Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
The Age of
By Patrick E. Halm P.E., Life Member ASHRAE
for river otters, how do you control humidity to keep visitors from
feeling like theyre swimming with the fish? That was only one
Mechanical Systems
ASHRAE Journal
June 2007
Aquariums
Design Criteria
Outdoor Conditions
17
ASHRAE Journal
ashrae.org
Chilled Water
Hydronic Heating
outdoor air, lighting, walls, roof and glass. Internal latent loads
are generally from people and evaporation with the evaporation
loads significant relative to other load elements. The effectiveness
of controlling the gallery environment depends on an effective
estimation of water evaporation rates.
With more than 8 million gallons (30 283 kL) in circulation,
the rate of evaporation is a critical calculation, as much for indoor
environmental concerns, including temperature and humidity, as
Gallery Conditioning
ASHRAE Journal
19
(1)
where
wp = evaporation rate of water, lb/h
A = area of pool surface, ft2
v = air velocity over water surface,
fpm
hfg = latent heat required to change
water to vapor at temperature of
surface water, Btu/lb
pa = saturation vapor pressure at dew
point temperature of
ambient air, in. Hg
pw = saturation vapor pressure at
temperature of surface water,
in. Hg
Of interest, this same equation, in
somewhat different form, is included in
the 2003 ASHRAE HandbookHVAC
Applications to predict a rate of evaporation for loads related to natatoriums. In
the case of open tanks, splashing is not
typical and wetted decks are unusual. The
evaporation rates are typically less.
A
wp = ( pw pa)(95 + 0.425 v)
(2)
Y
where
wp = evaporation of water, lb/h
A = area of pool surface, ft2
v = air velocity over water surface,
fpm
Y = latent heat required to change
water vapor at surface water temperature, Btu/lb
pw = saturation pressure at room air
dew point, in. Hg
pa = saturation vapor pressure taken at
surface water temperature, in. Hg
The units for the constant 95 are
Btu/(hft2in. Hg).
June 2007
(3)
(4)
where
Q = quantity of air, cfm
= standard air density, 0.075 lb/ft3
Wi = humidity ratio of pool air at design
criteria, lb/lb
Wo = humidity ratio of outdoor air at
design criteria, lb/lb
(5)
21
Engineered smoke control in the plaza and galleries is designed so occupants have enough time to egress the building
while tenable conditions are maintained. The system provides a
high level of safety for the occupants of the plaza during design
fire scenarios. The systems and control provided in the galleries and plaza comply with the performance and prescriptive
requirements allowed for Smoke Protected Assembly Seating
(Section 8-4.1 of the Life Safety Code) and the 2000 edition
of the Life Safety Code.
All of the air handlers and associated smoke control equipment are energized from a standby power source.
The system has been designed to provide not more than
100% and not less than 80% of the smoke exhaust capacity
for makeup air. The air handler within the gallery of origin for
a fire scenario is programmed to shut down, with the systems
providing 100% outside air to un-involved galleries.
The required outside air is provided through the planned airhandling units. The required exhaust of 120,000 cfm (56 634
L/s) for the plaza smoke control is provided using dedicated
exhaust fans on the roof over the plaza. Design calculations
show compliance with NFPA 92B, which is the required standard, referred to by NFPA Life Safety Code.
The public gallery and plaza spaces that communicate with
each other are designed with smoke control systems and sprinkler systems that comply with Section 6-2.4.6 of the Life Safety
Code, 1997 edition and the 2000 edition of the Life Safety
Code. These code sections, along with Chapter 8 of the 1997
edition of the Life Safety Code, allow persons to exit through
the atrium. Persons exiting through the atrium have been added
to the population of the plaza level.
Automatic sprinkler zones and smoke control zones are coordinated. The gallery sprinkler zones are separated from the
plaza sprinkler zones. Complete automatic smoke detection and
listed beam detection are provided in the galleries and plaza.
Aquatic Life Support
The 6 million gallon (27 712 kL) Ocean Voyager tank is the
largest aquarium tank in the world and has more than 100,000
fish. Of all the aquarium tanks in the world, it is the heaviest
in biomass. This means that it has the highest ratio of fish per
gallon of water of any tank, more than two to three times heavier
than any other aquarium to date. The level of biomass loading
was the result of the aquarium owner wanting diversity and a
22
ASHRAE Journal
ashrae.org
June 2007
The need to ensure survival of the more than 100,000 fish and
safety for the aquariums visitors in the event of an electrical
power outage in Atlanta was addressed by providing a standby
power system to maintain all aquatic systems as well as lifesafety systems for visitors. The generators used for standby
power are capable of producing more than 6 MW of power,
which is enough to power 250 homes.
Three generators provide power for the critical aquatic systems for the animals. A separate emergency generator provides
power for the life-safety systems for the human visitors.
In the first few minutes following a
power loss most of the aquarium staff
would be busy coordinating the safety of
the visitors. For this reason, the standby
power system was designed to start and
configure itself automatically, placing
the critical and emergency systems into
a safe mode that can operate autonomously until the staff has time to take
over manual operation. The standby power
system makes full use of the installed
generating capacity, but as a precaution,
to protect against possible overload in the
event one of the generators fails, a rudimentary load sequence/load shed control
system was developed that prioritizes the
loads that are connected to the standby
power.
The generators can also be used during an electrical energy emergency, or
brown-out, to reduce the amount of
electricity the aquarium draws from the
citys electrical power grid.
The basic challenge for designing the aquarium was dealing with the extremely technical nature of the designs while
meeting the client requirement for a creative theme. The team
continually balanced creativity with practicality. The result is a
world-class aquarium with a safe and comfortable environment
for animals and humans.
Lighting
ASHRAE Journal
23