Sei sulla pagina 1di 44

Wiring for

Damper Actuators and Control Valves


July 2011

Wiring for Damper Actuators and Control Valves


General Wiring Instructions

Always read the controller manufacturers installation


literature carefully before making any connections. Follow all

CAUTION: It is good practice to power electronic or digital controllers


from a separate power transformer than that used for actuators or other
end devices. The power supply design in our actuators and other end
devices use half wave rectification. Some controllers use full wave
rectification. When these two different types of power supplies are
connected to the same power transformer and the DC commons are
connected together, a short circuit is created across one of the diodes in
the full wave power supply, damaging the controller. Only use a single
power transformer to power the controller and actuator if you know the
controller power supply uses half wave rectification.

instructions in this literature. If you have any questions, contact


the controller manufacturer and/or Belimo.

Multiple actuators, one transformer

Transformer(s)
Belimo actuators require a 24 VAC Class 2 transformer. The
actuator enclosure cannot be opened in the field, there are no
parts or components to be replaced or repaired.
EMC Directive: 2004/108/EC
Software Class A: Mode of Operation Type 1
Low Voltage Directive: 2006/95/EC
Example: 3 AF Actuators Supplied, 16 Ga. wire (refer to table on
page 3)
350 ft. (allowable wire length) 3 actuators = 117 ft. maximum wire run

Typical Transformer Sizing


Actuator Series
EFB, EFX
AFB, AFX
AF
NFB, NFX
LF
TF
GMB
AMB / ARB
NMB
LMB / LRB
CMB
AHB
LHB
LUB
AMQB
NMQB
LMQB
AHQB
LHQB
GK / GKR
NK
AHK

Voltage
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

800-543-9038 USA

Required VA
Per Actuator
16
10
10
9
7
5
7
6
6
3
1.5
4.5
3
3
26
23
23
23
23
21
22
20

Multiple actuators may be powered from one transformer provided the


following rules are followed:
1. The TOTAL current draw of the actuators (VA rating) is less than or
equal to the rating of the transformer.
2. Polarity on the secondary of the transformer is strictly followed.
This means that all No. 1 wires from all actuators are connected
to the common leg on the transformer and all No. 2 wires from all
actuators are connected to the hotleg. Mixing wire No. 1 & 2 on one
leg of the transformer will result in erratic operation or failure of the
actuator and/or controls.

Multiple actuators, multiple transformers


Multiple actuators positioned by the same control signal may be powered
from multiple transformers provided the following rules are followed:
1. The transformers are properly sized.
2. All No. 1 wires from all actuators are tied together and tied to the
negative leg of the control signal. See wiring diagram.

Wire type and wire installation tips


For most installations, 18 or 16 Ga. cable works well with Belimo
actuators. Review job requirements and determine whether a plenum
or appliance rated cable is appropriate. Use code-approved wire nuts,
terminal strips or solderless connectors where wires are joined. It is
good practice to run control wires unspliced from the actuator to the
controller. If splices are unavoidable, make sure the splice can be
reached for possible maintenance. Tape and/or wire-tie the splice to
reduce the possibility of the splice being inadvertently pulled apart.

Wire length for actuator installation


Keep power wire runs below the lengths listed in the following tables.
If more than one actuator is powered from the same wire run, divide
the allowable wire length by the number of actuators to determine the
maximum run to any single actuator.

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

WARNING: The wiring technician must be trained and experienced


with electronic circuits. Disconnect power supply before attempting any
wiring connections or changes. Make all connections in accordance
with wiring diagrams and follow all applicable local and national codes.
Provide disconnect and overload protection as required. Use copper,
twisted pair, conductors only. If using electrical conduit, the attachment
to the actuator must be made with flexible conduit.

24 VAC

110 VAC

800-543-9038 USA

866-805-7089 CANADA

GM

1125

800

475

300
895

545

900

550

800
1125

900
1150

1125

800

500

310

575

200

500

12

350

14

345

125

375

16

325

325

220

80

200

7.5

AM

1150

925

600

375

200

6.5

NM

1150

925

600

375

200

7.5

AM

1125

700

450

300

150

6.5

NM

1125

800

500

325

175

1125

700

450

300

150

1125

800

500

325

175

MAX Distance between Actuator and Supply (feet)

9.5

1150

LFUS TFUS

1125

900

18

215

11

NF..UP

1150

800

175

120

18

AFUS

895

900

20

29

AF..UP

EF

wire
gauge

1050

440

545

500

12

650

575

375

275

500

325

14

575

375

325

345

165

415

110

VA

7.5

MAX Distance between Actuator and Supply (feet)

6.5

16

215

11

GM

1125

18

265

8.5

LFUS TFUS

420

175

21

NF..UP

440

800

20

wire
gauge

AF

1175

260

500

AF..UP

1125

275

160

105

EF

1000

1100

165

900

800

700

550

600

500

12

550

390

360

350

14

VA

NM

LM/LR

1.5

CM

1125

700

450

250

4.5

LM

1125

700

450

250

4.5

LM

700

450

250

1500

1000

600

325

3.5

CM

1150

1000

600

350

3.5

CM

1200

1150

800

MAX Distance between Actuator and Supply (feet)

22

NKQ GM/GR AM/AR

325

110

21

GK/
GKR

225

450

TFUS

145

325

LFUS

16

250

NF

18

220

10

AF

175

16

EF

20

wire
gauge

VA

1175

1125

750

400

LU

1175

1125

750

400

LU

600

375

200

AH

700

450

250

LH

700

450

250

LU

1400

1200

1100

TR

500

300

200

125

70

18

AMQ NMQ
LMQ AHQ
LHQ

*Belimo actuators and auxiliary switches are designed as a IEC protection class II, double insulated, and do not require an independent ground wire to
earth, unless otherwise indicated in this document

220 VAC

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Wire Size vs. Length of Run for Damper Actuators and Control Valves

203-791-8396 LATIN AMERICA / CARIBBEAN

24 VAC

110 VAC

800-543-9038 USA

866-805-7089 CANADA

SY2
Amps

357

606

905

SY1

Amps

12

10

5051

7937

12821

19608

33333

49751

18

16

14

12

10

0.3

29851

20000

11765

7692

4762

3030

0.5

29851

20000

11765

7692

4762

3030

0.5

Amps

SY3

5000

SY2

14925

5000

2941

1923

Amps

10000

10

2941

1923

SY1

5882

12

1190

758

Amps

SY3

543

364

214

140

Amps

3846

14

1190

758

364

214

140

87

55

7463

2381

16

wire gauge

7463

1515

18

0.5

543

233

14

87

55

92

144

16

wire gauge

SY3
Amps

SY4
6

Amps

SY5
6.5

Amps

1.5

Amps

SY5

250

168

99

65

40

1.8

Amps

SY6
3.2

Amps

SY7
4

Amps

SY8
3.2

Amps

SY9

0.7

Amps

SY5

4975

3333

1961

1282

794

505

0.8

Amps

SY6

4146

2778

1634

1068

661

421

1.6

Amps

SY7

2332

1563

919

601

372

237

Amps

SY8

1866

1250

735

481

298

189

1.6

Amps

SY9

2332

1563

919

601

372

237

24876

16667

9804

6410

3968

2525

21322

14286

8403

5495

3401

2165

18657

12500

7353

4808

2976

1894

9328

6250

3676

2404

1488

947

7463

5000

2941

1923

1190

758

9328

6250

3676

2404

1488

947

MAX Distance between Actuator and Supply (feet)

0.6

Amps

SY4

5741

3846

2262

1479

916

583

MAX Distance between Actuator and Supply (feet)

1.3

Amps

SY4

271

182

107

70

43

MAX Distance between Actuator and Supply (feet)

1.8

18

wire gauge

SY2
Amps

SY1

7463

5000

2941

1923

1190

758

Amps

SY10

1866

1250

735

481

298

189

Amps

SY10

9328

6250

3676

2404

1488

947

1.6

Amps

SY11

2488

1667

980

641

397

253

Amps

SY11

6784

4545

2674

1748

1082

689

2.2

Amps

SY12

1866

1250

735

481

298

189

Amps

SY12

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

The NEC mandates that 24 VAC over 100 VA power requires CLASS 1 wiring conduit. Local codes may vary. Do NOT mix CLASS 1 & CLASS 2 circuits in
the same conduit. Generally, 24 VAC actuators over 100 VA should be changed to 120 VAC models.

220 VAC

Amps

Wire Size vs. Length of Run for SY Series Actuators

Wiring for Damper Actuators and Control Valves

W236_11

On/Off, Spring Return, Electronic Fail-Safe, 24V

Actuators: EFB24(-S)
TF24(-S) US

EFX24(-S)
GKB24-3

AF24(-S) US
GKX24-3

NFB24(-S)
NKQB24-1

Hazard Identification

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.
On/Off

LF24(-S) US

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION

NFX24(-S)
NKQX24-1

Provide overload protection and disconnect as required.

Actuators may also be powered by 24 VDC.

Actuators with plenum rated cable do not have


numbers on wires; use color codes instead.

Actuators with appliance cables are numbered.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.

On/Off
1

24 VAC Transformer

24 VAC Transformer

Blk (1) Common

Line
Volts

Red (2) +

Blk (1) Common

Line
Volts
N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

a open
a closed

Red (2) + Hot

Wht (3) +

The indication of direction


is valid for switch position 1.

NKQ

On/Off
1

24 VAC Transformer
Line
Volts

Blk (1) Common


a

Red (2) + Hot

Wht (3) + Y1 input

GK

Refer to page 26 for auxiliary switch (-S models) wiring.


800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Wiring for Damper Actuators and Control Valves

W231_A_11

On/Off, Spring Return, 120, 230V and UP

Actuators: EFB120(-S)
NFBUP(-S)

EFX120(-S)
NFXUP(-S)

AFBUP(-S)
AFXUP(-S)
AF120(-S) US/AF230(-S) US
LF120(-S) US/LF230(-S) US
TF120(-S) US

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION

14

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.

TF120(-S) US can be supplied with both 120 VAC


and 230 VAC.

19

UP models and TF120(-S) US uses L instead of H


on #2 wire.

20

All 120 VAC, 230 VAC and UP actuators use appliance rated
cables.

UP

Universal Power Supply (UP) models can be supplied


with 24 VAC up to 240 VAC.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.

On/Off

Line
Volts

14

UP
2

20

19

Wht N

Wht (1) Neutral

Blk H

Blk

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

120 VAC
230 VAC

(2) Hot

Refer to page 26 for auxiliary switch (-S models) wiring.


800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Wiring for Damper Actuators and Control Valves

W232_11

Floating Point, Spring Return, 24V

Actuators:

LF24-3(-S) US

TF24-3(-S) US

LFC24-3...US

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.

INSTALLATION NOTES

Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.

Actuators with plenum rated cable do not have numbers on


wires; use color codes instead. Actuators with appliance
cables are numbered.
Actuators Hot wire must be connected to the control board
common.
For triac sink the Common connection from the actuator
must be connected to the Hot connection of the controller.
The actuator must be connected to the control board common.

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Actuators may also be powered by 24 VDC.

CAUTION

6
11

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.

Actuator

Wire Number
4
5
4
5

TF24-3 US
TF24-3-S US
LF24-3 US
LF24-3-S US

Floating Point

Color
Org
Org
Grn
Wht

Triac Source
24 VAC Transformer

24 VAC Transformer

Blk (1) Common

Line
Volts

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

5
Line
Volts

Red (2) + Hot


a

Wht (3) +

2
Hot

Com

Blk (1) Common


Red (2) + Hot

CW

CCW

Wht (3) +

LF24-3(-S) US
LFC24-3-R US
LFC24-3-S US
TF24-3(-S) US

The indication of direction


is valid for switch position CW.

CW

CCW

LF24-3(-S) US
TF24-3(-S) US
The indication of direction
is valid for switch position CW.

Controller

Triac Sink

Triac Sink with Separate Transformer

24 VAC Transformer
Line
Volts

2
Hot

Com

11
24 VAC Transformer

Blk (1) Common


Red (2) + Hot

24 VAC Transformer

Line
Volts

Wht (3) +

CW

Line
Volts

+
CCW

Blk (1) Common


Hot

LF24-3(-S) US
TF24-3(-S) US

Com

Red (2) + Hot

Wht (3) +

Controller
The indication of direction
is valid for switch position CW.

CW

+
CCW

LF24-3(-S) US
TF24-3(-S) US

Controller

The indication of direction


is valid for switch position CW.

Refer to page 26 for auxiliary switch (-S models) wiring.


800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Wiring for Damper Actuators and Control Valves

Actuators: LMB24-3(-S) (-P5) (-P10) (-T)


TR24-3(-T) US
CMB24-3

NMB24-3
ARB24-3-5

AMB24-3(-S)
GMB24-3
GRB24-3-5

LMX24-3(-T)
NMX24-3(-T)
GRB24-3-7

Hazard Identification

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.

LRB24-3(-S) ARX24-3
ARB24-3(-S) LRX24-3
LRCB24-3(-S)

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION

AMX24-3(-T)
GMX24-3
GMB24-3-X1

Actuators may also be powered by 24 VDC.

Actuators with plenum rated cable do not have


numbers on wires; use color codes instead.
Actuators with appliance cables are numbered.

16

The TR24-3-T US actuators are provided with


a numbered screw terminal strip instead of cable.

17

TR24-3 US actuators cannot be wired in parallel.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.

Floating Point

On/Off
24 VAC Transformer

24 VAC Transformer

Blk (1) Common

Line
Volts

Blk (1) Common

Line
Volts

Red (2) +

Red (2) +

a
a open
a closed

Wht (3) +
1 0

The indication of direction


is valid for switch position 1.

Wht (3) +

LMB(X)24-3...
NMB(X)24-3...
AMB(X)24-3...
GMB(X)24-3...
CMB24-3...
LRB(X)24-3...
ARB(X)24-3...

Line
Volts

The indication of direction


is valid for switch position 1.

GMB(X)24-3...
CMB24-3...
LRB(X)24-3...
ARB(X)24-3...

16

17

24 VAC Transformer

Blk 1 Common

16

17

Blk 1 Common

Line
Volts

Red 2 +

Red 2 +

Wht 3 +

Note: TR24-3 (-T) US cannot


be wired in parallel with
any actuator.

LMB(X)24-3...
NMB(X)24-3...
AMB(X)24-3...

Floating Point

On/Off SPDT Switch

24 VAC Transformer

1 0

Wht 3 +

Note: TR24-3 (-T) US cannot


be wired in parallel with
any actuator.

TR24-3 (-T) US

TR24-3 (-T) US

Refer to page 26 for auxiliary switch (-S models) and -P5, -P10 potentiometer wiring.
800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

W332_11

On/Off and Floating Point, Non-Spring Return, 24V

Wiring for Damper Actuators and Control Valves


W612_11

Floating Point, Electronic Fail-Safe, 24V

Actuators: GKB24-3

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Provide overload protection and disconnect as required.

Actuators may also be powered by 24 VDC.

Control signal may be pulsed from either the Hot (source)


or the Common (sink) 24 VAC line.

Contact closures A & B also can be triacs.


A & B should both be closed for triac source and open for
triac sink.

For triac sink the common connection from the actuator


must be connected to the hot connection of the controller.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Floating Point

GKB24-3

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Wiring for Damper Actuators and Control Valves

Actuators:

LMX120-3
NMX120-3

AMX120-3
GMX120-3

LRX120-3
ARX120-3

CMB120-3

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.

15

LMB(X), NMB(X), AMB(X), GMB(X), LRB(X), and ARB(X)


can be supplied with either 120 VAC or 230 VAC.

19

All 120VAC and 230VAC actuators use appliance rated


cables.

Actuators with appliance cables are numbered.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.

Floating Point

On/Off

100 to 240 VAC

15

19

100 to 240 VAC

15

19

N L1

Blu (1) Common

N L1

Blk (1) Common

H L2

Blk (2) +

H L2

Red (2) +

a open
a closed

The indication of direction


is valid for switch position 1.

Wht (3) +

Wht (3) +

The indication of direction


is valid for switch position 1.

Refer to page 26 for auxiliary switch (-S models) wiring.


800-543-9038 USA

10

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

W364_11

On/Off and Floating Point, Non-Spring Return, 100 to 240V

Wiring for Damper Actuators and Control Valves


W233_A_11

Proportional, Spring Return, 24V

Actuators:

EFB24-SR(-S)
NFB24-SR(-S)

EFX24-SR(-S)
NFX24-SR(-S)

AFB24-SR(-S)
AFX24-SR(-S)
AF24-SR US
LF24-SR(-S) US
TF24-SR(-S) US

AFA24-SR US

Hazard Identification
INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
4

Equipment damage!
Up to four actuators may be connected in parallel if not
mechanically linked. Power consumption and input
impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Actuators may also be powered by 24 VDC.

Actuators with plenum rated cable do not have


numbers on wires; use color codes instead.
Actuators with appliance cables are numbered.

Only connect common to neg. () leg of control circuits.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.
7

A 500 resistor converts the 4 to 20 mA control


signal to 2 to 10 VDC.

The AFA24-SR US and TF24-SR(-S) US are supplied


without position feedback.

Actuator
24 VAC Transformer

Line

Blk (1) Common

Volts
N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Red (2) + Hot

()
Control Signal
(+)
VDC/mA

500

2 to 10 VDC ()
Feedback Signal (+)

5
Wht (3) Y Input,
2 to 10

Wire Number
5
5
5
5
5
5
5
5
5

EFB24-SR(-S)
EFX24-SR(-S)
AFB24-SR(-S)
AFX24-SR(-S)
AF24-SR US
NFB24-SR(-S)
NFX24-SR(-S)
LF24-SR US
LF24-SR-S US

Color
Org
Org
Org
Org
Wht
Org
Org
Grn
Wht

(5) U Output,
2 to 10V

CW

CCW

EFB24-SR(-S)
EFX24-SR(-S)
AFB24-SR(-S)
AFX24-SR(-S)
AF24-SR US
NFB24-SR(-S)
NFX24-SR(-S)
LF24-SR(-S) US

24 VAC Transformer
Line

Blk (1) Common

Volts

()
Control Signal
(+)
VDC/mA
6

500

Red (2) + Hot

5
Wht (3) Y Input,
2 to 10V

AFA24-SR US
TF24-SR(-S) US

Refer to page 26 for auxiliary switch (-S models) wiring.


800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

11

Wiring for Damper Actuators and Control Valves

W333_11

Proportional, Non-Spring Return, Electronic Fail-Safe, 24V

Actuators: LMB24-SR (-T)

NMB24-SR
LMX24-SR (-T)
GMB24-SR
AMX24-SR (-T)
CMB24-SR-R GKB24-SR

AMB24-SR
CMB24-SR-L

NMX24-SR (-T)
GMX24-SR
GKX24-SR

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.
3

Actuators may also be powered by 24 VDC.

Actuators with plenum rated cable do not have


numbers on wires; use color codes instead.
Actuators with appliance cables are numbered.

Only connect common to neg. () leg of control circuits.


Terminal models (-T) have no-feedback.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
4

LRB24-SR TR24-SR (-T) US


ARB24-SR LRX24-SR
ARX24-SR
NKQB24-SR NKQX24-SR

Equipment damage!
Up to four actuators may be connected in parallel if not
mechanically linked. Power consumption and input
impedance must be observed.

APPLICATION NOTES
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Blk

Line

()

500

Control Signal
(+)
VDC/mA

24 VAC Transformer

Line

(1) Common

()
Control Signal
(+)
VDC/mA

Wht (3) Y Input 2 to 10V

500

Red (2) + Hot

5
Wht (3)

Y Input, 2 to 10V

Org (5)

U Output, 2 to 10V

7
2 to 10 VDC ()
Feedback Signal (+)

Blk (1) Common

Volts

Red (2) + Hot

Volts

A 500 resistor converts the 4 to 20 mA control


signal to 2 to 10 VDC.

TR24-SR (-T) US

6
1 0

LMB(X)24-SR...
NMB(X)24-SR...
AMB(X)24-SR...
GMB(X)24-SR...
LRB(X)24-SR...
ARB(X)24-SR...
LHB(X)24-SR...
AHB(X)24-SR...
LUB(X)24-SR
CMB24-SR...
GK...
NK...

800-543-9038 USA

12

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

24 VAC Transformer

Meets cULus requirements without the need of an


electrical ground connection.

Wiring for Damper Actuators and Control Valves

W365_11

Proportional, Non-Spring Return, 100 to 240V

Actuators: LMX120-SR
NMX120-SR

AMX120-SR
LRX120-SR

ARX120-SR

Hazard Identification
INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION

15

LMB(X), NMB(X), AMB(X), GMB(X), LRB(X), and


ARB(X) can be supplied with either 120 VAC or 230 VAC.

Only connect common to neg. () leg of control circuits.

19

All 120 VAC and 230 VAC actuators use appliance rated
cables.

Actuators with appliance cables are numbered.

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

A 500 resistor converts the 4 to 20 mA control


signal to 2 to 10 VDC.

19

N L1

Wht (1) Neutral

H L2

Blk (2) Hot +

Cable 2

15

Meets cULus requirements without the need of an


electrical ground connection.

Blk (1) Common

7
()
Control Signal
VDC/mA (+)
2 to 10 VDC ()
Feedback Signal (+)

Red (2) Hot +

5
Wht (3) Y Input, 2 to 10V
Org (5) U Output, 2 to 10V
1

800-543-9038 USA

Cable 1

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

100 to 240 VAC

APPLICATION NOTES

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

13

Wiring for Damper Actuators and Control Valves

W225_2_11

Phasecut Control Signal, Spring Return and Non-Spring Return, 24V

Actuators:

AF24-PC US
NMX24-PC

LMX24-PC
GMX24-PC

AMX24-PC
ARX24-PC

LRX24-PC

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.
3

Actuators may also be powered by 24 VDC.

Actuators with plenum rated cable do not have


numbers on wires; use color codes instead.
Actuators with appliance cables are numbered.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.

APPLICATION NOTES

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Meets cULus requirements without the need of an


electrical ground connection.

24 VAC Transformer

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Blk (1) Common

Line
Volts

Red (2) Hot +


Wht *(3) Y Input, 0 to 10V phasecut
()

Control Signal
(+)
0 to 10 V Phasecut

Org (5) U Output, 2 to 10V

PC

* White color wire for AF24-PC US, Pink color for all others.
White color wire for AF24-PC US, Orange color for all others.

800-543-9038 USA

14

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Wiring for Damper Actuators and Control Valves

W604_11

Proportional, Spring Return, 24V, 3 k or 10 k Control Input

Actuators: LF24-ECON-R03 US

LF24-ECON-R10 US

AF24-ECON-R03 US

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Equipment damage!
Actuators may be connected in parallel. Power consumption
and input impedance must be observed.

Override Control

27

A relay or switch can spring return the actuator when the


RTU fan de-energizes, or if low ambient temperature is sensed.
A standard relay can be used to close the sensor circuit to
engage economizer mode, e.g. outside air changeover device
like a dry bulb or enthalpy limit switch. Honeywell logic
module W7459A and enthalpy sensor C7400 also provide
terminals for this switching.

29

A remote CO2 sensor or DDC controller can change the


standard relay opening or closing the sensor circuit. This
device can be a relay or a dry bulb/enthalpy limit switch.

30

Override control for Y2 only accepts 0 to 10 VDC


override control.

Application

Drive closed (0%)

Morning warm-up cycle

24 VAC

W203

AF24-ECON
LF24-ECON position

Y1

Common

Drive open (100%)

Smoke Purge

Y1

Open wire

Drive to min. position

Mechanical cooling in
use, RTU thermostat
calls for heat.

0 VDC to 10 VDC

Min. position of 0% to 100%

B
Line
Volts

Blk (1) Common


Red (2) + Hot

27

Wht (3) Y1

Override potentiometer
via a remote C02
sensor/controller or
DDC controller.

Standard Economizer Mode Wiring

24 VAC Transformer

Org (4) Y2 Min-pos, 0 to 10V


Grn (5) U Output, 2 to 10V
Default
CW
CCW

Override
Closed (0%)

Override
Open (100%)

()
Control Signal
(+)
0 to 10 VDC

29

30

26

.8

.2
.4

.6
MIN

AF24-ECON-R03 US
LF24-ECON-R03 US
LF24-ECON-R10 US

W202

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Min-position is adjustable from 0 to 100% with a


potentiometer on the actuator cover.

Override

Wire Input Signal

Y2

26

28

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Y1

Actuators with plenum rated cable do not have numbers on


wires; use color codes instead. Actuators with appliance
cables are numbered.

CAUTION

24 VAC Transformer
Line
Volts

Blk (1) Common


Red (2) + Hot

27

Wht (3) Y1

3 k NTC*
MA thermistor
setpoint 55F

Org (4) Y2 Min-pos, 0 to 10 V


Grn (5) U Output, 2 to 10V

28

Default
CW
CCW

()
Control Signal
(+)
0 to 10 VDC

29

30

26

.8

.2
.4

.6
MIN

AF24-ECON-R03 US
LF24-ECON-R03 US
LF24-ECON-R10 US

*10 k NTC thermistor for -R10 types.

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

15

Wiring for Damper Actuators and Control Valves


Proportional, Spring Return, 24V, 2 to 10 VDC (or 4 to 20 mA)

W605_11

Control Signal or Three-Position On/Off Control

Actuators: LF24-SR-E US

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Equipment damage!
Actuators may be connected in parallel. Power consumption
and input impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Actuators may also be powered by 24 VDC.

Actuators with plenum rated cable do not have numbers on


wires; use color codes instead. Actuators with appliance
cables are numbered.

A 500 resister converts the 4 to 20 mA control signal to


2 to 10 VDC.

26

Min-position is adjustable from 0 to 100% with a


potentiometer on the actuator cover.

31

For three-position control set direction of rotation to CW (default).

32

Switch A, actuator spring returns when open (e.g., fan interlock).

21 24 VAC Transformer
Blk (1)

Red (2) x + Min-position

32

Wht (3) D Y Full Open

Grn (5)

31

Three-Position Control Signals


Switch A Wire 2-Red (x)
Wire 3-White (D)
Any

Any

Closed (via spring)

24 VAC

Open

Min-position*

Closed

Open

24 VAC

Full Open*

Closed

24 VAC

24 VAC

Full Open*

* Desired position achieved by driving actuator with motor.


** An example would be to interlock the actuator power supply with the fan
motor starter.

LF24-SR-E US

21 24 VAC Transformer
W179

Line

Blk (1) Common

Volts

.2

MIN

5
Blk (1)

Volts
Line

.4

Min-Position with Full Open Override (with a single


contact closure)

2 to 10 VDC Control of LF24-SR-E US


5

.8
.6

26

Closed

24 VAC Transformer

Default
CW
CCW

Position

Open**

21

U Output, 2 to 10V

Common

Red (2) x + Min-position

32

24 VAC
Wht (3) D Y Full Open

Red (2) + Hot

Grn (5)

()
Control Signal (+)
2 to 10 VDC

Wht (3) Y Input, 2 to 10V

31

Grn (5) U Output, 2 to 10V


Default
CW

CCW

LF24-SR-E US

.8
.6

26

.8

.4

800-543-9038 USA

.6

26

16

U Output, 2 to 10V

Default
CW
CCW

LF24-SR-E US

.4
0

.2

MIN

.2

MIN

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Provide overload protection and disconnect as required.

21

Common

24 VAC

Volts

Meets cULus requirements without the need of an


electrical ground connection.

Line

APPLICATION NOTES

W176

Three-Position Control with a SPDT Switch or Two Contact


Closures (e.g. fan, cooling Y)

W176

Wiring for Control Valves

W606_11

On/Off and Floating Point, Spring and Non-Spring Return, 24V

Actuators:

NV24-3 US

NVD24-3 US

NVFD24 (-E) US

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Equipment damage!
Actuators may be connected in parallel. Power consumption
and input impedance must be observed.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.

Floating Point and On/Off Control (diagram shown with default


position of S1.2: Off)

24 VAC Transformer
Line

On/Off Control-using actuator to drive open/close, spring upon


power loss. (diagram shown with default position of S3.2: 3-way
Off, 2-way On)

Blk (1) Common

Volts

Wht (2) +

24 VAC Transformer

extending

Line
Wht (3) +

Blk (1) Common

Volts

retracting

Red (2) + Hot


Wht (3) Y1 Input

NV24-3 US
NVD24-3 US
NVFD24 US
NVFD24-E US

= actuator plunger extending


= actuator plunger retracting

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Triac Source Floating Point


On/Off Control (diagram shown with default position of S1.2: Off)

Line

24 VAC Transformer (AC only)

Volts

24 VAC Transformer
Line
Volts

2
Hot

Com

Blk (1) Common


Wht (2) +

extending

Wht (3) +

retracting

Blk (1) Common


Wht (2) + Hot
Wht (3) Y1 Input

Controller

NV24-3 US
NVD24-3 US

NV24-3 US
NVD24-3 US

Triac Sink Floating Point


Line

On/Off Control-using actuator to drive one direction and spring the


opposite direction. NOTE: A bridge must be made inside the NVF
between terminals 2 and 3 (diagram shown with default position of
S3.2: 3-way Off, 2-way On)

24 VAC Transformer
Line
Volts

Volts

2
Hot

Com

Blk (1) Common


Wht (2) + Hot

2
Controller

Wht (3) Y1 Input

Blk (1) Common


NV24-3 US
NVD24-3 US

Wht (2) + Hot


Wht (3) Y1 Input
NVFD24 US
NVFD24-E US

800-543-9038 USA

24 VAC Transformer (AC only)

SPRING RETURN ACTUATORS MODEL DESIGNATION

866-805-7089 CANADA

retracting plunger (spring up)


NVFD24 US
NVFD24-MFT US
NVF24-MFT US

extending plunger (spring down)


NVFD24-E US
NVFD24-MFT-E US
NVF24-MFT-E US

203-791-8396 LATIN AMERICA / CARIBBEAN

17

Wiring for Control Valves

Actuators:

NVF24-MFT (-E) US

NVFD24-MFT (-E) US

NV24-MFT US

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.
10

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

Equipment damage!
Actuators may be connected in parallel. Power consumption
and input impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

For triac sink the Common connection from the actuator


must be connected to the Hot connection of the controller.
Position feedback cannot be used with a triac sink controller.
The actuator internal common reference is not compatible.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.
8

Control signal may be pulsed from either the Hot (Source)


or Common (Sink) 24 VAC line.

12

IN4004 or IN4007 diode.


(IN4007 supplied, Belimo part number 40155)

Triac Source Floating Point


24 VAC Transformer (AC only)

Floating Point Control. (diagram shown with default position of


S3.2: 3-way Off, 2-way On.)

Line
Volts

2
Hot

24 VAC Transformer

12 Requires diode

NVD24-MFT US

COM

Blk (1) Common


Red (2) + Hot

Line

Blk

Volts

(1) Common

Wht (3) Y1 Input, 2 to 10V

Red (2) + Hot

Wht (5) U Output, 2 to 10V

Wht (3) Y1 Input

CCW

2 to 10 VDC
Feedback Signal

CW

12

12
Wht (5) U Output, 2 to 10V

Controller

Position
Feedback

NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US

NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US

Direction of rotation switch


CCW

CCW

CW

CW

B 1

B 1

Pulse Width Modulation Control Wiring (diagram shown with default


position of S3.2: 3-way Off, 2-way On)
12
2

24 VAC Transformer
Line

Blk

Volts

(1) Common

Triac Sink Floating Point

Red (2) + Hot

24 VAC Transformer (AC only)

Line
Volts

Wht (3) Y Input

()

2 to 10 VDC
Feedback Signal (+)

10

Wht (5) U Output

Hot

NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US

COM

Red (2) + Hot


Wht (3) Y1 Input, 2 to 10V
Wht (5) U Output, 2 to 10V

12

MFT Typical 2 to 10 VDC or 4 to 20 mA Wiring (diagram shown with


default position of S3.2: 3-way Off, 2-way On)
24 VAC Transformer
Line

()
Control Signal
VDC/mA (+)
()
2 to 10 VDC (+)
Feedback Signal

Controller

NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US

2
Blk

Volts

Blk (1) Common

(1) Common

SPRING RETURN ACTUATORS MODEL DESIGNATION

Red (2) + Hot

500
Wht (3) Y1 Input, 2 to 10V

retracting plunger (spring up)


NVFD24 US
NVFD24-MFT US
NVF24-MFT US

extending plunger (spring down)


NVFD24-E US
NVFD24-MFT-E US
NVF24-MFT-E US

Wht (5) U Output, 2 to 10V


NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US

800-543-9038 USA

18

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

W607_11

MFT, Spring and Non-Spring Return, 24V

Wiring for Damper Actuators and Control Valves

W228_A_11

MFT, Spring Return, 24V

Actuators: TF24-MFT US

LF24-MFT(-S) US

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.

INSTALLATION NOTES
3

Actuators may also be powered by 24 VDC.

CAUTION

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.

Actuators with plenum rated cable do not have numbers on


wires; use color codes instead. Actuators with appliance
cables are numbered.

Equipment damage!
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.
7

A 500 resistor converts the 4 to 20 mA control signal to


2 to 10 VDC.

Contact closures A & B also can be triacs. A & B should both be


closed for triac source and open for triac sink.

12

4
Blk

Line
Volts

8
()
2 to 10 VDC
Feedback Signal (+)

IN4004 or IN4007 diode. (IN4007 supplied, Belimo part


number 40155).

(1) Common

Two Position

Red (2) + Hot

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

10

For triac sink the Common connection from the actuator must
be connected to the Hot connection of the controller. Position
feedback cannot be used with a Triac sink controller. The
actuator internal common reference is not compatible.

10

Floating Point
24 VAC Transformer

Control signal may be pulsed from either the Hot (Source)


or Common (Sink) 24 VAC line.

Wht (3) Y1 Input

24 VAC/DC Transformer

12

(5) U Output 2 to 10V

Line

Blk (1)

Common

Volts

Red (2)

Hot

CCW CW

()
Position
Feedback VDC (+)
Direction of rotation switch
CCW

CW

CW

Y Input

U Output

(5)

CCW CW

CCW

Wht (3)

B 5

Override Control to min, mid, max, Positions


PWM

24 VAC Transformer (AC only)


24 VAC Transformer (AC only)

Blk (1) Common

Line

Volts
Line

Blk (1)

Common

Red (2)

+ Hot

Wht (3)

Y Input

Volts
()
Position (+)
Feedback VDC

(5)

Red (2) + Hot

()
Control Signal
2-10 VDC or 4 to 20 mA (+)

U Output

B
C

Wht (3) Y1 Input, 2 to 10V

500

1/4 watt

A
Min*
Mid*
Max*
Normal**

Actuator
TF24-MFT US
LF24-MFT US

Wire Number
5
5

800-543-9038 USA

Color
Org
Wht

Functions

CCW CW

0%
50%
100%
Control mode acc. to Y

* Default selectable 0-100%. See Configuration Data Sheet.


** Customizable. See Configuration Data Sheet.

Refer to page 26 for auxiliary switch (-S models) wiring.


866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

19

Wiring for Damper Actuators and Control Valves

W400_A_11

MFT, Spring Return, Non-Spring Return, Electronic Fail-Safe, 24V

Actuators: EFB24-MFT(-S) EFX24-MFT(-S) AFB24-MFT(-S) AFX24-MFT(-S) NFB24-MFT(-S) NFX24-MFT(-S)


LMX LRX NMX AMX ARX GKX NKQ ARX24-MFT-5 ARB24-MFT-5 GRX24-MFT-5
GMX24-MFT-X1 GRB24-MFT-S GRB24-MFT-5 GRB24-MFT-7

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.

Equipment damage!
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.

10

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed
electrician or other individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all electrical safety
precautions when exposed to live electrical components could result in death or
serious injury.

APPLICATION NOTES
Meets cULus requirements without the need of an electrical
ground connection.
7

A 500 resistor converts the 4 to 20 mA control signal


to 2 to 10 VDC.

Contact closures A & B also can be triacs. A & B should


both be closed for triac source and open for triac sink.

VDC/4-20 mA
4

24 VAC Transformer

For triac sink the Common connection from the actuator


must be connected to the Hot connection of the controller.
Position feedback cannot be used with a triac sink controller.
The actuator internal common reference is not compatible.

Blk (1) Common

Line
Volts

Two Position

Red (2) + Hot


500
1/4
watt

()
Control Signal
(+)
4 to 20 mA or 2 to 10 VDC

24 VAC/DC Transformer

Wht (3) Y1 Input, 2 to 10V


7

Pnk (4) Y2 Input

Blk (1) Common

Line

Grn (5) U Output, 2 to 10V

Volts

Red (2) Hot


a

CCW CW

Position
Feedback VDC

Wht (3) Y Input


Pnk (4) Y2 Input
Org (5) U Output

()
(+)

Floating Point (except NKQ)


10

24 VAC Transformer

Blk (1) Common

Line
Volts

Red (2) Hot +

A
8

Wht (3) Y1 Input

Override Control to min, mid, max, Positions

()
2 to 10 VDC
Feedback Signal (+)

Pnk (4) Y2 Input

Org (5) U Output 2 to 10V

24 VAC Transformer (AC Only)

CCW
CW

B 5

Volts

CCW

B 5

()
Control Signal
2-10 VDC or 4 to 20 mA (+)

Triac Source and Sink Diagrams (See page 21)

Red (2) + Hot

CW

B
C

Wht (3) Y1 Input, 2 to 10V


Pnk (4) Y2 Input
Org (5)

500
1/4 watt

PWM (except NKQ)


24 VAC Transformer (AC only)

Functions

Min*

Blk (1) Common

Line
Volts
Position ()
Feedback VDC (+)

800-543-9038 USA

20

Red (2) + Hot


Wht (3) Y Input
Pnk (4) Y2 Input
Org (5) U Output

866-805-7089 CANADA

Blk (1) Common

Line
Direction of rotation switch

Mid*
Max*
Normal**

0%
50%
100%
Control mode acc. to Y

* Default selectable 0-100%. See Configuration Data Sheet.


** Customizable. See Configuration Data Sheet.

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Actuators may also be powered by 24 VDC.


Actuators with plenum rated cable do not have numbers on
wires; use color codes instead. Actuators with appliance
cables are numbered.
Control signal may be pulsed from either the Hot (Source)
or Common (Sink) 24 VAC line.

Wiring for Damper Actuators and Control Valves

W402_11

MFT, Non-Spring Return, 24V

Actuators: LMX
ARB24-MFT-5
GRB24-MFT-7

LRX
GMX24-MFT

NMX
AMX
ARX
GMX24-MFT-X1 GRX24-MFT-5 GRX24-MFT-7

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
4

Equipment damage!
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.

Actuators with plenum rated cable do not have numbers on


wires; use color codes instead. Actuators with appliance
cables are numbered.

Only connect common neg (-) leg of control circuits.

11

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Triac Sink

ARX24-MFT-5
GRB24-MFT-5

For triac sink with common connection from the actuator


must be connected to the hot connection of the controller.
The actuator must be connected to the control board
common.

APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.

Triac Sink with Separate Transformer


24 VAC Transformer
24 VAC Transformer

Line
Volts

24 VAC Transformer

11

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Hot

Com

Blk (1) Common

Volts

Line

Volts

Red (2) + Hot


Wht (3) Y1 Input

Line

Blk (1) Common


Hot

Pnk (4) Y2 Input


Org (5) U Output 2 to 10 V

Com

Red (2) + Hot


Wht (3) Y1 Input
Pnk (4) Y2 Input
Org (5) U Output 2 to 10 V

Controller
Controller

Triac Source
24 VAC Transformer
Line
Volts

4
Hot

Com

Blk (1) Common


Red (2) + Hot
Wht (3) Y1 Input
Pnk (4) Y2 Input
Org (5) U Output 2 to 10 V

Controller

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

21

Wiring for Damper Actuators and Control Valves

W234_A_11

Wiring Multiple MFT Actuators

Control Type: PWM

Hazard Identification

INSTALLATION NOTES
3

Actuators may also be powered by 24 VDC.

Actuators with plenum rated cable do not have numbers on


wires; use color codes instead. Actuators with appliance
cables are numbered.

Control signal may be pulsed from either the Hot or


Common 24 VAC line.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
4

Equipment damage!
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Wiring multiple...MFT actuators to single shaft and/or on


valves. All MFT actuators are wired in master-slave
configuration.

Pulse Width Modulation

24 VAC Transformer (AC Only) Master


.1 to 25.5 sec

Blk (1) Common

Line
Volts

Red (2) + Hot

3
Position
Feedback VDC
0 to 5 VDC

()

Wht (3) Y Input

(+)

Org (5) U Output


2 to 10 VDC

CCW CW

MFT actuator configurations should also co-ordinate with


each other. Meaning the master input = controllers output.
Master output = slave input. Slave output = controller input.

Slave

Example

Blk (1) Common

Controller
Output

Master
Feedback

Slave
Input

Slave
Feedback

Red (2) + Hot

0.1 to 25.5 sec

2 to 10 VDC

2 to 10 VDC

0 to 5 VDC

Wht (3) Y Input


2 to 10 VDC

Org (5) U Output

Multiple Actuators Mounted to One Control Shaft


Max. Qty Per Shaft

Torque Generated

EFB24-MFT(-S)
EFX24-MFT(-S)

Model

810 in-lb

AFB24-MFT(-S)
AFX24-MFT(-S)

432 in-lb

GMX(B)24-MFT

640 in-lb

GKX(B)24-MFT

640 in-lb

800-543-9038 USA

22

866-805-7089 CANADA

CCW CW

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

Wiring for Damper Actuators and Control Valves

Actuators: AFB24-MFT95

AFX24-MFT95

GMX24-MFT95

AMX24-MFT95

High Limit Control

22
23
24

25

Volts

22

Pnk (4) W

Series 90
Controller

Red (2) + Hot

5 = Gray
6 = Orange

Series 90
Controller

Volts

Line

W015

21 24 VAC Transformer

Blk (1) Common


Red (2) + Hot

23

A
Pnk (4) W
135

Wht (3) R

Gry (5)

21
Line

Blk (1) Common

Volts

Red (2) + Hot

24 VAC Transformer

Volts

Pnk (4) W

Wht (3) R

23

Shunting
Resistor

24

24

22

Honeywell T675A
Morning Warmup

Blk (1) Common


Red (2) + Hot

23
Pnk (4) W

No. of
actuators Resistance
2
1300
3
910
4
768
Resistor Kit No. ZG-R06

23

S963A
Minimum Position
Potentiometer

Red (2) + Hot


B

22

25

Pnk (4) W
Wht (3) R
Gry (5) B
Org (6) U5 Output 2 to 10 VDC

23

Gry (5) B
Org (6) U5 Output 2 to 10 VDC
To other
actuators

Used with the W973 and W7100 controllers

Honeywell Q209A
Minimum Position
Potentiometer

Line

Blk (1) Common

Volts

Red (2) + Hot

22

23

Shunting
Resistor

Pnk (4) W

Wht (3) R

W973, W7100
T775

Org (6) U5 Output 2 to 10 VDC

Honeywell
T675A Morning
Warmup

-MFT95

21
Line

21

21

Line

Blk (1) Common

Volts

Line
Volts

Red (2) + Hot

Pnk (4) W

Wht (3) R

Gry (5) B

Series 90 low limit control


135 for 0 to 50% control
280 for 0 to 100% control

24
To other
actuators

23
25

Wht (3) R

23

Pnk (4) W
25
Wht (3) R
Gry (5) B
Org (6) U5 Output 2 to 10 VDC

23
22

Pnk (4) W

Blk (1) Common

Red (2) + Hot

Series 90
Controller

Red (2) + Hot

22

22

Blk (1) Common

23
25

Gry (5) B

Volts

24 VAC Transformer

-MFT95

-MFT95
R

-MFT95

Low Limit Control

25

Wht (3) R

-MFT95

H205 Change- Occupied


over Controller Contact

Org (6) U5 Output 2 to 10 VDC

Controller

Volts

24

Gry (5) B

Occupied
Contact

Blk (1) Common

A
Line

To other
actuators

Series 90
Controller

-MFT95

Pnk (4) W
25
Wht (3) R
Gry (5) B
Org (6) U5 Output 2 to 10 VDC

Line
Volts

Org (6) U5 Output 2 to 10 VDC


24 VAC Transformer

-MFT95
W

Shunting
Resistor

21

Wiring Multiple Actuators to a Series 90 Controller


using a Minimum Position Potentiometer
21

Gry (5) B

21 24 VAC Transformer

24

W016

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

The direction of rotation switch is set so that the fail safe position and the
position of the damper is closed with no signal at wire R.

Volts

Red (2) + Hot

Damper Position

Damper Closed

Wht (3) R

Line

Blk (1) Common

No. of
actuators Resistance
2
140
3
71.5
4
47.5
5
37.5
6
28
Resistor Kit No. ZG-R03

23
25

W973, W7100
Controller

23

21

Damper Open

-MFT95

Line
Switch B

Pnk (4) W

24

Pnk (4) W
25
Wht (3) R
Gry (5) B
Org (6) U5 Output 2 to 10 VDC

Blk (1) Common

Shunting
Resistor

Org (6) U5 Output 2 to 10 VDC

24 VAC Transformer

Volts

-MFT95

Wiring Multiple Actuators to a Series 90 Controller

Override
Switch A

H205
Changeover
Controller

22

Line

Red (2) + Hot

22

Gry (5) B

Series 90 high limit control - 280

24

3 = White
4 = Pink

24

Org (6) U5 Output 2 to 10 VDC

Wire Colors

Blk (1) Common

Volts

Wht (3) R

1 = Black
2 = Red

Line

Red (2) + Hot

23

21

Q209A
Minimum Position
Potentiometer

Blk (1) Common

W018

21

Line

LMX24-MFT95

Typical wiring diagrams for multiple actuators


used with the W973, W7100 and T775 controllers
21 24 VAC Transformer

W019

24 VAC Transformer

21

Actuators with plenum rated cable do


not have numbers on wires; use color
codes instead. Actuators with
appliance cables are numbered.
Provide overload protection and
disconnect as required.
Actuators and controller must have
separate transformers.
Consult controller instruction data for
more detailed information.
Resistor value depends on the type of
controller and the number of
actuators. No resistor is used for one
actuator. Honeywell resistor kits may
also be used.
To reverse control rotation, use the
reversing switch.

W017

INSTALLATION NOTES

NMX24-MFT95

W020

Wnew60408_6

Spring Return and Non-Spring Return, 24V for use with


Honeywell Electronic Series 90, or a 0 to 135 input

Gry (5) B
Org (6) U5 Output 2 to 10 VDC
To other
actuators

-MFT95

-MFT95

Org (6) U5 Output 2 to 10 VDC

800-543-9038 USA

-MFT95

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

23

Wiring for Damper Actuators and Control Valves

LF24-MFT-S-20 US

6 to 9 VDC Control of LF24-MFT (-S) -20 US

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.

21

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
2

24 VAC Transformer

Line

Blk (1)

Common

Volts

Red (2)

+ Hot

Wht (3)

Y Input, 6 to 9V

Control Signal
6 to 9 VDC (+)

Equipment damage!
Actuators may be connected in parallel. Power consumption
and input impedance must be observed.

W027

Actuators: LF24-MFT-20 US

Wht (4) Output +20 VDC


Wht (5) U Output 2 to 10V

Power to Controller

Wht (6) Common +20 VDC


Controller Common ()

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

CW

CCW

Feedback 2-10 VDC

LF24-MFT (-S) -20 US

Multiple LF24-MFT (-S) -20 US Actuators from One Controller


W029

W609_11

Proportional, Spring Return, 24V, 6 to 9 VDC


Output Power Supply 20 VDC provides power to controllers

21 24 VAC Transformer

INSTALLATION NOTES

Line

Blk (1) Common

Volts

Red (2) + Hot

Wht (3) Y Input, 6 to 9V


Control Signal
6 to 9 VDC (+)

Actuators may also be powered by 24 VDC

21

Provide overload protection and disconnect as required.

Wht (4) Output +20 VDC

Feedback 2-10 VDC

Wht (5) U Output 2 to 10V

Power to Controller

Wht (6) Common +20 VDC

Controller Common ()

CW

Typical Control Wiring for MP-52XX Series Actuators to


Controllers Requiring External 20 VDC Power Supply

LF24-MFT (-S) -20 US


W215

CP-8102
TP-810X
TP-8121
TP-8124
TP-8232

1
Vac
Power

Typical
Controller

+20 (Red)
OP1 (Yellow)
COM (Blue)

1 24 Vac: Black/Blue
120 Vac: White
240 Vac: White/Black
Belimo modulating actuators
are 24 VAC/DC, if 120 or 240
is available an external
transformer is required.
2 Maximum of 2
3 MP-52XX-500 models include
internal SPDT auxiliary switch.

21 24 VAC Transformer

MP-52XX
2

Black
Red
Yellow
Blue

Line

Blk (1) Common

Volts

Red (2) + Hot

Wht (3) Y Input, 6 to 9V

N.C.
COM

Brown
Aux.
Switch Orange
Green

Wht (4) Output, +20 VDC

N.O.

Wht (5) U Output 2 to 10V


Wht (6) Common +20 VDC
CW

CCW

Wire cross reference


MP-52XX
Black/Blue, Power
Black, Power
Red, +20
Yellow, OP1
Blue, COM
Brown, N.O.
Orange, N.C.
Green, Ground

CCW

Belimo
(SR or MFT)
2, Hot
1, Com
4, +20 VDC
3, Signal
6, Com VDC
S3, N.O.
-S type
S2, N.C.
-S type
Not used

To other actuators

LF24-MFT (-S) -20 US

Refer to page 26 for auxiliary switch (-S models) wiring.


800-543-9038 USA

24

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Wiring for Damper Actuators and Control Valves


W234_2_B_11

Wiring Multiple MFT Actuators

Control Type: VDC or 4-20mA

MFT95

VDC or 4-20mA

Hazard Identification

Red (2) + Hot

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
4

Blk (1) Common

Line
Volts

CAUTION

Master

24 VAC Transformer

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

()

Control Signal
(+)
2 to 10 VDC or
4 to 20 mA

Wht (3) Y Input, 2 to 10 V


500
1/4 watt

Org (5) U Output 2 to 10 V

Equipment damage!
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.

CCW CW

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Slave

Blk (1) Common


Red (2) + Hot

Maximum
4 actuators
per shaft.

Wht (3) Y Input, 2 to 10 V


Org (5) U

CCW CW

INSTALLATION NOTES
3

Actuators may also be powered by 24 VDC.

Actuators with plenum rated cable do not have numbers on


wires; use color codes instead. Actuators with appliance
cables are numbered.

Multiple Actuators Mounted to One Control Shaft

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

21

21

Provide overload protection and disconnect as required.

23

Consult controller instruction data for more detailed


information.

24 VAC Transformer

Blk (1) Common

Line
Volts
3

W
R

25

To reverse control rotation, use the reversing switch.

Master

Red (2) + Hot

23

Wht (3) W
Pnk (4) R
Gry (5) B

25

Org (6) U Output, 2 to 10 V

-MFT95

Wiring multiple...MFT actuators to single shaft and/or on


valves. All MFT actuators are wired in master-slave
configuration.

Slave

Blk (1) Common

MFT actuator configurations should also co-ordinate with


each other. Meaning the master input = controllers output.
Master output = slave input. Slave output = controller input.

Red (2) + Hot

23

Wht (3) Y1 Input

25

Pnk (4) Y2 Input


Org (6) U Output 2 to 10 V

Example
Controller
Output

Master
Feedback

Slave
Input

Slave
Feedback

2 to 10 VDC

2 to 10 VDC

2 to 10 VDC

0 to 5 VDC

CCW CW

-MFT
4

Multiple Actuators Mounted to One Control Shaft


Model

Max. Qty Per Shaft

Torque Generated

810 in-lb

432 in-lb

640 in-lb

640 in-lb

EFB24-MFT(-S)
EFX24-MFT(-S)
AFB24-MFT(-S)
AFX24-MFT(-S)
GMX(B)24-MFT
GKX(B)24-MFT
800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

25

Wiring for Damper Actuators and Control Valves

Actuators:

EFB...-S
EFX...-S AFB...-S AFX...-S AF...-S US
AMB(X)...-S
LMB(X)...-S ARB(X)...-S LRB(X)...-S

NFB...-S
S1A/S2A

NFX...-S
LF...-S US
LMB(X)...(-P5)(-P10)

TF...-S US

INSTALLATION NOTES

APPLICATION NOTES

One built-in auxiliary switch (1xSPDT), for end position


indication, interlock control, fan startup, etc.

Meets cULus requirements without the need of an


electrical ground connection.

13

Two built-in auxiliary switches (2xSPDT), for end position


indication, interlock control, fan startup, etc.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

Same voltage must be used for dual switch models.


Either 24 VAC or line voltage, not both.

Auxiliary Switch Wiring for LF-S US, TF-S,


LMB(X)24-3-S, AMB(X)24-3-S, LRB(X)24-3-S, ARB(X)24-3-S
1
S1
NC

S2
S3

Auxiliary Switch Wiring for EFB...-S, EFX...-S, AFB...-S,


AFX...-S, NFB...-S, NFX...-S
13

NC

S3
NO

10

Auxiliary Switch Ratings


Voltage
Product

S4
NC

S5
S6

NO

10 to 90
10 to 85 for EF...

EFB-S AFB-S NFB-S


EFX-S AFX-S NFX-S

Auxiliary Switch Wiring for AF -S US


13
S1
S2

NC

S3
NO

NC

S5
NO

Resistive
Load

Inductive
Load

EFB...-S, EFX...-S
AFB...-S, AFX...-S

250
250

3.0 A
3.0 A

0.5 A
0.5 A

AF...-S US
NFB...-S, NFX...-S

250
250

7.0 A
3.0 A

2.5 A
0.5 A

LF...-S US

250

3.0 A

0.5 A

TF...-S US

250

3.0 A

0.5 A

AMB(X)...-S

250

3.0 A

0.5 A

LMB(X)...-S

250

3.0 A

0.5 A

ARB(X)...-S

250

3.0 A

0.5 A

LRB(X)...-S

250

3.0 A

0.5 A

S1A, S2A

250

3.0 A

0.5 A

S4

S6

0 to 95

LF-S US
TF-S US
LMB(X)24-3-S
AMB(X)24-3-S
LRB(X)24-3-S
ARB(X)24-3-S

S1
S2

NO

25 to 85

Potentiometer and Auxiliary Switch Wiring for


LMB(X)24-3(-S)(-P5)(-P10)

AF-S US

Add on Auxiliary Switches


S1A/S2A for GMB(X), AMB(X), NMB(X), LMB(X), GRB(X),
ARB(X), NRB(X), LRB(X)
S1

S1
NC

NC

S2

S2

5/10K

S3

S3

NO

NO

S4

S1A

NC

S5

Potentiometer

S6

Auxiliary Switch

NO

S2A

800-543-9038 USA

26

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

W224_A_11

Auxiliary Switch Wiring

Interface Wiring Detail


SYx-MFT, 24V, 120/230V

Actuators: SYx-MFT

Notes:
1. Motor CAMS have been factory calibrated and should not be moved.
2. An adaption must be performed if any limit switch is adjusted. This will
calibrate the beginning and end stopping points. Press the adaption
button for 3 seconds and release.

INSTALLATION NOTES
CAUTION

Control Signal +
Control Signal FDBK +
FDBK -

MFT Connection

24V

Direction of Rotation
N
H

Control Signal +
Control Signal FDBK +
FDBK -

Adaption

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Adaption

Direction of Rotation

800-543-9038 USA

866-805-7089 CANADA

120/230V

203-791-8396 LATIN AMERICA / CARIBBEAN

27

SYx-P Interface Wiring Detail

LED Open
LED Close

N Power Supply (4)


+ Power Supply (5)
Control Signal (6)
Control Signal (7)

Sensitivity switch setting


is position #3 for factory
default. To widen deadband, select a higher
number (up to 9).

Feedback (11)
Feedback (12)
Sensitivity

VR1
VR2

CAUTION
Dip
Switch
Settings

Notes:
1. Do not change sensitivity or dip switch settings with power applied!
2. VR1 and VR2 are factory calibrated and should not be moved.
3. Motor CAMS have been factory calibrated and should not be moved.

8 7 6 5 4 3 2 1 OFF

8 7 6 5 4 3 2 1 OFF

RESPONSE = DIRECT

INPUT = 2-10 VDC


ON

ON

8 7 6 5 4 3 2 1 OFF

8 7 6 5 4 3 2 1 OFF

RESPONSE = REVERSE

INPUT = 4-20mA
ON

ON

8 7 6 5 4 3 2 1 OFF

INPUT = 1-5 VDC

8 7 6 5 4 3 2 1 OFF

ON

LOSS OF SIGNAL = CLOSED


(Direct Acting)

LOSS OF SIGNAL = OPEN


ON

8 7 6 5 4 3 2 1 OFF

(Reverse Acting)

8 7 6 5 4 3 2 1 OFF

ON

LOSS OF SIGNAL = CLOSED

ON

8 7 6 5 4 3 2 1 OFF

LOSS OF SIGNAL = OPEN


(Direct Acting)

OUTPUT = 4-20mA

(Reverse Acting)

8 7 6 5 4 3 2 1 OFF

OUTPUT = 2-10 VDC


ON

LOSS OF SIGNAL = STOP


ON

WARNING

Potentiometer
(Factory Pre-set)

*On modulating
actuators DO NOT
master/slave using
optional potentiometer.

800-543-9038 USA

28

For 2-position actuators with 1k feedback option


Potentiometer points 1, 2, 3 are wired to terminal blocks 8, 9, 10.
When a valve is closed:
8, 9
1k
9, 10
0k
When a valve is opened:
8, 9
0k
9, 10
1k
For modulating actuators with 1k feedback option*
Potentiometer points 1, 2, 3 are wired to terminal blocks 8, 9, 10.
When a valve is closed:
8, 9
1k
9, 10
0k
When a valve is opened:
8, 9
0k
9, 10
1k

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

INSTALLATION NOTES

Wiring for Damper Actuators and Control Valves

W546_11

On/Off, 24V, 120V or 230V

SY Actuator Wiring Diagram, SY15-24V On/Off


SY112-120V or 230V On/Off

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout


this manual. Read these carefully.

Observe class 1 and class 2 wiring restrictions.

CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.

Transformer sizing = SY actuator draw X 1.25 (safety margin)


(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
3.75A X 24 VAC = 90VA Transformer).

Indicates an action or condition that may cause irreversible


damage to the actuator(s) or associated equipment.
Equipment damage!
Power consumption and input impedance must be observed.

NOTES SY112-120V or 230V


sCaution: Power Supply Voltage
s)SOLATIONRELAYSMUSTBEUSEDINPARALLELCONNECTIONOFMULTIPLEACTUATORS
using a common control signal input.
s(, CANNOTBECONNECTEDTOTERMINALANDSIMULTANEOUSLY
sRequired: 4ERMINALNEEDSTOBEFIELDWIREDTOENABLEHEATERCIRCUIT

NOTES SY15-24
Each actuator should be powered by a single, isolated
33 control transformer.
s)SOLATIONRELAYSMUSTBEUSEDINPARALLELCONNECTIONOFMULTIPLEACTUATORS
using a common control signal input.
s(CANNOTBECONNECTEDTOTERMINALANDSIMULTANEOUSLY
sRequired: 4ERMINALNEEDSTOBEFIELDWIREDTOENABLEHEATERCIRCUIT

33 24V AC/DC Transformer

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Line
Volts

Open

Close

Ground

Common

Open

Closed

Connect to #1 for fully


open indication

Connect to #1 for fully


open indication

Connect to #1 for fully


closed indication

Connect to #1 for fully


closed indication

HTR

7
A

120V or 230V AC/DC


N L1
Open

H L2
Close

HTR

Ground

Common

Open

Closed

LS3

A-C (Open Indication)

A-C (Open Indication)

LS4

LS4

E
F

D-F (Closed Indication)


Contact Rating: 5A 250 VAC Max.

SY25-24

LS3

B
C
E
F

LS3

D-F (Closed Indication)


Contact Rating: 5A 250 VAC Max.

SY212-120V or 230V

LS3

B
A-B (Open Indication)
Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
LS4

A-E (Closed Indication)

SY1-24

A-B (Open Indication)


Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

E
F

LS4

A-E (Closed Indication)

SY1-110 (220)

SY1 Contact Arrangements

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

29

Wiring for Damper Actuators and Control Valves

W547_11

Proportional, 24V, 120V or 230V

SY Actuator Wiring Diagram, SY1-24P and SY1-110P (220P)

Hazard Identification

INSTALLATION NOTES

7ARNINGSAND#AUTIONSAPPEARATAPPROPRIATESECTIONSTHROUGHOUT
this manual. Read these carefully.

/BSERVE#LASSAND#LASSWIRINGRESTRICTIONS

CAUTION

4RANSFORMERSIZING39ACTUATORDRAW8SAFETYMARGIN
%X39 REQUIRES!X! !86!#6!4RANSFORMER

)NDICATESAPOTENTIALLYHAZARDOUSSITUATIONWHICH IFNOTAVOIDED
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.

APPLICATION NOTES

Indicates an action or condition that may cause irreversible


damage to the actuator(s) or associated equipment.
%QUIPMENTDAMAGE
0OWERCONSUMPTIONANDINPUTIMPEDANCEMUSTBEOBSERVED

34

Ground shielded wire at control panel chassis.


Tape back ground at actuator.

36

Use of feedback is optional.

NOTES SY1110P (220P)

NOTES SY124P

sCaution:0OWERSUPPLYVOLTAGE

Each actuator should be powered by a single, isolated


33 control transformer.
s0OWERSUPPLY#OM.EUTRALAND#ONTROL3IGNAL "" wiring to a common is
prohibited. Terminals 4 and 6 need to be wired separately.

s0OWERSUPPLY#OM.EUTRALAND#ONTROL3IGNAL "" wiring to a common is


prohibited. Terminals 4 and 6 need to be wired separately.
s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITHPOWERAPPLIED

33 24V AC/DC Transformer

Line
Voltage

Control signal
34

Ground

Power Supply Com

Power Supply Hot

Control Signal (-)

Control Signal (+)

Ground

N L1

Power Supply Com

H L2

Power Supply Hot

Control Signal (-)

Control Signal (+)

Internal Use Only

Internal Use Only

120 or 230 VAC

Internal Use Only

Internal Use Only

Control signal
34

10 Internal Use Only

10 Internal Use Only


Feedback

11 Feedback (-)

LS3

12 Feedback (+)

C
E
F

LS3

B
! "/PEN)NDICATION
#ONTACT2ATING !6!#-AX
!6!#-AX
LS4

! %#LOSED)NDICATION

SY1-24P

800-543-9038 USA

11 Feedback (-)

36

36

30

Feedback

12 Feedback (+)

866-805-7089 CANADA

C
E
F

! "/PEN)NDICATION
#ONTACT2ATING !6!#-AX
!6!#-AX
LS4

! %#LOSED)NDICATION

SY1 -110P (220P)

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITHPOWERAPPLIED

Wiring for Damper Actuators and Control Valves

W547_2_11

Proportional, 24V, 120V or 230V

Actuator:

SY25-24MFT

SY2...12-120MFT

SY2...12-230MFT

Hazard Identification

INSTALLATION NOTES

7ARNINGSAND#AUTIONSAPPEARATAPPROPRIATESECTIONSTHROUGHOUT
this manual. Read these carefully.

/BSERVE#LASSAND#LASSWIRINGRESTRICTIONS

CAUTION

4RANSFORMERSIZING39ACTUATORDRAW8SAFETYMARGIN
%X39 REQUIRES!X! !86!#6!4RANSFORMER

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.

APPLICATION NOTES

Indicates an action or condition that may cause irreversible


damage to the actuator(s) or associated equipment.
%QUIPMENTDAMAGE
0OWERCONSUMPTIONANDINPUTIMPEDANCEMUSTBEOBSERVED

NOTES SY2...5-24MFT

34

Ground shielded wire at control panel chassis.


Tape back ground at actuator.

36

Use of feedback is optional.

NOTES SY2...12-120MFT (230MFT)

Each actuator should be powered by a single, isolated


33
control transformer.

sCaution:0OWERSUPPLYVOLTAGE

s0OWERSUPPLY#OM.EUTRALAND#ONTROL3IGNAL "" wiring to a common is


prohibited.

PC Tool
Service Jack

Control Signal

Feedback

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

36

34

Control Signal (+)

Control Signal (-)

Feedback Signal (+)

U5

Feedback Signal (-)

Not Used -

C1

Not Used -

C2

Internal Use Only

Internal Use Only

Internal Use Only

Internal Use Only

Internal Use Only

/-

Power Supply Com

~/+

Power Supply Hot

Internal Use Only

Internal Use Only

10

Internal Use Only

24V AC/DC

Address

33
Adaption

Y2

SYx-24MFT

Y1

PE

Power Supply Com 120v (N) / 230v (L1)


Power Supply Hot 120v (H) / 230v (L2)

Control Signal

Feedback

36
34

PC Tool
Service Jack

Internal Use Only

Internal Use Only

Control Signal (-)

Internal Use Only

Feedback Signal (+)

U5

Internal Use Only

Feedback Signal (-)

Not Used -

C1

Not Used -

C2

Internal Use Only

Internal Use Only

10

Internal Use Only

Adaption

Address

LS3

Internal Use Only

Control Signal (+)

Y1

SYx-120MFT
SYx-230MFT

! "/PEN)NDICATION
#ONTACT2ATING !6!#-AX
!6!#-AX

Y2

PE

LS4

! %#LOSED)NDICATION

SY2...5-24MFT
SY2...12-120MFT
(230MFT)

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

31

Wiring for Damper Actuators and Control Valves

W549_11

On/Off, 24V, 120 or 230V

SY Actuator Wiring Diagram, SY15-24 Multiple Wiring


SY112-110 (220) Multiple Wiring

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate sections throughout this


manual. Read these carefully.

Observe class 1 and class 2 wiring restrictions.

CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.

Transformer sizing = SY actuator draw X 1.25 (safety margin)


(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
3.75A X 24 VAC = 90VA Transformer).

Indicates an action or condition that may cause irreversible damage to the


actuator(s) or associated equipment.
Equipment damage!
Power consumption and input impedance must be observed.

Line
Voltage

Open

K1

Close

K1-B

Actuator B

Ground

Common

120 or 230 VAC


N L1
Open

Open

4
5
6

Closed

7
A

K1-B

HTR

Common

Open

Closed

5
6
7
A

LS3

A-C (Open Indication)

LS4

Actuator A

Ground

Common
Open

Closed

Closed

5
6
HTR

A-C (Open Indication)

C
E
F

A-B (Open Indication)


Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

LS4

A-E (Closed Indication)

SY1 -24

LS3
A-C (Open Indication)

LS4

E
D-F (Closed Indication)
Contact Rating: 5A 250 VAC Max.

SY25-24

D-F (Closed Indication)


Contact Rating: 5A 250 VAC Max.

SY212-110 (220)

A-B (Open Indication)


Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

LS4

HTR

E
F

7
A

LS3

Actuator A

K1-A

Ground

LS3

Common

Open

LS3

SY212-110 (220)

LS4
D-F (Closed Indication)

K1-A

* The isolation relays may not be needed.


Dependent on signal

LS3
A-C (Open Indication)

Contact Rating: 5A 250 VAC Max.

SY25-24

HTR

E
D-F (Closed Indication)
Contact Rating: 5A 250 VAC Max.

Actuator B

Ground

K1

H L2
Close

LS4

A-E (Closed Indication)

SY1-110 (220)

SY1 Contact Arrangements

800-543-9038 USA

32

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

24V AC Transformer

NOTES
sCaution: Power Supply Voltage.
s)SOLATIONRELAYSMUSTBEUSEDINPARALLELCONNECTIONOFMULTIPLEACTUATORS
using a common control signal input.
s(, CANNOTBECONNECTEDTOTERMINALANDSIMULTANEOUSLY
sRequired: 4ERMINALNEEDSTOBEFIELDWIREDTOENABLEHEATERCIRCUIT

Wiring for Control Valves

W550_11

Proportional, 24V

SY Actuator Wiring Diagram, SY1-24P Multiple Wiring

Hazard Identification
Warnings and Cautions appear at appropriate
sections throughout this manual. Read these carefully.

33

24V AC/DC Transformer

Line
Voltage

CAUTION
Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.

35

Indicates an action or condition that may cause


irreversible damage to the actuator(s) or
associated equipment.

Actuator B

Ground

Power Supply Com

Power Supply Hot

Control Signal (-)

Control Signal (+)

Internal Use Only

Internal Use Only

10 Internal Use Only


Feedback (B)

Equipment damage!
Power consumption and input impedance
must be observed.

11 Feedback (-)
12 Feedback (+)

36

LS3

B
C

A-B (Open Indication)


Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

INSTALLATION NOTES

Observe class 1 and class 2 wiring restrictions.


Transformer sizing = SY actuator draw X 1.25 (safety margin)
(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
3.75A X 24 VAC = 90VA Transformer).

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

NOTES SY1-24P
Each actuator should be powered by a single, isolated
33 control transformer.

33 24V AC/DC Transformer

Line
Voltage

35

s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITH
power applied.

Actuator A

Ground

Power Supply Com

Power Supply Hot

Control Signal (-)

Control Signal (+)

Internal Use Only

Internal Use Only

10 Internal Use Only


Control Signal

APPLICATION NOTES

Feedback (A)

11 Feedback (-)
12 Feedback (+)

36

36

A-E (Closed Indication)

SY1 -24P

sSY1-24P notes: Power supply Com/Neutral and Control Signal


"" wiring to a common is prohibited. Terminals 4 and 6 need to
be wired separately otherwise irreversible damage will occur.

35

LS4

Recommended twisted shielded pair for control wiring.


Ground shielded wire at control panel chassis.
Tape back ground at actuator.

LS3

B
C
E

Use of feedback is optional.

A-B (Open Indication)


Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
LS4

A-E (Closed Indication)

SY1 -24P

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

33

Wiring for Control Valves

Actuators: SY2...5-24MFT

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate


sections throughout this manual. Read these carefully.

Observe class 1 and class 2 wiring restrictions.

CAUTION

Transformer sizing = SY actuator draw X 1.25 (safety margin)


(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
3.75A X 24 VAC = 90VA Transformer).

Indicates a potentially hazardous situation which, if


not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.

NOTES SY2...5-24MFT

Indicates an action or condition that may cause


irreversible damage to the actuator(s) or
associated equipment.

Each actuator should be powered by a single, isolated


33 control transformer.

Equipment damage!
Power consumption and input impedance
must be observed.

APPLICATION NOTES
35

Recommended twisted shielded pair for control wiring.


Ground shielded wire at control panel chassis.
Tape back ground at actuator.

36

Use of feedback is optional.

Actuator A

PC Tool
Service Jack

Feedback
36
35

Feedback
36
35

Power Supply Com

~/+

Power Supply Hot

Internal Use Only

Feedback Signal (+)

U5

Feedback Signal (-)

Not Used -

C1

Not Used -

C2

24V AC/DC

Address

33

Adaption

Control Signal (+)

Control Signal (-)

Feedback Signal (+)

U5

Feedback Signal (-)

SYx-24MFT

Y2

Internal Use Only

10

Internal Use Only

Internal Use Only

Internal Use Only

Internal Use Only

Internal Use Only

Internal Use Only

/-

Power Supply Com

Not Used -

C1

Not Used -

C2

~/+

Power Supply Hot

Internal Use Only

Internal Use Only

10

Internal Use Only

Address

Y2

24V AC/DC

33

Adaption

Y1

Internal Use Only

C
LS4

Internal Use Only

PE

Control Signal

Control Signal (-)

PC Tool
Service Jack

A-C (Open Indication)

Internal Use Only

/-

Actuator B

LS3

Internal Use Only

Internal Use Only

Control Signal (+)

Y1

SYx-24MFT

PE

E
D-F (Closed Indication)

Contact Rating: 5A 250 VAC Max.

SY25-24MFT

800-543-9038 USA

34

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

W550_2_11

Proportional, Multiple Wiring, 24V

Wiring for Control Valves

W552_1_11

Proportional, 120 or 230V

Actuators: SY1-110P

SY1-220P

Actuator B

Ground

N L1

Power Supply Com

H L2

Power Supply Hot

CAUTION

Control Signal (-)

Indicates a potentially hazardous situation which, if


not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.

Control Signal (+)

Internal Use Only

Internal Use Only

Hazard Identification
Warnings and Cautions appear at appropriate
sections throughout this manual. Read these carefully.

120 or 230 VAC

35

10 Internal Use Only

Indicates an action or condition that may cause


irreversible damage to the actuator(s) or
associated equipment.

11 Feedback (-)

Feedback (B)

12 Feedback (+)

36

Equipment damage!
Power consumption and input impedance
must be observed.

LS3

B
C

A-B (Open Indication)


Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

E
F

INSTALLATION NOTES

LS4

A-E (Closed Indication)

SY1 -110P (220P)

Observe class 1 and class 2 wiring restrictions.

APPLICATION NOTES

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

35

36

Recommended twisted shielded pair for control wiring.


Ground shielded wire at control panel chassis.
Tape back ground at actuator.
Use of feedback is optional.

Control Signal
35

NOTES SY1-110P (220P)

Actuator A

Ground

Power Supply Com

Power Supply Hot

Control Signal (-)

Control Signal (+)

Internal Use Only

Internal Use Only

10 Internal Use Only

sCaution: Power supply voltage.

Feedback (A)

s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITH
power applied.

11 Feedback (-)
12 Feedback (+)

36

LS3

B
C
E
F

A-B (Open Indication)


Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
LS4

A-E (Closed Indication)

SY1 -110P (220P)

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

35

Wiring for Control Valves

W552_2

Proportional, Multiple Wiring, 120/230V

Actuators: SY2...12-120MFT

SY2...12-230MFT

Hazard Identification

INSTALLATION NOTES

Warnings and Cautions appear at appropriate


sections throughout this manual. Read these carefully.

Observe class 1 and class 2 wiring restrictions.

CAUTION
Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.

APPLICATION NOTES
35

Indicates an action or condition that may cause


irreversible damage to the actuator(s) or
associated equipment.

36

Equipment damage!
Power consumption and input impedance
must be observed.

Recommended twisted shielded pair for control wiring.


Ground shielded wire at control panel chassis.
Tape back ground at actuator.
Use of feedback is optional.

NOTES SY2...12-120MFT (230MFT)


sCaution: Power supply voltage.

Power Supply Com 120 VAC (N) / 230 VAC (L1)


Power Supply Hot 120 VAC (H) / 230 VAC (L2)

Internal Use Only

Internal Use Only

Control Signal (-)

Internal Use Only

Feedback Signal (+)

U5

Internal Use Only

Feedback Signal (-)

Not Used -

C1

Not Used -

C2

Internal Use Only

Internal Use Only

10

Internal Use Only

Adaption

Address

Y1

PE

Internal Use Only

Control Signal (+)

36
35

Y2

SYx-120MFT

Actuator A

SYx-230MFT

Power Supply Com 120 VAC (N) / 230 VAC (L1)


Power Supply Hot 120 VAC (H) / 230 VAC (L2)

Control Signal

Feedback

PC Tool
Service Jack

Internal Use Only

Internal Use Only

Internal Use Only

Control Signal (+)

Control Signal (-)

Internal Use Only

Feedback Signal (+)

U5

Internal Use Only

Feedback Signal (-)

Not Used -

C1

Not Used -

C2

Internal Use Only

Internal Use Only

10

Internal Use Only

36
35

LS3

Adaption

Address

B
A-C (Open Indication)

Y1

C
G

PE

Actuator B

SYx-120MFT
SYx-230MFT

Y2

LS4

E
F

D-F (Closed Indication)


Contact Rating: 5A 250 VAC Max.

SY2...12-120MFT
SY2...12-230MFT

800-543-9038 USA

36

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Feedback

PC Tool
Service Jack

Wiring for Control Valves


On/Off, 24V, 120V

Actuators:

ZONE 24NC
ZONE120NC-S

ZONE24NO
ZONE24NC-S
ZONE120NO-S

ZONE24NO-S

ZONE120NC

ZONE120NO

T-STAT
L1(HOT)
MOTOR

L2

Motor Lead Color

24
120/230
Black
Black

Red

Red

TO AUXILIARY
CIRCUIT

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Built-in Auxiliary Switch (optional) (-S models)

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

37

W610_11

Wiring Diagrams for Fire and Smoke Damper Actuators

Actuators:

FSLF120(-S) US
FSAF24(-S) US

FSLF24(-S) US

FSNF120(-S) US

FSNF24(-S) US

FSAF120(-S) US

INSTALLATION NOTES

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.

Actuators may also be powered by 24 VDC.

CAUTION

13

Two built-in auxiliary switches (2xSPDT), for end position


indication, interlock control, fan startup, etc.

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.

21

Provide overload protection and disconnect as required.

39

S4 makes to S6 when the actuator is powered open.

Equipment damage!
Actuators may be connected in parallel. Power consumption
and input impedance must be observed.
Equipment damage!
Actuators may be connected in parallel if not mechanically
linked. Power consumption and input impedance must
be observed.

40

Double insulated.

41

Two built-in auxiliary switches (2xSPST), for end position


indication, interlock control, fan startup, etc.

Wht

APPLICATION NOTES

21

1 Neutral

L1

2 Hot
3 Ground

Meets cULus requirements without the need of an electrical


ground connection.
All
on this page indicates
temperature limit or relay.

Blk

24V 120V
N
C

No ground on 24 V models

FSNF24 US
FSNF120 US

manual reset high

21

24V

120V

C=Blk

N=Wht

1 Common, Neutral

Violet

S1

H=Red

L1=Blk

2 Hot

Violet

S2

41
NC

10

NO

85

3 Ground
No ground for 24V models

FSLF24 US
FSLF120 US

Gray

S4

Gray

S6

39

40

FSLF24-S US
FSLF120-S US

24 VAC Transformer

21

Line

Blk (1) Common

Volts

21

Auxiliary Switch Wiring for FSNF24-S US, FSNF120-S US

N N
L1 H

Red (2) + Hot

FSAF24 US

NC

13

S3
NO

S4
NC

Blk (2) Hot

40

S5
S6

FSAF120 US

800-543-9038 USA

S2
All
White
Tagged

Wht (1) Neutral

120 VAC

38

S1

866-805-7089 CANADA

85
NO

FSNF24-S
FSNF120-S

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Auxiliary Switch Wiring for FSLF24-S US, FSLF120-S US

W611_11

Wiring Diagrams for Fire and Smoke Damper Actuators

Actuators:

FSAF24-BAL (-S) US

FSAF24-SR US

Auxiliary Switch Wiring for FSAF24-BAL-S US,


FSAF24-SR-S US

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.

CAUTION

S1

Indicates a potentially hazardous situation which, if not avoided,


may result in minor or moderate injury. It may also be used to
alert against unsafe practices.

S2

NC

10

13
40

S3
NO

Equipment damage!
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.

S4

Equipment damage!
Actuators may be connected in parallel if not mechanically
linked. Power consumption and input impedance must
be observed.

FSAF24-BAL-S US
FSAF24-SR-S US

NC

S5
S6

30 to 90
NO

Balancing Control Fire and Smoke

APPLICATION NOTES

21

24 VAC Transformer
Blk (1) Common

Line

Meets cULus or UL requirements without the need of an


electrical ground connection.

(3)

INSTALLATION NOTES

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

37

Actuators may also be powered by 24 VDC.

Only connect common neg (-) leg of control circuits.

A 500 resister converts the 4 to 20 mA control signal to


2 to 10 VDC.

13

Two built-in auxiliary switches (2xSPDT), for end position


indication, interlock control, fan startup, etc.

21

Provide overload protection and disconnect as required.

37

Only connect Hot, Wire 2 to Wire 3 override controls.

OVERRIDE CONTROL
See technical
documentation for
typical methods.

Override Open

FSAF24-BAL

Proportional Control Fire and Smoke


21

24 VAC Transformer
Blk (1) Common

Line

40

Red (2) + Hot

Volts

Red (2) + Hot

Volts

Wht (3) Y1 Input, 2 to 10V

()

Control Signal
2 to 10 VDC (+)

Double Insulated

All
on this page indicates
temperature limit or relay.

Grn (5) U Output, 2 to 10V

FSAF24-SR US

manual reset high


21

24 VAC Transformer

Auxiliary Switch Wiring for FSAF24-S US, FSAF120-S US


Line

Blk (1) Common

Volts
Violet
Violet

S1
S2

NC

()

41

4 to 20 mA
Control Signal (+)

10
Gray

S4

Gray

S6

Red (2) + Hot

500
Wht (3) Y1 Input, 2 to 10V

7
NC

NO

30 to 90

FSAF24-S US
FSAF120-S US

800-543-9038 USA

()
2 to 10 VDC
(+)
Feedback Signal
6

Grn (5) U Output, 2 to 10V

FSAF24-SR US

4
866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

39

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Notes

800-543-9038 USA

40

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Notes

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

41

N40067 - 7/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Notes

800-543-9038 USA

42

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

G & O Thermal Supply


5435 N. Northwest Highway
Chicago, IL 60630
Phone: 773-763-1300
With branches in IL

Aireco Supply
9120 Washington Boulevard
Savage, MD 20763-0414
Phone: 301-953-8800
With branches in MD, VA

Industrial Controls Distributors LLC


1776 Bloomsbury Avenue
Wanamassa, NJ 07712
Phone: 800-631-2112
With branches in
GA, KY, IN, MA, ME, NC, NY, OH, PA, TN

Amcon Controls, Inc.


11906 Warfield Street
San Antonio,TX 78216
Phone: 210-349-6161
Houston, TX branch 713-464-7002
Mandeville, LA branch 985-624-3303
Applied Automation
A Wilson Mohr Company
3186 South Washington Street, #230
Salt Lake City, UT 84115
Phone: 801-486-6454
Boston Aircontrols, Inc.
8 Blanchard Road
Burlington, MA 01803
Phone: 781-272-5800
Charles D. Jones Co.
445 Bryant Street, Unit #1
Denver, CO 80204-4800
Phone: 800-777-0910
With branches in CO, MO, KS
Climatic Control Div/ICD
5061 W. State Street
Milwaukee, WI 53208
Phone: 800-242-1656
With branches in WI
Cochrane Supply and Engineering, Inc.
30303 Stephenson Highway
Madison Heights, MI 48071-1633
Phone: 800-482-4894
With branches in MI and Maumee, OH
Columbus Temperature Control
1053 E. 5th Avenue
Columbus, OH 43201
Phone: 800-837-1837
Controlco
985 3rd Street
Oakland, CA 94607
Phone: 510-636-7900
With branches in CA, NV
Control Products
9101 Jameel, Suite 130
Houston, TX 77447
Phone: 713-849-7200
Edward C. Smyers & Co.
223 Fort Pitt Boulevard
Pittsburgh, PA 15222-1505
Phone: 412-471-3222
Engineered Control Systems
4805 N.W. 79th Avenue
Suite 11
Miami, FL 33166
Phone: 305-418-8901
With branches in FL

Interstate HVAC Controls


30 Vineland Street
Brighton, MA 02135
Phone: 617-782-9000
Jackson Controls
1708 E. 10th Street
Indianapolis, IN 46201
Phone: 317-231-2200
M & M Controls
9E West Aylesbury Road
Timonium, MD 21093
Phone: 410-252-1221
With a branch in Alexandria, VA
MICONTROLS, Inc.
6516 5th Place South
Seattle, WA 98124
Phone: 800-877-8026
With branches in WA, OR
Meier Supply
123 Brown Street
Johnson City, NY 13790
Phone: 607-797-7700
With branches in NY, PA
Minvalco, Inc.
3340 Gorham Avenue
Minneapolis, MN 55426-4267
Phone: 952-920-0131
With branches in MN
RSD/Refrigeration Supply Distribution
26021 Atlantic Ocean Drive
Lake Forest, CA 92630
Phone: 949-380-7878
With branches in
CA, NV, OR, AK, AZ, ID, UT, WA, MT
Saint Louis Boiler Supply, Co.
617 Hanley Industrial Court
St. Louis, MO 63144
Phone: 314-962-9242
South Side Control Supply, Co.
488 N. Milwaukee Avenue
Chicago, IL 60610-3923
Phone: 312-226-4900
With branches in IL, IN
Stromquist and Company
4620 Atlanta Road
Smyrna, GA 30080
Phone: 404-794-3440
With a branch in Orlando, FL
Temperature Control Systems
10315 Brockwood Road
Dallas, TX 75238
Phone: 214-343-1444
With branches in OK, TX

Tower Equipment Co., Inc.


1320 West Broad Street
Stratford, CT 06615
Phone: 800-346-4647
Twinco Supply Corporation
55 Craven Street
Huntington Station, NY 11746-2143
Phone: 800-794-3188
With branches in NY
Wilson-Mohr, Inc.
12610 West Airport Blvd, Suite 100
Sugarland, TX 77478
Phone: 281-295-8850
CANADA

ACR Supply Company Inc.


4040 S. Alston Avenue
Durham, NC 27713
Phone: 919-765-8081
With branches in NC

For a complete list of distributors


in Canada, please visit our
website: www.belimo.ca
or call toll free: 866-805-7089

LATIN AMERICA AND THE CARIBBEAN

USA

Belimo Platinum Distributors

For a complete list of distributors


in Latin America and the Caribbean,
please visit our website: www.belimo.us
or call: 203-791-8396

Belimo worldwide: www.belimo.com


BELIMO Americas
USA Locations, 43 Old Ridgebury Road, Danbury, CT 06810
Tel. 800-543-9038, Fax 800-228-8283, marketing@us.belimo.com
1049 Fortunado Loop, Sparks, NV 89436
Tel. 800 987-9042, Fax 800-987-8875, marketing@us.belimo.com
Canada Locations, 14/16 5716 Coopers Avenue, Mississauga, Ontario L4Z 2E8
Tel. 866-805-7089, Fax 905-712-3124, marketing@us.belimo.com
Latin America and the Caribbean Customer Service,
Tel. 203-791-8396, Fax 203-791-9139, marketing@us.belimo.com

Potrebbero piacerti anche