BLUESTAR LIMITED

Digital Scroll System

3.3. Dip Switch Setup


Dip-Switch setting is effective after power on again, or to press S4 reset key.
3.3.1 Outdoor Setup
On the Outdoor board, the capacity of the compressor, the number of phases for the power supply, and the number of
Indoor board used is defined by the Dip Switch SW1. In the following tables, 1 corresponds to switch in the ON
position. 0 corresponds to switch in the opposite position.
Select JP4 & JP8 for mode & capacity configure:
JP4

Mode configure

Open

Cooling

Closed

Heat Pump

JP8

Capacity configure

Open

6HP, 12HP

Closed

18HP, 24HP

Switch S1/S2 are used to determine Solo/ Tandem/ Multi Tandem


S1

S2

System configure

Total Rate Capacity(HP)

Indoor online(Max)

0 (open)

Solo

1 (Close)

Tandem

12

16

Multi Tandem

24

32

Multi Tandem

32

32

Switch S3 is used to determine power supply.


-- The system ignore phase order and current error alarm if S3 is selected off,
S3

Power Supply

0 (OFF)

Single Phase

1 (ON)

3 Phase

Switch S4-S5 uses to determine outdoor EXV initial opening


S4

S5

Default
Initial
Opening X

Temperature
Coefficient T

Compressor PWM
Coefficient P

450

80

400

70

350

60

300

50

Switch S1-S2, S6-S8 uses to determine system rated capacity.


S1 S2

S6

S7

S8

System
Rated
Capacity (KW)

Digital Compressor

Fixed Compressor
N0.1 or 1-3

Multi Tandem System


0

100.0kw

25.0kw

25.0kw

90.0kw

22.5kw

22.5kw

80.0kw

20.0kw

20.0kw

62.5kw

17.5kw

15.0kw

60.0kw

15.0kw

15.0kw

52.5kw

15.0kw

12.5kw

50.0kw

12.5kw

12.5kw

42.5kw

12.5kw

10.0kw

BLUESTAR LIMITED

Digital Scroll System

Tandem System
1

50.0kw

25.0kw

25.0kw

45.0kw

22.5kw

22.5kw

40.0kw

20.0kw

20.0kw

32.5kw

17.5kw

15.0kw

30.0kw

15.0kw

15.0kw

27.5kw

15.0kw

12.5kw

25.0kw

12.5kw

12.5kw

22.5kw

12.5kw

10.0kw

Solo System
0

25.0kw

25.0kw

22.5kw

22.5kw

20.0kw

20.0kw

17.5kw

17.5kw

15.0kw

15.0kw

15.0kw

15.0kw

12.5kw

12.5kw

12.5kw

12.5kw

3.3.2 Indoor Unit(s) Setup


In the following tables, 1 corresponds to switch in the ON position. 0 corresponds to switch in the opposite position.
Switch SW-8: S1-S3 use to configure the indoor unit size.
S9

S3

S2

S1

(KW)

2.5

3.5

7.5

10

12.5

15

17.5

20

22.5

25

30

35

40

Switch SW-8: S5-S8 is used to set number of indoor unit


S4

S5

S6

S7

S8

Indoor ID =0-31#

BLUESTAR LIMITED

Digital Scroll System

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

11. System Message


Indoor Unit: Cassette/Ductable/CS Units
** Normal, The APW04 shows setting temperature, local indoor No.(when its on), 2 Compressors on/ off state
and current mode, Fan speed, sleep, timer etc.
** Abnormality, if the any indoor thermistor is fail(shortness or open), the E1E4 shows on LCD panel.
** The outdoor alarm and other message blink on indoor LED board of Cassette/Ductable/CS Units. See the table
as follows,
Message description

LED1

OutDoor Inlet Open/short

OutDoor Mid Open/short


OutDoor Outlet Open/short

LED2

LED4

APW04 Shows as
F1

F2

F3

OutDoor Amb Open/short


OutDoor DLT Open/short

LED3

F4

F5

F6

F7

Or Red-Area
OutDoor Hi / Lo Pressure
OutDoor Phase Error

OutDoor Current Error


Indoor Freeze Protect
Indoor Room Open/ short

V
V

F8

E5

E1

BLUESTAR LIMITED
Indoor Inlet Open/ short

Digital Scroll System


V

E2

E3

E4

E6

EF/ FF

Indoor Mid Open/ short


Indoor Outlet Open/ short

Communication Fail
Power on/ Fresh Start Prog

Indoor Unit: Wallmounts


** Normal, The APW04 shows setting temperature, local indoor No.(when its on), 2 Compressors on/ off state
and current mode, Fan speed, sleep, timer etc.
** Abnormality, if the any indoor thermistor is fail (shortness or open), the E1E4 shows on LCD panel.
** The outdoor alarm and other message blink on indoor LED board of Wall mount Units. See the table
as follows,
Message description

LED1(Powerful

LED2(Quite)

LED3(Power)

LED4(Timer)

APW04 Shows as

)
OutDoor

Inlet

F1

Open/short
OutDoor

Mid

F2

F3

F4

F5

F6

F7

Open/short
OutDoor

Outlet

Open/short
OutDoor

Amb

Open/short
OutDoor

DLT

Open/short
Or Red-Area
OutDoor Hi / Lo
Pressure
OutDoor Phase Error
OutDoor

Current

F8

E5

Error
Indoor Freeze Protect

Indoor Room Open/

E1

E2

E3

E4

E6

EF/ FF

short
Indoor Inlet Open/

short
Indoor

Mid

Open/

short
Indoor Outlet Open/

short
Communication Fail
Power on/ Fresh Start

Prog