Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
TRANSMISSION LINES
The 14 bus system contains 15
transmission line has same length with different rsistance,
reactance and susceptance per unit length depending on the
material. However, since the length of transmission line does not
affect the analysis, only the per unit parameters are present in
APPENDIX A1.The data in the table are Pu system at base voltage
of100KV and 100MVA the resistance, impedance and susceptance
are given for the total length of transmission lines.
TRANSFORMER
The transformer data consists of R T(Resistance)
and xT (Reactance) which are the equivalent of the primary and
secondary windings of the transformer the APPENDIX A2 provides
the transformer parameters. All the data in the table are in per
unit based on 20KV for the primary windings and 345 KV for the
secondary.
GENERATORS
There are 5 generators in the system the 5
generators are connected to bus through 1, 2,3,6,8 buses. Bus 1
is considered as slack bus, while remaining 4are called PV Buses.
The 9 remaining Buses are all called PQ Buses. The APPENDIX A3
gives the initial load flow condition of the 5 generator Buses. All
the values are based on 100 MVA and the machines rated
terminal voltages. The APPENDIX A4 gives the generators rated
voltage, inertia, resistance, leakage reactance and time
constants.
LOADS
FIGURE-2
LOAD FLOW RESULT OF 14 BUS SYSTEMS
By NEWTON
RAPHSON technique for load flow analysis with base MVA as 100
and nominal system frequency is 50 HZ. Bus number 1 is taken as
slack bus.
The bus voltages and powers obtained from load flow analysis are
shown below in table 1.
BUS1
1.0600
ANGL
E
DEGR
EE
0.000
BUS2
1.0450
-5.01
40.000
BUS3
1.0100
0.000
BUS4
1.0184
BUS5
1.0207
12.77
10.40
-8.85
0.000
0.000
7.6
BUS6
1.0700
0.000
BUS8
1.0900
BUS
9
BUS
10
BUS
11
BUS
12
BUS
13
BUS
14
DUM
0001
1.0479
14.22
13.68
15.20
15.31
14.89
15.51
15.61
16.43
13.59
0.000
11.60
4
19.85
4
0.000
0.000
0.000
0.000
0.000
0.000
6.100
0.000
13.50
0
14.90
0
0.000
11.2
0
0.00
0
29.5
0
9.00
0
3.50
0
1.60
0
5.80
0
5.00
0
0.00
0
10
11
12
13
14
15
1.0442
1.0534
1.0360
1.0098
1.0129
1.0579
MW
GENERATI
ON
MVAR
GEN
233.865
0.000
17.37
8
42.56
6
23.49
5
0.000
0.000
0.000
0.000
MW
MVA
LOAD R
LOA
D
0.00 0.00
0
0
MVA
R
COM
P
0.00
0
21.7
0
94.2
0.00
0
0.00
0
0.00
0
0.00
0
0.00
0
0.00
0
0.00
0
0.00
0
0.00
0
0.00
0
0.00
0
0.00
0
0.00
0
47.8
12.7
19.0
0
3.90
1.60
0
7.50
0
0.00
0
16.6
0
5.80
0
1.80
0
1.60
0
5.80
0
5.00
0
0.00
0
273.865 MW
80.140 MVAR
0.000 MW
0.000 MVAR
0.000 MVAR
259.000 MVAR
73.500 MVAR
0.962
0.000MVAR
0.000MVAR
14.864656
MW(14.864656+0.000000)
5.428
27.502365 MVAR
BUS 4
MACHINE CONNECTED TO
FAULTED BUS
GENERATOR-3
LINE-3(BUS 3 TOBUS 4)
1 SEC
1.1SEC
0 SEC
3 SEC
TABLE-3
SWING CURVE
FIGURE-3
FIGURE-4
FIGURE-5
1 SEC
1.2 SEC
0 SEC
3 SEC
TABLE-4
SWING CURVE
FIGURE-6