Preface
Preface
This manual is intended for technicians involved in the installation, commissioning and service of the
Enraf Series 870 Securiterre
A description preceding the technical procedures gives the technical information necessary to understand the
operation of the Securiterre. It is strongly recommended to read this description prior to performing any of the
procedures.
The options applicable for your installation are specified on the identification label of your Securiterre
Safety and prevention of damage
Safe execution of the procedures in this manual requires technical experience in handling tools, and
knowledge of safety regulations for electrical installations in hazardous environments.
"Warnings", "Cautions", and "Notes" have been used throughout this manual to bring special matters to the
immediate attention of the reader.
The sequence of steps in a procedure may also be important from the point of view of personal safety and
prevention of damage; it is therefore advised not to change the sequence of procedural steps or alter a
procedure.
Legal aspects
The information in this manual is copyright property of Enraf BV, Netherlands.
Enraf BV disclaims any responsibility for personal injury or damage to equipment caused by:
Page 3
Preface
EC declaration of conformity
This instrument is in conformity with the protection requirements of EC Council Directive 89/336/EEC.
The CE conformity marking fulfills the provisions of:
EN 50081-2 Generic Emission Standard
EN 50082-2 Generic Immunity Standard
When installed, maintained and applied according to the requirements as specified in this manual.
For delivery within EC only.
Safety Notice
The securistore cable dispenser contains a hermetically closed mercury wetted contact.
If the Securiterre is dismantled, this contact should be disposed properly through recycling or hazardous
waste recovery programs which area in accordance with prevailing community regulations that may apply to
the disposal of mercury.
Additional information
Please do not hesitate to contact Enraf or its representative if you require any additional information.
Page 4
Table of contents
Table of contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Securiterre . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Securistore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.1 Truck version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.2 Train version (also for small ships without cathodic protection) . . . . . . . . . . . . . . . . . . . . .
1.3.3 Drum version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Grounding clamp and grounding cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
6
6
6
6
6
7
7
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Safety aspects of the Securiterre . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Personal safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Safety conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
8
8
8
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1 Mechanical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.2 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
14
14
14
15
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Page 5
Introduction
Introduction
1.1 Securiterre
The Model 870 Securiterre is a grounding system for loading gantries that offers improved safety during the
transfer of flammable liquids. It ensures that reliable grounding has been achieved before any product
transfer can take place. It is an indispensable item for every loading facility of flammable non-conducting
liquids and powders of pellets.
Electrostatic charge can be generated and accumulated during pumping, filtering and loading of tank
compartments with non-conducting liquids such as petroleum products and chemicals. As a result, the tank
obtains a different potential than the loading equipment. This can lead to sparking when for example the
loading arm is brought in, igniting the product vapors.
1.2 Securistore
The Enraf Securistore is a reliable cable dispenser, provided with a low-capacitance neoprene cable with a
length of 15 m and an earth clamp with break-release. The break-release as such prevents cable and
Securistore raptures in case of driver departure with still clamped on clamps. The dispenser is fitted with a
return spring to rewind the cable automatically after use.
1.3.2 Train version (also for small ships without cathodic protection)
After connection of the grounding clamp to the object (train wagon or ship), the Securiterre measures the
resistance of the object to ground (max 1 K). After verification of the maximum resistance to ground, a
relay connects the measuring circuit directly to ground. Another relay switches the signal lamp to green and
switches an extra contact to externally mounted equipment.
Page 6
Introduction
1.3.3 Drum version
The drum version uses a double isolated ground clamp. The Securiterre measures the resistance over the
poles of the clamp (max. 3 ). After verification of the maximum resistance to ground, a relay connects the
measuring circuit direct to ground. Another relay switches the signal lamp to green and switches an extra
contact to externally mounted equipment.
Page 7
Safety
Safety
The Securiterre complies with European Standards EN 50.014, EN 50.018, and EN 50.020 and is ATEX
certified as EEx d [ia] ia IIC T6 acc. to LCIE France.
Caution
The Securiterre is an explosion proof instrument with intrinsically safe output/input circuits.
Modifications to the instrument may only be carried out by trained personnel which is authorized by Enraf.
Failure to adhere to this will invalidate the approval certificates.
Caution
The Securiterre may be installed in hazardous areas. The classification of the hazardous area may
vary with the optional functions of the Securiterre and per approval certificate.
Before starting installation, check whether the actual area of installation complies with the area
classification on the applicable approval certificate for your type of Securiterre.
Page 8
Unpacking
3.1 Storage
During storage, the Securiterre should preferably be kept in its original packing and stored indoors.
When the Securiterre has already been installed on site and will be out of operation for a prolonged period, it
is recommended to keep the mains on. When this is not possible, put some moisture-absorbing material such
as silica gel in the electronic compartment of the Securiterre.
SECURITERRE
Inventory checklist:
ENRAF
870 Securiterre
Securistore (optional)
the instruction manual you are reading now
12V
TYPE UA 1870
N de fab.
L.C.I.E. 87.B6.029.
EEx d [ia] ia II C T6
R3
Page 9
Installation
Installation
The Securiterre is designed to be installed in a hazardous area and to operate under extreme ambient
temperatures. It does not require any special protection.
Caution
The Securiterre may be installed in hazardous areas. The classification of the hazardous area may
vary with the optional functions of the Securiterre and per approval certificate.
Before starting installation, check whether the actual area of installation complies with the area
classification on the applicable approval certificate for your type of Securiterre.
Caution
Before opening the covers, do not forget to remove the blocking device (Refer to Appendix A).
Keeps threads of covers and Securiterre free from dirt.
Grease them lightly with an acid free grease after the Securiterre has been opened.
When closing, never tighten the covers before the threads are properly engaged.
The covers should be turned counterclockwise until the thread clicks into place,
then turn clockwise until the covers are fully closed.
After closing the covers, do not forget to place the blocking device.
The terminal box is fitted with two threaded explosion proof glands of 3/4" NPT.
The explosion proof box is fitted with one 3/4" NPT entry and fitted with an explosion proof gland for the blue
measuring cable.
Securiterre
Power supply
Ground cable
:
:
:
Page 10
Installation
10
9
8
7
6
5
4
3
2
1
SECURITERRE
12V
12V
Earth screw
Earth clamp
R3
R5
2 m
To Securistore
6 m
Mains
Normally closed (NC)
Common (C)
10
9
8
7
6
5
4
3
2
1
LEGEND
5
6
7
9
10
SPDT
voltage free contact; 5 A, 220 V
for external use
Mains: 110 or 220 V~ selectable (see figure 5.2)
Power consumption: 10 VA
Securicable
Securiterre
Blind
plug
Cable gland
3/4" NPT (2x)
SECURITERRE
CIRCUIT
LAMPS
12V
12V
R3
R5
RED DOT
BLACK DOT
Break-release
TRANSFORMER
Earth clamp
Cable length: 1 or 2 meter
part no. 3890.023
Page 11
Installation
After installation, the following procedure should be executed:
Truck version
orange
orange
green
red
LED
LED
cluster of 7 LEDs
cluster of 7 LEDs
SECURITERRE
L3
ENRAF
L2
L1
12V
12V
TYPE UA 1870
N de fab.
L.C.I.E. 87.B6.029.
EEx d [ia] ia II C T6
L4
R3
Page 12
Commissioning
Commissioning
connect the grounding. This must be done before making any other connection.
Wait a few seconds for the release (green LEDs on)
Note:
To achieve correct grounding conditions, the cable gland must be properly connected. If there is no
release after a few seconds (red LEDs on), check the earth connection. It should be clean and rust free.
If in case of the tank truck version of Securiterre, the impedance cannot be measured because of
excessive humidity or the presence of brine, a magnetically operated bypass can be activated to
establish the initial grounding. Place the brine magnet on the red dot on the Securiterre outside.
The instrument should now respond within 0.5 second.
Warning
Before starting a transfer it is imperative that the object is properly earthed and that
electrostatic charges are safely diverted to ground in order to prevent the generation of sparks
which could cause an explosion.
Page 13
The instrument is adjusted in the factory and is carefully tested before shipping. Hence installation without
any adjustments is possible after receipt of the instrument. After replacement of the measuring cable or for
special applications readjustments may be required. Check the instrument thoroughly before starting a
readjustment procedure.
Warning
All covers must be closed before switching on the electrical power.
2.
3.
Switch on the power. Make sure that the ground connection to the housing is made.
4.
The two orange LEDs L1(12 V), L2 (12 V) and the red clusters of LEDs are lighted. Check.
5.
Connect a resistor of 820 in parallel to a capacitor of 1000 pF between the clamp and earth
(from Securiterre). The Securiterre should not operate.
6.
Slowly turn potentiometer R5 clockwise until the instrument just operates (green LEDs are switched on).
From that point, turn R5 three full turns clockwise.
7.
8.
Reconnect the clamp to earth, the instrument should not operate. (Red LEDs on).
Connect the grounding clamp to a resistor of 820 (without the parallel capacitor).
The instrument should not operate (red LEDs on).
2.
Replace the resistor of 820 by a resistor of 470 parallel to a capacitor of 1000 pF.
The instrument should not operate (red LEDs on).
3.
3.
Page 14
C13
R22
R21
R26
R25
R24
R23
R20
C11
R19
C8
R12
C7
R11
C6
R10
IC1
R3
R5
R19
R20
RL1
C3
Road
Rail
1k
5k
47k
39k
REED
--
--27k
68k
-100nF
R13
C9
T2
T3
D1
R6
C5
TR1
RL2
L1
R2
C1
R1
R5 Adjust level
RL1
Page 15
Appendix A
Appendix A Dimensional drawings
Cable gland 3/4" NPT
(2 x and 1 spare)
230
82
Blind plug
Red dot
SECURITERRE
12V
12V
R3
7 (4x)
Blocking device
143
149
Securiterre
386
368
78
85
78
114
129
Top view
21
*
*
Cable gland
*Mounting holes 12 (4x)
Securistore
Page 16
Appendix B
Appendix B Specifications
Electrical
Main supply
Power consumption
Measuring voltage
Measuring current
Truck capacitance
Truck resistance
Number of relays
Contact rating
Cabling
Max. cable length
Safety
Grounding system
Environmental
Ambient temperature
: -20 to +60C
Page 17
Appendix C
Appendix C Spare parts
Spare parts list Securiterre
Description
Part. No.
2547.080
0870.951
0870.952
2547.076
0870.804
0870.805
3881.010
3890.023
0870.113
Part. No.
Cable 15 m*
0870824
* order length/metre
Page 18
Index
Index
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Adjustment procedure . . . . . . . . . . . . . . . . 14, 15
Brine magnet . . . . . . . . . . . . . . . . . . 6, 12, 13, 18
Cable dispenser . . . . . . . . . . . . . . . . . . . . . . . . . 6
Caution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3, 8
Circuit board
measuring . . . . . . . . . . . . . . . . . . . . . . . . . . 15
power supply . . . . . . . . . . . . . . . . . . . . . 15, 18
Dimensional drawing
Securistore . . . . . . . . . . . . . . . . . . . . . . . . . 16
Securiterre . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Grounding
cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
clamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Hazardous area . . . . . . . . . . . . . . . . . . . . . . . 3, 8
Identification code . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation
electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
mechanical . . . . . . . . . . . . . . . . . . . . . . . . . 10
Label on Securiterre . . . . . . . . . . . . . . . . . . . . . . 9
LED
green . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-14
orange . . . . . . . . . . . . . . . . . . . . . . . . . . 12, 14
red . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-14
Note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3, 8
Principle of operation . . . . . . . . . . . . . . . . . . . . . 6
Relay circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Safety approvals . . . . . . . . . . . . . . . . . . . . . . . . . 8
Securistore . . . . . . . . . . . . . . . . . . . . 6, 11, 14, 18
Spare parts list
Securistore . . . . . . . . . . . . . . . . . . . . . . . . . 18
Securiterre . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3, 8
Page 19
Notes
Page 20
Honeywell Enraf
Delftechpark 39
2628 XJ Delft
The Netherlands
Tel: +31 (0)15-2701 100
Email: enraf-nl@honeywell.com
www.honeywellenraf.com
4416568 - Revision 4
May 2009
2009 Honeywell International Inc.