TeleService?
How do you configure a connection between WinCC flexible Runtime (PC or Panel)
and a SIMATIC S7-300 / S7-400 via Industrial Ethernet?
How do you configure a PROFINET connection to an S7 controller in WinCC
flexible?
How do you specify the MPI address of an FM in the HMI configuration tool if the
address doesn't appear in the HW Config and is thus unknown?
How do you connect a panel to a SIMATIC H station?
What settings have to be made for a PROFIBUS DP connection between a panel or a
PC with WinCC flexible Runtime and an S7-200?
What should you watch out for when connecting a SIMATIC HMI device configured
with WinCC flexible ES to a SIMATIC ET 200 CPU?
How do you configure communication between WinCC flexible Runtime or a
Windows-based operator panel and an S7-200 (CP 243-1) via Ethernet?
PROFIBUS communications between Windows-based operator panel (configured with
WinCC flexible 2004) and WinAC Basis / WinAC RTX V4.0
How do you configure communication between the WinCC flexible Runtime and
WinLC via SOFTBUS on a PC?
Why is the communication driver marked "orange" in WinCC flexible when another
Ethernet communication is added to an existing MPI/DP?
How do you access S7-1200 tags with a panel or RT configured with WinCC flexible 2008 SP2?
Core statement
With WinCC flexible 2008 Service Pack 2 all panels with an Ethernet interface that can be
configured with WinCC flexible 2008 and the WinCC flexible 2008 Runtime can access S71200 data blocks using absolute addresses (no symbolic DBs) via the "SIMATIC S7 300/400"
driver.
Compatibility
The following items are supported:
Data type: Bool, Byte, Char, DInt, DWord, Int, Real, Time, Word, String, Array
New S7-1200 data type:
o SInt can be connected in WinCC flexible 2008 SP2 as Char
(range: -128 to 127)
o USInt can be connected in WinCC flexible 2008 SP2 as Byte
(range: 0 to 255)
Procedure
The procedure for the communication with WinCC flexible 2008 Runtime is described below.
No. Remarks
1
Create a data block using an absolute address in STEP 7 Basic V10.5 via "Add new
block" and "Global DB".
Fig. 01
Remove the check mark for the option "Symbolic access only".
2
In the data block, you create the tags that WinCC flexible 2008 will access.
Fig. 02
3
In WinCC flexible 2008, you create a connection via "Communication > Connections".
Fig. 03
Enter the IP address for the WinCC flexible Runtime and the S7-1200 station.
Select "S7ONLINE" as the operator panel's access point.
Specify "1" as the PLC's expansion slot.
Open the PG/PC interface under "Start > Control panel > Set PG/PC interface".
In the PG/PC interface, you must set the access point "S7ONLINE" to "TCP/IP -> [Used
network card]".
Fig. 04
5
Create the S7-1200 tags using absolute addresses under "Communication > Tags"
(compare with Fig. 02).
Fig. 05
Table 01
Notice
Service Pack 2 for WinCC flexible 2008 is available under entry ID: 38612895.
Entry ID:38111886 Date:2010-05-26