586
460
290
75
354
439
354
439
354
439
354
439
460
580
460
580
631
801
460
460
345
375
40
53
Vertical, horizontal or front terminals
Vertical terminals
Vertical, horizontal or front terminals
Vertical terminals
#187 tab terminals or screw terminals
Manual or motor charging
No OCR, L-characteristic for general feeder, R-characteristic for general feeder, or S-characteristic for generator protection
Group indication or individual indication; automatically selected according to OCR type
Standard equipment for OCR-equipped ACB
Optional
Optional
4C (standard), 7C or 10C; available for general feeder or microload
#187 tab terminals (standard) or screw terminals
AC100 - 120V
DC100 - 125V
DC24V shared
shared or
shared or
AC200-240V
DC200 - 250V
DC48V
Power consumption: 5 VA
Permissible voltage range: 85 - 110% (AC) or 75 - 110% (DC) of ratings
AC100 - 120V, AC200 - 240V, DC100 - 125V, DC200 - 250V, DC24V or DC48V
KRB-5237e
IEC, EN, AS
JIS
Marine use
1250
AR212H
1600
AR216H
2000
AR220H
1600
AR316H
2000
AR320H
2500
AR325H
3200
AR332H
1250
1600
2000
1600
2000
2500
3200
1600
3
1000
690
Control power
Operation power
2000
3
1000
690
1600
3
1000
690
2000
3
1000
690
2500
3
1000
690
55/121
80/176
55/121
85/187
100/220
85/196
80/176
100/230
55/128
80/186
85/201
100/233
3200
3
1000
690
40/40
80
65
30000
15000
100
85
25000
12000
30000
15000
25000
12000
20000
10000
20000
10000
12000
10000
12000
10000
7000
7000
10000
7000
10000
7000
5000
5000
94
79
94
105
125
105
125
105
125
105
125
360
445
360
445
360
445
466
586
466
586
466
586
466
586
460
290
75
354
439
354
439
354
439
460
580
460
580
460
580
460
580
460
345
40
Vertical terminals (Horizontal terminals can be specified as an option)
Vertical terminals (Horizontal terminals can be specified as an option)
#187 tab terminals or screw terminals
Manual or motor charging
No OCR, L-characteristic for general feeder, R-characteristic for general feeder, or S-characteristic for generator protection
Group indication or individual indication; automatically selected according to OCR type
Standard equipment for OCR-equipped ACB
Optional
Optional
4C (standard), 7C or 10C; available for general feeder or microload
#187 tab terminals (standard) or screw terminals
AC100 - 120V
DC100 - 125V
DC24V shared
shared or
shared or
AC200-240V
DC200 - 250V
DC48V
Power consumption: 5 VA
Permissible voltage range: 85 - 110% (AC) or 75 - 110% (DC) of ratings
AC100 - 120V, AC200 - 240V, DC100 - 125V, DC200 - 250V, DC24V or DC48V
Altitude
Ambient
temperature
Humidity
Vibration
Shock
Atmosphere
KRB-5237e
2000 m max.
-5C to +45C
45 to 85% rel. max.
0.7G max.
200 m/s2 (20G) max.
No excessive water vapor, oil vapor, dust, or corrosive gases. No sudden change in temperature and no condensation.
Ammonia (NH3): 0.5 ppm max, Hydrogen sulfide (H2S)/sulfur dioxide (SO2)/hydrogen chloride (HCl): 0.1 ppm max.,
Chlorine (Cl2): 0.05 ppm max.
Different from standard ACBs in that Ambient temperature: 60C max. and Humidity: 95% rel. max. (no condensation)
Different from standard ACBs in that Ambient temperature: -25C min. for use and -40C min. for storage (no condensation)
Different from standard ACBs in that NH3: 50 ppm max, H2S: 10 ppm max., SO2/HCl: 5 ppm max., and Cl2 : 1 ppm max.
Table 6 shows the dielectric withstand voltage and the insulation resistance of the ACBs.
CAUTION
z Do not perform dielectric withstand/insulation resistance tests under other conditions than specified. Doing so may cause a
malfunction.
Table 6 Dielectric withstand voltage and insulation resistance
AC3500V
AC2500V
AC2000V
AC2000V
AC2000V
1 minute
1 minute
1 minute
1 minute
1 minute
12kV
6kV
4kV
4kV
4kV
Insulation
resistance
(DC500V Megger
used)
300M
100M
100M
100M
100M
AC2500V
1 minute
6kV
100M
AC2000V
1 minute
4kV
100M
Circuit
Impulse
withstand voltage
Uimp
Main circuit
For general feeder
Auxiliary
switches
For microload
Control
Position switches
circuit
Overcurrent release
Undervoltage trip device,
Reverse power trip device
Other accessories
The above data applies to new ACBs. Device terminals within ACBs are not covered. Use a DC500V Megger to measure the insulation resistance.
Table 7 shows the internal resistance and power consumption of the ACBs.
Table 7 Internal resistance and power consumption
Type
Frame size (A)
DC internal resistance (m) (for 1-pole ACB)
AC power consumption (W) (for 3-pole ACB)
AR208S
800
0.030
170
AR212S
1250
0.030
310
AR216S
1600
0.028
350
AR220S
2000
0.024
490
AR325S
2500
0.014
600
AR332S
3200
0.014
780
AR440S
4000
0.014
1060
Type
Frame size (A)
DC internal resistance (m) (for 1-pole ACB)
AC power consumption (W) (for 3-pole ACB)
AR212H
1250
0.024
260
AR216H
1600
0.024
350
AR220H
2000
0.024
490
AR316H
1600
0.014
310
AR320H
2000
0.014
430
AR325H
2500
0.014
600
AR332H
3200
0.014
780
Table 8 shows applicable current of the ACBs. The applicable current varies depending on the ambient temperatures.
Table 8 Dependence of applicable current on ambient temperature
Type
AR208S
AR212S
AR216S
AR220S
AR325S
AR332S
AR440S
2 50 5t
2 80 5t
2 100 5t
3 100 5t
2 100 10t
3 100 10t
4 150 6t
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
1250
1250
1250
1250
1250
1250
1240
1180
1110
1040
1250
1250
1250
1250
1230
1250
1220
1160
1110
1050
1600
1600
1600
1600
1460
1540
1470
1390
1310
1230
1600
1600
1540
1460
1390
1460
1400
1340
1280
1220
2000
2000
2000
1820
1740
2000
1960
1860
1750
1640
2000
1900
1820
1740
1650
1740
1680
1600
1530
1450
2500
2500
2500
2500
2400
2500
2500
2440
2300
2150
2500
2470
2400
2310
2230
2370
2280
2180
2080
1970
3200
3200
3200
2990
2850
3200
3010
2860
2690
2520
3200
2900
2800
2710
2610
2610
2510
2400
2290
2170
4000
4000
4000
4000
3760
3700
3580
3470
3350
3150
3700
3580
3470
3350
3230
3230
3100
2970
2830
2690
AR212H
AR216H
AR220H
AR316H
AR320H
AR325H
AR332H
2 80 5t
2 100 5t
3 100 5t
2 100 5t
3 100 5t
2 100 10t
3 100 10t
1250
1250
1250
1250
1250
*
*
*
*
*
1250
1250
1250
1250
1250
*
*
*
*
*
1600
1600
1600
1600
1550
1600
1560
1480
1390
1300
1600
1600
1600
1550
1480
1500
1440
1380
1310
1250
2000
2000
2000
1820
1740
2000
1960
1860
1750
1640
2000
1900
1820
1740
1650
1740
1680
1600
1530
1450
1600
1600
1600
1600
1600
*
*
*
*
*
1600
1600
1600
1600
1600
*
*
*
*
*
2000
2000
2000
2000
2000
*
*
*
*
*
2000
2000
2000
2000
1900
*
*
*
*
*
2500
2500
2500
2500
2400
2500
2500
2440
2300
2150
2500
2500
2500
2400
2280
2370
2280
2180
2080
1970
3200
3200
3130
2990
2850
3200
3010
2860
2690
2520
3200
2900
2800
2710
2610
2610
2510
2400
2290
2170
Conductor size
Standard
IEC60947-2
EN60947-2
AS3947-2
JIS C8201-2
NEMA,SG-3
ANSI C37.13
JIS C8372
JEC-160
Ambient
temperature (C)
40 (standard ambient temperature)
45
50
55
60
40 (standard ambient temperature)
45
50
55
60
40 (standard ambient temperature)
45
50
55
60
40 (standard ambient temperature)
45
50
55
60
Type
Conductor size
Standard
IEC60947-2
EN60947-2
AS3947-2
JIS C8201-2
NEMA,SG-3
ANSI C37.13
JIS C8372
JEC-160
Ambient
temperature (C)
40 (standard ambient temperature)
45
50
55
60
40 (standard ambient temperature)
45
50
55
60
40 (standard ambient temperature)
45
50
55
60
40 (standard ambient temperature)
45
50
55
60
Notes: For AR208S, AR212S and AR216S, it is assumed that main circuit terminals are of horizontal type at both the line and load sides. For other types, it is assumed that
main circuit terminals are of vertical type at both the line and load sides. The above values may vary depending on the switchboard configuration.
*: Contact us
KRB-5237e
6 ON-OFF indicator
19
Front cover
7 Charge indicator
16
ON-OFF cycle counter
4
OFF button
15
ON-OFF button cover
14
Lock-in-OFF plate
8 Charging handle
5 ON button
18
Overcurrent release (OCR)
17
OCR cover
20 Rating nameplate
9 Position indicator
13
Position padlock lever
51 Draw-out handle
12
Release button
11
Draw-out handle insertion hole
1 ACB
37
Position switches
38
Control circuit terminal
25
Control circuit contact
41 Auxiliary switches
42 Terminal block
24
Main circuit contact
34 Body stopper
30
Breaker fixing bolt (red)
33 Hook pin
31
Draw-out rail
36 Rail stopper
32
Draw-out rail end
50
Protrusion
22
Specification nameplate
25 Control circuit
contact
26
Arc chamber
28 Mold cover
46
Arc gas barrier
45
Gas exhaust port
27
Current sensor
48
Main circuit terminal
Main circuit
24
contact
29 Mold base
22 Specification
nameplate
10 Grip
47
Breaker draw-out arm
Ground terminal
44
M8 tapped hole
23 Breaker body
roller
21 Carry-out roller
KRB-5237e
10
1 ACB
2 Draw-out cradle
37 .
switches
3
19 .
Breaker body Contains the ON-OFF mechanism, the closing coilthe tripping device, and overcurrent release
4 OFF button
6 ON-OFF indicator Shows OFF when the ACB is open and ON when it is closed.
7 Charge indicator Shows CHARGED when the closing springs are charged and DISCHARGED when it is released.
9 Position indicator Indicates the present breaker body position: CONN., TEST, or ISOLATED.
11 Draw-out handle insertion hole Insert the draw-out handle into this hole to move the breaker body.
12 Release button
13 Position padlock lever (optional) Accommodates up to three padlocks to lock the breaker body in the CONN., TEST or
ISOLATED position. (Padlocks are not supplied. Use padlocks with a 6 mm-diameter shackle.)
14
Lock-in-OFF plate
Padlocking this plate allows the ACB to be locked in the open (OFF) state. (Padlocks are not supplied.
supplied. Use padlocks with a 6 mm-diameter shackle.) Up to three padlocks can be installed.
16
ON-OFF cycle counter (optional) Reads the number of ON-OFF cycles. It counts a series of operations from close to
open as one cycle.
This protective device is supplied power via the power CT installed in the ACB main circuit.
When the current sensor detects an overcurrent in the main circuit, the OCR instructs the magnet hold trigger (MHT) to trip
open the ACB.
19 Front cover A plastic cover of the breaker body front panel.
20 Rating nameplate Indicates the type, applicable standards and rated breaking capacity of the ACB.
22 Specification nameplate Indicates the number of poles, operation method, accessories, and serial number of the ACB.
24 Main circuit contact Closes when the breaker body is in the CONN. position.
25 Control circuit contact Closes when the breaker body is in the CONN. or TEST position.
26 Arc chamber Extinguishes the arc that occurs in the breaking operation.
27 Current sensor Converts the current in the main circuit into a voltage signal in proportion to the magnitude of the current
18 .
and sends the signal to overcurrent release
28 Mold cover A plastic cover of the breaker body side face.
Allows the breaker body to be locked in the CONN. position even if the ACB is
34 Body stopper Prevents the breaker body from falling when the body is drawn out from the draw-out cradle.
36 Rail stopper (red) Allows the draw-out rail to be locked in the drawn-out or retracted state.
11
KRB-5237e
37 Position switches (optional) Indicate the present breaker body position: CONN., TEST, ISOLATED or INSERTED. The
position switches are available in 2C or 4C configuration. Connections to the position switches are made through #187 plugin tab terminals (standard) or M4 screws.
38
Allow connections of external control wire to the control circuits. Wire connections are made
through #187 plug-in tab terminals (standard) or M4 screw terminals. Fig. 8 shows the #187 tab terminals and M4 screws
terminals.
M4 screw terminals
Fig. 8 Control circuit terminals
Protects the position switches, the control circuit terminals and the auxiliary
Indicate the state of the ACB (ON or OFF). The auxiliary switches are available in 4C
configuration (standard), or 7C or 10C configuration (optional). Connections to the switches are made through #187 plug-in
tab terminals (standard) or M4 screw terminals.
42 Terminal block Contains position switches
36 , control circuit terminals
37 , and auxiliary switches
38 .
45 Gas exhaust port Allows the arc gas to be discharged from arc chamber
25 in a horizontal direction when the ACB trips
open.
46
47 Breaker draw-out arm Is retracted in the draw-out cradle when the breaker body is in the CONN. position.
Allow connections of external conductors. These terminals are available in three configurations as
shown in Fig. 9.
Vertical terminals
Horizontal terminals
Front terminals
Allows lifting attachments or wire ropes to be used for lifting the ACB.
51 Draw-out handle (removable) Use to draw out /insert the breaker body from/into the draw-out cradle.
KRB-5237e
12
+ and
mean the polarity for DC)
Table 9 Terminal functions and circuit symbols (Applicable to both 50 and 60Hz for AC.
Terminal No.
01 ,
11
11
+ ,
21
01
+ ,
21
02
+ ,
22
03 ,
12
05 ,
15
05 ,
25
05 ,
06
05 ,
16
05 ,
26
05 ,
17
05 ,
27
10 ,
20
Function
AC100 - 120V
DC100 - 125V or DC24V
AC200 - 240V, DC200 - 250V or DC48V
AC100 - 120V, AC200 - 240V, DC100 - 125V, DC200 - 250V, DC24V or DC48V
ON switch
Group indication or long time delay (LT) operation indication
Short time delay (ST) and instantaneous trip (INST/MCR) operation indication
One-step pretrip alarm (PTA) indication
Ground fault trip (GF) indication
System alarm indication
Trip indication
Spring charged indication
AC100V, AC110V, AC120V, AC200V, AC220V, AC240V,
DC24V, DC48V, DC100V, DC110V, DC125V, DC200V or DC220V
Terminal No.
08 ,
09 ,
18 ,
28
08 ,
09
18 ,
09
28 ,
09
24 ,
30
OFF switch
19 ,
29
19
Polarity:
04 ,
07 ,
13 ,
14 ,
23
Symbol
M
LRC
MHT
SHT
UVT
S1 - S4
AC100V coil
100V
110V
120V
AC200V coil
200V
220V
240V
AC400V coil
380V
415V
440V
29
Meaning
Spring charging motor
Latch release coil
Magnet hold trigger
Shunt trip device
Fixed type undervoltage trip device
Current sensors *6
Symbol
CT1 - CT3
13
KRB-5237e
111
3rd character: Type of contact
Tables 10 - 15 show the ratings of the operation power supply, the shunt trip device (SHT), the fixed type undervoltage trip
device (UVT), auxiliary switches, position switches, operation indication contacts, and the N-phase CT.
Table 10 Ratings of operation power supply
Rated
voltage
(V)
AC100
AC110
AC120
AC200
AC220
AC240
DC24
DC48
DC100
DC110
DC125
DC200
DC220
Permissible
charging/closing
voltage range
85 - 110
94 - 121
102 - 132
170 - 220
187 - 242
204 - 264
20 - 26
41 - 53
85 - 110
94 - 121
106 - 138
170 - 220
187 - 242
Permissible voltage
range (V)
70 - 110
77 - 121
84 - 132
140 - 220
154 - 242
168 - 264
16.8 - 26.4
33.6 - 5.28
70 - 110
77 - 121
87.5 - 137.5
140 - 220
154 - 242
Steady-state current
(A)
0.32
0.26
0.24
0.16
0.13
0.12
1.1
0.57
0.26
0.25
0.21
0.13
0.12
KRB-5237e
14
280 - 350
330 - 420
450 - 560
1120 - 1380
1400 - 1730
1800 - 2210
15 - 19
63 - 78
280 - 350
330 - 420
450 - 560
1120 - 1380
1400 - 1730
40
Opening voltage
range (V)
35 - 70
38.5 - 77
42 - 84
70 - 140
77 - 154
84 - 168
133 - 266
145 - 290
154 - 308
Attraction voltage
(V)
85
93.5
102
170
187
204
323
352
374
Coil exciting
current (A)
0.3
30
50
330 - 420
Voltage (V)
AC100 - 250
AC251 - 500
DC8
DC30
DC125
DC250
DC125 - 250
Position switches
Resistive load
(A)
11
10
6
0.6
0.3
-
Inductive load
(A) *2
6
6
5
0.6
0.3
-
Group indication
Voltage (V)
8
5
0.5
0.3
Type of N-phase CT
CW80-40LS
EC160-40LS
15
200/5A
1250/5A
1600/5A
3200/5A
Ratings (A)
400/5A
1600/5A
2000/5A
4000/5A
800/5A
2500/5A
KRB-5237e
4. OPERATION
4-1. Charging and Opening operation
DANGER
z Never touch live terminal parts. Otherwise, electric shock may result.
CAUTION
z Do not force down the charging handle after completion of manual charging operation. Doing so may cause a malfunction.
z The permissible operating voltage of the spring charging motor is 85 to 110% of the rated ac voltage or 75 to 110% of the
rated dc voltage. Be sure to supply a voltage within the above ranges to the motor. Otherwise, burnout may result.
z Repeated open/close operation by the motor charging mechanism without pause should not exceed 15 times. If repeated
continuous open/close operation is inevitable, a pause of at least 20 minutes should be provided after the repetitions of 15
times. Otherwise, a spring charging motor may be burnt out.
z Do not bring your hand or face close to arc gas vent of the arc chamber while the ACB is energized. Otherwise, a burn may
result from high-temperature arc gas blowing out of the arc gas vent when the ACB trips open.
z If the ACB trips open automatically, remove the cause of tripping operation before re-closing the ACB. Otherwise, a fire
could result.
z If the ACB has the breaker fixing bolts, make sure the bolts on both sides are securely tightened before using the ACB.
Loosened fixing bolts may cause a malfunction of the ACB, in particular when it is installed in such an area that is subject
to strong vibrations.
The ACBs are available in two types in terms of the closing spring charging method and the remote operation capability: a
manual charging type and a motor charging type. The manual charging type requires the charging and ON-OFF (close/open)
operation to be done manually while the motor charging type allows the operation to be done either manually or by using a motor.
z Manual charging
2 ) until the charge indicator (Fig. 13
1 ) shows CHARGED Pumping the handle with
Pump the charging handle (Fig. 13
the full stroke 10 - 13 times will fully charge the closing springs.
1 Charge indicator
10
ON-OFF indicator
6
OFF button
7
Lock-in-OFF plate
8
ON-OFF button cover
9 ON button
2 Charging handle
3
Position indicator
KRB-5237e
16
z Motor charging
1 ) changes to DISCHARGED while the specified operation voltage is applied to the
When the charge indicator (Fig. 13
02 and
22 , the charging motor is activated to start charging the closing springs. Upon completion of
control circuit terminals
the charging operation, the charge indicator shows CHARGED and the charging motor is automatically deactivated. The
time required for the motor charging operation depends on the operation voltage or the ACB types, but does not exceed 10
seconds.
z Manual closing
8 ) and press the ON button (Fig.13
9 ). The ACB will be closed with a sound. The
Open the ON-OFF button cover (Fig.13
10 ) shows "ON" and the charge indicator (Fig. 13
1 ) shows "DISCHARGED".
ON-OFF indicator (Fig. 13
z Electrical closing
Press the ON switch shown in Fig. 10. The latch release coil (LRC) (Fig. 10) will be excited and the ACB is closed with a
10 ) shows "ON", the charge indicator (Fig. 13
1 ) shows "DISCHARGED", and the
sound. The ON-OFF indicator (Fig. 13
z Electrical opening
Press the OFF switch shown in Fig. 10. The shunt trip device (SHT) or the fixed type undervoltage trip device (Fig. 10) will
10 ) shows "OFF".
be excited so that the ACB trips open with a sound. The ON-OFF indicator (Fig.13
17
KRB-5237e
1 rotates
For manual closing operation, ON button
counterclockwise. For electrical closing operation, push
1 ' protrudes downward from the latch release coil
rod
2 rotates clockwise. This
(LRC) and charge latch trigger
3 clockwise and closing
rotates closing trigger shaft
4 disengages from a semicircular pawl and
release lever
5
rotates
rotates clockwise. And charging cam
7 disengages
counterclockwise, so that charging lever
6 and rotates counterclockwise.
from closing spring
8 is pushed up by charging lever
7 and
Closing cam
rotates clockwise. At this time, each component is
positioned as shown in Fig. 16. Continued to Fig. 15.
1 '
13
12
10
11
13
KRB-5237e
18
1 "
1 rotates
For manual opening operation, OFF button
2 rotates clockwise.
counterclockwise and trip linkage
1 protrudes
For electrical opening operation, push rod
downward from the shunt trip device (SHT) or the fixed
type undervoltage trip device (UVT). For tripping
operation by the overcurrent release (OCR), moving core
1 protrudes downward from the magnet hold trigger
2
rotates counterclockwise.
(MHT) and trip linkage
(Parts marked with an asterisk (*) are trip pins. To avoid
superposition in the figure, magnet hold trigger related
parts are drawn in positions that are different from actual
3
2 "
*
1 '
12
10
11
12
10
19
KRB-5237e
1. CONN. position
4. Removed position
Position indicator
Position indicator
Draw-out cradle
Control circuit
contact
Breaker body
Control circuit
contact
Rollers
Draw-out rail
Insert
Insert
2. TEST position
Draw-out
3. ISOLATED position
Position indicator
Position indicator
Insert
Drawout
KRB-5237e
20
DANGER
z Never touch live terminal parts. Otherwise, electric shock may result.
z Do not leave the ACB body in the removed position. The weight of the ACB may cause serious injury.
CAUTION
z If the ACB has the breaker fixing bolts, be sure to loosen the bolts on both sides before draw-out operation. Otherwise,
damage to the ACB may result.
z Make sure the draw-out cradle is secured with mounting screws before drawing out the breaker body. Otherwise, the drawout operation may cause the breaker body or the draw-out cradle to fall, resulting in damage to the ACB or personal injury.
z When retracting the draw-out rail into the draw-out cradle, be sure to push the rail end. Do not hold the hook pin, body
stopper, or body stopper shaft. Doing so may cause your fingers to be pinched, resulting in injury.
Use the separate draw-out handle to draw-out the breaker body.
4-2-2-1. Moving the breaker body from the CONN. position to the TEST position
1 ) cannot be inserted).
1) Open the ACB. (If the ACB remains closed, the draw-out handle (Fig. 19
2 ), if used, to unlock the breaker body (Fig. 19
3 ).
2) Loosen the breaker fixing bolts (Fig. 19
14 ) if locked. See section 4-5.
3) Unlock the position lock lever (Fig. 19
4 ) and slowly turn counterclockwise until the
4) Insert the draw-out handle into the draw-out handle insertion hole (Fig. 19
5 ) shows TEST.
position indicator (Fig. 19
z When the main circuit is disconnected at the disconnect contacts, the breaker body will be slightly pushed forward by the
spring action of the main circuit disconnect contacts. At this moment, a bang sound will be heard. This sound does not
mean a malfunction.
z The ACB cannot be closed as long as the draw-out handle is in the draw-out handle insertion hole. To close the ACB e.g.,
for ON-OFF testing, remove the draw-out handle.
7 Draw-out cradle
3 Breaker body
13
ON-OFF indicator
2 Breaker fixing bolt
10 Grip
14
Position lock lever
4 Draw-out handle insertion hole
1 Draw-out handle
5
Position indicator
6
Release button
11
Auto-discharging device
Body stopper
9 Draw-out rail
Hook pin
Body stopper shaft
17
Draw-out rail end
8 Rail stopper
Draw-out direction
21
KRB-5237e
4-2-2-2. Moving the breaker body from the TEST position to the ISOLATED position
1 ) cannot be inserted).
1) Open the ACB. (If the ACB remains closed, the draw-out handle (Fig. 19
6 ). The release button will be locked depressed.
2) Press the release button (Fig. 19
14 ) if locked. See section 4-5.
3) Unlock the position lock lever (Fig. 19
4 ) and slowly turn counterclockwise until the
4) Insert the draw-out handle into the draw-out handle insertion hole (Fig. 19
5 ) shows ISOLATED and a freewheeling sound is heard. Turning the draw-out handle will
position indicator (Fig. 19
4-2-2-3. Moving the breaker body from the ISOLATED position to the removed position
7 ) is secured with mounting screws.
1) Make sure the draw-out cradle (Fig. 19
14 ) if locked. See section 4-5.
2) Unlock the position lock lever (Fig. 19
8 ) outward on both sides of the draw-out cradle to unlock the draw-out rail (Fig. 19
9 ), and
3) Push the rail stoppers (Fig. 19
then uphold and pull out the rail until it stops. The draw-out rail will be locked again by the stoppers. (The breaker body
cannot be drawn out unless the rail is locked).
10 ), draw out the breaker body until it stops.
4) Holding both the grips (Fig. 19
11 ), the closing springs of the ACB will be
z If the ACB is equipped with an optional auto-discharging device (Fig. 19
automatically discharged with a mechanical sound. This sound does not mean a malfunction.
z Do not leave the ACB body on the draw-out rail pulled out.
3 ) to a safe place. Refer to section 2-1-2.
5) Use an optional lifter or lifting plate to transfer the breaker body (Fig. 19
4-2-3. Putting the breaker body back into the draw-out cradle
DANGER
z Never touch live terminal parts. Otherwise, electric shock may result.
z Do not leave the ACB body in the removed position. The weight of the ACB may cause serious injury.
CAUTION
z Make sure the draw-out cradle is secured with mounting screws before inserting the breaker body into the draw-out cradle.
Otherwise, the insertion operation may cause the breaker body or the draw-out cradle to fall, resulting in damage to the
ACB or personal injury.
z When retracting the draw-out rail into the draw-out cradle, be sure to push the rail end. Do not hold the hook pin, body
stopper, or body stopper shaft. Doing so may cause your fingers to be pinched, resulting in injury.
z Do not forcedly turn the draw-out handle clockwise when the breaker body is in the CONN. Position. Doing so may cause
a malfunction.
z If the ACB has the breaker fixing bolts, make sure the bolts on both sides are securely tightened before using the ACB.
Loosened fixing bolts may cause a malfunction of the ACB, in particular when it is installed in such an area that is subject
to strong vibrations.
Use the separate draw-out handle to insert the breaker body.
then uphold and pull out the rail until it stops. The draw-out rail will be locked again by the stoppers. (The breaker body (Fig.
3 ) cannot be inserted unless the rail is locked).
19
3) Use an optional lifter or lifting plate to place the breaker body rollers (Fig. 20) on the draw-out rail (Fig. 20).
z Do not leave the ACB body on the draw-out rail pulled out.
2 ), make sure the bolts are loosened and, holding both the grips (Fig. 19
10 ),
4) If the ACB has the breaker fixing bolts (Fig. 19
KRB-5237e
22
then push the rail ends to insert the rail until it stops. The draw-out rail will be locked again by the stoppers.
Breaker body
Draw-out cradle
Draw-out rail
4-2-3-2. Moving the breaker body from the ISOLATED position to the TEST position
13 ) shows OFF. (If the ACB remains closed, the draw-out handle (Fig. 19
1 )
1) Make sure the ON-OFF indicator (Fig. 19
cannot be inserted).
14 ) if locked. See section 4-5.
2) Unlock the position lock lever (Fig. 19
4 ) and slowly turn clockwise until the position
3) Insert the draw-out handle into the draw-out handle insertion hole (Fig. 19
5 ) shows TEST.
indicator (Fig. 19
z The ACB cannot be closed as long as the draw-out handle is in the draw-out handle insertion hole. To close the ACB e.g.,
for ON-OFF testing, remove the draw-out handle.
4-2-3-3. Moving the breaker body from the TEST position to the CONN. position
1 ) cannot be inserted).
1) Open the ACB. (If the ACB remains closed, the draw-out handle (Fig. 19
14 ) if locked. See section 4-5.
2) Unlock the position lock lever (Fig. 19
6 ). The release button will be locked depressed.
3) Press the release button (Fig. 19
4 ) and turn clockwise until the position indicator
4) Insert the draw-out handle into the draw-out handle insertion hole (Fig. 19
5 ) shows CONN. and the handle cannot be turned with its max.
(Fig. 19
release button.
z When the main contact starts engaging, the force required to turn the
handle will increase as shown in Fig. 21. This symptom does not mean a
malfunction. Continue to turn the handle. Rotating the handle more 13 or
13 or 14 turns
Operating torque
operating torque (14.7 N-m). Turning the draw-out handle will unlock the
TEST
CONN.
Position
14 turns moves the breaker body to the CONN. position, where the handle
cannot be turned with its max. operating torque.
5) Remove the draw-out handle.
2 ), if used, to lock the breaker body.
6) Tighten the breaker fixing bolts (Fig. 19
23
KRB-5237e
OFF
CONN.
TEST
ISOLATED
Removed
Status of
a-contact
Status of
b-contact
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Status of
a-contact
Status of
b-contact
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ISOLATED
TEST
CONN.
Padlock
ON-OFF button cover locking hole
KRB-5237e
24
OFF button
OFF-lock tab
Padlock
25
KRB-5237e
U-notch
Grip
Fig. 25 Securing the breaker fixing bolts
Padlock
OCR cover
OCR cover padlock hole
KRB-5237e
26
z AGR-11L
z AGR-11R
z AGR-11S
5-1. Specifications
Specifications of the OCR are shown in Table 18 and Fig. 27.
Table 18 Specifications of type AGR-11 OCR (z: Standard, {: Optional, : Not applicable)
Application
Characteristic
Type designation
Suffix (XX or XXX) of type designation *1
Long time delay trip (LT)
Short time delay trip (ST)
Instantaneous trip (INST/MCR)
Protective
Ground fault trip (GF) *2
function
N-phase protection *3
Pretrip alarm (PTA) *3
COLD/HOT (LT) *4
I2t ON/OFF (ST)
Protection
characteristic INST/MCR (INST) *5
I2t ON/OFF (GF)
Group indication LED and
contact output
Individual indication LEDs and
Trip
contact output
indication
Tripped indication
Spring charged indication
Test function
Control power supply
AL
L
AGR-11L-XX
GL
PS
PG
AL_
R
AGR-11R-XXX
GL_
PS_
PG_
For generator
protection
Reference
S
section
AGR-11S-XX
AL
PS
z
z
z
z
{
z
z
z
z
{
z
z
z
z
z
{
z
z
z
z
z
z
z
z
{
z
z
z
{
z
z
z
z
{
z
z
z
z
z
z
z
z
5-3.
5-1.
5-3.
5-1.
5-3.
5-4.
{
{
{
{
{
{
z
{
{
z
{
{
{
{
{
{
z
{
{
z
{
{
{
{
z
5-5.
Not
Not
Not
Not
Not
Required Required
Required Required
Required
required required
required required
required
3-3.
*1: An under bar in the type designatios means a number from 1 to 5 representing a type of the long time delay trip (LT) characteristic as follows:
"1: I0.02t, 2: It, 3: I2t, 4: I3t, 5: I4t.
The type of LT characteristics is factory set according to your order specification. Refer to section 5-3-2.
*2: The OCR is factory equipped with the ground fault indication function only or with both the ground fault trip function and ground fault indication function according
to your order specification. Control power supply is required when the CT rated primary current [ICT] is not more than 800A and the ground fault trip pickup current
setting [IG] is 10% of ICT.
*3: Disabled when control power is lost.
*4: The long time delay trip and N-phase protection functions can be set
1 COLD mode
trips open the ACB in shorter time than in COLD mode when an
state, the operating time is approx. 80% of
overload occurs. The HOT mode will be suitable for protection of
the time required in COLD mode.
heat sensitive loads. The OCR is factory se to COLD mode. A
3 HOT mode: When an overload occurs in a 75%-load
*5: When INST is enabled, the OCR trips open the ACB when the trip
state, the operating time is approx. 20% of
pickup current is reached or exceeded, irrespective of the ACB
the time required in COLD mode.
status. When MCR is enabled, the OCR trips open the ACB when
the ACB making current setting is reached or exceeded, and after
tripping operation, it locks the ACB in the open state. When using
Fig. 27 COLD and HOT mode
the MCR function, control power supply is required. MCR provides
the INST function if the control power is lost.
27
KRB-5237e
CAUTION
z OCR setting changes must be performed by competent persons.
z Use a small flatblade screwdriver with a torque of not more than 0.1 Nm or a force of not more than 0.1 N when adjusting
the setting switches (rotary step switches or slide switches). An excessive torque or force may cause a malfunction.
The following describes how to set the OCR.
1) Open the ACB.
2) If the OCR is fed by the control power supply, isolate the OCR from the power supply by e.g., moving the breaker body to
the ISOLATED position.
3) Push the right end of the OCR cover to the left at the hollow on the front cover to unlatch and open the OCR cover. See Fig.
28. If the OCR cover is padlocked, first remove the padlock.
OCR cover
Hollow
Front cover
Rotary step switches must be adjusted with a small flatblade screwdriver. Turn switch knobs stepwise and do not
stop the knobs halfway between calibration markings.
Slide switches must also be adjusted with a small flatblade screwdriver. Do not stop switch knobs halfway.
IR:
Dial
0.95
0.9
1.0
Rotary switch
knob
Slide switch
knob
Bold line
(same setting
in this range)
0.85
0.8
XIn
Rotary step switch
Slide switch
KRB-5237e
28
8 ,
10 ,
13
11
12
14
15
Setting item
Symbol
Rated current*1
In
IR
IN
tR
Isd
tsd
10
11
12
13
14
15
I2t tsd
Ii
Ig
tg
I2t tg
IP1
tP1
Setting range
CT rated primary current [ICT] (0.5-0.63-0.8-1.0) (A)
Applied [ICT] (A)
200
400
800
1250
1600
2000
2500
3200
4000
[ICT] 0.5
100
200
400
630
800
1000
1250
1600
2000
Rated
[ICT] 0.63
125
250
500
800
1000
1250
1600
2000
2500
current
[In]
[ICT] 0.8
160
320
630
1000
1250
1600
2000
2500
3200
(A)
[ICT] 1.0
200
400
800
1250
1600
2000
2500
3200
4000
[In] (0.8-0.85-0.9-0.95-1.0-NON) (A)
Non tripping at not more than [IR] x 1.05, Tripping at more than [IR 1.05 and not more than [IR] 1.2
[ICT] (0.4-0.5-0.63-0.8-1.0): Fixed to a single point
Non tripping at not more than [IN] 1.05, Tripping at more than [IN] x 1.05 and not more than [IR] 1.2
Long time delay: (0.5-1.25-2.5-5-10-15-20-25-30) (sec) at 600% of [IR], Tolerance: 15%, +0.15s 0s
N-phase protection: (0.5-1.25-2.5-5-10-15-20-25-30) (sec) at 600% of [IN], Tolerance: 15%, +0.15s 0s
HOT/COLD, selectable
[In] (1-1.5-2-2.5-3-4-6-8-10-NON) (A), Tolerance: 15%
Relaying time (ms.)
50
100
200
400
600
800
Resettable time (ms.)
25
75
175
375
575
775
Max. total clearing time (ms.)
120
170
270
470
670
870
ON/OFF
[In] (2-4-6-8-10-12-14-16-NON) (A), Tolerance: 20%
Selectable
[ICT] (0.1-0.2-0.3-0.4-0.6-0.8-1.0-NON) (A), Tolerance: 20%
Relaying time (ms.)
100
200
300
500
1000
2000
Resettable time (ms.)
75
175
275
475
975
1975
Max. total clearing time (ms.)
170
270
370
570
1070
2070
ON/OFF
[In] (0.75-0.8-0.85-0.9-0.95-1.0) (A), Tolerance: 7.5%
(5-10-15-20-40-60-80-120-160-200) (sec) at not less than [IP1], Tolerance: 15%, +0.1s 0
29
KRB-5237e
1-
(1.125 IR )2
i2
15%0.15
[sec]
-0
KRB-5237e
30
,,
Setting item
Symbol
Rated curent *1
In
IR
IN
tR
Isd
tsd
10
11
12
13
14
15
I2t tsd
Ii
Ig
tg
I2t tg
IP1
tP1
Setting range
CT rated primary current [ICT] (0.5-0.63-0.8-1.0) (A)
Applied [ICT] (A)
200
400
800
1250
1600
2000
2500
3200
4000
[ICT] 0.5
100
200
400
630
800
1000
1250
1600
2000
Rated
[ICT] 0.63
125
250
500
800
1000
1250
1600
2000
2500
current
[In]
[ICT] 0.8
160
320
630
1000
1250
1600
2000
2500
3200
(A)
[ICT] 1.0
200
400
800
1250
1600
2000
2500
3200
4000
[In] x (0.8-0.85-0.9-0.95-1.0-NON) (A)
Non tripping at not more than [IR] 1.05, Tripping at more than [IR] 1.05 and not more than [IR] 1.2
[ICT] x (0.4-0.5-0.63-0.8-1.0): Fixed to a single point
Non tripping at not more than [IN] 1.05, Tripping at more than [IN] 1.05 and not more than [IR] 1.2
Long time delay: (1-2-3-4-5-6-7-8-10-13) (sec) at 300% of [IR], Tolerance: 20%, +0.15s 0s
N-phase protection: (1-2-3-4-5-6-7-8-10-13) (sec) ) at 300% of [IN], Tolerance: 20%, +0.15s 0s
R1: I0.02t, R2: It, R3: I2t, R4: I3t, R5: I4t
[In] (1-1.5-2-2.5-3-4-6-8-10-NON) (A), Tolerance: 15%
Relaying time (ms.)
50
100
200
400
600
800
Resettable time (ms.)
25
75
175
375
575
775
Max. total clearing time (ms.)
120
170
270
470
670
870
ON/OFF
[In] (2-4-6-8-10-12-14-16-NON) (A), Tolerance: 20%
Selectable
[ICT] (0.1-0.2-0.3-0.4-0.6-0.8-1.0-NON) (A), Tolerance: 20%
Relaying time (ms.)
100
200
300
500
1000
2000
Resettable time (ms.)
75
175
275
475
975
1975
Max. total clearing time (ms.)
170
270
370
570
1070
2070
ON/OFF
[In] x (0.75-0.8-0.85-0.9-0.95-1.0) (A), Tolerance: 7.5%
(5-10-15-20-40-60-80-120-160-200) (sec) at not less than [IP1], Tolerance: 15%, +0.1s 0
31
KRB-5237e
t 1.98110-2tR
0.02
[sec]
-1 20%0.15
-0
1.125IR
i
[sec]
-1 20%0.15
-0
KRB-5237e
32
i
1.125IR
[sec]
-1 20%0.15
-0
i
1.125IR
-1 20%0.15
[sec]
-0
33
KRB-5237e
i
1.125IR
-1 20%0.15
[sec]
-0
KRB-5237e
34
8 ,
10
14
15
Setting item
Rated current *1
Long time delay trip pickup current (continuous)
Long time delay trip timing
Short time delay trip pickup current
10
14
15
Symbol
In
IR
tR
Isd
tsd
I2t tsd
Ii
IP1
tP1
Setting range
CT rated primary current [ICT] (0.5 - 1.0) (A): Fixed to a single point
[In] (0.8-1.0-1.05-1.1-1.15-NON) (A), Tolerance: 5%
(15-20-25-30-40-50-60) (sec) at 120% of [IR], Tolerance: 15%, +0.1s 0
[In] (2-2.5-2.7-3-3.5-4-4.5-5-NON) (A), Tolerance: 10%
Relaying time (ms.)
100
200
300
Resettable time (ms.)
75
175
275
Max. total clearing time (ms.)
170
270
370
ON/OFF
[In] (2-4-6-8-10-12-14-16-NON) (A), Tolerance: 20%
Selectable
[In] (0.75-0.8-0.85-0.9-0.95-1.0) (A), Tolerance: 5%
(10-15-20-25-30) (sec) at 120% of [IP1], Tolerance: 15%, +0.1s 0
400
375
470
600
575
670
800
775
870
35
KRB-5237e
Pretrip alarm
Note 1: The operating time (t) at a long time delay trip pickup current setting is given by
t = -0.843 tR ln
1-
IR 2
i2
15%0.15
[sec]
-0
Note 2: The short time delay trip function has precedence over the long time delay trip function. The OCR operates at
the short time delay trip timing even in those current ranges in which the long time delay trip time setting is
shorter than the short time delay time setting.
KRB-5237e
36
6
(Red)
4 (Yellow)
(Red)
2 (Red)
3 (Red)
7 Reset button
Control
power
supply
Operation
AGR-11L-AL
AGR-11L-GL
AGR-11R-AL
AGR-11R-GL
AGR-11S-AL
Not
required
AGR-11L-GL
AGR-11R-GL
Not
required
Required
Type of OCR
AGR-11L-PS
AGR-11L-PG
AGR-11R-PS
AGR-11R-PG
AGR-11L-PG
AGR-11R-PG
AGR-11S-PS
Position
Normal
State
pickup Trip/Alarm
Reset
Terminal No.
See Fig. 10
OFF
OFF
05 ,
15
Flash
OFF
OFF
ON *2
OFF *3
05 ,
26
OFF
Flash
OFF
OFF
05 ,
15
ON
OFF
OFF
OFF
OFF
Flash
-
ON *4
ON
OFF *3
05 ,
06
05 ,
26
OFF
Flash
ON
OFF
05 ,
16
Required
Flash
OFF
ON *2
Turn OFF automatically
after ON for 40 ms or
more *5
OFF
OFF *3
OFF
ON
ON *4
ON
OFF
05 ,
25
OFF
05 ,
06
05 ,
26
OFF
OFF
ON *4
ON
OFF *3
OFF
ON
OFF
OFF
05 ,
15
OFF
ON
05 ,
25
OFF
Reset
05 ,
15
Flash
OFF
OFF
Required
Contact output
State
Normal
Trip/Alarm
ON *4
ON
OFF
OFF *3
z The ACB can be opened, closed or tripped, irrespective of whether or not the operation indication is reset.
z The operation indication is updated when a protective function is activated.
*1: AGR-11S-AL is not equipped with the N-phase protection function (NP).
*2: When the main circuit is energized and the OCR control power is established.
*3: The OCR has a self-monitoring feature that monitors the OCR internal circuit, the magnet hold tripper (MHT) circuit, and the ACB state. An alarm caused by transient noise
can be reset by pressing the reset button. If an alarm cannot be reset, check the ACB. See chapter 7.
*4: Turns OFF automatically when the current decreases below the alarm pickup current setting.
*5: A self-hold circuit is required.
Operation
Terminal
No.
See Fig.
10
State
Closing spring
Charged
Discharged
ACB closed
05 ,
17
Trip
OFF
05 ,
27
ON
OFF
Spring charge
z The ACB can be opened, closed or tripped, irrespective of whether or not the operation indication is reset.
* Ready to close means that all of the following conditions are met:
1. The closing springs are charged.
2. Opening operation is complete (At least 40 ms has elapsed after trip signal was produced).
3. The OFF button is released.
4. The specified voltage is applied to the fixed type undervoltage trip device (if equipped).
All
37
ACB open
Not ready to close
Ready to close *
*
ON
OFF
-
Reset
No change
No change
KRB-5237e
CAUTION
z OCR function check and setting changes must be performed by competent persons.
z Use a small flatblade screwdriver with a torque of not more than 0.1 Nm or a force of not more than 0.1 N when adjusting
the setting switches (rotary step switches or slide switches). An excessive torque or force may cause a malfunction.
z After completion of OCR tests, be sure to return the setting switches to the original positions. Failure to do so may cause a
fire or burnout.
The following function check is applicable to the OCR types that require control power. To test other types of OCR, use type
ANU-1 OCR checker (optional). See Fig. 39 and Tables 24 and 25 for how to test the OCR.
Test item
Object
ACB
Breaker body
OCR settings
Breaker body
ACB
TEST MODE button
SELEXT HI/LO button
TRIP button
8
NON TRIP button
9
10
RESET button
OCR settings
z The ground fault trip and N-phase protection functions cannot be checked.
z Steps 6 - 8 must be completed within 10 seconds. Otherwise, the test mode will be canceled. In such a case, start testing from step 6 again.
z When checking the long time delay trip timing, determine the OCR input signal timing from characteristic curves (Figs. 31, 33 - 37, 39) and compare the results with the
values measured by a timer or the like.
*1: If button operation is aborted, the OCR will cancel the test mode automatically. In such a case, start testing from step 6 again.
*2: Use a tester to check for normal contact output.
Table 25 Protective functions that can be checked and OCR setting changes to be done
Protective function that
can be checked
Long time delay trip
Short time delay trip
Instantaneous trip
MCR trip
Pretrip alarm
KRB-5237e
Type of OCR
AGR-11L
AGR-11R
AGR-11S
AGR-11L,AGR-11R, AGR-11S
AGR-11L,AGR-11R,AGR-11S
AGR-11L,AGR-11R, AGR-11S
AGR-11L
AGR-11R
AGR-11S
38
Normal
Harsh
Abnormal
z
z
Inspection
level
Normal/
Detailed
Thorough
Overhaul
Normal/
Detailed
Every year
Every half year after 2
years since installation
Open/close
condition
Nearly no current
level
Rated current
level
800AF or
1250AF 3200AF or more
less
2500AF
Every 1000 cycles
Every 500 cycles after 1000 cycles
Every 1000 Every 500
Every 100
cycles
cycles
cycles
Every 500
Every 250
Every 50 cycles
cycles after
cycles after
after 100 cycles
1000 cycles
500 cycles
Thorough
Every 2 or 3 years
Every 2 years after 6 years
Every 2500 - 3000 cycles
since installation
Every 2000 cycles after 3000 cycles
Every year after 10 years
since installation
Overhaul
800AF or
less
1250AF
2500AF
Every 25
cycles
Every 25
cycles
Every 25 cycles
Every time
Every time
Every time
Thorough
Overhaul
3200AF or more
Normal inspection includes inspection and actions that can be done only with removing the arc chamber, contacts, front cover and
the like. Normal inspection can be performed by the user. Terasaki also provides normal inspection service.
Detailed inspection includes inspection, actions, and parts replacement that will be done to prevent functional degradation caused
by aging or the like when abnormality is found during normal inspection.
You are recommended to use Terasakis detailed inspection service.
Thorough inspection must be left to Terasaki. Overhaul will be done in a Terasakis factory.
39
KRB-5237e
CAUTION
z ACB maintenance, inspection and parts replacement must be performed by competent persons.
z Do not touch ACB current carrying parts and ACB structural parts close to a current carrying part immediately after the
ACB trips open. Remaining heat may cause a burn.
z Prior to commencing any work on the ACB, open an upstream circuit breaker or the like to isolate all sources of
power/voltage from the main and control circuits. Otherwise, electric shock may result.
z Take care to avoid adhesion of dust to main and control circuit contacts. Dust on the contacts may result in a fire.
z Prior to commencing maintenance, inspection, or parts replacement, make sure that the closing springs are released and the
z
z
z
z
z
ACB is open. Otherwise, unintentional open/close operation may lead to fingers or tools to be pinched by the open/close
mechanism, resulting in injury.
Retighten the terminal screws periodically to the specified torque. Otherwise, a fire could result.
When grinding a contact tip, be careful to prevent grinding dust from entering the breaker operating mechanism. Wipe the
tip clean after grinding. Otherwise, a malfunction or fire could result.
Do not perform dielectric withstand/insulation resistance tests under other conditions than specified. Doing so may cause a
malfunction.
Be sure to reinstall the arc chamber if removed. Failure to do so or incorrect installation of the arc chamber may result in a
fire or burn.
When charging the closing springs or performing open/close operation of the ACB with the arc chamber, front cover and/or
side covers removed during maintenance or inspection work, do not touch parts other than those required for the above
operation (charging handle, ON/OFF buttons, moving core and the like). Doing so may cause fingers or tools to be pinched,
resulting in injury.
When replacing an auxiliary, do not damage the control wire for the auxiliary or pinch the wire between the auxiliary and
the breaker body. Doing so may cause a malfunction.
To ensure safety, be sure to perform the preparation work described in section 6-2-1 unless otherwise specified in the inspection
procedures. The normal inspection procedure and the detailed inspection procedure are shown in Tables 28 and 29 respectively.
Description
AR_____ __ __ poles with draw-out cradle
__________ ______
Reference
Rating nameplate
Product Specifications
In
Manual charging
Motor charging
CLOSING section on
Rated operation voltage:
specification nameplate
Non
Equipped
Type: AGR-11__ _______
OCR section on
Rated control voltage: AC DC _____V
specification nameplate
Shunt trip device (SHT)
Rated voltage: AC DC _____V
TRIPPING section on
Fixed type undervoltage trip device (UVT)
Rated voltage: AC DC _____V specification nameplate
OTHERS section on
SR: ________
SO: ________
specification nameplate
Working conditions
(Voltage, current,
environment)
Symptom of abnormality
(in detail): When, How,
Where, etc.)
Inspection done/actions
taken (if any)
6-1.
KRB-5237e
40
No.
1
2
General
3
4
Main/control
circuit terminals
See 2-3.
Main/control
circuit contacts
Arc chamber
See 6-2-2.
Contacts
See 6-2-2, 6-2-3
and 6-2-4.
9
Main circuit, Arc
chamber
See 6-2-2.
10
Operating
mechanism
See 6-2-7.
11
Control circuit
See 6-2-5.
12
13
Auxiliary
switches
See 6-2-9.
14
15
16
Operation
related
mechanism
See 4-1 and 42.
17
18
19
Check item
Description
Discoloration Check connection conductors, main circuit terminals, and current carrying parts for heat discoloration.
of conductors If such a symptom is found, contact us.
Check that screws, bolts, nuts, washers, springs, retainers and the like are not missing. If any parts
Parts missing
are missing, contact us.
Damage to
Check for deformation, cracks, chips, or other damage of parts. If damage is found, contact us.
parts
Dust
Check that no dust is accumulated in ACB. If dust is accumulated, use vacuum cleaner to remove
accumulation dust and wipe off with dry, clean cloth.
Check main circuit terminal screws, ground terminal screw, auxiliary switch terminal screws, control
circuit terminal screws, and position switch terminal screws for looseness. If loose, tighten to specified
Connections
torque. If #187 tab terminals are used, check that receptacle terminals are inserted correctly. If
incorrect, reinsert correctly.
Check that contacts have no dust accumulation and discoloration. If dust is accumulated, use vacuum
cleaner to remove dust and wipe off with dry, clean cloth. If surface is discolored badly, polish it with
#200 sandpaper. * For main circuit contacts, apply contact grease (SS grease, No. F-5G, FUJI
Surface
KAGAKU SANGYO) to contact surface after cleaning.
condition
z Excessive grease may foster dust accumulation. Grease should be applied lightly.
z Blackening of contacts is caused by oxidation or sulfuration and has no harmful effect except in
extreme cases. If heat discoloration, arc marks, roughness, or peeling of plating layer is found,
contact us.
Remove arc chamber and check it for foreign object or dust accumulation, deformation, cracks, chips
Dust
and other damage. If foreign matter or dust is accumulated, use vacuum cleaner to remove foreign
accumulation
matter of dust and wipe off with dry, clean cloth. If metal spatters are adhered, use sandpaper to
/Damage
remove them. * If arc chamber has stubborn adherents suffers damage, replace arc chamber.
Remove arc chamber and check contact circumference, contacts, and contact tips for foreign object
or dust accumulation, deformation, cracks, chips and other damage. If dust is accumulated, use
vacuum cleaner to remove dust and wipe off with dry, clean cloth. If contact tips are badly discolored
Surface
or roughened, polish with #200 sandpaper. * If contact tip suffers damage or is less than 0.7 mm thick
condition
after polishing, replace both moving and stationary contacts.
z Blackening of contact tips is caused by oxidation or sulfuration and will be removed during closing
operation. It has no harmful effect except in extreme causes. If heat discoloration is found,
perform detailed inspection.
Looseness of
Check moving and stationary contact mounting screws A and B for looseness. If loose, retighten.
screws
Use DC500V Megger to check that insulation resistance between main circuit terminals, between
main circuit terminal group and ground, and between ends of adjacent grids exceeds 5M ohm. If
Insulation
resistance does not exceed 5M ohm, use sandpaper to remove carbonized portions of insulation
resistance
around contacts or current carrying parts and/or spatters adhered to arc chambers and arc
extinguishing grids. If problem persists, contact us.
With OCR removed, check internal mechanism for missing parts, deformation, cracks, chips, foreign
Internal
mater or dust accumulation, breakage of springs, and rust. If foreign matter or dust is accumulated,
mechanism
use vacuum cleaner to remove foreign matter of dust and wipe off with dry, clean cloth. If any parts
are missing or damaged or springs are broken, contact us.
Remove side and front covers, check that wiring is properly connected, and not disconnected nor
damaged. If incorrect connection is found, connect correctly. If disconnection or damage is found,
Wiring
contact us.
State of
Current conducting
Current conducting
Check that auxiliary switches
operation lever between _11 and _12 between _11 and _14
operate as shown to the right.
100 m or less
Operation
Natural position
Non
If not so, replace switches.
Uppermost lift
100 m or less
Non
position
Auxiliary
Remove auxiliary switches and check contacts for roughness. If roughened excessively, replace
contacts
contacts.
Looseness of
Check screws of auxiliary switches for looseness. If loose, retighten.
screws
DrawDraw out and insert breaker body to check that draw-out handle can be turned with max. operating
out/insertion
torque or less, position indictor provides correct indication, release button operates normally, and no
mechanism
abnormal sound is heard during handle operation. If abnormality is found, contact us.
With breaker body in ISOLATED position, charge closing springs manually and attempt closing ACB
UVT
to make sure ACB cannot be closed. If ACB can be closed, perform detailed inspection.
Operation
With breaker body in TEST position and operation mechanism, SHT and UVT supplied with power,
mechanism,
perform closing spring charging operation and manual and electrical open/close operation several
LRC, SHT
times to check that charge indicator, ON-OFF indicator and ON-OFF cycle counter provide correction
and UVT
indication and no abnormal sound is heard. If abnormality is found, perform detailed inspection.
Move the breaker body to TEST position and supply ACB with control power, and then check that
System alarm system alarm LED on OCR front panel is off. If LED is on, press reset button and make sure LED
turns off. If LED remains on, see chapter 7.
* Take care to avoid grinding dust from entering the ACB. Wipe contact surfaces clean of grinding dust.
41
KRB-5237e
No.
Check item
Description
Parting
1 distance
Contacts
See 6-2-2,
6-2-3 and
6-2-4
With ACB open, remove arc chamber and, using feeler gauge, make sure distance between moving
and stationary contact tips is 201mm. If not so, replace both moving and stationary contacts. If it is
useless to replace contacts, contact us.
Insert 3.5 - 4.0-mm-dia x 50-mm-length rod into engagement measuring hole vertically until it stops,
and measure protrusion of rod when ACB is open and closed. Make sure difference in protrusion is
2 Engagement following: line side; 2.7-3.4mm, load side; 2.7-4.0mm. (The difference of the value of line side and
load side must not exceed 1.0mm.) If not so, replace both moving and stationary contacts. If it is
useless to replace contacts, contact us.
With ACB closed, remove arc chamber and, using graduated ruler, make sure displacement between
3 Displacement corresponding contact tips is within 2 mm. If displacement is 2 mm or more, replace both moving and
stationary contacts. If it is useless to replace contacts, contact us.
With ACB closed, remove arc chamber and, using tester, make sure resistance between moving and
stationary contact tips is not more than 100 . If not so, replace both moving and stationary
4 Resistance
contacts. If it is useless to replace contacts, contact us. After inspection, open ACB and discharge
closing springs.
Current
sensors
See 6-2-3.
Looseness of
screws
Coil
resistance
Length and
7 stroke of
plunger
Hand
8
connector
Looseness of
9
screws
6
Latch
release coil
(LRC)
See 6-2-5.
10
Mechanical
motion
Coil
resistance
Length and
12 stroke of
plunger
Hand
13
connector
Looseness of
14
screws
11
Shunt trip
device
(SHT)
See 6-2-6.
Fixed type
undervolta
ge trip
device
(UVT)
See 6-2-1.
15
Mechanical
motion
16
Coil
resistance
17 Operation
Length and
18 stroke of
plunger
Hand
19
connector
Looseness of
20
screws
Coil
21
resistance
22 Operation
Magnet
hold trigger
(MHT)
See 6-2-8.
Length and
23 stroke of
moving core
Hand
24
connector
Looseness of
25
screws
Charging
motor and
LRC
26
Electrical
operation
SHT
27
Electrical
operation
UVT
28
Electrical
operation
OCR and
MHT
29 Operation
KRB-5237e
42
CAUTION
z ACB maintenance, inspection and parts replacement must be performed by competent persons.
z Do not touch ACB current carrying parts and ACB structural parts close to a current carrying part immediately after the
ACB trips open. Remaining heat may cause a burn.
z Prior to commencing any work on the ACB, open an upstream circuit breaker or the like to isolate all sources of
power/voltage from the main and control circuits. Otherwise, electric shock may result.
z Take care to avoid adhesion of dust to main and control circuit contacts. Dust on the contacts may result in a fire.
z Prior to commencing maintenance, inspection, or parts replacement, make sure that the closing springs are released and the
ACB is open. Otherwise, unintentional open/close operation may lead to fingers or tools to be pinched by the open/close
mechanism, resulting in injury.
z Be sure to reinstall the arc chamber if removed. Failure to do so or incorrect installation of the arc chamber may result in a
fire or burn.
z When replacing an auxiliary, do not damage the control wire for the auxiliary or pinch the wire between the auxiliary and
the breaker body. Doing so may cause a malfunction.
6-2-1. Preparation
Be sure to make the following preparations for parts replacement in order to ensure safety.
1) Open an upstream circuit breaker or the like to isolate all sources of power/voltage from the main and control circuits.
2) Draw out the breaker body to the removed position, and remove it using an optional lifter or lifting plate. Refer to sections 42-2 and 2-1-2.
3) Discharge the closing springs and open the ACB.
z When the ACB is not equipped with the undervoltage trip device (UVT):
Perform manual closing/opening operation of the ACB.
z When the ACB is equipped with the undervoltage trip device (UVT):
(1) Turn the cover mounting screws five or six turns to loosen as shown in Fig. 40. If the ACB is equipped with side covers,
first remove the side covers and then loosen the front cover mounting screws. (The cover mounting screws are of captive
type and cannot be removed from the side and front covers.)
Location of cover mounting screws
Front cover
Side covers
Cover mounting
screws
AR3/4 series
Front cover
43
KRB-5237e
(2) Remove the contact block fixing screws as shown in Fig. 41.
Contact block
(3) Slide the front cover to the left and flip the contact block up as shown in Fig. 42.
Front cover
Contact block
(4) Turn the UVT mounting screws eight or ten turns to loosen, disconnect the manual connector (red), and then remove
the UVT. (The UVT mounting screws are of captive type and cannot be removed from the UVT.)
UVT mounting screw (captive),
Pan head M4 x 85 (2)
with spring washer
Tightening torque: 1.3 - 1.7 Nm
Hand connector
UVT
LRC
Fig. 43 Removing the UVT
KRB-5237e
44
(5) Flip the contact block down and slide the front cover to the original position as shown in Fig. 44.
Front cover
Contact block
(6) Perform manual closing/opening operation of the ACB. Refer to sections 4-1-2 and 4-1-3.
(7) Reinstall each part or component in reverse order of removal after inspection. When installing the UVT, make sure the
nameplate on the UVT can be viewed from the front of the ACB.
45
KRB-5237e
Spacer
7 cm or higher
Fig. 46 Laying the breaker body on spacers
3) Turn the arc chamber mounting screw eight or ten turns to loosen as shown in Fig. 47. (The arc chamber mounting
screws are of captive type and cannot be removed from the arc chamber.)
4) Holding the arc chamber mounting screw, remove the arc chamber.
5) Reinstall each part or component in reverse order of removal after inspection.
KRB-5237e
46
Moving contact
Insulated operating rod
Current sensor
Stationary contact mounting
screws B,
Pan head M6 x 20 (12)
with spring and flat washers
Tightening torque: 4.7 - 5.9 Nm
47
KRB-5237e
Control wire
Stationary contact
(tilted)
Power supply CT
Stationary contact
(removed)
5) Reinstall each part or component in reverse order of removal after inspection. As to the moving contact-related parts,
however, install the insulated operation rod, insulation plate, spacer, moving contact, upper separator, lower separator,
flat washer, spring washer, and moving contact mounting screw in this order. See Fig. 53.
6) After installing the moving and/or stationary contact, be sure to perform 10 - 20 cycles of open/close operation and then
retighten the contact mounting screws to the specified torque.
Opening
distance
measuring
points
Resistance
measuring
points
Open state
Closed state
Fig. 52 State of contacts
KRB-5237e
48
Upper separator
Moving contact mounting
screw,
Hex. socket head M8 x 30-6 (8)
with spring and flat washers
Tightening torque: 14.7 Nm
Moving contact
Insulated operating rod
Lower separator
Spacer
Spacer
Lower separator
Moving contact
Upper separator
Moving contact
mounting screw
Fig. 54 Moving contact-related parts
5) Reinstall each part or component in reverse order of removal after inspection. As to the moving contact-related parts,
however, install the insulated operation rod, insulation plate, spacer, moving contact, upper separator, lower separator,
flat washer, spring washer, and moving contact mounting screw in this order. See Fig. 53.
6) After installing the moving and/or stationary contact, be sure to perform 10 - 20 cycles of open/close operation and then
retighten the contact mounting screws to the specified torque.
49
KRB-5237e
Contact block
Hand connector
(green)
LRC
7) Reinstall each part or component in reverse order of removal after inspection. When installing the LRC, make sure the
nameplate on the LRC can be viewed from the front of the ACB.
Moving core
located in the center hole
KRB-5237e
50
Hand connector
(black)
Contact block
SHT
LRC
Fig. 57 Removing the SHT
7) Reinstall each part or component in reverse order of removal after inspection. When installing the SHT, make sure the
nameplate on the SHT can be viewed from the front of the ACB.
Plunger
Moving core
located in the center hole
51
KRB-5237e
5) Unscrew the OCR mounting screws and remove the wiring from the wire tie. See Fig. 60.
OCR mounting screw,
Pan head M5 x 10 (2)
with spring and flat washers
Tightening torque: 2.7 - 3.5 Nm
Wire tie
Wiring
OCR
KRB-5237e
52
6) Pull out the OCR as shown in Fig. 61 and place it on the floor.
Hand connector
(red, with two terminals)
Hand connector
(white, with three terminals)
OCR
Hand connector
(white, with six terminals)
Hand connector
(white, with two terminals)
7) Unscrew the contact block mounting screws as shown in Fig. 41 and flip the contact clock up as shown in Fig. 42.
8) Unscrew relay base mounting screws A and B, raise the relay base to unlatch from other parts, remove the base and place
it on the top of the breaker body.
z When relay base mounting screw A, the relay base ground terminal will also be removed.
Relay base mounting screw A,
Pan head M5 x 10
with spring and flat washers
Tightening torque: 2.7 - 3.5 Nm
Relay base
Relay base
mounting screw
Latch
53
KRB-5237e
9) Remove the relay retainer shown in Fig. 63 and remove the control relay from the relay base.
Control relay
Relay retainer
Relay seat
10) Reinstall each part or component in reverse order of removal after inspection. Do not forget to install the OCR ground
terminal and the relay base ground terminal.
KRB-5237e
54
MHT
Moving core
To remove the moving
core, insert a small rod
into the center hole on
the skew and, holding
the rod, lift the core.
Fig. 65 General view of MHT
55
KRB-5237e
4) Depressing the AUX lock lever shown in Fig. 67, raise the operation lever.
Operation lever
KRB-5237e
56
5) With the operation lever raised, uplift the auxiliary switch unit, pull the shaft lever through the U-notch, and remove the
auxiliary switch unit.
Operation lever
Shaft lever
6) Reinstall each part or component in reverse order of removal after inspection. When installing the auxiliary switch unit,
apply molybdenum grease to the engagement of the operation lever and the shaft lever.
z Auxiliary contacts can be checked visually through the inspection holes shown in Fig, 69.
Auxiliary contact
Inspection holes
Shaft lever
57
KRB-5237e
7. TROUBLESHOOTING FLOWCHARTS
Figs. 70 - 74 are troubleshooting flowcharts where typical troubles and remedial actions are shown.
Yes
No
NG
Repair
OK
No
Yes
NG
Repair/replace
OK
End
OK
End
NG
Contact Terasaki.
Contact Terasaki.
Contact Terasaki.
OK
Is manual charging
possible?
No
No
NG
Is manual charging
possible?
Repair
Yes
Yes
NG
Is motor charging
possible?
OK
Yes
No
NG
Contact Terasaki.
Repair
OK
KRB-5237e
58
End
Is manual closing
possible?
Yes
No
Yes
No
Yes
No
No
Charge
Yes
NG
Repair/replace
OK
Yes
No
NG
Repair
OK
Yes
Is manual closing
Possible?
Unlock
No
No
Contact Terasaki.
Yes
Yes
NG
Deactivate
No
OK
NG
OK
NG
Repair
OK
NG
Repair/replace
OK
NG
Repair/replace
OK
NG
Is electrical closing
possible?
Repair
OK
Yes
End
No
Is manual closing
possible?
No
Contact Terasaki.
Contact Terasaki.
Yes
59
KRB-5237e
Is manual opening
Possible?
No
NG
Contact Terasaki.
Yes
Repair/replace
OK
NG
Is electrical opening
possible?
OK
Yes
End
No
NG
Contact Terasaki.
Repair
OK
An overheat occurs.
No
Correct/adjust
Yes
No
Correct/adjust
Yes
No
Yes
Retighten
Contact Terasaki.
NG
Repair/replace
OK
NG
Yes
Repair/replace
OK
No
Contact Terasaki.
KRB-5237e
NG
OK
No
Repair
OK
Yes
NG
60
End
Fax: 81-6-6791-9274
E-mail: kiki-info@terasaki.co.jp
61
KRB-5237e