Overfluxing (V/Hz)
ANSI code 24
Description
Protection which detects overfluxing of transformer or generator magnetic circuits by
calculating the ratio between the greatest phase-to-neutral or phase-to-phase
voltage divided by the frequency.
Overfluxing of magnetic circuits is caused by machine operation with excessive
voltage or insufficient frequency. It provokes saturation of the magnetic materials and
results in temperature rise. In severe cases, a major leakage flux may occur and
seriously damage the materials around the magnetic circuit.
The protection function picks up when the U/f or V/f ratio, depending on machine
coupling, exceeds the set point. The function is delayed (definite time (DT) or IDMT)
according to three curves (see tripping curve equation on page 226).
The typical tripping set point is 1.05 pu.
Block diagram
DE51541
Machine coupling
This setting adapts the function voltage measurement to the coupling of the magnetic
circuit, depending on the measurements made possible by Sepam wiring.
Voltage used by the protection function
92
VT wiring
Delta coupling
3V
2
2U + V 0 2U
2
1U + V 0 1U
2
1V + V 0
1
1V
1
Star coupling
SEPED303001EN - 01/2013
Protection functions
Overfluxing (V / Hz)
ANSI code 24
DE50718
Characteristics
Settings
Machine coupling
Setting range
Tripping curve
Setting range
Gs set point
Setting range
Accuracy (1)
Resolution
Drop out/pick up ratio
Time delay T (operation time at 2 pu)
Definite time
Setting range
Accuracy (1)
IDMT
Setting range
Accuracy (1)
Resolution
Characteristic
Delta / star
Definite time
IDMT: type A, type B, type C
1.03 to 2.0 pu (2)
2 %
0.01 pu (2)
98 % 1 %
0.1 to 20000 s
2 % or from -10 ms to +25 ms
0.1 to 1250 s
5 % or from -10 ms to +25 ms
10 ms or 1 digit
times (1)
Operation time
Overshoot time
Reset time
Inputs
Designation
Protection reset
Protection inhibition
Syntax
Equations Logipam
P24_x_101 b
b
P24_x_113 b
b
Outputs
Designation
Syntax
Instantaneous output (pick-up)
P24_x_1
Delayed output
P24_x_3
Protection inhibited
P24_x_16
x: unit number.
(1) Under reference conditions (IEC 60255-6).
(2) 1 pu represents 1 x Gn.
Equations
b
b
b
Logipam
b
b
b
Matrix
b
Example 2. transformer
DE50662
A transformer is generally protected by an IDMT set point, set to 1.05 Gn with a long
delay.
For example: type C curve, Gs = 1.05 and T = 4 s.
SEPED303001EN - 01/2013
93
Protection functions
General
Tripping curves
Curve type
Coefficient values
k
0.14
0.02
13.5
1
120
1
80
2
315.2
2.5
Standard inverse / A
Very inverse / B
Long time inverse / B
Extremely inverse / C
Ultra inverse
k
T
t d ( I ) = -------------------- --
---I- 1
I s
RI curve
Equation:
2.97
1.50
13.33
0.808
1
1
T
t d ( I ) = ----------------------------------------------------- -----------------I 1 3.1706
IEEE curves
Equation
Curve type
Coefficient values
A
B
0.010
0.023
3.922
0.098
5.64
0.0243
Moderately inverse
Very inverse
Extremely inverse
T
A
t d ( I ) = ---------------------- + B --p
I
- 1
--
I
0.241
0.138
0.081
p
0.02
2
2
IAC curves
Equation
Curve type
Inverse
Very inverse
Extremely inverse
Coefficient values
A
B
0.208
0.863
0.090
0.795
0.004
0.638
C
0.800
0.100
0.620
D
-0.418
-1.288
1.787
E
0.195
7.958
0.246
0.297
0.165
0.092
T
B
E
D
t d ( I ) = A + ------------------- + ---------------------- + ---------------------- x ----2
3
I
---- C ---I- C
---I- C
I
I
I
s
s
T
t d ( V ) = --------------------V
1 ------
V s
T
t d ( V ) = ---------------------V
------ 1
V
s
1
t d ( G ) = ------------------------- x T
p
G
------ 1
G
Curve type
A
B
C
p
0.5
1
2
226
SEPED303001EN - 01/2013