This article aims to diagnose, analyze, propose suggestions and focus studies and
possible solutions regarding the electrical medium voltage Federal University of Mato
Grosso. Comment about cabins and medium voltage transformer substations installed
present measurements performed on the 13.8 kV substations, and relate to their rated
power. Also know the actual monthly expenses with electricity consumption, relate their
real energy demand measured by the concessionaire with the processing equipment
installed on campus, identify actions that can be taken to minimize expenditures for the
incorrect sizing of transformers and rank all the factors that contributed to the designs
of existing cabins. The approach of the methodology was carried out through the
characterization of the area being studied: with on-site visit, photos, interviews with
UFMTs engineers; analysis of the designs and plans of situation; inspection booths
strength; diagnostic measurements of the electrical power with field survey, power
transformers in the existing transformer stations and cabins; lifting record accounts of
the Federal University of Mato Grosso (FUFMT), to data from the energy distribution.
For measuring the cabins were used equipment analyzers energy meters are devices
that universal quantities that have mass memory for recording of measurements for
certain periods. Thus, conceptualize and analyze the processes involved from the
planning to the use of high power transformers, with positives and negatives of the
situation is that the plant medium voltage UFMT show which types of loss in the use of
transformers the empty and full load and recommend improvements for the primary
processing units so there is system reliability.