Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
SUMMARY
A.
B.
The requirements of this Section do not supersede or take precedence over any
provision of the General Conditions and Supplementary General Conditions, and
should any discrepancy become apparent between these requirements and the General
Conditions and Supplementary General Conditions, the Contractor shall notify the
Engineer in writing, and the Engineer shall interpret and decide such matters in
accordance with the applicable provisions of the General Conditions and
Supplementary General Conditions.
1.02
EXTENT OF WORK
The Contractor shall supply all labor, materials, equipment, tools, appurtenances,
storage, services and temporary work, necessary to completely install, in accordance
with these specifications and the drawings.
Work, materials, equipment or services not specifically mentioned in other clauses of
these specifications or elsewhere, or indicated on the drawings but found necessary for
the completion and perfect functioning of the installations must be included in the
Contractors price.
The work shall include also operation of the installations after completion and
acceptance including maintenance and guarantee of the works as described hereinafter.
The work shall be designed and carried out in accordance with the contract drawings
and specifications as well as the standards of the country of origin.
The following builders work shall be considered as part of this work:
i.
Concrete foundations and pads under pumps, chillers and other equipment.
ii. All Builders work in connection with fixing support, hangers, anchors, etc.
iii. Cutting or forming all openings, mortar, chase, etc., in floors, walls and ceilings
required for the installation and making good after.
iv. Painting items of equipment and exposed pipes and supports.
v. Labeling.
Page 1 of 16
1.03
SYSTEM DESCRIPTION
A.
Division 15 of this specification covers the supply and installation of the mechanical
and Air Conditioning services as shown on the design drawings and in this
specification.
B.
To balance, adjust and test heating and chilled water systems, air moving equipment,
air distribution, exhaust air systems and other systems as herein specified.
C.
It shall be clearly understood that these specifications and design drawings are
complimentary documents, intended for the selection of equipment having the general
and specific characteristics as detailed in the documents.
D.
E.
Materials and methods included in this Section are of a general nature, and apply to
most systems and installations in this Contract. Refer to individual system sections for
materials and methods specifically required for the respective systems.
F.
G.
46C
35.1C
In Winter
7.2C
2. Indoor Temperatures
Unless other wise noted on drawing and in this book of specifications the indoor
room conditions are:
In summer
- Indoor areas
231C
505%
Relative humidity.
Page 2 of 16
In winter,
20C
1.04
QUALITY ASSURANCE
A.
Materials and equipment shall conform to the latest edition of reference specifications
specified herein and to applicable codes and requirements of local authorities having
jurisdiction.
1. Mechanical equipment shall conform to the latest version of ASHRAE Standard.
2. Reference Standards
a. Provide materials and equipment listed by Underwriters Laboratories, Inc. except
in those cases where an Underwriters Laboratories listing is not available.
b. Comply with the latest applicable standards of the following:
1) ASME American Society of Engineers.
2) ARI Air-conditions and Refrigeration Institute.
3) ANSI - American National Standards Institute.
4) ASTM - American Society of Testing Materials.
5) AMCA - Air- moving and Conditioning Association.
6) AGA American Gas Association.
7) NEMA National Electrical Manufacturers Association.
8) AWS American welding Society.
9) NFPA National Fire Protection Association.
10) BS British Standards.
11) SMACNA Sheet Metal and Air-conditioning Contractors.
12) DIN Deutsches Institute for Normalisierung
13) FM Factory Matual.
14) IRR Institute of Boiler and radiator Manufacturers.
15) ISO International Standardization organization.
16) Local Standards (SBC)
1.05
SUBMITTALS
A.
Page 3 of 16
3. Samples shall include physical examples of materials in complete units for visual
inspection. Samples shall indicate applicable specification section number and item
numbers within that section.
4. Certificates shall include statements of applicability, certifying reports from
governing and testing agencies, industry standards and applicable certificates
specified in each Section of the specifications.
5. Test and inspection reports shall include reports specified in each section of the
specifications.
6. Miscellaneous submittals shall include submittals related directly to the work (nonadministrative) including warranties, maintenance agreements, workmanship
bonds, reports, and physical work records, copies of industry standards, record
drawings, field measurement data and similar information applicable to the work
and not processed as shop drawings, product data, samples or certificates.
7. No equipment or materials are to be purchased or delivered to site until the
required submittals have been approved.
1.06
INTENT
The purpose of the shop drawings and specification is to provide an approach for
intended complete installations, finished, fully adjusted, tested commissioned and put
in perfect operating condition. The spirit as well as the letter of the drawings and
specification shall be followed, and all work shall be executed according to the true
intent and meaning of the drawings and specifications.
1.07
1.08
ENGINEER'S DRAWINGS
The Engineer's drawings are generally diagrammatic and include general layouts and
typical details of the various systems to be installed. No deviations from the drawings
shall be made without receipt of prior written approval from the Engineer.
The drawings shall not be scaled. The Contractor shall base all measurements both
horizontal and vertical from established bench marks. All work shall agree with these
established lines and levels. All measurements shall be verified on Site and checked as
to correctness of same as related to the work.
Page 4 of 16
The Contractor shall check all Architectural, Structural and Electrical drawings in
laying out work for verifying the adequacy of space in which work will be installed.
Maximum headroom and space conditions shall be maintained all points. Where head
room or space conditions appear inadequate the Engineer shall be notified before
proceeding with installation.
1.09
Page 5 of 16
1.11
RECORD DRAWINGS
The Contractor shall submit to the Engineer for record a complete set of as-built
drawings including three sets of soft copies on CAD 2004 and electrical wiring
diagrams, in tracing or other reproducible form reflecting all the changes made from
the original drawings during the progress of the work. The drawings and electrical
wiring diagrams shall show all labeled equipment, valves, controls, instruments and
electrical devices.
Page 6 of 16
1.12
1.13
1.14
1.15
Page 7 of 16
interpreted as establishing a standard of quality and performance and shall not in any
way be construed as an intention to eliminate the products of other manufacturers and
suppliers having approved equivalent products.
Approval of a manufacturer does not necessarily constitute approval of his equipment
as equal to those specified. After award of Contract and before start of construction, the
Contractor shall submit for the approval of the Engineer a complete summary of
proposed equivalent to be furnished indicating service, manufacturer, figure number,
type and pressure rating.
The Tender shall be based on the trade name and catalogue reference named in the
specification and products of the approved manufacturers. Should the Contractor wish
to use any equipment, material or products other than those specified, he should so state
as an alternative to the Tender, naming the proposed substitutions and indicating what
difference, if any, will be made to the Contract, price and detailing all differences
entailed by the substitution.
All the times the Engineer shall be the only judge of equality between the proposed
alternative and the item specified. No alternative shall be implemented without the
written approval of the Engineer.
Where the Contractor proposes to use equipment other than that specified or indicated
which requires any redesign of the structure, partitions, foundations, piping, wiring or
any other part of the works, all such redesign, new drawings and detailing required
shall be prepared by the Contractor at his own expense. All additional costs resulting
from such substitution if approved by the Engineer in writing shall be paid by the
Contractor.
Where such approved substitution requires a different quantity or arrangement of
piping, wiring, conduit and equipment from that specified or shown on the drawings,
the Contractor shall provide all such piping, structural supports, installation,
controllers, motors, starters, electrical wiring and conduits and any other additional
equipment required by the system, at no additional cost to the Employer.
1.16
PROTECTION
The Contractor shall order all equipment from the manufacturer specifying adequate
packing for export at the factory to avoid damage during shipment to the Site.
The Contractor shall be responsible for safe storage and the adequate protection of all
material and equipment until finally installed, tested and accepted.
He shall protect work against theft, injury or damage and shall carefully store material
and equipment received on Site in their original crates or containers until they are
installed. This responsibility shall embrace any delay pending final testing of systems
and equipment due to any condition.
The Contractor shall close open ends of work with temporary covers or plugs during
construction and storage to prevent entry of obstructing material.
The Contractor shall coordinate the protection of the work of all trades and shall be
liable for any damage sustained to other trades resulting from his work.
Page 8 of 16
If any equipment is damaged during shipment be before it is tested and accepted, the
Contractor shall replace or repair the equipment depending on the extent of damage and
as determined and decided by the Engineer, on the Contractors own account and
without additional cost to the Employer.
1.17
ACCESSIBILITY
Contractor shall be responsible for determining in advance of purchase that equipment
and materials proposed for installation shall fit into the confines indicated areas,
allowing adequate space for maintenance.
All work shall be installed so as to be readily accessible for operation, maintenance and
repair. Deviations from the drawings may be made to accomplish this, after the written
approval of the Engineer.
Concealed valves and devices shall be grouped together in as practical a way as
possible in order to be accessible through access doors.
1.18
ACCESS DOORS
The Contractor shall arrange for access doors and frames to be provided for easy
access to concealed equipment, controls, valves, traps, vents, drains, cleanout and other
devices that require periodic operation, inspection or maintenance.
However, the dimensions and locations of access doors shall be the responsibility of the
Contractor and shall have the approval of the Engineer before the work is installed.
Requirements of access doors shall be submitted in sufficient advance time to be
installed in the normal course of the work.
The Contractor shall be responsible for the correct identification of access doors by
means of buttons, tabs or markers to indicate the location of concealed work. The
method and schedule for identification of access doors shall be approved by the
Engineer.
1.19
NAMEPLATES
Each piece of equipment provided shall carry, at a conspicuous location, attached in a
permanent manner to the equipment at the factory, a certified nameplate on which shall
be printed or stamped clearly the name and address of the manufacturer, the equipment
model number, serial number, date of manufacture, Electrical characteristics,
performance rating or duty, pressure, temperature or other limitations and all other
pertinent data as deemed necessary by the manufacturer for any future reference to the
equipment.
1.20
LABELING
The Contractor shall label and identify all equipment, instruments, controls, electrical
devices, valves, etc. as to duty, service or function.
Page 9 of 16
Labels on equipment shall be of laminated bakelite with black surface and white core,
with incised lettering nomenclature written in English.
Labels shall be attached to equipment, instruments, controls, electrical devices, etc. or
to adjacent permanent surfaces, in an approved permanent manner.
The Contractor shall submit to the Engineer for his approval prior to installation a
schedule of all equipment and devices to be labeled and the suggested nomenclature.
Controls and electrical devices shall be labeled to indicate clearly which equipment
they control.
1.21
GUARANTEE
All works are to be guaranteed for a period of one year dated from the final acceptance
of the work by the Owner.
Repairs or replacements made under the guarantee shall bear an additional one year
guarantee dated from the final acceptance of the repair or replacement.
Provide complete warranty information for each item to include product or equipment,
date of beginning of warranty or bond, duration of warranty or bond, and names,
addresses, and telephone numbers and procedures for filling a claim and obtaining
warranty services.
The guarantee is to cover perfect mechanical operation of systems, acceptable noise
and vibration levels, reasonable consumption of power, fuel and water, and perfect
attainment of temperatures and humidity within specified design conditions for HVAC
systems.
If during the guarantee period any equipment or material proves defective or any part
of a system fails to function properly, equipment is to be replaced and defects and
malfunctions corrected as directed by the Engineer.
If during the guarantee period any piece of equipment is replaced or rebuilt, the
guarantee period for this equipment is to be extended for a new period equal to the
original guarantee period.
During the guarantee period, provide necessary skills and labor to assure proper
operation and to provide regular and preventive maintenance for equipment and
controls, on a continuous 24 hour basis.
Act promptly to correct problems arising in operation of equipment or system.
Provide Owner with monthly inspection certificates of equipment, record findings on a
check list and certify that each piece of equipment has been examined, is operating as
intended and has been properly maintained as recommended by manufacturer.
Check all controls monthly to ascertain that they function as designed.
Spare parts for normal wear and tear during guarantee period are to be provided by
Contractor.
Page 10 of 16
PART 2 - EXECUTION
2.01
EXAMINATION
A.
Examine conditions at the job site where Mechanical Work is to be performed to insure
proper arrangement and fit of the work. Start of work implies acceptance of job site
conditions.
2.02
PREPARATION
A.
The Engineers drawings issued with these specifications show the approximate
location of mechanical apparatus, the exact locations are subject to the approval of the
Engineer.
2.03
INSTALLATION
A.
B.
C.
D.
Arrange for chases, slots and openings in other building components during progress of
construction, to allow for electrical installations.
E.
F.
G.
Where mounting heights are not detailed or dimensioned, install systems, material, and
equipment to provide the maximum headroom possible.
H.
I.
Install systems materials and equipment to conform with approved submittal data,
including coordination drawings, to greatest extent possible. Conform to arrangements
indicated by the Contract Documents, recognizing that portions of the work are shown
only in diagrammatic form. Where coordination requirements conflict with individual
system requirements, refer conflict to the Engineer.
Page 11 of 16
J.
Install systems, materials and equipment level and plumb, parallel; and perpendicular
to the other building systems and components, where installed exposed in finished
spaces.
K.
L.
Install access panels or doors where units are concealed behind finished surfaces.
Access panels and doors are specified in Section 15050 - Basic Mechanical Materials
and Methods .
M.
N.
Painting
1. Follow manufacturers recommendations for surface preparation and application
procedures for paints and finishes.
2. Thoroughly clean surfaces requiring prime painting of rust, loose scale, oil, grease
and dirt by the use of wire brushes, solvent and other required means.
3. Do not paint on damp or frosty surfaces or during wet, foggy or freezing weather.
4. Spread and brush paint evenly to eliminate drips, runs or sagging.
5. Fill voids, open or hollow places and irregularities with compound.
6. Thoroughly clean and retouch damaged or dirtied shop coat surfaces.
7. Do not paint controls, nameplates or labels.
8. Paint thickness is measured when dry.
9. Machinery: Before shipment, paint machinery including fans, compressors, pumps
and motors with the manufacturers standard shop prime coat.
10. Piping
a. Prime coat steel and cast iron piping and related pipe supports, immediately after
insulation, regardless of whether or not they will be subsequently covered with
insulation and / or finished paint. Apply prime coat in accordance with
manufactures specifications. Do not prime galvanized metals.
O.
Page 12 of 16
6)
2. Cut remove and legally dispose of selected electrical equipment, component and
materials as indicated, including but not limited to removal of mechanical items
indicated to be removed and items made obsolete by the new work.
3. Protect the structure, furnishings, finishes and adjacent materials not indicated or
scheduled to be removed.
4. Provide and maintain temporary partitions or dust barriers adequate to prevent the
spread of dust and dirt to adjacent areas.
5. Protection of Installed Work: During cutting and patching operations, protect
adjacent installations.
6. Patch existing finished surfaces and building components using new materials
matching existing materials and experienced Installers. Installers qualifications
refer to the materials and methods required for the surface and building
components being patched.
7. Patch finished surfaces and building components using new materials specified for
the original installation and experienced Installers. Installers qualifications refer to
the materials and methods required for the surface and building components being
patched.
2.04
A.
Tests
1. Perform tests on individual equipment, systems and controls in the presence of the
Representatives of the Employer, Engineer and such other parties as may have
legal jurisdiction.
2. Supply labor, materials, properly calibrated instruments, power, etc., required for
testing, unless otherwise indicated.
3. Before conducting any tests on system or equipment, thoroughly clean the
associated systems or equipment just prior to testing.
4. Test equipment and systems which normally operate during certain seasons during
the appropriate seasons. Where the equipment or system under test is interrelated
with and depends upon other equipment, systems, and/or controls for proper
operation, functioning and performance, operate the latter simultaneously with the
equipment or system under test.
5. The duration of tests shall be as determined by authorities having jurisdiction, but
in no case less than the time prescribed in each section of the specifications.
6. In general, apply pressure tests to piping only, before connection of fixtures,
equipment and appliances. Do not subject any piping, fixtures, equipment or
appliances to pressures exceeding their test rating.
Page 13 of 16
7. Promptly repair or replace defective work and repeat the tests until the particular
system and components parts thereof receive the approval for the Engineer.
Replace any damages resulting from tests, as directed by the Engineer.
8. Submit test records on reproducible sheets to the Engineer for approval and include
approved copy in the instruction Manual. The Engineer shall approve the format of
the record sheet prior to actual testing of equipment.
9. During tests of equipment and systems, fully instruct the Employers representative
on the operation and maintenance of the equipment and systems. This period is in
addition to any required special instruction, elsewhere specified.
B.
Final Inspection
1. At final inspection, it is essential that certain trades be properly represented
including the following:
a.
b.
c.
d.
the
the
the
the
2. The Mechanical Contractor shall verify the actual operation of equipment and
controls prior to final inspection
2.05
A.
Thoroughly clean any apparatus before placing in operation. Restore finished surfaces
if damaged and deliver the entire installation in an approved condition.
B.
2.06
A.
Refer to Division 15 Section PIPES AND PIPE FITTINGS for the installation of
pipe sleeves.
B.
C.
Lay out the work in accordance with approved shop drawings. Furnish and set in place,
in advance of placing of slabs or construction of walls, all inserts and sleeves necessary
to complete the Work.
D.
Pipe Sleeves: Unless otherwise indicated or specified, pipe sleeves are to be as follows:
1. General floor sleeves are to be standard weight galvanized steel pipe with bottom
and flush with surface, calked with glass wool and sealed at top and bottom with
Page 14 of 16
butyl mastic. Top end is to extend 25 mm above floor level in mechanical rooms.
Top end of sleeves is to be flush with finished floor surface in finished rooms.
2. Sleeves in Foundation Walls: Cast iron fabricated sleeves, flush inside and outside,
calked water tight.
3. Sleeves in Concrete Walls: Standard weight galvanized steel pipe, flush with wall
surface at both ends, calked with glass wool and sealed at both faces with butyl
mastic.
4. Sleeves in Interior Partitions and Ceilings: 20 gauge galvanized steel with lock
joints.
5. Sleeves for uninsulated piping are to be approximately 20 mm larger than pipe
passing through. Sleeves for insulated piping are to be large enough to
accommodate the full thickness of the pipe covering with clearance for expansion
and contraction.
6. Fire Rated Wall or Floor Sleeves-Galvanized Pipe : Annular space between pipe
and sleeve in the fire rated wall or the fire rated floor is to be packed with fire rated
silicon foam.
E.
Duct Sleeves: Where ducts pass through walls and partitions, provide sheet metal
sleeves and pack tight between duct and opening with fiber glass. The exposed side of
ductwork is to have galvanized 40 mm angle iron closure around duct. The angle irons
are to be secured to the wall construction.
2.08
A.
Excavation and backfilling of trenches required for the installation of all utility services
and underground piping within the building, and to points of connection with exterior
underground utilities outside of the building, are to be performed by each trade for its
work as specified.
B.
Excavate to the required depths and grade, the bottoms of trenches to secure the
required slope for pipe lines. Rock or existing concrete, where encountered, are to be
excavated to a minimum depth of 150 mm below the bottom of pipe. Where mud or
otherwise unstable soil is encountered in the bottom of the trench which is incapable of
supporting the pipe or utility lines, such soil is to be removed to firm bearing and the
trench is to be backfilled with sand to the proper grade and tamped to provide
uniformly firm support. Pipe is not to be laid on frozen subgrade.
C.
Trench Size: Sides of trenches at point 300 mm above the top of pipe is not to be more
than 4/3 overall lateral dimension of the pipe, expressed in millimeters plus 200 mm.
Above this point the sides of trenches are to be kept as nearly vertical as possible and
are to be braced and shored to protect foundations, utility pipe lines and workmen.
Where machines are used to excavate pipe trenches, such machine excavation is to
terminate 75 mm above the invert of the pipe. Final excavation and shaping of the
trench is to be performed only for short distances in advance of the pipe laying.
D.
Separation: Separate trenches are to be provided for potable water and sewer lines.
Page 15 of 16
E.
The trenches are not to be backfilled until the piping has been tested by the Contractor
as required and reviewed by the Engineer and any local authorities having jurisdiction.
2.09
A.
B.
Operate the completed systems for a period of time prescribed by the Engineer to
determinate the capability of the equipment and controls to conform to the
requirements of the drawings and specifications.
C.
Guarantee period for mechanical works shall be one years from the date of issuance of
taking over certificate.
D.
Make final operating tests with systems in simultaneous operation and building in
normal operating modes.
2.10
TRAINING
A.
The Contractor shall instruct and train Owners designated personal in the operation and
maintenance of every part, device and piece of equipment in the systems with emphasis
on proper startup and shutdown procedures, preventive maintenance and lubrication
procedures with recommended lubricants, overhaul and maintenance methods,
adjustment and calibration of instruments and controls, use of special tools and safe
practices.
The duration of training shall be for a total period of ninety working days, eight hours
a day.
This period shall follow the final inspection date and shall not necessarily consist of a
single series of consecutive days. Apportion time between summer, winter, and
intermediate operating seasons as mutually agreed.
B.
All expenses for training Owners personnel shall be at Contractors own cost..
C.
Page 16 of 16
SECTION 15030
ELECTRICAL WORKS FOR MECHANICAL SYSTEM
A.
SCOPE
Supply and install all Electrical Works, equipment and accessories specified under the
various Mechanical Systems.
Electrical Works shall comply with any of the following standards:
ANSI, NEMA, BS, VDE, DIN, IEC, UTE.
Electrical Works for mechanical systems shall comply with SBC requirements.
All electrical equipment, materials, accessories, etc,... to be supplied for the
Mechanical Systems, as well as all electrical works and tests to be done shall conform
also with the requirements of the relevant Specifications for the Electrical Systems.
The scope of the Electrical Works under this section and executed by the Mechanical
Contractor includes the supply and installation of the followings:
B.
a.
Motor control centers, motor control panels for each item or system and
housing all protection gear, switches and controls required for the specified
function.
b.
All cables and wires between equipment and the corresponding motor control
center or motor control panel.
c.
C.
a.
Power close to each electrically operated equipment not fed from a control
panel.
b.
Main feeder to the motor control centers and control panels of mechanical
equipment.
GENERAL REQUIREMENTS
a.
Ratings of circuit breakers serving electric motors are design values and must
be checked and readjusted, if need be, to conform with motor actual power and
rating as recommended by motors Manufacturers.
Page 1 of 11
b.
c.
Cables shall be color coded for identification. Red, Yellow and Blue shall be
used for phase conductors, Black for neutral and Green for earth conductors.
d.
Control voltage for starters and control circuits shall not exceed 240 volts.
e.
ii.
iii.
iv.
v.
vi.
f.
g.
h.
Rigid conduits are not to terminate in nor be fastened to a motor frame or base.
j.
k.
l.
Conduits are not to cross pipe or vent shafts, ducts or openings. They are to be
run a minimum 100 mm away from pipes of non-electrical services.
m.
n.
Page 2 of 11
D.
p.
q.
r.
s.
t.
u.
v.
CONDUITS
Size is to be minimum 20 mm unless otherwise specified.
Steel conduits are to be welded, drawn, heavy gauge, to BS 4568 Part 1 or approved
equal, galvanized internally and externally and threaded both ends.
Fittings for steel conduits are to be threaded, galvanized or cadmium plated malleable
iron specifically designed for size and type of conduit.
E.
Page 3 of 11
Armored cables to have the armor as single layer of galvanized steel wire under the
PVC sheath.
Connections to motors to be single conductor wires pulled inside conduits or multicore
cables armored or no armored and fixed on cable trays or supports.
Special conditions: where required high temperature resistant cables, silicone rubber,
cross linked polyethylene, MICC, or approved equal, corrosion resistant sheath is to be
provided.
F.
ELECTRIC MOTORS
Motors are to be supplied by driven equipment manufacturer, to be as specified for
equipment concerned and specifically supplied for available supply voltage and
frequency.
Motors 1/2 horsepower and under to be single phase and over 1/2 horsepower to be
three phase. Motors to be totally enclosed, fan cooled type, unless otherwise specified.
Motors are to have Class B insulation as a minimum requirement as defined in IEC 85
and
IEC 34-I.
Motors that will operate outdoors are to have Class F insulation.
Motors operating in ambient temperatures exceeding 45 deg. C to be tropicalized and
derated for satisfactory operation.
Motors to be rated for continuous operation.
Power to be adequate to operate driven equipment without motor overload under all
operating conditions and loads and throughout capacity range of equipment. Motor to
be capable of delivering full rated output when operating at voltage deviating by 5%
from rated voltage at rated frequency.
Starting and torque characteristics to be as required by driven equipment.
Speed to be as specified for equipment concerned.
Conduit terminal box on motor to be approved model for type of motor enclosure.
Motor windings to be connected to terminals in terminal box at factory. One additional
earthing terminal to be connected to motor frame.
Motor base to be adjustable where motors are directly connected to driven equipment,
unless otherwise specified. Motors connected to equipment through V-belt drive to
have adjustable sliding base. Fractional horsepower motors to have slotted mounting
holes in base.
Page 4 of 11
G.
STARTERS
The starting current of all motors above 10 hp shall not exceed twice its rated full load
current, for 15 seconds. For motors of rating 10 hp and below, the starting current shall
not exceed 6 times its rated full load current, for 5 seconds.
In general, motors above 10 hp shall have assisted start in the form of Star-Delta
starters of the close transition type. Motors below 10 hp can be Direct on line Start.
Motors above and including 50 HP should be assisted by soft-starter.
Each three-phase motor shall be provided with means of automatic starting and to
disconnect the supply to the motor in case of:
a. Failure of one or more phases.
b. Serious drop in voltage.
c. Flow of excess current.
All starters shall be properly derated for operation in an ambient temperature of 45C.
All starters shall be of the magnetic automatic type fitted with thermal over load
relays/devices calibrated for close motor protection.
These devices shall trip the starters in case of overload and shall not allow it to reset
except manually.
The starters shall be capable of making and breaking their rated current adequately and
shall withstand as high as 5 times their rated current for at least 10 seconds without any
injury or failure.
Starters shall be fitted with On/Off/Fail Pilot lights, start and stop push buttons,
Hand/Off/Auto selector where required. All starters shall be provided with contacts for
BMS control and signaling (start/ stop and fault). Contacts to be provided to show the
position of the selector switch on BMS.
The contactors shall be capable of withstanding an intermittent duty and the number of
switching cycles required in the Standards. They shall be AC3 duty rated.
The contactors shall be provided with auxiliary contacts for connection of signaling,
interlocking, and other circuits required for controls.
The enclosures of the contactors, starters, etc., as well as their installation and
accessibility for operation and repair shall be suitable for the corresponding motors
with which they are related.
The contactors shall be suitable for mounting in any position. The contacts shall be
silver plated, bounce free and fully enclosed.
All motors control gear and ancillary equipment shall be protected by thermal and
magnetic circuit breakers in addition to the protective starter mentioned above.
Where starter operating circuits and ancillary apparatus are energized by an auxiliary
supply other than the main power circuit to the motor, the isolator shall also incorporate
auxiliary contacts to effectively isolate all poles of phases of such other power supply.
Page 5 of 11
All Starters not in a central panel shall have a sheet metal enclosure with a removable
lid and cover and necessary brackets for mounting on panel or wall. A clear schematic
diagram of the starter circuit shall be fixed inside the cover of each starter.
H.
ISOLATING SWITCHES
Isolating switches to be non fusible, single throw type, housed in separate metallic
enclosure, with arc quenching devices on each pole capable of interrupting at least six
times its rated current. They are to simultaneously interrupt power supply to all line
conductors, any neutral and control circuits.
Isolating switches for single phase fractional horsepower motors to be single pole,
dolly operated type, rated 15/20 A at 250 V AC, quick make, quick break, with silver
alloy contacts, flush or surface mounted to suit application. They shall be AC3 duty
rated.
Operating mechanism to be quick make quick break type, with external operating
handle mechanically interlocked with enclosure cover to necessitate disconnecting
switch to be in OFF position for access to inside of enclosure. Means are to be provided
for by passing interlocks. Position of isolating switch to be clearly indicated on cover.
Isolating switches for motors with star/ delta starting shall be interlocked with the
starter control circuit to reset the starter to the star connection in a way to prevent the
starting of the motor on delta connection after closing the switch.
Enclosure to be general purpose type, unless otherwise indicated or required, with
provision for locking operating handle in OPEN and CLOSED positions.
Enclosures where indicated or required by location to be weatherproof totally sealed
water and dustproof type.
J.
Page 6 of 11
K.
PUSH BUTTONS
Push buttons to be one unit momentary contact START/STOP with normally open or
normally closed contacts as required by wiring diagrams and with lockout attachments.
Heads to be color coded and STOP button to be protected. Push buttons controlling one
piece of equipment to be housed in separate enclosure.
L.
RELAYS
Relays to be multipole with normally open or normally closed contacts, electrically
operated at 240 V maximum, and magnetically held. Contacts to be double break,
silvered type, interchangeable from normally open to normally closed without
additional parts. Relays are to be rated at 10 A, 600 V.
M.
CIRCUIT BREAKERS
Circuit breakers to be thermal magnetic type, with molded case, manually operated for
normal switching functions and automatically operated under overload and short circuit
conditions.
Circuit breakers to give positive trip free operation on abnormal overloads, with quick
make quick break contacts under both manual and automatic operation. Stationary and
movable contacts to be non welding silver alloy adequately protected with effective
and rapid arc interruption.
Branch circuit breakers to be minimum 125 A frame size, unless otherwise shown.
Main circuit breakers to be 125 A frame size or larger as shown on the Drawings.
Breakers of 250 amp frame size and larger to have electronic trip units.
Main incoming breakers to be current operated, earth leakage type, or suitably
equipped to provide earth fault protection. Earth fault detection and interruption to be
time coordinated with those of main incoming breaker on main distribution board.
Multiple pole breakers to have single handle mechanism. Each pole to have inverse
time delay thermal over current trip element and magnetic instantaneous over current
trip element for simultaneous tripping of all poles.
Trip elements to be ambient temperature compensated type.
N.
Page 7 of 11
Enclosure shall have provision for locking the operating handle in the OPEN and
CLOSED positions.
MCC shall be constructed such that all compartments doors are interlocked preventing
access to the starter until the corresponding isolating switch or breaker is in the off
position.
Motor control centers are to be provided with Automatic transfer switches.
Construction to be 2 mm thick sheet steel, adequately reinforced and braced for
maximum rigidity, sand blasted, rust inhibited after fabrication and sprayed with one
coat primer and two coats enamel internally and externally.
Components motor control centre to include the following:
1.
Main incoming circuit breaker or isolating switch as shown on the Drawings
for terminating incoming supply cables and isolating the bus bar system
2.
Main copper bus bars rated as main incoming circuit breaker or as shown on
the Drawings
3.
Branch copper bus bars of adequate capacity to distribute power to each circuit
breaker and starter served
4.
Neutral copper bus bar rated at half capacity of main bus bar and distributed
throughout whole motor control centre
5.
Earth copper bus bars to be minimum half the neutral bus bar rating extending
full length of motor control centers
6.
7.
8.
9.
10.
Bus bars to be adequately isolated and braced to sustain maximum possible short
circuit current.
Compartment doors to be interlocked so that isolators or breakers must be in OFF
position before door can be opened.
Spare positions to be fully equipped cells ready for connection to motors are to be
provided in adequate number.
Space positions to be fully equipped cells ready to receive control unit are to be
provided in adequate number. Space positions to have blank cover plates.
Page 8 of 11
Q.
SWITCHES
Float switches to be level operated, heavy duty, bracket mounted type, suitable for
application in open tanks, complete with 178 mm spun copper float, brass rod, two
stops, floor mounting stand, lever and counterweight. Switch to have oil tight and dust
tight enclosure and 2 pole double throw silver contacts that open on liquid rise.
Pressure switch to be industrial, heavy duty, bellows actuated type, suitable for water
service, with contacts to close on falling pressure. Range to be 0.1 to 8 kg/cm2. Switch
to be good for 1720 kPa operating pressure and to have 6 mm pipe tap bottom
connection. It is to have oil tight and dust tight enclosure, single pole double throw
contacts and setting adjustment.
Page 9 of 11
Low suction pressure switch to be industrial, sensitive, low range, diaphragm actuated
type, suitable for water service, with range of 2 to 20 kPa of falling pressure, preset at
factory to 3 kPa. Switch to be good for 690 kPa operating pressure and to have 6 mm
pipe tap bottom connection. It is to have oil tight and dust tight enclosure, single pole
double throw contacts, range adjustment knob, sealing cap and range locking nut.
R.
SWITCHBOARD INSTRUMENTS
1. General.
Instruments shall be supplied and arranged as called for on the drawings and herein
specified.
All instruments shall be housed in identical 4 inch white enameled square metal
cases suitable for switchboard flush installation.
Instruments shall be with linear scales and markings in according.
Instruments shall be suitably protected and sealed for tropical use.
Accuracy of all instruments shall be within 1% unless otherwise specified.
2. Voltmeters
Voltmeters shall be moving coil type 90 scale and a center zero adjuster.
Voltmeters shall be fitted with a rotary type 7-position selector switch permitting
both line to line and line to neutral readings and OFF position.
3. Ammeters
Ammeters shall be moving coil shunt operated type with 90 scale and center zero
adjuster.
4.
Page 10 of 11
6. Current Transformers
Current transformers shall be suitable for withstanding thermal and dynamic
stresses due to switchgear short-circuit currents. Current transformers connections
to protective and control devices and all outgoing current terminals shall be by
means of terminals which can be short circuited, isolated, and in addition provided
with plug in test points for portable instruments.
Unused secondary terminals shall be short-circuited. Additional taps on current
transformers shall be wired to the outgoing terminal block.
The current transformer range shall match the associated device.
END OF SECTION
Page 11 of 11
SUMMARY
A.
Provide labor, materials, equipment and services, and perform operations required for
complete installation of basic mechanical materials and related work as indicated on
the drawings and specified herein.
B.
Related Work
Division 15:
Division 16:
C.
Mechanical
Electrical
Work Included: The work shall include, but not be limited to, the following:
1. Excavation for underground utilities and service.
2. Miscellaneous metals for support of mechanical materials and equipment.
3. Access panels and doors in walls, ceilings and floors for access to mechanical
materials and equipment.
4. Mechanical equipment nameplate data.
1.02
QUALITY ASSURANCE
A.
Materials and equipment shall conform to the latest edition of reference specifications
specified herein and to applicable code and requirements of local authorities having
jurisdiction.
1.03
SUBMITTALS
A.
Submit the following submittals in accordance with Section 15010 Basic Mechanical
Requirements.
B.
C.
Shop drawings detailing fabrication and installation for metal fabrications, and wood
supports and anchorage for mechanical materials and equipment.
D.
Coordination drawings for access panel and door locations in accordance with
Section15010 Basic Mechanical Requirements .
E.
Page 1 of 4
service, and details for dust, fire and noise control. Coordinate sequencing with
construction phasing and Employer occupancy specified in the contract Documents.
1.04
A.
Deliver joint sealer materials in original unopened containers or bundles with labels
informing about manufacturer, product name and designation, color, expiration period
for use, pot life, curing time and mixing instructions for multi-component materials.
B.
PART 2 - PRODUCTS
2.01
MATERIALS
A.
B.
Sealant
1. Provide ready-to-use silicone penetration seal that will stop passage of fire, smoke,
and water will cure in the presence of atmospheric moisture to product durable and
flexible seal, and will form airtight and watertight bonds with most common
building materials in any combination including cement, masonry, steel, and
aluminum.
2. Sealant Composition shall be one-part ready-to-use materials with consistency of
soft caulk at temperatures ranging from -35 to 160 F, and extension and
compression properties of plus/minus 40% of original gap.
C.
Access Doors
1. Steel Access Doors and Frames: Factory-fabricated and assembled units, complete
with attachment devices and fasteners ready for installation. Joints and seams shall
be continuously welded steel, with welds ground smooth and flush with adjacent
surfaces.
2. Frames: 16-gauge steel, with a 1 inch wide exposed perimeter flange for units
installed in unit masonry, precast or cast-in-place concrete, ceramic tile or wood
paneling.
a. For installation in Masonry, Concrete, Ceramic Tile, or Wood Paneling : 1 inch
wide exposed perimeter flange and adjustable metal masonry anchors.
Page 2 of 4
EXAMINATION
A.
Examine conditions at the job site where work of this section is to be performed to
insure proper arrangement and fit of the work. Start of work implies acceptance of job
site conditions.
3.02
PREPARATION
A.
Examine the Contract Drawings and Specifications in order to insure the completeness
of the work required under this Section.
B.
Verify measurements and dimensions at the job site and cooperate in the coordination
and scheduling of the work of this Section with the work related trades, so as not to
delay job progress.
C.
Provide templates as required to related trade for location of support and anchorage
items.
D.
3.03
A.
B.
Page 3 of 4
3. Location
a. Locate access doors in hung ceilings, walls, furred spaces, partitions and other
components of the structure, where required to service fire dampers, smoke
detectors, duct access doors, controls, valves, cleanouts and other items
installed under this Division of the specification.
b. Contractor shall coordinate the exact location and quantity with Mechanical
and Electrical requirements. Access doors are not required in suspended
acoustical lay-in tile ceilings unless specifically shown.
3.04
A.
Inspect seal after 48 hours for complete adhesion, and seal and correct any deficiencies.
B.
C.
Inspect seal after 24 hours. Remove damming materials to inspect under site.
D.
3.05
A.
Clean excess cured sealant from nonporous surfaces with commercial solvent such as
naphtha mineral solvents, following instructions on container label.
B.
Clean spills of liquid components with high-flash mineral spirit solvent, following
instructions on container label. Trim excess foam with sharp knife or blade.
C.
Remove equipment, materials and debris. Leave area in undamaged, clean condition.
END OF SECTION
Page 4 of 4
WELDING
SECTION 15051
PART 1 - GENERAL
1.01
RELATED WORK
A.
1.02
SYSTEM DESCRIPTION
A.
This section covers the standard of shop welding and erection welding of mechanical
equipment, steel structure, framework, supports and piping.
1.03
REFERENCES
A.
Reference Standards
The latest editions of the following standards and recommendations shall apply in
applicable parts.
1. American Standards
a. American Welding Society (AWS)
AWS B 1.0
AWS B 3.0
AWS D 10.4
Recommended practices for welding austenitic chromiumnickel stainless steel piping and tubing.
AWS D 10.9
Page 1 of 3
1.04
SUBMITTALS
A.
Product Data
1. All electrode rode types, and sizes shall be given indicating the intention of use.
B.
Qualified Staff
1.
The name, certificates of standard of welding obtained, and picture of each welder to
be used in a list indicating the level of welding the person is intended to be used for.
A simple, clearly shown, overall identification system to indicate the individual
capacity of experience.
2.
PART 2 - PRODUCTS
2.01
OPERATORS
A.
Each operator shall wear an identification system to indicate their level of experience.
Operators shall be certified welders or from an approved governmental institute.
Records of the welding procedures and welder performance qualification tests for work
done shall be maintained by the Supplier for review.
The method and procedure adopted for welding in workshops and at the site shall be
approved before production starts.
The applicable parts of the following documents from the American Welding Society
shall apply:
AWS B 3.0
AWS D 10.9
ANSI / AWS B 4.0
B.
Processes
1. Carbon Steel
Manual shielded, metal-arc, submerged arc, gas metal -arc, flux-cored arc, gas tungsten
arc, and other applicable welding processes and methods may be used in the
construction and fabrication of welded carbon steel equipment shall as far as possible
be prefabricated in the workshop. Use electrodes for steel 6010 root pass and 7018
filler pass, and for copper use 15% silver electrodes for copper brazing, and non lead on
antimony rod for solder.
For the welding of carbon steel piping, ANSI Code B 31.3 shall apply.
Page 2 of 3
PART 3 - EXECUTION
3.01
A.
B.
3.02
TESTS
Contractor shall execute X-ray test at random as requested by the Engineer for 50
welds. If tests fail Contractor shall redo the X-ray test after re-welding till the Engineer
is satisfied.
END OF SECTION
Page 3 of 3
RELATED WORK
A.
Division 15 - Mechanical
1.02
SYSTEM DESCRIPTION
A.
This section covers the general piping and fittings supply and installation required for
the works.
1.03
REFERENCES
A.
Reference Standards
The latest edition of the following standards:
1. American Society for Testing and Materials (ASTM):
a. ASTM A53B Welded and Seamless Steel Pipe for Ordinary Use, Specification
for Black and Hot Dipped Zinc Coated.
b. ASTM B88 Specification for Seamless Copper Water Tube.
2. American National Standards Institute (ANSI): Standards as specified herein.
3. Manufacturer's Standardization Society (MSS): Standards as specified herein.
4. American Welding Society (AWS): Standards as specified herein.
5. American Petroleum Institute (API): Standards as specified herein.
1.04
SUBMITTALS
A.
Product Data:
Descriptive literature for each of the actual proposed material to be used
including:
1.
2.
3.
4.
5.
B.
Shop Drawings
Shop drawings for each of the actual proposed systems shall include the
following:
1. Working or manufacturing drawings.
2. Calculations
Page 1 of 24
3. Installation details
4. Connections to other services
5. Accessories available indicating those included
6. System diagrams.
1.05
QUALITY ASSURANCE
A.
Qualify welding processes and operators for structural steel according to AWS D1.1
"Structural Welding Code--Steel".
B.
Qualify welding processes and operators for piping according to ASME "Boiler and
Pressure Vessel Code", Section IX, "Welding and Brazing Qualifications".
1. Comply with provisions of ASME B31 Series "Code for Pressure Piping".
2. Certify that each welder has passed AWS qualification tests for the welding
processes involved and that certification is current.
3. Submit welder certificated signed by the Contractor certifying that welders comply
with the requirements specified above.
1.06
A.
B.
PART 2 - PRODUCTS
2.01
PIPES
Service
Pipe Material
1.
2.
Chilled Water
3.
UPVC - 16 bar
4.
5.
6.
7.
8.
Refrigerant Pipes
Copper Type L.
9.
10
UPVC 16 bar
11.
12.
13.
Pool Pipes
14
Expansion Pipes
15
16
17
18
19
B.
Sizes
1. Unless otherwise specified pipework of 65 mm nominal bore and over shall be
welded, while 50 mm nominal bore and below the pipework shall be screwed.
Page 3 of 24
2.02
PIPING MATERIALS
A.
Copper Piping
a. Pipe work shall be Type K hard temper copper tubing conforming to ASTM B
88, or table Y to BS 2871 with PVC coating or tape.
b. Copper fittings shall be streamlined wrought copper solder type of pattern to suit
requirements (ANSI B 16.22).
c. Flanges for copper pipes shall be cast bronze with raised ground face and bolt hole
spot faced. Flanges shall be rated for 1.5 MPa water working pressure.
d. Gaskets shall be of a material suitable for the fluid, temperature, and pressure for
which they will be used.
e. Lead-and antimony based solders should not be used for potable water system.
Brazing and silver solders should be employed. Use 15 % silver rods for brazing.
B.
C.
Page 4 of 24
f.
Pipe wall thickness and weight for medium class pipes shall be as follows:
Pipe Size
(inches)
1/2
3/4
1
1 1/4
1 1/2
2
2 1/2
D.
Thickness
(mm)
2.65
2.65
3.25
3.25
3.25
3.65
3.65
E.
Pipe fittings shall be UPVC of the same weight and quality as the pipe.
c.
All pipes and fittings shall be marked with the Kite Mark of the standard to
which they are manufactured.
d.
Unless specifically stated otherwise, pipes and fittings for drainage works shall
be suitable for rubber ring pressure joint. Sealing rings to be rubber to BS 2494
Part 2.
Page 5 of 24
F.
G.
H.
CPVC pipes shall be Chlorinated Polyvinyl Chloride (PN 20) conforming to DIN
8087 or to ASTM F441 schedule 80.
b.
Pipe fittings (tees, elbows, crosses, reducers, unions, flanges, etc,...) shall be of the
same weight and quality as the pipe.
I.
2. Mechanical Joints:
When making a mechanical joint a check shall be made to ensure that the depth of
entry mark is indicated on every spigot before insertion into the socket, so that the
spigot enters the socket within 13/25 mm of the bottom of the socket.
Page 6 of 24
The spigot end of the pipe shall be chamfered to half the wall thickness and made
with suitable hand tools provided by the manufacturer
When making a mechanical joint care shall be taken to ensure that the seal ring is
not misplaced.
Due allowance shall be made for the control of thermal movement.
3. Solvent Joints:
When making a solvent joint the spigot and sockets shall be wiped clean and
thoroughly degreased with cleaner to remove oil, grease, etc,. after which the spigot
and socket shall have solvent adhesive applied.
The sockets and spigots shall be assembled as quickly as possible after applying the
adhesive and within forty seconds after which it shall be held together for up to five
minutes.
Special care shall be taken to prevent dirt and rubbish entering the open ends of
pipes during erection. Wrought iron screwed caps or plugs, or plastic covers only
shall be used. Wood, rag or paper plugs shall not be used. Failure to comply with
this instruction shall mean that the Engineer shall have the right to order the
pipework to be dismantled for as far as considered necessary and the pipework to
be cleaned internally. Such work shall be carried out by the Contractor and all cost
shall be borne by the Contractor.
The Contractor is reminded that the valve fitted to the open end of disconnected
pipes is not considered satisfactory to prevent the entry of rubbish. The open end
shall be capped, plugged or crimped.
2.03
A.
General
1. Refer to individual piping system sections for required pipe fittings and specialties
not covered herein.
2. Fittings whether black, galvanized, copper or brass shall be compatible with the
pipe work system they are connected to.
3. Iron fittings shall be generally of the malleable iron type: while steam and
condensate services shall use wrought iron fittings.
B.
3. Unless otherwise stated, elbows shall be long radius bends with a radius of 1.5
times the nominal size, and shall be smooth and not made of welded segments.
4. Tees up to and including an outside diameter of 323.9mm shall be of the pressed
type.
5. Unless otherwise specified, reducers shall be made with a length L = 3 (D-d),
where L is the construction length, D the outer diameter of the large end and d that
of the small end. Unless otherwise stated, the wall thickness of a reducer shall be
the same as that of the adjacent large straight pipe.
C.
Flanged Joints
1. Flanges shall, unless otherwise stated be welding neck over 100mm pipe or slip on
weld for 100mm pipe and under, with raised faces complying with ANSI B16-5.
Screwed flanges can be used, but welded flanges shall be preferable.
2. The material of the flange shall be compatible to the pipe and service the flange is
connected to.
3. Galvanized flanges are to be screwed wherever possible. If this is not possible,
black steel flanges are to be welded to the pipe work in the normal way and before
final fitting; the whole prefabricated section shall be proprietary hot dipped in a
galvanized bath depositing the amount of zinc specified for the galvanized tube.
4. Corrugated brass rings for flanged joints shall match the pair of flanges they are
gasketting and shall be used between the flange faces to form the seal.
D.
E.
Page 8 of 24
F.
Unions
1. Unions in steel pipe other than steam piping shall be malleable iron and have
female pattern, brass to iron seat, and ground joint, for 65mm and smaller, and
flanged connections for larger than 65mm. Unions shall be rated for minimum of
1.5 MPa water working pressure. Threaded unions for steam & condensate pipes
shall be used for pipes up to 32 mm only.
2. Unions in copper piping shall be cast bronze, female pattern, brass to brass seat and
ground joint threaded end connections for 50mm and smaller, and flanged
connections for larger than 50mm. Unions shall be rated for minimum of 1.0 MPa
water working pressure.
2.04
A.
The contractor should verify that the pipe supported weight does not exceed
the recommended maximum load of the clamp as provided by the
manufacturer. The clamps should consist of two half rings suitably connected
with welded on connection nut for fixing the clamp to the threaded rod. Where
copper pipes, hot water and chilled water steel pipes are used, the rings should
provide with a pre-fitted rubber inlay with suitable temperature resistance
characteristics for the application.
d- Pipe Hangers for Sprinkler Fire Fighting Systems: Galvanized band hangers
and screw clamping pipe rings should be used for supporting fire-fighting
system. The system should be approved for loading as per UL, FM regulations
for Fire Fighting Systems.
e- Threaded Rods used should be manufactured as per DIN 976 of Steel Grade
4.6, galvanized and used to support pipe duct ring clamps onto the C-channel
or directly to concrete anchors depending on the application. The threaded
rods, nuts and flat washers used should have a clean thread and flawless
galvanized condition.
f- Concrete Anchors: Internally threaded Anchors used for fixing threaded rods
and pipe clamps should be made from galvanized steel, anchors should have a
flared end for accurate setting flush with the surface, and should have an
intelligent expansion selection that adapts to suit strength of the base material.
Concrete stud anchors should be used for fixing C-channels to the concrete
suitable for through in-place fattening with reliable fixing. All Concrete
anchors used should be provided with full load characteristics and used in
accordance with manufacturer recommendations with regards to application
and setting details. Concrete Anchors should also be fire rated to verify that
they can withstand the required loads within the fire integrity limits of the
supporting building structure.
g- For riser pipes, Anchor Fixed Point Clamps should be used to support the
weight of the riser pipe. Fixed Point Clamps should be used in location as
recommended by supporting system manufacturer and approved by the
Engineer.
B.
C.
Hanger Rods
1. Galvanized solid steel, all thread rods, with lock-nuts.( 10mm dia. Per pipe)
2. For trapeze supports submit calculation for threaded hager rod diameter with at
least 8 times load factor.
Page 10 of 24
D.
E.
F.
Trapeze Hangers
1. Where numerous pipes are run in parallel to one another, they may be supported
from a trapeze type hanger arrangement. Rollers supports shall be used to support
each run of piping on trapeze hangers to permit independent movement of
individual pipes.
2. Piping supports shall consist of channels, fittings, pipe brackets, pipe rollers, pipe
clamps, post bases, stud nuts, etc., as required to properly support and hang piping.
G.
Stiff-legs or Stanchions
1. Stiff-legs or two-leg stanchion supports shall be provided in cases where support
from overhead structure is not possible. Pipe rollers shall be provided for pipe
rigidly supported from floor.
H.
Alignment Guides
1. Guides to be constructed with steel base and T-bar with Teflon or graphite plates
bonded to the steel components to allow minimum static friction and selflubrication for unlimited movement. Units shall be factory painted. Guide base
shall be welded to the pipe; like F & S "Unislide", Elcen, or equal.
Page 11 of 24
I.
J.
K.
HORIZONTAL (m)
BORE mm
STEEL
10-12
15
20-32
40-50
65-80
100 &
above
1.8
2.4
2.4
2.5
2.5
COPPE
R
1.0
1.2
1.8
2.4
2.5
2.5
VERTICAL (m)
UPVC
STEEL
0.8
0.8
1.0
1.2
1.2
2.5
2.5
2.5
2.5
2.5
COPPE
R
1.2
1.8
2.4
2.5
2.5
2.5
UPVC
0.8
1.0
1.5
1.7
1.7
A.
All openings through fire rated walls, ceilings and floors due to penetrations
of mechanical installations as well as those due to construction joints,
should be sealed with fire rated products suitable for the specific application
as specified hereunder.
B.
The product shall be capable of stopping the passage of fire, smoke, air and
water through wall, floor and ceiling penetrating, cladding and expansion
joints. The product shall exhibit the minimum designed fire resistant
properties.
Page 12 of 24
C.
D.
Metal pipe bare or insulated: the annular space around the pipe shall be
packed with fire rated high density backing material such as RockWool
and the ends shall be filled and sealed with fire rated intumescent
mastic, or Elastic sealant according to UL, FM, or BS and manufacturer
data to attain the required rating. The size of the circular opening shall
be maintained as the barest minimum as recommended by the mastic
manufacturer.
2.
Page 13 of 24
2.06
PIPE SLEEVES
A.
General
1. Sleeves for all pipes passing through floors, walls, partitions, (except where floors
and walls are a part of fire-rated assembly) concrete beams, girders, and any other
building construction shall be provided in types as described below, and of
adequate diameter to allow minimum of 19mm clearance all around between sleeve
and pipe. When pipe is insulated, insulation shall pass continuously through sleeve
with 19 mm clearance between insulation and sleeve.
2. Pipes passing through fire-rated walls, partitions, or floor shall be sealed, smoketight, with a fire proof compound. Insulation shall not pass through the sleeve as
specified above. Fill inner space with Rockwool insulation with fire rated
compound up to the rating of the wall.
3. Allow 50 mm of steel sleeve above F.F.L, and flush with walls.
B.
FLASHING
A.
B.
Lead Flashing: 24.5 kg/m2 (5lb/sq.ft.) sheet lead for waterproofing, 5kg/m2 ( 1
lb/sq.ft.) sheet lead to sound proofing.
C.
D.
Caps: Steel, 22 gauge (0.80 mm) minimum, 16 gauge (1.50 mm) at fire resistance
structures
2.08
SEALANTS
A.
Page 14 of 24
3. Acrylic Latex: one part, gun grade, paintable, with a temperature range from -17 to
+82 degrees C.
4. Butyl: one part, gun grade, suitable for both horizontal and vertical joints.
5. Fire rating compound similar to wall rating and as described under paragraph 2.05
of this section.
2.09
COMPENSATORS
A.
General
1. All compensators shall be selected for the function it is to perform and the
suitability for the fluid type; pressure and temperature to be conveyed.
2. The compensator shall be the same size bore as the pipework it shall be connected
to, and shall have flanged connections for ease of maintenance.
B.
Isolating Compensators
1. This type of compensator shall be to isolate a treated vibrating piece of equipment
from the pipework system. The compensator shall not allow for any expansion and
contraction movement nor misalignment of interconnecting flanges.
2. The single neoprene rubber convolution and rubber facing flange in a single
molding shall have a mild steel backing flange.
3. The compensator shall be capable of a working pressure of 1.5 MPa and a
temperature range of -15 to 90C.
4. This type of compensator shall be suitable for vibration and noise control on
LPHW, chilled water and HWS systems.
C.
Axial Compensators
1. This type of compensator shall absorb movement under strict guiding in an axial
direction only. No side thrusts can be permitted.
2. The stainless steel convolutions of the number required to accommodate the
determined movement shall be protected internally and externally by a heavy mild
steel sleeve for physical protection against damage.
3. The compensator shall be capable of a working pressure of 2.5 MPa and a
temperature range of -15 to 400C.
4. Large expansion compensators capable of up to 200mm shall be considered to keep
the number of compensators to a minimum.
5. This type shall be suitable for LPHW, steam, condensate, chilled water, HWS in
long straight runs such as crawlways and service tunnels.
D.
Angular Compensators
Page 15 of 24
1. This type of compensator, similar to the axial, has a hinged restrain in one plane
only. When used in a controlled condition with more than one compensator
together with natural pipe movement it shall allow for large movement with
minimum thrust upon the anchor points.
2. The stainless steel convolutions shall be protected with an internal lining.
3. The compensator shall be capable of a working pressure of 1.5 MPa and a
temperature range of -15 to 400C.
4. This type of compensator shall be suitable for LPHW, steam, condensate, chilled
water, and HWS where the pipework can have natural 90 bends incorporated
between anchor points.
E.
Articulated Compensator
1. This type of compensator is a purpose made unit containing two axial compensator
units contained within a set of hinged tie bars which together with natural pipe
curving movement permits a controlled angular expansion movement with
minimum internal pressure on the axial compensator and the least external thurst
upon the anchor point.
2. The stainless steel convolutions shall be protected with an internal lining.
3. The compensator shall be capable of a working pressure of 1.5 MPa and a
temperature range of -15 to 400C.
4. This type of compensator shall be suitable for LPHW, steam, condensate, chilled
water, and HWS where the pipework can have natural 90 bends incorporated in a
limited space with little thrust upon pipe anchors, in cases such as equipment
rooms adjacent to equipment connection.
2.10
A.
Where metal chilled pipes are subject to thermal expansion, particular attention should
be given and pipe runs should be studied and designed to compensate for the expansion
forces and reduce the stress on the pipes and supporting system.
B.
The contractor should provide sufficient shop drawings and load calculations to verify
the suitability of the system for critical thermal applications run as per the engineers
requirement. Allowance for free thermal expansion distance at pipe bends should be
marked.
C.
ACCESSORIES
A.
B.
Page 17 of 24
PART 3 - EXECUTION
3.01
PIPING INSTALLATIONS
A.
General
1. Installation instructions contained in this Section pertain to most systems. For
specific requirements for installation of each system, refer to individual system
specification sections.
B.
13. High points in closed piping systems shall be vented by Automatic air vents.
Drainage piping shall slope as required by code or as indicated. Steam and
condensate shall slop down in direction of flow 12 mm per 500 mm unless
otherwise indicated. Slope water piping up in the direction of flow 12 mm per 500
mm.
14. Piping shall be cut accurately to measurements established at the site, worked into
place without springing or forcing, and shall clear all windows, doors and other
openings. Cutting or other weakening or building structure to facilitate piping
installation is not permitted; install to permit free expansion and contraction
without damage.
15. Swing joints at run outs to equipment and risers. Provide expansion loops at all
other points for flexible piping systems.
16. Drain piping from pump glands, relief valves, condensate drain pan etc., to spell
over open sight drains, floor drains, or other acceptable discharge points
terminating drain line with plain end ( unthreaded ) pipe.
17. Provide necessary temporary connections, valves, oversize flushing connections,
pumps, etc., as required to properly clean and test systems.
18. Coordinate piping installations with ductwork, structure, lighting, electrical conduit
and all other materials and equipment.
19. Use flexible pipe connectors for all inlet and discharge final connections to pumps
(except in line pumps) and other vibration producing equipment.
20. Provide flanges on all valves, apparatus, and equipment having 50 mm and larger
connections.
21. Reduction in pipe sizes except in drainage pipe, shall be made using eccentric
reducer couplings installed with the level side up on water piping and level side
down on steam and condensate piping.
22. Provide unions adjacent to each valve at the final connection to each piece of
equipment of plumbing fixture having 50 mm and smaller connections and where
otherwise indicated.
23. Wherever wells are installed in piping for thermometers, pressure gages, probes,
etc., pipe size shall be increased by one pipe diameter to accommodate same.
24. Provide air chambers at the top of all hot and cold domestic risers, at the end of
each water header in utility spaces, at the end of each branch line, and at the top of
all branches to fixtures. Provide shock absorbers at each solenoid valve or piece of
equipment that has a quick closing type valve. Air chambers shall be a minimum of
two pipe sizes larger than the terminating pipe and shall be equipped with an
accessible drain valve and air recharging petcock or installed at least 600 mm
above fixture to permit recharging by draining air chamber.
Page 19 of 24
25. Use fittings for all changes in direction and all branch connections and take - off
from mains. Changes in direction and branch connection in welded piping shall
conform to Section 15051 Welding.
26. Connect dissimilar piping material using dielectric unions or insulating flanges.
C.
ROD DIAMETER
12 mm through 50 mm
60 mm and 75 mm
100 mm and 125 mm
150 mm
200 mm through 250 mm
300 mm
9 mm
12 mm
15 mm
19 mm
22 mm
25 mm
Page 20 of 24
10. Rods for trapeze hangers supporting several pipes shall be sized for the equivalent
load.
11. Hangers rods shall be attached to structural members of the building.
12. Provide additional hangers or anchoring devices necessary for support of piping at
corners, tops of risers, etc.
13. Anchors shall consist of rigid members clamped or welded to the pipe to prevent
pipe movement at that point. Attach anchors to structural members of the building.
D.
Joints
1. Any leaking joints shall be completely disassembled and remade with new
materials.
2. Caulked joints in drainage piping shall be made using spun oakum to within 25 mm
of hub and the remaining space filled with poured pure pig lead and swigged.
3. Ends of all copper tubing and the interior of the cup of the fitting shall be
thoroughly cleaned and polished prior to the application of the flux and solder. The
flux shall not be used as a substitute for proper joint preparation.
4. All pipes shall be carefully reamed. Threaded pipe shall have full length clean cut
threads.
5. All sockets and pipe ends of PVC shall be cleaned and solvent cement applied for
full circumferential cover.
E.
Pipework Expansion
1. The contractor shall supply and fix expansion devices, anchors and guides to
adequately allow for the expansion and contraction of the pipework. The minimum
number considered necessary are shown on the contract drawings...
2. Whenever possible, such as brunch take-offs, natural expansion shall be used
within the configuration of the pipework system.
3. Pipe work expansion shall be carefully controlled to prevent damage to the
pipework system, equipment, structure, etc.
4. Special consideration shall be given to steam, condensate, LTHW and hot water
services.
5. Chilled water and cold water pipework generally where installed in the services
building , main services duct, equipment rooms and other areas where relatively
high ambient temperatures may occur , and where movement cannot be absorbed
naturally, shall incorporate flanged joints of the type which allow expansion,
contraction and some measure of lateral movement. These joints shall be a
mechanical pipe coupling consisting of a center sleeve, and flanges wedge shaped
rubber sealing rings and nuts and bolts. The main components shall be constructed
from high quality malleable or cast iron for sizes up to 80 mm diameter and steel
Page 21 of 24
above this size. All nuts and bolts shall be galvanized. Sealing rings shall be
suitable for the liquid type, temperature and pressure range. Sizes up to 345 mm
diameter shall be supplied preassembled. Larger sizes shall be supplied unfitted for
ease of handling. Coupling shall allow for a setting regularity of + 6 up to 600
mm + 5for 600 mm to 750 mm and 4 for 750 to 900 m. Each coupling shall allow
for a repeated maximum pipe movement of 9.5 mm and sufficient couplings shall
be installed on this basis.
6. All expansion devices shall be suitable insulated to prevent accident to personnel,
but does not restrict the movement of the pipework
7. All expansion devices and natural expansion pipework systems shall be installed
with 50 % cold draw of the total movement.
8. Anchor points shall be provided as shown on the drawings. The anchor shall be
capable of resisting the maximum stresses that be applied. The contractor shall
ensure that the structure, that the anchor is attached to, shall also be capable of
withstanding the same stresses.
9. The method of anchoring the pipework to a secured point shall be :
a.
Mild Steel
Welding
b.
Cast Iron
c.
Copper
10. Care shall be taken when installing and positioning guides to ensure that the
amount of free play in the pipeline is kept to an absolute minimum and that the
resulting thrust of expansion is taken up in the designed manner. Means for
Lubrication shall be provided where necessary. Guides for pipework over 50 mm
shall be of the type incorporating reinforced PTFE in order to allow reduced
frictional resistance to movement. Guides and skid supports shall be provided in
accordance with the manufacturers recommendations and shall form part of the
submission.
3.02
VIBRATION CONTROL
A.
General
1. All vibrating equipment connected to the pipework system shall be isolated to
eliminate transmission of noise and vibration.
B.
Noise Criteria
1. Each piece of mechanical equipment selected shall be evaluated for quietness.
Particular care shall be taken to evaluate acoustical performance as well as
Page 22 of 24
mechanical function. Sound pressure level within spaces shall not exceed the NC
curves indicated.
C.
Piping Insulations
1. All piping 65 mm and larger specified with vibration isolation shall have anti vibration hangers. Static deflections as follows:
a. First three hangers away from any spring isolated piece of equipment shall
have hangers with same static deflection as equipment isolators.
b. All others shall have 25 mm static deflection.
2. All piping 50 mm and smaller shall have isolators as follows:
a. First three hangers away from any spring isolated piece of equipment shall
have hangers with same static deflection as equipment isolators.
b. For insulated piping outside equipment rooms isolators are not required.
3.03
ACCESSIBILITY
A.
Locate all equipment that must be serviced, operated, or maintained, in fully accessible
positions. Minor deviations from the drawings may be allowed for better accessibility
at written approval.
B.
Allow ample space for removal of parts that may require replacement or service in the
future.
C.
3.04
A.
Contractor shall be responsible for all cutting, fitting, or patching of his work which
may be required to make its several parts come together properly and fit it to receive, or
be received, by work of other trades. Cutting of structural members shall not be done
without written approval.
B.
Any cost caused by defective or ill-timed work shall be borne by the contractor, as
determined by the Engineer. Contractor shall not endanger any work, persons, or
construction by cutting, digging or otherwise.
C.
Place sleeves through all walls, floors, and ceilings during the initial construction
where it is necessary for piping to go through. When this is not done, do all cutting and
Page 23 of 24
patching required for the installation of the work. Any damage caused to the building
by this cutting and patching, shall be corrected at no additional cost.
D.
Patching of all openings for new installations and all openings resulting from the
removal or relocation of any installations shall be done by craftsmen skilled in the
particular trade effected, with materials of like type adjoining openings.
END OF SECTION
Page 24 of 24
VALVES
SECTION 15100
PART 1 - GENERAL
1.01
SUMMARY
A.
Provide labor, materials, equipment and services, and perform operations required for
complete installation of Valves and related work as indicated on the drawings and
specified herein.
B.
Work Included: The work shall include, but not be limited to, the following:
1. Types of valves specified in this section include but not limited to the following:
a.
b.
c.
d.
e.
f.
g.
h.
i.
Gate Valves.
Globe Valves.
Butterfly Valves.
Valve Box
Double regulating Valve
Check Valves
Float Valves
Strainers
Air Vents..........
1.02
QUALITY ASSURANCE
A.
Materials and work shall conform to the latest edition of reference specifications,
industry standards listed below and specified herein and to applicable codes and
requirements of local authorities having jurisdiction, whichever is more stringent.
B.
Tests: Test valves in accordance with the appropriate section of the specification
describing each system.
1.03
SUBMITTALS
A.
Page 1 of 10
1.04
A.
Exercise proper care in the handling of work so as not to injure the finished surfaces,
and take proper precautions to protect the work from damage after it is in place.
PART 2 - PRODUCTS
2.01
GENERAL
A.
B.
All valves shall be line size, except control valves or calibrated orifice flow indicating
valves, which shall be sized to achieve proper flow control and mid-range flow
readings, respectively.
C.
Valves and specialties specified in this Section are of a general nature and are
appropriate for most systems. For special use valves and specialties refer to the
individual system sections.
D.
All cast iron valve bodies used for water service shall be internally and externally
epoxy resin coated.
E.
F.
All valves must be rated for minimum of 16 bars at 192C fluid temperature.
2.02
GATE VALVES
A.
Page 2 of 10
2.03
GLOBE VALVES
A.
2.04
CHECK VALVES:
A.
2.05
BALL VALVES:
A.
Valves shall be bronze ball type with threaded ends, Teflon stem packing seals, Teflon
seats, T handle for 25 mm and smaller, insulated operating lever for 30 mm and
larger, and blowout proof silicone bronze stem. Valves shall be rated for PN16.
2.06
BUTTERFLY VALVES:
A. Valves shall be designed for minimum of 0.68 MPa differential pressure with the down
stream flange removed through 300 mm size. Factory test data of differential pressure
rating is required. Valves shall have cast iron body, conforming to ASTM A126 Class
B body, tin bronze disc, in accordance with ASTM B30 copper alloy and EPDM seals.
Shafts design shall be 416 stainless steel. All valves shall have extended necks for a
minimum of 50 mm insulation. Valves 63 mm through 150 mm shall be provided with
lever operators and memory stop. Valves 200 mm and larger shall be driven by a worm
gear operator or screw driven operator with position indicator. Operators shall be fully
enclosed in cast iron housing, be watertight, and require no more than 150 N rim pull.
Operators shall be designed to withstand, without damage, an input torque of 1.3 KN.
Valves shall be rated for PN16.
Page 3 of 10
2.07
CHAINWHEEL OPERATORS:
A.
2.08
VALVES BOXES
Supply and install, wherever shown on the drawings and as specified herein, all
valve boxes.
Size and number of valves in each valve box shall be as shown on drawings.
Each valve box shall be of masonry wall construction or metallic wall
construction encased within masonry.
Each valve box shall conform to the following requirements:
2.09
a-
b-
Valve boxes located outside shall provide a minimum cover of 30cm over
pipes passing through.
c-
Indoor valve boxes shall have a steel cover matching space internal finish.
d-
Outdoor valves boxes shall be provided with a heavy duty cast iron cover,
lockable.
Page 4 of 10
2.10
2.11
2.12
This valve shall be used on domestic hot water lines wherever applicable.
Temperature and pressure relief valve shall be self-closing type with test lever and
screwed connections.
Valve shall be suitable for a pressure of 75 to 150 psi (520 to 1030 Kpa) service
and shall be supplied with temperature relief set at 210 oF (100 oC).
2.13
A.
B.
Backflow preventers to include test cocks and pressure- differential relief valve located
between two positive seating check valves.
C.
Page 5 of 10
2.14
A.
B.
Safety relief valve designed, manufactured, tested, and labeled in accordance with the
requirements of Section IV of the ASME Boiler and Pressure Vessel Code. Valve body
shall be cast-iron, with all wetted internal working parts made of brass and rubber, 1.5
MPa working pressure and 121 C maximum operating temperature. Select valve to
suit actual system pressure and kCal capacity. Provide with fast fill feature for filling
hydronic system.
2.15
2.16
WATER STRAINERS
Strainers shall be located at inlets to control valve arrangements and pump sets
and generally as detailed on the drawings.
The strainer shall be simplex or duplex as indicated on the drawings.
Each strainer shall be provided complete with a stainless steel screen AISI 304
as follows:
Application
In pipework 15 mm to 50mm nominal bore on inlets to all
Perforation
Size mm
0.8
Page 6 of 10
control valves
In pipework 65 mm to 100 m nominal bore
1.2
1.6
2.17
2.18
EXPANSION DEVICES
Expansion devices on copper pipework shall be manufactured with
convolutions of single wall 18/8T1 stainless steel, argon arc welded to a
stainless steel ring with a M.S. backing flange. All internal parts in contact
with the fluid shall be stainless steel and the ends shall be flanged to BS 4504.
Expansion devices on steel pipework size 50 mm and below shall be
manufactured with convolution of single wall 18/18T1 stainless steel, argon arc
welded to heavyweight mild steel end flanged to BS4504.
Expansion devices on steel pipework size 65 mm and above shall be
manufactured with convolutions of heavy wall hot formed Cr-Mo steel welded
to mild steel end flanged to BS 4504.
All expansion devices shall be provided with internal sleeves. External sleeves
shall be provided on devices in plant-rooms and underground ducts. Pressure
Page 7 of 10
2.20
AUTOMATIC FILTERS
Automatic filters shall be RainBird Model AF 150-LSS with 1 Y filter or
approved equal. Filters shall have automatic backwash.
Page 8 of 10
2.21
2.22
FLOAT VALVES
Float valves shall be of all bronze construction including levers and arms, with PVC
float and suitable for a cold water working pressure of 10 bars. Float valves shall have
screwed inlets.
Float valves shall be of the full bore, equilibrium ball type, designed to close tight
against maximum pressure when half submerged. They shall have renewable synthetic
rubber valve discs and balancing piston buckets.
2.23
Page 9 of 10
PART 3 - EXECUTION
3.01
GENERAL
A.
Floor plans and flow diagrams are intended to be complimentary since not all valves
can be shown on the floor plans. In general, flow diagrams and details show valving
arrangement and floor plans show locations when possible.
B.
All water valves which regulate flow shall be globe, ball or butterfly type and valves
that are either open or closed shall be gate, ball or butterfly type. Steam valves
for all purposes shall be globe type and for condensate gate type . For valves for use on
medical and non-medical gases, air and vacuum systems refer to Sections 15310 and
15320.
C.
Provide shut-off valves in each supply branch from mains and at each supply
connection to equipment. Provide a balance valve at each return branch to mains at
each return connection from equipment, and in the bypass line of a three-way control
valve.
END OF SECTION
Page 10 of 10
PUMPS
SECTION 15140
PART 1 - GENERAL
1.01
RELATED WORK
A.
B.
C.
D.
E.
F.
G.
Section 15990:Instrumentation
H.
1.02
SYSTEM DESCRIPTION
A.
This section covers the manufacture and supply of various pumps required for the
mechanical services.
B.
Fire pump fabrication, installation, and testing shall be in conformance with latest
NFPA Standards.
C.
Centrifugal, rotary, and reciprocating pump fabrication, installation, and testing shall
be in conformance with HIE.35.01, E.37.01, and E.39.01 respectively.
D.
The selection of pump type and pump drive shall be based on each specific application
requirements. Pump drivers shall be selected to be non- overloading over the whole
range of the Q-TDH curves, considering temperature variation of the fluid being
pumped.
E.
Pump Q-TDH curve shall be progressively dropping from shut-off head to run out. It
shall be such that it provides stable operation for the pump when operating at any point
on the curve. Shut - off head shall approximately be 25 to 35 percent above the rated
head.
F.
G.
Constant speed pumps shall have the first critical speed at 25% below, or above, the
running speed. Variable speed pumps shall have the first critical speed at 25 % above
the maximum speed.
Page 1 of 29
1.03
REFERENCES
A.
Reference Standards
The following codes and standards are intended to provide an acceptable level of
quality for materials and products. The Contractor may propose alternative codes and
standards provided they give an equivalent degree of quality as the referenced codes
and standards and are submitted for review and approval in advance of their use.
1. American National Standards Institute (ANSI):
a.
ANSI
B15.1
mechanical
power
A36
Structural Steel.
b.
A48
c.
A53
d.
A108
e.
A120
f.
A276
g.
A278
h.
A296
j.
A395
k.
A536
l.
B62
m.
B148
n.
B584
Copper Alloy
Application.
Sand
Casting
for
General
Page 2 of 29
E101
20
E.35.01
Centrifugal Pumps.
b.
E.37.01
Rotary Pumps.
c.
E.39.01
Reciprocating Pumps.
9. MEMA
10. NEC
1.04
SUBMITTALS
A.
Manufacturer's Data: Submit manufacturer's data on pumps, including but not limited
to, pump characteristics and performance curves.
B.
f)
g)
h)
i)
j)
k)
2. Indicate the limits of the range of rate of flow at which the pump can successfully
operate on such curve when the operable range differs from the complete range
shown. Approval of the characteristic pump curve shall in no way be construed to
be permissive to proceed with the manufacture of the pump. Upon receipt of an
approved pump curve, the Contractor shall submit, if he has not previously done
so, all other drawings, material lists and other information specified, requested
and/or necessary to coordinate the pumping installation with the balance of the
work and to show complete compliance with all details of the Contract Documents.
C.
Shop Drawings:
1. Submit drawings and information necessary for final design of foundations,
structural supports, connected piping and valves, pump drip and drainage piping,
electrical connections, starting and protective equipment and auxiliary equipment.
2. Submit for all pumping units, a dimensioned and scaled assembly outline drawing
or drawings of the complete pump, drive and all associated equipment furnished.
Such drawing or drawings shall show plan, elevation and any other view or section
requested.
3. For all pumping units a scaled cross-sectional drawing of the assembled pump
showing full details and materials of construction shall be submitted for approval.
For pumping units powered by motors rated at 20 horsepower or less, catalog cuts
may be submitted to supplement the outline and cross furnished with steel base
plates, sub-bases and similar components, detailed dimensioned drawings giving
full information thereon shall be submitted for approval. Steel components shall be
at least 9.5 mm thick and no undrained pockets will be permitted.
1.05
A.
B.
Inspect hardware at time of delivery for shipment damage and for compliance with
specification.
C.
D.
Page 4 of 29
1.06
QUALITY ASSURANCE
A.
B.
Electrical Standards: Provide electric motors and products which have been listed and
labeled by Underwriters Laboratories and comply with National Electrical
Manufacturers Association (NEMA) standards.
C.
D.
All pumps shall be assembled in country of origin. Local assembly is not acceptable.
E.
All pumping units shall be designed and built for twenty-four hour continuous service
at any and all points within the specified range of operation, without overheating,
without cavitation, without excessive vibration or strain and requiring only that degree
of maintenance generally accepted as normal for the specific type of pump required.
All parts and components of all pumping units shall be designed and built for
interchange ability so that replacement parts may be installed without any additional
fitting or machining. Upon request, or if hereafter specified, the manufacturer shall
submit evidence that the tolerances and finishes on the detail drawings so permit, and
the manufacturer's shop is equipped with the necessary machinery, jigs, fixtures and
gauges to assure such interchange ability.
F.
Failure to successfully comply with the requirements of the previous paragraphs will
constitute grounds for disqualification of the pump manufacturer. Poor performance of
similar pumping equipment now in operation under the specified conditions of service
and pump rating constitute grounds for disqualification of the pump manufacturer,
supplier or both, unless such poor performance has been corrected.
PART 2 - PRODUCTS
2.01
MATERIALS
A.
General
1. All goods and products covered by these specifications shall be factory tested and
assembled and not locally assembled.
2. Pumps shall be made of materials meeting specific application requirements, and in
accordance with specifications detailed below.
B.
Pump casing shall be made of any one of the following materials and as described in
each pump specifications.
1. Gray iron casting conforming to ASTM A48 or A278. Class of castings shall be as
specified in the documents.
Page 5 of 29
C.
Pump shaft shall be made of either of the following materials as described in each
pump.
1. Stainless steel conforming to ASTM A276, Type 316 L.
D.
Impeller and impeller seal ring shall be made of any one of the following materials and
as described in each pump specifications.
1. Gray iron casting conforming to ASTM A48 or A278.
2. Bronze casting conforming to ASTM B584 or B184.
3. Stainless steel casting conforming to ASTM or A296.
E.
Tubing and pipe shall conform to ASTM A53 or A120, and in any case, shall be
suitable for the service under consideration.
F.
Base plate shall be made of either of the following materials and as described in each
pump specifications.
1. Gray iron casting conforming to ASTM A48.
2. Structural steel conforming to ASTM A36.
G.
H.
J.
All other pump parts shall be made from material compatible with pumps basic
material and suitable for the liquid being pumped.
K.
The pumps shall be equipped with drains and vents, with copper pipes for draining and
aerating the pumps to the floor drain. Waste oil shall be conducted to a waste oil
collector located on the base plate.
L.
The suction and discharge flanges for the pumps shall comply with ANSI B16-5.
M.
The electric motors shall, unless otherwise stated, be squirrel cage induction type, as
specified generally in Section 16150 but with Class F insulation and shall be suitably
rated for the duty as shown in the schedules.
N.
The pumps shall, unless otherwise stated, be suitable for temperatures up to 100C and
a working pressure up to 1.0 MPa in an ambient of 50C.
Page 6 of 29
2.02
FABRICATION
A.
All like parts of same type pumps fabricated by the same manufacturer shall be
interchangeable.
B.
Whenever possible the pumps shall be manufactured such that it shall be possible to
disassemble the rotor assembly with minimum disassembly of other parts such as
suction and discharge nozzles, bearing supports, etc. being left in place.
C.
D.
All foundry and machine work shall be in accordance with good practice for the class
of work involved.
E.
All parts shall conform to the required dimensions and shall be free from defects that
will prevent proper functioning of the pump.
F.
G.
All internal parts, such as impeller, requiring surface treatment shall be sprayed with a
primer in accordance with pump manufacturers standards practice.
H.
Pump sets shall be assembled as completely as possible as a unit including base plate,
driver, couplings and guards, lubrication, seal flush, etc. by the supplier, as the
requirement allows. Seal flush systems shall be equipped with appropriate controls,
strainers and filters as recommended by the manufacturer.
J.
Pump exterior shall be sprayed with a primer and shall be painted to meet specific
application requirements in accordance with pump manufacturers standard practice.
2.03
WATER PUMPS
A.
General: Provide electric motor driven, volute type centrifugal pumps as indicated on
drawings. Equipped with insulated, quiet, TEFC, when installed outside, or drip proof,
for indoor installation, ball bearing type motor of rotation speed, hp rating and power
characteristics indicated; factory aligned and couple motor to pump. Provide pumps
rated for capacities, pressures and suction/discharge heads as shown on drawings, with
flanged pipe connections, with dynamically balanced enclosed type impellers locked to
pump shafts and shall be rated for 80C water temperature and shall be close-coupled
or with flexible coupling as indicated on drawings.
Domestic Booster pumps shall be centrifugal vertical type multi stage pump complete
with control panel.
Chilled water pumps shall be centrifugal, split case type, single stage, horizontal, and
as specified..
The pumps shall be of cast iron bronze fitted construction. The volute and bearing
brackets are to be cast iron the impeller of bronze and the pump shaft of stainless steel.
The pumps shall employ a mechanical seal, with a carbon seal ring and ceramic seat.
The motor shall be resilient mounted equipped with oil lubricated journal bearings or as
indicated on the drawings.
Page 7 of 29
B.
Pump characteristics: The Contractor shall provide pumps according to the capacities
and schedules as shown on drawings. The pump shut-off pressure shall not be less than
25% higher than the design load. The speed shall not exceed 1450 RPM unless
otherwise specified on drawings.
C.
Equip pumps with sleeve bearings and force-feed lubrication systems, and protect
pump shafts internally with non-ferrous sleeves, Provide bearing bracket assemblies of
the type which can be removed without disturbing piping or motors.
D.
All pumps shall be connected to building control system as indicated under electrical
section.
2.04
2.05
IN-LINE CIRCULATORS
Description: In-line, centrifugal, single-stage, bronze-fitted, split case design; rated for
860kPa minimum working pressure and a continuous water temperature of 107C
include the following:
1. Casing: cast iron, with threaded companion flanges for piping connections smaller
than 65mm and threaded gate tapings at inlet and outlet connections.
a. Connection Option: Include unions, instead of threaded companion flanges, at
connections for casings that are not available with threaded companion flanges.
Page 8 of 29
2. Impeller: ASTM B584, cast bronze, statically and dynamically balanced, closed,
overhung, single suction, and keyed to shaft.
3. Shaft and Sleeve: stainless steel shaft with oil-lubricated copper sleeve.
4. Seals: mechanical DUNA-N type. Include carbon-steel rotating ring, stainless steel
spring, ceramic seat, and flexible bellows and gasket.
5. Pump bearings: Oil lubricated, bronze journal and thrust type.
6. Motor bearings: Oil lubricated, sleeve type.
7. Coupling: flexible, capable of absorbing torsion vibration and shaft misalignment.
8. Motor: resiliently mounted to pump casing.
9. Manufacturers to be proposed by Tenderer as part of his Tender, in all cases to be
approved by Consultant.
2.06
General
Supply and install wherever shown on the Drawings vertical multi stage centrifugal
pumps of capacities as indicated in the capacity schedule and/or shown on the
Drawings.
Each pump shall be of the type specified and shall be directly coupled to an electric
motor.
Pump casing shall be of stainless steel, with smooth water ways and fitted with
stainless steel wear ring. Impeller shall be stainless steel, enclosed, accurately
machined and statically and dynamically balanced. Shaft shall be one piece stainless
steel with stainless steel sleeve of ample size to carry any axial and radial thrust.
Pump shall have mechanical shaft seal of extra hard carbon and ceramic type. Pump
ball bearings shall be of ample size to withstand all axial and radial thrust.
Each pump, for water supply application, shall be complete with the following;
Electric control panel complete with circuit breakers, starters, automatic electric
alternators, indicating lights and selector switches. Panel shall be made of sheet
steel of dust and rust proof type with lockable door. Panel is to be from the same
pump manufacturer.
Float switches, installed in both domestic water reservoirs, and control cables
between the float switches and the electric control panel.
Page 9 of 29
2.07
One pump shall act as a standby (as indicated in the pump schedule)
A low water level float switch installed in the lower water tank shall prevent either
of the pumps to run dry if the lower tank is empty.
A float switch installed in the roof water tank with two predetermined levels. The
high level when reached shall stop the pump automatically and the low level when
reached shall start the pump automatically.
An electric alternator shall alternate the duty and standby pumps on every cycle. In
case of failure of duty pump to start, the standby shall be automatically started.
e. Water cooled, totally enclosed electric motor, rated for continuous duty. Motor
speed shall not exceed 2900 rpm. Motor to have thermal overload protection
and moisture sensing probes, pump and motor bearings shall be heavy duty,
permanently lubricated and sealed ball bearings guaranteed for a minimum of
100,000 hours continuous operation. Include a 3 conductor waterproof power
cable of length required, but not less than 6m with grounding plug and cable
sealing assembly for connecting at pump.
f.
Oil casing.
Sump pumps shall be installed in a concrete pit to be constructed by the Concreter with
checker plate cover over each pump.
The Contractor shall coordinate his piping with the Concreter and shall install all pipes
connected to the sumps pit in accordance with the layouts shown on the drawings.
It shall be his responsibility to coordinate and determine pipes inverts and locations of
pipe connections to the pit.
Control panel to be factory tested and assembled.
2. Controls
An automatic operating and control panel shall be provided for sump pumps operation.
Pumps shall be monitored by the BMS system. Control voltage not to exceed 24 Volts.
The panel shall be of light alloy construction, perfectly sealed against dust and water
and shall house pumps starters, breakers, floats, relays, interlocks, pilot lights, cables,
wires, etc,... to obtain to following results:
a. At low water level in the collecting pit, controls shall be inoperative.
b. When water level rises to the first normal level in the collecting pit, the lead
pump shall start.
c. When water level rises to the second normal level in the collecting pit, the
second pump shall start.
d. When water level drops to the first level, the last pump to start shall stop. The
first pump shall keep on running until water level drops to the low water level
setting.
e. An automatic alternating relay shall alternate pumps lead role after each cycle.
f. Should the water level rise to the alarm preset level or drop to the alarm preset
low level, controls shall act to operate an alarm bell which shall remain in
operation until put off manually. Alarm shall be indicated on the central alarm
panel and BMS.
Level switches shall be of the heavy duty sealed mercury tube type condensate
complete with twin core PVC insulated cable and shall be of a type intended
for use with domestic sewage.
3. Capacity
Capacity of each sump pump shall be as shown on the drawings.
Page 11 of 29
2.08
2.09
b.
c.
d.
e.
Casing: cast iron, minimum tensile strength 35000 psi, designed for working
pressure of as scheduled and hydrostatically tested at factory to not less than
17kg/cm2.
f.
g.
Shaft sleeves: to extend entire length of seal boxes to protect shaft and key
locked and threaded to tighten with rotation of shaft. Teflon gaskets to be
provided between impeller hub and shaft sleeves to protect pump shaft.
h.
i.
j.
Mechanical seals: carbon washer, Ni-resist face and stainless steel parts.
Page 12 of 29
k.
Electric motor: totally enclosed, fan cooled, squirrel cage, induction type
with permanently lubricated and sealed ball bearings. Motor speed is not to
exceed 2900 rpm.
l.
m.
The isolating switch and the circuit breaker shall be interlocked such that the isolating
switch can neither be opened nor closed while the circuit breaker is closed.
Page 13 of 29
Voltage Free Contacts (one NO & one NC) for indicating the following:
Loss of any phase at the terminals of the motor contactor
Pump Running
Phase Reversal
Pump Failed To Start
Loss Of Control Power
Pressure Switch
Second Pressure Switch (with a NO/NC contacts for remote indication of drop of pressure
below the starting pressure)
- Pressure Recorder
- Manual Start/Stop Push Buttons
- Minimum Running Period Timer
- Sequential Start Timer (to prevent the pumps from starting simultaneously)
- Remote Start Circuit
- Motor Current & Voltage Readout (on all three phases)
- Control Circuit Transformer (fed from two electric power phases feeding the fire pump)
Wye-Delta starting shall be of the closed transition type to prevent current
surges and disturbances to be fed back to the main power source. The
controller shall incorporate a mechanical and electrical interlock to prevent the
Wye connecting contactor to be energized at the same time as the Delta
contactor.
The power transfer switch shall be electrically operated and mechanically held.
It should be rated not less than 115 percent of the motor full-load current and
also suitable for switching the locked rotor current. A means for safe
(nonelectrical) operation of the power transfer switch shall be provided.
Power transfer to the emergency power supply shall be initiated by any of the following
signals:
-
Voltage on any phase at the load terminals of the circuit breaker falls below 85% of motor
rated voltage.
Phase reversal of the normal source power.
Transfer to the emergency source shall be inhibited until there is adequate voltage and
frequency to serve the fire pump load. Means shall be provided to prevent higher than normal
inrush currents when transferring the fire pump motor from one source to the other.
The fire pump power transfer switch shall include the following components, all other devices
necessary for the proper operation of the installation and compliance with NFPA20 shall be
provided:
- Emergency Power Isolating Switch
- Emergency Power Circuit Breaker
- Visible Indicators of the following:
- Emergency Power Available
Page 14 of 29
n.
Jockey pump shall pressurize the system and fulfill small demands. Upon increase of
demand and drop in pressure, the duty pump will come into operation first, then if
pressure continues to drop, second pump shall start. Pump will retire according to
increase in system pressure. An alternator shall interchange between the duty pumps and
standby pump. If duty pump fails standby pump shall come into operation automatically.
Low level switch located in fire water tank shall stop pumps and give alarm if tanks are
empty.
Controller door sets shall be interlocked mechanically when the main switch is on
position.
Manual operated spring assisted closing air circuit breaker.
Manual protection by magnetic type over current release unit which trips the circuit
breaker.
Stalled rotor protection with definite trip time 90 seconds at 600% of full load current.
Short circuit protection with instantaneous trips at 1200% of motor full load current.
Page 15 of 29
Normal setting at 300% of motor full load current with trip time in excess of 60 seconds.
Auto closing heavy duty line, start and run contactors rated at least 115% of motor full
load current. Push button operated for local, manual or remote start.
Lever operated mechanically for emergency direct on line start.
Control panel enclosure shall be NEMA ICS 6, Type 2 drop-off.
Panel shall be complete with push button operated for local, manual or remote electric
start.
Panel board shall be equipped with auto-stop control with wiring terminals at clearly
marked connector rail and external cable connection shall be through bottom fitted cable
glazed plate.
Performance Test: pump to be completely tested at factory with positive suction pressure
and with a 4.5m suction lift. Certified performance curves for both conditions to
submitted for approval prior to shipment.
2.10 JOCKEY FIRE PUMP
Supply and install jockey fire pump wherever shown on drawings and as specified
herein; conformity with NFPA Standards requirement is required. Pump shall be UL/FM
approved.
a. Type: Vertical multistage , centrifugal, directly coupled to motor.
b. Construction: casing to be cast iron. designed for working pressure of 17kg/cm2 and
hydrostatically tested at this pressure at factory. Impeller to be bronze, double
suction, hydraulically balanced design, dynamically balanced, keyed and bolted to
stainless steel shaft.
c. Construction: pump to have internal sealing water passages, removable chromeplated cast iron channel rings, mechanical seal with carbon washer, Ni-vesist face
and stainless steel parts, water slingers to protect bearings and 'O' ring gaskets to
prevent leakage.
d. Electric Motor to be close-coupled to pump, totally enclosed, fan cooled squirrel
cage, induction type, with permanently lubricated and sealed ball bearings. Motor
speed is not to exceed 2900 rpm.
e. Starter: totally enclosed, wall mounted, direct-on-line, with no-volt and overload
protection in each phase and suitable for automatic operation.
Page 16 of 29
2.11
General
*
The diesel internal combustion engine driving the fire pump shall be of
the compression ignition type, and shall be specifically listed for fire
pump service. Diesel Pump shall be to NFPA & UL listed.
The Engine shall have a brake horsepower rating not less than 20%
greater than the maximum brake horse power required to drive the
pump at its rated RPM.
B-
C-
Page 17 of 29
D-
E-
Engine Cooling
*
The engine cooling system shall be of the closed circuit type, including
a circulating-pump driven by the engine, a heat exchanger, and a
reliable engine jacket temperature regulating device. The coolant shall
comply with recommendation of the engine manufacturer.
The cooling water supply for the heat exchanger shall be from the
discharge of the pump, taken off prior to the pump discharge valve.
Separate pilot lights and a common bell indicated trouble caused by:
2.12
SURGE TANK
Provide surge tank as shown on the drawings, constructed for 1000 Kpa working
pressure, and 1500 Kpa test pressure of black steel stamped with U symbol and
supplied with National Board From U-1 denoting compliance with ASME boiler and
pressure vessel code. Provide fittings and connections to related equipment in
accordance with tanks manufacturers recommendations. Tank diaphragm shall
withstand 10 deg. C up to 120 deg C and specified pressure above . Surge tank shall
be coated with anti corrosion paint and enamle finish.
2.13
Each Cold water pressure sets shall be complete as specified in the following
clauses:
1. Pumps
Each pump shall be centrifugal; vertical split case, single or multistage, silent type,
complete with flexibly coupled electric motor and couplings. The pump and motor
assembly shall be mounted on a steel bed plate with an approved vibration isolator.
Pumps construction shall be stainless steel 304, impeller Laser weld, stainless steel
shaft and mechanical seal.
Pumps shall be flexibly coupled to the electric motor thru a flexible coupling.
Motor speed not to exceed 2900 rpm and as indicated on equipment schedule.
Page 19 of 29
Page 20 of 29
b. When suction water level drops to 100 mm above top of suction pipe, the pump
shall stop by the action of a low level float switch; it shall not be able to run
even if other controls call for its operation.
After water level rises to 150 mm above suction pipe, controls shall allow
pump operation again.
c. If operating pump fails to start the second pump shall operate automatically.
d. An automatic sequencing control shall be provided to operate pumps in a
rotational sequence after each cycle.
e. Panel shall be provided with OFF-MANUAL-AUTO selector switch to allow
the system to be stopped and/or put on manual or automatic operation.
f.
Panel shall be provided with an alarm buzzer and switch which shall be put in
operation in case of fault.
g. For each function specified with the panel, a pilot light shall be provided to
indicate the status of the particular function. Pilot lights colors shall be selected
in accordance with the function to be indicated.
h. A delay relay shall be incorporated within the panel to prevent immediate startup upon re-establishment of power after power failure.
j.
2.14
A.
Pumps to be of the monoblock rotary gear type with suction and discharge connections
screwed ANSI parallel thread. Casing and gears to be of cast iron construction with the
drive shaft in high tensile steel. Generally s clause 2.01.
B.
The shaft shall be supported by PTFE impregnated carbon bearings and sealed by
either PTFE impregnated packing or carbon faced mechanical seal. The pumps shall be
fitted with an integral relief valve for protection from excessive pressure.
C.
D.
E.
Description: horizontal, base mounted, horizontally split case, double suction, single stage,
centrifugal type, directly connected to motor through heavy duty flexible coupling and with
heavy gauge coupling guard.
Base: Pump and motor to be mounted on common cast iron base reinforced against deflection,
with drip rim, drain tapping, bolt holes, and grouting hole.
Page 21 of 29
Pump Casing: Bronze, high tensile strength alloy, designed for working pressure of 2000 kPa,
fitted with easily removable bronze wear rings dowelled to casing. Casing to be divided at
horizontal centerline and the 2 halves accurately machined, dowel aligned and bolted together.
Suction and discharge nozzles to be in-line piping design, cast integrally with lower half of
pump casing to allow rotating element to be removed without disconnecting suction and
discharge flanges.
Impeller: Bronze, enclosed, double suction type, fastened to shaft by stainless-steel key and
screw locked adjustable shaft sleeves.
Shaft And Shaft Sleeves: Shaft to be high strength steel, sized to carry axial and radial thrust
with minimum deflection and protected against corrosion from water by full length bronze shaft
sleeves. Teflon gaskets to be provided between impeller hub and shaft sleeves to prevent
pumped water corroding shaft.
Mechanical Seal: Ni-resist face, carbon washer and stainless steel metal parts.
Bearings: Pump rotating element to be supported by two heavy duty grease lubricated ball
bearings for both radial and thrust loads, mounted in machined moisture proof and dustproof
cast iron housings bolted to pump casing with register fits to ensure permanent alignment.
Bearing housing supports to be cast integrally with lower half of pump casing. Bearings to
have grease seals and water slingers to protect bearings from contamination and easily
accessible grease fittings for positive bearing lubrication.
2.16
Pumping Skid (complete with valves & fittings as per detail drawing)
Pump Control Panel
Adjustable Frequency Drive
Sensor Transmitters
Sequence of Operation
Pump base shall be floating slab installed on spring isolators to prevent vibration
when pumps are running at low frequencies.
b)
References
A. Hydraulic Institute
B. ANSI - American National Standards Institute
C. NEMA - National Electrical Manufacturers Association
D. UL - Underwriters Laboratories. Inc.
Page 22 of 29
Submittals
i)
ii)
d)
2.
Sequence of operation
3.
4.
5.
6.
Quality Assurance
i)
ii)
iii)
All functions of the variable speed pump control system shall be tested at
the factory prior to shipment. This test shall be conducted with motors
connected to AFD output and it shall test all inputs, outputs and program
execution specific to this application.
iv)
v)
vi)
e)
f)
Manufactured Units
i)
ii)
The control system shall include, as a minimum, pump & motor assemblies,
the programmable logic pump controller, adjustable frequency drive(s),
suction and discharge piping, valves and additional equipment as specified
or as required to properly execute the sequence of operation. Furnish field
installed remote sensor/ transmitters as indicated on the plans.
iii)
System shall require only suction and discharge connections and a single
point power connection with all interface connection to existing Building
Management System of the Hospital.
iv)
v)
Provide pumps as indicated on the pump schedule. Pumps and motors shall
be furnished as specified in respective sections of this document.
vi)
Pressure gauges shall be furnished for system supply and return headers.
Gauges shall be installed to be clearly visible from front of control panel.
Components
i)
2.
Motor overload
Pump flow surges
Hunting
End of curve
Page 24 of 29
3.
4.
5.
6.
The hydraulic stabilization program shall utilize a proportionalintegral-derivative control function. The proportional, integral and
derivative values shall be user adjustable over an infinite range.
7.
8.
The readout shall be two lines of forty 0.50" brightly lit fluorescent
characters capable of displaying the following values:
a.
b.
c.
d.
e.
f.
All read outs shall be interfaced with the BMS for remote reading
by BMS.
9.
ii)
Page 25 of 29
1.
2.
The AFD, including all factory installed options, shall have CSA
approval.
3.
4.
5.
6.
7.
8.
The AFD shall be suitable for elevations to 3300 feet above sea
level without derating. Maximum operating ambient temperature
shall not be less than 104 degrees F. AFD shall be suitable for
operation in environments up to 95% non-condensing humidity.
9.
10.
Frequency
Voltage
Current
Kilowatts per hour
Fault identification
Percent torque
Percent power
RPM
iii)
Sensor / Transmitters
Provide 16 field mounted differential pressure sensor transmitters as
indicated on the plans. Unit shall transmit an isolated 4-20mA dc signal
indicative of process variable to the pump logic controller via standard two
wire 24 DC system. Unit shall have stainless steel wetted parts with two
0.25" male NPT process connections. It shall be protected against radio
frequency interference and shall have a watertight, NEMA 4 electrical
enclosure capable of withstanding 2000 PSI static pressure with a 0.5" NPT
conduit connection. Accuracy shall be within 0.25% of full span.
iv)
Sequence of Operation
1.
2.
3.
4.
5.
6.
7.
When all set points are satisfied by the process variable, the pump
speed shall remain constant at the optimum energy consumption
level.
8.
9.
If the set point cannot be satisfied by the designated lead pump, the
pump logic controller shall initiate a timed sequence of events to
stage a lag pump .
10.
11.
Page 27 of 29
12.
When the set point criteria can be safely satisfied with fewer
pumps, the Technologic pump logic controller shall initiate a timed
destage sequence and continue variable speed operation.
13.
As the worst case zone deviates from set point, the pump logic
controller shall send the appropriate analog signal to the AFD to
speed up or slow down the pump/motor.
14.
15.
16.
17.
18.
19.
PART 3 EXECUTION
3.01
SHOP TESTING
A.
Pump performance tests shall be conducted in accordance with Hydraulic Institute test
codes as described in HI E.35.01, E.37.01, and E.39.01. In addition, each pump shall be
tested at five points of operation from shut-off head to run out condition including the
guaranteed pumps performance point.
Page 28 of 29
B.
All pumps shall be hydrostatically tested for leaks at 1.5 times the design pressure.
There shall be no leakage during the one hour test period.
C.
The manufacturer shall submit certificate including test data to show that the pump
meets performance specifications.
3.02
INSPECTION
A.
The Contractor shall inspect each pump prior to installation to verify that pumps are in
conformance with these specifications.
3.03
INSTALLATION
A.
B.
If flexible coupling is used between the pump and its driver, shafts shall be so
supported and aligned as not to produce undesirable stresses and noise during normal
operation.
C.
If oil or grease lubricated bearings are supplied with the pump, the oiler shall be filled
with the specified lubricating oil or bearings shall be pre-lubricated with specified
grease prior to start-up.
3.04
TESTING
A.
Field testing of the pumps shall be performed at the time of overall system start -up and
testing. Installed pumps shall meet the performance specifications. See Section 15991.
END OF SECTION
Page 29 of 29
TANKS
SECTION 15175
PART 1 - GENERAL
1.01
SUMMARY
A.
Provide labor, materials, equipment and services, and perform operations required for
complete installation of Plumbing Equipment and related work as indicated on the
drawings and specified herein.
B.
Work Included: The work shall include, but not be limited to, the following:
1.
2.
3.
4.
5.
6.
C.
1.02
QUALITY ASSURANCE
A.
Materials and work shall conform to the latest edition of industry standards, reference
specifications listed below and specified herein and to applicable codes and
requirements of local authorities having jurisdiction, whichever is more stringent.
B.
Qualifications
1. The Contractor shall provide the equipment specified, or equipment of the same
standard of construction and performance as produced by one of the listed
manufacturers.
2. Approval of the manufacturer does not necessarily constitute approval of its
products as equal to those specified. Immediately after the awarding of the
contract and prior to the start of construction, submit to the Engineer for approval a
complete written summary of the proposed manufacturer's equipment.
C.
Test
1. Factory Tests
a. Before shipment, the manufacturer shall test components hydrostatically at
150% of rated design pressure for ability to withstand maximum design
pressures and for tightness.
Page 1 of 9
1.03
SUBMITTALS
A.
B.
Maintenance Data: Submit maintenance data and spare parts lists for each type of
manufactured piping specialty. Include this data, product data, and shop drawings in
maintenance manual in accordance with requirements of Section 15010.
1.04
A.
Deliver materials and handle so as to prevent the inclusion of foreign materials and the
damage of materials.
B.
Store materials and equipment where designated and assume responsibility and security
for materials and equipment. Take precautions for protection from detrimental
conditions.
Page 2 of 9
PART 2 - PRODUCTS
2.01
MATERIALS/EQUIPMENT
A.
B.
C.
Expansion tank
1.
2.
All pipes into the water tank shall be located in place before concreting and shall be
provided with no-leak flanges welded to the pipe.
g. Contractor shall supply all material and labor to treat concrete water tanks with
internal lining, non toxic, solvent free epoxy paint, and two epoxy resin system
with water proofing capabilities minimum thickness 200 micron. Material used
shall be suitable for potable water and accordingly will not contaminate water.
h. Water tanks shall be monitored by BMS with all necessary controls.
Page 3 of 9
D.
Each tank shall be of the open cylindrical type fabricated from polyethylene and shall be
provided with screwed cover of the same thickness. Polyethylene used in manufacturing
shall be US FDA approved.
Each tank shall be provided with welded 5 x 5 cm x 5 mm thick structural angle support
with legs of the same angle size. The legs shall have 10 x 10 cm x 10 mm thick steel sole
plates welded on to them.
Each tank shall be complete with:
a.
Access cover.
b.
c.
Level float switches assemblies as required and as necessary for the control of
the relevant systems.
d.
e.
Drain valve.
f.
Drain and overflow pipes to nearest drain provision or as shown on the
and vent pipes with insect copper mesh screen.
g.
E.
drawings
Hypochlorinator
1.
Page 4 of 9
F.
2-
3-
Chlorine residual analyzer shall have an acetate reagent buffer solution system
with a constant head reagent feed system utilizing a control valve to meter
reagent into the sample cell.
4-
Chlorine residual controller shall be wall mounted and have in addition to set
point adjustment for setting the frequency of corrective action when a
difference exists between set point and measured residual chlorine.
5-
Chlorine residual recorder wall mounted solid state type requiring no ink and
incorporating a 30 day strip chart, an indicator strip for 0 to 2 PPM range and a
front clear glass cover with high and low level alarm contacts to actuate a
remote visual and audible alarms.
G.
Capacity
Filter installed a head of softener shall have the capacity indicated on the Drawings
and/or specified in the schedule of Equipment at a filter and backwash rate of 11
gpm/ft2 of filter area.
Materials
Tank shall be made of composite or heavy gauge reinforced fiberglass construction
or composite having a vertical cylindrical shape with dished and flanged heads
Page 5 of 9
suitable for a working pressure of 15 bar. All pipe connections to the tank shall be
flanged except for pipe sizes 1 1/2" (40 mm) and smaller which shall be screwed.
Tank shall have a manhole complete with cover, gasket, bolt and yoke located on
the top.
Tank shall be designed in accordance with ASME Section VIII DIV- 1 or
equivalent International Standard. Tank shall have a baffle to promote even
distribution of the effluent over the filter bed, and shall be equipped with a suitable
under drain.
The effluent laterals shall be 150 mm apart and shall have 27/64 (11mm) diameter
orifices every 150 mm.
The effluent laterals shall be of corrosion-resistant pipe with orifices directed
downwards. The effluent header shall be of schedule 80 steel.
Tank supports shall be of the adjustable jacklegs.
Internal finish lining shall be smooth, dust free, without pin holes or voids and
completely nontoxic.
Filter media shall consist of sand, gravel and rocks layers. Sand shall be of hard
durable grains of uniformly graded silica sand free from foreign materials,
limestone or clay. Sand shall be of 0.39mm. Effective size with uniformity coefficient of 1.2 to 1.4 Gravel and rock shall consist of clean, hard, rounded stones
with an average specific gravity of not less than 2.5 and should be free from shale,
mica, clay and other impurities.
Valves shall be of the butterfly type complete with companion flanges, gaskets and
bolts. A multiport valve can be used for backwashing. Filter shall be automatic
backwash or manual type as indicated on drawings.
H.
SAND FILTER:
The sand filter is used to remove turbidity and suspended solids, the filter
shall be vertical sand pressure filter. It shall have the following
characteristics:
Tested pressure:
10.2 Bar.
Service pressure: 1.5 Bar to
7.2 Bar.
Tank shells: #283, hot rolled carbon steel, 6mm thick, butt welded
inside and outside.
Working temperature range: 5 C
to 50 C.
Internal lining: special coating for drinking water
application.
Media type: multimedia, consisting of a number of media distinctly
layered.
The internal distribution system - filter internal equipment in contact with water
shall consist of 16 bars high impact UPVC piping, without any metal supports or
Page 6 of 9
Page 7 of 9
PART 3 - GENERAL
3.01
EXAMINATION
A.
3.02
PREPARATION
A.
B.
3.03
INSTALLATION
A.
B.
C.
D.
E.
F.
Pipe vents, bleeds, gland and base drains, and blow off connections to
nearest floor drain using copper tubing.
G.
H.
Page 8 of 9
3.04
A.
Field Tests
1. Perform field test to demonstrate the ability of the equipment to meet contract
requirements.
2. Should any part of the apparatus or system fail to meet the contract requirements,
adjust, repair or replace any defective or inoperative parts and, on completion,
again conduct the complete performance tests.
3. Refer to appropriate sections for additional required test data.
B.
Page 9 of 9
MECHANICAL IDENTIFICATION
SECTION 15190
PART 1 - GENERAL
1.01
SUMMARY
A.
Provide labor, materials, equipment and services, and perform operations required for
complete installation of Mechanical Identification and related work as indicated on the
drawings and specified herein.
B.
Work Included: The work shall include, but not be limited to, the following:
1. Extent of mechanical identification work required by this section is indicated on
drawings and/or specified in other Division 15 sections.
C.
1.02
QUALITY ASSURANCE
A.
Materials and work shall conform to the latest edition of reference specifications and
industry standards listed below and specified herein and to applicable codes and
requirements of local authorities having jurisdiction, whichever is more stringent.
1.03
SUBMITTALS
A.
Submit the following in accordance with the requirements specified under Submittals
in Section 15010.
1. Samples: Submit samples of materials specified herein for approval; obtain
approval before ordering materials. Sample shall include samples of each color,
lettering style and other graphic representation required for each identification
material or system. Provide mockup type sample installation for review and
approval by Engineer.
2. Product Data: Submit copies of manufacturer's latest published literature for
materials specified herein for approval; obtain approval before materials are
delivered to the site. Data shall include manufacturer's technical product data and
installation instructions for each identification material and device required.
Page 1 of 7
3. Maintenance Data: Along with product data and schedules, submit manufacturers
in maintenance manuals for maintaining identification work specified herein.
PART 2 - PRODUCTS
2.01
MATERIALS
A.
B.
Page 2 of 7
7. Lettering
a. Comply with piping system nomenclature as specified, scheduled or shown,
and abbreviate only as necessary for each application length.
b. Arrows: Print each pipe marker with arrows indicating direction of flow, either
integrally with piping system service lettering (to accommodate both
directions), or as separate unit of plastic.
C.
Plastic Tape
1. Provide manufacturer's standard color-coded pressure-sensitive (self-adhesive)
vinyl tape, not less than 3 mils thick.
2. Width: Provide 40 mm wide tape markers on pipes with outside diameters
(including insulation, if any) of less than 150 mm, , 65 mm wide tape for larger
pipes.
3. Color: As directed by the Engineer
E.
Valve Tags
1. Brass Valve Tags: Provide (19) gauge polished brass valve tags with black filled,
stamp-engraved piping system abbreviation in (6 mm) high letters and sequenced
valve numbers ( 15 mm ) high, and with (4 mm ) hole for fastener.
a.
b.
c.
d.
sequenced valve numbers (13 mm ) high, and with (4 mm ) hole for fastener.
Provide (40 mm ) square black tags with white lettering, except as otherwise
indicated.
3. Plastic Valve Tags: Provide manufacturer's standard solid plastic valve tags with
printed enamel lettering, with piping system abbreviation in approximately (5 mm )
high letters and sequenced valve numbers approximately (10 mm ) high, and with
(4mm) hole for fastener. Provide (32 mm ) square white tags with black lettering.
4. Valve Tag Fasteners: Provide manufacturer's standard solid brass (plated steel)
chain (wire link or beaded type), or solid brass S-hooks of the sizes required for
proper attachment of tags to valves; manufacture specifically for that purpose.
5. Access Panel Markers: Provide manufacturer's standard 1.6 mm thick engraved
plastic laminate access panel markers, with abbreviations and numbers
corresponding to concealed valve. Include 3 m center hole to allow attachment.
F.
Valve Schedule Frames: For each page of valve schedule, provide glazed display
frame, with screws for removable mounting on masonry walls. Provide frames of
extruded aluminum, with SSB-grade sheet glass.
G.
H.
Page 4 of 7
PART 3 - EXECUTION
3.01
EXAMINATION
A.
Examine conditions at the job site where work of this section is to be performed to
insure proper arrangement and fit of the work. Start of work implies acceptance of job
site conditions.
3.02
PREPARATION
A.
Examine the Contract Drawings and specifications in order to insure the completeness
of the work required under this Section.
B.
Cooperate in the coordination and scheduling of the work of this Section with the work
of related trades, so as not to delay job progress.
C.
3.03
INSTALLATION/APPLICATION
A.
Ductwork Identification
1. Identify air supply, return, exhaust, intake and relief ductwork with duct markers;
or provide stenciled signs and arrows, showing ductwork service and direction of
flow, in black or white (whichever provides most contrast with ductwork color).
2. In each space where ductwork is exposed, or concealed only by removable ceiling
system, locate signs near points where ductwork originates or continues into
concealed enclosures (shaft, underground or similar concealment), and at 30 feet
spacings along exposed runs.
3. Provide duct markers or stenciled signs on each access door in ductwork and
housings, indicating purpose of access (to what equipment) and other maintenance
and operating instructions, and appropriate safety and procedural information.
4. Where access doors are concealed above acoustical ceilings or similar
concealment, install plasticized tags for identification in lieu of specified signs, at
Engineer's option.
B.
2. Locate pipe markers and color bands as follows wherever piping is exposed to
view in occupied spaces, machine rooms, accessible maintenance spaces (shafts,
tunnels, plenums) and exterior non-concealed locations.
a. Near each valve and control device.
b. Near each branch, excluding short takeoffs for fixtures and terminal units;
mark each pipe at branch, where there could be question of flow pattern.
c. Near locations where pipes pass through walls or floors/ceilings, or enter
non-accessible enclosures.
d. At access doors, manholes and similar access points which permit view of
concealed piping.
e. Near major equipment items and other points of origination and termination.
f.
Valve Identification
1. Provide valve tag on every valve, cock and control device in each piping system;
exclude check valves, valves within factory-fabricated equipment units, plumbing
fixture faucets, convenience and lawn-watering hose bibs, and shutoff valves at
plumbing fixtures, HVAC terminal devices and similar rough-in connections of
end-use fixtures and units. List each tagged valve in valve schedule for each
piping system. Prepare and mount valve tagging schedules for the following
systems:
2. Mount valve schedule frames and schedules in machine rooms where indicated or,
if not otherwise indicated, where directed by Engineer. Where more than one
major machine room is shown for project, install mounted valve schedule in each
major machine room, and repeat only main valves which are to be operated in
conjunction with operations of more than single machine room.
D.
A.
Relocate any mechanical identification device which has become visually blocked by
work of this division or other divisions.
B.
END OF SECTION
Page 7 of 7
PART 1 - GENERAL
1.01
WORK INCLUDED
A.
1.02
RELATED WORK
A.
Division 15 Mechanical.
1.03
SYSTEM DESCRIPTION
A.
General
1. Acoustic and vibration transmission control shall be applied on all work to obtain
the limits specified in the acoustic specification report.
2. Work included:
a. All duct systems and associated equipment will be attenuated to prevent both
transmission noise and breakout from the equipment at any part of the system.
b. All rotating plant will be adequately isolated from the main structure of the
building to prevent the transmission of vibration.
c. All pipework will be suitably installed to prevent undue strain upon equipment
it is connected to and isolation of rotating equipment is also required to prevent
the transmission of vibration.
3. All systems and equipment shall be selected and installed to meet the required
noise criteria specified herein. Where items are not covered then ASHRE Guide
shall be taken as the reference.
B.
silencers are scheduled on the drawings the Contractor shall be responsible for
any adjustment in size required the meet the desired criteria, based on
equipment finally selected.
3. In-Duct Attenuation
a.
C.
1.04
REFERENCES
A.
Page 2 of 7
SUBMITTALS
A.
Product Data
1. Description literature for each of the actual proposed equipment to be used
including:
a. Capacity.
b. Insertion Losses.
c. Pressure Losses.
d. Fluid Flows.
e. Test Reports.
f.
B.
Certificates of approval.
Shop Drawings
1. Shop drawing for each of the actual proposed equipment shall include the
following:
a. Working or manufacturing drawings.
b. Calculations.
c. Installation details.
d. Accessories available indicating those included.
e. Pictures.
PART 2 - PRODUCTS
2.01
ATTENUATORS
A.
Construction
1. The attenuator casting shall be constructed from not less than 1.6mm thick mild
steel, galvanized after manufacture, with all joints continuously welded. The
internal splitters shall be manufactured from perforated galvanized sheet steel not
less than 0.5 mm thick, with aerodynamically shaped leading and trailing edges.
Each splitter shall be secured to the casing by sealed rivets or Pk screws. The
acoustic fill shall be an inert, non - combustible, non-hygroscopic and vermin proof
mineral wool or fiberglass packed to a density of not less than 70kg/m3 and shall
be sealed and protected from particle migration by an impervious membrane
Page 3 of 7
B.
Performances
1. Attenuator performance should meet at least the following criteria:
Straight Silencers
Length
(mm)
900
1200
1500
1800
5
5
6
7
7
9
11
13
14
18
22
26
20
25
31
36
22
27
32
37
19
23
26
30
14
16
19
21
9
10
11
12
5
6
6
9
11
11
18
22
23
25
31
33
27
32
34
23
26
38
16
19
19
10
11
11
7
7
9
13
14
17
26
29
34
36
40
45
37
41
47
30
33
37
21
23
26
12
12
14
Elbow Silencers
Effective Length ( mm )
1200
1500
1600
1800
2000
2400
2. Internal lining of ductwork shall be applied where necessary to achieve the required
level. The lining shall be minimum 15 mm thick and 25kg/m3 density otherwise as
described for attenuators above with minimum thermal conductivity of 0.055
W/mC.
3. Where internal duct lining is to be applied the duct sheet metal sizes shall be
increased to compensate and thus maintain the net free airway sizes noted on the
drawings as duct sizes.
4. Internal duct lining shall have a factory bonded PVC coating fixed to the insulation
with a synthetic rubber base adhesive which is flame retardant when dry.
2.02
A. The sound power level of the noise radiated from the casings of the boxes shall not
exceed the levels stated in the acoustic specification report.
B. Sound power levels are dB re 10 - 12 watts and are based upon terminal boxes
operating with 500 pa inlet air static pressure.
C. Sound power levels shall be determined from reverberate room laboratory test in
accordance with ASHRAE Standard 36B-63. Supporting test data shall be submitted
showing conformance with the above specification.
Page 4 of 7
2.03
A.
General : Select control devices in accordance with Schedule in Part 3. For each item of
isolated equipment, supply and install devices for equal deflection, ensure that
equipment is leveled and that there is adequate clearance under for cleaning.
B.
C.
Spring Mounts:
1. Where specified shall generally be of the unhoused steel compression type having a
height to diameter ratio not above 2.0 in the loaded condition and providing means
for leveling the equipment. Housed type spring mounts may be used only if the
design is submitted and approved.
2. The spring design shall be such that the operating deflection does not exceed 2/3rds
of the maximum available deflection.
3. Each mount shall incorporate a ribbed neoprene pad at least 8mm thick, to provide
isolation of acoustic frequencies . Holding down bolts are not to be used.
4. The number and location of spring mountings shall be such that the supported
equipment does not move or rock excessively under starting and normal operating
conditions.
D.
E.
Neoprene Mounts : These shall be of Rubber in Shear mounts in which the rubber
material is molded to steel inserts and is loaded in a composite of compression and
shear. These mounts shall be supplied only by manufacturers who provide complete
load deflection data and guarantee that data. The mounts shall by design and
management be fail safe . The rubber material shall be used where resistance to oil,
solvents etc., so dictates.
F.
G.
Where cork is used the Contractor shall supply the material and be responsible for its
correct positioning. All other ant vibration mountings shall be supplied and fixed by the
Contractor.
Page 5 of 7
2.04
MACHINERY BASES
A.
Provide at least 100mm high concrete bases for all equipment .Each base shall
comprise a concrete filled four sided welded galvanized surrounded of 50mm x 50mm
x 1.6mm MS angle with return edges fitted with rag-lugs for building in. Accurately
position each surrounded before filling with concrete and cove to floor finish. Submit
shop drawings of all surrounded and bases.
B.
Integrally mount each driving and driven piece of equipment on a suitable steel or cast
iron bedplate or in a fabricated frame and isolate as a single unit.
C.
Where inertia base is specified in the schedule mount the inertia base on the machinery
base specified above. The inertia base shall be of rigid steel and concrete construction
of equivalent weight to the machine and motor assembly, the whole mounted on spring
and neoprene pad assembly.
PART 3 - EXECUTION
3.01
EQUIPMENT CONSIDERATION
A.
Fans
1. Flexible collar connections between fans and ductwork shall be correctly aligned.
2. Centrifugal fans and motor assemblies shall be mounted on a rigid common inertia
base, the whole mounted on spring and rubber vibration isolation mounts.
3. For all fans having motor size 7.5 kw or larger, bases shall be of steel and concrete
weighing as much as the fan motor assembly. Bases shall be sufficiently rigid to
resist any twisting or bending forces, and any dynamic forces, without creating
vibration of the base of any other member of the assembly.
4. All holding down bolts shall be installed so as to avoid bridging of isolation.
B.
Pumps
1. All pumps shall be selected for the highest efficiency consistent with the specified
duty, but it is generally desirable that the pump impeller diameter should not
exceed 0.90 of the maximum impeller diameter capacity of the pump housing to
reduce the possibility of tonal effects. Departure from this to be made only with the
approval of the Engineer. The motor and pump assembly shall be mounted on a
rigid steel and concrete inertia base of equivalent weight to the pump-motor
assembly, the whole mounted on spring isolation mount selected for at least 90%
isolation efficiency but in any case having a minimum deflection of 25mm.
2. Pump bases shall be designed to support the weight of elbows, valves and other
fittings without creating undue stress on the pump assembly.
Page 6 of 7
C.
Refrigeration Equipment
1. The whole assembly shall be isolated from the structure on pads providing at least
90% isolation efficiency at rotational speed.
2. Ensure that the movement of the equipment during start-up or running is not
excessive and if this cannot be met supply the equipment with an inertia base.
3.02
PIPING
A.
All valves, including control valves, shall be adequately sized to prevent unduly high
local velocities and cavitations effects.
B.
Layout piping for flexibility in each of three planes. All piping connected to spring
mounted equipment and up to a distance of 50 diameters shall be supported on hangers
having spring and rubber in series and providing at least 25mm static deflection.
C.
All other pipe supports or hangers shall incorporate an isolating medium such as felt,
ribbed rubber, or high density fiberglass between pipe and hanger or hanger and
structure. This applies to all piping installed in horizontal runs or vertical risers.
D.
At pipe suspension point : fit pipe with 75mm to 100mm length of rigid fiberglass pipe
lagging of appropriate size and then provide oversized clamping bracket to hold pipe
firmly without crushing the insulation unduly. For small copper pipes under 25 mm
diameter , use wrapping of hair-felt or similar of minimum 15mm thick.
E.
Springs to be capable of an additional 50% travel after normal loaded condition takeup.
F.
Where uninsulated pipelines penetrate masonry walls and floors between equipment
rooms and riser ducts, riser ducts and ceiling spaces etc., they shall be isolated from
direct contact with the structure be sleeving with high density fiberglass, felt or other
approved material. Care shall be taken to provide a full acoustical seal at such
penetrations.
G.
Power leads, earth wires, and service pipes shall be provided with flexible connections
at convenient points close to the machine.
3.03
A. Fix lining on the inside of the duct with adjacent sides overlapping at the corners.
B. Lining shall be secured by impaling it over stud-welded rust-proof pins or spot-welded
sheet metal split lugs at not less than 300mm centers with a minimum of two rows of fastenings
per duct side.
C. Washers shall be fitted over the pins or lugs and applied flush to the face of the insulation
without depressing the surface more than 3mm.
END OF SECTION
Page 7 of 7
INSULATION
SECTION 15250
PART 1 - GENERAL
1.01
WORK INCLUDED
A.
1.02
RELATED WORK
A.
Division 15 Mechanical.
1.03
SYSTEM DESCRIPTION
A.
B.
Work included:
1. The following piping systems shall be insulated:
a. Domestic hot water systems (including hot water return).
b. Chilled water supply and return.
Page 1 of 8
1.04
QUALITY ASSURANCE
A.
B.
All insulation, jacket or facing, and adhesive used to adhere jacket or facing to the
insulation, (installed indoors), shall have fire and smoke hazard ratings as tested by
procedure ASTM E-84, not exceeding flame spread of 25, and smoke developed of
150. Accessories such as adhesives, mastics, comments, tapes and cloths for fittings
shall have similar component ratings.
C.
Installers Qualifications:
1. Use only applicators regularly engaged in the business of insulating mechanical
systems.
D.
E.
To ensure the correct specification and thickness of insulation has been applied, The
Contractor shall, if required by the Engineer, cut one of the sections from the finished
covering. If defects are revealed, the Contractor shall, at his own expense remove the
whole of the covering and provides and fix new insulation to the satisfaction of the
Engineer.
1.05
REFERENCES
A.
Referenced Standards:
1. American Society for Testing and Materials (ASTM).
a. E84, Surface Burning Characteristics of Building Materials.
1.06
DEFINITIONS
A.
B.
C.
D.
1.07
SUBMITTALS
A.
PART 2 - PRODUCTS
2.01.
GENERAL REQUIREMENTS
Supply and install all insulation and lagging wherever specified in this Book of
Specifications in accordance with the requirements of this section.
Fire-Test-Response Characteristics: As determined by testing materials identical to
those specified in this Section according to ASTM E 84, by a testing and inspecting
agency acceptable to authorities having jurisdiction.
All duct insulation shall be tested in accordance with test methods BS476 pt 6 Fire
Test on Building Materials and Structures, Method of Test for Fire Propagation for
Products.
All duct insulation shall be tested in accordance with test methods ISO 5659-Smoke
Density and Toxicity with Additional Gas Analysis. The insulation must comply with
the Standard in terms of smoke density (Dm <200) and combustion gas concentrations
must not exceed those specified in the Standard.
Test certificates form an independent testing authority shall be submitted.
All duct insulation should be accompanied by Manufacturers Test Certificate.
Product shall be resistant to attack of algae, bacteria, vermin and the growth of moulds
and fungi.
Before installing insulation, build mock-ups for each type of insulation and finish listed
below to demonstrate quality of insulation application and finishes. Build mock-ups
Page 3 of 8
according to the following requirements, using materials indicated for the completed
Work:
1.
2.
3.
4.
5.
6.
7.
8.
2.02.
a.
b.
Concerning the fresh air ducts inside floors and the Air conditioning ducts, preinsulated ducts will be specified, refer to section: 15801-2.11
12-mm
12-mm
Outdoor ducts
25-mm
Insulation Finish:
Insulation finish shall be executed as follows:
a.
b.
c.
All insulation exposed on roof or to weather agents shall be provided over and
above the Specification requirements with additional water proofing and
weather proofing material in 3 layers, plus a final outer jacket of aluminum
construction 0.8mm thick.
Page 5 of 8
d.
2.03.
All pipes running exposed on roof shall be insulated with rigid pipe insulation.
All pipes insulation shall be finished by a factory applied vapor barrier of
aluminum foil laminated on to Kraft paper and reinforced with glass yarn
mesh. All joints to be sealed with sealing tape and held in place by adequate
number of non-corrodible bands.
2.04.
Page 6 of 8
15 mm
20 mm
25 mm
INSPECTION:
A.
Prior to all work of this Section, carefully inspect the installation of the materials and
equipment to be insulated to verify that all such work is complete to the point where
this installation may properly commence.
B.
Verify that all insulation may be installed in accordance with all governing codes and
regulations, the original design, the referenced standards, and the manufacturers
written instructions.
C.
3.02
TESTS
A.
Do not install insulation until specified tests have been conducted on the system to be
insulated and results approved.
3.03
QUALITY
A.
Particular attention shall be given to the finished appearances of all thermal insulation
and cladding which must present a neat and symmetrical appearance running true in
line with pipe layouts. Any rough, irregular or badly finished surfaces shall be removed
and replaced to the satisfaction.
B.
All pipework shall be insulated separately, adjacent and parallel pipes shall not be
married together with insulating materials.
C.
Thermal insulation materials and their finishes shall be asbestos free. Canvas jackets
shall be non-combustible and flame-resistant.
D.
For painting and identification of the finished insulation refer to Sections 09900 and
01086.
Page 7 of 8
E.
Due allowance shall be made in all insulation applications to cater for movement due to
expansion and the Contractor shall provide and fix the necessary space piece to ensure
that the insulation is continuous where pipework passes through walls, floors, pipe
brackets etc. and other thin fire divisions.
F.
The Contractor shall ensure that particular attention shall be paid to sealing the
insulation against water or water vapor ingress at all flanges, expansion joints, valves,
anchors and pipe supports.
END OF SECTION
Page 8 of 8
GENERAL
1.1 CONTRACTORS RESPONSIBILITIES
The Contractor is responsible for the quality and the satisfactory operation of the
installations entrusted to him, as well as for compliance with the performance
stipulated in this document.
Consequently, for his own account and under his own responsibility, he must carry out
all calculations and select the necessary materials and equipment.
Apart from the required performance definitions, this document and the relevant
drawings also provide many indications resulting from the studies carried out by the
Engineer.
The Contractor shall review these studies and check the corresponding indications.
The same applies to equipment selection, for which the information given in this
document must be deemed as indicative, only and defines only the minimum
requirements.
1.2 SCOPE DESCRIPTION
The contractor shall furnish all labour, materials, tools, supplies, equipment,
transportation, supervision, technical, professional and other services, and shall
perform all operations necessary and required to satisfactorily complete all the
necessary engineering, procurement services, construction work and commissioning for
the fire protection systems and equipments for the project.
1.3 BASIC DESIGN CRITERIA
Refer tender Drawings and Documents.
1.4 CODES AND STANDARDS
All the systems shall be designed and installed in accordance with the applicable Local
Civil Defense Codes and Standards. They shall be particularly in accordance with the
following NFPA /BS EN/Vds standards:
NFPA 10, Standard for Installation of Portable Fire Extinguishers
NFPA 13, Standard for the Installation of Sprinkler Systems
NFPA 14, Standard for the Installation of Standpipe and Hose Systems
Page 1 of 43
NFPA 20, Standard for the Installation of Stationary Pumps for Fire
Protection
NFPA 22, Standard for Water Tanks for Private Fire Protection
NFPA 24, Standard for the Installation of Private Fire Service Mains and
their Appurtenance
NFPA-25, Standard for Inspection, Testing, and Maintenance of Water
Based Fire Protection Systems
NFPA-70, National Electric Code
NFPA 72, National Fire Alarm Code
NFPA 92A, Standard for Smoke Control Systems
NFPA-101, Life Safety Code
NFPA-110, Standard for Emergency and Stand by Power systems
NFPA-170, Standard for Fire Safety Symbols
NFPA 204, Standard for Smoke and Heat Venting
NFPA-220, Standard for types of Building Construction
NFPA-221, Standard for Fire Walls and Fire Barrier Walls
NFPA 780, Standard for the Installation Lightning Protection Systems
NFPA-2001, Standard on Clean Agent Fire Extinguishing systems
NFPA 5000, Building Construction & Safety Code
OSHA, Code of federal regulations, Title 29, Part 1926
BS EN 54 Standard for installation of Fire Alarm System.
1.5 SCOPE OF WORK:
This specification covers the suppy. Delivery and complete installation on site and
in full working order of the equipment specified in this document and/or shown on
the drawing
Full particulars, performance curves and illustrations of the equipment, complying
as closely as possible with this specification, shall be provided with the tender, but
any deviations from the specification must be fully and clearly indicated in the
tender submission schedules.
The Contractor shall provide and install:
The complete fire pumping station, including the firewater pumps (pumps,
diesel engines drive, engines drive controllers, skid, diesel underground storage
Page 2 of 43
& pump,...), the jockey pump (pumps, electric drive, electric drive controllers),
the piping & hanging, the valves, check-valves, relief valves, fittings, the
instrumentation, the storage fire water tanks and feeding controllers (valves &
controllers).
The firewater mains (sprinkler, standpipe & hydrant), including the piping, the
fittings, the hanging, the block-valves & the hydrants.
The wet sprinkler systems, including the control valves, the piping, the
hanging, the heads, the instrumentation.
The hose reels (standpipes, hose connections, external hose streams).
The portables extinguishers
Clean agent fire suppression system for the rooms mentioned in the drawings.
The marking of all the safety equipment
The Contractor shall be responsible for all the following aspects of the provided
systems:
The checking of the tender drawings and any calculations supplied with the
drawings. The Contractor shall check each drawing and satisfy himself that the
design is correct for the equipment offered and will meet all applicable rules
and regulations
The provision of any additional information required by the Contractors
installation engineers which are particular to the equipment being supplied e.g.
fabrication drawings, equipment data sheets, commissioning instructions etc.
The provision of drawings and equipment data related to the systems as
required by the Engineer
The supply of all required equipment and other fixtures associated with the
systems
Painting
Shop testing of equipment and provision of inspection facilities
Certification
The provision and fittings of suitable wall boxes, transits and plates where pipe
work or cable passes through walls, etc...as well as fire rating reinstatement
materials
The supply of as built drawings and as built calculations
The provision of scaffolding, ramps and any other equipment required to
enable the systems to be installed, tested and commissioned correctly
Page 3 of 43
A demonstration to key personnel in the use and testing of the systems and
equipment supplied
Operating and maintenance manuals.
1.6 MATERIALS
The Contractor shall supply all materials necessary to make up effective and
operable fire protection, detection and alarm systems, voice alarm system and
emergency & exit lighting systems for the facilities indicated in the drawings and
in the present specification, and particularly :
all the necessary pipe work, valves, equipment and instrumentation required for
the facilities
all electrical cable between panels, junction boxes, sensors, call points, pressure
switches, alarm bells, flashing lights, ... and generally all the cable (and their
supports) required for the facilities. Cables passing through fire walls shall not
modified the fire rating of the wall (reconstitution of fire rating with approved
sealant materials by the Contractor)
local alarms indicating actuation of the systems
All detectors, fire signalling and alarm cabling shall be installed by the
Contractor using materials in accordance with international standards.
All emergency lights, exit lights with directional arrow marks & pictograms as
required,central battery panels, addressable monitoring panel, interface
modules, phase monitoring relays and interconnecting cabling shall be installed
by the contractor using the materials in accordance with International
standards.
The main electrical supply to the Contractors equipment will be by others.
All instrumentation and electrical equipment will be enclosed to suit the Hazard
Class of the area. The Hazard Class of each area is indicated on the Hazardous
Area Layouts.
Hazardous Area Certificate will be required for each item supplied within the
Hazardous Area.
The Contractor shall define in the quotation the full specification of every system
proposed (pipe work, cables, equipment,)
1.7 QUALITY OF MATERIALS
Only materials of first-class quality shall be used and all materials shall be subject
to the approval of the Engineer.
Wherever applicable, the system and material is to comply with the relevant
International Standards of NFPA codes or British Standards /Vds /LPCB
specifications.
Page 4 of 43
Page 5 of 43
1.9.2
Drawings
1.10
Discharge tests shall be carried out on Site at the discretion of the Employer.
All tests shall be carried out in the presence of the Employers insurers or their
nominated representatives.
The Contractor shall provide all the necessary tools and equipment for testing
and commissioning activities.
1.11
FIRE FIGHTING.
2.1 FIRE EXTINGUISHERS.
2.1.1
General:
The classification of fire extinguishers shall consist of a letter that indicates the
class of fire on which a fire extinguisher has been found to be effective, preceded
by a rating number (Class A and Class B only) that indicates the relative
extinguishing effectiveness.
Page 6 of 43
The distribution of fire extinguishers shall comply with the prescribed requirements
of NFPA-10, as shown on the drawings and the specific requirements of the local
Civil Defence Authorities.
2.1.2
Definitions
The type of extinguisher needed depends on the right type of fire that may occurs in
the room or building.
According to NFPA 10, several classes of fire have been defined:
I. Class A Fires: Fires in ordinary combustible materials, such as wood, cloth,
paper, rubber, and many plastics.
II. Class B Fires: Fires in flammable liquids, combustible liquids, petroleum
greases, tars, oils, oil-based paints, solvents, lacquers, alcohols, and flammable
gases.
III. Class C Fires: fires that involve energized electrical equipment where the
electrical non-conductivity of the extinguishing media is of importance. (Where
electrical equipment is de-energized, fire extinguishers for class A or B fires can
be used safely.)
IV. Class D Fires: Fires in combustible metals, such as magnesium, titanium,
zirconium, sodium, lithium, and potassium.
V. Class K Fires: Fires in cooking appliances that involve combustible cooking
media (vegetable or animal oils and fats.)
a. Building presenting class B or C fire hazard shall be equipped with a
regular number of class A extinguishers dedicated to the building
protection, and shall also be equipped with adding class B or C
extinguishers.
b. According to these definitions, all parts of the buildings shall be
equipped with class ABC type extinguishers. In the meantime, rooms
such as Storages, Workshops and other rooms housing electrical
equipments, shall be equipped with adding class C extinguishers.
2.1.3
tube shall be made of PVC material.. All extinguishers shall carry instructions for
use in English and Arabic.
The Dry powder fire extinguishers shall have LPCB approval/KITE mark approval
and having Local Civil Defense approvals.
Multipurpose Dry Chemical Extinguishers (Class A, Class B, and Class C Fires).
The capacity of the extinguisher shall be 4Kg and shall have a fire rating of 21A
and 113B Rating as shown in the drawings.
2.1.4
Page 8 of 43
The Carbon dioxide fire extinguishers shall have LPCB approval/KITE mark
approval and or manufactured complying with BS EN3 standards and having
Local Civil Defence approvals.
Typical applications are electrical & electronic equipments, food preparation
areas, laboratories, and printing or duplicating areas, telephone equipment Rooms,
Engine Rooms, Control Rooms, Paint spray Booths, Flammable liquid storage
areas etc,. Since the agent is discharged in the form of a gas/snow cloud, it has a
relatively short range of 3 ft to 8 ft (1 m to 2.4 m). This type of fire extinguisher is
not recommended for outdoor use where windy conditions prevail, or for indoor
use in locations that are subject to strong air currents because the agent can rapidly
dissipate and prevent extinguishment. The concentration needed for fire
extinguishment reduces the amount of oxygen (air) needed for life safety when the
discharge is in a confined area (space).
2.2 EXECUTION:
1. Fire extinguishers shall be conspicuously located where they will be readily
accessible and immediately available in the event of fire. Preferably they shall
be located along normal paths of travel, including exits from areas.
2. Fire extinguishers shall not be obstructed or obscured from view.
3. Portable fire extinguishers other than wheeled types shall be securely installed
on the hanger or in the bracket supplied or placed in cabinets or wall recesses.
The hanger or bracket shall be securely and properly anchored to the mounting
surface in accordance with the manufacturers instructions. Wheeled-type fire
extinguishers shall be located in a designated location.
4. Fire extinguishers having a gross weight not exceeding 40 lb (18.14 kg) shall
be installed so that the top of the fire extinguisher is not more than 5 ft (1.53 m)
above the floor. Fire extinguishers having a gross weight greater than 40 lb
(18.14 kg) (except wheeled types) shall be so installed that the top of the fire
extinguisher is not more than 31/2 ft (1.07 m) above the floor. In no case shall
the clearance between the bottom of the fire extinguisher and the floor be less
than 4 in. (10.2 cm).
5. Fire extinguishers shall be installed in a 1.2 mm thick, stainless steel, polished
finish cabinets where required in finished rooms / office areas and as shown on
the drawings and shall be confirmed with the Architect.
2.3 STANDPIPE AND HOSE SYSTEMS:
2.3.1
The hose reel drum shall be made of stainless steel with the cabinet supported
with reinforced support arm, which shall be chrome plated and swing through
180 degrees. Welding of any part on cabinet front shall not be allowed. The
reels shall comply with BS EN 671 and comprise a reinforced rubber hose,
25mm. diameter x 30m long, coiled on a revolving drum. The outer end of a
hose shall be fitted with a jet / spray / shut-off control nozzle. The inner end
of the hose shall be connected through the reel to the water supply.
Page 9 of 43
The reels shall incorporate a valve that automatically turns on the water supply
when more than approximately 3 mtr of hose is unreeled, and shuts off again
when the hose is re-wound onto the reel. A manual shut-off valve of the wheel
type shall also be installed on the service pipe to each hose reel.
The hose nozzle shall be, (JET/SPRAY/SHUT OFF) type nozzle.
Each hose reel shall be installed and tested to BS 5274 and shall deliver not less
than 0.4 l/s when the two top-most reels are in use simultaneously providing a
jet of approximately 6 mtr. in length. Pressure reducing devices shall be
provided whenever necessary to limit the pressure as per local athority remotest
point requirenment.
An instruction plate shall be supplied with each reel indicating the method of
use in English and Arabic.
The hose reels shall be of a make, approved by the Ministry of the Interior Civil
Defense Department, and shall be supplied through an authorized agent.
Brief operating instructions should be clearly displayed on or by each hose reel
in both English & Arabic languages. e.g.
TO OPERATE
RUN OUT HOSE
TURN ON LOCK AT NOZZLE.
The hose reels shall be suitable for working pressures up to 4.5 bar (65psi) and
shall be installed in accordance with the manufacturers instructions.
2.3.2
LANDING VALVES:
Landing valves shall be of a type acceptable to the Fire Brigade use inside
buildings as shown on the drawings. Landing valves shall be UL listed and FM
approved or should have a BSI KITE Mark , install built in pressure reducing
landing valve where the pressure exeeds the 12 bar, with 65mm diameter bore
fitted with 65 mm. instantaneous female coupling to conform to BS 336 and a
blank cap secured by a suitable length of chain.
The valve shall be of brass / Gunmetal construction with approved finish.If the
landing valve is Ul listed then the outlet coupling must be quick instantanious
with local fire services and should have BSI Kitemark.The installation of the
coupling should be done by an certified installer.
Landing valves shall be installed inside the cabinet as shown in the drawing, at
a height above floor level between 750 mm and 1100 mm. The outlet shall be
installed to give clearances of not less than 150 mm on both sides and below
the valve and not less than 200 mm clearance above the hand wheel.
2.3.3
The unit shall be of UL listed / FM approved make or shall have BSI kite mark
approvals.
The inlet breeching piece shall be of horizontal pattern having a 150 mm
flanged outlet
and four 65 mm instantaneous male inlets complete with
blank caps and chains. A non-return (check) valve shall protect the inlet. The
coupling shall comply with BS 336. The inlet connections shall be of suitable
type of local fire brigade department / Local Civil Defense.
The breaching piece shall be equipped with a 25 mm drain valve to drain the
riser. The valve should be kept strapped and padlocked closed.
All parts including valve body, chain and caps shall be brass / gunmetal,
polished chrome plated finish.
Page 11 of 43
2.3.6
SPRINKLER SYSTEM:
3.1 HAZARD CLASSIFICATION:
The sprinkler system shall be designed as per NFPA-13 Installation of Sprinkler
System requirements. Spacing of sprinklers shall suit the hazard of the occupancy
as shown in the drawing.
Page 13 of 43
Page 14 of 43
.Alarm valves shall be complete with Water Motor Alarm Gong, all required
auxiliary valves and drains and with pressure switch for wiring into the building
electric alarm system.
Alarm check valves shall be iron body bronze trim for minimum175psig(12bar)
working pressure complete with electric pressure switches, test and alarm bell
connections. Pressure gauges and all other ancillaries.
3.3.2 WATER MOTOR ALARMS:
The sprinkler system shall be fitted with an approved water motor alarm, which
shall be located at a distance not exceeding 21m from the alarm valve, and at a
height not to exceed 6m above the alarm valve.
The pipe work and fittings used shall be to the sizes determined by the NFPA-13
The pipe work shall be arranged to drain through a fitting having an orifice not
exceeding 3 mm in diameter. The orifice plate may form an integral part of the
fitting but shall be manufactured from a non-ferrous material to prevent the hole
from becoming blocked by corrosion or foreign matter.
A 15 mm test valve shall be installed on the installation side of each alarm valve.
3.3.3 ELECTRIC ALARM PRESSURE SWITCHES:
The electric alarm pressure swithch should be UL 753 Listed.It shall be installed
in the system as per NFPA 13 and they shall be mounted on a vertical branch pipe
at least 300 mm long.
The pressure switch may be of the diaphragm bellows operated type, and shall be
sufficiently sensitive to operate when only one sprinkler is discharging. The
pressure switch shall be provided with volt free contracts to facilitate monitoring
by a Building Management System, and wired to the main fire alarm panel.
3.3.4 PRESSURE GAUGES:
Pressure gauges shall be fitted to meet the requirements of the LPC. Pressure
gauges shall conform to BS 1780 or equivalent International Standard. The
maximum reading of the scale shall be 150% of the maximum system pressure and
each scale shall have divisions not exceeding 0.2bar.
3.3.5 AUTOMATIC ZONE CHECK (ZONE CONTROL
VALVE)ASSEMBLY:
A zone control valve set shall UL, FM Approved and it is to be provided for each
sprinkler system zone as shown on the tender drawings, and shall comprise:
Butterfly valve shall have UL 1091 .It shall be fitted with factory installed UL/Fm
apporved tamper switch.
Flow alarm switch shall be UL listed and FM approved for the size of the pipe in
which it is installed as a paddle type water flow indicator. Shall be fixed after the
butterfly valve, on the main supply pipe and before any connection is taken off.
Page 15 of 43
stop valves shall be clearly marked to indicate which direction the wheel is to be
turned to close the valve.
An indication shall also be provided which shows whether the valve is open or
shut.
Each main stop valves shall be installed with a tamper / supervisory switch and
interconnected to the building fire alarm system or secured open by a padlock or
riveted strap.
3.3.7 DRAIN LINES
All drain lines from test valves, drain down points etc., shall discharge over
suitable and proper drain vent. Each drain vent shall be connected to a 50 mm
drain line, which shall discharge over a suitable gully.
3.3.8 EXECUTION/INSTALLATION.
The Protection Area of Coverage per sprinkler (As) shall be determined as the
multiplication of the distance between sprinklers upstream and downstream, and
the perpendicular distance between a sprinkler and another on the adjacent branch
line.
Installation for hydraulically calculated system with concealed pendent and
upright sprinklers shall be, according to NFPA 13 latest edition and local authority
requirements.
Complete Sprinkler system shall be installed in accordance with NFPA-13 and
Authority having jurisdiction requirements and as shown on the drawing.
The Fire protection contractor shall be responsible to co-ordinate his work with all
other trades and shall be completely familiar with and shall make allowance for
conditions which affect the fire protection installation.
The Zone control valve assembly locations and access panels shall be mounted
securely and provided with proper sign boards.
Provide a pressure guage with a isolation cock with inspectors test plug on top of
the each sprinkler pipe risers.
3.3.9 CLEANING AND TESTING
Tubes and all items of equipment shall be delivered, stored and maintained in
closed storage with their open ends effectively plugged, capped or sealed. All
fittings, valves and sundry items shall be stored in clean bins or bagged and stowed
in suitable racks. All such stored items shall be maintained under weatherproofed
cover to be supplied by the MEP sub-contractor until they are ready for
incorporation in the works. Particular care shall be taken to ensure that electrical
equipment and components are kept clean and dry.
Before installations are handed over or subjected to the inspection and tests, the
entire installation shall be thoroughly cleaned, both internally and externally.
Page 17 of 43
All fire protection installations shall be flushed out with clean water. During the
flushing out, provision shall be made to exclude any items of plant, which could be
damaged by the cleaning operation. The entire operation shall be carried out to the
satisfaction of the Engineer.
The fire protection system shall be tested in accordance with the NFPA codes and
the relevant standards, with particular reference the requirements set forth in this
section:
All testing shall be performed under the work of this section. All services required
for testing shall be a responsibility of the work of this section. The MEP subContractor shall notify the Engineer of all tests, 48 hours prior to testing.
The fire protection piping System shall be tested hydrostatically for not less than 2
hours and at one time of the system pressure without any leaks or as directed by
the local fire department.
If the systems are tested in sections, the connection to the previously tested section
shall be included.
All tests that may be required by the local fire authorities shall be performed under
the work of this section, in the presence of their representative, if so required.
All leaks shall be corrected and the system re-tested until no leaks are found, at no
cost to the client.
Functional tests of all water flow alarms are a responsibility of the works of this
Section.
When the various systems are completed,
equipment to demonstrate proper operating
under the observation of the inspector and
clients operators shall be instructed during
performed under the work of this section.
Should any piece of equipment or apparatus of any material or work fail in any of
these tests, it shall be immediately removed and replaced by a perfect material, and
the portion of the work replaces shall again be tested under the work of this
Section.
Cost to repair any damages to the building construction occasioned by pipe leaks
or defective materials shall be become under the works of this section, at no cost to
the client. All corrective work shall commence immediately after damage occurs.
PIPES, FITTINGS AND SUPPORTS.
4.1 PIPING
1. Pipes and fittings shall be in conformance with the following specifications unless
specified otherwise by the Authority having jurisdiction. Obtain approval of local
Authorities before proceeding with the work.
2. Pipe shall be seamless, black steel, schedule 40.
Page 18 of 43
5. Pipes bendings
a. Schedule 40 Steel pipes bending is allowed if bending are executed with no
defaults, no diameter reduction and no significant deviation in the pipes circle
symmetry.
The bending minimum radius must be:
Page 19 of 43
4.3 SUPPORTS:
1. Pipe hangers and supports must be in accordance to NFPA13.
2. Pipes supports shall be designed to maintain their integrity in case of fire
exposure.
3. All underground piping / valves shall be supported with Concrete Anchor
Thrust blocks as recommended by the manufacturer. Provide calculation for the
Engineers approval.
4. All Above ground piping / equipments hangers, supports and sway braces shall
be fabricated in accordance with ANSI B 31.1. The Hangers, rod supports and
supporting devices and accessories shall be capable of supporting at least twice
the live loads of the product being supported. All hangers, supports and
accessories shall be UL listed and FM approved make.
5. Hangers shall be adjustable clevis type, of yoke and lower U strap design with
cross bolt and manufactured from galvanised steel. Cross bolt shall have a
double locking nuts. Vertical adjustable supporting rod shall have a load nut
below the yoke and a locking nut above the yoke.
6. Concrete anchors shall be factory made cadmium plated alloy steel expansion
shield type.
7. Concrete inserts shall be factory made galvanised malleable iron, poured in
place type, screwed or toggle style.
8. Riser clamps shall be galvanised steel bands shaped to tightly fit O.D. of the
pipe, secured with bolts and nuts.
9. Piercing of load supporting system is not permitted.
10.The supporting structure can be directly attached to equipments if the
equipment supplier certifies this supporting feasibility;
11.The welding of pipes on the supports of the pipes is not permitted;
12.Pipes supporting system must be reinforced in order to reduce any movements
resulting from nozzles reaction and therefore preserve the system performance
and integrity if battering ram is used;
13.The maximum length for a non-supported DN 25 pipe is 0.8 meter;
14.When possible, loop-type clamps will be used
15.If spring hangers are used, they shall be installed and located in accordance
with NFPA 13 specifications.
16.The Contractor shall take into account the problem of dilatation (of his systems
but also of the buildings) and shall make the coordination with the others
Contractors to solve the support problems.
Page 20 of 43
Each system shall be design to insure the maximum pumping capacity even if 1
pump fails.
The total supplying of all the necessary equipment for the firewater production
(including pumps, engines driven, controllers, instrumentation, piping, valves,
relief valves, ) is included in the Contractors scope of work.
The supplying and installation of the day fuel tank of the engines is included in the
Contractors scope.
The fuel tank (and all the fuel installation) shall be in accordance with NFPA
standards & Environmental legislation of local Authorities
The air supply system of the diesel engines drive (automatic opening, venting
panels, ..) is included in the Contractors scope.
The fire pumps, motor, engine and controllers shall be UL listed or FM approved,
built in the country where the agreement is made.
The fire pumps and engine driven shall be in accordance with NPFA 20 (curves,
starting, protection, ).
The problem of surge (hammer effect) shall be taken into account in the design. A
surge analysis shall be conducted and specific surge pressure control system shall
be installed.
Over-pressure system shall also be installed.
The contractor shall provide fully certified hydraulic calculations for exact sizing
of the pumps.
The pumps shall be furnished with a full set of bench test certificates proving
acceptability for the design points of this installation.
5.2 PRODUCTS:
5.2.1
FIRE PUMPS:
Fire pumps shall be UL or ULC listed or FM approved and manufactured by an
approved manufacturer. Each pump shall have a capacity as shown in pump
schedule, adjusted as necessary to suit the hydraulic calculations.
Page 21 of 43
The pumping unit shall be listed by Underwriters Laboratories Inc., and shall be
fully approved by the Associated Factory Mutual Fire Insurance Companies. The
pumping unit shall meet all requirements of the National Fire Protection
Association Pamphlet No. 20.
The pumps shall also deliver not less than 150% of rated capacity at a pressure of
not less than 65% of rated pressure. The shutoff pressure shall not exceed 140%
of the rated pressure at rated capacity.
5.2.1.1 FIRE PUMPS TYPE:
Each fire pump shall be of horizontal split case centrifugal single stage or
multistage construction, specifically labeled for fire service and capable of
proving the required flow and pressure of the entire development. The pump shall
be connected to the combined sprinkler/standpipe system. The suction supply for
the fire pump shall be from a storage tank at a maximum pressure of 20 kPa and a
minimum pressure of 0 kPa. The pump casing shall be cast iron and rated to
withstand twice the working pressure.
5.2.1.2 PUMP CONSTRUCTION:
The pump construction shall be cast iron casing, Bronze impeller, Stainless Steel
shaft and gland packing.
Note: The pump shall also deliver not less than 150 % of the rated capacity at a
pressure of not less than 65 % of the rated pressure. The shut off pressure shall not
exceed 140 % of the rated pressure at rated capacity.
5.2.1.3 PUMP DISCHARGE & HEAD:
The pump discharge & head shown on the drawing schedule is an estimate. The
fire protection contractor shall select a pump discharge and head to satisfy the fire
protection system requirements resulting from the system hydraulic calculations.
5.2.1.4 FIRE PUMP ACCESSORIES:
The Fire and Sprinkler Pumps shall include the following accessories, as required
by NFPA standards:
1. Flow Metering Device, shall be of the Venturi type. Pilot and annular devices
will not be acceptable- One metering device shall be provided for each pump. or
as shown on the drawings. Pipe water back to the storage tank.
2. Discharge tee.
3. Necessary isolating valves with supervisory switches.
4. Air release valve and fittings.
5. Discharge pressure gauge.
Page 22 of 43
6. Main relief valve, pilot operated, enclosed relief valve overflow cone and
discharge tee with elbow (diesel drive only).
7. Main relief valve with discharge pipes to water tank.
8. Pump casing relief valve.
9. Pressure recorder as required by NFPA 20.
5.2.2
The Fire Pump motor control shall be UL listed and FM Approved. It shall be
completely assembled, wired and tested by the control manufacturer before
shipment from factory, and shall be labeled 'Fire Pump Controller". The controller
shall be located as dose as practical and within sight of the motor, preferably
mounted on the pump skid.
The controller shall be so located or protected that it will not be injured by water
escaping from the pump or connection. The controller shall be of the combined
manual and automatic auto transformer type. And shall be complete with:
1. Disconnect switch - externally operable, quick-break type.
2. Circuit breaker - time delay type with trips in all phases set for 300% of the
motor full load current3. Motor starter, capable of being energized automatically through the pressure
switch or manually by means of an externally operable handle. Motor starter shall
be of the autotransformer type.
4. Pressure switch, of adjustable type.
5. Running period timer - set to keep motor in operation, when started
automatically, for a minimum period of one minute for each 10 HP motor rating,
but not to exceed 7 minutes.
Page 23 of 43
Diesel engine shall be UL listed and FM approved for fire protection service.
The engine shall be of the self contained open type, mounted on a suitable base
with the following minimum plus any others that may be necessary by NFPA-20
and local CD requirements.
1. Dual battery set sized to NFPA -20 requirements with electrolyte shipped in
separate containers, rack and cables.
2. Dual battery charger of proper type for batteries used ( included in UL Listed /
FM Approved controller ). Power to battery charger shall be supplied from
electric pump control panel. Wiring from control panel to battery chargers
shall be by the contractor.
3. Electric starter with suitable generator and voltage regulator.
4. Engine water pump.
5. Heat exchanger cooling system.
6. Water cooled or ceramic blanketed exhaust manifold.
7. Lubricating oil pump and filter.
8. Speed governor.
9. Fuel injection system.
10. Air cleaner.
11. Drive plate
12. Fuel Pump
13. Proper instrument panel, complete with engine run warning light, water
temperature gauge, oil pressure gauge, ammeter, totalizing type tachometer and
hour meter.
14. Residential Grade Muffler.
15. Cooling water line for the engine heat exchanger assembly.
16. Flexible exhaust connectors.
Page 24 of 43
All engine wiring for automatic operation shall terminate in a proper junction box
to permit connection to control panel.
5.2.4.1 FUEL SYSTEM :
A suitable fuel system for the diesel engine shall be furnished. It must be in
accordance with NFPA Pamphlet No.20 and shall include above surface day
storage tank, flexible hose connectors, combination vent, flesh arrestor and fill cap.
5.2.4.2 SILENCER ( MUFFLER ) :
The silencer shall be for turbo-charged engines, sized and selected to
accommodate the allowable pressure drop of the engine.
The silencer shall provide an average attenuation of 20-25 Db (a).
The silencer shall be designed by HEAVY DUTY APPLICATIONS, with
noise attenuation across the entire audible range of the frequency spectrum 63
through 8000 Hz. The silencer shall consist of a series of chambers connected
by non-resonant tubes. The entire silencer shall be manufactured from plate
steel and be of a completely welded design. The heavy plate ensure longer
silencer life and better resistance to damage. The heavy plate shall prevent
shell radiated noise. There shall be no spot welds or press fits used.
Silencer inlet and discharge shall be flanged, manufactured from minimum
10mm thick plate and drilled to ANSI 70 kg. Silencers shall be either and
in/end out and side in/end out configurations to suit installation.
Provide 12mm drain connections. Prior to shipping, the silencers shall be
thoroughly cleaned and coated in a high temperature 650C aluminum paint.
5.2.4.3 DIESEL ENGINE DRIVE CONTROLLER :
Automatic Diesel Drive Engine Control Panel : The automatic engine control panel
shall be approved for fire pump service and shall meet the requirements of NFPA
Pamphlet No. 20. The panel shall be of the floor mounted type, and enclosed in
moisture and dust tight housing. A combination manual and automatic type
controller with Manual-Off-Automatic selector shall be provided and a 240 volt
single phase power failure relay or a pressure switch, which will ( when the system
pressure drops ) activate all electric circuits to automatically start the engine.
Should the engine fail to start after the required cranking cycles, the controller shall
disconnect the starting circuit and activate an alarm system using lights and buzzer
or bell. Low oil pressure and high jacket-water temperature shall also be
indicated by a suitable alarm system. The engine shall not shut down if either of
these conditions occurs during an operating cycle.
The engine shall be started automatically by the Controller at least once a week,
adjustable, and operate a minimum of 30 minutes ( adjustable ). An appropriate
timing arrangement shall determine the day and hour of this test.
Page 25 of 43
Starting the engine by fire alarm relay, deluge valve relay or remote push-button
station shall be included in the Controller circuit.
A remote alarm panel shall be furnished as per NFPA Pamphlet No. 20.
Pressure recorder (7 day drive) shall be provided within the control panel.
Fire Pump Controller shall be a diesel engine type, Controller approved and listed
by the Underwriters Laboratories for fire pump service, carry the labels of both UL
and CSA and meet the requirements of the National Fire Protection Association
Standards No. 20, as presently required by UL.
The controller shall be a Bulletin #500 diesel engine fire pump controller Model
FPD, as manufactured by Tornatech Inc., or approved equal, wired and tested by
the manufacture, rated for ( 12 or 24 ) V.D.C., with 240 volts, 50 Hz AC Input and
supplied in a floor mounting EEMAC 12 enclosure, complete with dripshield
suitable for pump room environment.
The controller shall incorporate the following:
1.
In case of battery failure, the charger shall initiate an alarm and provide a
signal to prevent the use of the defective battery during the start attempt cycle.
2.
Relays: All relays shall be equipped with manual test buttons, status ON
OFF indicators, be of the plug in type and shall meet all voltage and current
requirements.
3.
Page 26 of 43
Engine over speed, engine fails to start, low oil pressure, high
coolant temperature.
4.
5.2.5
Annunciator: The annunciator panel shall feature extra long life light
bulbs, rated at 14 V for a 12 V and 28 V for a 24 V system.
Page 27 of 43
3.
Option No.2
Option No.3
Option No.4
JOCKEY PUMPS:
The Jockey pump capacity and pressure shall be as indicated in the pump schedule
on the drawings.
Pump shall be constructed as follows:
Type
Rotation
Motor
Page 28 of 43
Motor bracket
: Cast type, connecting motor to pump
Diffuser cases
: Pressure containing, flow directing
Impellers
: Stainless steel
Shaft, l
: Stainless steel,
Pump discharge
: Flanged type
Control
: Definite purpose type, magnetic starter
In NEMA II enclosure, with reset button
Pump controller shall be factory pre-wired and tested. Pressure switch shall sense
low pressure in the fire pump system. Set cut-in pressure 5 PSI above main fire
pump cut-in pressure. Set cut-out pressure at system pressure. Provide minimum
run timer to operate the pump for a minimum of 3 minutes.
Across the fine start, H-O-A selector switch.
Control panel to contain a fusible 3-pole disconnect switch, magnetic motor
contractor and thermal overload relays with external reset Enclosure to be wall
mounted with hinged door.
5.2.7
Electronic water level indicator shall provide remote reading of water level into the
pump control panel. An alarm facility shall be provided for connection to the fine
pump control panel to indicate low water level and to provide a signal to shut down
the pumps if the tank is empty.
Fire pump (Diesel and electric) shall have performance; as indicated on the
drawings
5.3 EXECUTION:
1. The fire pumps shall be provided with a supervised isolating valve, flow meter
and throttling valve on the test piping. Test piping shall discharge water to the fire
water tank through a galvanized steel diffuser pipe.
2. Each pump, whether diesel or electric driven shall be complete with suction and
discharge pressure gauges, circulation relief valve, dosed relief cone, automatic air
release valve, drain valves coupling guard and its own control 'panel.
3. Provide remote annunciation panel for each pump which shall be located in the
Managers office and shall provide the following features: diesel and electric pump
status indicating rights and trouble tight for each pump. Wiring between control
panel and remote control panel shall be by division 15 installed in conduit as
described in section 16434.
4. Batteries shall be furnished in a dry charge, condition with electrolyte liquid in a
separate container. Electrolyte shall be added and the battery given a conditioning
charge at the time that the engine is put into service. Batteries shall be located so as
to be readily accessible for servicing and at least 300 mm above floor level.
Page 29 of 43
5. The electric motor driven unit shall have the pump. electric motor and control
panel mounted on a common base. The entire unit will be factory tested prior to
shipping.
6. The automatic engine control panel and the electric motor driven unit control
panel shall be specifically designed for fire pump service. All wiring between
pump, pump devices and controller shall be factory wired and tested. Wiring
between controller and the building fire alarm system shall be by Division 16.
Power wiring for the electric fire pump will be by Division 16.
7. The control panels shall be securely mounted in an enclosure which will protect
the equipment against mechanical injury and fading drops of water. All switches
required to keep the controller in the "automatic" position shall be within the
locked cabinet. Emergency access to the switch shall be by breaking the glass
panels.
8. A wiring diagram shall be provided and permanently attached to the inside of the
each enclosure showing exact wiring for the controller, including a legend of
identifying numbers of individual components. AH wiring terminals shall be
plainly marked to correspond with the wiring diagram furnished.
9. Wiring elements of the controllers shall be designed on a continuous-duty basis.
All wiring leading from the panel to the engine and to the batteries shall have
adequate carrying capacity. Such wiring shad be protected against mechanical
injury by metal conduit
10. Each operating component of the controllers shall be marked to plainly indicate
an identifying number referenced to the wiring diagram. The markings shall be
located so as to be visible after installation.
11. Complete instructions covering the operation of the controllers shall be
provided and conspicuously mounted on the controllers.
12. Prior to shipment, the electric pumps and control panels shall be thoroughly
shop-tested as a unit by the pump manufacturer. A characteristic curve showing the
pump performance based upon the results of the shop test shall be submitted to the
Consultant prior to shipment, and shall include the performance of the pump and
engine at the set-governor's speed. Absence of these test reports, indicating that the
complete unit has been tested in the factory by the driver, will be ample grounds
for the rejection of the equipment. The contractor shall include in his price the cost
and expenses of having one representative of the Owner from Abu-Dhabi witness
the complete factory test prior to shipment
5.4 CONTROL
1. The electric fire pump shall be the lead fire pump. The other diesel fire pump
shall be backup fire pump and will only operate if the lead fire pump cannot
maintain system pressure.
2. The Jockey pump shall maintain the system pressure.
Page 30 of 43
Page 31 of 43
SCOPE:
This specification outlines the requirements for a Total Flood Clean Agent Fire
Suppression System with automatic detection and control. The work described in
this specification includes all engineering, labor, materials, equipment and services
necessary, and required, to complete and test the suppression system.
6.1.2
The design, equipment, installation, testing and maintenance of the Clean Agent
Suppression System shall be in accordance with the applicable requirements set
forth in the latest edition of the following codes and standards:
1) NFPA No. 2001 - Clean Agent Fire Extinguishing Systems
2) NFPA No. 70 - National Electrical Code
3) NFPA No. 72 - Standard For Fire Alarm System
4) Factory Mutual Approval Guide
5) U.L Listings
6) Requirements of the Authority Having Jurisdiction (AHJ)
The standards listed, as well as all other applicable codes and standards, shall be
used as "minimum" design standards. Also to be considered are good engineering
practices.
6.1.3
REQUIREMENTS:
The clean agent Suppression System installation shall be made in accordance with
the drawings, specifications and applicable standards. Should a conflict occur
between the drawings and specifications, the specifications shall prevail.
6.1.4
INCLUSIONS / EXCLUSIONS:
The Specialist contract shall include the following materials / works in their scope
but not limited to:
1. Design & Engineering of clean Agent fire suppression system;
2. Prepare workshop drawing and technical submittals;
3. Perform Flow calculation;
4. Clean Agent gas storage cylinders filled with gas and all hardware accessories;
Page 32 of 43
QUALITY ASSURANCE:
6.1.5.1 MANUFACTURER:
1) The manufacturer of the Suppression System hardware and detection
components shall have a minimum of 10 years experience in the design and
manufacture of similar types of suppression systems and who can refer to similar
installations providing satisfactory service.
2) The name of the manufacturer, part numbers and serial numbers shall appear
on all major components.
3) All devices, components and equipment shall be new, standard products of the
manufacturers latest design and suitable to perform the functions intended.
4) All equipment shall be U.L listed and/or FM approved.
5) Locks for all cabinets shall be keyed alike.
Page 33 of 43
6.1.5.2 INSTALLER:
1) The installing contractor shall be trained by the supplier to design, install, test
and maintain Suppression Systems.
2) When possible, the installing contractor shall employ a NICET certified special
hazard designer, level 2 or above, who will be responsible for this project.
3) The installing contractor shall be an experienced firm regularly engaged in the
installation of automatic Clean Agent, or similar, fire suppression systems in strict
accordance with all applicable standards.
4) The installing contractor must have a minimum of eight (8) years experience in
the design, installation and testing of Clean Agent, or similar, fire suppression
systems.
A list of systems of a similar nature and scope shall be provided on request.
5) The installing contractor shall maintain, or have access to, a Clean Agent
recharging station. The installing contractor shall provide proof of his ability to
recharge the largest Clean Agent system within 24 hours after a discharge. Include
the amount of bulk agent storage available.
6) The installing contractor shall be an authorized stocking distributor of the
Clean Agent system
equipment so that immediate replacement parts are
available from inventory.
7) The installing contractor shall show proof of emergency service available on a
twenty-four hour, seven-days-a-week basis.
6.1.5.3 SUBMITTALS:
1) The installing contractor shall submit the following information for approval to
the local Fire Prevention Agency, owners Insurance Underwriter,
Architect/Engineer, and all other Authorities Having Jurisdiction before starting
installation:
a) Field installation layout drawings having a scale of not less than 1/8 = 1-0
or 1:100m detailing the location of all agent storage tanks, pipe runs, including
pipe sizes and lengths, control panel(s), detectors, manual pull stations, abort
stations, audible and visual alarms, etc.
b) Auxiliary details and information such as maintenance panels, door holders,
special sealing requirements and equipment shutdowns.
c) Separate layouts, or drawings, shall be provided for each level, ( i.e.; room,
underfloor, and above ceiling) and for mechanical and electrical work.
d) A separate layout or drawing shall show isometric details of agent storage
containers, mounting details and proposed pipe runs and sizes.
Electrical layout drawings shall show the location of all devices and include pointto-point conduit runs and a description of the method(s) used for detector
mounting.
Page 34 of 43
Internal control panel wiring diagram shall include power supply requirements and
field wiring termination points.
Graphic Annunciator wiring schematics and dimensioned display panel illustration
shall be provided. (Optional device)
Complete hydraulic flow calculations, from a U.L. listed computer program, for all
engineered Clean Agent systems.
Calculation sheet(s) must include the
manufacturers name and U.L. listing number for verification. The individual
sections of pipe and each fitting to be used, as shown on the isometrics, must be
identified and included in the calculation. Total agent discharge time must be
shown and detailed by zone.
Provide calculations for the battery stand-by power supply taking into
consideration the power requirements of all alarms, initiating devices and auxiliary
components under full load conditions.
A complete sequence of operation detailing all alarm devices, shutdown functions,
remote signaling, damper operation, time delay and agent discharge for each zone
or system.
System component datasheets.
6.2 CLEAN AGENT SYSTEM REQUIREMENTS :
6.2.1
A) The system shall be a Total Flood Clean Agent Suppression System supplied &
installed by an Authorised by the manufacturer.
B) The system shall provide a clean agent minimum design concentration of 7.2
%, by volume, in all areas and/or protected spaces, at the minimum anticipated
temperature within the protected area. System design shall not exceed the NOAEL
value of 9.0%, adjusted for maximum space temperature anticipated, unless
provisions for room evacuation, before agent release, are provided.
C) The system shall be complete in all ways. It shall include all mechanical and
electrical installation, all detection and control equipment, agent storage
containers, clean agent agent, discharge nozzles, pipe and fittings, manual release
and abort stations, audible and visual alarm devices, auxiliary devices and
controls, shutdowns, alarm interface, caution/ advisory signs, functional checkout
and testing, training and all other operations necessary for a functional, U.L.
Listed and/or F.M. approved Clean Agent Suppression System.
D) Provide two (2) inspections during the first year of service. Inspections shall
be made at 6 month intervals commencing when the system is first placed into
normal service.
E) The general contractor shall be responsible for sealing and securing the
protected spaces against agent loss and/or leakage during the 10 minute "hold"
period.
F) The system(s) shall be actuated by a combination of ionization and/or
photoelectric detectors installed at a maximum spacing of 250 sq. ft. (23.2 sq. m)
Page 35 of 43
per detector, in both the room, underfloor and above ceiling protected spaces. If
the air flow is one air change per minute, photoelectric detectors only shall be
installed at a spacing not to exceed 125 sq. ft. (11.6 sq. m) per detector. (Ref.
NFPA No. 72 - current edition)
G) Detectors shall be wired in Sequential Detection method of operation, standard
Cross-Zoned detection, or Single Detector Release, using either a Class "A" or
Class "B" wiring arrangement. No other detection / wiring arrangements will be
acceptable.
H) Automatic operation of each protected area shall be as follows:
1) Actuation of one (1) detector, within the system, shall:
a) Illuminate the "ALARM" lamp on the control panel face.
b) Energize an alarm bell and/or an optional visual indicator.
c) Transfer sets of 5 Amp rated auxiliary contacts which can perform auxiliary
system functions such as:
1) Operate door holder/closures on access doors.
2) Transmit a signal to a fire alarm system.
3) Shutdown HVAC equipment.
d) Light an individual lamp on an optional graphic annunciator.
2) Actuation of a 2nd detector, within the system, shall:
a) Illuminate the "PRE-DISCHARGE" lamp on the control panel face.
b) Energize an predischarge horn or horn/strobe device.
c) Shut down the HVAC system and/or close dampers.
d) Start time-delay sequence (not to exceed 60 seconds). System abort sequence
is enabled at this time.
f) Light an individual lamp on an optional graphic annunciator.
3) After completion of the time-delay sequence, the Clean Agent system shall
discharge and the following shall occur:
a) Illuminate a "SYSTEM FIRED" lamp on the control panel face.
b) Shutdown of all power to high-voltage equipment
c) Energize a visual indicator(s) outside the hazard in which the discharge
occurred.
d) Energize a "System Fired" audible device. (Optional)
Page 36 of 43
GENERAL REQUIREMENTS:
The Clean Agent System materials and equipment shall be standard products of
the supplier's latest design and suitable to perform the functions intended. When
one or more pieces of equipment must perform the same function(s), they shall be
duplicates produced by one manufacturer.
1) All devices and equipment shall be U.L Listed and/or FM approved.
6.3.2
Page 37 of 43
b) Ceiling plates, can be used with the nozzles to conceal pipe entry holes through
ceiling tiles.
9) Distribution piping, and fittings, shall be installed in accordance with the
manufacturer's requirements, NFPA 2001 and approved piping standards and
guidelines. All distribution piping shall be installed by qualified individuals using
good, accepted practices and quality procedures. All piping shall be adequately
supported and anchored at all directional changes and nozzle locations.
a) All piping shall be reamed, blown clear and swabbed with suitable solvents to
remove burrs, mill varnish and cutting oils before assembly.
b) All pipe threads shall be sealed with Teflon tape pipe sealant applied to the
male thread ONLY.
6.4 ELECTRICAL REQUIREMENTS :
6.4.1
CONTROL PANEL :
The control panel shall be a SHP (Single Hazard Panel) Control Panel.
The SHP Control System, and its components, shall be UL listed and FM
approved for releasing service and be suitable for clean Agent release service.
The SHP Control System shall perform all functions necessary to operate the
system detection, actuation and auxiliary functions, as outlined.
The SHP Control System shall be capable of providing 7AH or 18AH battery
standby power supplies.
The SHP Control System shall be microprocessor based with hardware and
software integration designed to guarantee reliability.
The SHP Control System shall support Cross Zoned, Sequential, Single Detector
Release and Manual Release detection/actuation methods.
The SHP Control System shall provide the following capabilities and functions:
a) Three (3) Class B (Style Y) indicating appliance circuits rated for 2.0 amps @
24 VDC.
b) Four (4) Class B (Style A) initiating circuits
c) Optional Class A (Style D) module for initiating circuits
d) Eight (8) Status LEDs plus alpha-numeric display for troubleshooting: AC
normal; alarm; pre-discharge; release; supervisory; trouble; alarms silenced and
system abort.
e) Programmable pre-discharge and discharge timers
f) Resettable and continuous auxiliary output power
g) Five (5) optional Abort types
Page 38 of 43
DETECTORS:
The detectors shall be spaced and installed in accordance with the manufacturer's
specifications and the guidelines of NFPA No. 72 current edition.
6.4.2.1
IONIZATION DETECTOR
The ionization fire and smoke detector shall continuously measures the products
of combustion in the air, and gives a proportional output. It shall meet the
requirements of EN54 part 7.
The detector shall be a dual-chamber type fully compensated for temperature,
humidity and barometric changes. The radioactive source shall be less then 1
micro-curie of Americium 241, and shall comply with all Atomic Energy Agency
requirements.
A light emitting diode (LED) on the base must illuminate when a detector is in
alarm.
6.4.2.2
The optical smoke detector shall continuously measure the smoke level in the air,
and gives a proportional output. It shall comply with the requirements of EN54
part 7.
The detector shall be an optical light scattering type sensitive to visible smoke and
be stable under all environmental conditions. The internal test and calibration
circuits shall use the same optical elements as the smoke sensing circuits, to
ensure reliability.
A light emitting diode (LED) on the base must illuminate when a detector is in
alarm
Page 39 of 43
6.4.3
The electric manual release switch shall be a dual action device which provides a
means of manually discharging the Suppression System when used in conjunction
with the Fike SHP Control System.
The Manual Release switch or Manual Pull station shall be a dual action device(s)
requiring two distinct operations to initiate a system actuation.
Manual actuation shall bypass the time delay and abort functions, shall cause the
system to discharge, and shall cause all release and shutdown devices to operate in
the same manner as if the system had operated automatically.
A Manual Release switch shall be located at each exit from the protected hazard
and shall have an advisory sign, provided at each location.
6.4.4
ABORT STATION :
The optional Abort Station shall be the "Dead Man" type and shall be located next
to each manual switch.
The Abort Station shall be supervised and shall indicate a trouble condition at the
SHP Control Panel, if depressed, and no alarm condition exists.
"Locking" or "Keyed" abort stations shall not be permitted.
The Abort Station shall be located adjacent to each manual station.
6.4.5
Alarm audible and visual signal devices shall operate from the SHP Control Panel.
The Alarm Bell, Alarm Horn and Horn/Strobe devices shall operate on 24 volts Dc
power to allow supervision of the circuit wires.
The alarm bell and horn shall deliver a minimum sound level of 92 decibels at a
distance of 3m.
Horn and strobe light are to operate simultaneous from one power supply with
flash rate of 1-3 flashes per second minimum over the listed input voltage range.
A Strobe device shall be placed outside, and above, each exit door from the
protected space. Provide an advisory sign at each light location.
6.4.6
MANUAL ACTUATOR:
Manually operated actuator shall be provided for independent means of operation
of clean agent system. The unit shall activate the system without the need for
external power or stored energy, therby providing a fail safe method of activation.
6.4.7
remove the container and weigh it on a calibrated scale. The device shall enable
the inspector to determine the weight of agent with the container safely secured in
its installed position.
6.4.8
Provide signs, as required, to comply with NFPA 2001 and the recommendations
of the equipment supplier:
Entrance sign: (1) required at each entrance to a protected space.
Manual Discharge sign: (1) required at each manual discharge station.
Flashing Light sign: (1) required at each flashing light over each exit from a
protected space.
6.5 SYSTEM AND CONTROL WIRING:
All system wiring shall be furnished and installed by the contractor.
All wiring shall be installed in electrical metallic tubing (EMT), or conduit, and
must be installed and kept separate from all other building wiring.
All system components shall be securely supported independent of the wiring.
Runs of conduit and wiring shall be straight, neatly arranged, properly supported,
installed parallel and perpendicular to walls and partitions.
The sizes of the conductors shall be those specified by the manufacturer. Color
coded wire shall be used. All wires shall be tagged at all junction points and shall
be free from shorts, earth connections (unless so noted on the system drawings),
and crosses between conductors. Final terminations between the SHP control
panel and the system field wiring shall be made under the direct supervision of a
factory trained representative.
All wiring shall be installed by qualified individuals, in a neat and workmanlike
manner, to conform to the National Electrical Code, Article 725, and Article 760,
except as otherwise permitted for limited energy circuits, as described in NFPA 72
- current edition. Wiring installation shall meet all local, state, province and/or
country codes.
The complete system electrical installation, and all auxiliary components, shall be
connected to earth ground in accordance with the National Electrical Code.
6.6 SYSTEM INSPECTION AND CHECKOUT:
After the system installation has been completed, the entire system shall be
checked out, inspected and functionally tested by qualified, trained personnel, in
accordance with the manufacturer's recommended procedures and NFPA
standards.
All containers and distribution piping shall be checked for proper mounting and
installation.
Page 41 of 43
All electrical wiring shall be tested for proper connection, continuity and
resistance to earth.
The complete system shall be functionally tested, in the presence of the owner or
his representative, and all functions, including system and equipment interlocks,
must be operational at least five (5) days prior to the final acceptance tests.
a) Each detector shall be tested in accordance with the manufacturer's
recommended procedures, and test values recorded.
b) All system and equipment interlocks, such as door release devices, audible and
visual devices, equipment shutdowns, local and remote alarms, etc. shall function
as required and designed.
c) Each SHP control panel circuit shall be tested for trouble by inducing a trouble
condition into the system.
6.7 TRAINING REQUIREMENTS:
Prior to final acceptance, the installing contractor shall provide operational
training to each shift of the owners personnel. Each training session shall include
system SHP Control Panel operation, manual and abort functions, trouble
procedures, supervisory procedures, auxiliary functions and emergency
procedures.
6.8 OPERATION AND MAINTENANCE:
Prior to final acceptance, the installing contractor shall provide complete operation
and maintenance instruction manuals, four (4) copies for each system, to the
owner. All aspects of system operation and maintenance shall be detailed,
including piping isometrics, wiring diagrams of all circuits, a written description
of the system design, sequence of operation and drawing(s) illustrating control
logic and equipment used in the system. Checklists and procedures for emergency
situations, troubleshooting techniques, maintenance operations and procedures
shall be included in the manual.
6.9 AS-BUILT DRAWINGS:
Upon completion of each system, the installing contractor shall provide four (4)
copies of system "As-Built" drawings to the owner. The drawings shall show
actual installation details including all equipment locations (i.e.: control panel(s),
agent container(s), detectors, alarms, manuals and aborts, etc.) as well as piping
and conduit routing details. Show all room or facilities modifications, including
door and/or damper installations completed. One (1) copy of reproducible
engineering drawings shall be provided reflecting all actual installation details.
6.10
ACCEPTANCE TESTS:
1) At the time "As-Built" drawings and maintenance/operations manuals are
submitted, the installing contractor shall submit a "Test Plan" describing
procedures to be used to test the control system(s). The Test Plan shall include a
step-by-step description of all tests to be performed and shall indicate the type and
location of test apparatus to be employed. The tests shall demonstrate that the
operational and installation requirements of this specification have been met. All
Page 42 of 43
tests shall be conducted in the presence of the owner and shall not be conducted
until the Test Plan has been approved.
2) The tests shall demonstrate that the entire control system functions as designed
and intended. All circuits shall be tested: automatic actuation, solenoid and
manual actuation, HVAC and power shutdowns, audible and visual alarm devices
and manual override of abort functions. Supervision of all panel circuits,
including AC power and battery power supplies, shall be tested and qualified.
3) A room pressurization test shall be conducted, in each protected space, to
determine the presence of openings which would affect the agent system
concentration levels. The test(s) shall be conducted using the Retro-Tec Corp.
Door Fan system, or equivalent, with integrated computer program. All testing
shall be in accordance with NFPA 2001.
4) If room pressurization testing indicates that openings exist which would result
in leakage and/or loss of the extinguishing agent, the installing contractor shall be
responsible for coordinating the proper sealing of the protected space(s) by the
general contractor or his sub-contractor or agent. The general contractor shall be
responsible for adequately sealing all protected space(s) against agent loss or
leakage. The installing contractor shall inspect all work to ascertain that the
protected space(s) have been adequately and properly sealed.
THE
SUPPRESSION SYSTEM INSTALLING CONTRACTOR SHALL BE
RESPONSIBLE FOR THE SUCCESS OF THE ROOM PRESSURIZATION
TESTS. If the first room pressurization test is not successful, in accordance with
these specifications, the installing contractor shall direct the general contractor to
determine, and correct, the cause of the test failure. The installing contractor shall
conduct additional room pressurization tests, at no additional cost to the owner,
until a successful test is obtained. Copies of successful test results shall be
submitted to the owner for record.
5) Upon acceptance by the owner, the completed system(s) shall be placed into
service.
6.11
SYSTEM INSPECTIONS:
The installing contractor shall provide two (2) inspections of each system,
installed under this contract, during the one-year warranty period. The first
inspection shall be at the six month interval, and the second inspection at the 12
month interval, after system acceptance. Inspections shall be conducted in
accordance with the manufacturer's guidelines and the recommendations of NFPA
2001.
Documents certifying satisfactory system(s) operation shall be submitted to the
owner upon completion of each inspection.
6.12
WARRANTY:
All system components furnished, and installed under this contract, shall be guaranteed against
defects in design, materials and workmanship for the full warranty period which is standard
with the manufacturer, but in no case less than one (1) year from the date of system acceptance.
Page 43 of 43
PART 1 GENERAL
1.01
SCOPE
A.
The work described in this section of the specification is related to the hot, cold,
Brackish and soft water distribution systems.
1.02
RELATED WORK
A.
B.
C.
D.
E.
F.
1.03
REFERENCES
A.
B.
C.
D.
1.04
SYSTEMS DESCRIPTION
A.
The hot and cold water systems comprise of a system of pipework, valves fittings and
appurtenances providing hot, cold and water to the various plumbing fixtures situated
throughout the buildings. The work includes recirculation hot water and specialties.
PART 2 - PRODUCTS
2.01
WATER SERVICES.
A.
See section 15060 Pipe and Pipe Fittings for Water Service Piping Materials and
Installation.
Page 1 of 10
2.02
MATERIALS
A.
Copper Piping
Refer to Section 15060 Paragraph 2.02 A.
B.
C.
D.
E.
Accessories
1. Flexible pipe connectors shall have a stainless steel bellows with a woven flexible
bronze wire reinforcing protective jacket. Connectors shall be minimum of 300 mm
in length with thread male or flanged ends as required for proper installations.
Sweat end connections re not acceptable. Connectors shall be rated for 2 MPa
water working pressure, 120C operating temperature and suitable for up to
maximum 20 mm misalignment.
2. Shock absorbers shall be elastomer bellows type, with stainless steel shell, glycerin
hydraulic displacement fluid and pressurized argon pneumatic displacement
cushion. Shock absorbers shall be individually sized as required for equipment
served.
F.
3. Float valves for use on incoming supplies to cold water storage tanks shall be cast
brass or gunmetal up to 75 mm dia. And cast iron with bronze seats for 100 mm
dia. and above.
Page 2 of 10
G.
b.
Stove enameled finished and 2" thick insulated metal outer jacket.
c.
d.
e.
f.
g.
h.
j.
Gate valve and check valve at water inlet and gate valve at outlet connections.
k.
Pressure and temperature relief valve for protection against excess pressure and
high temperature as well as loss of water from the shell.
Alternatively, a combination shut-off, drain and pressure temperature relief
valve may be used.
l.
m.
Steel supports.
.
All pipe work and accessories required for its installation and satisfactory
operation.
Page 3 of 10
PART 3 - EXECUTION
3.01
INSTALLATIONS
A.
See Section 15050: Basic Materials and Methods, for general piping installation
instructions.
B.
C.
Vacuum Breakers
1. Vacuum breakers shall be furnished and installed on all faucets and valves which
have provisions for hose connections and water supplies to equipment or devices
that have inlets below the overflow rim.
D.
Underground Piping
1. No underground or under slab water piping within building shall be permitted
unless specifically shown otherwise on the drawings.
E.
Joints
1. Joints shall be made using 95-5 Tin- Antimony solder ASTM B-32. Joints for
underground ( if any ) shall be made using a brazing compound containing silver
alloys having a melting point of 520C or higher. Wrought copper and bronze
fittings shall be to ANSI B16.22.
F.
Page 4 of 10
H.
Page 5 of 10
The trench shall not be opened up too far in advance of pipe laying and shall be
backfilled as soon as possible.
The width of the trench at the crown of the pipe shall be as participle but not more than
the outside diameter of the pipe plus 300 mm to allow for proper compaction of side
fill.
Care shall be taken to ensure that the bed of the trench will support the pipeline so as to
prevent localized loss of gradient or bridging and projections shall be removed to
prevent point loading of the pipe, all pockets or voids shall be graded with granular
material.
Free draining coarse sand and/or granular material maximum particle size 22 mm to be
used as side fill material free of large objects, and capable of being compacted
sufficiently to provide adequate support for the pipe.
The pipework side fill shall be firmly compacted between the side on the pipe and side
of trench.
Before backfilling is carried out any temporary packing shall be removed.
The thickness of granular bedding under the barrel of the pipe shall not be less than one
third of the diameter, and a minimum of 100 mm thick.
Where soft spots occur in the bottom of the trench the thickness shall be increased as
necessary to give a suitable bed.
The granular bedding shall be thoroughly compacted in layers not more than 150 mm
thick to give a uniform bed, true to gradient, on which the pipe is to be laid and placed
directly on the bedding.
Bricks or other hard materials shall not be placed under the pipes for temporary
support.
Further bedding material shall be placed around the pipe and thoroughly compacted in
65 mm layers, by careful tamping up to the crown of the pipe eliminating all cavities
under the two lower quadrants of the pipe.
To enable easy identification of the main, a warning tape shall be laid along the length
of the pipe.
The backfilling shall proceed in layers not exceeding 300 mm thickness each layer
being thoroughly compacted.
Heavy mechanical hammers shall not be used until the fill has reached a depth of 300
mm above the top of the pipe.
The maximum particle size shall not exceed 22 mm but the presence of a particle
between 22 mm and 40 mm is acceptable providing the total quantity of such particles
is a very small fraction of the whole.
If particles over 40 mm are present the material shall not be acceptable and be rejected.
Page 6 of 10
The route of the pipeline shall be permanently marked with an electronic traceable
indicator tape laid 300 mm above the crown of the pipe.
3.02
A-
General
All parts of hot and cold water circuits in contact with the water shall have clean
disinfected surfaces before being installed.
Materials specified and used shall be proof against the following hazards :
Dezincification or galvanic action
Chlorine treatments
Imparting taste or odor to the water
Contamination of water by lead, copper or other elements in excess of standards laid
down by the EEC.
Bacterial growth due to nutrients in pipework materials, jointing materials, pastes and
compounds, fluxes, solders, thread sealant tapes, gaskets, grommets, tap washers, O
rings, gland packing, valve seats, filters, hoses, greases, lubricants, protective coatings
or linings.
All materials and fittings shall be an approved type as tested and listed by the U.K.
Water Research Centre as suitable for potable water and not capable of promoting
bacterial growth.
Pipework circuits for cold water shall be run below or away from hot pipes to
minimize heat gain and keep water temperature below 20C to prevent the colonization
of Legionnella bacteria.
Backflow prevention devices or air gaps shall be provided and specified herein based
on BS 6700 and to BS 6281 Parts 1,2 and 3 and BS 6282 Parts 1,2,3 and 4 as
appropriate.
B-
Page 7 of 10
C-
D-
Working away from the cistern, and closing it when chlorinated water at 40-50 ppm is
discharged, the concentration being determined by calorimetric methods. The cistern
shall be refilled and chlorinated as above during these operations, to maintain a residual
chlorine level of 50ppm in the cistern at all times. The contact time shall commence
when the entire system is filled with chlorinated water, together with the cistern to
overflow level.
It is essential that the internal coatings of cisterns are thoroughly cured before
disinfection take place and care must be taken not to exceed 5 ppm chlorine
concentration.
The above procedures shall apply to cold water services and to the secondary circuits
of hot water systems before heat is applies and with the water cold. Care shall be taken
not to use excessive amounts of chlorine which may affect pipework or other materials.
Records shall be kept of all procedures, checks, tests and witnessing.
E-
F-
Page 9 of 10
The Contractor shall allow for the tests to be carried out by the Public Health Authority
Laboratory Service or the local Water Undertaking as agreed with the Engineer.
Two sets of tests shall be included, the first after setting-to-work and disinfecting and
the second in conjunction with the handover date and the date for occupation of the
premises.
G-
H-
Analysis Reports
All test reports shall be discussed with the Engineer and the Medical Officer for
Infection Control and where results are not satisfactory, suitable remedial action shall
be agreed upon and undertaken by the Controller.
If the results are found to be unsatisfactory due to poor workmanship and/or use of
unacceptable components, all remedial work shall be carried out at the Contractors
expense.
END OF SECTION
Page 10 of 10
PART 1 - GENERAL
1.01
SCOPE
A.
The work described in this section of the specification is related to the soil, waste and
ventilating pipework installation and the storm drainage system.
1.02
RELATED WORK
A.
B.
C.
D.
1.03
REFERENCES
A.
B.
C.
1.04
A.
Rain water pipes inside shaft and at floor level shall be UPVC type.
C.
D.
Soil and waste pipes inside main shaft and basement ceiling level to be UPVC.
F.
G.
Condensate drain pipe and water tank overflow to be Pressure UPVC 10 bars.
H.
.
1.05
SYSTEM DESCRIPTION
A.
Building shall have a comprehensive system of soil, waste, anti-siphon ventilation and
rainwater pipework so designed as to convey all soil, waste and rainwater to the main,
city sewage and rainwater storm holding tank.
Page 1 of 17
1.06
QUALITY ASSURANCE
A.
Comply with the provisions of ASME B31.9 Building Services Piping for materials,
products and installations.
B.
Provide listing / approval stamp, label or other marking on piping made to specified
standards.
PART 2 - PRODUCTS
2.01
1.
2.02
A.
UPVC sewage and vent pipes shall be extruded unplasticized polyvinyl chloride
conforming to the following European Standards for non pressure drainage pipes:
-
Pipes shall be European make suitable for rubber ring pressure joint. Sealing
rings to be rubber to EN681.
Fire stop jackets shall be installed on all PVC pipes penetrating floor slabs or
fire rated walls.
Pipe fittings shall be UPVC of the same weight and quality as the pipe.
Lubricant shall be as recommended by pipe manufacturer.
Page 2 of 17
Contractor to provide all accessories and supports of UPVC system to suite high rise
building applications and to provide all accessories to protect installation from the
seismic action defined for this project.
B.
Floor Drains
1.
2.
a)
b)
Adjustable level, heavy duty, large grate area, chrome plated brass strainer,
200mm x 200mm fixed onto the drain body with cover.
c)
d)
Floor drains shall have UPVC traps of minimum water seal of 7 cm.
Floor drains shall have a built in rodding eye.
3.
Trench drain
Trench drain shall be constructed of concrete and shall conform to the following
requirements:
a)
c)
c)
d)
e)
C.
Clean-Outs
Page 3 of 17
Supply and install all clean-outs wherever shown on the drawings and as specified
herein.
Each clean-out shall be of the same material and dimension as the pipe shall conform to
the following requirements:
2.03
a.
For pipes exposed or in false ceilings, clean-outs shall consist of a threaded cap
screwed onto pipe end.
b.
Floor clean-outs shall consist off capped wide elbows ending under a chrome
plated bronze tile 20 x 20cms with screwed cover.
2.04
2.05
CLEANOUTS
The cleanouts shall be of the same material and dimensions as the pipes to be cleaned
and shall be placed under the floor slabs or extended through to terminate flush with
the finished floor.
Cleanouts on concealed piping shall be extended through and terminate flush with the
finished floor.
Cleanouts shall be installed at each change of direction greater than 45.
They shall be also provided at or near the foot of each vertical soil and waste stack.
Cleanouts shall be installed such that the cleanout opens in a direction opposite to the
flow of the drainage line or at right angles thereto.
Floor cleanouts with covers shall be formed with a "Y", "F" or 45 elbow fitting of the
same material and size as the pipe accommodated and provided with an adapter and a
threaded brass plug.
Floor cleanout type FCO shall have cover plate and frame 20 x 20cm chrome plated
brass. The cover shall be threaded to the frame to ensure an air tight closure.
Page 4 of 17
Floor cleanout type FCO-1 shall be of UPVC with nickel bronze washed out and as
approved by the Engineer.
Ground cleanout GCO-1 shall be of UPVC with PVC lockable air tight cover 200 x
200 mm.
Ground cleanout GCO-2 shall be of cast iron with coated cast iron lockable cover.
2.6
PART 3 - EXECUTION
3.01
GENERAL
A.
Install cast iron soil pipes and fittings according to CISPI latest edition of cast iron soil
pipe and fittings hand book volume I chapter IV, installation of cast iron pipe and
fittings.
B.
Pipework shall be installed to the routes and diameters indicated on the drawings and
where exposed shall run in parallel lines when grouped together to obtain a neat and
satisfactory appearance.
C.
Open ends of pipework left during the progress of work shall be blanked off with a
temporary plug or cap to prevent the entry of any foreign matter.
D.
Make changes in direction for drainage and vent piping using appropriate Y - branches
, Y - branched with 1/8 bends, and long sweep 1/4 ,1/5, 1/6, 1/8, and 1/16 bends. Use
long turn double - Y branch and 1/8 - bend fittings where 2 fixtures are installed back
to back or side by side and have a common drain. Where different sizes of drainage
pipes and fittings are connected use standards increases and reducers.
E.
Branches on waste and soil pipe work must be swept in with the direction of flow.
F.
Pipes shall be spaced in ducts in a manner which will permit subsequent access to any
pipe for maintenance or removal without disturbance to the remaining pipes.
G.
Long radius bends shall be provided at the connection of all soil and rain water stacks
to the underground drain, with an access pipe above floor level.
3.02
3.03
All pipes shall be so installed as to ensure easy and even flow of the water to
and from all equipment and fixtures.
Pipelines shall be installed in a manner to allow for easy air escape and
system draining. It shall be endeavored to obtain this naturally by gravity.
However, where this cannot be met, provision should be made to ensure quick
and positive drainage and noiseless air discharge.
Vent pipes shall not be trapped and shall be graded to drip back to waste or soil
line.
All vents for waste and soil stacks shall extend above the highest point of the
roof and shall be equipped with a vent head and cap as specified.
Sleeves shall be supplied and installed wherever pipes cross slabs, walls,
partitions, etc.
Before installation, all pipes shall be cleaned of all foreign matter and shall be
reamed smooth after cutting. All trenches shall be cleaned up.
Steel pipe ends shall be cleaned and smoothed on edge to avoid all roughness
and unevenness before welding or threading.
Threading shall be done for the total length of joint or accessory with a reliable
threading machine.
Page 6 of 17
PVC pipes when cut shall be debarred and chamfered according to the
instructions of the manufacturer to ensure a proper and easy assembly.
All changes in pipe size shall be made with fittings. Eccentric reducing fittings
shall be used to prevent pocketing.
3.04
JOINTING
Cast Iron
The spigot of the pipe shall be centralized in the receiving socket by tightly caulking
sufficient turns of white jute gasket into the annular space formed . The gasket shall be
caulked to leave a depth of annular space unfilled relative to 2/3rd total depth of socket.
At no point during the operation shall caulking material be allowed to protrude within
the pipe. Where the axis of the two pipes are included one to the other the joint shall in
no part be less than 4.7 mm in thickness.
B.
An alternative procedure for pipe jointing shall be thru the use of compression joints
with neoprene rubber gaskets conforming to specified standards.
UPVC
-
Solvent weld joints shall be made with the proper solvent cement furnished by
the manufacturer for that purpose. Both, the inside of the socket and the outside
of the spigot end of the pipe shall be roughened using sand paper. All grease
and dirt shall be removed from the surface with a special cleaning fluid
supplied by the manufacturer. Immediately after cleaning, solvent cement shall
be applied and pipe pushed into the socket up to the shoulder without turning.
Rubber ring joints shall be made with the proper sealing ring furnished by the
manufacturer for that purpose. After the spigot end has been lubricated, it shall
be pushed fully into the socket and then pulled out by about 3mm per meter of
pipe length (but in no case less than 1cm) to allow for longitudinal thermal
expansion.
Page 7 of 17
3.06
FIXING
A.
The contractor shall be responsible for determining the nature of the materials to be
fixed to and for marking out positions of fixing for the cutting of cavities where
required. Where cast iron, galvanized steel and PVC pipes are fixed in a vertical plane
they shall be plumb or in alignment with the structure, and provided with sufficient
fixing to ensure a rigid installation on completion. Spacing of fixtures shall be in
accordance with the Uniform Plumbing Code. At changes of direction in the vertical
plane, fixings shall be located on the sockets of the bends. Where pipes are located
against walls they shall be provided with sufficient clearance from same to permit
maintenance and painting. Pipes laid horizontally or to gradients shall be fixed as
shown as on the spacing chart and around the socket of pipe. All pipework shall be
symmetrical and correctly aligned as required. The pipes shall be installed to true
gradients free from high spots or depressions. Failure to comply with this requirements
shall render the contractor liable at his own expense to any alteration, removal or
replacement that is required.
B.
Spacing
1. The contractor shall provide supports at the spacing outlined in the following table.
Material Pipe size
mm
GS
GS
GS
GS
GS
GS
GS
CI
UPVC
UPVC
2.00
2.50
2.50
2.50
2.50
2.50
2.50
1.5
1.2
1.8
2.500
2.50
2.50
2.50
2.50
2.50
2.50
1.5
2.4
3.0
32
40
50
65
80
100
150
All
65/50/40
75 & above
The bracket band around the socket of the pipe shall be secured together by means
of 8 mm hexagonal headed brass bolts, nuts and washers. The bracket tails shall be
set into the structure of a depth to give clearance behind the pipes barrel when
fixed 40 mm from the face of the finished wall. Where pipes are to be fixed
against walls where building in is not permitted they shall be secured thereto by
brackets of mild steel. The tails of the brackets shall be turned out at right angles
and drilled to receive bolt or screw fixings plugged into wall.
2. Where pipes 50 mm and under are to be fixed to walls and partitions fixing shall be
by means of two piece brass clip split pattern bracket of the appropriate size. The
walls shall be drilled and plugged and the clip secured with dome headed black
japanned screws of the required size.
3. Where pipes 50 mm are to be fixed to walls and partitions fixing shall comprise
mild steel trice drilled and counter sunk back plate for screw fixing to structure
incorporating female boss short extension rod and two piece brass ring clip of the
appropriate diameter with securing brass screws and boss for extension rod. The
walls shall be drilled and plugged as required and the ring dip backplate secured
thereto by means of black japanned screws. On completion the pipe shall be fixed
so that a clearance of 25 mm is provided to future finished surfaces.
D.
Duct Fixing
1. Where pipes are to be fixed in ducts in conjunction with other pipes, the contractor
shall provide angle iron bearers of approved size to bridge the duct cavity. The
pipes shall be fixed to the angle bearers by means of brackets as before described
but having welded boss on the back face to receive screwed extension rod tail. The
angle bearer shall be drilled to the correct size to pass the extension rod which shall
then be double bolted thereto. The burring out of holes in the angle bearers will not
be permitted.
2. Where pipes are to be fixed in ducts to angle iron bearers the pipe shall be fixed by
means of two piece ring pattern brass clip with threaded boss. The angle iron
support shall be drilled to the correct size to receive the extension rod which shall
be a maximum of 150mm long of the appropriate diameter for the pipe brackets,
threaded both ends and secured to the angle support with nut and luck nut. The pipe
fixing ring shall be threaded onto the extension rod and on completion the
extension rod bracket shall be square to the pipe.
E.
secured with dome headed black japanned screws of suitable size. The extension
rod shall be of sufficient diameter for the duty and of the required length for the
application, with threaded end s to receive backplate ring clip. The ring clip shall
be two piece patterns.
4. Where more than one pipe is required to be supported from one extension rod,
Approval of the Engineer to the method proposed is to be obtained.
5
Where pipes are to be suspended below slabs where screeds are to be formed they
shall be supported by means of hangers comprising 100 x 100 x 5 mm mild steel
plate set at structural slab level with extension rod double bolted thereto or welded
to the required length for suspension.
6. The extension rod shall have threaded end to receive two piece pattern ring clip.
3.07
CUTS IN PIPES
A.
Cut length to tubes shall be made by means of wheel type cutters or sharp hacksaws to
give a clean true square face to the pipe. Irregularities to cut faces are to be filed
smooth and the internal burr removed by means of a burring reamer. Reductions to the
true bore of the pipe are to be made good by the insertion of a metal turn - pin.
B.
Cut lengths to cast iron pipes shall be made by means of wheel type cutting tools to
give a clean true square face to the axis of the pipe. Exposed metal shall be coated to
the axis of the pipe. Exposed metal shall be coated with tar based solution applied
before installation of the pipe.
3.08
SOUND INSULATION
A.
3.09
PAINTING
A.
The contractor shall paint all pipe supports of mild steel to prevent corrosion with one
coat of red oxide primer.
3.10
CO - ORDINATION
A.
In areas such as false ceilings, builders work ducts, floor ducts, trenches and where
different services are run in close proximity, the contractor shall ensure that his
services do not prevent the installation of other services.
B.
In this respect the contractor will be deemed to have consulted other trades and all
relevant drawings issued by the consultant and sub - contractors. The contractor shall
not install any services in these areas until routing has been agreed with other trades.
Page 10 of 17
3.11
PROVISION OF ACCESS.
A.
Access points as before described are to be provided at the base of the soil pipes
immediately prior to connection with the drainage system and elsewhere as required to
be in such position that all times the location is accessible to ensure necessary
clearance of the system. Where working is in confined ducts the contractor shall be
responsible for determining this position in relation to any other service .
3.12
PROTECTION OF WORKS
A.
Both during and on completion of the works the contractor is to be held responsible for
the full protection of his works and freedom from blockages and obstructions.
B.
Prior to commissioning tests, grease felt washers to access doors shall be regreased and
the whole installation presented as new for testing.
3.13
PIPE SLEEVES
-
Provide all pipe openings through walls, partitions and slabs with sleeves having an
internal diameter at least 2" larger than the outside diameter of the pipe for
uninsulated lines or of the insulation for insulated pipes.
Install sleeves through interior walls and partitions flush with finished surfaces;
sleeves through outside walls to project 15 mm. on each side of the finished wall;
and floor sleeves to project 50mm. above finished floors.
Set sleeves in place before pouring concrete or securely fasten and grout in with
cement.
Sleeve construction:
Fill the space between outside of pipe or insulation and the inside of the sleeve or
framed opening with fibrous asbestos in interior walls and floors and pack with
oakum, seal with lead and watertight mastic or asphalt in exterior walls.
Sleeves in fire rated wall shall be of galvanized steel pipe 2 sizes bigger with fire
resistant seal as wall rating.
3.14
General
The accessories shall be of the same standard as the pipes on which they are fitted, they
shall be flanged, threaded or welded depending on the type and the diameter of the pipe
and the location in which the pipes are installed.
For PVC pipes, all fittings shall be made of PVC from the same series and by the same
manufacturer of the pipes.
Page 11 of 17
B.
C.
D.
Provide flanges or unions at all final connections to equipment and control valves
to facilitate dismantling. Arrange connections so that the equipment being served
may be removed without disturbing the piping.
Install all supply piping, pumps and other equipment including gate valves and
strainers therein, at line size with the reduction in size being made only at the outlet
piping from the control valve at the full size of the tapping in the equipment served.
Support, anchor and guide all piping to preclude failure or deformation. Construct
and install hangers, supports, anchors, guides and accessories to the approval of the
Engineer. Do not use wire, tape or metal bands. Supports shall be designed to
support weight of pipe, weight of fluid and weight of pipe insulation.
Fasten piping securely to the structure without overstressing any portion of the
supports or the structure itself. Secure pipe supports, anchors and guides to
concrete by means of inserts or if greater load carrying capacity is required by
means of steel fishplates embedded in the concrete.
Uninsulated copper or brass pipe and/or tubing shall be isolated from ferrous
hangers or supports
Support piping and tubing at intervals indicated in the schedule hereinafter and at
all changes in direction. Maximum deflection shall not exceed 3 mm.
Furnish pipe hangers and supports complete with rods, bolts, lock nuts, swivels,
couplings, brackets and all other components and accessories, to allow installation
to freely expand and contract.
Page 12 of 17
Hangers shall be formed steel clevis type, unless otherwise specified, with
adjustable attachment to hanger rod. For copper or brass pipe, use plastic sheathed
hangers. Pipe hangers shall fit over vapor sealed insulated piping.
Where pipe exceeds maximum loading recommended for clevis type hanger,
provide steel pipe clamps.
Provide trapeze hangers where several pipes can be installed parallel and at the
same level. Trapeze shall be of steel channel sized to support load and drilled for
rod hanger at each end. Provision should be made to keep the lines in their relative
position to each other by the use of either clamps or clips.
Use roller supports, where provision for expansion is required. Rollers shall have
cast iron adjustable bases.
For hanger rods on piping 10 mm thru 50 mm inclusive use 10 mm rods, and for
piping 65 mm thru 125 mm use 16 mm rods, and for piping 150 mm thru 300 mm
use 22 mm rods.
Provide additional steel members required for hanging piping systems in areas with
special conditions, or where vertical or horizontal structural steel supports are
required other than those provided in the structure.
Provide lateral bracing for supporting rods over 450mm. long braced at every
fourth hanger with diagonal bracing attached to slab or beam.
Floor supports - provide for supporting horizontal piping from floors with cast-iron
rests, with pipe nipples to suit. Fasten to floor. Where provision for expansion is
required, provide pipe roll stands, without vertical adjustment. Provide concrete or
steel pipe piers, fasten stands to piers.
Wall supports - provide for supporting horizontal piping from wall with steel JHook for pipe located close to wall and not larger than 80 mm pipe. For greater
loads, up to 680 Kg maximum loading provide welded steel bracket.
Vertical piping supports - support cast-iron soil pipe at every floor and at base of
stack, other pipes at every floor unless shown otherwise. Use steel extension pipe
clamps. Refer to manufacturer's rated maximum loading for each size pipe. Bolt
clamps securely to pipe, rest clamp-end extension on building structure. Place pipe
clamps at ceiling below, support clamp and extension from inserts where pipe
sleeves extend above floor.
Provide hanger shields to protect vapor sealed pipe insulation within mechanical
equipment rooms at each support point by a 360o insert of high density, 100 psi,
waterproofed calcium silicate encased in a 120o sheet metal shield. Insert
thickness shall be same as insulation. Shield length shall equal nominal pipe
diameter, minimum but shall not be shorter than 100mm. and need not be longer
than 300mm. if bearing load causes no discernible deformation. Insert shall extend
25mm. Beyond sheet metal shield. 100mm. shields shall be 26 gauge minimum.
Page 13 of 17
Shields 130 to 230mm. long shall be 20 gauge minimum. Shields longer than
230mm. shall be 16 gauge.
Provide penetration shields to encase insulated pipes penetrating fire walls or floors
in a 360o, 24 gauge minimum sheet metal hanger shield with insert of high density,
100 psi. waterproofed calcium silicate the same thickness as insulation and further
enclosed within the sleeve, sized for maximum 25mm. spacing between sleeve and
insulation shield, pack annular space between sleeve and shield on both ends with
double neoprene coated asbestos rope. Install an escutcheon plate to completely
cover the wall penetration opening and fit snugly over the pipe insulation shield.
Insert shall extend at least 25mm. beyond penetrated surface and escutcheon.
Provide oversize hangers with blocking the same thickness as the insulation to
pitch vapor sealed insulated pipes accurately at time of insulation.
Except for fire protection systems, maximum horizontal spacing for pipe hangers
are as follows:
Vertical spacing - PVC pipe twice as those of horizontal spacing. - Other pipes - at
every floor level.
E.
Hangers on PVC pipes shall be of design which does not clamp the pipe tightly but
permits axial movement.
Support but do not rigidly restrain PVC pipes at end of branches and at change of
direction or elevation. Vertical piping shall be maintained in the straight alignment.
Support traps arms in excess of 900mm in length as close as possible to the trap.
Plug all opening ends of piping, valves and equipment except when actual work is
being performed to minimize accumulation of dirt and debris.
Remove dirt and debris collected at screens, strainers and other points from the
system.
to receive a
Page 14 of 17
The Contractor shall disinfect water piping before it is placed in service. The
Contractor shall furnish all equipment and materials necessary to do the work of
disinfecting and shall perform the work in accordance with the procedure outlined
in AWWA Standard for Disinfecting Water Mains Designation C 601-68. The
dosage shall be such as to produce a chlorine residual for not less than 10 ppm after
a contact period of not less than 24 hours. After treatment, the piping shall be
flushed with clean water until the residual chlorine content does not exceed 0.2
ppm. During the disinfecting period, care shall be exercised to prevent
contamination of water in steel main.
3.15.
MANHOLE
A.
Manhole Construction
Manholes shall be constructed of class "B" concrete as shown on the drawings.
The base (where required) shall be of precast class "B" reinforced concrete.
The shaft shall be constructed of poured reinforced concrete to suit the required depth.
The top shall be of class "B" reinforced concrete. An opening suitable for the cover
shall be left in the top around which the radial concrete bricks or concrete ring are built
for proper adjustment of levels. Bricks shall be fully bedded in mortar and the inside
surface of joints finished flush and clean.
The benching shall be formed in the bottom of manholes in class "B" concrete. "U"
channels shall be formed with bottom flush with inside surfaces of pipes and sides
extending the full height of the largest pipe and then sloped back at a minimum fall of
10%. The benching and channels shall be finished with 2 cm thick rendering composed
of 1/2 cement/sand mortar, and surface hardened with two coats of sodium silicate
solution brushed on. The finished diameter of channels shall be the same as the
diameter of pipes entering or leaving the manhole.
The paint for the manhole and trenches interior shall be coal tar epoxy resin.
B.
Page 15 of 17
plugging, burning-in or filling will be allowed. All castings shall be carefully coated
inside and out with coal tar pitch varnish of approved quality.
3.16
3.17
A.
On completion of the soil and waste pipe works or section of the work as may be
required the contractor shall arrange the testing of the works and witnessing of the
tests.
B.
The tests shall comprise an air test as set out in the Uniform Plumbing Code, and
described below.
C.
Where the testing is to be carried out in sections the contractor shall retain on site a
drawing indicating sections tested and recording dates on which the tests took place
duly witnessed.
D.
The contractor shall be responsible for providing all skilled and unskilled labor
necessary to carry out tests and ensure that all supplies and instruments are available.
E.
Water Test
a. Apply the water tests to every part of each drainage system. Test each system
in its entirety or in sections. Tightly close openings in the piping.
b. If testing the system in sections, tightly plug each opening, except the highest
opening of the section being tested, and fill each section with water. Test
every section with a head of water equivalent to the greatest floor-to-floor
distance between floors with a minimum of at least a 10 foot head of water.
c. Keep the water in the system, or in the portion under test, for at least 15
minutes before inspection starts.
d. There shall be no leakage.
F.
Smoke Test
a. After connecting fixtures, perform a smoke test on the sanitary and laboratory
drainage systems.
b. Fill traps with water, then produce a thick, penetrating smoke with one or more
approved smoke machines and inject into the entire system. As the smoke
Page 16 of 17
appears at the stack openings on the roof, tightly close such openings and apply
a pressure equivalent to a 1 inch water column.
c. Maintain pressure of 1 inch water column for at least 15 minutes before
inspection starts.
d. Inspect traps. There shall be no leakage.
G.
3.18
PROTECTION
A.
The Contractor shall be responsible for repairing and replacing plumbing materials and
equipment, whether or not installed, which are damaged due to freezeups, until the
systems are approved by the Engineer and turned over to the Employer.
END OF SECTION
Page 17 of 17
PART 1 - GENERAL
1.01
SCOPE
A.
The work described in this section of the specification is related to water softening
equipment
B.
The contractor shall prior to the ordering of any equipment obtain two separate samples
of the water to be supplied to the site. These samples shall be sent to a laboratory for a
water analysis to establish all characteristics and a copy of the analysis shall be forward
to the consultants.
C.
It shall be the contractors responsibility to verify all equipment specified for water
treatment for size, flow rates and produce.
1.02
RELATED WORK
A.
B.
C.
D.
E.
1.03
QUALITY ASSURANCE
A.
The water softening plant shall be designed, manufactured, tested, certified and
stamped in accordance with the requirements of ASME code, Section VIII Div. I,
Unfired Pressure Vessel Code or any other similar international society.
1.04
REFERENCES
A.
B.
C.
Page 1 of 4
PART 2 - PRODUCTS
2.01
SOFTENING UNIT
A.
General Description
System to comprise two composite vessels, filled with softening grade strong cation
resin and support gravel media. Softeners shall be duplex type with one brine tank and
feeder pump.
Vessels to include top screen, bottom distributor and riser tube.
Control valves shall be top mounted type, brass bodied, 5 cycles programmable, with
inlet and outlet connections and to include water meter with setting range up to 375
m3. Brine tank assembly should include top opening HDPE tank, inclusive of brine
well, salt grid, safety brine valve (float valve), air check and removable cover.
Vessels will be operated in parallel as duplex type one duty and other standby and shall
alternate automatically during regeneration.
B.
Design Parameter
The operating feed water temperature will vary between a maximum of 25 Degrees
centigrade and minimum of 18 Degrees Centigrade.
Feed Water hardness is in the range of 200-300 ppm as Ca CO3 and Feed water TDS is
in the range of 500 1000 mg/l.
Required system capacity is 5.7 L/S, 2 softeners each 5.7 L/S. softeners shall operate
as duty standby and shall alternate automatically.
The systems total exchange capacity to be verified by the Contractor.
Design should be based on a duplex parallel system.
The total flow will be per one softener and each softener vessel with option to operate
one or two shall operate independently.
Regeneration of the resin will be initiated for each softener by a separate impeller
based water meter, which will send the signal to the control valve through a mechanical
signal.
System should be configured to automatically exclude hard water passage during the
non -service cycles.
System and piping configuration should allow for partial blending of product (soft)
water with feed (hard) water.
System to include safety brine valve in the brine tank to avoid brine tank overflow due
to power outages.
C.
Assembly
Page 2 of 4
2.02
A.
Composite Tanks:
Tanks to be of composite material, 4 inch threaded top opening complete with base.
Operating pressure 0 - 10 bars.
Operating temperature 1- 50 degrees centigrade
Minimum Fatigue testing 250, 00 cycles between 0 - 10 bar.
B.
Control Valves:
Valves to have fully adjustable cycles, type, meter initiated, include water meter,
electromechanical control type, brass bodied.
Valves should be equipped with the appropriate drain line flow controllers and brine
line flow controllers
Operating pressure range: 1.8 -8.5 bars
Working temperature range: 1- 43 degrees centigrade
C.
PART 3 - EXECUTION
3.01
EQUIPMENT
A.
The water softening equipment shall be a factory made skid mounted unit, which shall
be installed in the location indicated on the drawings within the space allocated, and the
manufacturer shall supervise the installation and his instructions followed.
B.
Damage Repair
1.
Prior to installation, the water softening plant shall be inspected for any
damage during shipping or storage.
2.
Any damaged sections of pipework shall be cut out and replaced with new
pipework of the same material. The outer coasting shall be inspected and any
defects made good.
Page 3 of 4
3.02
A.
Hydraulic Test
B.
1.
2.
The system shall be filled with water and subjected to 1.5 times the normal
work in pressure of the system. This pressure shall be maintained for 2 hours
without leakage before acceptance.
3.
A further test to ensure that all pumps, vessels, timers, and controls are
operational and meet the duty and requirements of the drawings shall be
initiated once the hydraulic test has proved satisfactory.
4.
After all tests are complete; the equipment shall be drained down, cleaned and
left ready for commissioning.
Commissioning
1.
END OF SECTION
Page 4 of 4
PART 1 - GENERAL
1.01
1.02
1.03
SCOPE
A.
B.
All sanitary items supply & installation to be in main contractors scope. The
MEP contractor shall provide only the services connection for these fixtures in
coordination with the main Contractor.
RELATED WORK
A.
B.
C.
WORK INCLUDED
A.
B.
C.
D.
E.
F.
G.
H.
PART 2 - PRODUCTS
2.01
2.02
SYSTEM DESCRIPTION
A.
B.
Where vitreous china is not available white glazed fireclay fittings shall be
used, e.g. shower trays, laboratory sinks and cleaners sinks.
C.
All taps, valves and sprays shall be made of good quality cast brass and
chromium plated. All hand held sprays in whatever location shall be fitted with
backflow (anti- vacuum) preventers.
GENERAL REQUIREMENT
A.
Page 1 of 4
2.03
Model Selection
Sanitary fixture model shall be selected by the interior decorator in coordination
with the Client
2.4
2.5
2.6
2.7
2.8
PART 3 - EXECUTION
3.01
INSTALLATION
A.
Set plumbing fixtures tight, level, and rigid on proper grounds. Use setting
compound under all settings surfaces.
B.
Provide required trim including supplies, loose-keyed stops, wastes, traps, and
floor and wall escutcheon plates.
Page 2 of 4
C.
Protect fixtures after they are set .Thoroughly clean them at the completion of
the project.
D.
1. Headers supplying flush valve fixtures shall run full size to last fixture.
2. Shut off valves shall be supplied in the furring for each fixture or to banks of two
or more fixtures, where required for proper system control, entrances of buildings
and to all equipment and controls.
3. Concealed valves shall be provided with access plates.
4. Install unions on one side of all valves, equipment connections and elsewhere as
shown or required for ease of service and / or installation, unless flanged are
indicated.
E.
Caulk around all plumbing fixtures with white silicone epoxy type, nonhardening compound, where fixtures meet floor or wall as required to present a
finish appearance. See Section on Sealants and Caulking.
F.
Set shower receptors and janitor receptors in a leveling bed of cement grout
and lead pan.
G.
The installation and connection of all sanitary fixtures shown on the drawings
or provided later shall satisfy the following specifications:
All exposed piping and trim shall be chrome plated and fully protected during
installation. Strap or padded wrenches shall be used on chrome pipe fittings and
valves.
All exposed metal parts in the sanitary blocks shall be chrome plated.
All exposed valves in the sanitary blocks shall be chrome plated of the recessed
type.
Plumbing fixtures shall be complete with all required trimmings, including faucets,
waste plugs, traps, supplies, stop valves, escutcheons and casings and all necessary
hangers, plates, brackets, anchors and supports.
All fixtures shall be equipped with chrome plated angle valves, whether specified,
shown on drawings or not.
Page 3 of 4
Fixtures shall be set in a neat, finished and uniform manner making the connection
to all fixtures at right angles with the walls, unless otherwise directed by the
Engineer.
Roughing for this work must be accurately laid out so as to conform to the finished
wall material.
Fixtures are not to be set until so directed by the Engineer.
The location and disposition of all items shall be as indicated on the relevant
drawings.
It is to be noted that all fixtures mentioned below shall be approved for shapes and
colors before ordering.
END OF SECTION
Page 4 of 4
PART I - GENERAL
1.01
General
The swimming pool system to be in the scope of specialist Contractor, the Mechanical
Contractor shall be responsible to provide all service provisions necessary for
connections and proper work in coordination with the Pool Specialist Contractor.
The term Contractor throughout this section refers specifically to the Pool
Specialist Contractor
Contractor shall provide all equipment and necessary accessories and fittings for
swimming pool and fountain equipment.
Scope of work shall include the following:
*
*
*
*
*
*
Approved Manufacturers:
Hayward
Wascop
Jacuzzi Pool Equipment
Swimquip
Culligan
or approved equal.
1.02
Design Conditions
For equipment specification refer to equipment schedule on drawings.
Guarantee in writing that when pool and fountain equipment are operated in
accordance with manufacturers instructions water will be crystal clear, sparkling
bright, free from suspended matter and completely sterilized at all times.
Water to be Clear: when pool and fountain are in use water is to be sufficiently clear
to permit a 150 mm diameter black disc on a white background placed on the bottom
of the pool to be clearly visible from the side walls of the pools at all distances up to
10m measured from a line drawn across the disc.
Water to be Sterile: when pool and fountain are in use not more than 15% of samples
of water taken covering any considerable period of time are to contain more than 200
bacteria per milliliter or are to show positive test in any of five 10 ml samples of the
water. Primary fermentation tubes showing gas should be confirmed.
Free Residual Chlorine in water at all times shall not be less than 0.7 ppm and not
more than 1.5 ppm.
Page 1 of 12
pH of Water: at all times shall not be less than 7.2 and not more than 7.8.
Piping
*
Heated pool and jacuzzi shall have its pipes insulated with fiber glass
blanket 32mm thick 32 kg/m3 wrapped with aluminum foil, cartoon,
canvas and foster layer 2mm thick.
Valves
Plastic, ball or butter fly valve, PN10.
Strainers
Basket type with stainless steel screen & stainless steel body (SS316) as shown
on drawings.
PUMPS
Supply and install wherever shown on the drawings pool recirculation pumps of
capacities as indicated on drawings.
Unless otherwise noted each pool & water fall pump shall be the centrifugal
end suction type, flexibly coupled to a drip proof electric induction motor, and
both mounted on a common steel base plate. Small pumps where noted on
drawings shall be inline centrifugal pump directly coupled to a drip proof
electric induction motor.
The casing of the pump shall be of good quality cast iron with renewable wear
rings, bronze impeller, high tensile stainless steel shaft, and flanged suction and
discharge connections.
Pump shall have mechanical shaft seal for continuous operation. Pump ball
bearings shall be of ample size to withstand all axial and radial thrust.
Each pump shall be complete with basket type strainer and gate valve at inlet,
check valve and globe at outlet and pipe flexible connection at inlet and outlet.
Unless otherwise noted pump speed shall not exceed 1450 RPM.
Page 2 of 12
This pump shall be used for vacuum cleaning of the pool also and to withstand
100C continuous water temperature when selected for heated pool.
The pump shut off pressure shall not be less than 25% higher than the design
load.
APPROVED MANUFACTURER
GRUNDFOS
BELL & GOSSETT
AURORA PUMPS
(USA)
(USA)
(USA)
PART II - PRODUCT
2.01
A-
Filters
Filters: high flow rate, sand filter, pressure type, designed for specified filtration
rate and operating pressure. Filters shall be hydrostatically tested at the factory
to specified test pressure. Quality of filtrate is to be guaranteed to be in the 2
micron range.
Filters: cylindrical, vertical type with diameter and straight sidewall height as
specified under Design Premise to allow a deep media structure. Filter heads
shall be dished to a radius equal to the diameter of the shell.
Filters: shall be designed with efficient influent and underdrain systems to
ensure uniform water flow through the filtering and backwash operations and to
prevent migration, mounding or channelling of the filter bed. Minimum
freeboard of 300 mm is to be provided between top of filter bed and influent
water distribution system. Influent and underdrain systems are to be fabricated
from corrosion resistant materials.
Page 3 of 12
Accessories
Filters shall be complete with the following accessories and appurtenances:
Standard size manhole on top dished head with boiler type cover.
Four jack type supports individually adjustable for filter level adjustment, of
adequate strength to carry the filter and contents.
Automatic air release valve on top dished head.
Gauge panel of cast bronze with two 100 mm minimum diameter dial pressure
gauges connected with copper tubes to the filter inlet and outlet connections.
Filter drain valve.
Substantial lifting lugs.
b)
Filter Media
Shall be as recommended by the filter manufacturer and as supplied by him
specifically for the filters. Components are to be shipped separately in clearly
marked bags.
Filter Media: provide clear instructions for field application of filter media in
the filters.
Filter Media: shall be graded rock and gravel to fine sand from bottom up
applied in layers of thickness as per manufacturers recommendations.
Rock and Gravel: shall consist of clean, hard, rounded stones with an average
specific gravity of not less than 2.5, free from shale, mica, clay, sandstone,
sand, loam or other impurities. Gravel is not to have more than 2% by weight of
thin, flat or elongated pieces.
Sand: shall consist of hard, durable grains of rounded or subangular silica sand,
free from clay, loam, dirt and organic matter. Not more than 1% may be flat or
micaceous particles. Sand is to meet the screen requirements given in the
following table and have an effective size of 0.35 to 0.45 mm and a uniformity
coefficient of 1.45 to 1.69.
Sand Screen Requirements
Sieve No.
U.S.
16
20
30
40
50
Tyler
14
20
28
36
43
% Retained on
Successive Screens
0-6
3-23
24-40
43-25
22-6
% Passing Through
Successive Screens
94-100
71-97
31-73
6-25
0-3
Page 4 of 12
c)
Hypochlorinator
1.
3-
Chlorine residual analyzer shall have an acetate reagent buffer solution system
with a constant head reagent feed system utilizing a control valve to meter
reagent into the sample cell.
4-
Chlorine residual controller shall be wall mounted and has in addition to set
point adjustment for setting the frequency of corrective action when a
difference exists between set point and measured residual chlorine.
5-
Chlorine residual recorder wall mounted solid state type requiring no ink and
incorporating a 30 day strip chart, an indicator strip for 0 to 2 PPM range and a
front clear glass cover with high and low level alarm contacts to actuate a
remote visual and audible alarms.
Page 5 of 12
6-
Ozonator Unit
Ozonator shall be as manufactured by prozone water purification system type
PZ or approved equal and shall be UL/UR approved. Ozonator shall generates
ozone and injects its into the return line. Ozonator shall be complete with all
necessary PVC pipes, injectors and all other accessories as recommended by
supplier.
7)
Brominator
Shall be complete as specified for Hypochlorinator but to feed powdered
sodium hypochloride.
8)
9)
10)
11)
Pool Fittings
General
Pool fittings shall be all plastic, heavy duty to withstand corrosion and the
action of chlorine. Pool fittings shall have color as requested by Engineer to suit
pool tiles color.
12)
Page 6 of 12
13)
No-Leak Flanges
Heavy PVC pipe pool with center flange and gussets, with 50 mm I.P.S. female
threaded pipe connections at both ends. To be fitted to inlet and floor fittings
and vacuum fittings within concrete wall of pool.
Main Drains
MD-1
Concrete pit with granite grating 300 x 300 to match pool finish as approved by
the Engineer. Grating free area is 40% with 160 mm drain pipe.
MD-2
Heavy duty body and flush vortex plate, white, 63 bottom connection and plug
similar to Hay ward Model SP-1045 or approved equal.
Gutter Drains
GD-1/ GD-2
63 FIP plus socket connection and grate similar to Hayward Model SP-1019 colors
approved by the Engineer.
Air Blower
Air blower for Jacuzzi shall be similar to hydro-air industries or approved equal.
Blower shall be 3HP, 415V, 50Hz.
Page 7 of 12
Cup Anchors
For attaching life line or racing lane ropes shall be embedded, flush type, with
integral no-leak flange, gussets, anchor and bronze eye bolt of 9.5 mm
minimum diameter.
Wedge Anchors
For securing ladders and life guard chairs shall be embedded, flush type, with
integral anchor flange and webs. They are to have cast bronze inwardly tapering
body with removable bronze locking wedge and stainless steel draw bolt and
washer. They are to be suitable for use with 48 mm O.D. tube or 40 mm I.P.S.
pipe.
Escutcheons
Shall be used with each wedge anchor to be specially designed for use with the
wedge anchor. They are to be cast bronze with polished chrome finish, and
fitted with locking screws.
B)
Ladders
48 mm O.D. corrosion resistant stainless steel tube, polished to give a brilliant
finish, complete with anti-skid steps, chlorine resisting white rubber buffers,
stainless steel escutcheons, and rounded, corrosion resistant metal fixing
screws.
C)
Supply Loose and hand to Employer in original containers after it is tested and
proved as working satisfactorily.
Vacuum Cleaner
Solid cast bronze with corrosion resistant finish, 450 mm working width, with
curved head and adjustable wheels, suitable for use with a 50 mm vacuum hose.
It shall be complete with 15 m of 50 mm white, corrugated, floating, flexible
plastic hose with formed polyethylene ends, and a 4.8 m long x 32 mm diameter
anodized aluminum telescopic handle complete with bolts and wing nuts.
Telescopic Handles
Anodized aluminum consisting of two concentric tube sections that can
telescope from 2.4 m to 4.8 m, with a positive locking device. They shall be 32
mm diameter, fluted for added strength. Inner tube to be 29 mm diameter drilled
for two 6 mm mounting bolts on 76 mm centers, complete with bolts and wing
nuts.
Algae Brushes
Page 8 of 12
Wall Brushes
450 mm long with curved ends, consisting of four dense rows of 29 mm long
nylon bristles permanently set in a strong moulded synthetic back reinforced
with an extruded aluminum section. A die cast aluminum handle holder with
two punched holes shall be securely attached to the back.
Leaf Rake
Synthetic fiber mesh screen set in a plastic covered aluminum frame with an
aluminum tube handle attachment and 25 mm O.D. anodized aluminum fluted
handle.
D)
Sundries
*
Strainers
Strainers on pump suctions shall be straight, in-line, flanged type, specially
designed for swimming pools. Size 100 mm with cast iron body and stainless
steel basket, suitable for a working pressure of 2 kg/cm2 (30 psig). It shall have
quick opening cover lid, positively sealing O-ring, yoke type cover clamp with
threaded tightening bolt and 40mm I.P.S. drain plug.
Flow Meters
Orifice type with direct reading manometer with indicating fluid other than
mercury, complete with 150 mm orifice flanges, orifice plate, piping to orifice
flanges and by-pass piping. It shall be suitable for measuring flows up to 500
U.S. gpm.
Flow meters shall be as manufactured by Meriam Model MS-37, or approved
equal.
Test Kits
Obtain from equipment manufacturer those kits necessary for running tests to
determine conformance of equipment performance with Contract requirements.
Page 9 of 12
Page 10 of 12
Workmanship
A-
General
Qualified Engineer or Senior Technician: engage from the equipment manufacturer
to supervise installation, start-up equipment, make necessary adjustments,
calibrations and tests in accordance with manufacturers instructions, and instruct
and train Employers personnel.
*
Equipment
Install in strict accordance with manufacturers instructions.
Strainers: provide on suction of each pump.
Flow Meters: install on supply branch pipe to each filter from the pump to
indicate filtering and backwash flow rates.
Backwash Sight Glass Indicators: install on backwash pipe from each filter
to provide a visual check of backwash flow.
Chemical Feeders: of 15 mm pipes with block valves on each feeder.
Page 11 of 12
B-
Tests
Hydrostatically Test pool piping as specified in Section 15950 - Testing &
Balancing to a pressure of 15 kg/cm2 applied for 24 hours.
*
Water Quality
Make chemical and bacterial analysis in accordance with procedures
recommended in the Standard Methods of the Examination of Water,
Sewage and Industrial Wastes of the American Public Health Association
insofar as these methods are applicable to swimming pool water.
*
Performance Tests
Carry out tests as necessary and as directed to demonstrate that equipment
meets the design requirements as noted on the Drawings and/or as specified.
3.02
PUMPS
A.
Shop Testing
All pumps shall be hydrostatically tested for leaks at 1.5 times the design
pressure. There shall be no leakage during the one hour test period.
The manufacturer shall submit certificate including test data to show that
the pump meets performance specifications.
Inspection
The Contractor shall inspect each pump prior to installation to verify that pumps
are in conformance with these specifications.
C.
3.03
Installation
-
If flexible coupling is used between the pump and its driver, shafts shall be
so supported and aligned as not to produce undesirable stresses and noise
during normal operation.
If oil or grease lubricated bearings are supplied with the pump, the oiler
shall be filled with the specified lubricating oil or bearings shall be prelubricated with specified grease prior to start-up.
Approved Manufacturers
AQUARIUS
WATER MASTER
EBD
EMCO
Or approved equal.
END OF SECTION
Page 12 of 12
1.01
PART 1 - GENERAL
a.
Drip legs: to comprise minimum 150 mm long nipple and cap connected to
bottom outlet of tee of same size as riser.
b.
c.
Valves 50 mm diameter and under to be plug type, semi-steel body with disc,
seat diaphragm and packing, resistant to action of LPG, 175 lb WOG rating,
wrench-operated with square head and with position of gate clearly indicated
on head. Each size of valve to be supplied complete with three operating
wrenches from factory.
d.
e.
f.
Valves over 65 mm diameter to be flanged, as manufactured by RockwellNordstrom fig. 143 or approved equal.
g.
h.
i.
Malleable iron threaded fittings shall be to ANSI B1603 class 150, standard
pattern for threaded joints, threads shall conform to ANSI B1.20.1.
j.
Steel fittings shall be ASTM A234, seamless or welded for welded joints.
k.
l.
Unions shall be ANSI B16.39 class 150 black malleable iron female patterns,
brass to iron seat; ground joint.
m.
Dielectric unions: ANSI B16.39, class 250, malleable iron and cast bronze with
threaded or soldered end connections.
n.
Solenoid valves shall be aluminum body, 240 volts AC, 50 Hz, class B
continuous duty molded coil Nema-4 enclosure electrically open and closed,
daul coils, normally closed UL listed and FM approved.
o.
Gas line pressure regulators, single stage, steel jacketed, corrosion resistant gas
pressure regulator with atmospheric vent, elevation compensator with threaded
ends for 50mm and smaller.
Page 1 of 5
p.
Gas pressure regulator installed on tank main pipe feeding building shall be
single stage type, designed to reduce tank pressure down to 10 psi water
column and to obtain pressure at appliances of 280 mm water column. It is to
have die cast aluminum alloy body and spring case, internal relief valve and 6
mm tapped and screened vent on low side. Relief valve to be factory set to start
to discharge at approximately 711 mm water column. Regulator seat to be
synthetic rubber, replaceable without disconnecting regulator from the line.
Regulator to be complete with mounting brackets. Obtain from one of the
following:
Fisher Controls Co.
Rockwell Mfg. Co.
q.
(U.S.A.)
(U.S.A.)
The sensor and control panel shall be interconnected via a 4-wire cable.
The indicator/controller module includes a direct reading, low level alarm,
rupture alarm indicators, output relays, power available and refill reminder
indicators.
Control power shall be 115 VAC, single phase 50 hertz with all necessary
transformers.
Tank monitor shall include the following alarms:
-
Refill reminder.
2.
Grip rings shall be of copper and collar of brass Stem size shall be 5/16 inches
diameters of the adjustable type with length suitable for day tank height.
Level switch shall be UL listed, Thomas products LTD level and flow switches
mode 4000 or approved equal.
Low level switch and high level switch in LPG tank shall be as described
above but shall give low level signal to BMS and high level signal to give
alarm that tank is over filled with fuel oil by tanker and a signal to BMS.
Approved Manufacturer
-
Automatic Controls:
Honeywell.
Barber-Colman Co.
Johnson Controls Inc.
I.T.T Controls.
Thomas Products LTD
Simplex
Instruments:
or approved equal.
1.02
GAS TANK
*
Page 3 of 5
Tank shall be constructed of welded fire grain high strength steel. Tank shall
be painted at factory with one coat anti-corrosion primer and 2 coats flat white
machine epoxy enamel.
Tank shall supplied complete with filter valve, service valve, internal safety
relief valve, liquid level gauge, drain plug, pressure gauge, magnetic float
gauge and rain cap on relief valve vent pipe.
Filter valve, service valve and pressure gauge shall have special hood to protect
them from mechanical damage.
1.03
Regulators shall be provided with necessary strainers and vents and securely
mounted to tank.
High pressure piping between tank and regulators to be extra strong black
seamless steel.
Tank welds to be X-ray controlled with test certificate submitted from certified
welders and government officials.
WORKMANSHIP
a.
b.
Install pipework at slope of not less than 9% with horizontal lines sloping
toward risers and from risers to appliances.
c.
Install pipework overhead and close to walls. Do not bury under buildings or
conceal in walls.
d.
Branch pipes are to be taken off from top or sides of horizontal lines.
e.
f.
Prohibited fittings: do not use unions. bushings, running threads or swing joints
made by combination of fittings.
g.
Flanged joints: use new gaskets only. If joint is broken and remade, destroy
used gasket so that it cannot be re-used.
h.
Outlets to appliances: locate far enough from floor. walls, slabs and ceilings to
permit proper use of wrenches without straining piping. Make with rigid pipe
only. Do not use hose of any kind.
j.
Mark valves clearly with metal tag to identify gas piping system.
k.
Drip legs: provide at bottom of all risers in locations readily accessible for
cleaning and emptying.
Page 4 of 5
1.04
1.05
1.06
TESTING
a.
Gas tightness: test piping by filling with air or inert gas such as carbon dioxide
or nitrogen. Do not use water or oxygen. Apply pressure from pressurised
cylinder or with air pump. Measure pressure with mercury manometer or
inclined gauge calibrated in increments not greater than 0.1 psi (0.07 g/mm2)
Isolate pressure source during test
b.
Gas tightness: test piping to 1 1/2 times normal working pressure or30 psig (10
g/mm2), whichever is greater. There is to be no drop in shut-in pressure for
two hours. Test for leaks by applying soap solution to joints. fittings and
valves. Do not use flame to look for leaks
COMMISSIONING
a.
Check for gas tightness: prior to turning on gas, close all shut-off valves at
appliances. Check that all openings are capped or plugged and that pipe work
is complete.
b.
Check for gas tightness: turn on gas, attach manometer calibrated in increments
of 2.5 mm water column to appliance outlet and open main shut-off valve
momentarily. No discernible drop in pressure is to occur during 3 minutes.
Should pressure drop he noted, identify cause, make necessary repairs and
repeat tests until perfectly tight system is assured.
c.
Alarm sounder.
Gas detectors.
Battery.
Control Panel.
Electric gas shut off valve.
END OF SECTION
Page 5 of 5
b.
c.
Furnish equipment supplier with all necessary data such as available electric
current characteristics, maximum and minimum ambient temperatures and
humidity, altitude, water quality and other particular site conditions so that
manufacturer will supply equipment to specifically suit Site conditions
particularly for necessary derating in capacity for altitude and temperature,
necessary class of insulation for electric motors, special construction for water
quality, high temperatures and humidities, sandy environment etc.
d.
Electric motors are to conform to the specification for electric motors given under
"Electrical Works for Mechanical Systems" and with requirements given under
equipment specifications for particular motor driving that equipment.
e.
f.
Pumps are to be selected so that their operating point falls nearest to the point of
maximum efficiency obtained from manufacturer's published data. Do not select
pumps to operate near the end of their curve.
g.
h.
Shop drawings for pumps: submit the following for approval, for each pump prior
to shipment:
certified performance curves showing job number, customer, customer order
number, pump designation number shown on the Drawings, date of manufacture,
model number, pump size, impeller diameter, impeller type, maximum impeller
diameter pump can accommodate, rpm, flow-head characteristic curve, consumed
horsepower curve, pump efficiency curve, cross-sectional drawing showing major
components with parts numbers and parts list.
i.
Shop drawings for pumps: submit the following for approval, for each pump prior
to shipment:
Outline dimensional drawing showing overall dimensions, location of foundation
bolt holes and size, location and rating of suction and discharge nozzles,
recommended list of spare parts, installation, operation and maintenance
instruction manual, details and wiring diagrams of pump controllers, starters,
Page 1/5
Vent pipe on fuel oil tank: extend to nearest outside wall of building; carry up at
least 3 m above grade with open end at least 1 m away from any building
opening. Pipe to be sloped back to tank with no traps and adequately supported.
End of pipe to have gooseneck bend or approved weatherproof vent cap.
Page 2/5
for high limit thermostat and numbered terminals strip for electrical connections to mains,
burner and heating control devices.
Maintenance Equipment: boiler to be provided complete with set of cleaning brushes with
handle, special tools required for maintenance and installation, gun for application of
sealing mastic and recommended quantity of sealing mastic in sealed containers required
for field sealing of joints.
Page 3/5
and painted on outside only with two coats of zinc chromate primer and two coats of
emulsified asphalt.
Page 4/5
a.
Plant Testing
Once the pipe laying has been completed, it is necessary to proceed with the plants
hydraulic test. Connecting to the distribution collector, the various circuits are filled while
taking care to vent the air sacks. The manual pressure pump will be connected to the
collector and, choosing the various circuits, they will be tested individually leaving the
plant in pressure (10 bars) for at least 24 hours. A physiological drop of the hydrostatic
pressure can occur according to variation of the temperature of (10C and can change the
pressure by 1 bar on the circuits.
Once the hydraulic trial is finished, proceed to covering the pipes with building mix,
mixed with the additive for thermal plants.
Pre-trial
Duration of 30 minutes.
While filling and venting the air, the pressure (10 bar) of each single ring should be
checked and restored every 15 minutes. Verify eventual leaks. At the end of the pre-trial,
the hydrostatic pressure should be stable.
Final Trial
Duration of 2 hours.
Recharge the plant with 10 bars of pressure which, over the duration of the final trial,
should undergo a maximum drop of 0.3 bar.
Testing Protocol
It is advisable to have a protocol that attests that the trials have been performed for each
single plant.
Notes:
b.
The testing pump pressure gauge should allow control of 0.1 bar variations.
c.
If severe temperatures are present (from +5C), it is possible to carry out the test
by adding antifreeze fluids to the water to protect the plant from eventual
temperature decreases and sub sequential formations of ice inside the pipes that
could become damaging to the plant itself.
Page 5/5
AIR-COOLED CHILLERS
SECTION 15680
PART 1 - GENERAL
1.01
DESCRIPTION OF WORK
Extent of Work: The extent of air-cooled chiller work is indicated by drawings and
schedules, and by requirements of this section. Each unit is defined to include (but
not by way of limitation), hermetic screw compressor, evaporator, air-cooled
condenser, controls and panel including gages and indicating lights, auxiliary
components, accessories and interconnecting piping. Required work also includes
additional requirements as compressor and fan, motor starters, vibration isolators and
seismic (earthquake) restrainers, evaporator insulation, anchor bolts and all required
accessories by the manufacturer.
1.02
QUALITY ASSURANCE
A.
B.
C.
Typical Performance Data: Prepare data for (ANSI/ARI 590) schedules full-load
capacity using "standard rating conditions" , part-load at 80%, 60% 40%, and 20% of
scheduled full-load capacity using "application rating conditions".
D.
Certify that sound pressure level will not exceed scheduled values when tested in
accordance with ARI 575. Include report of expected sound pressure level with
chiller operating at scheduled capacity, and include also report of expected sound
pressure level for each schedule capacity including part-load capacities.
E.
F.
Safety: Comply with ANSI/ASHRAE 15, safety code for Mechanical Refrigeration.
G.
UL Labels: Provide chiller electrical components which have been listed and labeled
by Underwriters laboratories.
NEMA compliance: Comply with applicable portions of National Electrical
Manufacturers Association standards pertaining to chiller motors and motor energy
management.
H.
Page 1 of 12
I.
1.03
2.
3.
4.
SUBMITTALS
Submit manufacturer's data on air-cooled chillers, including certified drawings
showing overall dimensions of complete assembly, operating weights, foundation
requirements, sizes, and locations of connection, accessories, auxiliary support
requirements, and parts lists. Include the following information:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Page 3 of 12
PART 2 - PRODUCTS
2.01
A)
General
-
The Contractor shall supply and install factory assembled air-cooled packaged
cooling only chiller. The number and capacity of which shall be as indicated in
the capacity schedule shown on the drawings.
Each machine shall consist of at least two accessible hermetic fully modulating
screw compressors air-cooled condenser, evaporator, interconnecting
refrigerant piping, controls, safety devices, accessories, and control power
transformer as applicable to limit control voltage to 240 volts maximum. No
phase to neutral voltage shall be required. Each compressor shall have its
independent circuit, evaporator, condenser, microprocessor-based controls and
a unit mounted motor starter.
The refrigerant circuit components shall include hot gas muffler, high side
pressure relief valve, liquid line shut off valve filter drier, liquid line sight
glass, liquid line solenoid valve and thermal expansion valve.
Chiller manufacturer shall provide for each chiller a certified factory run test
report.
The manufacturer shall perform all field testing, balancing and final adjustment
of the refrigeration machines in accordance with the applicable provisions of
the relevant ASHRAE Standards.
Page 4 of 12
B)
Any part of the machines or system failing to meet the contract requirements
shall be adjusted, repaired or replaced.
Chiller casing shall be capable of withstanding 500 hrs salt spray test in
accordance with ASTMB-117 standard.
Each packaged unit shall be factory equipped to connect to only one electrical
power feeder with the necessary built-in circuit breakers, and one main
disconnect switch. Disconnect switch shall be accessible from outside the
chiller without opening the panel door.
Each packaged unit shall be supplied with spring type vibration isolators
flexible enough to dampen any vibrations supplied by chiller manufacturer.
Each chiller shall have sound proof enclosure on compressor, condenser fan air
intake to maintain noise level of 60 dBA,10m away from chiller. Condenser
fan shall be of the low RPM type. Sound proof enclosure shall be factory
assembled and designed. Contractor shall provide additional sound treatment
around chiller to attain a maximum noise level of 30NC in the nearest room
included in the unit rate of the chiller.
Each packaged unit shall have a microprocessor control unit to provide all the
control and safety functions of the chiller with main circuit breaker for each
chiller.
Chiller shall be connected to building management system with pumps and all
other equipment as indicated in electrical drawings. Chiller shall have all the
necessary interface to connect to the selected BMS during execution.
A computer interface shall be provided for all the chiller including all control
and electrical works. The remote PC interface shall be connected to all chillers
at the same time and shall display all the data available at each chiller
microprocessor. This interface shall support the logging of alarms and all
operating parameters. This item is provisional incase chillers interface with the
selected BMS is not possible.
The chiller supplier shall train the project maintenance staff on the installed
chiller and the end of the training the attendees shall receive a certificate from
manufacturer for the operation and maintenance of chiller.
Compressor
-
The compressor shall have fully modulating capacity control by use of a slide
valve in the rotor section of the compressors positioned by hydraulic action.
Page 5 of 12
The compressor shall have squirrel cage two pole induction motor, suction gas
cooled
Each compressor shall be equipped with the following controls and instruments
and their respective connections:
C)
The compressor shall have hot gas discharge muffler and liquid line sight glass
and filter drier all as recommended by supplier.
Evaporator
-
The shell shall be constructed and tested in accordance with ASME Code for
Unfired Pressure Vessels.
The shell shall be completely insulated with 2"(50mm) thick urethane foam
insulation covered with a sheet steel jacket.
The shell shall be provided with an electric heater cable under the insulation.
Page 6 of 12
The evaporator shall be supplied with the following controls and instruments
and their respective connections:
D)
E)
Air-Cooled Condenser
-
Each condenser fan shall be in its own compartment to eliminate cross flow of
condenser air during fan cycling.
The condenser coil shall be made of seamless copper tubes, with aluminum
fins mechanically bonded to the tubes. With unti-corrosion paint factory
applied.
Fan motors shall be drip-proof type, with built-in over load protection, and
starting contactors. Motors shall be mounted on vibration isolators, and
provided with lubricated ball bearings.
Starter Panel
Chiller shall include a starter panel containing motor starter, disconnect switches
with fuses, 3 phase current transforment for motor overload protection.
F)
a)
Control Panel
Control panel shall be a microprocessor unit control module that provides all the
control and safety functions including startup and shut down, leaving chilled water
control, compressor and electronic expansion valve modulation, fans sequencing, antirecycle logic, automatic lead/lag compressor starting and load limiting. Unit protective
functions shall include loss of chilled water flow, evaporator freezing, loss of
refrigerant, low and high refrigerant pressure, reverse rotation, compressor starting and
running over current, phase loss, phase unbalance, phase reversal and loss of oil flow.
The unit shall include a menu driven digital display that indicate the chilled water
setpoint, current limit setpoint, leaving chilled water temperature, evaporator and
condenser refrigerant pressures and temperatures.
Page 7 of 12
b)
the microprocessor shall have an LCD type display with a minimum of 32 characters
with all messages in English. Coded messages and LED displays are not acceptable.
LCD display to be with light-emitting diode back light for outdoor viewing of data.
The control panel section shall include high and low pressure gauges.
Microprocessor shall be able to equalize the number of starts and the operatings of
each compressor in the chiller and to alternative between compressors to have equal
running hours and start ups.
The microprocessor shall be able to display the following readings.
-
Page 8 of 12
1.
2.
3. The microprocessor shall display the following in addition to the data listed on page
15680-6.
Page 9 of 12
G)
Cutout status and set-points for: supply water temperature, low suction
pressure, high discharge pressure, high oil temperature, low and high
ambient temperature, phase rotation safety, and low leaving chilled water
temperature, compressor motor current percent limit, fan control discharge
pressure set point.
Training for chillers:
Provide training for personnel. Training to include but not limited to:
i. Unit operation and maintenance.
ii. Unit theory of operation and trouble shooting methods for all
components.
iii. Service of all components down to compressor service and
microprocessor boards replaced.
iv. Checking unit for correct refrigerant and oil charge.
v. Unit refrigerant and oil charging and refrigerant recovery.
Page 10 of 12
PART 3 - EXECUTION
3.01
INSTALLATION
A.
B.
C.
D.
E.
F.
Install auxiliary piping, solenoid valves, shut-off valves, protective devices, water
strainers and controls within chiller work, and for ancillary systems. Comply with
manufacturer's installation instructions.
G.
H.
Paint damaged and abraded factory finish with touch-up paint matching factory
finish.
I.
Install gages in positions where machine vibrations will not interfere with taking
readings.
J.
Grounding:
components.
3.02
Observe installation of other work (related and connected to chiller work) and after
completion check for inadequacies and protect operation and performance of chiller
work to suit chiller manufacturer's requirements and to the Engineer satisfaction and
approval, do not start chiller work until inadequacies have been corrected in a manner
acceptable to the Engineer.
Page 11 of 12
3.03
3.04
CHILLER START-UP
A.
B.
C.
Cooperate with other trades of other work during the testing, adjusting, balancing and
start-up of mechanical systems.
3.05
TESTING
General: Except as otherwise indicated, test chiller in accordance with ANSI/ARI
Standard 590.
END OF SECTION
Page 12 of 12
HEAT EXCHANGERS
SECTION 15710
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
SUBMITTALS
A.
Product Data: Include rated capacities; shipping, installed, and operating weights; furnished
specialties; and accessories for each type of product indicated. Indicate dimensions, weights,
loads, and required clearances, method of field assembly, components, and location and size
of each field connection.
B.
1.4
QUALITY ASSURANCE
A.
Product Options:
Drawings indicate size, profiles, performance, and dimensional
requirements of heat exchangers and are based on the specific equipment indicated. Other
manufacturers' products with equal performance characteristics may be considered. Refer to
Division 1 Section "Substitutions."
B.
ASME Compliance: Fabricate and label heat exchangers to comply with ASME Boiler and
Pressure Vessel Code: Section VIII, "Pressure Vessels," Division 1.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Page 1 of 3
7.
8.
9.
2.2
Configuration: Freestanding assembly consisting of frame support, fixed and movable end
plates, tie rods, plates, and one-piece gaskets.
B.
Configuration: Brazed assembly consisting of two end plates, one with nozzles, and patternembossed plates.
C.
D.
E.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine areas for compliance with requirements for installation tolerances and for structural
rigidity, strength, anchors, and other conditions affecting performance of heat exchangers.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
3.3
CONNECTIONS
A.
B.
Maintain manufacturer's recommended clearances for service and maintenance. Install piping
connections to allow service and maintenance of heat exchangers.
C.
D.
E.
3.4
Drawings
CLEANING
A.
After completing system installation, including outlet fitting and devices, inspect exposed
finish. Remove burrs, dirt, and construction debris and repair damaged finishes.
Page 2 of 3
3.5
COMMISSIONING
A.
Verify that heat exchangers are installed and connected according to the Contract Documents.
B.
C.
Test and adjust controls and safeties. Replace damaged and malfunctioning controls and
equipment.
3.6
DEMONSTRATION
A.
Train Owner's maintenance personnel on procedures and schedules for starting and
stopping, troubleshooting, servicing, and maintaining heat exchangers.
Review data in maintenance manuals. Refer to Division 1 Section "Operation and
Maintenance Data."
Schedule training with Owner, through Engineer, with at least seven days' advance
notice.
END OF SECTION
Page 3 of 3
AIR DISTRIBUTION
SECTION 15801
PART 1 - GENERAL
1.01
1.02
RELATED WORK
A.
B.
C.
D.
E.
F.
SYSTEM DESCRIPTION
A.
Provide air distribution equipment and system as indicated on the drawings and
specified herein.
B.
1.03
QUALITY ASSURANCE
A.
B.
Unit fans shall be tested and performance rated in accordance with the
current AMCA standards.
Unit coils shall be ARI certified and labeled.
Electric heating coil shall be UL listed and labeled.
Manufacturer's Qualifications
1.
2.
Page 1 of 43
1.04
3.
Manufacturer shall have not less than five (5) years experience in
manufacturing the system specified herein, and will have supplied and
have in operation at least 5 systems similar in magnitude to the system
proposed for this installation.
4.
SUBMITTALS
A.
Product Data
1.
B.
Shop Drawings
1.
Shop drawings for each of the actual proposed equipment shall include
the following:
a.
b.
c.
d.
e.
f.
g.
1.05
Capacity
Operating Pressure Ranges.
Pressure Losses.
Fluid Flows.
Test Reports.
Certificates of approval including noise level ratings for fans
and terminal units.
Operation and Maintenance Data.
Any Other Technical Data.
REFERENCES
A.
B.
C.
Standard 181: Standard for Factory Made Air Duct Materials and Air
Duct Connectors.
D.
E.
2.
3.
2.
PART 2 - GENERAL
2.01
General
1.
2.
3.
Equipment design shall be such that the selected filter media, bearings
insulation etc. will be suitable for the ambient temperature existing
within the unit duct when heating coils are operating at their working
temperature.
4.
5.
6.
Page 3 of 43
B.
C.
Casings
1.
2.
3.
4.
5.
6.
Insulation
1.
D.
All fan sections, humidifier sections, coil sections and mixing box
sections shall be insulated using 50 mm thick, panel, with mineral
wool 80 kg/m3.
Page 4 of 43
E.
F.
Fan Section
1.
Fans shall be double width double inlet centrifugal type with airfoil
blades to suit the pressure and operating characteristics specified. Inlet
guide vanes shall be provided where applicable.
2.
Fan housing shall be constructed from mild steel sheet with angle
stiffeners utilized to prevent vibration and drumming. The casing shall
be constructed to a truly volute form.
3.
Casing shall have rigid cone inlets truly circular and free from dents.
All fan housings shall be welded on assembly irrespective of pressure
and air volume to provide a rigid airtight housing.
4.
Impellers shall be robustly fabricated from steel sheet, with a cast iron
boss and fabricated steel backplate. The boss shall be bored and
keywayed to the shaft. Impellers shall be rigidly braced to ensure
concentricity and eliminate vibration. They shall be statically and
dynamically balanced on their shafts after assembly.
5.
Shafts shall be cold finished, turned, and polished steel sized so the
first critical speed is at least 25% greater than the operating fan speed.
Flats or keyways shall be machined on to the shaft to provide a means
of securing the impeller. Keyways shall be provided for all driving
pulleys.
6.
7.
8.
9.
10.
A double ended fan shaft and extra mounting base for standby motor
shall be provided where indicated.
2.
All units with the exception of the operating rooms which have a
complete AHU for standby, with a duty and standby motor included.
3.
insulation and shall be suitably rated for the duty as shown in the
schedules.
4.
5.
G.
H.
J.
All fan motors above 4kw rating shall be fitted with bimetallic
type temperature sensing winding protection. The temperature
sensing circuits shall be connected to the central control and
monitoring system (BMS).
2.
2.
The dampers shall utilize painted steel blades with leading and trailing
edges specifically designed so that adjacent blades interlock on closure
to give a tight seal. Each blade shall be securely locked to its spindles
by means of an adjustable locking device and the spindles rotate in self
lubricating nylon brushes. Motorized dampers shall be
Electrically/Electronically operated as required by the control system.
3.
Page 6 of 43
K.
Fin tube heating element constructed of steel sheath with ceramic coated
steel fins, 80% nickel 20% chromium coiled resistor wire centered within
the sheath and highly compacted MgO film on the internal surface of the
sheath for electrical insulation and heat transfer.
Heavy gauge aluminized steel frame housing the heater, and shall be
suitable for horizontal and vertical mountings.
Control panel incorporated with the heater housing and same material as
the housing. Panel shall include the following:
Static pressure type air flow switch that prevents energization when
air flow is inadequate.
Fan delay control, to delay fan motor operation until the heating
elements have reached a preselected temperature.
Cooling Coils
1.
2.
3.
Tube sheets and top and bottom plates shall be of minimum 0.95 mm
galvanized steel. All tube sheets shall have die formed lipped holes to
receive tubes.
Page 7 of 43
L.
4.
Coil headers shall be fitted with plugged vent tapings and plugged
drain bosses to facilitate draining and venting.
5.
Coils shall be air pressure tested to 2MPa while immersing the coil in a
tank of water after completion.
6.
7.
8.
9.
No part of the coil tube ends or headers shall be external to the section.
Air baffles shall be arranged to prevent air by-pass of the coil. Coils
shall be suitably sealed with grommets where connections pass through
unit casing.
10.
11.
12.
Filter Section
1.
M.
2.
3.
4.
Page 8 of 43
2.02
5.
6.
The metering valve to be fully steam jacketed and to pass the metered
steam at atmospheric pressure to an internal drying chamber, fully
jacketed by steam at supply pressure, a silencer to be incorporated
using a stainless steel medium.
7.
8.
FILTERS
A.
General
1.
2.
3.
4.
5.
6.
B.
C.
Pre- Filters
1.
2.
3.
The section shall be insulated with glass fiber and of double skinned
construction. A hinged access door shall be provided for filter
changing.
Secondary Filter
1.
Shall be of the high efficiency disposable bag filter type. The bag filter
section shall be capable of accepting 50mm thick pre-filters and a
combination of 300mm by 600 mm ( nominal) bag filters. The bag
filters shall be of 95% efficiency against ASHRAE 52 Atmospheric
Duct Spot Test.
Page 9 of 43
2.
D.
The section shall be insulated with glass fiber and of double skinned
construction. A hinged access door shall be provided for filter
changing.
Grease Filters
1.
E.
The grease filters shall be of the corrugated plate or crimped wire mesh
type and shall be entirely of metal, and all ferrous metal shall be
protected against corrosion. Where grease filters are fitted in Kitchen
hoods, the assembly shall be include a drip tray and the element shall
be secured in the frame by quick release clips.
F.
Lint Filter
Lint filter shall be able to remove up to 98% of all lint and maintains a clean
lint screen. All lint shall be collected in plastic bag.
Lint filter shall be inline space saver lint filters as manufactured by Energetic
Corporation constructed of class A fire retarding fiber glass on aluminum
frame solid state 24 VAC 240 V with lint BAG.
Lint filter shall be compete with fire control system, and excess pressure alarm,
static pressure gauge, 360 degree rotating top side discharge and flexible lint
tube to collect lint at floor and automatic barometric damper.
2.03
2.04
Fan coil units consist of centrifugal fans, cooling coil, electric heating coil, (
where specified) and drain pan assembly, filter, insulated cabinet, discharge
grille, motorized valve kit, dynamic pressure compensating valve (Flowcon K)
return air grille, motor and drive all factory assembled. Units shall be
horizontal arrangement as scheduled or drawn. Motorized valve shall be of the
high pressure rating to withstand the maximum system pressure and operate at
the selected pump pressure at no additional cost.
Page 10 of 43
B.
C.
D.
E.
Main drip pan shall be provided with 2x24 mm OD drains ( one at each end)
for vertical units, one drain fitted with a removable plastic tap. Horizontal units
shall be provided with 1x22 mm OD drain.
F.
Unit casing shall be fabricated from galvanized sheet steel internally insulated.
Unit cabinet shall be fabricated from prepainted sheet steel with a baked
enamel finish. Cabinet shall have doors for easy access to the fan switch and
the connections on the coil.
G.
Units shall include speed control switch (3-speed/4 position) which shall select
any of the three available fan speeds and also switch off the fan. When the
switch is in the OFF position the unit shall be completely isolated from the
mains.
H.
Fan coil units shall be of the quite type with maximum noise level as specified
in various rooms. Unit shall be selected on medium speed, 35 dbA and
specified static pressure.
J.
Fan coil units shall be concealed type with plenum box and filter or exposed
type with cabinet decorative as shown on drawings.
K.
Fan coil units shall be complete with 2 way on-off motorized valves (3-way
valves in specific locations), gate valves, self balancing valves, double
regulating valves, strainers, di-electric fittings, unions and all other accessories
as detailed on drawings. All to be supplied built in the FCU- Factory
manufacture.
L.
Digital type thermostat shall include speed control switch ( 3-speed/4 position)
which shall select any of the three available fan speeds and also switch off the
fan. When the switch is in the OFF position the unit shall be completely
isolated from the mains. Thermostat shall have cooling mode to control the 2way or 3-way motorized valve thermostat in summer, or heating mode to
control the electric heater (when specified) in winter. Refer to section 15900
for thermostat specifications.
M.
Fan coil units shall be interlocked with lights system and windows to readjust
operation of FCU as shown on drawings.
Page 11 of 43
2.05
2.051
A.
FANS
GENERAL FAN REQUIREMENTS
General
1.
2.
3.
4.
5.
Performance data for all fans and spare parts shall be determined in accordance
with the provisions of ASHRAE 51.
Sound pressure level ratings of ducted fans shall comply with AMCA 301 and
shall be the result of tests made in accordance with AMCA 300.
Sound pressure level ratings of non-ducted fans shall comply with AMCA 301
and shall be the result of tests made in accordance with AMCA 300.
Application of sound pressure level ratings shall conform to AMCA 302. Unit
construction shall conform to applicable standards contained in AMCA 99 and
to requirements specified.
Safety provisions for power transmission equipment and non-ducted inlets and
outlets shall include guards and screens, unless other provisions are required,
and shall be constructed in accordance with applicable provisions of ASME
B15.1. Installation shall be such that fan vibration-isolation provisions are not
negated.
Fan wheels shall be statically and dynamically balanced at the factory.
B.
C.
Bearings
1.
2.
3.
4.
5.
Page 12 of 43
D.
Drives:
1.
2.
3.
4.
5.
6.
7.
8.
9.
E.
Belts:
1.
2.
2.052
A.
B.
Housings: Fabricated of steel with side sheets fastened with a deep lock seam or
welded to scroll sheets.
1.
C.
Fan Wheels: Single width, single inlet, welded to cast-iron or cast-steel hub and spunsteel inlet cone, with hub keyed to shaft.
1.
2.
D.
Fan Shaft: Turned, ground, and polished steel keyed to wheel hub.
E.
Page 13 of 43
F.
Belt Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1.
2.
3.
4.
G.
2.053
A.
B.
Housing: Removable, spun-aluminum, dome top and outlet baffle; square, one-piece,
aluminum base with venturi inlet cone.
1.
C.
Housing:
Removable, extruded-aluminum, rectangular top; square, one-piece,
aluminum base with venturi inlet cone.
D.
E.
F.
Belt-Driven Drive Assembly: Resiliently mounted to the housing, with the following
features:
1.
2.
Fan Shaft: Turned, ground, and polished steel drive shaft keyed to wheel hub.
Shaft Bearings: Permanently lubricated, permanently sealed, self-aligning ball
bearings.
Page 14 of 43
3.
4.
G.
3.
4.
5.
2.054
Page 15 of 43
2.055
A.
B.
Wind Band, Fan Housing, and Base: Reinforced and braced galvanized steel,
containing galvanized steel butterfly dampers and rain trough, motor and drive
assembly, and fan wheel.
C.
Wind Band, Fan Housing, and Base: Reinforced and braced aluminum, containing
aluminum butterfly dampers and rain trough, motor and drive assembly, and fan
wheel.
1.
D.
E.
F.
G.
Roof Curbs: Galvanized steel; mitered and welded corners; 50 mm thick, rigid,
fiberglass insulation adhered to inside walls; and 50 mm wood nailer. Size as
required to suit roof opening and fan base.
1.
2.
3.
4.
5.
6.
2.056
Fan Shaft: Turned, ground, and polished steel drive shaft keyed to wheel hub.
Shaft Bearings: Prelubricated and sealed, self-aligning, pillow-block-type ball
bearings.
Pulleys: Cast-iron, adjustable-pitch motor pulley.
Motor Mount: On outside of fan cabinet, adjustable base for belt tensioning.
A.
B.
Housing: Heavy-gage, removable, spun-aluminum, dome top and outlet baffle; venturi
inlet cone.
C.
Page 16 of 43
D.
Belt-Driven Drive Assembly: Resiliently mounted to the housing, with the following
features:
1.
2.
3.
4.
E.
2.057
Fan Shaft: Turned, ground, and polished steel drive shaft keyed to wheel hub.
Shaft Bearings: Permanently lubricated, permanently sealed, self-aligning ball
bearings.
Pulleys: Cast-iron, adjustable-pitch motor pulley.
Fan and motor isolated from exhaust air stream.
IN-LINE VENTILATORS
A.
Description: Centrifugal fans designed for installing in ceiling, wall, duct, or for
concealed in-line applications.
B.
C.
Fan Wheel: Centrifugal wheels directly mounted on motor shaft. Fan shrouds, motor,
and fan wheel shall be removable for service.
D.
E.
F.
Accessories: Manufacturer's standard roof jack, wall cap, or duct collars, and
transition fittings.
2.058
A.
B.
Housing: Split, spun-aluminum housing, with aluminum straightening vanes; inlet and
outlet flanges; and support bracket adaptable to floor, side wall, or ceiling mounting.
C.
Direct-Drive Units: Motor encased in housing out of air stream, factory wired to
disconnect located on outside of fan housing.
Page 17 of 43
D.
E.
F.
2.059
MOTORS
A.
B.
C.
Air-over-motor units shall be provided with NEMA-rated Class H insulation for all
services where air stream temperature exceeds 38 deg. C (100 deg. F). Air velocity
over motor surfaces shall be sufficient to maintain insulation temperatures within
NEMA standards at maximum fan horsepower. Motors used with variable frequency
drives (VFDs) shall be rated for VFD use.
D.
E.
Open drip proof motors where satisfactorily housed or remotely located during
operation.
Guarded drip proof motors where exposed to contact by employees or building
occupants.
Totally enclosed motors where located in unfiltered air streams.
Motor Bases: Motor shall be provided with adjustable motor bases, except as otherwise
specified. Motors over 7-1/2 horsepower (5600 watt of power) with fixed-sheave
standard belt section drives shall be provided with adjustable pivoted motor bases
wherever equipment configuration permits proper installation.
FACTORY FINISHES
F.
G.
H.
I.
Paint finish of fans exposed to outdoor shall be suitable for the hot and humid climate
of the project.
J.
Internal sides of fans used for 100 percent outdoor air shall be specially painted.
Page 18 of 43
2.
L.
Sound Power Level Ratings: Comply with AMCA 301, "Methods for
Calculating Fan Sound Ratings From Laboratory Test Data." Test fans
according to AMCA 300, "Reverberant Room Method for Sound Testing of
Fans." Label fans with the AMCA Seal.
Fan Performance Ratings: Establish flow rate, pressure, power, air density,
speed of rotation, and efficiency by factory tests and ratings according to
AMCA 210, "Laboratory Methods of Testing Fans for Rating."
Fans used for smoke extract shall be UL listed and suitable for high smoke temperature
of 250deg. C (500 deg. F) for a minimum of 2 hours continuous operation(Class B
smoke exhaust) ..
M. Noise level of fans shall not exceed noise level specified for location of installation.
The overall efficiency shall be minimum 60%.
N.
Fans utilized for kitchen extract shall be spark-resistant and suitable for kitchen
operation. Fans shall be UL and cUL listed for grease removal, tested under high
temperature exhaust of 190 deg. C (375 deg. F). Fans shall be tested in accordance
with relevant NFPA standard. Fan coating shall be as directed by the Engineer. Units
shall include the following:
1.
2.
3.
4.
5.
6.
7.
2.06
AIR CURTAINS
Each unit shall consist of an all-metal, corrosion-resistant, galvanized steel housing with
electrostatically -applied epoxy finish over powder primer.
Cabinets are to have flush louvers and full-length discharge with two 25mm directional vanes
for maximum 40 sweep for optimum air flow adjustment.
Cabinets shall be suited for continuous mounting.
Motor shall be fixed 2-speed with rocker-style hi/low selector switch. Motors shall be doubleshafted, resilient mounted, direct-drive, and totally enclosed.
Ball bearings shall be permanently-lubricated, rubber-sealed.
Blower wheels shall be cross-flow type for maximum outlet uniformity. Unit shall be furnished
with molded cord and plug assembly.
Sound level measured 10 feet from unit shall not exceed 54dbA. Mounting template and an
eight-page comprehensive operation, installation and parts manual shall be furnished with
every unit.
Page 19 of 43
2.07
Output frequency
Frequency resolution
Serial communication
Protection class
Immunity
Safety
Emissions
2.2 . 250 kW
2.2 . 315 kW
3ph, 415/440 Volts
45 66 Hz
0-U in
Ict + 50C ambient, overload : 1.5xIct,
1/10min. Ivt+40C no overload ability
200% from 0 rpm
2.5 Ict, max 2 s every 20 s max output frequency
lower than 30 Hz and heatsink temperature
lower than 60C.
0 . 500 Hz
0.01 Hz
Interbus-S Modbus, Echelon.
Ip21
The design fulfils EN 50082-1,2.
According EN 500178, CE,UL,C-UL,FI
EMC level I: EN50081-2;
EMC level C: EN50081-1,2
Variable speed motors shall be inverter-duty motors and shall be with manual bypass
for fixed speed operation incase the VFD is not operating.
2.08
General
1.
The Contractor shall supply and erect ductwork of the dimensions and
in the positions indicated on the drawings. The Contractor shall be
deemed to have checked building dimensions on site before the
preparation of the ductwork manufacturing drawings and shall submit
these drawings for approval before commencement of manufacture.
The Contractor shall also be required to erect ductwork in such an
order to maintain an overall continuity of work for all trades.
2.
Page 20 of 43
3.
All access opening shall be rigidly framed and fitted speedily removed
and re-fixed. Multiple set screws or self tapping screws are not
acceptable as a method of fixing, unless otherwise stated.
4.
Access doors and other openings in the duct work shall be provided for
the purpose given below.
5.
a.
b.
c.
d.
e.
f.
Static
Pressure
Rating Pressure
Seal
Class
Velocity
10 m/s Up
Medium
pressure
10 m/s Up
Medium
Pressure
10 m/s Up
Medium
Pressure
20 m/s Dn.
Low Pressure
Low Pressure
10 m/s Dn.
Page 21 of 43
2.09
General
1.
B.
Ductwork
Provide all ductwork, plenums, fittings and related sheet metal work
shown, noted and/or specified for the air conditioning and ventilating
systems.
Provide wood frames for air outlets fixing and duct passage through no
fire rated walls and slabs.
Conform accurately to the layout indicated on the drawings, and
construct to be straight and smooth on the inside with all joints neatly
finished.
Securely anchored to the building construction in an approved manner,
and installation to be completely free from vibration and pulsing under
all operating conditions.
Contractor shall be fully responsible for all off-sets,
up-slopes,
down-slopes, etc. necessary to avoid conflict with lighting fixtures,
sanitary piping, etc.
Bends and offsets shall have a minimum throat radius equal to the
width of the duct. Where short radius elbows are indicated or are
agreed by the Engineer as necessary due to site limitations the
dimensions and internal vane(s) shall be in accordance with duct detail
drawings.
Low pressure flat ducts over 450 mm wide shall be stiffened by cross
breaking.
Page 22 of 43
Fire rated and smoke ducts shall have two hour fire rating wrapping
material shall be of asbestos light weight non combustible material
board with square sawn edges and a smooth flat surface. Boards shall
be resistant to water and should not promote corrosion. Boards shall be
UL Listed.
All exposed ductwork shall be painted with one coat of primer suitable
to galvanized steel and two coats of finishing paint of type and color as
approved by the Engineer.
C.
2.
3.
4.
5.
0.6 mm
0.8 mm
1.0 mm
1.2 mm
1.6 mm
0.6 mm
0.8 mm
1.0 mm
1.2 mm
1.6 mm
0.6 mm
0.8 mm
1.0 mm
1.2 mm
1.6 mm
Page 23 of 43
6.
D.
0
300 mm
310 750 mm
760 1500 mm
1510 2200 mm
0.6 mm
0.7 mm
0.9 mm
1.0 mm
All duct fittings except where stated otherwise, shall be made from the
same material and specification of material as the adjoining ductwork.
The specifications with regards to stiffeners, joints, seams and
maximum distance between joints and stiffeners for straight ductwork
shall also apply to the duct fittings. The distance between joints
stiffeners of bends shall be taken around the centerline of the fitting,
and stiffeners shall be , when required, arranged in a radial pattern. The
larger dimension in all fittings shall determine the sheet thickness and
stiffening.
2.
Rectangular Fittings
a.
b.
c.
v 1. W ------- 1
v2
Page 24 of 43
Where t
V1
V2
=
=
=
D1
D2
W
=
=
=
Throat dimension
Air volume in branch
Air volume in main duct before branch
take off.
Depth of branch duct.
Depth of main duct before branch take off.
Width of main duct before branch take off.
E.
d.
e.
f.
g.
Maximum Spacing mm
60
60
30
60
Continuous
Page 25 of 43
2.
Maximum
spacing
for
cross joints mm
Maximum
spacing for
intermediate
stiffeners
RIVETS
Solid
Mechanically
closed
150
100
300
150
LOCK BOLTS
150
300
150
300
WELDS
Spot
Plug
Tack
75
150
150
150
300
300
The minimum number of fastening per side or per stiffener relating to table shall be
three.
3.
Maximum Spacing mm
LOCK BOLTS
BOLTS & NUTS
150
150
The minimum number of fastening per side relating to Table above shall be two .
F.
Minimum bearing
member mm
Maximum
spacing mm
M.S. rod mm
M.S. flat mm
Up to 500
10
25 x 3
25x25x3 angle
3000
501 - 800
10
25 x 3
40x40x4 angle
3000
801 - 1000
10
25 x 3
40x40x4 angle
2500
1001 - 1500
10
25x 3
50x50x5 angle
2500
1501 2250
12.5
40 x 3
100x50 channel
2000
Above 2250 to suit loading -----------------------------------------------------------------------
G.
2.
The bearing member shall not be required on ductwork above 1500mm where
the hanger supports are fixed to the duct joints, due to the provision of the
angle flanges.
3.
No screws, bolts or other fittings for brackets or supports shall penetrate the air
duct.
4.
The design of supports for vertical ducts is dictated by the site conditions and
spacing may be greater than that of horizontal ducts . Vertical ducts shall be
supported by the stiffening angles, or angle flanges, but where this is
impractical, supporting angles shall be fixed to the duct. Fastenings shall be in
accordance with the table for cross joints.
Sealants
1.
H.
Duct Protection
The Contractor shall by means of polyethylene or similar sheeting protects all openings
in ductwork during erection to prevent the collection of dust and dirt during the
building construction.
He shall be responsible for removing all these sealers from the systems prior to the plan
being commissioned.
He shall nevertheless be responsible for cleaning all ducts internally before the plant is
commissioned, the provision of the seals being a precaution aimed at reducing the
amount of cleaning necessary.
I.
J.
The Contractor shall be responsible for the quietness of the equipment in respect of
vibration and sound transmission to the structure and occupied spaces.
Where it is necessary to provide silencing equipment, anti vibration inserts mountings
and other acoustic devices, the Contractor shall include them in his tender.
K.
L.
Plenum Boxes
Plenum boxes construction and installation shall be similar to ductwork with internal
duct lining as specified above.
2.10
FLEXIBLE DUCTWORK
A.
General
1.
2.
The flexible duct shall have a liner and a cover of rough heat-resistant fabric
equal in durability and flexibility to glass fiber fabric and shall be impregnated
and coated with plastic. It shall be reinforced with a bonded galvanized spring
steel wire helix between the liner and the cover and an outer helix to glass fiber
cord, or equal shall be bonded to the cover to ensure regular convolutions.
Insulation shall be as specified for rigid steel.
3.
4.
The frictional resistance to the air flow per unit length of the flexible duct shall
not exceed 50% more than the frictional resistance per unit length of the
galvanized steel ducts of equivalent diameter. The radius ratio R/D for bends
shall not be less than 2. Where R is the centre line radius and D is the diameter
of the flexible duct.
Page 28 of 43
5.
The leakage from any section of flexible air duct shall not exceed 1% of the
design air flow rate at the static operating pressure.
6.
Flexible ducts shall be suitable for an operating temperature range of -18C to 120C and shall comply with BS 476 Part 1, Section 2, Clause 7 ( class 1 :
surface of very low flame spread).
7.
2.11
A.
Surface:
A.1 The panel shall be manufactured of CFC free and Halogen free, closed cell
phenolic foam thermo- bonded.
A.2 Foil Thickness in the inner side panel should be not less than 25 micron thickness
aluminum foil reinforced with a 5mm glass scrim for inner to insure smooth
surface and reduce friction loss.
A.3 Foil thickness in outer side panel should be rigid and embossed aluminum with
minimum 60 micron thickness to insure better durability and protection.
A.4 Both sides aluminum foil covering the panel must be maintained intact after
installation to ensure vapor barrier continuity.
B.
Density:
C.
Phenolic foam density must be not less than 60 kg/m3 as per ASTM D 1622: 03.
Thermal conductivity:
Thermal Conductivity: 0.024 W/ (m.K) at 35 +/-2 0C, 60 +/-5% RH, 24 h according to
ASTM C 518:2004.
D.
Compressive strength:
Compressive strength should be not less than 351.5 kPa at 23 +/- 2C, 50 +/- 5% RH
according to ASTMD 1621:00.
E.
F.
Water absorption must be less than 0.25% at 23 +/- 2C, 50 +/- 5% RH, 48 h
according to ASTM C 209:1998.
Water vapor transmission of materials should be 0.00 at 23 +/- 1C0 , 50 +/- 2%
RH according to ASTM E96-00.
Fire properties:
Page 29 of 43
G.
Class 0 according to BS 476 Parts 6 Fire Propagation Index I & BS 476: Part 7
Class 1 Surface Spread of Flame.
Reaction to fire test for Building Products exposed to the thermal attack by a
single Burning Item according to BS EN 13823: 2002
UL 181 Surface Burning Characteristics in accordance with Standard
ANSI/UL723, ninth edition, dated August 29, 2003
Ignitability of a Building Products subjected to Direct Impingement of a Flame
according to BS ISO 11925-2: 2002.
ASTM 84 Surface Burning Characteristics, Flame Spread and Smoke
Developed.
Toxicity:
Phenolic Panels must be Toxic free as per IMO test IMO RESOLUTION MSC 61 (67)
1996; Annex 1, Part 2 Smoke & Toxicity Test. WF Report
No. 160905 and No. 160906 dated 14th of February 2007 which is superior to NES 723.
H.
Temperature range:
No relevant reduction of insulation, chemical or physical characteristics of the panels to
be measurable, when conveying air in the temperature range
I.
Duct work:
The pre-insulated aluminum ductwork shall also have the following characteristics:
I.1
I.2
I.3
I.4
J.
Installation:
The general installation characteristics shall be as follows:
J.1
J.2
J.3
J.4
J.5
J.6
2.12
The joints between the ducts to be installed in air-conditioned areas and plant
rooms shall be made, using aluminum flange with aluminum slide-in-bayonet.
The joints between the ducts will be completed with the installation of
adhesive to reduce air leakage.
Proprietary inspection and access panels to be installed as SAT Insulation
requirement.
Flexible connections shall be provided between the ductwork and any piece of
equipment subject to vibration or movement (i.e. FCU).
DAMPERS
All dampers shall be fabricated by an approved Manufacturer and not by the
Mechanical Subcontractor duct-man.
A.
B.
Regulating Dampers
1.
2.
Each primary control damper shall be fitted with a non-corrodible label stating
the actual air flow in m/s and the cross sectional area; alternatively, these
figures shall be painted in a visible position on the adjoining ductwork or
insulation. The position of a damper as set after final regulation and balancing
shall be indelibly marked on the damper quadrant.
3.
Multileaf Dampers
1.
2.
No damper blade shall exceed 150 mm in width and where dampers are
required for greater widths, the damper sections shall be constructed in
multiple frames. Individual dampers blades shall not exceed 225 mm in height.
Each leaf of a multileaf damper shall consist of two plates of material of the
same thickness as the associated duct and rigidly fixed to each side of an
operating spindle, the ends of which shall be housed in brass, nylon, oil
impregnated sintered metal, PTFE impregnated or ball bearings. The ends of
the spindles shall be linked so that one movement of the operating handle shall
move each leaf an equal amount. An inspection door shall be provided adjacent
to each multileaf damper.
Page 31 of 43
C.
D.
3.
4.
Quadrants and operating handles shall be of die-cast aluminum with the words
OPEN and CLOSED cast on the quadrant. Quadrants shall be securely
fixed and the damper spindles shall be close fitting in the quadrant hubs to
prevent any damper movement when the damper levers are locked.
In ductwork 300 mm or less, single blade dampers may be used. The blade
shall be made from a single plate, at least 1.6 mm thick and suitably stiffened.
One end of the damper spindle shall be housed in brass, nylon, oil impregnated
sintered metal, PTFE impregnated or ball bearings. The other end shall extend
beyond the damper casing with an operating handle and quadrant.
2.
Quadrants and operating handles shall be of die-cast aluminum with the words
Open & Closed cast on the quadrant. Quadrants shall be securely fixed
and the damper spindles shall be close fitting in the quadrant tubes to prevent
any damper movement when the damper levers are locked.
E.
Page 32 of 43
2.13
FLEXIBLE JOINTS
A.
General
1.
Flexible joints shall be provided on the fan inlet and outlet connections and
elsewhere on the ductwork where indicated. They shall be of the full cross
sectional area of the mating fan inlet, outlet or duct section. The ends of the
ducts or the duct and the fan connection shall be in line.
2.
3.
All flexible joints other than fan inlet connections shall be between flanged
ends. The flexible material flange shall be backed by an angle or flat iron
flange and the flexible joint shall be securely held between the metal flanges.
Flat iron bands used with fan inlets shall be not less than 5 mm thick.
2.14
A.
General
1.
2.
3.
Grilles and diffusers shall be not less than the size indicated; where no size is
given they shall be capable of dealing with the air flow and distribution as
indicated with a maximum neck velocity of 4 m/s.
Page 33 of 43
B.
C.
D.
4.
All grilles except those on exposed ducting shall incorporate an edge seal.
5.
All grilles and diffusers shall have suitable color finish as approved by the
Engineer.
6.
The fixing of grilles and diffusers to the ductwork shall be by means of spring.
External screws will not be accepted.
Each sidewall supply air grille shall have two sets of separately adjustable
blades, one set horizontal and one set vertical, and shall be complete with an
opposed blade multi-leaf damper. The blades and the dampers shall be
adjustable from the front of the grille.
2.
Sidewall return air grilles shall have a single set of horizontal blades. Each
return air grille shall be complete with an opposed blade multi-leaf damper
operable from the front.
3.
All supply and return air grilles shall have quick release subframes.
Four-way supply diffusers shall have adjustable core pattern, shall be provided
with opposed blade volume control damper, and shall be compatible with the
ceiling system provided. Perforated face shall be finished in black enamel.
2.
3.
Egg crate return air grilles shall be fabricated of aluminum with extruded frame
and shall be compatible with the ceiling system provided.
4.
Diffusers and grilles shall be provided with volume control dampers of the
opposed blade type which shall be adjustable from the front of the diffuser.
5.
Liner diffusers shall include a control damper at the rear of the vanes giving
volume control down to complete shut-off and operated from the face of the
diffuser. Liner diffuser for supply air shall have adjustable blades to give
directional control of air flow. Where linear diffusers are mounted in a
continuous line, there shall be means of ensuring alignment between
consecutive diffusers and of equalizing pressure behind the vanes. Return air
linear grilles shall match supply diffusers. Linear diffusers shall have factory
supplied plenum box, internally lined as specified under ductwork.
6.
Page 34 of 43
External Louvers
All louvers for fresh air and exhaust air shall be fabricated from heavy duty aluminum
extrusions. The horizontal blades shall be angle down towards the front of the louvers
and each blade shall have a down turn at the front and up turn at the back edges in such
a manner that the ingress of rain is prevented. Each blade shall be securely fixed to the
surrounding frame.
All louvers shall be fitted with an aluminum bird wire screen on the inside face.
F.
Supply grilles shall include flow equalizing dampers and continuous plenum
box over the entire diffuser length. Plenum size shall be as indicated on the
drawings.
b)
c)
Fixing frame for outlet mounting on walls and false ceiling, etc... Frame may
be of wood of metallic construction as site conditions dictate. Fixing for linear
grilles shall be of the concealed fixing type; screws shall not be accepted.
d)
G.
Page 35 of 43
Linear diffusers: finish is to be natural anodized white or colored with black volume
and pattern blades.
Linear diffuser: factory supplied diffuser plenum fittings are to be coated steel insulated
internally with 12 mm thick duct insulation.
H.
2.15
Door Louvers
-
Supply and deliver door louvers to the door manufacturer for installation.
The door louvers shall be sized so that the face velocity does not exceed 250
fpm (1.3 m/s) unless otherwise indicated on the Drawings.
2.16
2.17
JET DIFFUSERS
Jet diffusers shall be manually adjustable allowing variation in discharge angle to
compensate for changing temperature difference.
Jet diffuser shall be adjusted 30 upwards to 30 downwards. The nozzle mounting
plate shall also be rotated though 360 which enables the air jets to be fully directional.
Jet nozzles shall be installed singularly or in banks as required.
Construction of jet diffusers shall be of aluminum, the border being extruded from
aluminum to BS- 1474 grade 6063 T6 and the mounting plate from aluminum sheet to
BS 1470 grade NS4.
Jet diffuser shall be supplied in different colors to suit the engineer requirement
Jet diffuser shall be supplied with a plenum box which is manufactured from
galvanized sheet steel to BS 2989 Z2 G275 M.
For supply air jet diffuser supply an opposed blade damper shall be installed in the rear
of the plenum box. Construction is of galvanized mild steel to BS2989 Z2 G275 M for
the border and BS 1472 grade 6063T6 for the extruded aluminum blades.
All visible surfaces of plenum box and damper unit shall be finished stove enamel paint
matt black.
2.18
Page 37 of 43
Hood shall be fabricated in a minimum number of sections with hair line butt field
joints.
Hood shall be provided with lighting fixtures, as herein described, equally spaced,
wired with Type A.V.A. wire in rigid galvanized conduit. Fixtures shall be commercial
vapor-tight square surface mounted units with square prismatic glass panel for a 150
watt lamp. Fixtures shall consist of a square metal housing with provisions for
mounting in stn. stl. hood together with horizontally mounted lamp with dome shaped
aluminum reflectors. Square face plate shall be formed of # 18 ga. stn. stl. with satin
finished hinged panel, and shall contain 215mm. square diffusers. Diffusers shall be
gasketed to frames and frames gasketed to housing forming completely vaportight
units.
The face of all exposed sides of the hood below ceiling shall be enclosed with vertical
facing of # 18 ga. stn. stl. Stn. stl. panels shall measure not more than 900mm. in width,
with each second panel removable and provided with a stn. stl. recessed finger grip.
Where panels meet at vertical joints, they shall be flanged inward 250 mm to form a
hairline joint. Provide a # 14 ga. stn. stl. trim member at ceiling and at joints against
walls.
Hood shall be fitted with built in automatic total flooding fire protection system
utilizing dry powder designed and installed in accordance with NFPA. Fire protection
System shall be UL listed. Contractor to submit all necessary calculations and system
components for approval.
Exposed kitchen hood ductwork shall be of stainless steel 1.2 mm thick, 304 type,
installed in accordance with NFPA 96.
Concealed kitchen hood ductworks shall be black steel 1.5 mm thick with flanged
joints and heat resistant gasket. All longitudinal seams shall be continuously welded
with provision for expansion. Duct shall be insulated as specified and installed in
accordance with NFPA 96.
2.19
SOUND ATTENUATORS
Supply and install sound attenuators on all air handling equipment to satisfy the
required noise level criteria whether or not shown on drawings and as specified.
a.
Sound attenuators to be suitable for 100 mm W.G. internal air pressure and 40
deg. C operating air temperature. Maximum static pressure drop through silencer is not to exceed 5 mm W.G. at specified air quantity. Silencer to
attenuate sound by at least 10 DB in the 125 Hz and 30 DB in the 2000 Hz
octave band mid-frequencies respectively.
b.
Sound attenuators for axial flow fans: to be the product of fan manufacturer,
designed to match fan with end rings drilled and tapped to match fan flanges.
Silencer to be cylindrical type with centre pod, comprising galvanized steel
casing lined with mineral wool and retained by expanded steel. Lining to be rot
proof and fire proof faced to withstand high air velocities without erosion.
Sound attenuators to have specially designed sound absorbent single or double
pods mounted concentricity within lined outer casing. It is to be complete with
lifting lugs and mounting feet of same type supplied for fan.
Page 38 of 43
c.
Sound attenuators for air handling units: straight, rectangular, splitter type,
designed for mounting in ducts, with pre- drilled flanges. Silencer is to have
number of air passages in parallel and in height and width to meet resistance to
air flow requirements and length to meet sound attenuation requirements.
Sound attenuators to comprise multiple galvanized steel splitters held in
galvanized steel casing. Splitters and casing to be lined with rot-proof and fireproof resin bonded mineral wool faced with woven glass fiber.
PART 3 - EXECUTION
3.01
GENERAL
A.
Air- handling units, fans and equipment generally shall be floor mounted on 100 mm
raised concrete housekeeping pads and supported from building structural frame using
vibration isolators. Provide all supporting steel, anchors etc. required to properly
support the unit.
B.
Replace throwaway filters just prior to building acceptance and after the system has
been balanced.
3.02
A.
Where metal ducts and fan inlets and outlets connect to builders work, connections
shall be by either built-in timber frames or built-in companion rings or flanges. Built-in
timber frames shall be used except where the connection is to be made in fire barrier
walls or in the fixing of fire dampers. Timber frames shall be constructed in hardwood
of 50 mm minimum thickness. Companion rings or flanges shall be provided with an
adequate number of suitably sized rag bolts or similar fixing devices.
B.
In all cases the duct end shall be finished with a mating flange and where this is fixed
to a timber frame the flange shall be wide enough to overlap the joint between timber
and masonry by least 15 mm.
C.
The material of the duct shall be extended in the form of a spigot, beyond the flanged
connection and into the builders work cavity.
D.
Joints between mating flanges and companion rings or hardwood frames shall be fitted
with a sealing gasket as specified previously.
3.03
DUCTWORK INSTALLATION
A.
General
1.
2.
3.
4.
Support drop rods and bolts shall be bright steel, nuts and washers shall be sheradized.
B.
C.
1.
Hinged access doors should not be larger than 600 mm high by 600 mm wide
unless necessary for equipment handling. Doors should preferably open against
the air pressure. Both the opening in the duct and the access door itself should
be adequately reinforced to prevent distortion. A suitable sealing gasket shall
be provided together with sufficient clamping type latches to ensure an air-tight
and water-tight seal between the door and the duct. The latches shall have
handles to operate from both the inside and outside of the door.
2.
Removable access covers shall not be larger than 375 mm wide by 300 mm
high, unless essential for access to equipment, in which case the size shall be
agreed. The opening in the sufficiently rigid shall be provided distortion. A
suitable sealing gasket shall be provided with sufficient fastenings to ensure an
air-tight seal.
3.
Access openings in insulated ducts shall have door frames extended beyond the
face of the duct by a measurement equal to the thickness of the insulation and
be so arranged that the insulation and finish can be dressed into the frame,
thereby ensuring that the opening is not concealed and that the edges of the
insulation are protected from accidental damage. The access door shall be
dished to contain the insulation.
4.
Test holes for instruments shall be provided at regular intervals along the
ductwork and to enable fan duties to be tested and the performance of
regulating dampers to be accessed. All holes shall be 25 mm diameter and
provided with an effective seal.
Flexible Joints
1.
2.
The flexible joints shall be manufactured from fire rated reinforced Neoprene
or glass fiber cloth and not be less than 75 mm wide (metal edge to metal edge)
and not more than 250 mm wide.
Page 40 of 43
D.
E.
F.
3.
4.
5.
6.
7.
The sealant shall be applied with a brush or gun and shall completely seal the
joint. The ductwork must not be pressurized until the sealant has cured. The
jointing between angles shall be suitable gaskets or mastic sealant.
2.
The gasket shall not be less than 3mm thick for ducts of up to 1mm sheet
thickness or not less than 4mm for ducts of up to 1.2mm sheet thickness.
Before application of the sealant, all surfaces shall be thoroughly cleaned.
Connections
1.
2.
Exposed ductwork shall have 75 mm clearance from walls and ceilings for
cleaning purposes.
Supports
1.
Supports and brackets for ductwork shall be purpose made and adjustable,
fixed to the building structure with special brackets and cantilevers and spaced
to ensure adequate support and where practicable, should be fitted at each joint
of the ductwork.
Page 41 of 43
2.
G.
Vertical ducts shall be supported by the stiffening angles or angle flanges but
where this is impractical, supporting angles should be fixed to the duct.
Spacing of supports for vertical ducts may be at greater intervals than for
horizontal ducts.
3.04
A.
Ductwork for the kitchen hoods and dishwasher shall be fabricated and installed in
accordance with the Uniform Mechanical Code, Chapter 20. Exposed ducts shall be of
stainless steel. Hidden ducts shall be of black steel painted and insulated as specified.
All duct connections shall be flange type with fire rated gasket. Access doors shall be
provided at each change of direction.
3.05
A.
Install air outlets and inlets in accordance with manufacturers written instructions and
in accordance with recognized industry practices to insure that products serve intended
functions.
B.
Coordinate with other work, including ductwork and duct accessories, lighting,
structural and Architectural elements, as necessary to interface installation of air outlets
and inlets with other work.
C.
Locate ceiling air diffusers, registers, and grilles, as indicated on general construction
"Reflected Ceiling Plans" or as approved by Engineer. Unless otherwise indicated,
locate units in center of acoustical ceiling modules.
D.
Diffuse supply air to assure air velocities not in excess of (50 fpm) 0.017 m/s at 1.8m
or less above the floor line. Mix room air with the primary air by induction to effect
subsequent equalization of the room temperature without stratification. Install all
outlets in accordance with manufacturer's recommendations.
E.
For outlets used with under-the-window or wall units, coordinate the outlet dimensions,
arrangement and pressure drop with the units and enclosure to assure compatibility.
F.
3.06
A.
3.
The size of the test section may vary from a complete supply or exhaust system
to a portion of a system, depending on its complexity and size. The Engineer
shall use Appendix F in the aforementioned SMACNA Manual as a guide in
determining test section sizes and locations.
4.
END OF SECTION
Page 43 of 43
COOLING SYSTEM
SECTION 15803
PART 1 - GENERAL
1.01
1.02
RELATED WORK
A.
B.
C.
D.
E.
F.
G.
SYSTEM DESCRIPTION
A.
1.03
1.
2.
REFERENCES
A.
1.04
General
SUBMITTALS
A.
Product Data
1.
Capacity
b.
c.
Pressure Losses
d.
Fluid Flows
e.
Test Reports
Page 1 of 6
B.
f.
Certificates of Approval
g.
h.
Shop Drawings
1.
Shop Drawings for each of the actual proposed equipment shall include
the following:
a.
b.
Calculations.
c.
Installation Details.
d.
e.
f.
g.
System Diagrams.
PART 2 - PRODUCTS
2.01
MATERIALS
A.
General
1.
2.
B.
C.
Page 2 of 6
2.02
PUMPS
A.
General
1.
2.03
2.04
EXPANSION TANK
1.
Provide compression tank ( expansion tank) as shown on the drawings, constructed for
930 Kpa working pressure for chilled water system and 1500 KPA for condenser water
system, stamped with U symbol and supplied with National Board From U-1
denoting compliance with ASME boiler and pressure vessel code. Provide fittings and
connections to related equipment in accordance with tanks manufacturers
recommendations. Tank shall be insulated externally. Insulation shall be same type
used for exposed ductwork, specified hereinbefore. Tank diaphragm shall withstand 10
deg. C up to 120 deg C suitable for heating water systems.
2.
2.05
Chemical Supply
Supervision of treatment program applied
Water analysis and recommendations.
The mechanical contractor shall make sure that the following are completed
and handed over to the engineer prior to commencement of water treatment
work s:
1.
2.
3.
4.
5.
Estimated volume of chilled water system and condenser water system are to be
verified by the Contractor and submitted for approval.
Page 3 of 6
2.06
B-
D-
General
The Contractor should make sure that the water treatment specialist execute the
following tasks during the one year guarantee period.
Schedule visits frequency
: 6 per annum.
The following is carried out on every visit by the chemist:
1234-
GENERAL INSTALLATION
A.
Piping
1.
2.
3.
4.
Provide balancing valves and pressure gage cocks in all returns from
equipment and three way valve bypass loops to balance the system.
5.
6.
END OF SECTION
Page 6 of 6
SECTION 15860
MINI SPLIT UNITS
PART 1 - GENERAL
1.01
SUMMARY
A.
Provide labor, materials, equipment and services, and perform operations required for
complete installation of the mini split units and related work as indicated on the
drawings and specified herein.
B.
Work Included: The work shall include, but not be limited to, the following:
1.
Extent units work required by this section is indicated on drawings and schedules, and
by requirements of this section. Types of units specified in this section include the
following:
a.
2.
Provide factory-mounted and wired controls and electrical devices as specified in this
section.
C.
1.
2.
1.02
QUALITY ASSURANCE
A.
Materials shall conform to the latest edition of industry standards and reference
specifications specified herein and to applicable codes and requirements of local
authorities having jurisdiction, whichever is more stringent.
2.
1.03
SUBMITTALS
A.
1.
Product Data: Submit manufacturer's technical product data, including rated capacities
of selected model clearly indicated, weights, furnished specialties and accessories and
installation and startup instructions.
Page 1 of 4
2.
3.
4.
Maintenance Data: Submit maintenance data and parts list for each packaged heating
and cooling unit, control and accessory, including "troubleshooting" maintenance
guide. Include this data and product data in maintenance manual in accordance with
requirements of Section 15010.
1.04
A.
Handle units and components carefully to prevent damage, breaking, denting and
scoring. Do not install damaged units or components; replace with new.
B.
Store units and components in clean dry place. Protect from weather, dirt, fumes,
water, construction debris and physical damage.
C.
Comply with manufacturer's rigging and installation instructions for unloading units,
and moving units to final locations for installation.
1.05
WARRANTY
A.
1.
2.
PART 2 - PRODUCTS
2.01
MINI-SPLIT UNIT
A)
General
Mini split system shall cover a range up to two tons of refrigeration and shall consist of
a condensing unit, an evaporator blower unit, and refrigerant piping network between
the blower coil and the condensing unit.
Page 2 of 4
B)
Condensing Unit
Condensing unit shall be of the air cooled type completely assembled at the factory and
shall consist of the following:
-
C)
PART 3 - EXECUTION
A.
EXAMINATION
1.
Examine Conditions at the job site where work of this section is to be performed to
insure proper arrangement and fit of the work. Start of work implies acceptance of job
site conditions.
B.
PREPARATION
1.
Examine the Contract Drawings and specifications in order to insure the completeness
of the work required under this Section. Provide supplementary parts necessary to
complete all insulation work, though not specifically indicated or specified herein.
2.
Verify all measurements and dimensions at the job site and cooperate in the
coordination and scheduling of the work of this section with the work of related trades,
so as not to delay job progress.
C.
INSTALLATION
1. Install mini-split units in accordance with manufacturer's installation instructions.
Install units plumb and level, firmly anchor in locations indicated and maintain
manufacturer's recommended clearances.
Page 3 of 4
3.
Electrical Wiring
a.
Turn over to Electrical Contractor devices furnished by manufacturer but not specified
to be factory-mounted. Furnish copy of manufacturer's wiring diagram submittal to
Electrical Contractor.
b.
4.
Drain Piping - Connect unit drain to nearest indirect waste connection. Provide trap at
drain pan, construct at least 1 inch deeper than fan pressure in inches of water.
D.
1.
Startup units, in accordance with manufacturer's startup instructions. Test controls and
demonstrate compliance with requirements. Replace damaged or malfunctioning
controls and equipment.
E.
DEMONSTRATION
1. Provide services of manufacturer's technical representative for one-half day to
instruct Employer's personnel in operation and maintenance of packaged cooling
units.
a. Schedule training with Employer, provide at least 7-day notice to Contractor and
Engineer of training date.
b. Provide operating and maintenance manuals as approved.
END OF SECTION 15860
Page 4 of 4
PART 1 - GENERAL
1.01 SCOPE OF WORK
The contractor shall supply and install all the control equipment, auxiliary devices, instruments,
etc. to perform satisfactory operations of all systems described in the specifications and/or
indicated on the drawings. The drawings and the specifications are complemented each to the
other. The sequence of operation of each system or piece of equipment is specified either
under the equipment specification section or detailed on the drawings.
1.02 QUALITY ASSURANCE
Materials shall conform to the latest edition of industry standards and reference specifications
specified herein and to applicable codes and requirements of local authorities having
jurisdiction, whichever is more stringent. Controls shall comply with NFPA and shall be UL
Listed and certified.
1.03 SUBMITTALS
Submit the following in accordance with the requirements specified under Submittals in
Section 15010.
1.
Product Data: Submit names of manufacturer and copies of latest published literature
including types, applications and thermal characteristics for materials specified herein
for approval; obtain written approval before ordering materials.
2.
Samples: Submit samples of materials specified herein for approval; obtain approval
before ordering materials.
B.
Deliver materials and handle to prevent the inclusion of foreign materials and the
damage of materials by water or breakage.
C.
Store materials and equipment where designated and within the manufacturer's
recommended temperature range. Assume responsibility and security for materials and
equipment and take precautions for protection from detrimental conditions.
Provide all relays, switches, gauges, sources of electricity and all other auxiliaries,
accessories and connections necessary to make a complete operable system.
Page 1 of 13
Unless otherwise noted, install all wall mounted thermostats 1400 mm above the floor,
measured to the center line of the instruments.
Insertion type thermostats shall have adjusting head at eye level, wherever practicable,
for adjustment and calibration.
Install all control valves horizontally with the power unit up.
Provide positive positioner devices on all controls operated in sequence and/or where
specified or required to maintain the set point within the required limits without
override.
After completion of installation, all automatic controls shall be regulated and adjusted
and placed in complete operating conditions subject to the approval of the Engineer and a
maintenance brochure including all operating instructions, specifications and sheets for
all instruments shall be submitted by the Contractor.
Electric control systems shall conform to the requirements shown on the Drawings and
shall effect the operation of the air conditioning systems contemplated by the design.
After all controls, valves and motors have been connected, test the systems in the
presence of the Engineer to demonstrate the capability of each automatic control system
to meet contract requirements.
Instrument wire shall be run in conduits separate from other types of wiring and shall
terminate on identified terminal strips.
The wire terminals on instruments shall not be used as junction points to facilitate
removal of instruments without disturbing others.
Instruments shall have laminated plastic name tags with tag numbers and service
engraved on the tag. Tags shall be securely fastened to the instrument. Tags shall be
black with white lettering.
The equipment shall be restarted after a power failure in the same sequence and with the
same time delays as specified for normal start-up.
Page 2 of 13
PART 2- PRODUCTS
2.01
DESCRIPTION OF OPERATION
.
A.
Heat Exchanger
1.
C.
Immersion temperature sensor located in the heat exchangers inlet and outlet pipe
at the AHU side and at the cooling plant side shall sense the water temperature and
end the relevant measurements to the PLC controller in order to modulate the flow
coming from the cooling plant accordingly.
D.
2.02
2.03
Page 3 of 13
Manufacturer's detailed Shop Drawings, specifications, and data sheets for all
equipment to be furnished shall be submitted to the Engineer for approval.
2.04
CONTROL DEVICES
A)
floor and in an
Panel-mounted controllers shall be supplied with metal mounting adaptor plate and
mounting assembly.
Controllers shall be designed for a throttling range of 2 oF (1 oC) for a 3Vdc
output change with a control dial range 55- 85 oF (13-29 oC) and shall be suitable for
ambient operating limits 40-135 oF (4-57 oC).
B)
Dampers
-
Motorized automatic dampers shall be of the louver type with not less than 13
gauges welded steel frames and galvanized finish. Blades shall have
interlocking edges, stainless steel side springs (or vinyl or neoprene gaskets),
and Teflon-coated stainless steel thrust washers. Blades shall be edged with
neoprene if the damper is to operate in outside air service either as an intake
or discharge damper. Damper blades shall have steel trunnions mounted in
nylon or oilite bearings.
C)
Provide parallel blade dampers arranged for maximum turbulance and mixing
of outside air with return air. Arrange dampers as necessary to prevent
stratification or provide baffles necessary to correct stratification problems.
Temperature Sensors
Duct temperature sensors shall have their sensing elements immersed inside the duct
and the wiring enclosure mounting on the outer surface of the duct and shall be of the
Page 4 of 13
averaging duct type with linear output and suitable for ambient limits -40 to 250 oF (40 to 120 oC).
Sensor shall be complete with a steel wiring enclosure with 1/2" (13mm) conduit
knockout (top and bottom) and a 5 feet (1.5m) long sensing element.
Sensors shall be of corrosion proof construction.
Sensing elements for water pipe mounting shall be of the rod and tube type with
linear output and shall be furnished complete with separable stainless steel bulb wells
filled with heat conductive compound. Sensors shall be factory calibrated and
tamperproof. If easily adjustable sensors are provided, they shall be located inside
metal enclosures with cylinder lock and key to prevent unauthorized setting.
D)
Room Thermostats
-
Shall have metal locking covers and shall be provided with concealed
adjustment means, and with thermometers.
Each room thermostat shall be supplied with metal auxilliary mounting bases
and metal subbase for surface mounting applications; plus a plastic guard to
protect thermostat from damage.
E)
Line voltage on/off thermostats shall be of the bimetal operated snap action
switch. They shall be underwriters' laboratories inc., listed at an electrical
rating appropriate to the application. Thermostat shall operate on 2 oF (1 oC)
differential and shall have a control dial range 55-85 oF (13-29 oC).
Low voltage thermostats shall be of the self contained type with a 1000 ohm
sensing element and an amplifier. Thermostat shall have a control dial range
55-85 oF (13-29 oC) and a throttling range of 2 oF (1 oC) for a 3 Vdc output
change.
Page 5 of 13
G)
Return Air Duct Thermostat and Temperature Controllers Type T-2: to provide line
voltage, proportional control of damper or valve motor through sensing element and
capillary adjusting potentiometer in proportion to temperature variations. To have the
following features:
-
liquid filled, fast response coiled capillary element for duct applications or
sensing bulb with immersion well components for chilled and heating water
pipes applications
Sequence Controller Type SC-1: to provide sequence control for multiple water chiller
units or multiple boiler units according to the preset temperatures and provide
programmed permutations for lead / lag chillers or boilers for equal use.
Advanced proportional plus derivative microprocessor control algorithm, with the
required number of steps for 3 water chiller units and for 2 water boiler heating units.
To be used with electronic temperature sensors.
H)
Sensors
1.
2.
Page 6 of 13
Low Limit Thermostat and Temperature Controller Type T-3: to provide line voltage,
on-off control of damper or valve by sensing temperature of air in duct or liquid
through spdt switch. To have the following features:
liquid filled, fast response coiled capillary element for duct applications and sensing
bulb with immersion well components for pipe applications
J)
1.
Motorized Valves Type A: low voltage, 3-way, mixing, proportional reversing type,
providing modulating control of water by-pass flow through operation of motor
actuator and valve linkage in response to signal from proportional controller. To have
the following features:
2.
valves 15 mm to 50 mm sizes, with two inlets and one outlet screwed end
connections, cast bronze body, stainless steel stem, brass plug, integral brass
seat and spring loaded, self-adjusting, Teflon cone packing
valves 65 mm and larger, with two inlets and one outlet flanged end
connections, cast iron body, stainless steel stem, brass plug, replaceable bronze
seat and spring loaded, self-adjusting, Teflon cone packing
reversing type motor, oil-immersed gear train, die-cast aluminum case, single
160 degree stroke, double-ended crankshaft, die-cast aluminum cover with
built-in transformer and direct drive feedback potentiometer
valve rated 250 deg. F maximum water temperature and 150 psi maximum
water pressure
Page 7 of 13
Motorized Control Valve shall be low voltage, 2-way, 2-position, providing openclosed control of water flow through operation of motor actuator and valve linkage in
response to signal from an on-off switch. To have the following features:
3.
reversing type motor, with oil-immersed gear train, die- cast aluminum case,
dual-stroke (90 and 160 degrees), double-ended crankshaft and die-cast
aluminum cover with built-in transformer
valve rated 240 deg. F maximum water temperature and 125 psi maximum
pressure for flanged end connections and 150 psi for screwed end connections
Valve shall be sized to produce a full flow pressure drop approximately 1.5
times the full flow pressure drop of the unit by-passed, unless noted
otherwise.
Valve shall be selected to withstand system pressure and operate at the selected
pump pressure at no additional cost.
Electric, 2-way, 2-position valve (where shown on drawing valve shall be 3way motorized on/off type)
Valve shall be sized to produce a full flow pressure drop approximately 1.5
times the full flow pressure drop of the unit by-passed, unless noted
otherwise.
4.
Valve shall be selected to withstand system pressure and operate at the selected
pump pressure at no additional cost.
Control Motor (Actuator)
Page 8 of 13
5.
K)
1.
General
Mount pressure gauges directly at the sensing point unless otherwise indicated.
Select the instrument so that the normal range of operating temperatures and
pressures falls within the middle-third of the instrument range. Use compound gauges
when normal operating pressure is near or below atmospheric.
Locate temperature sensing devices in a portion of the fluid stream where it will
measure the average fluid temperature without obstructing flow. Increase pipes 1
1/2" (40 mm) in diameter and smaller at least one pipe size at the point of insertion.
Where thermometer sensing bulbs are inserted in air ducts or casings, provide
perforated bulb housing with a 3" (80 mm) diameter union flange to permit removal.
Connections for sensing elements are to be brass except where otherwise specified.
Provide all thermometers in piping systems with stainless steel wells and 3/4" (20
mm) seperable sockets.
Provide extension necks where thermometers and pressure gauges are located in
insulated piping, vessels, ductwork, casings or equipment.
All thermometers and gages shall have both english and metric units gradings.
Page 9 of 13
2.
Thermometers
Permanently installed thermometers shall be mercury-in-steel dial type 150mm
diameter having a suitable length of copper covered steel capillary tubing to connect
the dial with the bulb, shall be supplied and installed as specified and as approved
by the Engineer. Each thermometer shall be provided with back flange or arranged
for flush mounting.
Mercury-in-glass type thermometers with metal guard shall be supplied and
installed as specified or as approved by the Engineer.
Unless otherwise specified, thermometer bulbs shall be of steel type, screwed 3/4"
(20mm) British Standard pipe and supplied with stainless steel separable pockets
suitable for screwing, brazing or welding into the pipe carrying the medium to be
measured.
Thermometers shall be tested to read alike on the midscale band, with their bulbs
immersed in water, and the discrepancy between the highest and the lowest
thermometer shall not exceed 0.5 oC.
A red mark on each thermometer scale shall indicate the working temperature at the
point of measurement.
Thermometers shall be marked in both Degree C and Degree F.
3.
Pressure Gauges
Bourdon-tube type with 120 mm. diameter cast aluminium case with moistureproof and dustproof blowout discs. Panelmounted gauges to have steel or aluminium
hinged rings; direct mounted gauges to have back flange, black numerals on a white
background face.
Pressure gauge shall be furnished with a lever-operated gauge cock, and shall have
snubbers installed between the gauge cock and the gauge to eliminate pulsations.
Bourdon Tube shall be Phosphor bronze, (beryllium copper bellows).
Socket shall be Stainless steel.
Accuracy shall be at least 1% of scale range , range shall be equal to twice the rated
working pressure of the unit ( pumps, chillers,....) reading shall be in psi. and Kpa.
Gauges for combined pressure and vacuum service to have compound seal.
4.
Page 10 of 13
Air flow test points shall be provided in the air ducting at all branches and
regulating dampers adjacent to each plant item and automatic control element at
all fan inlets and discharges and elsewhere as required.
Test points shall consist of a 40mm. diameter hole drilled through the ducting and
covered with a removable spring clip fastened cover.
5.
6.
7.
Indicators shall be provided for all air filter units on air handlers and main
fresh air louvers. The indicators shall be spirit or moving vane type suitably
calibrated and provided with flexible pressure tubes to a test point on each side
of all 'roughing' and 'fine' filters.
The position on the gauge dial at which the filters require cleaning or changing
shall be clearly marked.
Water flow switches shall be of the paddle type electric as manufactured by the
McDonnell and Miller Company. Those flow switches used in chilled water
applications shall be of the vaporproof type to prevent condensation on the
electrical switch.
Paddles shall be properly trimmed for the pipe sizes in which they are
installed. The flow switches shall be installed in accordance with
manufacturer's recommendations regarding locations in horizontal piping and
proper distance from fittings.
Firestats
Provide manual reset firestate for each fan of 750 cfm (0.35 m3/sec) or larger
capacity, to stop the fan on rise above set point temperature 136 oF (58 oC).
8.
9.
Freezestats
-
Provide a freezestat for each water coil subject to freezing to protect coil by
deenergizing the supply fan when triggered.
Smoke Detectors
Supply and install smoke detectors as shown on the Electrical drawings and as
required by NFPA code.
Smoke detectors shall be as specified under the Fire Alarm System section of the
specifications.
Page 11 of 13
Smoke detectors shall be supplied complete with the necessary power relays and
control wiring to perform the proper operations and function specified. Smoke
detectors shall be connected to the fire alarm system with independent zoning
designated on the fire alarm control panel.
10.
Ammeters
One 100 mm dial ammeter shall be supplied for each motor 10 HP (7.5KW) or
larger, and for all electrical apparatus fed from the control panel. Ammeter shall be
red lined at the normal running load.
11.
Voltmeters
One 150 mm dial voltmeter shall be supplied to indicate the voltage of the motor
control center in each Plant-Room.
The Voltmeter shall be complete with a seven-position, rotary switch to enable
reading the voltage between all phases and neutral.
12)
L)
The system shall basically consist of but not limited to the required number of
remote carbon monoxide detectors, transmitters and multiple centralized
control panels. The number of centralized control panels shall be dependent on
the maximum allowable distance between sensors, transmitters and panels.
b.
The central panels shall incorporate the required number of modules connected
to remote sensors. Modules shall be fully electronic incorporating solid state
circuitry, microprocessor based control, with decontamination sequence to
periodically remove water vapour and other contaminants from the sensor
elements surface.
The panel shall incorporate all the necessary logic circuits to operate the 2
speed exhaust fans as per the control diagram shown on the drawings.
Page 12 of 13
c.
Supply and install a carbon monoxide central detection and control system as specified
herein and as shown on drawings:
d.
Each module on the central panel shall have the following indications:
-
2.05
Low level
High level
Alarm
Fault
Power on
e.
f.
The system shall be provided complete with all wiring, conduits, contactors,
relays, transformers, circuit breakers, etc.... necessary for proper operation of
the system.
HARDNESS MONITOR
Hardness monitor installed on soft water blending valves shall be capable to read the
hardness of the water after blending zero ppm soft water with ordinary water to
produce 30 ppm soft water. The hardness monitor shall readjust automatically the 3way motorized mixing valve in order to result with a 30 ppm soft water.
The hardness monitor shall be of the high range type 5 to 100 mg/L. Alarm points
shall be expressed in mg/L of CaCo3 with an easy to read LED indicator with built in
alarm relay to actuate an external annunciator. Monitor shall be complete with power
cord kit with strain relief. The hardness monitor shall continuously sample water
every two minutes thru pump and necessary tubing and automatically control the
mixing process. Hardness monitor shall be HACH Model SP 510 or approved equal.
Power supply 240 V/ 1 PH/ 50Hz.
END OF SECTION
Page 13 of 13
FIRE DAMPERS
SECTION 15910
PART 1 - GENERAL
1.01
DESCRIPTION OF WORK
Extent of Work: The extent of fire dampers work is shown on drawings and by the
requirements of this section.
1.02
QUALITY ASSURANCE
A.
B.
C.
UL Labels: Provide units which have been approved and listed by Underwriters'
Laboratories (UL) and bear the UL Label, for 1 1/2 hour fire rating unless otherwise
indicated.
D.
NFPA code: Comply with National Fire Protection Association (NFPA) No. 90A,
"Standard for the Installation of Air Conditioning Ventilating Systems" pertaining to
fire dampers.
E.
NEC Code: Comply with National Electrical Code (NFPA No. 70), as applicable to
installation of electrical smoke detection and activation devices.
F.
Industry Standards: Comply with SMACNA (Sheet Metal and Air Conditioning
Contractors' National Association, Inc.) recommendations for fabrication,
construction and installation procedures as contained in applicable guides and
manuals on fire dampers and low velocity and high pressure ductwork.
1.03
SUBMITTALS
Submit manufacturer's data on fire dampers together with dampers fire rating
certifications.
PART 2 - PRODUCTS
2.01
Page 1 of 5
Dampers shall be tested, rated and labeled in accordance with UL 555 Standards (Sixth
Edition). Dampers shall have a UL555 fire rating of 1 hours.
Damper blades shall be roll formed 22Gauge galvanized steel interlocked between each
other folding in a curtain. Blades shall be held open (in the air stream or out of the
air stream) depending on the size of the fire damper and the calculated friction loss)
by a heat responsive device (fusible link) melting at a temperature rating of 165F,
212F or 285F according to the application.
If the closing of the fire damper should be controlled by the fire alarm or the building
management system an electro-thermal fusible link should be used.
Damper frames shall be roll formed 22Gauge galvanized steel with reinforced corners.
Fire damper should be equipped with a closure spring to ensure correct operation
regardless of whether the damper is horizontally or vertically mounted.
Fire damper should be equipped with a factory-mounted sleeve; the type of sleeve
should be selected according to the application.
For partition less than 4 or for wood partition, a thin type fire damper should be used
with the same specification as the normal fire damper.
Contractor should follow the installation instruction of the manufacturer.
2.02
Page 2 of 5
Damper actuators, spring return, UL listed, shall be factory mounted and shall be
electric type for 240,120 or 24 volts operation (depending of the control system).
Manufacturer's submittal data shall indicate actuator space requirements around the
damper.
Contractor should follow the installation instruction of the manufacturer.
2.03
SMOKE DAMPER.
Smoke Dampers meeting the following specifications shall be furnished and installed
where shown on plans and/or as described in schedules. Dampers shall meet the
requirements of NFPA 90A, 92A, and 92B.
Dampers shall be tested, rated and labeled in accordance with the latest edition of UL
Standards 555S (Forth Edition). Dampers shall be UL labeled for use in dynamic
systems. The damper shall have a dynamic closure airflow rating equal to or greater than
the airflow at the damper's installed location and a dynamic closure pressure rating of
4Wg.
Dampers shall have a UL555S Leakage rating and a Temperature rating of 250F.
Dampers shall have a UL555S operational airflow rating equal to or greater than the
airflow at its installed location and an operational pressure rating of 4Wg.
Damper actuators shall be factory mounted and qualified for use with the damper in
accordance with UL555S. Damper actuators, spring return, UL listed, shall be electric
type for 240,120 or 24 volts operation (depending of the control system). Manufacturer's
submittal data shall indicate actuator space requirements around the damper.
All UL555S Dynamic Closure Ratings, Operational Ratings and Leakage Ratings shall
be qualified for airflow and pressure in either direction through the damper. UL ratings
shall allow for mounting damper vertically (with blades running horizontal) or
horizontally.
Damper air performance data shall be developed in accordance with AMCA Standard
500-D.
Damper blades shall be 16Gauge galvanized steel 3 V type with three longitudinal
grooves for reinforcement. Blades shall be linked together with external linkage (out of
air stream). Blade shall have a stainless steel or fire rated silicon blades seal to provide
airtight seal between two blades.
Damper frames shall be 16Gauge galvanized steel formed into a structural hat channel
shape with reinforced corners. Bearings shall be sintered bronze, oil impregnated type
rotating in extruded holes in the damper frame. Jamb seals shall be stainless steel
compression type to provide airtight seal between blades and frame.
2.04
Page 3 of 5
Dampers shall be tested, rated and labeled in accordance with the latest edition of UL
Standards 555 (Sixth Edition) and UL 555S (Forth Edition). Dampers shall have a
UL555 fire rating of 1 hour. Each damper shall be equipped with a heat responsive
device, which has been tested and approved, for use with the damper assembly in
accordance with UL555. The heat responsive device shall have a temperature rating of
165F, 212F. Dampers shall be UL labeled for use in dynamic systems. The damper
shall have a dynamic closure airflow rating equal to or greater than the airflow at the
damper's installed location and a dynamic closure pressure rating of 4Wg.
Dampers shall have a UL555S Leakage rating and a Temperature rating of 250F.
Dampers shall have a UL555S operational airflow rating equal to or greater than the
airflow at its installed location and an operational pressure rating of 4Wg. Damper
actuators shall be factory mounted and qualified for use with the damper in accordance
with UL555S. Damper actuators, spring return, UL listed, shall be electric type for
240, 120 or 24 volts operation (depending of the control system). Manufacturer's
submittal data shall indicate actuator space requirements around the damper.
All UL555 and 555S Dynamic Closure Ratings, Operational Ratings and Leakage
Ratings shall be qualified for airflow and pressure in either direction through the
damper. UL ratings shall allow for mounting damper vertically (with blades running
horizontal) or horizontally.
Damper air performance data shall be developed in accordance with the latest edition
of AMCA Standard 500-D.
Damper blades shall be 16Gauge galvanized steel 3 V type with three longitudinal
grooves for reinforcement. Blades shall be linked together with external linkage (out of
air stream). Blade shall have a stainless steel or fire rated silicon blades seal to provide
airtight seal between two blades.
Damper frames shall be 16Gauge galvanized steel formed into a structural hat channel
shape with reinforced corners. Bearings shall be sintered bronze, oil impregnated type
rotating in extruded holes in the damper frame. Jamb seals shall be stainless steel
compression type to provide airtight seal between blades and frame.
Contractor should follow the installation instruction of the manufacturer.
PART 3 - EXECUTION
3.01
INSTALLATION
A.
General: Install fire damper products in accordance with the manufacturer's written
instructions and in accordance with recognized industry practices to ensure that
product serve the intended function. Comply with applicable portions of NFPA's
Installation Standard 90A.
B.
Page 4 of 5
C.
Damper Access Doors: Refer to Section 15860 for installation of damper access
doors in ductwork.
3.02
3.03
PERSONNEL TRAINING
Fire Damper Maintenance Training: Train employer's personnel (maintenance
persons) by demonstrating to them how to visually inspect and test damper operation
and how to reset frangible and fusible link assemblies, and how to replace used links.
END OF SECTION
Page 5 of 5
SECTION 15976
BUILDING MANAGEMENT SYSTEM (BMS)
PART 1
1.01
A.
1.02
A.
GENERAL
RELATED DOCUMENTS
Drawings and general provisions of Contract, including General and the Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
WORK INCLUDES
fully integrated building management system (BMS), UL listed, incorporating direct
digital control (DDC) for energy management, equipment monitoring and control,
including color graphic workstations. System major elements include, without being
limited to, the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
1.03
A.
RELATED WORK
The following Sections contain requirements that relate to this Section:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10
11.
12.
13.
14.
15.
16.
17.
18.
Page 1 of 56
19.
20.
21.
22.
1.04
A.
SCOPE OF WORK
General: all materials and/or equipment, necessary for proper operation of the systems,
not specified or described herein are to be deemed part of the Specification. Perform the
work under this section and provide all labour, materials, services, equipment and
accessories necessary to furnish and install all instrumentation and equipment as
indicated by the Drawings and/or as required by the Specification, which without limiting
the generality thereof, consists of the following:
1.
2.
3.
4.
5.
6.
7.
8.
1.05
A.
SYSTEM DESCRIPTION
Building Management System: Distributed process control system consisting of central
control, central communications, and remote control systems to monitor and control the
following building systems:
1.
2.
3.
4.
5.
6.
7.
8.
9.
Page 2 of 56
B.
C.
D.
Central Control System: Configure central processing units, mass memory units, data
terminal units, and related software to perform the following functions:
1.
Develop, store, access, and update building management data base.
2.
Provide human operator interface with system.
3.
Display and record system operation.
4.
Provide central monitoring and automatic control of building systems.
Central Communication System: Configure central communication units, data
communication network, and related software to control input and output between central
control system and remote control system.
Remote Control System: Configure remote control units, data interface units, input
sensing devices, and output control elements to perform the following functions:
1.
2.
3.
4.
5.
6.
7.
8.
E.
2.
3.
4.
F.
Process variable sensing, signal transmitting, and signal conversion for each input
point.
Signal conversion, transmitting, and operation of control drive or other element for
each output point.
Receive remote control programs and system data from central communication
system.
Manual entry of remote control programs.
Storage of data and remote control programs.
Execute remote control program commands.
Transmit local status data to central communication system.
Execute commands received from central communication system.
Definitions
1.
2.
3.
4.
Page 3 of 56
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
Control Wiring: This includes conduit, wire, and wiring devices to install
complete HVAC control systems, including motor control circuits, interlocks,
sensors, PE and EP switches, and like devices. This also includes all wiring from
node to node, and nodes to all sensors and points defined in the I/O summary
shown on drawings or specified herein, and required to execute the sequence of
operation. Does not include line voltage power wiring.
Diagnostic Program: Machine-executable instructions used to detect and isolate
system and component malfunctions.
Distributed Control: A system whereby all control processing is decentralized and
independent of a central computer.
Gateway: A device that contains an input/output (I/O) software driver to translate
input data from one format to output data in a second format.
Human-Machine Interface (HMI): Human-machine interfacing allows the operator
to manage, command, monitor, and program the system.
HVAC Control Systems: The complete LONWORKS control system, comprising
the user interface and routers, gateways, repeaters, nodes, the operator workstation,
software, portable operator terminals, network communications wiring and
raceways, and required field hardware, etc.
Integration: Establishing communication between two devices through the use of a
gateway.
Interoperable: Establishing communication between two devices through the use
of a common protocol and without the use of any gateways.
LonTalk: Open communication protocol developed by the Echelon Corporation.
LONWORKS: The overall communications technology for control systems
developed by Echelon Corporation. The technology employs routers, gateways,
bridges, and multimedia transceivers to permit topology and media- independent
control solutions.
LONMARK Interoperability Association: Standards committee consisting of
numerous independent product developers and systems integrators dedicated to
determining and maintaining the interoperability guidelines for the LONWORKS
industry.
LonMarked - device has been certified for compliance with LonMark standards
by the LonMark association.
LONWORKS Application Specific Nodes (LASN) - a networked device or node
that contains a complete, configurable application that is specific to a particular
task.
LONWORKS Programmable Nodes (LPN) - a programmable control product that
incorporates solid state components based upon the Neuron chip to perform
control loops or functions. The application in the controller is custom software
produced by the integrator specifically for the project.
LONWORKS Single Point Nodes (LSPN): devices such as temperature and
humidity sensors, that have an on-board Neuron microprocessor and network
interface allowing them to communicate on the LONWORKS network.
Network: A system of distributed control units that are linked together on a
communication bus. A network allows sharing of point information between all
control units. Additionally, a network provides central monitoring and control of
the entire system from any distributed control unit location.
Node: A LonWorks device with a neuron chip and LonTalk transceiver.
Operating System (OS): Software which controls the execution of computer
programs and which provides scheduling, debugging, input/output controls,
accounting, compilation, storage assignment, data management, and related
services.
Operator Workstation (OW): The OW consists of a high-level processing personal
computer that provides graphic user interface to network.
Page 4 of 56
24.
25.
26.
27.
28.
1.06
A.
1.07
A.
Design central processing unit with modular system architecture to allow expansion of
processor memory and addition of application software programs, terminal units, and
central memory units.
B.
C.
D.
Operator Data Terminal Unit: Provide operator interface functions through data terminal
unit, including manual setpoints and overrides, data base display and maintenance,
program loading and entry, operating system software functions, alarm display and
acknowledge, graphic display, and operation logging.
E.
Design operator display terminal data screens with the following features:
1.
2.
3.
F.
Split screen display to allow entering commands and variables while observing
status and alarm screen.
Provide constant display of date, time, outside environmental conditions, and
system status.
Indicate off-normal conditions in a flashing display.
Page 5 of 56
G.
Layout data terminal units to allow operator to view displays, acknowledge system
alarms and messages, manually enter data or commands, and communicate over
telephone or intercom systems from one seated position.
H.
I.
Design central communication system to control input and output between central
processing unit, data memory units, remote control units, and data gathering units.
1.
2.
3.
4.
5.
J.
K.
Signal inputs.
Control outputs.
Data and program memory.
Independent control and monitoring of local processes during failure of central
control or central communication systems.
Design and build all system components to be fault-tolerant.
1.
2.
3.
4.
5.
6.
L.
1.08
A.
Satisfactory operation without damage at 110% and 85% of rated voltage and at plus
3 Hertz variation in line frequency.
Static, transient and short-circuit protection on all inputs and outputs.
Protect communication lines against incorrect wiring, static transients and induced
magnetic interference.
Network-connected devices to be A.C. coupled or equivalent so that any single
device failure will not disrupt or halt network communication.
All real time clocks and data file RAM to be battery-backed for a minimum 72 hours
and include local and system low battery indication.
It must be possible to receive and print out alarms at a central location even when the
workstation at that location is non-operational or taken out of service for periodic
maintenance.
Design system to continue operation of alarm display and printing at central location and
operation of remote control unit functions during removal or failure of central processing
unit.
QUALIFICATIONS
Manufacturer and installer to have an office staffed with factory trained engineers and
technicians fully capable of providing instructions, routine maintenance and emergency
maintenance service on all system components.
Page 6 of 56
B.
C.
Supplier to have an in-place support facility within 250 km of the site with, spare parts
inventory and all necessary test and diagnostic equipment.
1.09
A.
REGULATORY REQUIREMENTS
All electronic equipment shall conform to the requirements of FCC Regulation, Part 15,
Section 15, Governing Radio Frequency Electromagnetic Interference and be so labeled.
BMS shall comply with UL 916 PAZX and 864 UDTZ or ETL LonMarkTM and be so listed at
the time of bid. All equipment used in system is to bear appropriate UL listing label/mark
to ensure compliance.
C.
The DDC system manufacturer shall provide documentation supporting compliance with
ISO-9000 certification mark from applicable registrar.
D.
Unitary controllers, intelligent sensors, and intelligent actuators shall comform to the
appropriate LonMarkTM functional profile configurations based on intended use and shall
be so labeled.
1.10
QUALITY ASSURANCE
A.
General: maintain a complete test, inspection and documentation program covering all
phases of construction and implementation of the instrumentation and control systems.
Also maintain an engineering assurance program throughout final design and equipment
selection phases of the project. Quality control and engineering assurance programs to be
fully documented in a project procedures manual which is to be submitted for approval.
B.
Project procedure manual is to detail, but is not necessarily limited to, the following:
1.
2.
3.
4.
5.
6.
7.
C.
Start up procedures: portions of the manual may be equipment dependent such as start up
procedures. In such cases submit these portions in accordance with the requirements of
sub-section SUBMITTALS. However, selection criteria, design standard, and installation
standards to be established and approved before detailed design starts.
D.
Inspection: the Engineer has the right, at all times, to inspect the work, piping material,
equipment, or quality assurance procedures as applicable to confirm that requirements as
set forth are being complied with. Provide all tools, instruments and equipment necessary
to facilitate these inspections.
E.
Inspection: cooperate with the Engineer in establishing when the various inspections or
tests will be performed during progress of the work.
Page 7 of 56
F.
Obligations: the presence or activities of the Engineer are in no way to relieve the
Contractor of his obligations.
G.
Inspection duties assigned to the Contractor's personnel are to include, but are not limited
to, the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
1.11
A.
verify that all non-destructive testing personnel are qualified for the work being
done
verify that all components received comply with the Specification and receipt,
inspection and storage of materials comply with requirements of the Specification
verify that the Contractor's storage facilities are maintained
verify that rack wiring check and electrical continuity tests are conducted in
accordance with the Specification
witness that all hydrostatic tests performed on instrument sensing lines are in
accordance with the Specification and that all tests are properly filled in signed and
submittal for approval
witness all pneumatic leak tests performed on instrument sensing lines and
pneumatic tubing required by the Specification
verify that all wiring insulation tests are performed in accordance with the
Specification and that all test reports are properly filled in, signed and submitted
for approval
verify that assembly and nameplates of the transmitter racks are in accordance with
the Specification
verify that all racks, panels and local instruments have been located in accordance
with the Specification
verify that all tubing supports are in accordance with the Specification
verify that all tubing has been installed in accordance with the Specification
verify that all repairs and revisions to instrument components and assemblies are in
accordance with the Specification
verify that all repairs and revisions to instrumentation, tubing and their components
is in accordance with the Specification
inspect in detail the tubing system or portions of the system as completed to verify
that system or portion of system is correct and complete as specified prior to the
initiation of any flushing, hydrostatic test, or leak test opera
witness the construction loop inspection performed by the Contractor. All items
control components to conform to the specification requirements and drawings.
Equipment and components to be undamaged as determined by visual examination.
All documentation as required to be complete and on file. Construction loop
inspection, as performed, to comprehensively
and conclusively prove
completeness and conformity of the installation to the Drawings and Specification
verify that calibration of instrumentation and control loops is in accordance with
the approved procedures as submitted in the project procedures manual
witness the calibrated loop check and verify that all calibration reports are properly
filled in, signed and submitted for approval
witness the system operational tests on a sub-system basis to assure operational
integrity and conformance to operational requirements as specified
verify all plant documentation required for plant acceptance is in accordance with
sub-section SUBMITTALS for completeness and conformance.
TECHNICAL PROPOSALS
Technical proposals shall be prepared in accordance with these specifications. Three
copies of the proposal shall be submitted. The technical proposal shall include the
following data/information as a minimum. The order of listing here is not intended to
Page 8 of 56
4.
5.
6.
7.
B.
C.
1.12
SUBMITTALS
A.
B.
C.
Product Data: Provide for each component, including sensors, control drives and
elements, plug-in circuit boards, and enclosed equipment units. Include cabinet
dimensions, weights, and support point locations for each item of enclosed equipment.
D.
E.
F.
G.
Submit software provider's license agreement stating limits on use, copying, and
transferring software.
I.
Page 9 of 56
J.
Where installation procedures, or any part thereof, are required to be in accord with the
recommendations of the manufacturer of the material being installed, printed copies of
these recommendations shall be furnished to the Engineer prior to installation.
Installation of the item will not be allowed to proceed until the recommendations are
received.
K.
P & I or process flow diagrams: to be completed for each system and submitted for
approval. Instrument symbols and identification to be in accordance with ISA-S5.1.
L.
Technical Data Sheets: control and instrumentation technical data sheets (TDS) to be
prepared for each device. TDS to be similar to and meet the intent of ISA-S20, 1975.
M.
Loop Diagrams: control and instrument loop diagrams prepared and furnished for all
instrument systems. Typical diagrams are not permitted. Loop diagrams are to be unique
for each loop.
N.
P.
Operating Consoles: drawings detailing operating consoles, instrument panel layouts and
dimensions and control room plans.
Q.
Instrument Installation: detail drawings for each field installation are to be furnished.
Details are to include but are not limited to instrument piping details, transmitter rack
details and pipe mounted equipment installation details.
R.
Logic Diagrams detailing the operational logic are to be completed for the digital binary
operations. In addition to these drawings, operational logic descriptions are to be
prepared detailing the sequence of operation and operational constraints and limitations.
These drawings are to be in conformance with ISA-S5.2, 1976. Submit details for each
primary and secondary processing units separately, in addition to logic diagrams relating
Central Control Room processing functions and resulting operations.
S.
Instrument Schedule listing all devices to be keyed to instrument loop number and device
numbers. Schedule to be submitted in two (2) formats; first, in an alpha-numeric listing
by device type and second, a listing with equipment grouped by loop number. Schedule
to contain as a minimum the following information:
1.
2.
3.
4.
5.
6.
7.
8.
T.
Instrument Schedule to provide a comprehensive data source indicating where all specific
information may be found for each service. Schedule to include not only balance of plant
Page 10 of 56
equipment but also that equipment furnished as part of packaged systems and is to be
noted as such.
U.
Prior to procurement of equipment submit for approval the following drawings and
documents:
1.
2.
3.
4.
V.
Prior to start of system installation and construction submit for approval the following
drawings and documents:
1.
2.
3.
4.
5.
6.
7.
W.
X.
Prior to system acceptance and turn-over and as a condition of system acceptance, the
following documents are to be submitted in four copies in accordance with requirements
of Division 1:
1.
2.
3.
4.
5.
Page 11 of 56
6.
7.
8.
1.13
tests and calibration data pertinent to each item installed in the systems.
Password at all levels.
Meets LonMark Interoperability Association Standards.
A.
Deliver, store, protect, and handle products to site under provisioins of the Contract
Documents
B.
C.
Protect products from construction operations, dust, and debris by storing in conditioned
space.
1.14
ENVIRONMENTAL REQUIREMENTS
A.
Do not install products when temperature is not within operating range requirements.
B.
Maintain temperature between 15 and 27 degrees C and relative humidity between 10 and
90 % during and after installation of central control equipment.
1.15
MAINTENANCE SERVICE
A.
Furnish service and maintenance of building management system for one year from Date
of Substantial Completion.
B.
1.16
A.
1.17
SPARE PARTS
As soon as practicable after approval of materials and equipment and, if possible, not
later than 4 months prior to the date of beneficial use, submit spare parts data for each
different item of equipment furnished. Data to include a complete source of supply, a list
of parts and supplies that are either normally furnished at no extra cost with the purchase
of the equipment, or specified hereinafter as EXTRA MATERIALS to be furnished as
part of the Contract; and a list of additional items recommended by the manufacturer to
assure efficient operation for a period of 360 days at the particular installation. The
foregoing is not to relieve the Contractor of any responsibilities under the guarantee
condition.
EXTRA MATERIALS
A.
B.
C.
PART 2 - PRODUCTS
Page 12 of 56
2.01
NETWORKING COMMUNICATIONS
A.
The system architecture shall utilize intelligent distributed control modules, located at
each site, which communicate using ANSI/EIA Standard 709.1-A-1999, LONWORKS
technology communication protocols, in one open, truly interoperable system. The design
of the BMS shall network operator workstations and stand-alone DDC Controllers.
B.
Access to system data shall not be restricted by the hardware configuration of the
Building Management System. The hardware configuration of the BMS network shall be
totally transparent to the user when accessing data or developing control programs.
1.
Operator workstations and DDC Controllers shall directly reside on a network such
that communications may be executed directly between DDC Controllers on a
peer-to-peer basis, directly between workstations and between DDC Controllers
and workstations.
3.
All operator devices shall have the ability to access all point status and application
report data or execute control functions for any and all other devices. Access to
data shall be based upon logical identification of building equipment. No hardware
or software limits shall be imposed on the number of devices with global access to
the network data.
4.
b.
c.
d.
5.
Provide high-speed data transfer rates for alarm reporting, quick report
generation from multiple controllers and upload/download efficiency
between network devices. System performance shall insure that an alarm
occurring at any DDC Controller is displayed at workstations and/or alarm
printers within 5 seconds.
Support of any combination of DDC Controllers and operator workstations
directly connected to the network.
Message and alarm buffering to prevent information from being lost.
Error detection, correction and retransmission to guarantee data integrity.
Synchronization of real-time clocks, to include automatic daylight savings
time updating between all DDC Controllers shall be provided.
6.
Options for connecting the operator workstation shall include connection directly
to the 78kbyte FTT 10 channel, connection to the 1.25 mB high speed bus or
connection to the Ethernet (IP) level.
7.
Page 13 of 56
General
a.
Equip each router and bridge with a network transceiver on each network
port (inbound and outbound) as dictated by the network type (Type 1 - FTT,
Type 2 - TP, Type 3 - PL, Type 4 - LP, Type 5 - RF).
b.
The network router shall be designed to route messages from a segment, subnet, or domain in full duplex communication mode.
c.
Routers shall utilize LonTalk protocol transport, network, session layers to
transparently route messages bound for a node address in another sub-net or
domain.
d.
Routers and repeaters shall be fully programmable and permit a systems
integrator to define message traffic, destination, and other network
management functions utilizing LONWORKS software tool.
e.
The routers and repeaters shall be capable of DIN rail or panel mounting and
be equipped with status LED lights for Network traffic and power.
f.
Provide a minimum of two Neuron 3120 or 3150 processors for use as the
network router communication controller.
2.
Ethernet IP Router
a.
Equip each router with a Ethernet IP communication on one side and a
LonTalk transceiver Type 1 FTT or Type 2 - TP on the other side.
b.
The network router shall be designed to route messages from a segment, subnet, or domain in full duplex communication mode.
c.
On Ethernet IP side, the router shall utilize Ethernet IP protocol transport to
route messages.
d.
On the LonTalk side, the routers shall utilize LonTalk protocol transport,
network, session layers to transparently route messages bound for a node
address in another sub-net or domain.
e.
Routers shall be fully programmable and permit a systems integrator to
define message traffic, destination, and other network management functions
utilizing LonWorks software tool.
f.
The routers shall be capable of DIN rail or panel mounting and be equipped
with status LED lights for Network traffic and power.
3.
Transceivers
a.
Type 1 network transceiver, free topology, twisted pair: Provide a
transformer isolated, twisted pair transceiver capable of mounting directly on
a printed circuit board.
The transceiver shall meet the following
specifications:
b.
Page 14 of 56
D.
Telecommunication Capability:
1.
2.
b.
3.
Operators at dial-up workstations shall be able to perform all control functions, all
report functions and all database generation and modification functions as
described for workstations connected via the network. Routines shall be provided
to automatically answer calls from remote DDC Controllers. The fact that
communications are taking place with remote DDC Controllers over telephone
lines shall be completely transparent to an operator.
a.
b.
E.
Provide all necessary hardware and software for remote communications with all remote
processors, back-up processors and all operator input/output peripheral devices.
Controller hardware for remote communications to be modular. It is to be possible for
each channel to be individually programmed (or re-programmed) for its function and
appropriate baud rate by on-line operator software. Each communications channel to be
fully buffered, and to support asynchronous data transmission and recep. All
communications channels to be able to communicate simultaneously to support the realtime, multi-tasking, multi-user operating syspecified here. Each communication channel
to be dual- trunk fully redundant type; loading to be up to 60% of manufacturer's
recommended limits.
Page 15 of 56
2.02
CENTRAL PROCESSINGS
A.
B.
D.
SPU is to have a 72 hours battery back-up of the data base stored in RAM. Each SPU is
to have the capability to communicate and programme up to 150 zone controllers.
E.
A user friendly programming language is to be used to programme the SPU and the zone
controller connected to it. Further the panel is to have the predefined software listed
below:
-
F.
input points
output points
pulse points
annual schedule
weekly schedule
alarm
controller
totalizer
trend log
zone controller access points
optimized start
system display
user access
scale range
load shed
Zone Processing Unit or Controller (ZPU) to be distributed stand alone DDC controller
for control of various unitary and terminal equipment or controls with built in network
communication for integration into the BMS system. Zone controller is to have flexible
control strategies with user configurable algorithms that reside in a non volatile memory.
Zone controllers are to have a serial port that will allow the connection of electronic
sensors, set point adjustment, overrides at service tools.
Page 16 of 56
G.
Data Dumpings: if SPU OR ZPU memory fails, the operator shall not have to manually
re-enter system data. Necessary hardware and software are to be supplied to:
-
2.03
allow periodic dumping of operator entered data onto another storage media online
reload this data as the operator desires.
Data dumpings are not to interrupt any other system operation (such as operator
input/output, scanning of field hardware, application software execution, etc.)
DDC CONTROLLER
A.
B.
C.
D.
E.
Control processes
Energy management applications
Alarm management applications including custom alarm messages for each level
alarm for each point in the system.
Historical/trend data for points specified
Maintenance support applications
Custom processes
Operator I/O
Dial-up communications
Manual override monitoring
A DDC shall operate totally stand-alone and independent of a central computer for all
specified control applications. Software shall include a complete operating system (OS),
communications handler, point processing, standard control algorithms, and specific
control sequences.
DDC packaging shall be such that complete installation and checkout of field wiring can
be performed prior to the installation of electronic boards. The complete DDC including
power supplies, etc., shall be factory-mounted, wired and housed in a NEMA 1 enclosure
or as required by the location and local code requirements.
The DDC LONWORKS network interface shall be a Type 1 transceiver. A
communication connection shall be provided for attaching POT to node for downloading
and troubleshooting applications.
Page 17 of 56
F.
b.
2.
G.
Analog inputs
1)
4-20 mA
2)
0-10 Vdc
3)
Thermistors
4)
1000 ohm RTDs
5)
PT1000
6)
LG-Ni 1000
7)
PT100
8)
0-20mA
Digital inputs
1)
Dry contact closure
2)
Pulse Accumulator
3)
Voltage Sensing
Direct control of pneumatic and electronic actuators and control devices. Each
DDC Controller shall be capable of providing the following control outputs
without the addition of equipment outside the DDC Controller cabinet:
a.
b.
Analog outputs
1)
0-20 psi
2)
4-20 mA
3)
0-10 Vdc
Each DDC Controller shall have a minimum of 20% spare capacity for future point
connection. The type of spares shall be in the same proportion as the implemented I/O
functions of the panel, but in no case shall there be less than two spares of each
implemented I/O type. Provide all processors, power supplies and communication
controllers complete so that the implementation of a point only requires the addition of
the appropriate point input/output termination module and wiring.
1.
Provide sufficient internal memory for the specified control sequences and have at
least 25% of the memory available for future use.
H.
DDC Controllers shall provide at least two RS-232C serial data communication ports for
operation of operator I/O devices such as industry standard printers, operator terminals,
modems and portable operator's terminals. DDC Controllers shall allow temporary use of
portable devices without interrupting the normal operation of permanently connected
modems, printers or terminals.
I.
As indicated in the point I/O schedule, the operator shall have the ability to manually
override automatic or centrally executed commands at the DDC Controller via local,
point discrete, on-board hand/off/auto operator override switches for digital control type
points and gradual switches for analog control type points. These override switches shall
be operable whether the panel processor is operational or not.
Page 18 of 56
1.
2.
J.
K.
DDC Controllers shall provide local LED status indication for each digital input and
output for constant, up-to-date verification of all point conditions without the need for an
operator I/O device. Graduated intensity LEDs or analog indication of value shall also be
provided for each analog output. Status indication shall be visible without opening the
panel door.
L.
M.
Isolation shall be provided at all peer-to-peer network termination, as was all field point
terminations to suppress induced voltage transients consistent with IEEE Standards 5871980.
N.
In the event of the loss of normal power, there shall be an orderly shutdown of all DDC
Controllers to prevent the loss of database or operating system software. Non-volatile
memory shall be incorporated for all critical controller configuration data and battery
backup shall be provided to support the real-time clock and all volatile memory for a
minimum of 72 hours.
1.
2.
2.04
A.
Upon restoration of normal power, the DDC Controller shall automatically resume
full operation without manual intervention.
Should DDC Controller memory be lost for any reason, the user shall have the
capability of reloading the DDC Controller via the local RS-232C port, via
telephone line dial-in or from a network workstation PC.
start stop push buttons for every AHU & fan motor.
Red-green indicating lamps for every AHU & fan motor
Labels for control devices of every AHU & fan motor
Page 19 of 56
2.05
A.
Scope of Work: The scope of the smoke management remote control panel is to include
all necessary field wiring, cabling, raceways, labelling, etc. from the remote control panel
to all relevant equipment, motor control panels/centers including wiring termination and
labelling at both ends, and coordination with the equipment and motor control
panel/center suppliers to provide all necessary interface devices and installations inside
their equipment.
B.
The DDC Controllers shall have the ability to perform the following pre-tested
control algorithms:
a.
b.
c.
d.
e.
2.
3.
4.
C.
Two-position control
Proportional control
Proportional plus integral control
Proportional, integral, plus derivative control
Control loop tuning
Control software shall include a provision for limiting the number of times each
piece of equipment may be cycled within any one-hour period.
The system shall provide protection against excessive demand situations during
start-up periods by automatically introducing time delays between successive start
commands to heavy electrical loads.
Upon the resumption of normal power, each DDC Controller shall analyze the
status of all controlled equipment, compare it with normal occupancy scheduling
and turn equipment on or off as necessary to resume normal operations.
DDC Controllers shall have the ability to perform any or all the following energy
management routines:
1.
2.
3.
4.
5.
6.
7.
Time-of-day scheduling
Calendar-based scheduling
Holiday scheduling
Temporary schedule overrides
Start-Stop Time Optimization
Automatic Daylight Savings Time Switchover
Night setback control
Page 20 of 56
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
D.
DDC Controllers shall be able to execute custom, job-specific processes defined by the
user, to automatically perform calculations and special control routines.
1.
2.
3.
4.
5.
E.
All programs shall be executed automatically without the need for operator
intervention and shall be flexible enough to allow user customization.
Time interval
Time-of-day
Date
Other processes
Time programming
Events (e.g., point alarms)
A single process shall be able to incorporate measured or calculated data from any
and all other DDC Controllers on the network. In addition, a single process shall be
able to issue commands to points in any and all other DDC Controllers on the
network.
Processes shall be able to generate operator messages and advisories to operator
I/O devices. A process shall be able to directly send a message to a specified device
or cause the execution of a dial-up connection to a remote device such as a printer
or pager.
The custom control programming feature shall be documented via English
language descriptors.
Alarm management shall be provided to monitor and direct alarm information to operator
devices. Each DDC Controller shall perform distributed, independent alarm analysis and
filtering to minimize operator interruptions due to non-critical alarms, minimize network
traffic and prevent alarms from being lost. At no time shall the DDC Controllers ability to
report alarms be affected by either operator or activity at a PC workstation, local I/O
device or communications with other panels on the network.
Page 21 of 56
1.
2.
3.
4.
All alarm or point change reports shall include the point's English language
description and the time and date of occurrence.
The user shall be able to define the specific system reaction for each point. Alarms
shall be prioritized to minimize nuisance reporting and to speed operator response
to critical alarms. A minimum of six priority levels shall be provided for each
point. Point priority levels shall be combined with user definable destination
categories (PC, printer, DDC Controller, etc.) to provide full flexibility in defining
the handling of system alarms. Each DDC Controller shall automatically inhibit the
reporting of selected alarms during system shutdown and start-up. Users shall have
the ability to manually inhibit alarm reporting for each point.
Alarm reports and messages will be directed to a user-defined list of operator
devices or PCs.
In addition to the point's descriptor and the time and date, the user shall be able to
print, display or store a 200 character alarm message to more fully describe the
alarm condition or direct operator response.
a.
5.
F.
DDC Controllers shall store point history data for selected analog and digital inputs
and outputs:
a.
2.
3.
Any point, physical or calculated may be designated for trending. Any point,
regardless of physical location in the network, may be collected and stored
in each DDC Controllers point group. Two methods of collection shall be
allowed either by a pre-defined time interval or upon a pre-defined change of
value. Sample intervals of l minute to 7 days shall be provided. Each DDC
Controller shall have a dedicated RAM-based buffer for trend data and shall
be capable of storing a minimum of 25000 data samples.
Trend data shall be stored at the DDC Controllers and uploaded to the workstation
when retrieval is desired. Uploads shall occur based upon either user-defined
interval, manual command or when the trend buffers are full. All trend data shall
be available for use in 3rd party personal computer applications.
DDC Controllers shall also provide high resolution sampling capability for
verification of control loop performance. Operator-initiated automatic and manual
loop tuning algorithms shall be provided for operator-selected PID control loops as
identified in the point I/O summary. Provide capability to view or print trend and
tuning reports.
a.
b.
In automatic mode, the controller shall perform a step response test with a
minimum one-second resolution, evaluate the trend data, calculate the new
PID gains and input these values into the selected LOOP statement.
For troubleshooting in manual mode, the operator shallbe able to select
variables to override default values. Calculated PID gains shall then be
reviewed before they are inserted into the selectLOOP statement.
Page 22 of 56
c.
G.
DDC Controllers shall automatically accumulate and store run-time hours for digital
input and output points as specified in the point I/O summary.
1.
2.
H.
2.
3.
DDC Controllers shall have the ability to count events such as the number of times a
pump or fan system is cycled on and off. Event totalization shall be performed on a daily,
weekly or monthly basis for points as specified in the point I/O summary.
1.
2.
2.06
The totalization routine shall have a sampling resolution of one minute or less.
The user shall have the ability to define a warning limit for run-time totalization.
Unique, user-specified messages shall be generated when the limit is reached.
DDC Controllers shall automatically sample, calculate and store consumption totals on a
daily, weekly or monthly basis for user-selected analog and digital pulse input type points
as specified in the point I/O summary.
1.
I.
Loop shall be capable of being initiated either locally at the DDC Controller,
from a network workstation or remotely using dial-in modems. For all loop
tuning functions, access shall be limited to authorized personnel through
password protection.
The event totalization feature shall be able to store the records associated with a
minimum of 9,999.9 events before reset.
The user shall have the ability to define a warning limit. Unique, user-specified
messages shall be generated when the limit is reached.
A.
Provide two portable operator terminals with a minimum LCD display of 80 characters
by 25 lines and a full-featured keyboard. The POT shall be handheld and plug directly
into individual distributed control panels as described below. Provide a user-friendly,
English language prompted interface for quick access to system information, not codes
requiring look-up charts.
B.
The POTs shall permit the project operating staff to perform network management, node
configuration, node programming, and node diagnostic.
B.
Page 23 of 56
8.
9.
10.
11.
C.
If the same Portable Operator's Terminal cannot be used for all control processors,
provide separate POTs to accomplish the above functional requirements.
D.
E.
Connection of a POT to a distributed control processor shall not interrupt nor interfere
with normal network operation in any way, prevent alarms from being transmitted or
preclude centrally initiated commands and system modification.
F.
2.07
A.
B.
Standards: all peripheral devices to utilize ASCII (American Standard Code for
Information Interchange) code and to be interfaced to the processing units with standard
RS232 port. Communication versatility is to comply with all methods previously
specified herein.
C.
Operator Station to comprise multiple operator peripheral input/output devices which can
all be used simultaneously. Characteristics of each device and the station to be totally on
line definable and completely independent of each other. If any device should experience
a failure, the system to automatically transfer its information to another device.
D.
The above authority keys to be software programmable while system is fully on-line with
at least six (6) priority levels. Each operator authority code to consist of from one to
eleven alphanumeric characters, each individually definable and modifiable through
keyboard entry while the system is online. Minimum of 50 authority codes to be
provided. Each authority code to have the following characteristics:
-
Page 24 of 56
Unit is to automatically create hardcopy record when an operator has been granted
access.This record to include date and time, which device and which operator was
granted access. System to also have capability to store this record historically (with or
without associated hardcopy record) with future retrieval/analysis capability, should this
mode of recording be preferred. Operator access to be terminated either by operator
command or automatically by the system as predetermined by the authority access timer.
Operator to have the ability to command points, request information, select entry method,
enter memory changes and edit any number of characters without having to retype an
entire line/screen.
E.
Operator Entry: there are to be multiple methods of operator entry. These to consist of,
but are not limited to, the following:
1.
2.
3.
tutorial method used as a prompting aid to assist an operator each step of the way
in executing the command function
dedicated method which will bypass the tutorial method to allow a quick, direct
command syntax/sequence for system processing. Systems without a direct
command are unacceptable
template method used for mass repetitive/data entry of information and commands.
This method to also be used for data base generation, including such items as point
definition, graphic generation, report creation, and custom/DSC programming/
translation.
Any method of entry is to be verified by the system prior to execution. Any invalid
entries to be highlighted by the system for operator correction. Operator to be able to
request help in any mode of operation at any time to aid in command entry. This help
request to convert mode or provide aid lists on the request parameters. Any operator entry
is not to inhibit any change-of-state COS reporting. Each time an operator command is
issued the system to automatically create a hardcopy record.
F.
Function Keys: as an aid to the operator, the system MMI to provide dedicated function
keys (DFK) for common/repetitive operator functions. These functions to be executed by
single operator keystroke. Utilization of dedicated function keys is not to inhibit any
COS reporting or any other simultaneous functions that operator may be performing.
Provide at least 12 DFK/keyboard. Different keyboards to be programmed to maideal
with specific areas or sub-systems (such as electrical, HVAC), although it is also to be
possible for any one to take over completely. This to be performed to aid operators in
sharing their duties. Clear markers to be affixed to each dedicated function key, giving
its actual function.
G.
Printers: system printers to provide hardcopy data retention of COS, operator initiated
actions, management reports, graphics and trended information. Printers which can be
interfaced include the following:
-
color printer
receive only (RO) printer
Main control station to be provided with one color and two receive only printers.
Secondary stations to be provided with one color and one receive printer.
H.
Page 25 of 56
communication rate shall be 19200 baud minimum (or latest standard). An operator
accessing the system via a modem shall be capable of executing all commands
permissible by his access level. Modem communication shall at not time interfere with
the operation and performance of the network computer or the direct digital field control
units.
2.08
A.
B.
C.
Provide a printer (RO) for recording alarms, operator transactions and systems reports,
meeting the following minimum requirements:
1.
2.
3.
4.
5.
6.
7.
C.
Provide a color printer for printing of graphics and any other screen displays. Printer
shall include as a minimum:
1.
2.
3.
4.
5.
6.
7.
2.09
80 Column tractor-feed for normal use with ability to switch to friction feed of
single sheets of paper without any mechanical adjustments.
360 x 360 Dot/Inch image resolution.
Draft and letter quality print selection for alpha-numeric operations.
Four color mix capability to provide true color printing of screen graphics.
Three built-in letter quality fonts from selectable front panel buttons.
64K Buffer to store complete graphics for printing.
Include colour kit.
Page 26 of 56
A.
General: provide Cathode Ray Tubes (CRT) and keyboards to display realtime data,
allow operator commands, perform data base generation and report system activity.
B.
CRTs connected to the system to include color CRT with direct video capability having
minimum 480 mm diagonal display with minimum of 48 lines and 80 character/column
screen with refresh rate of 60 times per second. The display area shall have a resolution
of 1024 x 840 pixels. Format of screen to permit output of dynamic color displays and/or
summaries specified hereinafter, while concurrently displaying the most recent COS
occurrence. It is to have detachable, tactile feedback keyboard having standard
typewriter layout plus 10-key numeric key pad and dedicated function keys.
The CRT shall be capable of displaying 17 colors selected from a palette of 256 colors.
The minimum screen diagonal measure shall be 19 inches.
A digita display clock shall display on the monitor at all times. Provision for manually
resetting it shall be provided. It shall be a 24 hour real time clock and seven day calendar
to provide data for logging.
The network computer keyboard and color graphic CRT shall be the primary means of
operator access to the system, providing the operator interface for the entire system.
C.
Format CRT to include and display in an individual dedicated and protected area of the
viewing screen the following dynamic information:
current time, date and day of week (including holidays)
highest priority unacknowledged COS
visual indication of the type of alarm/off-normal condition still active after
acknowledgement
current operator identification
current status of three points considered critical for that operator's CRT
system advisory alarm messages
operator work area to display various forms of point information, issue commands and
data base generation functions.
Formats are to permit the out of various forms of point displays specified hereinafter,
while concurrently displaying the most recent COS occurrence. Furthermore, while this
information is displayed, the operator to also be able to enter commands to the system.
D.
E.
Any and all CRT screen images to be printable upon single keystroke. While screen
image is being printed, the system is not to inhibit operator utilization of CRT.
F.
Color CRT to output chromatic system graphic displays as specified. These chromatic
graphic displays to detail all mechanical and electrical systems listed in the schedule
attached to this Specification. Operator request for a chromatic graphic display is to cause
associated system to be automatically selected and outputted on viewing screen. When a
point is in alarm on the CRT, the operator to be able to display a graphic with a single
keystroke.
Page 27 of 56
2.10
A.
Transducers: to include, but are not necessarily limited to, temperature sensors, pressure
switches or level switches. Transducer is a device that converts information about a
physical parameter from form in which it is received to some other form, e.g., pressure to
voltage. It is the primary element in an instrumentation and control system, is inserted in
the process flow stream, and provides the signal that can be read, recorded, alarmed or
provides control within a process.
B.
Flow Switch to be vane actuated type, designed to mount to pipeline with threaded
coupling 50 mm NPT. Suitably shaped and beveled coupling is welded to pipe and flow
switch is threaded directly into it. Flow switch to be designed for vertical installation on
horizontal pipelines and to be marked to indicate direction of flow. Actuating vane is
linked to pivoted mercury switch. When vane moves with increase in flow it will trip the
switch. Screw fasteners securing actuating vane to be back welded for added safety.
Switch to be SPDT sealed mercury switch with rating 13 amperes. All materials subject
to wetting to be 316 stainless steel. Switch to be in NEMA 4 housing. Conduit
connection to housing to be 20 mm NPT. Perform necessary tests to assure that flow
switch will be operational at specified flow rates. Repeatability of flow rate actuation
point is to be within 0.1 %.
C.
Pressure Switch to be flexible diaphragm type, with diaphragm sealed in place with "O"
ring. Diaphragm and ring to be of Buna-N. Diaphragm seals out the process fluid but
transfers pressure variations directly to a spring based piston. Pre-stressed spring to be
adjustable to calibrate operating point of switch. Switch element to be a snap action
contact transfer type transferring on 0.55 mm movement. Switch to be electrically rated at
480 volt (max) at 15 amps., AC service, and 125 volt, 0.5 amp, DC resistive load.
Pressure connections to be sized for 12 mm NPT fittings and pipe. Electrical connections
use 20 mm NPT conduit. Housings to be weathertight and conform to NEMA 4 ratings.
D.
Differential Pressure Elements to be bellows type with liquid fill. Bellows and center
plate to be completely filled with clean, non corrosive, low freezing point liquid, and to
stand repeated over-ranging in excess of working pressure of instrument housing without
causing calibration change. Temperature compensation to be provided for the fill. Torque
tube assembly to be an integral part of the bellows assembly to transmit motion. Torque
tube assembly to be so designed that it is installed in a preloaded condito prevent
backlash as it rotates through its complete range. Rotation of torque tube for full scale
differential pressure to be 8 deg.+/-10%. Unto operate within temperatlimits of-5 to +55
deg C. Process connections to be 12 mm NPT.
E.
Page 28 of 56
line voltage
power
:
line variation
operating temperature :
temperature sensitivity :
zero stability
span adjustment
terminal adjustment
output linearity
repeatability
output relays, DPDT
transmitter enclosure
:
220 V AC +/-10%, 50 hertz
20 watts
:
+/-0.5%/20V.
-5 deg. C to +55 deg. C.
0.01% per deg F maximum
:
0.01 pf per deg F maximum
:
10 to 3000 pf
:
0 to 250 pf
:
+/-0.5 %
:
+/-1 %
:
10 A 220 V AC noninductive
:
NEMA 4.
G.
Pressure Transmitter (PT): to be high stability transducer utilizing solid state circuitry.
Output is a 4.0 - 20.0 mA DC signal proportional to sensed pressure. Accuracy of
instrument to be 0.25 % of span. Two barrier type terminals for No.14 wire plus ground
connections to be provided. Process pressure connections to be made through 6 mm
NPT. Conduit for electrical connections to be 20 mm NPT. Instrument to be operational
in a thermal environment of from -29 deg C to +39 deg C.
Perform necessary tests to ensure that pressure transmitter meets all operational
manufacturer specifications.
H.
I.
J.
Carbon Monoxide transmitter shall use an electrochemical sensor to monitor the CO level
and output a 4-20 mA or voltage signal. Options shall include an LCD to display the CO
ppm level, control relays, an audible alarm and RS485 network communications.
Operating parameters shall be easily programmed via the keypad to configure the
transmitter to a specific application. The transmitter shall also features a pre-calibrated
replaceable sensor module for convenient maintenance.
Operating characteristics of transmitting unit to be as follows:
Page 29 of 56
Sample Method:
Measurement Range:
Standard Accuracy :
Stability :
Typical Area Coverage
:
Pressure Coefficient :
Response Time:
Warm-up Time :
200 seconds
0-50 C (32-122 F) standard, -20-50 C (-4 -122 F) optional,
Operating Conditions:
15-95 %RH
Power Supply:
20 30 Vac/dc (non-isolated half-wave rectified)
Reverse voltage protected, output limited, transient protected and
Protection Circuitry :
resettable fuse
Output Signal:
4-20 mA active or passive, 0-5 or 0-10 Vdc jumper selectable
Form C contacts (N.O. and N.C.), status LEDs, 5 Amps @ 250 Vac,
Optional Relay Output :
5 Amps @ 30 Vdc
Programming
Via internal push-buttons and jumpers
K.
Control Valves:
a.
2-Way Valves Modulating: low voltage, 2-way, proportional, spring return type,
providing modulating control of water flow through operation of motor actuator
and valve linkage and in response to signal from proportional controller. Valves to
have the following features:
Single seated valve, equal percentage flow characteristic, straight-through pattern;
screwed end connections, bronze body and removable brass seat on 15 to 40 mm
sizes; flanged end connections, cast iron body and removable bronze seat on 50 to
150 mm sizes; stainless steel stem and composition disc with removable throttling
plugs. Operator shall close valves against pump shutoff head.
Spring return type motor, with oil-immersed gear train, die-cast aluminium case.
single 160 degree stroke, double-ended crankshaft, die-cast aluminium cover with
built in transformer and spring to return motor to closed position on power failure.
Linkage directly mounted on motor, without adjustment requirements and
comprising roller, slide mechanism, cam and stem position indicator and with 710
N seal-off force.
Valve rated 115 deg. C maximum water temperature and pressure class based on
maximum pressure and temperature rating of piping system, unless otherwise
indicated. Motor rated 50 deg. C maximum ambient temperature.
L.
Electric Actuators
Page 30 of 56
a.
b.
M.
N.
Damper Actuator to provide linear motion for damper control without convertor for
2-position control and with electronic signal convertor for modulating damper.
Accessories include linkage for head mounting.
Indicators: are required for operating personnel to monitor the several process control
variables. They are located on control panels. Indicator may be operated electrically,
pneumatically or provide a direct indication. Readout area may be scale and pointer or
level glass.
a.
b.
Solid State Switch: to be a rack mounted card capable of selecting an analog input signal
and providing an output of contact transfer. Input to unit to be a 4.0 to 20.0 mA signal
applied to a precision resistor. Adjustable reference to be included to provide a set point.
Voltage of this point to be compared with voltage across precision resistor when input
signal exceeds pre-set value, a comparator-amplifier provides a sharp change in output
signal. Transfer contacts to be activated by change in out signal. These DPDT contacts to
be rated at 3 amps., 220 V, 50 hertz or 3 amps., 28 V DC. Operating parameters to be as
follows:
-
AC power input:
normal :
0.6 watts (1.60 VA)
tripped :
0.85 watts (2.0 VA)
minimum input impedance: power on or off : 1 mega-ohm
isolation: input completely isolated from other inputs and output as regards DC
operating span: 100 %
differential: adjustable: 0.2 % to 5 % total trip set point value
repeatability: +/-0.1 % of span
ambient temperature effects: 0.1% set point drift for temperature range of 2 to 40
degC
line voltage effects: +/-0.1% set point change for line variation of +/-10% at 220
volts, 50 Hertz
response time: 0.015 seconds.
Page 31 of 56
O.
P.
Adder-subtracter to be used in all cases where the sum of two to four signals is
required or the difference between two signals is the sought-for parameter. Module
to be a rack-mounted instrument of the non-indicating type. It is to be mounted in a
weatherproof enclosure with easy access to the adjustment controls. Unit to be
easily adjusted on site with capability of changing output equation as needed.
Circuitry of adder-substracter to comprise all solid-state components with
integrated circuit amplifiers to provide stability and longevity. Control signal
inputs to be 0.5 V DC and proportional to the sum of difference of the input
signals. Output load resistance can be between zero and 1850 ohms, as referenced
on the Drawings. Output to be short-circuit protected. Thermal stability of unit to
be such that temperature variation of 10 deg C between -5 deg C and +40 deg C to
affect output less than 0.5 %. Input power variations to affect output less than
0.025 % for +/-10 % change in supply voltage. Accuracy of unit to be better than
0.5 % of span. Power supply for unit to be capable of supplying +/-15 V DC at 30
mA each.
b.
Converter: electric transducer to convert 4.0 to 20.0 mA signals into standard linear
20.7 to 103.5 kPa a low level electric current into a coil working within the
magnetic fields of a permanent magnet produces a force operating linearly. This
force operates a pneumatic nozzle, the back-pressure on a nozzle, continually
balances the force produced by the coil, therefore, the transmitted air pressure to at
times be proportional to the coil current. Coil and a float below it to be integrally
mounted on a central shaft so that whole assembly is free to move. Float equals the
weight of the moving coil assembly. Unit to be shock and vibration proof and to be
mounted in an upright position (tilted not more than 10 % from vertical centerline).
c.
Page 32 of 56
d.
Care must be taken that input signal is free of noise because a differentiator will
greatly amplify any rapid swing of the input to the point that output is of no
practical value. The Contractor to be responsible for determining rate of change of
pressure that will be deemed unsafe and provide an RC network for unit that will
produce an alarm at unsafe limit.
Q.
2.11
Flow meter Sensor: to comprise flow meter with sensing device suitable to be
linked to BMS. Flow meter to be mechanical type designed to operate with dirty
water and high temperature water. Pressure rating is to suit system pressure. Body
to be in cast iron with with epoxy exterior coating. Flow meter sensor to be similar
to Schlumberger type WET/WET-P on approved equal.
A.
Provide uninterruptible Power Supply (UPS) System, on-line (load is continuously fed
through inverter), 3-phase, 380/220 V, 50 Hz, as specified under division 16, section
16610 for the central BMS equipment located at the BMS room. UPS capacity is to be
selected based on 125% of the maximum load of all equipment in addition to 25% extra
capacity for future expansion, noting that loads are of non-linear type, consisting of
computer equipment, and UPS capacity is not to be less than 30 kVA with a minimum
duration of 20 minutes. Calculation of the UPS capacity is to be submitted for approval.
B.
Each DDC is to be provided with a local UPS system, 1 or 3-phase, 380/220 V or 220 V
as appropriate, 50 Hz on line (load is continuously fed through inverter) as specified
under Division 16, Section 16610, with adequate capacity to cater for 125% of the
maximum load of DDC in addition to 25% extra capacity for future expansion for a
Page 33 of 56
2.12
A.
Page 34 of 56
B.
Page 35 of 56
Point information to provide for outputting information for single point, specific group of
points, specific class of points, type of points, etc. Execution of output command to be
recorded with date and time.
Point information displayed on screen or hardcopy recorded to be in the order
programmed by the operator. All screen information to be dynamic and system to
automatically update displayed information at least twice a minute.
Point information: to provide for operator requested information in the form of logs,
summaries, dynamic graphics, dynamic trending, historical data and cu
C.
Change-Of-State (COS) Reporting: BMS to detect and report any change from each
point's normal status. These changes to include, but are not limited to the following
general categories:
-
Page 36 of 56
Logs And Summaries to indicate on a per point basis the hardware communication status
through the use of special character of flags. These indicators to be kept current with the
advisories.
E.
F.
2.
Program elements shall be able to be combined into a custom template which can
then be used as a standard function.
3.
Program checkout and debug tools shall include display of real-time and/or
simulated system variables and inter-object data on the programming screens. The
user shall be able to fix or force values of variables to enable program checkout
during debugging.
4.
The programming software shall reside on each POT and OW server for
programming and/or configurating each model of LONWORKS node on the
project. The applications shall be downloaded and executed at the appropriate
nodes. The software shall allow for updated applications via the network from the
OW.
5.
DDC programs are to be provided to meet the control strategies as called for in the
sequence of operation sections of these specifications. Each LPN shall have
available a full library of DDC algorithms, intrinsic control operators, arithmetic,
logic, Proportional Control, Proportional plus Integral (PI), Proportional plus
Integral plus Derivative (PID), and relational operators for implementation of
control sequences.
2-POSITION, FLOATING, STANDARD I/O AND
COUNTER INPUTS, TIME BASED DATA, CURVE FIT FUNCTION,
PSYCHOMETRIC FUNCTIONS, INTEGRATION,
6.
All DDC setpoints, gains, and time constants associated with DDC programs shall
be available to the operator for display and modification via the POT or OW
interface.
Page 37 of 56
separate software tools or processes to create applications and user interface display shall
not be acceptable.
G.
H.
I.
J.
Calculator objects, (basic stuff), including if-then-else, log, ln, exp, and trig functions.
K.
Recognize standard network variable type data (nvi) and create network variables to put
on the network (nvo)
L.
Programming Objects
1.
Provide the capability to copy objects from the supplied libraries, or from a userdefined library to the users application. Objects shall be linked by a graphical
linking scheme by dragging a link from one object to another. Object links will
support one-to-one, many-toone, or one-to-many relationships. Linked objects
shall maintain their connections to other objects, regardless of where they are
positioned on the page and shall show link identification for links to objects on
other pages for easy identification.
2.
Configuration of each object will be done through the objects property sheet using
fill-in the blank fields, list boxes, and selection buttons. Use of custom
programming, scripting language, or a manufacturer-specific procedural language
for configuration will not be accepted.
3.
The software shall provide the ability to view the logic in a monitor mode. When
on-line, the monitor mode shall provide the ability to view the logic in real time for
easy diagnosis of the logic execution. When off-line (debug), the monitor mode
shall allow the user to set values to inputs and monitor the logic for diagnosing
execution before it is applied to the system (step function and run mode, integral
trend logging).
4.
M.
The system shall support object duplication within the Owners database. An
application, once configured, can be copied and pasted for easy re-use and
duplication. All links, other than to the hardware, shall be maintained during
duplication.
Object Libraries
1.
A standard library of object function blocks shall be included for development and
setup of application logic, user interface displays, system services, and
communication networks.
2.
The function blocks in this library shall be capable of being copied and pasted into
the users database and shall be organized according to their function. In addition,
the user shall have the capability to group objects created in their application and
store the new instances of these objects in a user-defined library.
3.
Page 38 of 56
N.
O.
4.
P.
Network Management
1.
2.
Network management shall include the following services: brows all network
variables on nodes; Attach, Detach, Manage, Add, Remove, and Replace nodes;
plus transmission error off-line, on-line reporting.
3.
The software shall have Client/server capability to allow multiple users ability to
manipulate the database simultaneously.
Graphics Generation: color graphics generation to be done through any color operator
terminal. While in the generation process, the color terminal is not to be inhibited from
receiving any COS information. Generation of graphics to be accomplished with the
following attributes:
-
BMS is not to restrict the number to graphics that may be generated. Capability to be
provided for storage of graphics on request in a library for future use in formatting other
graphics.
Page 39 of 56
Help request to be available to assist operator in designing a graphic at any time during
creation process without loosing any graphic information that is already defined. This
help request to provide aid lists for selection of definition attributes, available point types,
colors, and symbols.
BMS to provide library of predefined symbols, consisting of industry standard
representations of HVAC control, plumbing, electrical, fire and security
equipment/devices. Library is to be used by operator for generation of graphic symbols.
If operator wishes to define custom symbols, the BMS to provide capability to
accomplish this during generation phase of each individual graphic. Lines are to include
but are not limited to vertical, horizontal, diagonal and free hand. Character strings are to
include alphanumeric characters and to be capable of 60 characters minimum length.
Q.
Data Base Generation: This is to be done via fill-in-the blank, mass template entry
method. Operator to be able to online:
-
Interface Prompting to be used to direct operator throughout program, to use fill-in-theblank, walk-through method to queue and edit operator entered parameters.
R.
Load Control:
a.
Page 40 of 56
b.
c.
d.
e.
g.
h.
demand interval
current KW power
current measured demand
projected demand usage
energy units defined for the energy system
maximum expendable load
average expandable load
Page 41 of 56
i.
System Load Summary to include, but is not limited to, the following:
-
j.
k.
l.
2.
HVAC Control:
a.
b.
c.
Page 42 of 56
d.
e.
g.
S.
Page 43 of 56
c.
Page 44 of 56
For each bar and line graph display, the BMS to provide a vertical scale of either
actual values or a percentage scale (operator selectable at each display) and a
horizontal scale which the system is to automatically time base with up to 200
samples per screen.
Compression/interval and dynamic forward/backward
scrolling feature to be available to display "off screen" historical data values.
Dynamic Display feature is to provide the display of dynamic data values while
displaying graphs. This dynamic display to automatically update new sample
values and to dynamically display for each point graphed, either observed highest
and lowest data values or lowest and newest data values.
d.
Historical Data Storage: BMS to provide the capability to historically store logs,
summaries, COS records, acknowledgement records and operator commands. This
information to be stored on the PC hard or floppy disks. Unit to be later recalled by
operator command. Information stored to be operator selectable and categorized for
storage as desired. Amount of disk space allocated for each category to be operator
selectable online.
BMS to also provide the capability for remote historical data storage to the PC
storage disk unit loading media. Capability to be provided to remotely store
categories in any order desired. Recall of remote stored information to be by
information type directly from loading media. It is not to be necessary to copy
information back onto mass storage disk unit for operator analysis.
Weekly Scheduling capability to be provided through the BMS to:
-
e.
Page 45 of 56
equipment runtime
binary/digital point status (alarm/off-normal/normal) condition
analog point status condition.
Consumption totalization to accumulate data for the amount of the measured data
value recorded over a period of time. Attributes of consumption totalization to
include:
Page 46 of 56
base units of measured data value to be totalized (i.e. litres, watts, watts/hour
etc.)
instantaneous time factor totalization is to be based upon (seconds, minutes,
hours, none)
measured data value scaling factor
associated data point status totalization should occur under.
Each totalized value to have a selectable alarm and reset limit. When totalized
value reaches its alarm limit, a COS message to be output and totalization to
continue. When totalized value reaches it reset limit, a COS message to be output
and total to automatically be reset to zero and totalization continued. Total to also
be able to reset to zero by a manual command.
Totalization value to be accessible for display and/or as a mathematical input in
any custom report or programming language. System is not to restrict this usage in
any manner, nor is operator to duplicate this feature capability to provide this
function.
h.
Page 47 of 56
BMS to allow any combination to these functions in any order to read point data,
calculate any mathematical value, and process decision logic statements for control
action, either intra-process or inter-process.
Custom Programming Language to provide user advisory information for system
output during any stage of its control execution. This information to be provided
through a minimum of seventy character user defined message strings. Number of
messages definable for each custom program or the overall system is not to be
restricted.
BMS to provide the ability to review any custom process source code on any CRT
or printer. Online text editing on any CRT to be provided for addition, deletion
and/or modification of any custom process. Text editing to include a HELP
command to prompt an operator on editing functions.
Upon completion of custom process definition, the BMS to provide a resident
translator to develop the executable object code online. If any translation errors are
detected, error messages to be generated indicating location of error and type of
error.
i.
fortran Compiler
assembler Program
source Editor
loader Program
disk Utility Program
memory Dump and Modify Program
debug Program
system Generation
system Save and restore
diagnostic Software.
2.14
A.
B.
The Web browser software shall run on any operating system and system configuration
that is supported by the Web browser. Systems that require specific machine
requirements in terms of processor speed, memory, etc., in order to allow the Web
browser to function with the Web server, shall not be acceptable.
C.
The Web browser shall provide the same view of the system, in terms of graphics,
schedules, calendars, logs, etc., and provide the same interface methodology as is
provided by the HMI.
D.
The Web browser client shall support at a minimum, the following functions:
1.
Page 48 of 56
3.
Storage of the graphical screens shall be in the Web Server without requiring any
graphics to be stored on the client machine.
4.
5.
6.
[The system shall provide the capability to specify a users (as determined by the
log-on user identification) home page. Provide the ability to limit a specific user to
just their defined home page. From the home page, links to other views, or pages
in the system shall be possible, if allowed by the system administrator.
7.
2.15
Graphic screens on the Web Browser client shall support hypertext links to other
locations on the Internet or on Intranet sites, by specifying the Uniform Resource
Locator (URL) for the desired link.
WEB SERVER
A.
An operator workstation central server shall be provided. The server shall support all
Owners network whether local or remote.
B.
MULTIPLE SERVER (single client can access data from all servers)
C.
Local connections shall be via an Ethernet LAN. Remote connections shall be via ISDN,
ADSL, T1 or dial-up connection.
D.
It shall be possible to provide access to all LONWORKS nodes via a single connection
to the Web Server.
E.
Global Data Access: The server shall provide complete access to distributed data
defined anywhere in the system.
2.
3.
Page 49 of 56
2.14
4.
5.
6.
7.
[The server shall accept time synchronization messages from trusted precision
Atomic Clock Internet sites and update its master clock based on this data.?????]
A.
B.
Operation station to have a central processing unit such that it can be configured as a
fully operational stand-alone maintenance management system. Operator display to
consist of a color CRT capable of displaying 48 lines x 80/132 color with a screen size of
19" and a resolution of 1056 x 400 image points. The printer to be capable of printing
132 characters per line on standard 8.5 x 11 inch continuous contractor feed paper at a
minimum rate of 220 characters per second. The printer shall be capable of using fan
fold single sheets of paper.
The system to have a minimum of 4 megabytes of random access mass storage and be
expandable to 200 megabytes. Storage may be added by connecting additional storage
units and assigning portions of the programming, data base or maintenance history to the
auxiliary storage devices.
The system to operate through the use of linked menus which guide the operator to the
proper screen or function. The operator to be capable of directly accessing any system
operation without stepping through successive menus. He is to be capable of directly
accessing frequently used functions by a single keystroke through the use of software
designated function keys.
Operator displays to employ color to differentiate data types and to emphasize system
advisories. Colours to be selected in such a manner that they are not distracting to overall
operations.
The operator to have access to all system documentation while operating the system. This
to include information detailing the use and operation of the menu, template, and field in
the system. He is to be capable of displaying the information to either the display or
printer. The system to grant operator access to system functions on a per menu selection
basis. A minimum of fifteen passwords shall be supported.
The system to be capable of executing other facility functions when not executing
maintenance management software. These functions shall include:
-
word processing
accounting
graphics
spreadsheets.
Page 50 of 56
C.
Data Base: the entire data base to be structured to allow a minimum number of required
entries for facilities where the operation is not data intensive. The system to also be
comprehensive and flexible enough to ensure that additional optional data can be entered
to allow more sophisticated configurations to be created.
The component data base to allow the following data to be entered on either a mandatory
or optional basis:
*
*
*
*
*
*
*
Component ID
Quantity
Location
PM Program
Levels of Service
Tools and Material
Warranty
*
*
*
*
*
Component Name
*
Use
Classification
Master Schedule
*
Seasonal Tasks
Begin and End Weeks
Date Entered.
Separate data to exist for recording information on sub- component parts and repair parts.
Additionally, the system to have the capability of creating user defined component data
base parameters.
The system to allow for a property data base such that non maintainable components can
be tracked as part of the system. All maintainable components may also have a property
record. The property data base shall include such parameters as:
*
*
*
*
*
*
*
D.
*
*
*
Component Name
*
Use
*
Classification
*
Acquisition Code
Serial Number
Inventory Date
Date Entered.
Task Schedules: the system to support a system of master schedules such that
components with similar maintenance requirements can all draw on a single master
schedule. The schedule to be constructed in such a way that minor maintenance variations
between similar components can be accommodated without resorting to creating
additional master schedules. The master schedules to include the following information:
*
*
*
*
*
*
E.
Component ID
Quantity
Location
Accounting Code
Part Number
Purchase Date
Warranty
Task ID
Manuals
Craft
Task Synopsis
Task length
Contractor
*
*
*
*
*
Intervals of Service
*
Tools and Materials
Number of Employees
Priority
Plant Condition
Cost.
BMS Interface: the system to support an interface data base to the BMS system to allow
the transfer of runtime and alarm data to the work order generator. Components to be
capable of being assigned a minimum of three runtime schedules and one alarm schedule.
The data base to include the following information:
*
*
*
Alarm Schedule
Last Runtime Issued
Current Runtime
*
Runtime Schedules
Next Runtime Expected
*
Component ID
Page 51 of 56
F.
Work Order Generation: the system to support scheduled work order generation on a
weekly basis, for any segment of the year or seasonally, or by runtimes as accumulated at
the BMS. Scheduling to be done on either a calendar or a fiscal year basis. Work orders
to be sorted before printing by several user selectable criteria. The system to be capable
of generating one million work orders per year.
The system to support repair work order generation on a demand basis or by alarms
accumulated at the BMS. Repair work orders may be requested and serviced
immediately, or planned for future completion (backlogged).
The system to support a user defined custom work order format. This format is to be
applicable to both scheduled and repair work.
G.
Employee Assigned
Date Assigned
Accounting Code
Wage Differential
Hour/Minutes Spent
Downtime
Comments
*
*
*
*
*
Craft
Date Complete
*
Number of Employees
*
Overhead Costs
PM/Repair Type
Materials Used
Condition/Action/Cause
Maintenance history to also compute year-to-year totals and other pertinent history data.
H.
The system to allow a minimum of one year of maintenance history to be stored on-line.
Additional storage capability shall be possible to be added. User to be able to achieve online maintenance history to a bulk storage media for later processing and to free random
access storage devices for current data.
Management Reports: in addition to standard maintenance reports, the system to have the
capability of providing user defined reports. These reports shall be stored in a user library
and recalled upon demand. The reports to be capable of accessing any portion of the data
base or maintenance history, sorting based on user selection and performing math
functions.
2.16
REFER TO APPENDIX.
Page 52 of 56
PART 3 - EXECUTION
3.01
EXAMINATION
A.
B.
C.
Verify that required utilities are available, in proper locations, and ready for use.
D.
3.02
A.
3.03
HARDWARE INSTALLATION
Provide a separate DDC Controller for each AHU. Two AHU systems may be placed on
one DDC Controller if sufficient points are available. However, all points associated with
any AHU system must be located on the same DDC Controller.
A.
B.
Connect motor controllers, lighting controls, fire alarm and smoke detection devices,
intrusion detection and security access devices, sensing and measurement devices,
electrical controls and relays, programmablelogic controller, under provisions of Div16
related Sections.
3.04
A.
3.05
ON-SITE TESTING
A.
B.
Field Test: When installation of the system is complete, calibrate equipment and verify
transmission media operation before the system is placed on-line. All testing, calibrating,
adjusting and final field tests shall be completed. Provide a detailed cross-check of each
sensor within the system by making a comparison between the reading at the sensor and a
standard traceable to the National Bureau of Standards. Provide a cross-check of each
control point within the system by making a comparison between the control command
and the field-controlled device. Verify that all systems are operable from local controls in
the specified failure mode upon panel failure or loss of power. Submit the results of
functional and diagnostic tests and calibrations to the Engineer for final system
acceptance.
Page 53 of 56
C.
Compliance Inspection Checklist: Submit in the form requested, the following items of
information to the Engineer for verification of compliance to the project specifications.
Failure to comply with the specified information shall constitute non-performance of the
contract. The contractor shall submit written justification for each item in the checklist
that he is unable to comply with. The Engineer will initial and date the checklist to
signify contractor's compliance before acceptance of system.
1.
Verify to the Engineer in letter form that supplier has in-place support facility.
Letter shall show location of support facility, name and titles of technical staff,
engineers, supervisors, fitters, electricians, managers and all other personnel
responsible for the completion of the work on this project.
2.
3.
4.
5.
Disconnect one DDC Controller from the network to demonstrate that a single
device failure shall not disrupt or halt peer-to-peer communication. Panel to be
disconnected shall be selected by the Engineer.
6.
b.
c.
3.06
At least one temperature setpoint and at least one status condition, i.e., on or
off for a system or piece of equipment attached to that panel as well as for
points at another DDC Controller on the network.
The diagnostic results as specified for a system or piece of equipment
attached to that panel as well as for a system or piece of equipment attached
to another DDC Controller.
The ability to add a new point to the DDC Controller with the POT and have
it automatically uploaded to the workstation to modify that panel's stored
database.
FIELD SERVICES
A.
Adjust setpoints, alarm points, and display configurations so that system performs as
specified.
B.
Include installing and debugging hardware and software. Perform hardware configuration
revisions required to accommodate software patches.
C.
3.07
A.
CLEANING
Clean equipment finishes and interiors of equipment cabinets.
Page 54 of 56
3.08
A.
General Requirements: Provide all services, materials and equipment necessary for the
successful operation of the entire BMS system for a period of one year after completion
of successful performance test. Provide necessary material required for the work.
Minimize impacts on facility operations when performing scheduled adjustments and
non-scheduled work.
B.
Description of Work: The adjustment and repair of the system includes all computer
equipment, software updates, transmission equipment and all sensors and control devices.
Provide the manufacturer's required adjustments and all other work necessary.
C.
D.
Schedule of Work: Provide two minor inspections at 6 month intervals and two major
inspections offset equally between the minor inspections to effect quarterly inspection
ofalternating magnitude, and all work required as specified. Minor inspections shall
include visual checks and operational tests of all equipment delivered. Major inspections
shall include all work described for minor inspections and the following work:
1.
2.
3.
4.
5.
E.
Emergency Service: Owner will initiate service calls when the system is not functioning
properly. Qualified personnel shall be available to provide service to the complete
system. Furnish owner with a telephone number where service representative can be
reached at all times. Service personnel shall be at the site within 24 hours after receiving
a request for service. Restore the control system to proper operating condition within 3
days.
F.
Operation: Performance of scheduled adjustments and repair shall verify operation of the
system as demonstrated by the initial performance test.
G.
H.
Software: Provide all software updates and verify operation in the system. These updates
shall be accomplished in a timely manner, fully coordinated with the system operators,
and shall be incorporated into the operations and maintenance manuals, and software
documentation.
3.09
A.
DEMONSTRATION
Provide systems demonstration under provisions of the Contract Documents.
Page 55 of 56
B.
3.10
A.
The Contractor shall provide competent instructors to give full instruction to designated
personnel in the adjustment, operation and maintenance of the system installed rather
than a general training course. Instructors shall be thoroughly familiar with all aspects of
the subject matter they are to teach. All training shall be held during normal work hours
as follows:
B.
C.
Provide additional training quarterly for a period of one year from final coof the project.
END OF SECTION.
Page 56 of 56
PART 1 - GENERAL
1.01
RELATED WORK
A.
Division 15 - Mechanical
1.02
SYSTEM DESCRIPTION
A.
This Section covers the testing and commissioning requirements for air handling,
piping controls and mechanical systems generally.
1.03
QUALITY ASSURANCE
A.
The testing and balancing shall be conducted by a specialist agency other than
the Mechanical Contractor subject to the approval of the Engineer, professional
in balancing and testing such systems as herein specified.
1.04
SUBMITTALS
A.
Certificate
a.
2.
3.
Data Sheets
a.
b.
c.
Report Forms
a.
Submit specimen copies of report forms, for approval for their use on
this project.
b.
Forms shall be quarto paper for loose leaf binding, with blanks for
listing of the required test ratings and for certification of report.
Page 1 of 13
systems. The contractor shall allow sufficient points and where required by the
Engineer for the correct and complete regulation, testing and commissioning. All test
points shall be indicated on the working and record drawings. Test points shall be fitted
with removable plugs, flanges or other approved devices appropriate to the service
concerned.
Balancing valves and dampers shall be included on every main branch and sub circuit
to facilitate system commissioning. All such devices shall be identified on the working
drawings and submitted for approval.
Each volume control damper and fire damper shall be complete with adjacent access
panel.
Balancing valves shall be propriety commissioning sets consisting of double regulating
valve and close coupled orifice plate.
The Contractor shall prepare system loading diagrams for each system including
control dampers, regulating valves and test points and shall indicate their physical
location in pipework or ductwork.
Recording of Test Results :
The Contractor shall give 7 days notice, to the Engineer in writing, prior to any
regulation, testing and balancing being undertaken to enable he Engineer to witness the
work.
The Contractor shall formulate and provide all test sheets to a format agreed by the
Engineer. Each sheet shall contain the project title, the logos of the Employer and the
Engineer . Each sheet shall have witnessing signatory space specific to the Contractors
Engineer, and the Engineers designed representative.
The test result sheets shall be fully cross-referenced to the system loading diagrams
which shall be updated to include the actual test results.
Duplicate signed test certificates shall be provided after each test which will be
countersigned by the Engineer who witnesses the test. The test certificate shall give the
following particulars :
Apparatus or Section under test
Makers number ( if any )
Nature, duration and conditions of test
Result of test
No test shall be valid until the test certificate is provided.
Duplicate copies of test certificates carried out at manufacturer works shall be
forwarded to the Engineer for approval prior to dispatch of the article to site.
No Section of the works shall be insulated or in any other way concealed prior to
testing and inspection and subsequent concealment where applicable shall only take
place following written authority from the Engineer.
Page 2 of 13
All necessary facilities, measuring and recording instruments including test pumps and
gauges for inspection/testing and commissioning requirements shall be provided and
shall be checked or calibrated as necessary before use. The Engineer reserves the right
to call for a demonstration of the accuracy of any instruments provided.
Testing Instruments :
The Contractor shall submit with his Tender a full list of instruments, together with
relevant standards, which he intends to use in the regulation, testing and balancing of
the Contract Works. The Contractor shall include the full cost of regular calibration test
to be carried out on all instruments used and the cost of any necessary recalibration.
Certified documentation confirming current certificate calibration shall be available for
examination by the Engineer at all times. Instruments not supported by up-to-date
calibration certificates shall not be used.
All instruments necessary for conducting the test shall be provided including the
following minimum range :
Tube type velometer ( Range 1.5 to 13 m/sec).
Sloping tube manometers.
Pitot tubes of various length to suit duct sizes.
Mercury in glass thermometers.
Weekly recording thermometers.
Weekly recording R.H. meters.
Specially mounted anemometers fixed in a conical sheet metalwork hood for measuring
accurately air flow from diffusers.
Ammeters.
Tachometers.
Surface contact dial indicating pyrometer.
Hot wire digital anemometers.
Sound meters.
Digital touch thermometers.
Multi-channel digital thermometers ( where necessary ).
U tube manometers.
Commissioning set electronic flow meters.
Brass cased certified thermometers.
The Contractor shall prepare and submit with his Tender a schedule of recommended
test equipment suitable for Technician Grade maintenance staff to assess whether the
commissioned standards are being maintained. Whilst the level of equipment need not
be comparable to the Specialist Commissioning Contractors own test equipment it
should meet the following requirements :
a)
b)
Page 3 of 13
c)
4.
Water flow measurement using commissioning valves sets provided under the
Mechanical Services Contract.
Final Report
a.
b.
All test reports shall be assembled, indexed, and submitted to the Engineer.
Page 4 of 13
PART 2 - PRODUCTS
NOT USED
PART 3 - EXECUTION
3.01
A.
The Contractor shall make the necessary adjustments for each system and piece of
apparatus installed, using factory-trained technicians wherever practicable, and shall
thoroughly instruct the client appointed representatives in the roper operation of the
apparatus. Printed instructions written in both Arabic and English, shall be permanently
attached to the relevant equipment.
3.02
TESTING GENERALLY
A.
B.
Unless otherwise indicated, the Contract shall include the cost of all tests, necessary
instruments, equipment, supervision and labour both at the manufacturers plant and on
site. The accuracy of the test instruments shall be demonstrated where so directed.
C.
The site test shall be of at least six hours duration. On large installations, the site test
may last several days and shall be long enough to allow the taking of all the
measurements required in subsequent clauses of this Section and to demonstrate the
performance of the installation. Any defects of workmanship materials and
performance, maladjustments or other irregularities which become apparent during the
tests shall be rectified by the Contractor at his expense and the tests shall be repeated at
the Contractors expense to the satisfaction.
D.
The Contractors representative present at the site tests shall be fully conversant with
the operation of the thermostatic controls, the control panel and the refrigeration
system, representatives of the manufacturers of the equipment shall be present,
3.03
A.
Unless otherwise indicated, tests shall be carried out in accordance with the appropriate
Standard or Code or Practice. Test certificates for works tests shall be submitted
induplicate.
B.
For Fans : Type test certificates showing fan characteristic curves and type test
certificates for sound levels.
2.
For Pumps : Type test certificates for head, discharge, speed and power input.
3.
For Electrical Motors : Type test certificates for motors of 40 KW output and
above, routine ( individual ) test certificate.
Page 5 of 13
4.
For Starters and Control Gear : Type test certificates for control panels as a
whole, routine ( individual ) high voltage test.
5.
6.
For Hydraulic Equipment : Test certificates for hydraulic and air pressure
testing at works.
3.04
A.
Upon the completion of each length or section of the pipework the Contractor shall
subject the length or section to a hydraulic test and demonstrate to the satisfaction of
the Engineer that the length of the section is sound and watertight. The test pressure
shall be one and a half times the maximum working pressure or 700 KPa, whichever is
the greater, for a period of two consecutive hours. Items of equipment, e.g. safety
valves, bursting discs, set to operate at or below this pressure shall be isolated or
removed prior to applying this test.
B.
All faults discovered during such-test- shall be remedied by the Contractor at his own
expense and the test re-applied until the Engineer is satisfied that the section is sound
and watertight.
C.
D.
All pressure tests shall be carried out before the application of thermal insulation.
E.
On completion of the test, the water is to be released and drained completely away as
rapidly as possible, the section then being thoroughly sluiced through to ensure the
removal of as much dirt and foreign matter as possible before being refilled and put
into service.
3.05
A.
General
1.
All ductwork and equipment items shall be checked for air leakage. This shall
be completed before installation or enclosure of ductwork and before any
terminal units are fixed.
2.
The air leakage tests shall be based on the measurement of air leakage at
constant pressure. The test pressure shall be the design static pressure of the
section to be tested plus 250 pa. The aggregate of air leakage shall not exceed
1% of the system design air flow rate, and leaks shall not be audible. The air
leakage rate for any section shall not be in excess of the permissible rate, in
m3/s per meter, for the whole system.
3.
Sufficient time shall be allowed, before testing, for the sealant to cure. The
ductwork system, or section to be tasted shall be sealed by the incorporation of,
blanking plates fitted at flanged joints, for main ducts and for small open ends,
Page 6 of 13
polythene bags may be used. The polythene bags may be retained to aid in
preventing the ingress of dirt into the system.
4.
B.
Portable test apparatus shall be provided by the Contractor and shall comprise
the following equipment: Electrically driven fan capable of delivering not less
than 0.03m3/s against a duct pressure of 2.5 Kpa, a static pressure gage
suitable for recording the duct static pressure test, an inclined pressure gage, a
variable speed type, and a flow measuring device complete with test cocks.
The accuracy of the measuring device shall be +/-5% of the permitted air
leakage rate.
2.
The apparatus shall be connected to the blanking plate inserted in the section of
ductwork to be tested. With the bleed valve fully open or the variable speed
motor set to minimum speed, start-up fan, and adjust fan speed or close bleed
valve until static pressure reading on static pressure gage reaches desired value.
If pressure cannot be obtained, the ductwork shall be checked for obvious leaks
and rectified. With the duct section maintained at the test pressure, the
ductwork shall be checked for major and audible leaks. The leakage rate, as
indicated on the inclined pressure gage, connected across the flow measuring
device, shall be recorded and checked that it is within the permitted limits. This
leakage rate shall be maintained for at least 15 consecutive minutes without
increasing.
3.
The fan shall then be turned off and the pressure in the test section of duct
returned to zero before starting the fan again and establish that the air leakage
rate has not increased from the previous reading.
4.
Any results not within the permitted limits shall require that the ductwork be
examined and any leaks rectified. Time shall be allowed for the sealant to cure
before the test is restarted.
5.
Readings of the test for each section of ductwork shall be recorded and
presented to the Engineer before any further work is carried out on the section
of ductwork tested.
3.06
A.
On completion of the soil and waste pipe works or section of the work as may be
required the plumbing contractor shall arrange the testing of the works.
B.
The tests shall comprise an air test as set out in the Uniform Plumbing Code, and
described in section 15405, and a performance discharge test as required. Should the
Engineer deem the test unsatisfactory his visit shall at his desecration be considered
abortive and all costs incurred in respect of time, travel and expenses shall be
recoverable from the contractor who shall then rectify the works and arrange for a
further test to be witnessed at his own expense.
Page 7 of 13
C.
Where the testing is to be carried out in sections the Contractor shall retain on site a
drawing indicating sections tested and recording dates on which the tests took place
duly witnessed.
D.
The Contractor shall be responsible for providing all skilled and unskilled labor
necessary to carry out tests and ensure that all supplies and instruments are available.
3.07
COMMISSIONING GENERALLY
A.
General
B.
1.
2.
b)
c)
Adjustments
1.
Adjust blowers, fans and ducts to deliver or exhaust design air flow
rate.
b)
c)
d)
e)
Adjust all zones for design supply and return air flow rates.
f)
g)
h)
3.08
A.
Preparation :
Page 8 of 13
B.
1.
2.
3.
4.
Fan air handling quantities and other major air flow quantities where required,
shall be measured by pitot tube and inclined manometer using multi-point
traversing techniques.
2.
The following items shall be specifically checked and/or adjusted and recorded
on the Site Test Certificate for each air handling unit.
a)
b)
c)
Air dry bulb temperature and relative humidity in each main return
duct.
d)
Air dry bulb temperature and relative humidity before and after each
air heater.
e)
Air dry bulb temperature and relative humidity before and after each
air cooler.
f)
Air dry bulb temperature and relative humidity before and after a
humidifying equipment.
g)
Air dry bulb temperature and relative humidity before and after a fresh
and return air mixing chamber.
h)
Air dry bulb temperature and relative humidity in each main supply air
duct.
j)
k)
l)
m)
Page 9 of 13
n)
3.
C.
Air flow (m3/s) in each main supply, return a grille and diffuser.
b)
c)
Fan and ,motor speeds, air quantity and dry bulb temperature and
relative humidity, both on and off the cooling coil, for at least two of
each size fan of the cooler unit.
d)
e)
Current taken under running conditions for each fan above 4 KW and
each electric air heater, and maximum current for each electric air
heater.
f)
Record Data
Record the following minimum data :
1.
2.
3.
4.
5.
Air flow rate, delivery or exhaust at each diffuser, register and grille.
3.09
A.
Preparation :
Prior to system testing and balancing
1.
Open all valves to full open position. Close coil bypass stop valves. Set mixing
valves to full coil flow.
2.
3.
Examine water in system and determine if water has been treated and cleaned.
4.
Page 10 of 13
B.
5.
Clean and set automatic fill valves for required system pressure.
6.
Check expansion tanks to determine that they are not air bound and the system
is completely full of water.
7.
Check air vents at high points of water systems and determine if all are
installed and operating freely.
8.
Set all temperature controls of all coils calling for full cooling. Same procedure
when balancing hot water coils : set for full heating.
9.
10.
11.
General
a.
C.
2.
3.
4.
5.
6.
7.
8.
Upon completion of flow readings and adjustments at coils, mark all settings
and record data.
9.
After adjustments to coils are made, recheck settings at pumps and readjust if
required.
10.
Install pressure gages in gage fittings provided on coil, read pressure drop
through coil at set flow rate for full cooling and on full heating. Set pressure
drop across bypass valve to match coil full flow pressure drop.
Record Data
Page 11 of 13
2.
3.
4.
5.
6.
List all mechanical specifications of pumps. Check and record starter size,
heater sizes, etc.
7.
8.
3.10
A.
The following items shall be checked and/or tested and entered on the Site Test
Certificate:
a.
b.
c.
d.
e.
f.
3.11
CONTROL SYSTEMS
A.
B.
1.
2.
The following items shall be checked and/or tested and recorded on the Site Test
Certificate :
Page 12 of 13
1.
2.
3.
3.13
A.
Sound level readings shall be taken with a simple sound level meter using the A scale
weighting network. The spaces in which readings shall be taken as agreed but will in
general, be the following :
B.
1.
Equipment rooms.
2.
3.
Outside equipment rooms facing air intakes and exhausts and condensing
discharge, to assess possible nuisance to adjacent accommodation, if the
adjacent accommodation is private residential building tests may be required at
night.
4.
In the space served by the first grille or diffuser after a fan outlet.
5.
Alternatively, sound level readings shall be taken using a sound analyses to give an
octave band analysis of the sound spectrum and to pinpoint the frequency values of
peak sound levels.
END OF SECTION
Page 13 of 13