Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
2 ● Trane Engineers Newsletter volume 36–4 providing insights for today’s HVAC system designer
• Controls: Q3: I’m designing a large chilled-
Table 2. 100-year ODP and GWP values for
– Automatic shutdown (systems water system. Can an HFC several common refrigerants
> 15,000 Btu/h) refrigerant automatically achieve EA Refrigerant ODP GWP Application
Credit 4 (one point)? If not, which
– Setback controls in all but the refrigerants can achieve R-22 0.04 1,780 Unitary and
most humid climates EA Credit 4? No man-made chillers
– Optimum start (systems > refrigerant automatically achieves EA R-123 0.02 76 Chillers
10,000 cfm) Credit 4 (EAc4), Enhanced Refrigerant
R-134a ~0 1,320 Chillers
Management. EAc4 changed
• Construction and insulation: duct substantially between LEED-NC R-407C 1,700 Unitary
and piping insulation requirements versions 2.1 and 2.2.
R-410A 1,890 Unitary and
• Completion requirements: chillers
drawings, manuals, balancing, and To achieve this credit, one can either
use no refrigerants, or perform a Table 3 shows the maximum
commissioning
calculation using the properties and refrigerant charge (Rc) that would allow
Prescriptive requirements quantities of the refrigerants used in a piece of equipment to achieve EAc4.
the equipment. Attaining EAc4 These values are determined by
• Economizers: specified by system performing the calculation using the
depends on refrigerant global warming
size and climate zone refrigerant properties and defaults for
potential, refrigerant ozone depletion
• Simultaneous heating and cooling potential, annual leakage rate, and each refrigerant.
limitation: with exceptions for equipment life. Defaults are defined by Table 3. Maximum refrigerant charge (lb/ton)
variable-air-volume (VAV) systems, the LEED NC 2.2 Reference Guide. allowable based on equipment life
use of recovered energy, and Refrigerant 10 years 15 years 20 years 23 years
humidity control The equation, variable definitions and
defaults are provided below. The R-22 0.57 0.64 0.69 0.71
• Air-system design and control: calculation can be performed using a R-123 1.60 1.80 1.92 1.97
maximum fan power usage, fan- spreadsheet available at:
pressure optimization required on www.trane.com/green. *Trane R-123 5.15
VAV systems with direct-digital centrifugal
chiller
controls (DDC), variable-frequency LCGWI d + LCOD I × 10 ≤ 100
5
models
drives (VFD), or similar CVHE,CVHF,
performance, required on VAV fans GWP r × R c × ( L r × life + M r ) CVHG,CDHF
LCGWI d = ------------------------------------------------------------------------
-
15 hp and larger life
R-134a 2.52 2.80 3.03 3.10
• Hydronic system design and ODP r × R c × ( L r × life + M r )
LCODI = ----------------------------------------------------------------------
- R-407C 1.95 2.20 2.35 2.41
control: requires variable flow in life
many systems R-410A 1.76 1.98 2.11 2.17
where,
• Heat rejection equipment: requires Higher efficiency equipment generally
LCGWId = life-cycle direct global warming
fan speed reduction for 7.5 hp and index, equivalent lb CO2 /ton-yr uses larger heat exchangers and
above LCODI = life-cycle ozone depletion index, requires a larger refrigerant charge for
equivalent lb CFC-11/ton-yr a given capacity. While calculations
• Energy recovery: GWPr = global warming potential of should always be performed, below is
refrigerant, 0 < GWPr < 12,000 lb
– Airside systems (>5,000 cfm of CO2 /lbr
some general guidance if only one type
supply air and >70% outdoor Rc = refrigerant charge, lb refrigerant/ of refrigerant is used on a project.
air) require energy recovery ton of cooling capacity
• R-22 equipment is unlikely to
effectiveness of 50%. Lr = refrigerant leakage rate, % of
charge/yr (proposed default: 2%) achieve EAc4
– Waterside systems require to life = equipment life, yr
• High-efficiency R-410A equipment
recover heat from water-cooled 10: Window air conditioning units
and heat pumps may not achieve EAc4
chiller's condenser when all of
15: Unitary, split, and packaged
the following are met: • High-efficiency R-134a equipment
air-conditioning units and heat
pumps may not achieve EAc4
– Operates 24 hours per day
20: Reciprocating and scroll • *Due to being able to use a 0.5%
– Heat rejection load is greater chillers
leakage rate, all Trane R-123 chillers
than 6,000,000 Btu/h (450 23: Centrifugal, absorption, and
helical-rotary (screw) chillers can achieve EAc4. (See the CIR
ton plant) issued by the USGBC in 2006 that
Mr = end-of-life loss, % of charge
– Design service water (proposed default: 10%) allows use of this lower leakage
ODPr = ozone depletion potential of rate for these specific chillers.)
heating load is 1,000,000
refrigerant, 0 < ODPr < 0.2 lb
. Btu/h CFC-11/lbr
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 36–4 ● 3
If there is more than one piece of In addition, drier air often allows the the temperature in each zone
equipment in a project, a weighted space temperature setpoints to be reaches occupied setpoint just in
equation may be used: raised. For example, the space time for occupancy. Optimal stop
temperature setpoint can often be uses the BAS to determine how
raised to 76°F or 77°F and still provide early heating and cooling can be
5
[ Σ ( LCGWP + LCODP × 10 ) × Q unit ] the same comfort level as a shut off for each zone, so that the
------------------------------------------------------------------------------------------------ ≤ 100
Q total
conventional system with a 75°F indoor temperature drifts only a
where, setpoint (see Trane ENEWS-29/2, Cold few degrees from occupied
LCGWP = LCGWId Air makes Good $ense). setpoint.
LCODP = LCODI
Qunit = cooling capacity of an individual • Supply-air-temperature reset
Exhaust-air energy recovery (using an
HVAC or refrigeration unit, tons should be used wisely, especially in
Qtotal = total cooling capacity of all HVAC or enthalpy wheel, for example) reduces
a VAV system. Humidity control
refrigeration equipment, tons the ventilation load on cooling and
must be maintained and a
heating equipment. However, be sure
comparison between fan and
In summary, EAc4 can be achieved if to control the wheel properly and
compressor energy use must be
no refrigerant is used. If refrigerant is bypass the wheel when the airside
performed.
used, a calculation must be performed economizer is activated (see Trane
(no refrigerant gets a free pass). If the ENEWS-29/5, Air-to-Air Energy • Ventilation optimization reduces
calculated result is < 100, EAc4 is Recovery). the amount of outdoor air during
achieved for the project. Using the periods of partial occupancy
weighted calculation may allow a Control strategies. (demand-controlled ventilation) and
project with varied equipment (and during times when system
refrigerants, including R-22) attain • Optimal start: required by ASHRAE ventilation efficiency is higher in a
EAc4. Standard 90.1-2004 for systems VAV system (ventilation reset).
larger than 10,000 cfm, optimal
start uses a building automation Trane EN35-4, Energy-Saving Control
Q4: I am designing a commercial system (BAS) to determine the Strategies for Rooftop VAV Systems,
building targeted for LEED gold length of time required to bring further describes these optimized
rating. What are some practices for each zone from current control strategies, and suggests a
airside and waterside HVAC systems temperature to the occupied significant potential for energy savings
that help reduce overall building setpoint. The system waits as long (Figure 2).
energy cost in order to achieve EAc1 as possible before starting, so that
(optimize energy performance)
points? To minimize overall building Figure 1. Comparison of conventional and low-flow, high-efficiency systems
energy cost, design teams should use
100
a holistic approach that considers the
interaction of building orientation and
envelope construction with lighting and 95
HVAC systems. Improvements to the
building envelope and more efficient 90
% of HVAC energy consumption
4 ● Trane Engineers Newsletter volume 36–4 providing insights for today’s HVAC system designer
Figure 2. Demand and peak consumption • Consider a VFD on the chiller if the Example:
reduction chiller will operate for enough A 20-ton cooling load (as part of a
100 hours of the year at low load larger system) where the condenser
HVAC energy consumption, % of base
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 36–4 ● 5
difference between the humidity ratio Q7: I'm designing an underfloor air resulting from application of the IAQP
entering and leaving the coil. distribution (UFAD) system. With can be expected to vary more widely
LEED-NC v2.1, I could achieve one than those resulting from the
• Humidity ratio difference:
EQc2 point (ventilation application of the VRP. For this reason,
0.0112 - 0.0087 = 0.0025 lb of
effectiveness). Why can't I EQp1 only allows the VRP to be used.
water/lb of dry air
automatically get this credit
• Moisture removed by coil: anymore? Earlier versions of EAc2 Q9: I usually specify "high-efficiency,
(6,100 ft3/min x 0.075 lb/ft3) x attempted to improve breathing zone throw-away filters" with a 35
0.0025 lb of water/lb of dry air = air quality by requiring a minimum zone percent dust-spot efficiency rating.
(1.14 lb of water/min) / (8.33 lb/ air change effectiveness of 0.9. Do these high-efficiency filters
gallon) = 0.14 gpm or 8.24 gallons/ However, the credit didn't have the qualify for EQc5.1 (indoor chemical
hour desired result for two reasons. First, & pollutant source control) credit?
most overhead cooling systems have
Note: The density of air is dependent zone air distribution effectiveness of No. ASHRAE publishes two particle-
on pressure (i.e., elevation) and 1.0 (because cool air drops into the filter test methods: Standard 52.1
temperature. Using the density of breathing zone) so most conventional which results in a dust-spot efficiency
standard air (0.075 lb/ft3) is usually systems could receive this credit, not value, and Standard 52.2 which results
sufficient for most applications. just UFAD or displacement ventilation in a minimum efficiency reporting value
systems. Second, ASHRAE Standard (MERV). Although there is not a one-to-
In the preceding example, 25 percent
62.1 (required by EQ Prerequisite 1) one comparison between the two
of the cooling tower make-up water
requires the designer to account for tests and associated results, a throw-
can be supplied by recovering
zone air distribution effectiveness (Ez) away filter with a 35 percent dust-spot
condensate from the cooling coil. Note
and increase zone airflow accordingly (per Standard 52.1) efficiency would
that these savings are at design
for minimum IAQ.[5] In LEED-NC likely exhibit a minimum efficiency
conditions. The overall water savings
version 2.2, EQc2 was changed to reporting value (from Standard 52.2) of
will vary depending on the application
require a 30 percent increase in about MERV 8. EQc5.1 requires at
and the annual weather conditions.
minimum outdoor airflow to more least MERV 13 filters. If you want to
Trane’s TRACE™ 700 software
directly improve indoor air quality. meet the filtration requirement for this
provides monthly values for cooling
tower make-up water. credit, you should specify filters that
Q8: I like air cleaners. Why can't I get have been tested in accordance with
any LEED-NC credits when I use the Standard 52.2 requirements and that
Q6: I'm designing a VAV system for a
indoor air quality procedure (IAQP) have achieved a MERV of at least 13.
school. Does LEED-NC v2.2, EQc1
— a valid approach for complying Filters with at least 80 percent dust-
(outdoor air delivery monitoring)
with ASHRAE Standard 62.1 —to spot efficiency often achieve MERV 13.
require a CO2 sensor in every
determine the minimum required
room? No. EQc1 requires a CO2
outdoor air intake flow? The Q10: I’m a mechanical contractor
sensor to indirectly monitor the
ventilation rate procedure (VRP) is working on the required
ventilation rate per person in densely-
prescriptive in nature. Minimum zone documentation for a LEED
occupied zones (those zones designed
outdoor airflow rates are prescribed for submittal. Can Trane help fill out the
for 25 or more people per 1000 ft2). For
each occupancy category, along with MRc4.1 and MRc4.2 forms regarding
systems that serve zones that are not
specific calculation procedures to find the percent of recycled content used
densely occupied, EQc1 requires direct
system-level intake airflow for various in the HVAC equipment? How about
monitoring of the outdoor airflow rate.
ventilation system types. The designer the MRc5.1 and MRc5.2 forms
Using an airflow measurement station
need only make "judgments" related to regarding the use of regional
is one example. If one air handler
zone population density and materials? How about the EQc4.1
serves both densely occupied and non-
distribution. The IAQP, on the other and EQc4.2 forms regarding the use
densely occupied zones, the densely
hand, is performance-based. It requires of low-emitting materials (such as
occupied zones require CO2
the designer to make many judgments adhesives, sealants, paints, and
monitoring and the air handler requires
including identification of coating) on HVAC equipment? The
a means to directly measure outdoor
contaminants-of-concern (CC), the LEED-NC rating system explicitly
airflow at the intake. Whether
sources of each CC, the combined states that "mechanical, electrical and
monitoring CO2, intake airflow, or both,
source strength for each CC, target plumbing components … shall not be
the system must be configured to
concentration for each CC, and so on. included" in the calculations for
generate an alarm when the monitored
Considering the number and nature of recycled content (MRc4.1 and MRc4.2)
condition varies from the currently
judgments involved, the design or the calculations for regional
required ventilation rate by more than
outcomes (in terms of intake airflow) materials (MRc5.1 and MRc5.2).
10 percent .
6 ● Trane Engineers Newsletter volume 36–4 providing insights for today’s HVAC system designer
For EQc4.1 and EQc4.2 (low-emitting greenhouse gas emissions by a
materials), the rating system states collective average of 5% below their
that adhesives, sealants, paint, or 1990 levels.[8] References.
coatings that are "used on the interior
of the building (defined as inside of the The Clinton Climate Initiative, part of [1] "USGBC Unveils 8 Climate Actions", press
weatherproofing system and applied the former President Clinton's release, November 15, 2006 [online; cited 19
Foundation, created a global Energy Oct 2007] <https://www.usgbc.org/News/
on-site)" shall comply with the
PressReleaseDetails.aspx?ID=2941>
requirements listed in these two Efficiency Building Retrofit Program
credits. Mechanical and electrical to upgrade existing buildings through [2] "Energy Performance Requirements within
systems normally have these available funding and technologies LEED Green Building Rating System to
components applied before leaving the for 40 large cities in the world. Increase", press release, June 26 2007 [online;
President Clinton said in the cited 19 Oct 2007] <http://www.usgbc.org/
factory (rather than on-site), so they are News/PressReleaseDetails.aspx?ID=3217>
excluded from these requirements. program's inauguration, "The
However, insulation materials that are businesses, banks and cities [3] Bahnfleth and Peyer. "Comparative Analysis of
applied on-site will need to meet these partnering with my foundation are Variable and Constant Primary-Flow Chilled-
addressing the issue of global Water-Plant Performance", HVAC Engineering,
requirements.
April 2001
warming because it's the right thing
to do, but also because it's good for [4] CoolTools Chilled Water Plant Design Guide.
their bottom line. They're going to pp. 6.30-31.
save money, make money, create www.hvacexchange.com/cooltools
A Collaborative Effort jobs and have a tremendous
[5] Taylor, "LEED® and Standard 62.1", ASHRAE
collective impact on climate change
Governments and the building industry Journal, September 2005
all at once…"[9]
are collaborating to set examples and
[6] Mazria AIA, The 2030 Challenge, Architecture
policies for sustainable building In California, the seventh largest 2030. [online; cited 19 Oct 2007] <http://
practices. Here are a few examples: economy in the world, Governor www.architecture2030.org/2030_challenge/
index.html>
Schwarzenegger is leading by
Edward Mazria, founder and
example to protect the environment. [7] "Sustainable Buildings Standard to Define
executive director of Architecture
The Global Warming Solutions Act of Green Buildings," press release, May 25, 2007
2030, initiated the 2030 Challenge to
2006 requires carbon emissions ASHRAE. [online; cited 19 Oct 2007] <http://
dramatically reduce greenhouse gas www.ashrae.org/pressroom/detail/16309>
reduction to 1990 levels by the year
emission of new buildings to carbon-
2020, and 80 percent reduction from
neutral by 2030. Organizations such [8] Kyoto Protocol, United Nations Framework
1990 emissions level by 2050.[10] Convention on Climate Change [online; cited
as the U.S. DOE, U.S. EPA, U.S.
19 Oct 2007] <http://unfccc.int/
conference of Mayors, USGBC, AIA, Through these collaborative efforts to kyoto_protocol/items/2830.php>
ASHRAE, and IESNA, academics, build green, the future of the
and other countries have joined the sustainable built environment will [9] Clinton Climate Initiative, Clinton Foundation
challenge.[6] [online; cited 19 Oct 2007] <http://
accelerate. LEED continues to be an www.clintonfoundation.org/cf-pgm-cci-
important topic for HVAC system home.htm>
ASHRAE Standard 189P, Standard for
designers. Although many products
the Design of High-Performance [10] "Governor Schwarzenegger Gives Address at
and systems often claim to guarantee
Green Buildings Except Low-Rise United Nations on Climate Change", press
LEED points, this is rarely the case.
Residential Buildings, is being release, September 24, 2007 [online; cited 19
More accurately, products may help Oct 2007] < http://gov.ca.gov/index.php?/
developed through the joint efforts
designers to achieve points. The best press-release/7532/>
of ASHRAE, IESNA, and USGBC,
way to assure that the right decisions
and will be the first of its kind in the
are made is to keep up-to-date on the
United States. Upon written
LEED rating system. We welcome
completion in code language,
more questions from designers as
Standard 189P will be an ANSI-
these will help us generate the next
accredited standard that can be
top ten questions on LEED.
incorporated into building code.[7]
By Chris Hsieh, LEED AP, systems engineer and
On the international front, the Kyoto
Jeanne Harshaw, information designer, Trane.
protocol has been ratified by many
You can find this and previous issues of the
countries and became effective on
Engineers Newsletter at www.trane.com/
February 16, 2005. By 2012,
engineersnewsletter. To comment, e-mail us at
developed countries (listed under
comfort@trane.com
Annex I) are required to reduce their
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 36–4 ● 7
TRACE
TRACE 700
Join Trane in celebrating 35 years of TRACE™.
Introduced into the HVAC industry in 1972, the HVAC
design and analysis program was the first of its
kind and quickly became a de facto industry standard.
It continues to grow with the industry meeting requirements
for ASHRAE Standard 140*, ASHRAE 90.1, and LEED®
Green Building Rating System and recently approved
35 1 9 7 2
—
by the IRS to certify energy savings for building owners. 2 0 0 7
Find out more, visit www.trane.com
*ASHRAE Standard 140, Standard Method of Test for Evaluation of Building Energy Analysis Computer Programs.
For more information, contact your local Trane Trane believes the facts and suggestions presented here to be accurate. However, final design and
office or e-mail us at comfort@trane.com application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.