The Fire Code, first introduced in 1974, is a living document which
is periodically reviewed by the SCDF in ensuring that the fire safety
standards keep pace with the changing building landscape and reflect the
needs of the building industry. Its evolution is influenced and shaped by the
local building industrys practices, experiences and architectural heritage
based on feedback which the SCDF had received from QPs through the
consultation sessions, dialogues, and Standing Committee Meetings.
The latest 7th edition of the Fire Code, published in January 2013,
is the result of concerted efforts put in by members of the Fire Code
Review Committee, led by the SCDF. Its members comprise esteemed
representatives from SCDFs stakeholders of professional bodies, academia
and statutory boards namely: SIA, IES, IFE, ACES, REDAS, NTU, NUS, BCA,
LTA, TUV SUD PSB and HDB. The revised code involved many months of
deliberation by the committee members on a slew of changes made in the
past 5 years.
In the process of review, the committee was guided by the need for
a code that not only emphasizes on fire safety but one that is user-friendly,
pro-business and keeps pace with the latest developments. The review
also utilizes research studies based on fire engineering tools to improve
the quality of the Fire Code requirements. One of the key changes of the
code is the incorporation of new fire safety features within buildings to
facilitate the evacuation of persons with disabilities during an emergency
situation.
Prior to the publication of the latest edition of the Fire Code,
the SCDF had already disseminated some of the changes in the code to
the members of the building industry via circulars. These changes were
also discussed and presented in SCDFs recent fire safety seminars. In
addition, to aid the users of the Fire Code to interpret the latest changes
and appreciate their rationale, the Fire Code Handbook, through its rich
diagrammatic illustrations, will be updated by the SCDF by mid 2013 to
reflect these changes.
Through the years, SCDF and its stakeholders have successfully
built sound and reputable fire safety standards in buildings. This is
something which we can all be proud of and a standard we must continue
to upkeep. In essence, we must continue to be nimble and keep abreast of
latest operating environment such as the new building designs which are
increasingly sophisticated in nature, requiring ingenuity, innovation and
creativity to be infused into the building architectural as well as fire safety
building design requirements.
SCDF has and will continue to welcome feedback and suggestions
on the fire safety requirements and I look forward to the building industrys
continued support and stakeholders strong partnership with the SCDF in
periodically reviewing and enhancing the document.
On that note, allow me to place on record my appreciation for the
Fire Code Review Committee for assiduously putting together a robust
and comprehensive 7th edition of the Fire Code. Let us continue to make
Singapore a fire safe city to live, work and enjoy in.
ERIC YAP
COMMISSIONER
SINGAPORE CIVIL DEFENCE FORCE
January 2013
Deputy Chairman
Mr Boo Geok Kwang
Secretary
Maj Cheong Yew Dong
Editor
Mr Tan Eu Seng, Randy
Members
Mr Song Yew Kee
Mr Alfred Cheng Ho Ho
Ms Tan Lily
AC Christopher Tan
CHAPTER 1
GENERAL
ROOT OBJECTIVES
There are no root objectives for this chapter.
SUB-OBJECTIVES
There are no sub-objectives for this chapter.
1(I)
CHAPTER 1
1.1
GENERAL
The code serves to establish the minimum requirements for
fire safety provisions. It takes into account the function, design,
management, operation, and maintenance of buildings to secure
the life safety of occupants in the event of a fire.
This chapter lists the Appendixes for specific buildings or usage
and the definitions of the commonly used terms in the code.
1.1.1
1.1.1.1
1.1.1.2
1.1.2
1.1.3
1.1.4
1.1.5
1.1.6
1.1.7
1.1.8
1.1.9
1.1.10
1.1.11
1.1.12
1.1.13
1.1.14
1.1.15
1.1.16
1.1.17
Circular dated
15th Nov 2003
Circular dated
15th Apr 2008
1.1.19
1.1.20
Circular dated
14th Dec 2008
Circular dated
26th Nov 2008
Circular dated
27th Nov 2008
Circular dated
22nd Feb 2010
1.1.23
Circular dated
21st Jan 2011
Circular dated
25th Mar 2011
1.1.26
Circular dated
6th Dec 2011
Circular dated
17th Aug 2012
1.1.27
Circular dated
20th Jan 2010
1.2
DEFINITIONS
1.2.1
The abbreviations listed in the following table are used in this Code:
Abbreviation
BS
CP
Cl.
NFPA
AS
ISO
SS
ASTM
EN
Abbreviation
Definition
British Standard
Code of Practice
Clause
National Fire Protection Association
Australian Standard
International Organisation For
Standardisation
Singapore Standard
ASTM International
European Norm
1.2.1(A)
1.2.2
Approved
1.2.2(A)
Ancillary office
1.2.2(B)
(a)
Ancillary usage
Table 1.2.1A
Minimum Air-well size
Max. Habitable Height of
Min. Clear width of Air-well
Building
18m
10m
24m
11m
36m
12m
48m
13m
60m and above
14m
1.2.4
1.2.5
Area of Building
(a) The area of any storey of a building or compartment shall
be taken to be the total area of that storey bounded by the
inner finished surfaces of the enclosing walls or, on any side
where there is no enclosing walls, by the outermost edge of
the floor on that side.
(b) The area of any room or space shall be taken to be the total
area of its floor bounded by the inner finished surfaces of
the walls forming the room or space.
(c) The area of any part of a roof shall be taken to be the actual
visible area of such part measured on a plane parallel to the
pitch of the roof.
(a) In the building under consideration, an area of refuge is
an area adequately separated from the rest of the building
by fire resisting construction (see Cl.3.3 for details), and
evacuees from the rest of the building enter the area of
refuge using an external corridor that links this area to the
rest of the building. An area of refuge may serve as required
exit in lieu of the provisions given under Cl.1.2.24.
(b)
An area of refuge may also be an area in an adjoining building
which is separated from the building under consideration
by fire resisting construction and evacuees similarly enter
this area of refuge using an external corridor.
(c) An area of refuge shall always be accessible.
Area of building
Atrium
Atrium
Area of refuge
1.2.6
Basement Storey
(a)
A storey of a building which is below the first storey and the
floor of which is situated at such a level that more than half
the height of such storey is below the level of the ground
adjoining its perimeter walls for more than half the length
of such perimeter walls, and
(b) Where the building has no storey above ground, a storey
the floor of which is situated at such a level that either the
whole storey is below ground or more than half the height
of such storey is below the level of the ground adjoining
its perimeter walls for more than half the length of such
perimeter walls.
Basement
storey
1.2.7
Boundary
1.2.8
Construction provided :
Cavity barrier
(a)
(b)
1.2.9
Ceiling
1.2.10
Circulation
space
1.2.11
Code of
practice
1.2.12
Compartment
1.2.13
Compartment wall
& compartment
floor
1.2.14
Concealed space
(cavity)
1.2.15
Corridor
1.2.16
Cubical extent of
building or
compartment
1.2.17
Dead-end
1.2.18
Direct distance
1.2.19
Door
1.2.20
Electromagnetic
or electromechanical
device
susceptible to
smoke
(a)
(b)
(c)
(d)
1.2.21
Element of Structure
(a)
(b)
(c)
(d)
(e)
(f)
Element of
structure
Emergency
generator
Emergency
lighting and
exit lighting
1.2.23
1.2.24
Exit
1.2.25
Exit door
Exit access
1.2.26
Exit passageway
1.2.27
Exit staircase
1.2.28
External
cladding
1.2.29
(a)
External exit
staircase
(b)
1.2.30 An exit passageway open to the outdoor air, that serves as a required
exit.
External exit
passageway
External wall
(or side of a
building)
1.2.32
Fire resistance
1.2.33
Fire stop
1.2.34
Fire-fighting
lobby
1.2.35
Flexible joints
and flexible
connections
(a)
(b)
1.2.35(A) Fire Engine Access Road
An access road to allow a fire fighting appliance to move from one
location to another within a development for fire fighting purpose/
operation. It shall comply with clause 4.2.2.
1.2.35(B) Fire Engine Accessway
1.2.36
Habitable floor
The habitable height is the height measured from the lowest level
of fire engine accessway or access road (applicable to buildings
under Purpose Group II) to the finished floor level of the highest
habitable floor.
Habitable height
1.2.38
Height of
building
1.2.39
High hazard
occupancy
1.2.37
(b)
(c)
(d)
(e)
1.2.40
Load-bearing
wall
1.2.41
Masonry
1.2.42
Noncombustible
material
(a)
(b)
(c)
1.2.43
Non load bearing wall means a wall which supports no load other
than its own weight.
Non load
bearing wall
1.2.44
Notional
boundary
1.2.45
Occupant load
(a)
(b)
1.2.46
Permitted limit
of unprotected
area
1.2.46(A) Private lifts are passenger lifts which are meant for the exclusive
use of occupants in the building, and are located to open its door
directly into private enclosed spaces. Private lifts shall exclude
vehicle lifts, home lifts and stair lifts.
Private lifts
1.2.47
Protected shaft
1.2.48
Protecting
structure
(a)
(b)
(c)
A roof.
1.2.49
Public building
1.2.50
Purpose group
1.2.52
1.2.53
Rooflight
1.2.54
Room
1.2.55
Separated part
(of a building)
1.2.56
1.2.57
Separating wall
Smoke check
door
Smoke-stop
lobby
1.2.51
1.2.58
1.2.58(A) Storey
A storey means any floor or part thereof including platform,
mezzanine, attic level and M&E floor.
1.2.58(B) Tenancy unit refers to an individual unit or subdivided unit within
a building or a compartment, and which is managed by a different
operator registered with the Accounting and Corporate Regulatory
Authority (ACRA).
Relevant
boundary
Storey
Tenancy unit
1.2.59
1.2.60
Travel distance
an exit staircase, or
an exit passageway, or
an open exterior space,
unless otherwise permitted under this Code as in the case of
hotel bedrooms (Cl.2.7.3), residential apartments or maisonettes
(Cl.2.4.7) and exit to Area of Refuge (Cl.2.2.6(f)).
Where more than one exit is required from a building or portion
thereof, such exits shall be remotely located from each other and
shall be arranged and constructed to minimise the possibility that
more than one can be rendered unusable by any one fire or other
emergency condition.
(a) If two exits or exit access doors are required, they shall
be placed at a distance from one another equal to or not
less than half the length of the maximum overall diagonal
dimension of the building or area to be served, measured in
a straight line between the furthest edges of the exit doors
or exit access doors (see diagram 1.2.60(a)(i) to (v)), subject
to :
(i) If the distance between the 2 exits or exit access doors
is less than half the length of the maximum overall
diagonal dimension of the building or area to be served,
it shall be considered as a one-way escape arrangement;
and
(ii) The separation distance measured in a straight line
between the furthest edges of the doors of the two
exits (exit staircases, exit passageways or exit ramps)
shall not be less than 7m.
Two-way escape
(Remoteness of
exits)
(b)
Reduction in exit
separation
Two-way escape
(c)
(d)
1.2.61
Exit separation
measured along
exit access
corridor
One-way travel
Unprotected
area
1.2.62
1.2.63
Vertical exit
Wall surface
but excluding:
(i) door frames and unglazed parts of doors, and
Table1.2A
1.2AOccupancy
Occupancy Load
Table
LoadTables
Tables
Schedule 2
Purpose Group II
Residential.
Schedule 3.1
Schedule 3.2
Schedule 3.3
Schedule 4
Purpose Group IV
Schedule 5
Purpose Group V
Schedule 6
Purpose Group VI
Schedule 7.1
Schedule 7.2
Community Centres.
Schedule 7.3
Schedule 7.4
Schedule 7.5
Public Libraries.
Schedule 7.6
Religious Buildings.
Schedule 7.7
Schedule 7.8
Schedule 7.9
Schedule 7.10
Schedule 8
18
Table
1.2B
Designation
of Purpose
Groups
Table
1.2A
Occupancy
Load Tables
Purpose
Group
Descriptive
Title
Small residential
II
Other residential Accommodation for residential purposes other than any premises
comprised in Group I to include flats, maisonettes, apartments etc.
III
Institutional
IV
Office
Shop
VI
Factory
VII
Place of public Premises used for social, recreational or business purposes to include
resort
hotels, holiday
resorts, boarding houses, service apartments,
convention centres, private clubs, community centres, museums,
public art galleries, exhibition centres, theatres, cinemas, concert halls,
public libraries, religious buildings, public sports complex, stadium,
public swimming complex, recreational buildings, amusement centres,
eating houses, restaurants, coffee shops, hawker centres, fast food
outlets, bus terminals, train stations, airport and ferry terminals.
VIII
Storage
19
SCHEDULE 2
OTHER RESIDENTIAL
APARTMENTS, MAISONETTES
FUNCTIONAL SPACES
REMARKS
15.0
non-simultaneous
5.0
OCCUPANCY LOAD-
SCHEDULE 3.1
PURPOSE GROUP-III
INSTITUTIONAL
BUILDING TYPES -
HEALTH-CARE OCCUPANCY
(HOSPITAL, CLINIC & POLYCLINIC)
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/
Visitors Lounge
Out-patient Waiting Area
non-simultaneous
OCCUPANCY LOAD
(m2/person)
3.0
3.0
1.5
Admin Offices
Doctors Offices
Nursing Station
Staff Lounge
10.0
10.0
10.0
3.0
Consultant/Treatment/
Examination Room
Therapy Centre
Operation Theatre
Surgical Viewing Gallery
Patient Accommodation
5.0
Intensive Care
Room (max 2 beds)
Ward
10.0
7.5
3.0
20.0
10.0
10.0
Laboratories
Pharmacy
20.0
20.0
Kitchen/Housekeeping
Laundry*(1)
Toilet/Locker/ Changing Room
10.0
10.0
non-simultaneous
Storage
Canteen
Restaurant
Shop
30.0
1.5
1.5
5.0
----
OCCUPANCY LOAD-
SCHEDULE 3.2
PURPOSE GROUP-III
INSTITUTIONAL
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
Admin Office
Staff Office
Library/Reading Room
non-simultaneous
Stack Area
Reading Area
Common Room
Multi-purpose Room
Student Bedroom
Wardens Accommodation
Sleeping Quarters/ Dormitories
Detention Room
Sick Room
Toilets/Bath/ Changing Rooms
OCCUPANCY LOAD
(m2/person)
3.0
3.0
10.0
10.0
10.0
5.0
1.5
1.5
non-simultaneous
non-simultaneous
1.5
1.5
10.0
Laundry*(1)
Service Area
Storage Area
Dining/Canteen
10.0
10.0
30.0
1.5
Shop
5.0
30.0
----
OCCUPANCY LOAD-
SCHEDULE 3.3
PURPOSE GROUP-III
INSTITUTIONAL
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
non-simultaneous
Admin Office
Staff Office
Class Room
Computer Classroom
Seminar Room
Lecture Room
Library
3.0
3.0
10.0
10.0
Commercial School
Others
1.5
1.5
3.0
Stack Area
Reading Area (School)
(Others)
1.5
1.5
10.0
5.0
5.0
*School/Colleges
Others
1.0
1.5
Stage Area
Viewing Gallery
Design Studio
Laboratories
Workshop
Club/Society Room
Sick Room
Storage Area
Kitchen/Service Area
Toilets/Changing Room
Canteen
Mechanical Plant Room
OCCUPANCY LOAD
(m2/person)
3.0
1.5
5.0
5.0
5.0
non-simultaneous
non-simultaneous
1.5
30.0
10.0
1.5
30.0
----
* Where school are provided with both Multi-purpose Hall and Indoor Sport Hall (ISH), the occupancy load for ISH
can be based on 3m/person instead of 1m/person
OCCUPANCY LOAD-
SCHEDULE 4
OFFICE
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
non-simultaneous
Admin Office
Business Centre
Meeting/Seminar Room
Archive/Library
Stack Area
Reading Area
OCCUPANCY LOAD
(m2/person)
3.0
3.0
10.0
10.0
1.5
10.0
5.0
Filing Room/Store
Computer Room
Design Studio
Drafting Office
Trading Floor
Trading Gallery
Banking Hall
Deposit/Strong Room
Machine/Printing Room*(2)
10.0
5.0
5.0
5.0
2.0
1.5
3.0
30.0
10.0
Restaurant
Canteen
Staff Canteen
Shop
Toilets
Storage Area
Mechanical Plant Room
1.5
1.5
1.5
5.0
30.0
30.0
non-simultaneous
Aboveground or underground
pedestrian linkways with
commercial activities
2.0
----
OCCUPANCY LOAD-
SCHEDULE 5
PURPOSE GROUP V-
SHOPS
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby
Fixed Corridors
Waiting Area/Visitors Lounge
Atrium Floor/Concourse
Exhibition/Promotion Area
non-simultaneous
non-simultaneous
OCCUPANCY LOAD
(m2/person)
3.0
3.0
3.0
1.5
Shop Floor
Showroom
Supermarket/Bazaar
Department Store
5.0
5.0
5.0
5.0
Restaurant
Canteen
Cafeteria
Fast Food Outlet
1.5
1.5
1.5
1.0
Admin Office
Toilets/Staff Rest Room
non-simultaneous
10.0
Storage
30.0
30.0
Aboveground or underground
pedestrian linkways with
commercial activities
2.0
----
OCCUPANCY LOAD-
SCHEDULE 6
FACTORY
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
non-simultaneous
Admin Office
Meeting/Seminar Room
Library
Stack Area
Reading Area
OCCUPANCY LOAD
(m2/person)
3.0
3.0
10.0
1.5
10.0
5.0
Workshop
Laboratories
Exhibition
10.0
5.0
1.5
Production Area*(2)
10.0
Packing/Distribution Area
Material/Product
General Storage
10.0
30.0
Multi-purpose Area
Staff Recreation Room
Staff Rest Room
Staff Canteen
Toilets/Changing/ Locker Room
Sick Room
non-simultaneous
non-simultaneous
non-simultaneous
non-simultaneous
non-simultaneous
1.5
1.5
30.0
----
OCCUPANCY LOAD-
SCHEDULE 7.1
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
Atrium Floor/Concourse
non-simultaneous
OCCUPANCY LOAD
(m2/person)
3.0
3.0
3.0
Guestroom/Accommodation unit
Backpacker hotel
Serviced Apartment
Per unit
15.0
Bar/Pub
Discotheque
Night Club
Restaurant
Gross area
Gross area
Gross area
1.0
1.0 (including dine & dance area)
1.5 (including dine & dance area)
1.5
Exhibition/Multi-purpose area
Function/Ball Room
Pre-function Room
Business Centre
Admin Office
Conference Room
Meeting/Seminar Room
Library
Shop
Health Club/Centre/SPA*(3)
Swimming Pool Deck
Swimming Pool
Squash Court
Staff Rest Room
Staff Canteen
Toilets/Changing/ Locker Room
Kitchen/Service Area
Laundry*(1)
Mechanical Plant Room
non-simultaneous
Stack Area
Reading Area
2 per court
non-simultaneous
non-simultaneous
1.5
1.5
10.0
10.0
1.5
1.5
10.0
5.0
5.0
5.0
10.0
1.5
10.0
10.0
30.0
OCCUPANCY LOAD-
SCHEDULE 7.1
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
OCCUPANCY LOAD
(m/person)
Aboveground or underground
pedestrian linkways with
commercial activities
2.0
----
OCCUPANCY LOAD-
SCHEDULE 7.2
BUILDING TYPES -
COMMUNITY CENTRES
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
Concourse
Admin Office
Multi-purpose Hall
Meeting Room
Library
Health/Fitness Room/SPA*(3)
Games Room
Canteen/Cafeteria
Kitchen
Toilets/Changing Room
Storage Area
non-simultaneous
Stack Area
Reading Area
non-simultaneous
OCCUPANCY LOAD
(m2/person)
3.0
3.0
3.0
10.0
1.5
1.5
10.0
5.0
5.0
1.5
1.5
10.0
30.0
30.0
----
OCCUPANCY LOAD-
SCHEDULE 7.3
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
OCCUPANCY LOAD
(m2/person)
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
Concourse
Admin Office
Reading Area
non-simultaneous
3.0
3.0
3.0
10.0
Archive/Library
Stack Area
Reading Area
10.0
5.0
Exhibition Area
Auditorium/Theatre
1.5
1.5 (For Assembly occupancy, it can be
based on fixed seating for purpose of
computing occupant load)
Storage Area
Shop
Restaurant
Canteen/Cafeteria
Kitchen
30.0
5.0
1.5
1.5
10.0
non-simultaneous
non-simultaneous
30.0
----
OCCUPANCY LOAD-
SCHEDULE 7.4
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Foyer
Corridors
non-simultaneous
OCCUPANCY LOAD
(m2/person)
3.0
3.0
3.0
10.0
10.0
by numbers or
non-simultaneous
non-simultaneous
1.5
3.0
1.5
3.0
5.0
5.0
30.0
1.5
1.5
10.0
30.0
----
OCCUPANCY LOAD-
SCHEDULE 7.5
BUILDING TYPES -
PUBLIC LIBRARIES
FUNCTIONAL SPACES
REMARKS
Reception Area
Foyer
Lobby/Corridors
Waiting Area/Visitors Lounge
Admin Office
Library Area
Stack Area
Reading Area
OCCUPANCY LOAD
(m2/person)
3.0
3.0
3.0
10.0
10.0
5.0
Multi-purpose Room
Book/General Storage
3.0
1.5 (For Assembly occupancy, it can be
based on fixed seating for purpose of
computing occupant load)
1.5
30.0
Cafeteria/Snack Bar
Kitchenette
1.5
10.0
Toilets
Mechanical Plant Room
non-simultaneous
30.0
----
OCCUPANCY LOAD-
SCHEDULE 7.6
BUILDING TYPES -
RELIGIOUS BUILDINGS
FUNCTIONAL SPACES
REMARKS
Reception Area
Foyer
Lobby/Corridors
Waiting Area/Visitors Lounge
non-simultaneous
OCCUPANCY LOAD
(m2/person)
3.0
3.0
3.0
Admin Office
Meeting/Seminar Room
Class Room
10.0
1.5
1.5
Prayer Hall/Gallery
Choir Gallery
1.5
1.5
Crematoria
1.5
Mortuary
30.0
Refreshment Area
Kitchenette
Staff Quarter
1.5
10.0
15.0
General Storage
Toilets/Changing Room
Mechanical Plant Room
non-simultaneous
30.0
30.0
----
OCCUPANCY LOAD-
SCHEDULE 7.7
BUILDING TYPES -
PUBLIC SPORTS
COMPLEX.
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Concourse/Foyer
Waiting Area/Visitors Lounge
non-simultaneous
Admin Office
Meeting/Seminar Room
Multi-Purpose Sports Hall
Gymnasium
Training Area
Grandstand/Seating Area
Squash Court
COMPLEX,
STADIUM,
SWIMMING
OCCUPANCY LOAD
(m2/person)
3.0
3.0
3.0
10.0
1.5
3.0
3.5
3.0
1.5
2 per court
5.0
2.5
Restaurant
Cafeteria
Fast Food Outlet
Kitchen
1.5
1.5
1.0
10.0
General Storage
Toilet/Changing Room
PUBLIC
non-simultaneous
30.0
30.0
----
OCCUPANCY LOAD-
SCHEDULE 7.8
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
non-simultaneous
Admin Office
Meeting/Seminar Room
OCCUPANCY LOAD
(m2/person)
3.0
3.0
10.0
1.5
Bowling Alley
1.0
Amusement Park
Billiards Room
1.0
5.0
Skating Rink
Rink Area
Spectator Area
3.0
1.5
Discotheque
Pub/Bar
Karaoke Lounge
Night Club
Gross area
Gross area
Gross area
Gross area
Health Club/Centre*(3)
5.0
Restaurant
Cafetaria/Snack Bar
Fast Food Outlet
Kitchen/Service Area
1.5
1.5
1.0
10.0
Toilet/Changing Room
General Storage
Mechanical Plant Room
non-simultaneous
30.0
30.0
----
OCCUPANCY LOAD-
SCHEDULE 7.9
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area
non-simultaneous
Admin Office
Meeting/Seminar Room
OCCUPANCY LOAD
(m2/person)
3.0
3.0
10.0
1.5
Dining Area
Hawker Centres
Fast Food Outlets
Others
1.5
1.0
1.5
Bar/Pub
Lounge
Kitchen/Service Area
Gross area
1.0
2.5
10.0
Storage Area
Toilet/Changing Room
Staff Rest Room
Mechanical Plant Room
non-simultaneous
non-simultaneous
30.0
30.0
Aboveground or underground
pedestrian linkways with
commercial activities
2.0
----
OCCUPANCY LOAD-
SCHEDULE 7.10
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
Concourse
non-simultaneous
Admin Office
Meeting/Seminar Room
Ticketing Office
Business Centre
Passenger Arrival/
Departure Areas/Foyers
OCCUPANCY LOAD
(m2/person)
3.0
3.0
3.0
10.0
1.5
10.0
10.0
Bus Terminal
Others
1.5
3.0
Restaurant
Cafeteria
Fast Food Outlet
Kitchen/Service Area
1.5
1.5
1.0
10.0
Shop
5.0
non-simultaneous
non-simultaneous
30.0
30.0
Above-ground or underground
pedestrian linkways with
commercial activities
2.0
----
OCCUPANCY LOAD-
SCHEDULE 8
BUILDING TYPES -
FUNCTIONAL SPACES
REMARKS
Reception Area
Lobby/Corridors
Waiting Area/Visitors Lounge
non-simultaneous
OCCUPANCY LOAD
(m2/person)
3.0
3.0
Admin Office
Meeting/Seminar Room
Packaging Area
Goods Storage
General Storage
10.0
1.5
10.0
30.0
30.0
Loading/Unloading Area
4 per Bay
non-simultaneous
non-simultaneous
1.5
10.0
30.0
----
Note:
a)
b)
For building types not included in the above tables, occupancy load calculation shall be based on the
figures established for buildings within the same purpose group, or as otherwise determined by the
Relevant Authority.
*(1)
Laundry Areas equipped with machine operation, occupancy may be calculated at 15.0sq m per person.
*(2)
Production Area whether automated or not , shall be calculated on the basis of 10.0m per person
*(3)
Annex E
Occupant Load Factors for Roof Garden/Roof Terrace/Sky Garden/Sky Terrace
FUNCTIONAL SPACES
REMARKS
3.0
1.5
1.5
Depth/height of
sunken/elevated water feature
(permanent/fixed structure) less
than 300mm
3.0
Depth/height of
sunken/elevated water feature
(permanent/fixed structure)
300mm or more
3.0
5.0
----
Note: When A/A works are carried out at an existing roof garden , roof terrace, sky garden, sky terrace, regardless
whether the A/A works increase the occupant load, QP shall submit plans to SCDF for approval.
Diagram
1.2.17
DEAD-END CORRIDORS
c. Example of two common types of dead-end corridors. Both dead-end pockets serve as
traps because travel into them does not lead to an exit; the egress path must be reversed
to reach an exit staircase
37
Diagram
1.2.60(a)(i)toto(a)(iv)
(a)(iv)
Diagram 1.2.60(a)(i)
Diagram 1.2.60(a)(i)
Diagram 1.2.60(a)(iii)
Diagram 1.2.60(a)(ii)
Diagram 1.2.60(a)(iv)
38
Diagram 1.2.60(a)(v)
Diagram
1.2.60(a)(v)
39
Diagram1.2.60(c)
1.2.60(c)
Diagram
Remoteness of exits is measured along 1-hour rated corridor with hour fire doors.
In place of measuring physical distance between exit stair enclosures, distance for
purposes of determining remoteness is permitted to be measured along a protected
corridor.
40
CHAPTER 2
MEANS OF ESCAPE
ROOT OBJECTIVES
The primary intentions of this chapter are encapsulated in
the following statements:R2.1
R2.2
S2.1
S2.2
S2.3
S2.4
S2.5
S2.6
S2.7
S2.8
S2.9
S2.10
S2.11
Provisions
for
occupancies.
S2.12
S2.13
S2.14
temporary
2(II)
refuge
for
healthcare
CHAPTER 2
MEANS OF ESCAPE
2.1
2.1.1
2.2
GENERAL
The provisions of this chapter of the Code shall serve to express
the intentions for determining the design, construction, protection,
location, arrangement and maintenance of exit facilities to provide
safe means of escape for occupants from all buildings hereafter
erected, altered or changed in occupancy. Areas which are
designated as means of escape, such as exit staircase, fire-fighting
lobby, smoke-stop lobby, exit passageway, escape corridors shall
not be turned into other usage.
DETERMINATION OF EXIT REQUIREMENTS
The determination of exit requirements for a building shall be
based upon the type of use or occupancy of the building, the
occupant load, the floor area, the travel distance to an exit and the
capacity of exits as provided in Table 2.2A and herein. Every storey
of a building shall be provided with exit facilities for its occupant
load. Vertical exits provided from any storey above ground level
may serve simultaneously all storeys above the ground level and
vertical exits provided from any storey below ground level may
serve all storeys below ground level, subject to the provisions of
Cl.2.3.5 which prohibit basement staircases being continuous with
exit staircases serving the upper storeys, unless otherwise allowed
by the Relevant Authority.
General
Mixed
occupancy
2.2.3
Multiple
occupancy or
use
2.2.4
Nonsimultaneous
occupancy
2.2.1
2.2.2
2.2.5
Capacity of exits
and exit facilities
(b)
(c)
(d)
(e)
(f)
Determination of
travel distance
(g)
(h)
Ancillary office
within other
Purpose
Groups
2.2.7
(b)
(c)
2.2.8
2.2.9
Minimum
width
A single leaf swing door along the means of egress shall not
exceed 1250mm in clear width
Maximum
width
Measurement of
width
(ii) In the case of an exit door having 2-leaf and fitted with
an approved automatic flush bolt, the clear openings
shall be measured between the surface of one leaf to
the other door leaf when opened at an angle of 90
degrees; and
(iii) If one of the door leaves is bolted to the door frame and/
or floor by a manually operated bolt, this door leaf shall
not be considered for the purpose of determining the
exit capacity of the door.The opening of the other door
leaf shall have a clear width of not less than 850mm,
measured between the edge of the bolted door leaf and
the surface of the other door leaf, when opened at an
angle of 90 degrees;
(iv) Door hardware and handrails which do not protrude
more than 80mm into the clear width of exit opening
can be ignored.
2.2.10
Number of
exits from
rooms and
spaces
Maximum Occupant
Load with One Door
25
50
50
High Hazard
Patient accommodation area
Classrooms
Godowns, stores, and factories not
50
being of high hazard type
Assembly
50
Rooms and spaces with occupancy of more than 50 persons shall
comply with the requirements for `Number and Width of Exits'
under Cl.2.8.2 for Assembly Occupancy.
Note:
i.
ii.
iii.
iv.
v.
2.2.11
Number of exit
staircases or
exits per storey
2.2.12
All exits and access facilities shall be required to comply with the
following:
Location of
exits & access
to exits
(a)
(b)
(c)
2.2.13
Smoke free
approach to exit
staircase
(a)
External
approach
(b)
Smoke-stop
lobby
(c) Exception:
(i) The omission of smoke-stop lobby required under
Cl.2.2.13(b) to exit staircase of any building exceeding
4 storeys is allowed under the following situations,
provided the door opening into the exit staircases
shall be at least 1-hour fire resistance and fitted with
automatic self-closing device to comply with the
requirements of Cl.3.9.2:
(1) where the internal exit staircase is provided with
pressurization up to a habitable height of 24m in
compliance with the requirements of Chapter 7;
(4) in an open-sided car park floor where crossventilation is provided. Under this situation, the
fire door to the exit staircase can be -hour fire
rated.
(3) where the exit staircase is designated as firefighting staircase adjacent to a fire lift as required in
Chapter 6.
Omission of
smoke-stop
lobby is
allowed
Omission of
smoke-stop lobby
is not allowed
2.2.14
(b)
2.2.15
(c)
Smoke free
approach in
basement
Area of refuge
and exit
reduction
(c)
(d)
(e)
2.3
2.3.1
(b)
General
Location of the
signage
Colour of the
signage
2.3.2
Exit passageways
(a)
Exit passageways that serve as a means of escape or required
exits from any building or storey of a building shall have the
requisite fire resistance as specified under Cl.3.3.
(b) Internal exit passageway
(i) an internal exit passageway which serves as required
exit of the building shall be enclosed with construction
complying with the provisions of Cl.3.3, and
(ii) the enclosure walls of an exit passageway shall have
not more than two exit doors opening into the exit
passageway, and
(iii) exit doors opening into an exit passageway shall have
fire resistance rating as required for exit doors opening
into exit staircases, fitted with automatic self closing
device and complying with the requirements of Cl.3.9.2
for fire resisting doors, and
(iv) the minimum width and capacity of exit passageway
shall comply with the requirements as provided in
Table 2.2A, and
(v) changes in level along an exit passageway requiring
less than two risers shall be by a ramp complying with
the provisions under Cl.2.3.8, and
(vi) if the exit staircase which connects to the internal
exit passageway is pressurised, the internal exit
passageway shall not be naturally ventilated but shall
be mechanically ventilated, and it shall be pressurised
to comply with the requirements in Chapter 7.
(c) External exit passageway:
(i) an external exit passageway can be used as a required
exit in lieu of an internal exit passageway. The external
wall between the exit passageway and the rest of the
floor space can have ventilation openings of non
combustible construction, fixed at or above a level
1.8m, measured from the finished floor level of the
passageway to the sill level of the openings and such
ventilation openings shall be located not less than 3m
from any opening of an exit staircase, and
Fire resistance
Internal exit
passageway
External exit
passageway
2.3.3
(d) Ventilation
(i) all internal exit passageways shall be naturally ventilated
by fixed ventilation openings in an external wall, such
ventilation openings being not less than 15 per cent of
the floor area of the exit passageway, and
(ii) internal exit passageways that cannot be naturally
ventilated shall be mechanically ventilated to comply
with the requirements in Chapter 7.
Ventilation
Exit Staircase:
(a)
Internal Exit Staircase
Internal exit
staircase
Unprotected
Openings
(iv) Exception
Single storey
basement
car park
Standalone car
park
(b)
External exit
staircase
Exception
(c)
Discharge
(d)
Winders
Treads for
circular staircase
Handrails
Ventilation
Pressurisation
(h)
2.3.4
2.3.5
Scissor Exit Staircase
(a) Where two separate internal exit staircases are contained
within the same enclosure, each exit staircase shall be
separated from the other by non combustible construction
having fire resistance for a minimum period equal to that
required for the enclosure, and
(b) Such scissor exit staircases shall comply with all applicable
provisions for exit staircase, and
(c)
Door opening into scissor exit staircases shall be at least 7m
measured as travel distance between the two closer edges
of the staircase doors, and
(d) Where there is only one pair of scissor exit staircases, the
door opening into scissor exit staircases shall be spaced at
least 1/3 the diagonal dimension of the area to be served in a
sprinkler protected building and the diagonal dimension
in a non-sprinkler protected building in accordance with
Cl.1.2.60, and
(e) The ventilation openings of each staircase shall be located
on alternate storeys if such openings or windows are serving
both staircases on the same wall.
Basement Exit Staircase
(a) Any exit staircase which serves a basement storey of a
building shall comply with all the applicable provisions for
exit staircase, and
(b) Such exit staircase shall not be made continuous with any
other exit staircase which serves a non basement storey of
the building, and
Scissor exit
staircase
Basement
exit staircase
(c)
(d)
2.3.6
Separate
protected
shaft
Upper storey
staircase
continues into
basement
Entry at
basement
Barrier
Smoke-stop
lobby
Signages
Hardwood
staircase
Apartment or
maisonette unit
within
residential
building
2.3.7
2.3.8
Spiral Staircase
(a) Spiral staircases shall not serve as required exits except
that external unenclosed spiral staircases when built of non
combustible materials and having a tread length of at least
750mm may serve as required exits from mezzanine floors
and balconies or any storey having an occupant load not
exceeding 25 persons, and
(b) Such spiral staircases shall be not more than 10m high , and
(c) Spiral staircase shall not be designed as the sole means of
escape for buildings under Purpose Group I and maisonettes
and penthouses for buildings under Purpose Group II.
Internal and external exit ramps may be used as exits in lieu of
internal and external exit staircases subject to compliance to the
applicable requirements of Cl.2.3.3. and to the following:
(a)
The slope of such exit ramps shall not be steeper than 1 in
10, and
(b) Exit ramps shall be straight with changes in direction being
made at level platforms or landings only, except that exit
ramps having a slope not greater than 1 in 12 at any place
may be curved, and
(c) Platform
(i) level platforms or landings shall be provided at the
bottom, at intermediate levels where required and at
the top of all exit ramps, and
(ii) level platforms shall be provided at each door opening
into or from an exit ramp, and
(iii) the minimum width of a platform or landing and length
shall be not less than the width of the ramp, except that
on a straight run ramp, the length of the level platform
or landing need not be more than 1m, and
(d) Exit ramps shall have walls, guards or handrails and shall
comply with the applicable requirements of Cl.2.3.3(d) for
exit staircases, and
Spiral staircases
Exit ramp
Slope
Changes in
direction
Platform
Guards and
handrails
(e)
(f)
2.3.9
(g)
Surface
the
Ventilation
Enclosure
exemption
Exit doors and exit access doors shall comply with the following:
(a) Exit doors shall be capable of being opened manually,
without the use of a key, tool, special knowledge or effort
for operation from the inside of the building; (not applicable
to buildings under Purpose Group I & II) and
(b) Exit doors which are required to have fire resistance rating
shall comply with the relevant provisions for fire resisting
doors under Cl.3.9.2; and
(c) Exit doors and exit access doors shall open in the direction
of exit travel:
(i) when leading to an area of refuge, exit and exit
passageway, or
(ii) when used in exit enclosure, including smoke-stop and
fire-fighting lobbies in a building. It shall not apply to
doors of individual residential units that open directly
into an exit enclosure, or
(iii) when serving a high hazard area, or
(iv) when serving a room or space with more than 50
persons, and
(d) (i) Exit doors opening into exit staircases and exit
passageways shall not impede the egress of occupants
when such doors are swung open, and
(ii) All doors which open into the corridor shall not
hinder movement of occupants. The corridors clear
width shall at least remain to be half of the required
clear width as stipulated under Table 2.2A when such
door(s) is swung open.
Door swing
Exit door
opening
Door opening
into corridor
(e)
(f)
(g)
(h)
Vision panel
Side-hinged or
pivoted swing
door
Note:
2.3.9(c)(i) - when leading to an area of refuge, exit and exit
passageway, or
2.3.9(c)(iii)- when serving a high hazard area
Manually operable sliding doors or roller shutters shall be
capable of being opened and closed manually from either
side of the door. The maximum door opening force shall be
30N at 0 degree and 20N at 30 degree opening.
(i) Manually operable sliding door or roller shutter that
can remain in closed position during the period of
occupation is permitted at rooms or spaces with
occupant load not exceeding 50 persons.When opened,
it shall not reduce the effective width/height of the
doorway leading to the escape route. Sliding door or
roller shutter is allowed within rooms or spaces that
serve more than 50 persons provided it shall remain in
the full open position during the period of occupation.
A readily discernible sign with the lettering THIS
DOOR TO REMAIN OPEN WHEN THE BUILDING IS
OCCUPIED shall be permanently pasted on both
sides of such sliding door or roller shutter at a height
of 1.4m from the finished floor level. The lettering
shall be 25mm in height and painted in white on a red
background with reflective surface, or
(ii) Wicket door shall be permitted to be incorporated
within a roller shutter or sliding door. The wicket door
shall be of the swing type having a minimum head height
of 2m and a clear width of not less than the required
door clear width. The wicket door shall comply with
all the requirements of exit access door, and be clearly
marked and readily visible so that the occupants can
readily see where the door is. It should be fitted only
with simple fastenings that can be manually operated
for ease of escape, or
(iii) A sliding door which can be swung open shall swing in
the direction of escape travel when a certain horizontal
force is applied to the door. When the sliding door is
converted to a swing door, it shall comply with all the
requirements of an exit access door. The maximum
door opening force shall be 30N at 0 degree and 20N
at 30 degree opening. A readily visible sign with the
letterings IN EMERGENCY, PUSH TO OPEN shall be
affixed onto the door, or
Manually
operable
sliding doors/
roller
shutters
Wicket door
Sliding door
with swing-out
feature
Power operated
sliding doors/
roller shutter
Fail-safe type
Manual override
(j)
(l)
2.4
2.4.1
RESIDENTIAL OCCUPANCY
Means of escape for a building or a separate part of a building of
single occupancy of Purpose Group I can be provided via access
staircases, and exit staircase under the provision of Cl.2.3 is not
required.
Residential
buildings of
Purpose
Group I
2.4.2
Residential
buildings of
Purpose
Group II
2.4.3
No of exit
staircases or
exits per
storey
Provision for
buildings not
exceeding 24m
in habitable
height
2.4.4
(a)
(b)
(c)
2.4.5
(b)
The single exit staircase shall serve not more than four
apartments or maisonettes at each storey level, and
(c)
Provision for
buildings
exceeding 24m
in habitable
height
2.4.6
(d)
(e)
(f)
Approach to the exit staircase shall be through crossventilated lobby. The ventilation openings having a minimum
width of 2000mm and a minimum height of 1200mm
shall be unobstructed from parapet wall or balustrade
level upwards and be positioned on opposite sides of the
lobby such that they provide cross-ventilation throughout
the entire space of the lobby. Where multiple ventilation
openings are provided on opposite sides of the lobby, the
minimum width and height of each opening shall not be
less than 1000mm and 1200mm respectively, provided the
aggregate width of the openings at each opposite side is not
less than 2000mm. See diagram 2.4.5(f).
(g)
(h)
(i)
(b)
(i) the door shall not be located on the upper storey of the
unit; and
(ii) the floor area of the upper storey shall not exceed
60m, unless a separate exit is provided on this upper
storey.
Exits from
residential
unit
(c)
2.4.7
Travel distance shall be measured from the door or doors of the
residential apartment or maisonette unit. Where a residential
apartment is required to be provided with two doors at the same
storey level, and if only one-way escape or one exit staircase only
is provided, the travel distance shall be measured from the most
remote door. If two-way escape is achieved, the travel distance shall
be measured from each of the doors.
2.4.8
2.4.9
Travel Distance
(a)
In a block of residential apartment or maisonette where the
means of escape is through an external corridor, the one way
travel distance measured from the door of the apartment or
maisonette to exit staircase shall not exceed 20m or 24m
if the aggregate one-way travel distance within the unit
and along the external corridor does not exceed 40m. The
above one-way travel distances along the external corridor
shall not apply to residential apartments or maisonettes in a
building exceeding 24m permitted under Cl.2.4.5, and
Measurement
of travel
distance
Smoke-free
approach to
exit staircase
One-way travel
distance
2.4.10
(b)
(b)
Two-way travel
distance
Protection of
staircases
2.4.11
Residential
doors opening
into external
corridors
2.4.12
Attic floor
2.4.13
2.5
2.5.1
(a) Hospital
A building used for medical and surgical care and shall
include general hospitals, hospitals for psychiatric care,
children's hospitals, with 24 hours or in patient service.
(i) Basement
General
(ix) Staircase landing width/depth
(1) Exit staircases that serve patient accommodation
floor and are to be used by patients in an emergency
fire situation shall be designed to allow evacuation
of patients on mattresses or stretchers.
Table 2.5.1(a)(viii)(2)
MIN
MIN
STAIR
LANDING
LANDING
WIDTH
WIDTH
DEPTH
1000
2800
1900
))) Allows mattress or stretcher
evauation only (ie no
pedestrian passing).
1250
2800
1900
))) Allows mattress or stretcher
1500
3200
1550
evacuation and restricted
ambulant passing.
1750
3600
* 1350
))) Allows mattress or stretcher
2000
4000
* 1250
evacuation and ambulant
passing.
(b)
(c)
(e)
2.5.2
Number of doors
2.5.3
2.6
2.6.1
(d)
(e)
Number of exit
staircases or
exits per storey
2.6.2
(c)
(d)
(e)
(f)
2.7
2.7.1
Mezzanine floor
Internal corridor
to guestroom or
accommodation
unit
(a)
Guestroom or
accommodation
unit
(b) Doors opening into internal corridors shall have fire
resistance of at least half an hour and fitted with automatic
self-closing device to comply with the requirements of
Cl.3.9.2, and
(c) Internal corridors shall be naturally ventilated with fixed
openings in an external wall, such ventilation openings
shall comply with Cl.2.2.13(i) & (iv), and internal corridors
which cannot be naturally ventilated shall be pressurised
to comply with the requirements in Chapter 7.
2.7.2
2.7.3
2.7.4
(d)
External
corridor
Measurement
of travel
distance
Spacing of
smoke barrier
(d)
(e)
(f)
2.8
2.8.1
Vision panel
ASSEMBLY OCCUPANCY
Assembly Occupancy include all buildings or portions of buildings
used for gathering together of more than 50 persons for such
purpose as deliberation, worship, entertainment, eating, drinking,
amusement or awaiting transportation.
General
2.8.2
Min No of Doors
2
2
3
4
Min width
of corridors
1000 mm
1250 mm
1250 mm
1250 mm
Number and
width of exit
facilities
2.8.3
(b)
Gangway on two
sides
14
16
18
20
22
24
26
28
Limited by the
travel distance
(c)
Aisles and
gangways
2.8.4
(e)
flooring for the surface of steps and ramps forming the aisles
or gangways shall be finished using non slip materials, and
(f)
(g)
(a)
(b)
(c)
Combustible
seats
Exits from
a theatre,
cinema or a
concert hall
2.9
2.9.1
2.9.2
2.9.3
WORKERS DORMITORIES
Dormitories
(b)
(c)
(d)
(d)
Size
Occupant load
No of exit
staircases or
exit per storey
Maximum
travel distance
Internal
corridor to
dormitory
bedrooms
2.9.4
2.9.5
(e)
(f)
(g)
(b)
(c)
Entry into an exit staircase from any part of a building of more than
4 storey above ground level shall comply with requirements of
Cl.2.2.13 - requirements of smoke free approach to exit staircase.
Pressurisation of staircase in lieu of the provision of smoke-stop
lobby is not permitted.
2.10
2.10.1
2.10.2
External corridor
Smoke-free
approach to exit
staircase
Exit lighting
Exit and
directional sign
2.10.3
(b)
(c)
High hazard
Industrial buildings (factories,
workshops, godown/warehouse)
Shops
Offices
Places of public resort & carparks
Schools & educational buildings
Hospitals
Hotels, Boarding Houses, Serviced
Apartments, Hostels, Backpackers
Hotel, Dormitories
Blocks of flats/maisonettes (k)
Detached, semi-detached & terrace
house, including townhouses
(ii)
Max Travel Distance (m)
(One-way travel)
Unsprinklered
10
15
15
15
15
15
15
Sprinklered
20
25
25
30
25
25
25
(iii)
Max Travel
Distance (m)
(Two-way Escape)
(iv)
Capacity
No of persons per unit of width (x)
Door opening
(c), (d) & (e)
To outdoors Other exit
at ground
& corridor
level
doors
50
40
100
80
Unsprinklered
20
30
Sprinklered
35
60
45
45
45
45
30
60
75
60
60
45
100
100
100
100
30
60
(f)
Staircases
30
60
(v)
Min Width
(m)
(vi)
Max Dead End (m)
(d)
Ramps Corridors
Exits Passageways
Corridors
Stairs
Corridors
1.2
1.2
Unsprinklered
15
15
Sprinklered
20
20
15
15
15
15
15
20
20
20
20
20
50
100
1
1
50
60
60
60
60
15
45
100
100
100
100
30
1
1
1(h)
1
1
1.2
1.2
1.2 (h)
1(a)
2(b)
1.2
15
20
80
80
80
80
30
15
20
30
60
50
15(g)
20(j)
NR
30(g)
40(j)
NR
30
45(j)
NR
75
50
40
30
50
1(i)
1.2
15
20
NR
NR
NR
NR
NR
0.9
0.9
NR
NR
NR
(x)
(a)
Applies to corridors serving classrooms. Other corridors shall have a minimum width of 1.2 metre.
(b)
Applies to corridors serving patients. Other corridors shall have a minimum of 1.2 metre.
(c)
See Cl.2.3.9.
(d)
See Cl.2.3.8.
(e)
Where a door opening is divided by mullions into two or more openings, each such opening shall be measured separately in computing the number of units of exit width.
(f)
(g)
(h)
Refer to Cl.2.8.2.
(i)
(j)
(k)
Measurement of travel distance is from the residential unit door to exit . see Cl.2.4.7.
86
Diagram2.2.9(b)
2.2.9(b)
Diagram
2 LEAF DOOR
MULTI-LEAF DOOR
87
Diagram
2.4.5(f)
Diagram 2.4.5(f)
88
Diagram
Diagram2.4.6(a)
2.4.6(a)
Legend
Travel distance from any point within unit to the exit door (max. 20m)
89
Diagram
2.4.10
Diagram
2.4.10
Exit Staircase
For residential apartment or maisonette
90
Diagram 2.8.3(a)(ii)
(1)
Diagram
2.8.3(a)(ii)-(1)
91
Diagram
2.8.3(a)(ii)-(2)
Diagram 2.8.3(a)(ii)
(2)
Seatway widths should be not less than 300mm and should be constant throughout
the length of the row.
92
CHAPTER 3
STRUCTURAL FIRE PRECAUTIONS
ROOT OBJECTIVES
The primary intentions of this chapter are encapsulated in
the following statements:R3.1
R3.2
R3.3
S3.1
S3.2
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
S3.4
S3.5
S3.6
S3.7
S3.8
S3.9
3(II)
CHAPTER 3
STRUCTURAL FIRE PRECAUTIONS
3.1
GENERAL
3.1.1
General
3.2
3.2.1
3.2.2
(b)
(a)
Compartment
size-floor area
& cubical
extent
Cubical extent
for compartment exceeding
4m in height
3.2.3
3.2.4.
(b)
Cl.3.2.6,
Cl.7.5
(b)
(c)
Exception to
Cl.3.2.1
and
Compartmentation by Height
(a) In any compartment except those mentioned under
sub-clause 3.2.4(c), up to a habitable height of 24m, no
compartment shall comprise more than three storeys. This
requirement can be relaxed for Atrium spaces provided
the design of such spaces complies with the conditions
stipulated under Cl.3.2.6.
Where two buildings are connected by external opensided covered way or covered link-bridge, the buildings are
considered as separate buildings, if the following conditions
are complied with:
Compartmentation by
height
Single household
dwelling
3.2.5
Other cases
requiring
compartment
walls &
compartment
floors
(a)
Purpose
group II
(b)
(c)
Any floor immediately over a basement storey if such storey(i) forms part of a building of Purpose Group I which has
five or more storeys (including the basement storey)
or a building or compartment of Purpose Group II to
VIII. In the case of Purpose Group I building which has
five or more storeys (including the basement storey),
the basement level shall discharge directly to 1st storey
grade level.
Separation of
purpose groups
Floor over a
basement
(d)
Basement floors
(e)
Fire Command
Centre
(f)
Kitchen Separation
(g)
Separation by
proscenium wall
in theatres or
concert halls
Guestroom or
accomodation
unit
Workers
dormitories
(k)
(l)
Separation
of motor vehicle
workshop
Separation of
spray painting
room
(p)
Store room
Areas of special
high risk in a
building
Tenancy unit
(q)
(r)
3.2.6
3.2.7
Warehouse
The Relevant Authority may consent to modify the requirements
under Cl. 3.2.1 and 3.2.4(a) of this Code for the design of 'Atrium
spaces' in a building provided the following conditions are
complied with :
(a)
The minimum plan area of the Atrium void shall be not less
than 93m and no horizontal dimension between opposite
edges of the floor opening is less than 6m wide; and
(b) Occupancy within the floor space of the Atrium meets with
the specification for low or ordinary hazard content; and
(c)
The atrium is open and unobstructed in a manner such that
it may be assumed that a fire in any part of the space will
be readily obvious to the occupants before it becomes a
hazard; and
(d) The building is fitted throughout with an automatic
sprinkler system to comply with the requirements in
Chapter 6; and
(e) The building is fitted with an engineered smoke control
system in accordance with Cl.7.6; and
(f) Provision of openings and enclosures, and the planning
of means of escape shall be subject to the approval of the
Relevant Authority.
Buildings of High Hazard Occupancy
(a) The compartment of buildings of high hazard occupancy
shall not exceed one half of the sizes given in Table 3.2A and
each compartment shall comprise one storey only; and
Provision for
atrium spaces
Buildings of
high hazard
occupancy
(b)
(c)
3.2.8
Exemption from
Cl.3.2.1 on size
limitation of
compartment
3.2.9
(ii) No part of the floor space shall be more than 12m from
the openings on the perimeter walls of the building or
air-well. Air-well where provided for this purpose shall
have a superficial plan area of not less than 10m, or
0.1m for every 300mm of height, whichever is greater,
and have a minimum dimension on plan of 2000mm,
open vertically to the sky for its full height.
3.3
3.3.1
Minimum periods
of fire resistance
Exemption for
non loadbearing
external walls
3.3.2
(a)
(b)
Exemption for
steel structures
for standalone
carpark
3.3.3
Exemption for
single storey
buildings
3.3.4
3.3.5
(b)
Interpretation
and application
of this regulation
Wall separating
residential
apartment or
maisonette
3.3.6
Suspended
ceiling
3.3.7
(i)
(ii)
(iii)
(iv) Dry wall shall meet the criteria, in term of impact &
deflection performance, when subject to the test of BS 5588
Pt 5 Appendix A and BS 5234 Pt 2; and
Note : Fire rated boards should not be used to protect structural
steel in areas which may be subject to explosion risks as the
boards may be displaced by the force of the blast.
In buildings under Purpose Groups VI & VIII, where there
may be presence of corrosive atmosphere that may affect
the effectiveness of fire rated board for protection to
structural steel members of buildings, such proposal shall
be subjected to evaluation of the Relevant Authority.
3.4
3.4.1
Fire resistance
3.4.2
3.4.3
(b)
"Deem to satisfy"
provisions
Timber floors
EXTERNAL WALL
Requirements of External Walls shall be as follows:
(a)
Requirements of
external walls
(b)
3.5.2
(a)
(i) if that wall is:
(1) situated 1m or more from the relevant boundary;
and
(3) separated as described in Cl.3.3.4(b); or
(ii) if that wall is situated 1m or more from the relevant
boundary:
(1) of Purpose Group I and II of not more than three
storeys, or
(2) of single storey construction and not exceeding
15m in height and floor area not exceeding
Purpose Group III, IV, VII 3000m2
Purpose Group V, VI 2000m2
Purpose Group VIII 500m2 ;
or
(3) other than single storey buildings, but not
exceeding 7.5m in height and floor area not
exceeding
Exceptions
(b)
3.5.3
(b)
(i) used solely for the sale, storage and processing involving
goods and substances of a non combustible nature, or
(c)
(d)
Unprotected
areas in any side
of a building
(e)
3.5.4
(b)
Cladding on
external walls
3.5.5
Reference to
Part I II of
Appendix B
3.5.6
Buildings on
land in common
occupation
3.5.7
3.6
3.6.1
Vertical fire
spread
SEPARATING WALLS
Every separating wall shall:
(a) Form a complete barrier in the same continuous vertical
plane through the full height between the buildings it
separates, including roofs and basements and shall be
imperforate except for provisions of openings permitted
under Cl.3.6.2, and
(b) Have the appropriate fire resistance to comply with the
requirements of Cl.3.3, and
(c)
Be constructed of non combustible materials, together with
any beam and column which form part of the wall and any
structure which it carries.
(d) Not include glass fire resisting walls.
(e) Exception
Subclause (a) need not be applied to wall between car
porches of buildings under Purpose Group I. For terracehousing situation, this exception will not apply if the
carporch is spanning from one side boundary to the other.
Requirements of
separating walls
3.6.2
(b)
3.6.3
(c)
3.6.4
3.6.5
3.7
3.7.1
A separating wall shall be either carried up to form a close joint
with the underside of a pitched roof of non combustible covering
or carried up above the level of such roof covering. The junction
between such separating wall and roof shall be properly fire
stopped so as not to render ineffective the resistance of such
separating wall to the effects of the spread of fire.
(b)
(c)
Openings in
separating walls
with the
Requirements
of compartment
walls or
compartment
floors
3.7.2
(d)
(b)
Openings in
compartment
wall or
compartment
floor
(a)
(b)
3.7.4
3.7.5
Junction with
other structures
Opening in
curtain walling
Where a compartment wall forms a junction with a roof, such
compartment wall shall be carried up to form a close joint with
the underside of the roof and shall be properly fire stopped or shall
be carried up above the level of the roof covering and the junction
between such compartment wall and roof shall be properly fire
stopped so as not to render ineffective the resistance of such
compartment wall to the effects of the spread of fire.
No combustible material shall be built into, carried through or
carried across the ends of any compartment wall or compartment
floor or carried over the top of any compartment wall in such a
manner as to render ineffective the resistance of such wall or floor
to the effects of the spread of fire.
Compartment
wall - roof
junctions
Prohibition of
combustible
materials
3.7.6
Noncombustibility
of compartment
walls or floors
3.7.7
Use of fire
shutter
3.7.8
3.7.9
(a)
(b)
3.7.10
(c)
3.8
PROTECTED SHAFTS
3.8.1
Purpose of
protected shaft
3.8.3
(b)
(c)
Requirements of
protected shaft
Openings in
protected shaft
3.8.4
3.8.5
(iii) inlets to and outlets from and opening for the duct, if
the shaft contains or serves as a ventilation duct,
Noncombustibility
of protecting
structures
(b)
3.8.6
Exception :
Ventilation of
protected shaft
Doors in
protecting
structures
(a)
Protected shaft
containing exit
staircase
3.8.8
(b)
(i) Drywall shall be non-combustible; and
(ii) Drywall shall have fire resistance for not less than the
relevant period specified in Table 3.3A having regard
to the purpose group of the building of which it forms
a part and the dimension specified in that Table; and
(iii) Drywall shall meet the criteria, in terms of impact and
deflection performance, when subject to the tests of BS
5588 Pt 5 Appendix A and BS 5234 Pt 2; and
(iv) Drywall shall meet the criteria, in terms of water
absorption and bending strength performance, when
subject to the test of BS EN 520 (for gypsum plaster
board) or ISO 1896 (for calcium silicate or cement
board); and
(v) The building shall have at least two independent exit
staircase shafts (scissors staircases are considered as
single shaft).
A protected shaft which contains a lift shall comply with the
following:
(a)
(b)
(i) Drywall shall be non-combustible; and
(ii) Drywall shall have fire resistance for not less than the
relevant period specified in Table 3.3A having regard
to the purpose group of the building of which it forms
a part and the dimension specified in that Table; and
(iii) Drywall shall meet the criteria, in terms of impact and
deflection performance, when subject to the tests of BS
5588 Pt 5 Appendix A and BS 5234 Pt 2; and
Lift shaft
Openings for the passage of lift cables into the lift motor
room located above or at the bottom of the shaft shall be as
small as practicable.
(f)
(g)
Exception:
(h)
Private Lift
3.8.9
Protected shaft
containing
other services
installations
3.9
3.9.1
Omission of
self-closing
devices
Exception
PROTECTION OF OPENINGS
The provisions of this Clause are made in connection with the
protection of openings permitted in elements of structure or other
forms of fire resisting construction required to act as a barrier to
fire and smoke.
Application
3.9.2
(d)
(e)
Fire doors
3.9.3
(f)
(a)
Pipes
3.9.4
Ventilation ducts
(b)
(i) fitted with fire dampers at the inlets to the shaft and
outlets from it, and
(c)
3.9.5
Flues
3.9.6
(a)
Services passing
through Fire
Command
Centre, Fire
Pump Room,
Emergency
Generator
Room and
Smoke Control
Fans Room
(b)
Services running
inside and/or
passing through
fire-fighting lobby
& smoke-stop
lobby
3.10
EXIT STAIRCASES
3.10.1
Noncombustibility
of structure
3.10.2
The exit staircase shall be separated from other parts of the building
by a masonry structure or drywall complying with Cl.3.8.7(c)
which shall have fire resistance for not less than the period required
by Cl.3.3 for Elements of Structure.
Structure
separating exit
staircase
3.10.3
Doors opening into the exit staircase shall have fire resistance of
at least half an hour and fitted with automatic self-closing device.
Exit doors
3.10.4
Finishes
3.11
3.11.1
CONCEALED SPACES
Concealed spaces in a building shall be interrupted by construction
of cavity barriers to restrict the spread of smoke and flames.
General
provision
3.11.2
Closing the
edges of cavities
3.11.3
Interrupting
cavities
3.11.4
Sub-division
of extensive
cavities
3.11.5
3.11.6
(b)
(b)
(c)
(d)
(e)
3.11.7
(b)
(c)
Openings in
cavity barriers
Fire resistance
and fixing of
cavity barriers
(d)
3.11.8
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
Raised floors
with or without
accessible panels
(j)
(k)
(l)
3.11.9
(b)
(c)
(d)
(e)
Provision for
concealed
spaces between
floor or roof
and suspended
ceilings
3.11.11
Exemption of
cavity barriers
in ceiling space
(c)
Suspended
ceiling over
protected areas
3.11.12
3.12
FIRE STOPPING
3.12.1
General
provision
(a)
(b)
3.12.2
(c)
Fire stopping
3.12.3
Materials for
fire-stopping
(a)
(b)
3.13
3.13.1
3.13.2
3.13.3
(a)
(b)
Requirements
for Class 0
Requirements
for a class other
than Class 0
classification
3.13.4
3.13.5
Class of flame
spread to be
not lower than
specified
Where class of
flame spread may
be of any class
not lower than
Class 3
(b)
(i) *
3.13.6
(ii) *
Wall and ceiling finishes in the form of thin sheet of not more than
1.0mm thickness mounted on a non-combustible substrate will not
be subject to the requirement of surface spread of flame provisions
provided that this exception shall not apply to smoke-stop/firefighting lobbies, exit staircases and passageways.
Exception
3.14
ROOFS
3.14.1
Roof
construction
3.14.2
Provision for
buildings not
exceeding four
storeys
(a)
(b)
(c)
3.14.3
3.14.4 Roof terrace shall not be roofed over. If it is either partially or fully
roofed over, it shall be considered as a habitable floor.
3.15
3.15.1
Roof junction
with separating
wall and
compartment
wall
Roof terrace
(b)
Intumescent
Paints
3.15.2
3.15.3
Materials used for the protection of openings shall comply with the
relevant provisions of Cl.3.9 of the code for protection of openings.
3.15.4
3.15.5
3.15.6
3.15.7
3.15.8
Materials used for fire stopping shall comply with the relevant
provisions of Cl.3.12.2 and 3.12.3.
3.15.9
3.15.10
3.15.11
3.15.12
3.15.13
(a)
(b)
3.15.14
3.15.15
The walls and doors shall meet the Class A of the Impact
Performance requirements when subject to test under BS
6206 or AS 2208.
Walls, ceilings, roof covering and finishes shall not contain any
plastic material.
For additions and alterations to existing buildings, non-combustible
partitions shall be used for separation of areas undergoing A&A
works from other occupied areas of the building.
(2)
(3)
Compartments
2000m
7500m
4000m
15000m
2000m
7500m
75
TABLE 3.3A
(Minimum periods of fire resistance)
In this Table cubical extent means the cubical extent of the building or, if the building is divided into compartments, the
compartment of which the elements of structure forms part;
floor area means the floor area of each storey in the building or, if the building is divided into
compartments, of each storey in the compartment of which the element of structure forms part;
height has the meaning assigned to that expression by Cl 3.3.4 (b);
NL means No limit applicable.
PART I
BUILDINGS OTHER THAN SINGLE STOREY BUILDINGS
Minimum period of fire
resistance (in hours) for
elements of structure (*)
forming part of-
Maximum
dimensions
Height
(in m)
(2)
Floor
area
(in m2)
(3)
Cubical
Extent
(in m3)
(4)
Above
ground
storey
(5)
Basement
storey
(6)
I (Small residential)
House having not more than 3-storeys
House having 4-storeys
House having any number of storey
NL
NL
NL
NL
250
NL
NL
NL
NL
1(b)
1
1(a)
1
1
II (Other residential)
Building or part (+) having not more than two
storeys
Building or part (+) having 3-storeys
Building having any number of storeys
Building having any number of storeys
NL
NL
28
NL
500
250
3,000
2,000
NL
NL
8,500
5,500
1(b)
1
1
1
1
1
2
28
over 28
2,000
2,000
NL
NL
1
1
1
2
7.5
7.5
15
28
NL
250
500
NL
5,000
NL
NL
NL
3,500
14,000
NL
1(b)
1
1
1(a)
1
1
1
2
Purpose group
(1)
III (Institutional)
IV (Office)
76
PART I - continued
BUILDINGS OTHER THAN SINGLE STOREY BUILDINGS - continued
Minimum period of fire resistance
(in hours) for elements of structure
(*) forming part of-
Maximum
dimensions
Purpose group
(1)
V (Shop)
VI (Factory)
Height
(in m)
(2)
Floor area
(in m2)
(3)
Cubical Extent
(in m3)
(4)
Above
ground storey
(5)
Basement storey
7.5
7.5
15
28
NL
7.5
7.5
15
28
28
over 28
7.5
7.5
15
28
NL
7.5
7.5
15
15
28
28
over 28
150
500
NL
1,000
2,000
250
NL
NL
NL
NL
2,000
250
500
NL
1,000
NL
150
300
NL
NL
NL
NL
1,000
NL
NL
3,500
7,000
7,000
NL
1,700
4,250
8,500
28,000
5,500
NL
NL
3,500
7,000
7,000
NL
NL
1,700
3,500
7,000
21,000
NL
1(b)
1
2
1(b)
1
2
2
1(b)
1
1
1(b)
1
2
4(c)
4(c)
1(a)
1
1
2
4
1(a)
1
1
2
4
4
1(a)
1
1
1
2
1(a)
1
1
2
4(d)
4(d)
4(d)
(6)
Notes to Part I
For the purpose of Cl 3.3.1 the period of fire resistance to be taken as being relevant to an element of structure is the period
included in columns (5) or (6) in the line of entries which specifies the floor area with which there is conformity or, if there are
two or more such lines, in the topmost of those lines.
(*)
A floor which is immediately over a basement storey shall be deemed to be an element of structure forming part of a
basement storey.
(+)
(a)
The period is half an hour for elements forming part of a basement storey which has an area not exceeding 50 m2
(b)
This period is reduced to half an hour in respect of a floor which is not a compartment floor, except as to the beams
which support the floor or any part of the floor which contributes to the structural support of the building as a whole.
(c)
(d)
Single basement carpark storey, which is sprinklered protected, the element of structure can be reduced to half the
minimum period of fire resistance.
(1)
(2)
140
Purpose group
(1)
Maximum
floor area
(in m2)
(2)
Minimum period
of fire resistance
(in hours) for elements of
structure
(3)
(Small residential)
NL
II
(Other residential)
3,000
III
(Institutional)
3,000
IV
(Office)
3,000
NL
(Shop)
2,000
3,000
NL
1
2
VI
(Factory)
2,000
3,000
NL
1
2
VII
3,000
NL
VIII
500
1,000
3,000
NL
1
2
4(a)
Notes to Part 2
For the purpose of Cl 3.3.1 the period of fire resistance to be taken as being relevant to an element
of structure is the period included in column (3) in the line of entries which specifies the floor area
with which there is conformity or, if there are two or more such lines, in the topmost of those lines.
(a)
This period is reduced to 2-hours for open-sided buildings which are used solely for
carparking.
141
TABLE 3.3B
(Suspended ceilings)
Height of
building
(1)
Less than 15m
Type of floor
(2)
Required fire
resistance of floor
(3)
Description of
suspended ceiling
(4)
NonCompartment
1 hour or less
Compartment
Compartment
1 hour
15m or more
Any
1 hour or less
Any
Any
Ceiling
of
non-combustible
construction and jointless; supports
and fixings for the ceiling noncombustible.
Notes:
(1)
(2)
142
TABLE 3.4A
SPECIFIC PROVISIONS OF TEST FOR FIRE
RESISTANCE OF ELEMENTS OF STRUCTURE ETC
Minimum provisions when tested to BS 476: Part 20-23
(minutes)
Part of building
Stability
Integrity
Insulation
Method of exposure
no requirement
no requirement
exposed faces
no requirement
no requirement
Floors
30
15
15
from underside
(Note 1)
from underside
(Note 1)
each side
separately
15
from inside
*
(max. 60)
*
(max. 60)
*
(max. 60)
from outside
15
from inside
5 Separating wall
*
(min. 60)
*
(min.60)
*
(min. 60)
6 Compartment wall
(a)
(b)
External walls
(a)
(b)
(c)
143
Stability
Integrity
Insulation
Method of exposure
Doors
(a)
in a separating wall
No
Provision
+
(min. 60)
no
provision***
(b)
in a compartment wall if it
separates a flat or maisonette
from a space in common use
No
Provision
30
no
provision***
(c)
in a compartment wall or
compartment floor not
described in (b) above
No
Provision
no
provision***
(d)
in a protecting structure
situated wholly or partly
above the level of the
adjoining ground in a
building used for Flats,
Other Residential, Assembly
or Office purposes
No
provision
30
no
provision***
(e)
no
provision
**
(min. 30)
no
provision***
(f)
no
provision
30
no
provision***
10
30
30
30++
from outside
11
Cavity Barriers
(a) cavity barrier 1m x 1m or
Larger
30
30
15
30
30
no
provision
(c) ceiling
30
30
30
from underside
Modifications
++ No provision for insulation if the casing is more than 50mm from any pipe in the enclosure (except a pipe passing through the
casing).
Notes
*
+
**
***
1
2
Non-combustible
material1
Lead,
aluminium or
aluminium alloy,
or uPVC2
Any
other
material
150
100
40
150
40
Situation
Notes
1)
A non-combustible material (such as cast iron or steel) which if exposed to a temperature of 800
degrees Celsius will not soften nor fracture to the extent that flame or gases will pass through the wall
of the pipe.
2)
3)
i)
Within toilets, wash rooms or external corridors, maximum diameter of uPVC pipes may be
increased to double the size given in the above table.
ii)
Within areas of fire risk, such as kitchens, and adjacent to escape routes, uPVC pipes shall be
enclosed by construction having fire resistance of at least one half hour.
iii)
Where the size of uPVC pipes exceeds that specified under this Clause, approved fire collar
shall be fitted at all positions where such pipes pass through constructions required to act as a
barrier to fire.
145
VIII (Storage)
N/A
No control
No control
No control
No control
No control
3*
No control
No control
Room,
compartment
No control
No control
No control
No control
No control
3*
No control
No control
Circulation
space
Smoke-stop
/fire-fighting
lobby
Not Applicable
Applies to Detention facilities and Health-care, including hospital, old-aged homes, nursing homes for mentally or physically disabled patients.
VI (Factory)
N/A
3*
V (Shop)
N/A
Smoke-stop
/fire-fighting
lobby
IV ( Office)
N/A
Circulation
space
No control
II (Other residential)
III (Institutional)
No control
Room,
compartment
I (Small residential)
TABLE 3.13A
0
0
0
0
V (Shop)
VI (Factory)
VIII (Storage)
148
Not Applicable
No control
No control
No control
No control
No control
3**
No control
No control
N/A
No control
No control
No control
No control
No control
3**
No control
No control
Roof support can be of timber construction but not of plastic material. Roof covering shall not be of plastic material
No control
No control
No control
No control
No control
3**
No control
No control
Roof covering,
including supports
***
N/A***
N/A***
Applies to Detention facilities and health-care, including hospital, nursing homes for handicapped, disabled, aged or persons with mental and/or mobility impairment.
N/A
Internal non-load
bearing wall and
ceiling within room,
compartment
**
0/1/3
IV (Office)
No control
II (Other residential)
III (Institutional)
No control
Roof covering,
including
supports
I (Small residential)
TABLE 3.13B
2.
..
..
..
1.
149
75
75
75
63
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
180
180
180
125
75
75
75
63
100
100
100
75
4
hours
100
100
100
75
Minimum thickness excluding plaster (in mm) for period of fire resistance of
Loadbearing
Non-loadbearing
2
1
1
4
3
2
1
1
hours
hours
hour
hour
hours
hours
hours
hours
hour
150
150
150
hour
Any material or type of construction or method of mixing, preparing, using, applying or fixing the material as referred to in the table, shall conform with the relevant
provisions of the Building Control Act (Chapter 29) and the relevant Singapore Standard or Singapore Standard Code of Practice in respect of the material or such
matters. In the absence of a Singapore Standard or Singapore Code of Practice on the material or such matters, the relevant British Standard or British Code of
Practice or other accepted Standard or Code of Practice shall be applicable.
(d)
Mansonry construction:
In the case of a cavity wall , the load is assumed to be on inner leaf only except for fire resistance period of four hours.
(c)
A.
(b)
PART 1 : WALLS
Class 1 aggregate means foamed slag, pumice, blast furnace slag, pelleted fly ash, crushed brick and burnt clay products (including expanded clay) well-burnt clinker
and crushed limstone.
Class 2 aggregate means flint gravel, granite, and all crushed natural stones other than limestones.
(a)
In this Appendix:
APPENDIX A to C1 3.4
7.
6.
5.
.
4.
.
3.
A.
180
100
140
100
150
150
150
100
200
200
200
3
hours
200
200
200
4
hours
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
150
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
150
150
150
100
100
150
150
150
100
150
100
100
75
100
170
170
170
170
170
170
100
100
100
75
62
100
100
100
75
75
75
75
75
100
100
100
100
100
75
75
75
62
100
100
100
75
75
75
75
62
100
100
100
100
100
75
75
62
50
75
75
75
75
75
75
75
50
75
75
75
75
Minimum thickness excluding plaster (in mm) for period of fire resistance of
Loadbearing
Non-loadbearing
2
1
1
4
3
2
1
1
hours
hours
hour
hour
hours
hours
hours
hours
hour
75
75
75
62
50
50
50
50
50
50
50
50
50
75
75
75
75
hour
9.
10.
11.
8.
A.
140
100
100
150
100
100
3
hours
4
hours
100
100
100
151
100
100
100
100
100
100
100
100
100
75
75
75
200
150
150
150
125
75
75
75
75
100
150
150
150
100
75
75
75
100
125
125
125
100
75
75
75
100
100
100
125
125
125
100
Minimum thickness excluding plaster (in mm) for period of fire resistance of
Loadbearing
Non-loadbearing
2
1
1
4
3
2
1
1
hours
hours
hour
hour
hours
hours
hours
hours
hour
75
75
75
75
75
62
125
100
100
75
hour
Period of
fire resistance
(in hours)
Steel frame with external cladding of 16 mm rendering on metal lathing and internal lining of
autoclaved aerated concrete blocks, density 480-1120 Kg/m3 of thickness of
50mm
62mm
75mm
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
2.
Steel frame with external cladding of 100mm concrete blocks and internal lining of 16mm gypsum
plaster on metal lathing
...
...
...
...
3.
Steel frame with external cladding of 16mm rendering on metal lathing and internal lining of 16mm
gypsum plaster on metal lathing
...
...
...
4.
2
3
4
4
1
(a)
(b)
(c)
...
(d)
...
...
...
...
...
...
...
...
2
1
1
(e)
12.5mm plasterboardunplastered
...
...
...
...
with gypsum plaster of thickness of 12.5mm ...
...
...
...
(f)
...
...
...
2
1
1
(g)
19mm plasterboard (or two layers of 9.5mm fixed to break joint) without finish
(h)
19mm plasterboard for two layers of 9.5mm with vermiculite-gypsum plaster of thickness of16mm ...
...
...
...
...
...
...
...
10mm ...
...
...
...
...
...
...
...
(i)
(j)
...
...
...
...
2
1
1
...
2
1
Period of
fire resistance
(in hours)
Compressed straw slabs in timber frames finished on both faces with gypsum plaster of thickness of 5mm
...
...
...
6.
7.
(a)
unplastered
...
(b)
(c)
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
unplastered
...
(b)
(c)
8.
9.
Plasterboard 12.5mm bonded with neat gypsum plaster to each side of 19mm plasterboard
...
...
...
...
10.
11.
2
...
...
...
...
...
...
1
...
...
2
75mm
...
...
...
...
...
...
...
...
...
50mm
...
...
...
...
...
...
...
...
...
12.
Compressed straw slabs, with 75mm by 12.5mm wood cover strips to joints, of thickness of 50mm
Steel frame with external cladding of non-combustible sheets and internal lining of(a)
...
...
(b)
...
...
(c)
(d)
...
...
(e)
...
...
(f)
...
...
...
...
153
...
...
External walls (non-loadbearing) more than 1m from the relevant boundary - continued.
Period of fire
resistance
(in hours)
Timber frame with external cladding of 10mm cement-sand or cement-lime rendering and internal lining of(a)
(b)
...
...
...
...
...
(c)
...
...
(d)
(e)
50mm
...
...
62mm
...
75mm
100mm
...
...
1
1
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
3.
Timber frame with external cladding of 100mm clay, concrete or sand-lime bricks of blocks, finished internally
with 16mm gypsum plaster on metal lathing
*4
Timber frame with external cladding of weather boarding or 9.5 mm plywood and interal lining of-
(a)
(b)
...
...
...
...
...
...
(c)
...
...
(d)
(e)
...
...
...
...
...
...
50mm
...
...
...
...
...
...
...
...
...
62mm
...
...
...
...
...
...
...
...
...
75mm
...
...
...
...
...
...
...
...
...
100mm
...
...
...
...
...
...
...
...
...
The presence of a combustible vapour barrier within the thickness of these constructions shall not be regarded as affecting these
periods of fire resistance.
154
154
Description
1.
mm
mm
mm
mm
mm
mm
65*
55*
45*
35
25
15
280
240
180
140
110
80
2.
(a)
(b)
...
...
...
...
3.
(a)
(b)
beam width
...
...
...
50*
40
30
20
15
15
210
170
110
85
70
...
...
250
25
15
15
15
15
15
...
...
170
145
125
85
60
60
50
45
35
30
20
15
250
200
160
130
100
80
4.
(a)
(b)
beam width
...
...
...
(b)
beam width
...
...
...
...
...
Vermiculite/gypsum plaster should have a mix ratio in the range of 1 - 2:1 by volume.
155
Description
1.
mm
mm
mm
mm
mm
mm
2.
...
...
...
...
100*
280
85*
240
65*
180
50*
140
40
110
25
80
...
...
...
...
75*
210
60
170
45
125
35
100
25
70
15
70
...
...
...
...
65
180
50
140
35
100
25
70
15
60
15
60
...
...
90*
250
75
210
50
170
40
110
30
85
15
70
...
...
75*
170
60
145
45
125
30
85
25
60
15
60
...
...
...
...
50
140
45
125
30
85
25
70
15
60
15
60
...
...
...
...
80
250
65
200
50
160
40
130
30
100
20
80
3.
4.
5.
...
...
6.
7.
Vermiculite/gypsum plaster should have a mix ratio in the range of 1 -2: 1 by volume.
156
1.
mm
mm
mm
mm
mm
mm
450
400
300
250
200
150
300
275
275
225
225
200
150
150
150
120
150
120
275
225
200
190
150
275
225
200
150
150
2.
...
3.
...
...
...
...
...
300
300
Vermiculite / gypsum plaster should have a mix ratio in the range of 1 - 2:1 by volume.
Type of construction
1.
mm
mm
mm
mm
mm
mm
180
150
100
100
75
75
125
100
75
75
65
65
Vermiculite / gypsum plaster should have a mix ratio in the range of 1 - 2:1 by volume.
157
Encased steel stanchions (Mass per metre not less than 45 kg)
A.
SOLID PROTECTION*
(unplastered)
1.
4
hours
3
hours
2
hours
1
hours
1
hours
hours
(a)
50
25
25
25
25
(b)
75
50
50
50
50
100
75
50
50
50
50
75
60
50
50
50
50
38
32
19
12.5
2.
3.
4.
Sprayed vermiculite-cement
B.
HOLLOW PROTECTION++
1.
115
50
50
50
50
2.
75
50
50
50
50
..
..
..
158
Encased steel stanchions (Mass per metre not less than 45 kg) continued
3.
4.
(a)
...
5.
(a)
...
...
4
hours
3
hours
2
hours
1
hours
1
hours
hours
38
25
19
12.5
50
19
16
12.5
12.5
44
19
12.5
12.5
12.5
12.5
12.5
12.5
10
16
15
10
10
38
20
13
10
10
Solid protection means a casing which is bedded close to the steel without intervening cavities and with all joints in that casing
made full and solid.
Reinforcement shall consist of steel binding wire not less than 2.3mm in thickness , or a steel mesh weighing not less than 0.48
kg/m2. In concrete protection, the spacing of that reinforcement shall not exceed 150mm in any direction.
++
Hollow protection means that there is a void between the protective material and the steel. All hollow protection to columns
shall be effectively sealed at each floor level.
Light mesh reinforcement required 12.5mm to 19mm below surface unless special corner beads are used.
159
PART
PART
PARTV:V:
V:STRUCTURAL
STRUCTURAL
STRUCTURALSTEEL
STEEL
STEEL- --continued
continued
continued
AA
A
Encased
Encased
Encasedsteel
steel
steelstanchions
stanchions
stanchions(Mass
(Mass
(Massper
per
permetre
metre
metrenot
not
notless
less
lessthan
than
than4545
45kg)
kg)
kg)- -continued
- continued
continued
Minimum
Minimum
Minimumthickness
thickness
thickness(in
(in
(inmm)
mm)
mm)ofof
of
protection
protection
protectionfor
for
fora aafire
fire
fireresistance
resistance
resistanceofof
of- --
Construction
Construction
Constructionand
and
andmaterials
materials
materials
BB
B
444
hours
hours
hours
333
hours
hours
hours
222
hours
hours
hours
111
hours
hours
hours
111
hours
hours
hours
hours
hours
hours
6363
63
- --
2525
25
2525
25
2525
25
2525
25
HOLLOW
HOLLOW
HOLLOWPROTECTION*PROTECTION*PROTECTION*-CONTINUED
CONTINUED
CONTINUED
7.7.
7. Vermiculite
Vermiculite
Vermiculite- -cement
- cement
cementslabs
slabs
slabsofof
of4:1
4:1
4:1mix
mix
mix
reinforced
reinforcedwith
withwire
wiremesh
meshand
andfinished
finishedwith
with
reinforced
with
wire
mesh
and
finished
with
plaster
plasterskim.
skim.Slabs
Slabsofof
ofthickness
thicknessofof
of .. ....
.. ....
plaster
skim.
Slabs
thickness
BBB
. ..
Encased
Encased
Encasedsteel
steel
steelbeams
beams
beams(Mass
(Mass
(Massper
per
permetre
metre
metrenot
not
notless
less
lessthan
than
than30kg)
30kg)
30kg)
Minimum
Minimum
Minimumthickness
thickness
thickness(in
(in
(inmm)
mm)
mm)ofof
of
protection
protection
protectionfor
for
fora aafire
fire
fireresistance
resistance
resistanceofof
of- --
Construction
Construction
Constructionand
and
andmaterials
materials
materials
A.A.
A.
1.1.
1.
2.2.
2.
444
hours
hours
hours
333
hours
hours
hours
222
hours
hours
hours
111
hours
hours
hours
111
hours
hours
hours
hours
hours
hours
7575
75
5050
50
2525
25
2525
25
2525
25
2525
25
7575
75
7575
75
5050
50
5050
50
5050
50
5050
50
- --
- --
3838
38
3232
32
1919
19
12.5
12.5
12.5
+ (unplastered)
SOLID
SOLID
SOLIDPROTECTION
PROTECTION
PROTECTION+ +(unplastered)
(unplastered)
Concrete
Concrete
Concretenot
not
notleaner
leaner
leanerthan
than
than1:2:4
1:2:4
1:2:4mix
mix
mixwith
with
withnatural
natural
natural
aggregate
aggregate
aggregate- -(a)(a)
(a)
concrete
concrete
concretenot
not
notassumed
assumed
assumedtoto
tobebe
beload
load
loadbearing
bearing
bearing
, ,,
++
++
++
reinforced
reinforced
reinforced
.. ....
(b)
(b)
(b)
concrete
concrete
concreteassumed
assumed
assumedtoto
tobebe
beloadbearing
loadbearing
loadbearing, ,,
reinforced
reinforced
reinforcedinin
inaccordance
accordance
accordancewith
with
withBS
BS
BS5950
5950
5950.. ....
Sprayed
Sprayed
Sprayedvermiculite
vermiculite
vermiculite- -cement
- cement
cement .. ....
.. ....
.. ....
160
160
160
Encased steel beams (Mass per metre not less than 30kg) - continued
B.
HOLLOW PROTECTION*
1.
2.
3.
4
hours
3
hours
2
hours
1
hours
1
hours
hours
38
25
19
12.5
22
19
16
12.5
32
12.5
12.5
12.5
12.5
12.5
12.5
(b)
12.5
10
12.5
(b)
16
15
10
10
(c)
32
10
10
(d)
20
13
10
10
161
Encased steel beams (Mass per metre not less than 30kg) - continued
B.
4.
1
hours
1
hour
hour
63
25
25
25
25
50
38
38
38
HOLLOW PROTECTION*
Vermiculite-cement slabs of 4:1 mix reinforced with wire
mesh and finished with plaster skim. Slabs of thickness of
..
..
..
..
Gypsum-sand plaster 12.5 mm thick applied to
heavy duty (Type B as designated in BS 1105: 1972
Wood wool slabs of thickness of
..
5.
4
hours
Hollow protection means that there is a void between the protective materials and the steel. All hollow protection to columns
shall be effectively sealed at each floor level.
Solid protection means a casing which is bedded close to the steel without intervening cavities and with all joints in that casing
made full and solid.
++
Reinforcement shall consist of steel binding wire not less than 2.3mm in thickness , or a steel mesh weighing not less than 0.48
kg/m2. In concrete protection, the spacing of that reinforcement shall not exceed 150mm in any direction.
Light mesh reinforcement required 12.5mm to 19mm below surface unless special corner beads are used.
162
A.
SOLID PROTECTION*
1.
Sprayed vermiculite-cement
..
4
hours
2
hours
1
hours
1
hour
hour
..
..
..
44
19
HOLOW PROTECTION+
1.
..
..
32
22
16
12.5
2.
..
..
19
12.5
3.
22
16
10
10
Solid protection means a casing which is bedded close to the alloy without intervening cavities and with all joints in that casing
made full and solid.
Hollow protection means that there is a void between the protected material and the alloy. All hollow protection to columns shall
be effectively sealed at each floor level.
163
(A)
(B)
hour
modified++
hour
16
16
12.5
Plain edge boarding on timber joists not less than 38 mm wide with ceiling of (i)
(ii)
(iii)
..
..
..
16
(b)
..
..
..
12.5
12.5
vermiculite
..
..
..
..
..
(iv)
..
..
(v)
12.5
(vi)
12.5
(vii)
25
19
(viii)
(ix)
12.5
(x)
16
9.5
..
Tongued and grooved boarding of not less than 16mm (finished) thickness* on timber
joists not less than 38 mm wide ceiling of (i)
(ii)
(iii)
..
..
..
22
16
(b)
..
..
..
12.5
12.5
9.5
(iv)
vermiculite
..
..
..
..
164
..
..
(v)
(C)
1 hour
hour
modified++
hour
..
..
..
12.5
(b)
..
12.5
(vi)
(vii)
22
(viii)
(ix)
..
..
(a)
..
..
(b)
..
10
Tongued and grooved boardings of not less than 21 mm (finished) thickness* on timber
joists not less than 175 mm deep by 50 mm wide and ceiling of (i)
..
..
16
(ii)
..
..
16
(iii)
..
..
9.5
(iv)
..
(a)
..
..
..
12.5
(b)
..
12.5
(v)
(vi)
..
..
19
(vii)
..
..
12.5
(viii)
12.5
(ix)
..
..
..
(b)
..
10
++
The term modified hour refers to the requirements specified in item 3(a) of Table 3.4A
165
Cored slabs in which the cores are circular or are higher than wide.
Not less than 50 % of the gross across section of the floor should
be solid material
Hollow box section with one or more longitudinal cavities which are
wider than high
Upright T-section
166
Solid slab
65*
40
70
150
65*
40
75
150
65*
65
150
150
25
125
190
25
50
230
25
50
190
55*
30
60
150
55*
30
70
150
55*
55
140
150
25
100
175
25
40
205
25
40
175
25
150
mm
mm
25
150
45*
25
50
100
45*
25
60
125
45*
45
115
125
20
90
160
20
40
180
20
40
160
20
125
mm
35
20
40
100
35
20
45
125
35
35
90
125
20
80
140
20
30
155
20
30
140
20
125
mm
25
15
35
75
25
15
40
100
25
25
75
100
15
70
110
15
25
130
15
25
110
15
100
mm
15
10
25
65
15
10
30
90
15
15
60
90
15
50
100
15
20
105
15
20
100
15
100
mm
Floor construction
PART VIII:
Cored slabs in which the cores are circular or are higher than wide.
Not less than 50 % of the gross across section of the floor should
be solid material
Hollow box section with one or more longitudinal cavities which are
wider than high
Upright T-sections
Solid slab
100*
50
110
150
100*
50
125
150
100*
100
250
150
65*
125
190
65*
65
230
65*
50
190
65*
150
4
mm
85*
45
90
150
85
45
100
150
85*
85
200
150
50*
100
175
50*
50
205
50*
40
175
50*
150
3
mm
65*
35
70
125
65*
35
75
125
65*
65
150
125
40
90
160
40
40
180
40
40
160
40
125
2
mm
50*
25
50
125
50*
25
55
125
50*
50
110
125
30
80
140
30
30
155
30
30
140
30
125
1
mm
40
20
45
100
40
20
45
100
40
40
90
100
25
70
110
25
25
130
25
25
110
25
100
1
mm
25
15
30
90
25
15
30
90
25
25
60
90
15
50
100
15
25
105
15
20
100
15
90
mm
Floor construction
PART IX:
PART X: GLAZING
1.
1 hour
hour
6.35
6.35
6.35
6.35
98.43
Glass , in direct combination with metal , the melting point of which is not lower than 982.2
oC , in square not exceeding 0.015 sq.m. in area
.. ..
Thickness of glass ..
2.
Minimum thickness of
glazing in mm for a period of
..
..
..
..
..
Glass reinforced with wire not less than 0.46 mm in diameter laid to a square mesh
measuring 12.70 mm from centre to centre of wire , and
electrically welded at the intersections , or laid to a hexagonal mesh
measuring 25.40 mm across the flat side ..
Thickness of glass ..
..
..
..
..
..
In windows , doors , borrowed lights , lanterns and skylights , glass complying with
paragraphs 1 or 2 of this Table shall be fixed with wood or metal beads or with a glazing
compound in conjunction with sprigs or clips in panels not exceeding 0.372 sq.m. in area in
timber frames (fixed shut) having a minimum width and thickness of 44.45 mm clear of
rebates
..
3.
4.
Glass reinforced with wire as in paragraph 2 of this Table , in windows , doors , borrowed
lights , lanterns and skylights , fixed with metal beads in panels not exceeding 1.115 sq.m in
metal frames (fixed shut) all metal having a melting point not lower than 982.2oC , the
thickness of glass ..
..
..
..
..
Glass bricks or blocks in walls ..
..
..
..
..
Laid in cement / lime / sand mortar with light wire reinforcing mesh in every third
horizontal joint in a panel not exceeding 2.438 m in width or height set along the sides and
head into recesses in the surrounding non-combustible construction. The depth of such
recessed shall be not less than 25.40 mm , the glass blocks extending into the recesses to a
depth of 12.70 mm and bedded upon layer of glass fibre. A non-hardening mastic shall be
used to fill the spaces between the sides of the recesses and the faces of the panels
In this Table the absence of a figure in a period column indicated that glazing described is not acceptable for the period applicable
to that column.
168
APPENDIX B TO C1 3.5
PART 1
CALCULATION OF PERMITTED LIMITS OF UNPROTECTED AREAS
General rules applicable to this Appendix
1.
The permitted limit of unprotected areas in any side of a building or compartment shall be calculated by reference to the requirements
of Part II.
2.
For the purposes of this Appendix , the expression "unprotected area" has the meaning ascribed to it by C1 1.2.61, but in calculating
the size of unprotected areas or the permitted limit of unprotected areas, the following provisions shall apply (a)
where any area of an external wall is an unprotected area, only because it has combustible material attached to it as cladding, the
area of that unprotected area shall be deemed to be half the area of such cladding;
(b)
when unprotected openings in the same compartment are recessed at a distance or an angle to the plane of reference, the width
of the unprotected opening can be reduced accordingly when projected to the plane of reference based on Table III and IV.
However, such reduction is not applicable to the following:
(i)
(ii)
(c)
Concave building profile or the like where a specific point on the receiving panel receives radiation from more than one
source.
When the unprotected opening is along a continuous circular profile where its size and angle cannot be determine.
(iii)
(iv)
an unprotected area which does not exceed 0.1 m2 and which is not less than 1.5 m from any other unprotected area in
the same side of the building or compartment (unless that other falls within (iii) below);
one or more unprotected areas having an area (or, if more than one, the aggregate area) not exceeding 1 m2 and not less
than 4 m from any other unprotected area in the same side of the building or compartment (except any such area as is
specified in (1) above);
an unprotected area in any part of an external wall which forms part of a protected shaft ;
an unprotected area in the side of a building not divided into compartments , if the area is not less than 28 m above any
ground adjoining that side of the building.
PART II
Rules of calculation by reference to an enclosing rectangle
3.
The conditions of this Part of this Appendix shall be satisfied if a building or compartment is so situated that no point on the relevant
boundary is either between the relevant plane of reference and the side of the building or compartment or at a distance from the
relevant plane of reference which is less than the distance specified in the Tables to this Part of this Appendix , according to the
purpose group of the building or compartment, the dimensions of the enclosing rectangle and the unprotected percentage.
4.
(b)
(c)
enclose all the outer edge of any unprotected area of the building or , if the building is divided into compartments, of the
compartment (other than any of an unprotected area which is at an angle of more than 80o to the plane of reference the outer
edges being for this purpose projected on the plane of reference by line perpendicular to such plane:
have two horizontal sides; and
have height and width falling within those listed in the Tables to this Part of this Appendix:
"unprotected percentage" means the percentage of the area of the enclosing rectangle which is equal to the aggregate of the
unprotected areas taken into account in calculating the enclosing rectangle and as projected on it.
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
3
6
9
12
15
18
21
24
27
30
40
No limit
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
1.0
1.0
1.0
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
20
40
50
1.0
1.5
1.5
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
1.5
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
1.0
1.5
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
1.5
2.0
2.5
3.0
3.0
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
2.0
2.5
3.0
3.5
4.0
4.0
4.0
4.5
4.5
4.5
4.5
4.5
5.0
5.0
5.0
5.0
1.0
1.0
1.0
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
30
2.0
3.0
3.5
4.0
4.5
4.5
5.0
5.0
5.0
5.0
5.5
5.5
5.5
6.0
6.0
6.0
1.5
2.0
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
60
2.0
3.0
4.0
4.5
5.0
5.0
5.5
5.5
6.0
6.0
6.5
6.5
6.5
7.0
7.0
7.0
1.5
2.0
2.5
3.0
3.0
3.0
3.0
3.5
3.5
3.5
3.5
3.5
70
2.5
3.5
4.5
5.0
5.5
5.5
6.0
6.0
6.5
6.5
7.0
7.5
7.5
7.5
8.0
8.0
2.0
2.5
3.0
3.0
3.5
3.5
3.5
3.5
4.0
4.0
4.0
4.0
80
2.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.0
7.0
8.0
8.0
8.5
8.5
8.5
8.5
2.0
2.5
3.0
3.5
3.5
4.0
4.0
4.0
4.0
4.0
4.0
4.0
90
Distance in metres from relevant boundary for unprotected percentage not exceeding
3.0
4.0
5.0
5.5
6.0
6.5
7.0
7.0
7.5
8.0
8.5
9.0
9.5
9.5
10.0
10.0
2.0
3.0
3.5
3.5
4.0
4.0
4.5
4.5
4.5
4.5
5.0
5.0
100
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
1.0
1.5
1.5
1.5
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
1.0
1.0
1.5
1.5
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
20
1.5
2.5
3.5
3.5
4.0
4.5
4.5
5.0
5.0
5.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
2.0
3.0
4.0
4.5
5.0
5.0
5.5
5.5
6.0
6.0
6.5
6.5
7.0
7.0
7.0
7.0
7.0
1.5
2.5
3.0
3.5
3.5
4.0
4.0
4.5
4.5
4.5
5.0
5.0
5.0
5.0
5.0
5.0
5.0
2.0
3.0
3.5
4.5
5.0
5.0
5.5
6.0
6.0
6.5
6.5
7.0
7.0
7.0
7.5
7.5
7.5
2.0
3.5
4.5
5.0
5.5
6.0
6.5
7.0
7.0
7.5
8.0
8.5
9.0
9.0
9.5
9.5
9.5
1.0
2.0
2.5
3.0
3.0
3.5
3.5
3.5
3.5
3.5
3.5
4.0
4.0
4.0
4.0
4.0
4.0
2.5
4.0
5.0
6.0
6.5
7.0
7.5
8.0
8.0
8.5
9.5
10.0
10.5
11.0
11.5
11.5
12.0
2.5
3.5
4.5
5.0
5.5
6.0
6.5
6.5
7.0
7.0
7.5
8.0
8.0
8.5
8.5
8.5
8.5
3.0
4.5
5.5
6.5
7.0
7.5
8.5
8.5
9.0
9.5
10.5
11.0
12.0
13.0
13.5
13.5
14.0
2.5
4.0
5.0
5.5
6.0
6.5
7.0
7.5
7.5
8.0
8.5
9.0
9.5
10.0
10.0
10.0
10.5
3.0
5.0
6.0
7.0
8.0
8.5
9.0
9.5
10.5
10.5
12.0
13.0
13.5
14.5
15.0
15.0
15.5
3.0
4.5
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
11.0
11.5
11.5
11.5
12.0
3.5
5.0
6.5
7.5
8.5
9.0
10.0
10.5
11.0
11.5
12.0
14.0
14.5
16.0
16.5
17.0
17.0
3.0
4.5
5.5
6.5
7.0
8.0
8.5
9.0
9.5
9.5
10.5
11.5
11.5
12.5
12.5
12.5
12.5
Distance in metres from relevant boundary for unprotected percentage not exceeding
30
40
50
60
70
80
90
3.5
5.5
7.0
8.0
9.0
10.0
10.5
11.5
12.0
12.5
14.0
15.0
16.0
17.0
18.0
18.5
19.0
3.5
5.0
6.0
7.0
7.5
8.5
9.0
9.5
10.0
10.5
11.5
12.5
13.0
13.5
14.5
14.5
15.0
100
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
1.0
1.5
2.0
2.5
2.5
2.5
3.0
3.0
3.5
3.5
4.0
4.0
4.0
4.0
4.0
4.0
4.0
1.0
1.5
2.0
2.0
2.0
2.5
2.5
3.0
3.0
3.0
3.0
3.5
3.5
3.5
3.5
3.5
3.5
20
2.0
3.0
4.0
5.0
5.5
6.0
6.5
6.5
7.0
7.5
8.0
8.5
8.5
9.0
9.0
9.0
9.0
2.5
4.0
5.0
5.5
6.5
7.0
7.5
8.0
8.5
8.5
9.5
10.0
10.5
11.0
11.5
11.5
12.0
1.5
2.5
3.5
4.0
4.5
5.0
5.5
5.5
6.0
6.5
7.0
7.0
7.5
7.5
7.5
7.5
8.0
2.0
3.5
4.5
5.0
6.0
6.5
7.0
7.5
8.0
8.0
9.0
9.5
10.0
10.0
10.0
10.0
10.0
172
2.5
4.0
5.0
6.0
7.0
7.5
8.0
8.5
9.0
9.5
11.0
11.5
12.0
13.0
13.5
14.0
14.0
1.5
2.5
3.0
3.5
4.0
4.5
5.0
5.0
5.5
5.5
6.0
6.0
6.5
6.5
6.5
6.5
6.5
2.5
4.5
6.0
7.0
8.0
8.5
9.5
10.0
10.5
11.0
12.0
13.0
14.0
15.0
16.0
16.5
17.0
2.5
4.5
5.5
6.5
7.0
8.0
8.5
9.0
9.5
10.0
11.0
12.0
12.5
13.5
14.0
14.0
14.5
3.0
5.0
6.5
7.5
8.5
9.5
10.5
11.0
11.5
12.0
13.5
15.0
16.0
17.0
18.0
19.0
19.5
3.0
5.0
6.0
7.0
8.0
8.5
9.5
10.0
10.5
11.0
12.5
13.5
14.0
15.0
16.0
16.5
17.0
3.5
5.5
7.0
8.5
9.5
11.0
11.5
12.0
12.5
13.5
15.0
16.5
17.5
19.0
20.5
21.0
22.0
3.5
5.5
6.5
8.0
9.0
9.5
10.5
11.0
11.5
12.0
13.5
15.0
15.5
17.0
18.0
18.5
19.0
4.0
6.0
8.0
9.0
10.5
11.5
12.5
13.0
13.5
14.5
16.5
18.0
19.5
21.0
22.5
23.5
24.0
3.5
5.5
7.0
8.5
9.5
10.5
11.0
12.0
12.5
13.5
15.0
16.5
17.0
18.5
19.5
20.5
21.0
Distance in metres from relevant boundary for unprotected percentage not exceeding
30
40
50
60
70
80
90
TABLE 1 - continued
4.0
6.5
8.5
10.0
11.0
13.0
13.0
14.0
14.5
15.5
17.5
19.0
20.5
22.5
24.0
25.5
26.5
4.0
6.0
7.5
9.0
10.0
11.0
12.0
13.0
13.5
14.0
16.0
17.5
18.0
20.0
21.5
22.5
23.0
100
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
0.5
1.5
2.0
2.5
3.0
3.0
3.5
3.5
4.0
4.0
4.5
5.0
5.0
5.0
5.0
5.5
5.5
0.5
1.5
2.0
2.5
2.5
3.0
3.0
3.5
3.5
4.0
4.5
4.5
4.5
4.5
4.5
4.5
4.5
20
2.0
3.5
4.5
5.5
6.5
7.0
7.5
8.0
8.5
9.0
10.0
11.0
11.5
12.0
12.0
12.0
12.0
2.5
4.0
5.5
6.5
7.5
8.0
9.0
9.5
10.0
10.5
12.0
13.0
13.5
14.5
15.5
16.0
16.0
1.5
2.5
3.5
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.5
9.0
9.5
10.0
10.0
10.0
10.0
2.0
3.5
5.0
6.0
6.5
7.5
8.0
8.5
9.0
9.5
11.0
12.0
12.5
13.5
13.5
13.5
13.5
173
2.5
4.5
5.5
7.0
8.0
8.5
9.5
10.0
11.0
11.5
13.0
14.0
15.0
16.5
17.0
17.5
18.0
1.5
2.5
3.5
4.0
5.0
5.5
6.0
6.0
6.5
7.0
7.5
8.0
8.5
8.5
9.0
9.0
9.0
3.0
5.0
6.5
8.0
9.0
10.0
10.5
11.5
12.5
13.0
14.5
16.0
17.0
18.5
20.0
20.5
21.0
3.0
5.0
6.5
7.5
8.5
9.5
10.5
10.5
11.5
12.0
13.5
14.5
15.5
17.0
18.0
18.5
19.0
3.5
5.5
7.5
8.5
10.0
11.0
12.0
12.5
13.5
14.0
16.0
17.5
19.0
21.0
22.5
23.5
24.0
3.0
5.5
7.0
8.5
9.5
10.5
11.0
12.0
13.0
13.0
15.0
16.5
17.5
19.0
20.5
21.5
22.0
3.5
6.0
8.0
9.5
11.0
12.0
13.0
14.0
15.0
15.5
18.0
19.5
21.0
23.5
25.0
26.5
27.5
3.5
6.0
7.5
9.0
10.5
11.5
12.5
13.0
14.0
14.5
16.5
18.0
19.5
21.0
22.5
23.5
25.0
4.0
7.0
9.0
10.5
12.0
13.0
14.0
15.0
16.0
17.0
19.0
21.0
23.0
25.5
27.5
29.0
30.0
4.0
6.5
8.5
10.0
11.0
12.5
13.5
14.0
15.0
16.0
18.0
20.0
21.0
23.5
25.0
26.5
26.5
Distance in metres from relevant boundary for unprotected percentage not exceeding
30
40
50
60
70
80
90
TABLE I - continued
4.5
7.0
9.5
11.5
13.0
14.0
15.0
16.0
17.0
18.0
20.5
22.5
24.5
27.5
29.5
31.0
32.5
4.5
7.0
9.0
10.5
12.0
13.0
14.0
15.0
16.0
16.5
19.0
21.0
22.5
25.0
27.0
28.5
29.5
100
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
1.0
1.5
2.0
2.5
3.0
3.5
3.5
3.5
4.0
4.0
5.0
5.5
5.5
6.0
6.0
6.0
6.0
20
40
50
1.5
2.5
3.5
4.5
5.5
6.0
6.5
7.0
7.5
8.0
9.0
9.5
10.5
11.0
11.0
11.5
11.5
2.0
3.5
5.0
6.0
7.0
8.0
8.5
9.0
10.0
10.0
11.5
12.5
13.5
14.5
15.5
15.5
15.5
2.5
4.5
6.0
7.0
8.5
9.0
10.0
11.0
11.5
12.0
14.0
15.0
16.0
17.5
19.0
19.5
20.0
30
3.0
5.0
7.0
8.0
9.5
10.5
11.5
12.5
13.0
13.5
15.5
17.0
18.5
20.5
21.5
22.5
23.5
60
3.5
6.0
7.5
9.0
10.5
11.5
13.0
13.5
14.0
15.0
17.5
19.0
20.5
22.5
24.5
26.0
27.0
70
4.0
6.5
8.5
10.5
11.5
12.5
14.0
15.0
16.0
17.0
19.0
21.0
22.5
25.0
27.0
28.5
29.5
80
4.0
7.0
9.5
11.0
12.5
13.5
15.0
16.0
17.0
18.0
20.5
22.5
24.5
27.5
30.0
32.0
33.0
90
Distance in metres from relevant boundary for unprotected percentage not exceeding
TABLE I - continued
4.5
7.5
10.0
12.0
13.5
14.5
16.0
17.0
18.0
19.0
22.0
24.0
26.5
29.5
32.0
34.0
35.0
100
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
3
6
9
12
15
18
21
24
27
30
40
50
60
80
No limit
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
1.5
2.0
2.5
3.0
3.0
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
1.0
1.5
1.5
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
20
40
50
2.0
2.5
3.0
3.0
3.5
3.5
3.5
3.5
4.0
4.0
4.0
4.0
4.0
4.0
4.0
2.0
3.0
3.5
3.5
4.0
4.0
4.5
4.5
4.5
4.5
5.0
5.0
5.0
5.0
5.0
2.0
3.0
3.5
4.0
4.5
4.5
5.0
5.0
5.0
5.0
5.5
5.5
5.5
6.0
6.0
6.0
6.0
2.5
3.5
4.5
5.0
5.5
5.5
6.0
6.0
6.5
6.5
7.0
7.5
7.5
7.5
8.0
8.0
8.0
3.0
4.0
5.0
5.5
6.0
6.5
7.0
7.0
7.5
8.0
8.5
9.0
9.5
9.5
10.0
10.0
10.0
1.5
2.0
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
30
3.0
4.5
5.5
6.5
7.0
7.5
8.0
8.5
8.5
9.0
10.0
10.5
11.0
11.5
12.0
12.0
12.0
2.5
3.0
4.0
4.0
4.5
5.0
5.0
5.0
5.5
5.5
5.5
6.0
6.0
6.0
6.0
60
3.5
5.0
6.0
7.0
7.5
8.0
9.0
9.5
9.5
10.0
11.0
11.5
12.0
13.0
13.5
14.0
14.0
2.5
3.5
4.0
4.5
5.0
5.0
5.5
5.5
6.0
6.0
6.5
6.5
7.0
7.0
7.0
70
3.5
5.5
6.5
7.5
8.0
9.0
9.5
10.0
10.5
11.0
12.0
13.0
13.5
14.5
15.0
15.5
16.0
2.5
3.5
4.5
5.0
5.5
6.0
6.0
6.0
6.5
6.5
7.0
7.5
7.5
8.0
8.0
80
4.0
5.5
7.0
8.0
9.0
9.5
10.0
10.5
11.0
12.0
13.0
14.0
15.0
16.0
16.5
17.0
18.0
3.0
4.0
5.0
5.5
6.0
6.5
6.5
7.0
7.0
7.5
8.0
8.0
8.5
9.0
9.0
90
Distance in metres from relevant boundary for unprotected percentage not exceeding
4.0
6.0
7.0
8.5
9.0
10.0
10.5
11.0
12.0
12.5
14.0
15.0
16.0
17.5
18.0
19.0
19.0
3.0
4.0
5.0
5.5
6.0
6.5
7.0
7.5
7.5
8.0
8.5
9.0
9.5
9.5
10.0
100
V (SHOPS), VI (FACTORY) & VIII (STORAGE & GENERAL OPEN-SIDED CARPARKING DECKS SEE TABLE 1)
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
2.0
3.0
3.5
4.5
5.0
5.0
5.5
6.0
6.0
6.5
6.5
7.0
7.0
7.0
7.5
7.5
7.5
1.5
2.5
3.5
3.5
4.0
4.5
4.5
5.0
5.0
5.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
20
40
50
3.0
4.5
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
11.0
11.5
11.5
11.5
11.5
3.5
5.0
6.0
7.0
7.5
8.5
9.0
9.5
10.0
10.5
11.5
12.5
13.0
13.5
14.5
14.5
15.0
2.5
4.0
5.0
6.0
6.5
7.0
7.5
8.0
8.0
8.5
9.5
10.0
10.5
11.0
11.5
11.5
12.0
3.0
5.0
6.0
7.0
8.0
8.5
9.0
9.5
10.5
10.5
12.0
13.0
13.5
14.5
15.0
15.0
15.5
3.5
5.5
7.0
8.0
9.0
10.0
10.5
11.5
12.0
12.5
14.0
15.0
16.0
17.0
18.0
18.5
19.0
2.5
3.5
4.5
5.0
5.5
6.0
6.5
6.5
7.0
7.0
7.5
8.0
8.0
8.5
8.5
8.5
8.5
30
4.0
6.5
7.5
9.0
10.0
11.0
12.0
12.5
13.5
14.0
15.5
17.0
18.0
19.5
21.0
22.0
22.5
4.0
5.5
6.5
7.5
8.5
9.5
10.0
11.0
11.5
12.0
13.0
14.0
15.0
16.0
16.5
17.0
17.5
60
4.5
7.0
8.5
9.5
11.0
12.0
13.0
14.0
14.5
15.0
17.5
19.0
20.0
21.5
23.0
24.0
25.0
4.0
6.0
7.5
8.5
9.5
10.0
11.0
12.0
12.5
13.0
14.5
15.5
16.5
17.5
18.5
19.5
20.0
70
5.0
7.5
9.0
11.0
12.0
13.0
14.0
15.0
16.0
16.5
18.5
20.5
21.5
23.5
25.5
27.0
28.0
4.5
6.5
8.0
9.0
10.0
11.0
12.0
13.0
13.5
14.0
15.5
17.0
18.0
19.5
21.0
21.5
22.5
80
5.5
8.0
9.5
11.5
13.0
14.0
15.0
16.0
17.0
17.5
20.0
23.0
23.5
26.0
28.0
29.5
30.5
5.0
7.0
8.5
9.5
11.0
12.0
13.0
13.5
14.5
15.0
17.0
18.5
19.5
21.5
22.5
23.5
24.5
90
Distance in metres from relevant boundary for unprotected percentage not exceeding
TABLE 2 - continued
5.5
8.5
10.5
12.0
13.5
14.5
16.0
16.5
17.5
18.5
21.0
23.0
25.0
27.5
30.0
31.5
34.0
5.0
7.0
9.0
10.5
11.5
12.5
13.5
14.5
15.0
16.0
17.5
19.5
21.0
23.0
24.5
26.0
27.0
100
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
2.0
3.5
4.5
5.0
6.0
6.5
7.0
7.5
8.0
8.0
9.0
9.5
10.0
10.0
10.0
10.0
10.0
2.0
3.0
4.0
5.0
5.5
6.0
6.5
6.5
7.0
7.5
8.0
8.5
8.5
9.0
9.0
9.0
9.0
20
40
50
3.5
5.5
6.5
8.0
9.0
9.5
10.5
11.0
11.5
12.0
13.5
15.0
15.5
17.0
18.0
18.5
19.0
4.0
6.0
7.5
9.0
10.0
11.0
12.0
13.0
13.5
14.0
16.0
17.5
18.0
20.0
21.5
22.5
23.0
2.5
4.5
6.0
7.0
8.0
8.5
9.5
10.0
10.5
11.0
12.0
13.0
14.0
15.0
16.0
16.5
17.0
3.5
5.5
7.0
8.5
9.5
11.0
11.5
12.0
12.5
13.5
15.0
16.5
17.5
19.0
20.5
21.0
22.0
4.0
6.5
8.5
10.0
11.0
12.0
13.0
14.0
14.5
15.5
17.5
19.0
20.5
22.5
24.0
25.5
26.5
2.5
4.5
5.5
6.5
7.0
8.0
8.5
9.0
9.5
10.0
11.0
12.0
12.5
13.5
14.0
14.0
14.5
30
5.0
7.5
9.5
11.0
12.5
13.5
14.5
15.5
16.5
17.0
19.5
21.5
23.0
26.0
28.0
29.5
30.5
4.5
7.0
8.5
10.0
11.5
12.5
13.5
14.5
15.0
16.0
18.0
19.5
21.0
23.0
24.5
25.5
27.0
60
5.0
8.0
10.0
12.0
13.5
14.5
16.0
16.5
17.5
18.5
21.5
23.5
26.0
28.5
31.0
32.5
34.0
5.0
7.5
9.5
11.0
12.5
13.5
14.5
15.5
16.5
17.0
19.5
21.5
23.5
25.5
27.5
28.5
30.0
70
6.0
9.0
11.0
13.0
14.5
16.0
17.0
18.5
19.5
20.5
23.5
26.0
27.5
31.0
33.5
35.5
37.0
5.5
8.0
10.0
12.0
13.5
14.5
16.0
17.0
18.0
18.5
21.0
23.0
25.0
28.0
30.0
31.5
34.0
80
6.5
9.5
12.0
14.0
15.5
17.0
18.0
19.5
20.5
21.5
25.0
27.5
29.5
33.5
36.0
39.0
41.0
6.0
9.0
11.0
13.0
14.5
15.5
16.5
18.0
19.0
20.0
22.5
25.0
27.0
30.0
32.5
34.5
36.0
90
Distance in metres from relevant boundary for unprotected percentage not exceeding
TABLE 2 - continued
6.5
10.0
12.5
14.5
16.5
18.0
19.5
20.5
21.5
22.5
26.0
29.0
31.0
35.0
38.5
41.5
43.5
6.0
9.0
11.5
13.5
15.0
16.5
17.5
19.0
20.0
21.0
23.5
26.0
28.0
31.5
34.5
37.0
39.0
100
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
2.0
3.5
5.0
6.0
6.5
7.5
8.0
8.5
9.0
9.5
11.0
12.0
12.5
13.5
13.5
13.5
13.5
2.0
3.5
4.5
5.5
6.5
7.0
7.5
8.0
8.5
9.0
10.0
11.0
11.5
12.0
12.0
12.0
12.0
20
40
50
3.5
6.0
7.5
9.0
10.5
11.5
12.5
13.0
14.0
14.5
16.5
18.0
19.5
21.0
22.5
23.5
25.0
4.5
7.0
9.0
10.5
12.0
13.0
14.0
15.0
16.0
16.5
19.0
21.0
22.5
25.0
27.0
28.5
29.5
3.0
5.0
6.5
8.0
9.0
10.0
10.5
11.5
12.5
13.0
14.5
16.0
17.0
18.5
20.0
20.5
21.0
3.5
6.0
8.0
9.5
11.0
12.0
13.0
14.0
15.0
15.5
18.0
19.5
21.0
23.5
25.0
26.5
27.5
4.5
7.0
9.5
11.5
13.0
14.0
15.0
16.0
17.0
18.0
20.5
22.5
24.5
27.5
29.5
31.0
32.5
3.0
5.0
6.5
7.5
8.5
9.5
10.0
10.5
11.5
12.0
13.5
14.5
15.5
17.0
18.0
18.5
19.0
30
5.0
8.5
11.0
12.5
14.5
15.5
16.5
18.0
19.0
20.0
23.0
25.5
27.5
31.0
33.5
36.0
37.5
5.0
8.0
10.0
12.0
13.5
14.5
15.5
16.0
18.0
18.5
21.5
23.5
25.5
28.5
31.0
32.5
34.5
60
5.5
9.5
12.0
14.0
15.5
16.5
18.0
19.5
20.5
21.5
25.0
27.5
30.0
34.5
37.0
39.5
42.0
5.5
9.0
11.0
13.0
14.5
16.0
17.0
18.0
19.0
20.5
23.0
25.5
28.0
31.5
34.5
36.5
38.0
70
6.0
10.0
13.0
15.0
17.0
18.5
20.0
21.0
21.5
23.5
27.5
30.0
32.5
37.0
40.0
43.0
45.5
6.0
9.5
12.0
14.0
16.0
17.0
18.5
20.0
21.0
22.0
25.5
28.0
30.5
34.0
37.0
39.5
41.5
80
7.0
10.5
13.5
16.0
18.0
19.5
21.0
22.5
24.0
25.0
29.0
32.0
35.0
39.5
43.0
46.5
49.5
6.5
10.0
13.0
15.0
16.5
18.0
20.0
21.0
22.5
23.5
27.0
30.0
32.5
36.5
40.0
43.0
45.5
90
Distance in metres from relevant boundary for unprotected percentage not exceeding
TABLE 2 - continued
7.5
11.0
14.5
16.5
19.0
20.5
22.0
24.0
25.5
26.5
30.5
33.5
36.5
41.5
45.5
49.0
52.0
7.0
10.5
13.5
16.0
17.5
19.5
21.0
22.0
23.5
25.0
28.5
31.5
33.5
38.5
42.0
45.5
48.0
100
3
6
9
12
15
18
21
24
27
30
40
50
60
80
100
120
No limit
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
2.0
3.5
5.0
6.0
7.0
8.0
8.5
9.0
10.0
10.0
11.5
12.5
13.5
14.5
15.5
15.5
15.5
20
40
50
3.0
5.0
7.0
8.0
9.5
10.5
11.5
12.5
13.0
13.5
15.5
17.0
18.5
20.5
21.5
22.5
23.5
4.0
6.5
8.5
10.5
11.5
12.5
14.0
15.0
16.0
17.0
19.0
21.0
22.5
25.0
27.0
28.5
29.5
4.5
7.5
10.0
12.0
13.5
14.5
16.0
17.0
18.0
19.0
22.0
24.0
26.5
29.5
32.0
34.0
35.0
30
5.5
8.5
11.5
13.5
15.0
16.5
18.0
19.0
20.0
21.0
24.5
27.0
29.5
33.0
36.5
39.0
40.5
60
6.0
9.5
12.5
14.5
16.5
17.5
19.0
20.5
22.0
23.0
26.5
29.5
32.0
36.5
40.5
43.0
44.5
70
6.5
10.5
13.5
16.0
18.0
19.5
21.0
22.5
24.0
25.0
29.0
32.0
35.0
39.5
43.0
46.5
48.5
80
7.0
11.0
14.5
17.0
19.0
20.5
22.5
24.0
25.5
26.5
30.5
34.5
37.0
42.0
46.5
50.5
52.0
90
Distance in metres from relevant boundary for unprotected percentage not exceeding
TABLE 2 - continued
7.5
12.0
15.0
17.5
20.0
21.5
23.5
25.5
27.0
28.0
32.5
36.0
39.0
44.0
48.5
53.0
55.5
100
72%
85%
90%
94%
95%
96%
97%
98%
98%
98%
99%
99%
99%
99%
99%
99%
3m
6m
9m
15m
21m
27m
30m
40m
50m
60m
70m
80m
90m
100m
110m
120m
1m
98%
98%
98%
98%
98%
97%
97%
96%
95%
94%
93%
91%
88%
80%
72%
54%
2m
98%
97%
97%
97%
96%
96%
95%
94%
93%
90%
90%
87%
82%
72%
62%
41%
3m
97%
96%
96%
96%
95%
94%
94%
92%
90%
88%
86%
83%
77%
65%
54%
33%
4m
96%
96%
95%
95%
94%
93%
92%
90%
88%
85%
83%
79%
72%
59%
47%
28%
5m
95%
95%
94%
94%
93%
92%
90%
89%
86%
82%
80%
75%
68%
54%
41%
24%
6m
94%
94%
93%
93%
92%
90%
89%
87%
84%
79%
77%
72%
64%
49%
37%
21%
7m
94%
93%
92%
92%
90%
89%
88%
85%
82%
77%
75%
69%
60%
45%
33%
18%
8m
93%
92%
91%
90%
89%
88%
86%
84%
80%
74%
72%
66%
57%
41%
30%
16%
9m
92%
91%
90%
90%
88%
87%
85%
82%
78%
72%
70%
63%
54%
38%
28%
15%
10m
91%
90%
90%
89%
87%
86%
83%
80%
76%
70%
67%
61%
51%
36%
25%
13%
11m
90%
90%
89%
88%
86%
84%
82%
79%
74%
68%
65%
58%
48%
33%
24%
12%
12m
90%
89%
88%
87%
85%
83%
81%
77%
73%
66%
63%
56%
46%
31%
22%
11%
13m
89%
88%
87%
86%
84%
82%
79%
76%
71%
64%
61%
54%
43%
29%
21%
11%
14m
88%
87%
86%
85%
83%
81%
78%
74%
69%
62%
59%
51%
41%
28%
19%
10%
15m
88%
87%
85%
84%
82%
80%
77%
73%
68%
60%
57%
50%
40%
26%
18%
9%
16m
1m
2.6 m
Relevant boundary
85%
Setback Distance
100%
100%
72%
Plane of reference
Width of
unprotected 100%
opening
Bldg A
Width of
100%
unprotected
opening
Illustration A
Bldg B
Width of
unprotected
opening (4m)
100%
Illustration A (Enlarged)
2.6 m
Distance to
Plane of reference
100%
72% (2.88m)
Plane of reference
87%
86%
84%
83%
81%
79%
76%
72%
66%
58%
55%
48%
38%
25%
17%
9%
17m
85%
84%
83%
81%
79%
76%
73%
69%
63%
55%
52%
44%
35%
22%
15%
8%
19m
85%
83%
82%
80%
78%
75%
72%
68%
62%
54%
50%
43%
33%
21%
15%
7%
20m
Relevant boundary
86%
85%
84%
82%
80%
78%
74%
70%
65%
57%
54%
46%
36%
24%
16%
8%
18m
Note: * To take next higher width when actual width exceeds that of the table. Interpolation of the figures is not permitted.
+ To take the lower distance from table when actual distance exceeds that of the table. Interpolation of the figures is not permitted.
84%
83%
81%
79%
77%
74%
71%
66%
60%
52%
49%
41%
32%
21%
14%
7%
21m
83%
82%
80%
78%
76%
73%
70%
65%
59%
51%
48%
40%
31%
20%
13%
7%
22m
83%
81%
80%
78%
75%
72%
69%
64%
58%
49%
46%
39%
30%
19%
13%
6%
23m
82%
81%
79%
77%
74%
71%
68%
63%
57%
48%
45%
38%
29%
18%
12%
6%
24m
81%
80%
78%
76%
74%
70%
67%
62%
55%
47%
44%
36%
28%
17%
12%
6%
25m
81%
79%
77%
75%
73%
70%
66%
61%
54%
46%
43%
35%
27%
17%
11%
6%
26m
80%
78%
77%
74%
72%
69%
65%
60%
53%
45%
41%
34%
26%
16%
11%
6%
27m
16%
6m
9m
32%
33%
40%
43%
52%
59%
64%
68%
71%
74%
76%
78%
79%
21m
27m
30m
40m
50m
60m
70m
80m
90m
100m
110m
120m
79%
77%
75%
73%
70%
67%
63%
58%
51%
42%
39%
24%
15%
10%
5%
29m
25%
15m
5%
11%
3m
28m
78%
76%
74%
72%
69%
66%
62%
57%
50%
41%
38%
32%
24%
15%
10%
5%
30m
77%
76%
74%
71%
68%
65%
61%
56%
49%
40%
37%
31%
23%
14%
10%
5%
31m
77%
75%
73%
71%
68%
64%
60%
55%
48%
40%
37%
30%
22%
14%
9%
5%
32m
76%
74%
72%
70%
67%
63%
59%
54%
47%
39%
36%
29%
22%
13%
9%
5%
33m
76%
74%
72%
69%
66%
63%
58%
53%
46%
38%
35%
28%
21%
13%
9%
4%
34m
75%
73%
71%
68%
65%
62%
57%
52%
45%
37%
34%
28%
21%
13%
9%
4%
35m
74%
72%
70%
68%
65%
61%
57%
51%
45%
36%
33%
27%
20%
12%
8%
4%
36m
74%
72%
70%
67%
64%
60%
56%
50%
44%
35%
33%
26%
19%
12%
8%
4%
37m
73%
71%
69%
66%
63%
59%
55%
50%
43%
35%
32%
26%
19%
12%
8%
4%
38m
73%
71%
68%
66%
63%
59%
54%
49%
42%
34%
31%
25%
19%
11%
8%
4%
39m
72%
70%
68%
65%
62%
58%
54%
48%
41%
33%
31%
25%
18%
11%
7%
4%
40m
72%
69%
67%
64%
61%
57%
53%
47%
41%
33%
30%
24%
18%
11%
7%
4%
41m
71%
69%
66%
64%
60%
57%
52%
47%
40%
32%
29%
24%
17%
11%
7%
4%
42m
70%
68%
66%
63%
60%
56%
51%
46%
39%
31%
29%
23%
17%
10%
7%
3%
43m
1m
2.6 m
Relevant boundary
85%
Setback Distance
100%
100%
72%
Plane of reference
Width of
unprotected 100%
opening
Bldg A
Width of
100%
unprotected
opening
Illustration A
+ To
Bldg B
Width of
unprotected
opening (4m)
100%
Illustration A (Enlarged)
2.6 m
Distance to
Plane of reference
100%
72% (2.88m)
Plane of reference
70%
68%
65%
62%
59%
55%
51%
45%
39%
31%
28%
23%
17%
10%
7%
3%
44m
69%
67%
64%
61%
58%
54%
49%
44%
37%
30%
27%
22%
16%
10%
6%
3%
46m
68%
66%
63%
61%
57%
53%
49%
43%
37%
29%
27%
21%
16%
9%
6%
3%
47m
Relevant boundary
69%
67%
65%
62%
58%
55%
50%
45%
38%
30%
28%
22%
16%
10%
7%
3%
45m
Note: * To take next higher width when actual width exceeds that of the table. Interpolation of the figures is not permitted.
take the lower distance from table when actual distance exceeds that of the table. Interpolation of the figures is not permitted
68%
65%
63%
60%
57%
53%
48%
43%
36%
29%
26%
21%
15%
9%
6%
3%
48m
67%
65%
62%
59%
56%
52%
47%
42%
36%
28%
26%
21%
15%
9%
6%
3%
49m
67%
64%
62%
59%
55%
51%
47%
41%
35%
28%
25%
20%
15%
9%
6%
3%
50m
66%
64%
61%
58%
55%
51%
46%
41%
35%
27%
25%
20%
14%
9%
6%
3%
51m
66%
63%
61%
58%
54%
50%
46%
40%
34%
27%
24%
19%
14%
9%
6%
3%
52m
65%
63%
60%
57%
54%
50%
45%
40%
34%
26%
24%
19%
14%
8%
6%
3%
53m
65%
62%
60%
57%
53%
49%
45%
39%
33%
26%
24%
19%
14%
8%
6%
3%
54m
10
91%
5
96%
87%
15
83%
20
78%
25
74%
30
70%
35
66%
40
62%
45
48
45% (1.4m)
45
Relevant boundary
Setback Distance
62% (3.7m)
100%
72% (2.2m)
Plane of reference
1m
2m
100% (6m)
Bldg A
100% (3m)
Angle of opening
with respect
to plane of reference
100% (4m)
62% (2.5m)
Note: *: To take the smaller angle from table when actual angle exceeds that of the table. Interpolation of the angles is not permitted.
50
50%
60
Bldg B
54%
55
46%
65
43%
70
39%
75
36%
80
32%
85
29%
90
CHAPTER 4
SITE PLANNING & EXTERNAL
FIRE FIGHTING PROVISIONS
ROOT OBJECTIVES
The primary intentions of this chapter are encapsulated in
the following statements:R4.1
R4.2
S4.1
S4.2
S4.3
S4.4
S4.5
4(I)
CHAPTER 4
SITE PLANNING & EXTERNAL
FIRE FIGHTING PROVISION
4.1
GENERAL
4.1.1
4.2
4.2.1
General
Introduction
Provision of
accessway
(1)
(2)
Minimum
4000m2 to 8000m2
>8000m2 to 16,000m2
>16,000m2 to 32,000m2
>32,000m2
(c)
Minimum
>28,400m3
>56,800m3
>85,200m3
>113,600m3
Minimum
>56,800m3
>113,600m3
>170,400m3
>227,200m3
Accessway
Location
(d)
Width of
accessway
Gradients of
accessway and
access road
Turning facilities
Overhead
clearance
Public road
Obstruction
Marking of fire
engine accessway.
4.2.3
Definition
Signage
Size
Buildings other
than residential
Access opening
to compartment
or spaces
Position
Additional
openings
4.4
4.4.1
REQUIREMENTS
(a) (i) Every part of a fire engine access road and/or
an accessway in a private lot shall be within an
unobstructed distance of 50m from a hydrant. Where
a public hydrant conforming to such requirement is
not available, private hydrant(s) shall be provided (see
diagram 4.4.1(a)).
(ii) Existing public hydrants along one side of a public road
shall not be designated to serve developments that are
sited across the other side of the public road, except
for a one-way or two-way lanes road.
(b) In situations where more than one private hydrants are
required, the hydrants shall be located along the fire engine
access road and/or an accessway such that every part of
the access road and/or accessway is within an unobstructed
distance of 50m from any hydrant (see diagram 4.4.1(b)).
Access to
buildings with
rising mains
Private fire
hydrant
(c)
(d)
4.4.2
WATER SUPPLY FOR PRIVATE HYDRANT
Provision of water supply for private hydrant system where required
by this Code shall comply with one of the following requirements:
(a)
(i) The nominal bore of the hydrant pipe and the bulk
water meter shall not be less than 150mm in diameter;
and
(ii) The running pressure/flow at the hydraulically most
unfavourable hydrant of the private hydrant system
shall comply with the following :
(2) Flow Rate >= 0.9 x water flow of the nearest public
hydrant or >= total flow demand (as required
in Table 4.4.2) of the private hydrant system,
provided the running pressure at the remotest
private hydrant is greater than 2 bars.
Note :
Purpose
Purpose Group (*) III,
Group I & II IV, V, VII
2 bars
2 bars
2 bars
<1000m - 38L/s
<5000m - 57L/s
<10000m - 76L/s
(57L/s if sprinkler
protected)
500m - 38L/s
<5000m - 57L/s
<10000m - 76L/s
(57L/s if sprinkler
protected)
Minimum duration
4.4.3
45 mins
(b)
(c)
(d)
Protection of
hydrant mains in
buildings
Diagram 4.2.2(d)(v)
Diagram 4.2.2(d)(vi)
189
Diagram 4.2.2(d)(v)
Diagram 4.2.2(d)(vi)
190
Diagram 4.4.1(a)
Every part of a fire engine access road and/or an accessway in a private lot shall be
within an unobstructed distance of 50m from a hydrant. Where a public hydrant
conforming to such requirement is not available, private hydrant(s) shall be
provided.
191
Diagram 4.4.1(b)
In situation where more than one private hydrants are required, the hydrants shall be
located along the fire engine access road and/or an accessway such that every part of
the access road and/or accessway is within an unobstructed distance of 50m from
any hydrant.
192
CHAPTER 5
ELECTRICAL POWER SUPPLIES
ROOT OBJECTIVES
The primary intentions of this chapter are encapsulated in
the following statements:R5.1
5(I)
CHAPTER 5
ELECTRICAL POWER SUPPLIES
5.1
INSTALLATION
5.1.1
5.2
5.2.1
(b)
(c)
(d)
Primary and
secondary
supplies
(e)
(f)
(g)
(h)
(i)
Secondary
source of
supply
Cable installation
(j)
5.2.3
(b)
Emergency
generator
CHAPTER 6
FIRE FIGHTING SYSTEMS
ROOT OBJECTIVES
The primary intentions of this chapter are encapsulated in
the following statements:R6.1
R6.2
R6.3
R6.4
S6.1
S6.2
(ii)
(ii)
S6.3
S6.4
(iii)
(iv)
(v)
(vi)
(ii)
(iii)
(iv)
(v)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
6(III)
CHAPTER 6
FIRE FIGHTING SYSTEMS
6.1
PORTABLE EXTINGUISHERS
6.1.1
General
(a)
(b)
(c)
6.1.2
General
6.1.3
Installation,
marking
6.2
6.2.1
(a)
Type of rising
main
(b)
(c)
6.2.2
Where the building has access from more than one ground
level or road level, the height measurements for the purpose
of this code shall be taken from the level of accessway or fire
engine access road (applicable to buildings under Purpose
Group II) provided.
(b)
(c)
(d)
Note:
Number, location
and size of rising
mains
(e)
6.2.3
(b)
6.2.4
Capacity of the water supply from the public mains and the
storage capacity for a wet rising main system shall comply
with the requirements in SS 575 Code of Practice for Fire
Hydrant systems and Hose Reels.
Wet rising
main
(b)
Flow
(c)
Running
pressure
(d)
Static pressure
(e)
(f)
6.2.5
(iii) Each hose shall have a standard length of 30m and shall
be kept stowed in a Dutch Rolled position and housed
in a glass fronted cabinet.The Dutch Roll shall be rolled
in the manner shown in Diagram 6.2.5(a).
(b) Position
(i) The fire hose shall be installed just next to, but not more
than 2m from the landing valve as shown in Diagram
6.2.5(b).
(ii) The entire fire hose and cabinet shall be out of direct
sunlight.
(c) Mounting
(v) The depth of the cabinet shall not exceed 250mm for
one fire hose or 350mm for two fire hoses.
(d) General
(i) Only clean, dry and compact rolled (Dutch Roll with
the Velcro strap secured as shown in the Diagram
6.2.5(a) and (b)) hose shall be placed in the cabinet.
6.2.6
Building under
construction
6.2.7
Foam inlets
Hose Reels
(a)
Hose reels
(4) Not being used as public entertainment outlet;
(5) Not belonging to Purpose Group VI & VIII.
(iii) Any other small standalone single-storey guardhouse,
bin centre, electrical sub-station and open-sided shed
not exceeding 200m (excluding those in Purpose
Group VI & VIII).
(iv) Subject to compliance with Cl.2.6.2, provision of
hose reel on the mezzanine floor of factory unit is not
required provided the coverage distance of the nearest
hose reel at the main floor to the most remote point of
the mezzanine floor shall not exceed 36m.
(b) The hose shall be of 20mm or 25mm nominal diameter
and conform to EN 694, not exceeding 30m in length and
terminating in shut-off branches with 4mm or 6mm nozzles.
(c)
Water supply for hose reels in terms of flow rate and minimum
running pressure shall comply with the requirements in SS
575.
(d)
(e)
6.2.9
Water supply
Siting &
installation
6.3
6.3.1
General
(a)
(b)
Group II mixed
occupancy
Group II with
lower car park
floors
(c)
(d)
6.3.2
Fire alarm
panel
6.3.3
(c)
(d)
(e)
(b)
Manual alarm
call points
(c)
(d)
(e)
6.3.4
6.3.5
Alarm Device
(a)
(b)
Automatic fire
alarm
Alarm
device
Visual alarm
signal
6.3.6
6.3.7
A theatre or cinema shall be provided with an electrical fire alarm
system of the manual type complying with the following:
(a)
(b)
(c)
(b)
(c)
(d)
Alarm system
for cinema
Connection to
fire station
6.3.8
6.4
SPRINKLER INSTALLATION
6.4.1
Sprinkler
protected
building
General
(a)
(b)
(c)
(d)
Basement
(ii) Where the basement storey is effectively crossventilated such as to avoid smoke logging conditions,
the basement storey may be exempted from the
requirements of provision of an automatic sprinkler
system, at the discretion of the Relevant Authority.
Exemption
Sprinkler system
& smoke purging
system
(c)
(d)
(e)
External corridor
Installation
(a)
Connection to
fire station
(b)
6.4.2
6.4.3
Atrium ceilings
External linkway
6.4.4
(b)
(c)
Special
purpose rooms
6.4.5
Water mist
system
(b)
(c)
6.4.6
6.4.7
6.5
6.5.1
6.5.2
6.6
LIFTS
A set of requirements using lifts for building evacuation during
emergency is drawn up at Fire Safety Requirements FSR 7: 2011
& FSR 8: 2011. These requirements are applicable to all buildings
except residential developments.
Installation
6.6.1
6.6.2
6.6.3
(c)
The power supply to the lift shall be connected to a sub main
circuit exclusive to the lift and independent of any other
main or sub main circuit. The power cables serving the lift
installation shall be routed through an area of negligible fire
risk.
Fire Lift
(a) With the exception of Purpose Group I and II buildings,
all other buildings shall be provided with at least two fire
lifts if the habitable height exceeds 24m. See Fire Safety
Requirements FSR 8:2011 on the design details.
Hoistway
ventilation
Emergency
power supply
Fire lift
All buildings shall also be provided with at least two fire lift
if the depth of the basement exceeds 9m below the average
ground level.
(b)
(c)
(d)
(e)
(f)
The fire lift shall be located such that any part of every
storey shall be accessible to fire-fighters from the fire lift.
(g) Regardless of whether the building is installed with
automatic sprinkler system, the number of fire lifts required
shall be such that any part of a storey of the building is within
60m coverage from the fire lift door; subject to provisions of
at least 2 fire lifts in accordance with sub-clause (a).
6.6.4
Homing of lifts
(a) Homing of lifts for buildings which are required to be
provided with fire alarm system.
In a fire emergency when any one of the fire detection
devices or fire alarm systems is activated, all the passenger
lifts shall be brought to the designated floor (usually) 1st
storey) and park there with the lift landing doors remaining
opened.
(b) Homing of lifts for buildings which are required to have
standby generating plant.
In the event of power failure or power interruption in the
building,the supply to the lifts shall be automatically switched
over to the emergency power supply from the generating
plant and the lifts shall be brought to the designated floor
and park there with the lift landing doors remaining open
until all the lifts have been brought down to the designated
floor. Thereafter, one or more lifts may resume operation
depending on the capacity of the emergency generating
plant, in addition to the fire lift. Normal operation of the lift
shall be automatically reset on the return of normal power
supply.
(c)
Homing of lifts for buildings which are not required to have
standby generating plant.
Homing of lifts
(e)
Diagram 6.2.5(a)
Diagram 6.2.5(b)
TABLE 6.3A
PROVISION OF FIRE ALARMS ACCORDING TO
PURPOSE GROUP, HEIGHT & SIZE OF THE BUILDING
A
Purpose group & No
of storeys of building
III (Institutional)
(i)
Schools & others
a
- Single storey building
b
- Building of 2 to 4 storeys
c
- Building of more than 4 storeys
(ii)
Health care occupancy with stay-in facilities
a
- Single storey building
b
- Building of 2 to 4 storeys
c
- Building of more than 4 storeys
(iii)
Health care occupancy without stay-in facilities
a
- Single storey building
b
- Building of 2 to 4 storeys
c
- Building of more than 4 storeys
(iv)
Dormitories
a
- Single storey building
b
- Building of 2 to 4 storeys
c
- Building of more than 4 storeys
B
Total floor area
(per storey in sq m) in excess of which
alarm must be provided
C
Type of
Alarm
NL
400.
400**
(m)+
(a)
NR
NR
NR
(m)
(a)
(a)
NL
200.
NR
(m)
(a)
NR
NR
NR
(m)
(m)
(a)
IV (Office)
a
b
c
400*
200.
NR
(m)
(m)
(a)
400*
200.
NR
(m)
(m)
(a)
VI (Factory)
a
b
c
-
400*
200.
NR
(m)
(m)
(a)
V (Shop)
a
b
c
NR
NR
NR
(m)
(a)
(a)
400*
200.
NR
(m)
(m)
(a)
VIII (Storage)
a
b
c
-
2000*
1000.
NR
(m)
(m)
(a)
*
**
+
.
Single storey building with area less than indicated is not required to be provided with alarm system unless otherwise specified by the
Relevant Authority.
Building of more than 4 storeys but area less than 400sqm, only manual alarm system is required.
Where used for sleeping accommodation, automatic alarm system may be required by the Relevant Authority.
The total floor area per storey shall not exceed that as stated in Cl.6.3.1(c).
NL
=
no limit
(m)
=
manual type
NR
=
not relevant
(a)
=
automatic + manual type
Remarks:
(1)
When there are 2 or more purpose groups in a building, the strictest requirement for any one of the purpose groups shall
be applicable to the whole building.
(2)
Where purpose group II forms part of a mixed use building, Cl.6.3.1(b)(i) shall be followed.
215
Table 6.4A:
Store room 1
AHU room
Kitchen 2
Boiler room (oil fired)
Low voltage Switch room
High voltage Switch room
Transformer room (oil type)
Oil Tank room
Generator room
A/C Plant room
Electric Lift motor room
Hydraulic Lift motor room
Essential Fan room
Electrical room
Battery room
Sprinkler/Wet Riser Tank room
Fire Pump room
Fire Command centre
MDF room
PABX room
Compartmentation and door rating in this table are specified in one of the following ways:
N
B
=
=
The fire resistance rating stipulated in this table shall be the minimum.
Requirement for sprinkler in the special purpose rooms is specified in one of the following ways:
S
Ex
=
=
Requirements stated herein apply to kitchens in hotel, restaurant, coffee house or other similar places where the
preparation of food is required. However, special considerations will be given to the followings:
(a)
(b)
Where AHU rooms are vertically stacked, each AHU room shall be separated by a compartment floor at every
level. In the case of AHU serving more than one compartment, fire dampers shall be provided in air ducts at
penetration through the compartment wall and floors, see Cl.7.1.2.
216
CHAPTER 7
MECHANICAL VENTILATION
AND SMOKE CONTROL SYSTEM
ROOT OBJECTIVES
The primary intentions of this chapter are encapsulated in
the following statements:R7.1
R7.2
S7.1
(ii)
at visibility levels
evacuation; and
(iii)
adequate
for
occupant
S7.3
7(I)
S7.4
S7.5
of
the
mechanical
(i)
(ii)
(ii)
7(II)
in
which
emergency
CHAPTER 7
MECHANICAL VENTILATION AND
SMOKE CONTROL SYSTEMS
7.1
7.1.1
General
(a)
(b)
Construction of
ductwork
(c)
Pipework
insulation
Duct enclosure
(e)
Ductwork
through smokestop or firefighting lobbies
(f)
Plenum
(iii) Exception
Fire Dampers
Any fire damper shall have a fire resisting rating of not less
than that required for the compartment wall or compartment
floor through which the relevant section of the ventilation
duct passes. Fire dampers shall be of the type approved by
the relevant authority and constructed in accordance with
the requirements in SS 333 - Specifications of fire dampers.
Separating walls
Provision of fire
dampers
Installation of
fire dampers
Connections to
fire dampers
(8) Each fire damper installation shall be provided
with an inspection access door either upstream
or downstream as appropriate. The access door
dimension shall preferably measure 450mm
(length) 450mm (width); for smaller ducts, the
door width dimension may be reduced to the
width or depth of the duct. Access doors shall be
hinged and fitted with sash locks, and constructed
of minimum 1.25mm sheet steel suitably braced.
Openings in ducts shall be stiffened by sheet steel
frame.
(iii) Fire dampers shall not be fitted in the following
locations:
(3) anywhere in an air pressurising system;
(4) where explicitly prohibited in this Code.
Access door in
ventilation duct
for inspection of
fire damper
Prohibition of
fire dampers
(i)
(j)
Fire resisting
floor-ceiling
and roof
ceiling
(k)
7.1.2
Locations of
intakes and
return air
openings
(b)
(c)
Air handling
unit rooms
Smoke detectors
(d)
7.1.3
Stop Switch
Exits
Exits
(a)
(i) Supply air for the system shall be drawn directly from
the external, with intake point not less than 5m from
any exhaust discharge openings.
(iii) Where the supply air duct serving the exit staircase
has to penetrate the staircase enclosure, the portion
of the duct where it traverses outside the staircase
shall be enclosed in masonry construction or drywall
complying with Cl.3.8.7(c) of at least the same fire
resistance as the elements of structure and it shall not
be fitted with fire dampers.
Exit staircase
and internal exit
passageway
7.1.4
Mechanical ventilation system for smoke stop lobbies and firefighting lobbies shall be a system exclusive to these lobbies, and it
shall comply with the following requirements:
(a)
(b)
(c)
(d)
7.1.5
Mechanically
ventilated smoke
stop lobby and
fire-fighting
lobby
Engine driven
fire pump and
generator
(b)
(c)
(d)
7.1.6
The Fire Command Centre can either be AC, NV, or MV. The AC
or MV shall be independent of each other and any other system
serving other parts of the building. Where mechanical ventilation
is required, it shall also comply with the following requirements:
(a) Supply air shall be drawn directly from the external and
its intake point shall not be less than 5m from any exhaust
discharge openings. Exhaust discharge shall also be direct
to the external and shall not be less than 5m from any air
intake openings.
(b) Where the corresponding ducts run outside the fire
command centre, they shall either be enclosed in a structure
or be constructed to give at least the same fire rating as the
room which they serve or that of the room through which
they traverse, whichever is higher. Where the duct risers
are required to be enclosed in a protected shaft constructed
of masonry or drywall complying with Cl.3.8.9(a), they
shall be compartmented from the rest of the shaft space
containing other ducts or services installations.
(c)
(d)
Duct serving areas other than the fire command centre shall
not pass through the room.
Fire Command
Centre
7.1.7
Kitchen
Kitchen
(a)
(iii) For other smaller F&B outlets such as snack bars, food
kiosks etc.
Rooms involving
use of flammable
& explosive
substances
7.1.9
7.2
PRESSURISATION FOR EXIT STAIRCASES
7.2.1
General
(a)
Basement car
park
General
7.2.2
(b)
Basement
(c)
Purpose
Group II
occupancy
Pressurisation Level
(a)
(b)
(c)
7.2.3
7.2.4
Leakages
(a)
(b)
Pressurisation
level
Egress velocity
Leakages
7.2.5
7.2.6
(b)
Distribution of
pressurising air
Equipment
(a)
(b)
(c)
7.3
7.3.1
7.4
7.4.1
(a)
Equipment
Pressurisation
of internal
corridors
in hotels
Scope
(b)
Exception
7.4.2
The number and their sizes shall be such that the aggregate
effective vent openings shall not be less than 2.5% of the
basement floor area served.
(b)
(c)
The position of all vent outlets and the areas they serve shall
be suitably indicated adjacent to such outlets.
Smoke vents
(d)
(e)
7.4.3
Engineered
smoke control
7.4.4
Smoke purge
system for
non-car park
occupancy
(a)
(b)
(c)
(d)
(e)
7.5
7.5.1
Smoke control
system
7.6
7.6.1
(b)
(c)
(d)
Acceptable
design guidance
(Note: BR 186 and 258 are reports published by the Fire Research
Station, Building Research Establishment, Borehamwood, Herts
WD62BL).
7.6.2
Sprinkler system
7.6.3
Fire size
Occupancy (Sprinklered)
Shops
Offices
Hotel Guest Room
Hotel Public Areas
Assembly Occupancy with
fixed seating
7.6.4
Fire Size
Heat Output
Perimeter of
(MW)
Fire (m)
5
12
1
14
0.5
6
2.5
12
2.5
12
Capacity of
an engineered
smoke control
system
7.6.5
The design smoke layer base shall be above the heads of people
escaping beneath it.The minimum height shall be 2.5m.
Clear layer
7.6.6
Smoke reservoir
7.6.7
For cases where smoke is removed from the room of origin the
smoke reservoir size for a smoke ventilation system shall not
exceed:
Smoke reservoir
size
(a)
(b)
7.6.8
7.6.9
7.6.10
7.6.11
(b)
(b)
Removal
of smoke from
circulation or
atrium spaces
Discharge of
smoke into
circulation/
atrium spaces
The maximum length of the smoke reservoir shall not exceed 60m.
Length of
smoke reservoir
Stagnant
regions
7.6.12
7.6.13
(b)
Replacement air
velocity
(b)
Distance from
exhaust air
discharge
(c)
Replacement
discharge
position
(d)
Siting
of inlets
(e)
Replacement air
for engineered
smoke control
system
7.6.15
Emergency
power supply
7.6.16
Mode of
activation
(f)
7.6.14
Perforated ceiling
7.6.17
7.6.18
Manual
activation
7.6.19
Shut down
of other air
conditioning
& ventilation
systems
7.6.20
Standby fans or
multiple fans
7.6.21
7.6.22
Protected
circuits
7.6.23
Electrical supply
7.6.24
7.6.25
7.6.26
The time taken for the smoke ventilation system within a smoke
zone to be fully operational shall not exceed 60 seconds from
system activation.
7.6.27
Fail-safe system
7.6.28
7.6.29
Smoke curtain
7.6.30
Obstruction to
means of escape
7.6.31
Smoke or
chanelling
screens
7.6.32
7.7
7.7.1
7.7.2
CHAPTER 8
OTHER SYSTEMS
ROOT OBJECTIVES
The primary intentions of this chapter are encapsulated in
the following statements:R8.1
lighting; and
(ii)
R8.2
R8.3
R8.4
S8.1
S8.2
(ii)
(i)
(ii)
S8.4
(ii)
(iii)
(iv)
(v)
(vi)
(ii)
(iii)
(iv)
(v)
basement conditions.
8(II)
CHAPTER 8
OTHER SYSTEMS
8.1
8.1.1
8.1.2
8.1.3
Exit lighting
Emergency
lighting for
corridors &
lobbies
Emergency
lighting for
occupied areas
8.1.4
8.1.5
(b)
Fire-fighting
facilities
Secondary
source of power
supply
(c)
8.1.6
8.1.7
Luminaire
Directional
signs
Self-illuminating
signs
8.2
8.2.1
(a)
System
requirements
Construction
(v) fire lift;
Where the lift car is equipped with built-in intercom
system that complies with clause 9 of SS 546, the twoway communication system can be exempted.
(vi) each area of refuge; and
(vii) air-handling control rooms.
Where AHU can be remotely monitored and controlled
at the Fire Command Centre, and cannot be by-passed
locally, and the electrical cabling between AHU rooms
and FCC are fire rated, the two-way communication
system can be exempted.
(c)
8.2.2
Where a one-way or two-way emergency communication system
is required by this code, it shall comply with the requirements
stipulated in SS 546: Code of Practice for Emergency Voice
Communication Systems in Buildings.
8.2.3
Fire Command
Centre
(b)
Size
Location
(c)
Construction
8.2.4
Two-way
communication
system
Exception :
(i)
Single-level basement, irrespective of its usage of building
under Purpose Groups II to VIII and basements of building
of Purpose Group I are not required to be provided with
two-way emergency communication.
(ii) Multi-level basements of building under Purpose Group II
are not required to be provided with two-way emergency
communication system, provided the basements are used
solely for car parking and not exceeding two basement
storeys in depth.
CHAPTER 9
FIRE SAFETY REPORT
ROOT OBJECTIVES
There are no root objectives for this chapter.
SUB-OBJECTIVES
There are no sub-objectives for this chapter.
9(I)
CHAPTER 9
FIRE SAFETY REPORT
9.1
9.2
9.2.1
PURPOSE
Fire safety report is to document the provision of fire protection
and life safety features in the building and/or plants/installations.
This report would serve as a useful reference to fire safety managers,
building owners, registered inspectors, the Relevant Authority
and to qualified persons appointed to carry out any subsequent
additions and alteration works. Where the nature of the additions
and alteration works would require the updating of the fire safety
report, the qualified person shall be responsible to submit revised
and updated report to the building owner/s and the Relevant
Authority.
SUBMISSION OF REPORT ON FIRE PROTECTION & LIFE
SAFETY FEATURES
Qualified Person should submit a report on fire protection and life
safety features when making Building Plan submission for projects
such as:(a) high-rise (over 60m in building height) commercial
buildings;
(b)
(c)
(d)
(e)
(f)
9.2.2
In buildings under Purpose Groups VI & VIII, where there may be
presence of corrosive atmosphere that may affect the effectiveness
of intumescent paints for protection to structural steel members of
buildings and fire rated dry board, such proposal shall be subjected
to evaluation of the Relevant Authority.
9.3
9.3.1
A
Project Description
B
Fire Safety Design Concept
C
Fire Engine Accessibility
D
Means of Escape
E
Structural Fire Precautions
F
Control and Exhaust of Smoke and Toxic Fumes
G
Fire-Fighting Systems
H
Fire Alarm System
I
Emergency Power Supply
J
Emergency Evacuation Lighting
K
Emergency Voice Communication System
L
Two-Way Emergency Communication System
M
Emergency Lift Control
N
Areas of Fire Risk
O
Fire Scenario
P
Fire Safety Management
Q Conclusion
9.4
The write-up of the report on fire protection and life safety features
should include the following subjects. However, qualified person
could expand or modify the report to suit his presentation:-
Project Description
Means of Escape
Fire-Fighting System
This would include the active protection system such as
portable fire extinguishers, hose reels, dry/wet rising mains,
sprinkler system, gas flooding system, fixed/portable water
monitors, fixed water spray, drenchers etc.
Fire Scenario
Under this subject, the qualified person would have to
assume the outbreak of a fire in one of the critical floors
or areas and describe the sequence of operation of the fire
protection and life safety design features.
Fire Safety Management
This would include a brief description of the general
management of the fire protection and life safety features.
Q Conclusion
This would include the summing up of the outline concepts
and systems that have been designed for the project.