Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
PAGE 1 OF 11
REV 1
1. Introduction:
This document presents a report on cable sizing calculation for the Ras Tanura Intigrated Project.
The design calculation aims at appropriate selection of cables considering the installation conditions,
ambient temperature, group de-rating and short circuit withstand. The cable sizes and the maximum
cable lengths are calculated based on continuous current rating, ensuring voltage drop is within
permissible limits and are checked for thermal short circuit capacity. Cable selection charts have been
prepared and are annexed for reference.
3. References :
XXXX
XXXX
A554-K-299-EL-DWG-EA1-001
4. Specification Requirements:
As per clause 10.1.1 of A554-K-PRG-EL-GEN-PHL-005
The voltage at any point on the RTIP system will normally remain within the nominal values as
stated below, unless abnormal conditions prevail. Under exceptional circumstances, the maximum
over voltage limits stated below should not be exceeded for more than 30 minutes.
Nominal range
30 min over voltage
+/+
5%
10%
PAGE 2 OF 11
REV 1
5. Basis of Design:
The system design parameters and the site ambient conditions are listed below.
4160 V, 3-phase
480 V, 3-phase,3 Wire
System Frequency
60 Hz
50 C
50kA, 1 sec
Low Voltage
65kA, 1 sec
Allowable voltage drops (starting and running) for LV and MV motors: 15 % and 5%
respectively.
25 mm
2.5 mm
Riyadh Cable data has been used for MV motor feeders and Ducab Cable data has been used
for LV motors.
For Motor details of MV motors ABB ANSI motor catalogue has been used, for LV motors
Brook Crompton ANSI motor catalogue has been used.
PAGE 3 OF 11
REV 1
6. Calculation
These cables are sized to account for the minimum thermal rating required by applying the de-rating
factors based on the laying conditions and the maximum short circuit withstand capability of the cable
has to be chosen greater than 50 kA ( for circuit breaker protected feeders). The maximum feeder length
is guided by the voltage drop calculations.
SIZING CRITERION A
Cables feeding a single motor used in a continuous duty application shall have an ampacity of not
less than Service Factor times the motors full load current rating.
Therefore the cable should be chosen such that the normal ampacity meets this criterion.
FLC
xS .F
DF
(A)
Where,
FLC
S.F
D.F
kW
3xkVxP.Fxefficien cy
(A)
Where,
kW
P.F
PAGE 4 OF 11
REV 1
De-rating Factor
a)
b)
c)
=
=
=
=
=
0.82
0.85
aXb
0.82 X 0.85
0.70.
Now for a 300 HP motor feeder the following calculation demonstrates the selection of cable cross
section based on SIZING CRITERION A:
kW
3xkVxP.Fxefficien cy
(A)
224
3 x 4 x0.84 x.93
Now the cable ampacity required to feed the above motor is calculated as:
Ampacity required =
FLC
xS .F
DF
(A)
41
x1.0
0.70
= 58.57 (A).
2
1R X 3C X 25mm cable has a non de-rated ampacity of 150 (A). This is the minimum cable size
available for MV feeders.
2
Based on the calculations above it can be concluded that 1R X 3C X 25mm cable can feed 300 HP
motor feeder.
PAGE 5 OF 11
REV 1
SIZING CRITERION B
The short circuit withstand capacity of the cable determines the minimum cross section area of the cable
which can be used.
The minimum cross section of the cable
Ix t
K
Where,
A
Ix t
K
Where A is the minimum Area of cross section required for 4.16 kV cable system.
K is the insulation coefficient of XLPE insulated cable = 143.
Then the Minimum Cross Section Area of the cable for 4.16 kV system
= 156.36 mm
50000 x 0.2
143
185 mm being the nearest available standard cross section of cable available is chosen to be the
minimum cross section of the cable.
= 0.005 sec.
PAGE 6 OF 11
REV 1
Ix t
K
Where A is the minimum Area of cross section required for 4.16 kV cable system.
K is the insulation coefficient of XLPE insulated cable = 143.
50000 x 0.005
143
= 24.72 mm
25 mm being the nearest available standard cross section is chosen to be the minimum cross section of
cables for fuse protected motor feeders.
So it can be concluded that for fuse protected feeders all cable sizes can be used and for breaker
2
operated feeders minimum cable size which can be selected is 185 mm .
SIZING CRITERION C
The cable impedence causes a voltage drop at the load terminal, the same needs to be arrested within
the permissible limits. The following checks are performed towards achieving the above. For motor
feeders voltage drop criteria needs to be checked for both running and starting conditions.
Vd running =
(V)
Vd starting =
(V)
Where,
Im
Ilrc
cosr
cosst
Nc
PAGE 7 OF 11
REV 1
The maximum length of cable which can be used maintaining the prescribed voltage drop limits is
calculated as follows:
m running =
m starting =
x1000 (m)
Vd x N C
3 xI m xR cosr X sin r
Vd x N C
3 xI lrc xR cosst X sin st
x1000 (m)
The permissible running and starting voltage drops are 5% and 15% respectively.
2
When feeding a 300 HP motor with 1R X 3C X 25 mm cable the maximum running and starting lengths
are:
mrunning
4000 x5 x 1
x1000
3 x 41x0.927 x0.84 0.146 x0.54 x100
= 3283 m.
mstarting
4000 x15 x 1
x1000
3 x 266 .5 x0.927 x0.22 0.146 x0.975 x100
= 3778 m.
Based on the above calculations it is concluded that a fuse protected 300 HP motor feeder can be fed
2
with a single run of 3 core 25 mm cable to a maximum length of 3283 m satisfying the running and the
starting voltage drops. As suggested above the same cable would not be suitable for feeding the same
motor feeder in the event the feeder is circuit breaker protected.
PAGE 8 OF 11
REV 1
Sizing of 460 volt motor feeder cables shall take into account the following parameters:
a)
b)
These cables are sized to account for the minimum thermal rating required by applying the de-rating
factors based on the laying conditions and the voltage drop limitations.
SIZING CRITERION A
Cables feeding a single motor used in a continuous duty application shall have an ampacity of not less
than Service Factor times the motors full load current rating.
Therefore the cable should be chosen such that the normal ampacity meets this criterion.
FLC
xS .F
DF
(A)
Where,
FLC
S.F
D.F
kW
3xkVxP.Fxefficien cy
(A)
Where,
kW
P.F
De-rating Factor
a)
b)
c)
=
=
=
=
=
0.82
1
aXb
0.82 X 1
0.82.
Now for a 10 HP motor feeder the following calculation demonstrates the selection of cable cross
section based on SIZING CRITERION A:
kW
3xkVxP.Fxefficien cy
(A)
PAGE 9 OF 11
REV 1
7 .5
3 x0.46 x0.84 x.895
Now the cable ampacity required to feed the above motor is calculated as:
Ampacity required =
FLC
xS .F
DF
(A)
12.5
x1.15
0.82
= 17.53 (A).
2
1RX 4CX 2.5 mm cable has a non de-rated ampacity of 33 ampere. This is the minimum cable size
available for LV feeders.
2
Based on the calculations above it can be concluded 1RX 4CX 2.5 mm cable can feed 10 HP motor
feeder.
SIZING CRITERION B
The cable impedence causes a voltage drop at the load terminal, the same needs to be arrested within
the permissible limits. The following checks are performed towards achieving the above. For motor
feeders voltage drop criteria needs to be checked for both running and starting conditions.
Vd running =
(V)
Vd starting =
(V)
Where,
Im
Ilrc
cosr
cosst
Nc
PAGE 10 OF 11
REV 1
The maximum length of cable which can be used maintaining the prescribed voltage drop limits is
calculated as follows:
m running =
m starting =
x1000 (m)
Vd x N C
3 xI m xR cosr X sin r
Vd x N C
3 xI lrc xR cosst X sin st
x1000 (m)
The permissible running and starting voltage drops are 5% and 15% respectively.
2
When feeding a 10 HP motor fed with 1RX 4CX 2.5 mm cable the maximum running and stating
lengths are:
m running =
460 x 1x5
x1000
3 x12.50 x9.45 x0.84 0.121x0.54 x100
=132.87 m
m starting =
460 x 1x15
x1000 m
3 x81x9.45 x0.54 0.121x0.84 x100
= 94.5 m
Based on the comparison made between the length based on voltage drop, the maximum cable length is
taken as the shorter of the two. So based on the calculations above it can be concluded that a 10 HP motor
2
can be fed by a 1RX 4CX 2.5 mm cable up to a maximum length of 94.5 m.
T=( k X s )/I
PAGE 11 OF 11
REV 1
Where k is the cable insulation thermal constant (143 for XLPE insulated cables) and s is the cable cross
2
section in mm .
The cable of chosen cross-section and the short circuit capacity is checked to determine if it is capable of
withstanding the let-through energy of the connected protective device.
2
Now for feeding a 15 HP motor with a 2.5 mm it can be checked that the cable withstand for 0.005 sec is
2
5.06 kA, while the fuse let through current stands at 5.7 kA. So the only restriction is 2.5 mm cable can feed
motors up to 10 HP.
If the duty exceeds the cable de-rated capability then a =T= is displayed in the chart.
For Breaker fed MV motors a =T= is also displayed even if the short circuit capability of the cable is
exceeded.
For motor feeders, the spreadsheet determines whether the starting conditions or the running conditions
determine the maximum permissible cable, this is denoted by a {s} or {r} alongside the figures on the sheet.
For the motor feeders, the criterion which determines the maximum permissible cable length is displayed by
the side as
(=T=) when the thermal limit of the cable is exceeded and a larger cable is required,
(=L=) when the cable exceeds the specified maximum length
Also
{S} when voltage drop at starting dictates the length (for motors).
{R} when voltage drop at running condition determines the length (for motors).