Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Bedding
Conductor screen
Index Terms-- cable metallic screen rating, double line-toground fault, medium voltage (MV) power cable, MV urban
network, short-circuit current, unsymmetrical faults
Insulation screen
(semi-conductor)
Insulation
Conductor
Metallic screen
Cable armour
I. INTRODUCTION
1,1U n
2Z 1s + Z
(1)
where:
Un - network nominal voltage, in kV,
Z1s - positive sequence impedance (equal to the negative
sequence impedance) of the power source, in ,
Z - additional impedance, equal to the sum of
impedances of all power cables situated on the
double line-to-ground fault current flow path, in .
After the substitution to (1) the value of additional impedance
Z = 0, the maximum possible value of double line-toground short-circuit current is obtained. In this case, the shortcircuit current value is equal to a phase-to-phase short-circuit
current value during the fault on MV busbar. It can be
calculated by using the formula as follows
I z 2 = I "k 2 =
Fig. 2. The three possible points (A, B and C) of double line-to-ground faults
in the medium voltage distribution cable network
1,1U n
3 "
=
I k 3 = 0 ,866 I "k 3
2Z 1s
2
(2)
I z2
I2
I4
I1
x1
I z2
I3
x2 x1
I5
L
Z = a 0 (x1 + x2 ) + a1
x12
xx
+ (2 Z 1 2a 0 a1 ) 1 2
L
L
Z1 = Z r Z m
x
x
I 2 = I z2 I1
I 1 = I z 2 b1 1 + (b 0 b1 ) 2
L
L
Rp
Rp
b0 =
b1 =
Z p Zm
2 Z 2m
Zp
Z p + Zm
(Z rp Z m )2
Z p Zm
x
x
I 3 = I z 2 b1 2 + (b 0 b1 ) 1
L
L
a 0 = Z r Z rp + R p
R 2p
a1 =
Zp
I 4 = I z2 I 3
2 Z 2m
Z p + Zm
I 5 = I z 2 (b 0 b1 )
x1 x2
L
Fig. 3. The equivalent circuit scheme and formulas for calculating the single-core cables additional impedance and the short-circuit current flow in the metallic
screens during double line-to-ground faults
I z2
I z2
I1
I2
I1
x2 x1
x1
L
I z2
I z2
I1
I2
I1
x2 x1
x1
L
Z = a 0 x1 + a1
I 1 = I z 2 b1
(x1 x2 )2 + (2Z a )x
1
0
2
x1 x 2
L
Z1 = Z r Z m
I 2 = I z2 I1
b1 =
a 0 = Z r Z rp + R p
a1 =
R p2
Zp
Rp
Zp
Fig. 4. The equivalent circuit scheme and formulas for calculating the additional impedance of the traditional three-core cables or the three-core cables with the
common copper centre conductor and the short-circuit current flow in the metallic screens or the common centre conductor during double line-to-ground faults
(3)
where:
Ith
- thermal equivalent short-circuit current, in kA,
Tk
- duration of double line-to-ground short-circuit
current, in s,
Imax - the biggest current flowing in individual sections of
metallic screens, in kA
m, n - factors for the calculation of the thermal equivalent
short-circuit current, dimensionless values,
Ithr - rated short time (one-second) thermal current, in k.
0.6
frequency
0.4
I k'' 2 = 10 ,49 kA
0.2
0
0
0.2
0.4
0.6
0.8
I z 2 I k'' 2
Fig. 5. The frequency histogram of double line-to-ground fault current in 6 kV
cable conductor for the actual (126 MVA) value of the short-circuit power
0.4
0.3
frequency
I k'' 2 = 5,34 kA
0.2
0.1
0
0
0.2
0.4
I z2 I
0.6
0.8
''
k2
0.4
individual power cable sections and the smaller the crosssection of the metallic screens are, the bigger decrease in fault
current is. The influence of these factors is growing when the
bulk power transformer rated power is increasing. As a result
double line-to-ground fault currents in 6 kV networks are
much smaller than in 20 kV networks.
For the actual value of the short-circuit power, the average
value of fault currents flowing in cable metallic screens in
analyzed real 20 kV networks ranges from 3.0 to 3.7 kA. For
the maximum possible value of the 20 kV short-circuit power,
the average value of these fault currents increases and ranges
from 4.0 to 4.9 kA (which gives about 45 60 % of the
phase-to-phase short-circuit current value during the fault on
20 kV busbar). In analyzed 6 kV networks, for the actual
value of the short-circuit power, the average value of fault
currents flowing in cable metallic screens ranges from 1.8 to
2.4 kA. For the maximum possible value of the 6 kV shortcircuit power the average value of these fault currents ranges
from 2.0 to 2.7 kA (which gives about 12 15 % of the
phase-to-phase short-circuit current value during the fault on
MV busbar).
I k'' 2 = 10,49 kA
0.6
0.2
0
0
0.2
0.4
I max I
0.6
0.8
frequency
frequency
0.6
''
k2
0.4
I k'' 2 = 16 ,65 kA
0.2
0.4
0.2
0.4
0.6
I max I
frequency
0.3
I k'' 2 = 5,34 kA
0.2
0.8
''
k2
0.4
0.1
0.2
0.4
0.6
0.8
I max I k'' 2
frequency
0.3
0
I k'' 2 = 8,24 kA
0.2
0.1
0
0
0.2
0.4
0.6
I max I
0.8
''
k2
Fig. 10. The frequency histogram of the biggest value of current flowing in
20 kV cable metallic screens for the increased (330 MVA) value of the shortcircuit power
V. CONCLUSIONS
TABLE I
THE REPETITION CYCLE (IN YEARS) OF THE EXCEEDING OF THE RATED
SHORT TIME THERMAL CURRENT FOR POWER CABLE METALLIC SCREENS
Power cables installed in analyzed network:
ShortType / Conductor cross-section [mm2] /
circuit
power
Metallic screen cross-section [mm2]
MVA
Real *)
5C/120/16 5C/240/25 5F/120/35
155
171
32
48
82
Un = 6 kV
175
141
30
41
73
lenght = 42,5 km
200
111
29
36
66
222
577
16
125
90
Un = 20 kV
260
215
9
59
46
lenght = 25 km
330
74
6
21
22
*)
different types of power cables with the different conductor cross-section;
mostly the metallic screen cross-section is equal to 50 mm2
Analyzed
network
VI. REFERENCES
[1]
[2]
[3]
[4]
[5]
[6]
VII. BIOGRAPHIES
Roman Korab was born in Zawiercie, Poland, on
October 6, 1973. He obtained his M.Sc. and Ph.D.
degree from the Silesian University of Technology
in 1998 and 2003, respectively.
He is presently working at Faculty of Electrical
Engineering,
Institute
of
Power
Systems
Engineering and Control. His research interests
mainly include power system operation and
development economics, optimization and control.