Air System Sizing Summary for 1.

CHILDREN PLAY
Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

1.CHILDREN PLAY
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1905.2 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Jul 1500
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

13.3
159.1
125.7
6748
6748
6748
0.790
143.7
83.5
31.83

Tons
MBH
MBH
CFM
CFM
CFM

23.7
6748
6748
2.37

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Jul 1500
107.0 / 75.0
77.2 / 66.5
59.9 / 58.9
58.0
0.100
66
58.0
0 of 1
0.1

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
12.4
68.3 / 71.6 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

6748 CFM
6744 CFM
3.54 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

795 CFM
0.42 CFM/ft

CFM/person

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

11.20 CFM/person

Page 1 of 78

Zone Sizing Summary for 1.CHILDREN PLAY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

1.CHILDREN PLAY
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1905.2 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
99.1

Design
Airflow
(CFM)
6748

Minimum
Airflow
(CFM)
6748

Time of
Peak Load
Jul 1400

Maximum
Heating
Load
(MBH)
9.7

Zone
Floor
Area
(ft)
1905.2

Zone
CFM/ft
3.54

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
1.CHILDREN PLAY

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

99.1

Jul 1400

6748

9.7

1905.2

3.54

Page 2 of 78

Air System Design Load Summary for 1.CHILDREN PLAY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 107.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
97 ft
1437
97 ft
1657 ft
5139
1657 ft
2331
1905 ft
40602
1905 ft
6879
97 ft
1046
97 ft
518
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
312 ft
557
312 ft
0
0 ft
0
0 ft
0
1912 W
6522
0
0
0W
0
0
0
4000 W
13648
0
0
71
20955
32294
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
8991
1615
0%
0
0
98897
33908
9729
0
96710
33908
9704
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
6748 CFM
0
6748 CFM
0
795 CFM
29005
-572
795 CFM
13950
0
6748 CFM
0
6748 CFM
0
0
0
0%
0
0%
0
125714
33336
23654
0
125714
33344
0
0
0
23654
125714
33344
23654
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 3 of 78

Zone Design Load Summary for 1.CHILDREN PLAY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
97 ft
1119
97 ft
1657 ft
5107
1657 ft
2331
1905 ft
41128
1905 ft
6879
97 ft
1028
97 ft
518
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
312 ft
551
312 ft
0
0 ft
0
0 ft
0
1912 W
6522
0
0
0W
0
0
0
4000 W
13648
0
0
71
20955
32294
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
9006
1615
0%
0
0
99063
33908
9729
0

Page 4 of 78

System Psychrometrics for 1.CHILDREN PLAY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

July DESIGN COOLING DAY, 1500

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
107.0
77.2
59.9
59.9
59.9
59.9
73.2
73.2

Specific
Humidity
(lb/lb)
0.01129
0.01143
0.01038
0.01038
0.01038
0.01038
0.01144
0.01144

Airflow
(CFM)
795
6748
6748
6748
6748
6748
6748
6748

CO2 Level
(ppm)
400
1880
1880
1880
1880
1880
2077
2077

Sensible
Heat
(BTU/hr)
29005
125714
0
0
96710
0

Latent
Heat
(BTU/hr)
-572
33344
33908
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
98897

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
96710

Zone
Temp
(F)
73.2

Zone
Airflow
(CFM)
6748

CO2
Level
(ppm)
2077

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 5 of 78

System Psychrometrics for 1.CHILDREN PLAY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
68.3
68.3
71.6
71.6
71.6
70.3
70.3

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
795
6748
6748
6748
6748
6748
6748
6748

CO2 Level
(ppm)
400
469
469
469
469
469
478
478

Sensible
Heat
(BTU/hr)
-13950
0
23654
0
-9704
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-9729

Zone
T-stat
Cond
Mode (BTU/hr)
Deadband
-9704

Zone
Temp
(F)
70.3

Zone
Airflow
(CFM)
6748

CO2
Level
(ppm)
478

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 6 of 78

Air System Sizing Summary for 2.ENTRANCE LOBBY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

2.ENTRANCE LOBBY
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1659.8 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Aug 1400
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

5.1
61.8
57.8
3603
3603
3603
0.936
322.3
37.2
12.36

Tons
MBH
MBH
CFM
CFM
CFM

9.4
3603
3603
0.94

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Aug 1400
106.5 / 74.9
74.4 / 64.2
59.5 / 58.5
57.9
0.100
61
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
5.7
69.2 / 71.6 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

3603 CFM
3601 CFM
2.17 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

180 CFM
0.11 CFM/ft

CFM/person

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

11.98 CFM/person

Page 7 of 78

Zone Sizing Summary for 2.ENTRANCE LOBBY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

2.ENTRANCE LOBBY
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1659.8 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
52.9

Design
Airflow
(CFM)
3603

Minimum
Airflow
(CFM)
3603

Time of
Peak Load
Jul 1400

Maximum
Heating
Load
(MBH)
6.3

Zone
Floor
Area
(ft)
1659.8

Zone
CFM/ft
2.17

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
2.ENTRANCE LOBBY

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

52.9

Jul 1400

3603

6.3

1659.8

2.17

Page 8 of 78

Air System Design Load Summary for 2.ENTRANCE LOBBY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
201 ft
583
201 ft
283
1660 ft
35278
1660 ft
5993
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
1528 ft
2699
1528 ft
0
0 ft
0
0 ft
0
1542 W
5261
0
0
0W
0
0
0
0W
0
0
0
15
3675
3076
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
4750
154
0%
0
0
52246
3230
6276
0
51272
3230
6282
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
3603 CFM
0
3603 CFM
0
180 CFM
6551
734
180 CFM
3101
0
3603 CFM
0
3603 CFM
0
0
0
0%
0
0%
0
57823
3964
9383
0
57823
3969
0
0
0
9383
57823
3969
9383
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 9 of 78

Zone Design Load Summary for 2.ENTRANCE LOBBY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
201 ft
619
201 ft
283
1660 ft
35830
1660 ft
5993
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
1528 ft
2699
1528 ft
0
0 ft
0
0 ft
0
1542 W
5261
0
0
0W
0
0
0
0W
0
0
0
15
3675
3076
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
4808
154
0%
0
0
52892
3230
6276
0

Page 10 of 78

System Psychrometrics for 2.ENTRANCE LOBBY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

August DESIGN COOLING DAY, 1400

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
106.5
74.4
59.5
59.5
59.5
59.5
72.7
72.7

Specific
Humidity
(lb/lb)
0.01129
0.01047
0.01024
0.01024
0.01024
0.01024
0.01043
0.01043

Airflow
(CFM)
180
3603
3603
3603
3603
3603
3603
3603

CO2 Level
(ppm)
400
1153
1153
1153
1153
1153
1193
1193

Sensible
Heat
(BTU/hr)
6551
57823
0
0
51272
0

Latent
Heat
(BTU/hr)
734
3969
3230
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
52246

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
51272

Zone
Temp
(F)
72.7

Zone
Airflow
(CFM)
3603

CO2
Level
(ppm)
1193

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 11 of 78

System Psychrometrics for 2.ENTRANCE LOBBY


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
69.2
69.2
71.6
71.6
71.6
70.0
70.0

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
180
3603
3603
3603
3603
3603
3603
3603

CO2 Level
(ppm)
400
586
586
586
586
586
595
595

Sensible
Heat
(BTU/hr)
-3101
0
9383
0
-6282
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-6276

Zone
T-stat
Cond
Mode (BTU/hr)
Deadband
-6282

Zone
Temp
(F)
70.0

Zone
Airflow
(CFM)
3603

CO2
Level
(ppm)
595

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 12 of 78

Air System Sizing Summary for 2.PRAY AREA MEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

2.PRAY AREA MEN


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
547.9 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Jun 1500
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

6.4
76.6
49.4
2505
2505
2505
0.644
85.8
139.9
15.34

Tons
MBH
MBH
CFM
CFM
CFM

8.8
2505
2505
0.88

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Jun 1500
106.0 / 75.0
77.3 / 67.9
59.1 / 58.2
57.0
0.100
74
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
16.1
67.8 / 71.1 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

2505 CFM
2504 CFM
4.57 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

0.00 BHP
0.00 kW
0.00 in wg

356 CFM
0.65 CFM/ft

CFM/person

5.83 CFM/person

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

Page 13 of 78

Zone Sizing Summary for 2.PRAY AREA MEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

2.PRAY AREA MEN


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
547.9 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
36.8

Design
Airflow
(CFM)
2505

Minimum
Airflow
(CFM)
2505

Time of
Peak Load
Jul 1400

Maximum
Heating
Load
(MBH)
2.3

Zone
Floor
Area
(ft)
547.9

Zone
CFM/ft
4.57

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
3.PRAY AREA MEN

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

36.8

Jul 1400

2505

2.3

547.9

4.57

Page 14 of 78

Air System Design Load Summary for 2.PRAY AREA MEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jun 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
249 ft
770
249 ft
350
548 ft
11600
548 ft
1978
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
614 ft
1075
614 ft
0
0 ft
0
0 ft
0
509 W
1737
0
0
0W
0
0
0
0W
0
0
0
61
18004
27745
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
3319
1387
0%
0
0
36505
29132
2328
0
36516
29132
2630
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
2505 CFM
0
2505 CFM
0
356 CFM
12839
-1847
356 CFM
6197
0
2505 CFM
0
2505 CFM
0
0
0
0%
0
0%
0
49355
27286
8826
0
49355
27287
0
0
0
8826
49355
27287
8826
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 15 of 78

Zone Design Load Summary for 2.PRAY AREA MEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
249 ft
779
249 ft
350
548 ft
11827
548 ft
1978
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
614 ft
1084
614 ft
0
0 ft
0
0 ft
0
509 W
1737
0
0
0W
0
0
0
0W
0
0
0
61
18004
27745
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
3343
1387
0%
0
0
36773
29132
2328
0

Page 16 of 78

System Psychrometrics for 2.PRAY AREA MEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

June DESIGN COOLING DAY, 1500

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
106.0
77.3
59.1
59.1
59.1
59.1
72.6
72.6

Specific
Humidity
(lb/lb)
0.01152
0.01246
0.01016
0.01016
0.01016
0.01016
0.01262
0.01262

Airflow
(CFM)
356
2505
2505
2505
2505
2505
2505
2505

CO2 Level
(ppm)
400
3223
3223
3223
3223
3223
3690
3690

Sensible
Heat
(BTU/hr)
12839
49355
0
0
36516
0

Latent
Heat
(BTU/hr)
-1847
27287
29132
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
36505

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
36516

Zone
Temp
(F)
72.6

Zone
Airflow
(CFM)
2505

CO2
Level
(ppm)
3690

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 17 of 78

System Psychrometrics for 2.PRAY AREA MEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
67.8
67.8
71.1
71.1
71.1
70.1
70.1

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
356
2505
2505
2505
2505
2505
2505
2505

CO2 Level
(ppm)
400
455
455
455
455
455
464
464

Sensible
Heat
(BTU/hr)
-6197
0
8826
0
-2630
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-2328

Zone
T-stat
Cond
Mode (BTU/hr)
Deadband
-2630

Zone
Temp
(F)
70.1

Zone
Airflow
(CFM)
2505

CO2
Level
(ppm)
464

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 18 of 78

Air System Sizing Summary for 4.ADMIN OFFICE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

4.ADMIN OFFICE 1
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1604.9 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Jun 1500
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

6.1
73.2
71.1
4600
4600
4600
0.971
263.1
45.6
14.65

Tons
MBH
MBH
CFM
CFM
CFM

12.3
4600
4600
1.23

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Jun 1500
106.0 / 75.0
73.7 / 63.7
59.4 / 58.5
57.8
0.100
60
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
7.7
69.4 / 71.9 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

4600 CFM
4597 CFM
2.87 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

134 CFM
0.08 CFM/ft

CFM/person

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

22.39 CFM/person

Page 19 of 78

Zone Sizing Summary for 4.ADMIN OFFICE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

4.ADMIN OFFICE 1
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1604.9 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
67.5

Design
Airflow
(CFM)
4600

Minimum
Airflow
(CFM)
4600

Time of
Peak Load
Jun 1500

Maximum
Heating
Load
(MBH)
10.2

Zone
Floor
Area
(ft)
1604.9

Zone
CFM/ft
2.87

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
4.ADMIN OFFICE 1

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

67.5

Jun 1500

4600

10.2

1604.9

2.87

Page 20 of 78

Air System Design Load Summary for 4.ADMIN OFFICE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jun 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
517 ft
8237
517 ft
1178 ft
3607
1178 ft
1657
1605 ft
33978
1605 ft
5795
517 ft
5405
517 ft
2763
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
108 ft
189
108 ft
0
0 ft
0
0 ft
0
1491 W
5087
0
0
0W
0
0
0
1000 W
3412
0
0
6
1470
1230
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
6138
62
0%
0
0
67523
1292
10215
0
66277
1292
10005
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
4600 CFM
0
4600 CFM
0
134 CFM
4818
795
134 CFM
2307
2
4600 CFM
0
4600 CFM
0
0
0
0%
0
0%
0
71095
2086
12312
2
71095
2092
0
0
0
12312
71095
2092
12312
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 21 of 78

Zone Design Load Summary for 4.ADMIN OFFICE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jun 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
517 ft
8237
517 ft
1178 ft
3607
1178 ft
1657
1605 ft
33978
1605 ft
5795
517 ft
5405
517 ft
2763
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
108 ft
189
108 ft
0
0 ft
0
0 ft
0
1491 W
5087
0
0
0W
0
0
0
1000 W
3412
0
0
6
1470
1230
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
6138
62
0%
0
0
67523
1292
10215
0

Page 22 of 78

System Psychrometrics for 4.ADMIN OFFICE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

June DESIGN COOLING DAY, 1500

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
106.0
73.7
59.4
59.4
59.4
59.4
72.8
72.8

Specific
Humidity
(lb/lb)
0.01152
0.01031
0.01022
0.01022
0.01022
0.01022
0.01027
0.01027

Airflow
(CFM)
134
4600
4600
4600
4600
4600
4600
4600

CO2 Level
(ppm)
400
804
804
804
804
804
816
816

Sensible
Heat
(BTU/hr)
4818
71095
0
0
66277
0

Latent
Heat
(BTU/hr)
795
2092
1292
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
67523

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
66277

Zone
Temp
(F)
72.8

Zone
Airflow
(CFM)
4600

CO2
Level
(ppm)
816

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 23 of 78

System Psychrometrics for 4.ADMIN OFFICE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
69.4
69.4
71.9
71.9
71.9
69.9
69.9

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
134
4600
4600
4600
4600
4600
4600
4600

CO2 Level
(ppm)
400
725
725
725
725
725
735
735

Sensible
Heat
(BTU/hr)
-2307
0
12312
0
-10005
0

Latent
Heat
(BTU/hr)
-2
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-10215

Zone
T-stat
Cond
Mode (BTU/hr)
Heating
-10005

Zone
Temp
(F)
69.9

Zone
Airflow
(CFM)
4600

CO2
Level
(ppm)
735

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 24 of 78

Air System Sizing Summary for 5.BACK OFFICE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

5.BACK OFFICE
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1043.0 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Jul 1500
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

3.5
41.8
39.3
2395
2395
2395
0.940
299.1
40.1
8.37

Tons
MBH
MBH
CFM
CFM
CFM

7.3
2395
2395
0.73

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Jul 1500
107.0 / 75.0
74.8 / 64.3
59.6 / 58.6
57.9
0.100
61
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
7.0
69.1 / 71.9 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

2395 CFM
2393 CFM
2.30 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

140 CFM
0.13 CFM/ft

CFM/person

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

15.51 CFM/person

Page 25 of 78

Zone Sizing Summary for 5.BACK OFFICE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

5.BACK OFFICE
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1043.0 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
35.2

Design
Airflow
(CFM)
2395

Minimum
Airflow
(CFM)
2395

Time of
Peak Load
Jul 1400

Maximum
Heating
Load
(MBH)
4.8

Zone
Floor
Area
(ft)
1043.0

Zone
CFM/ft
2.30

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
5.BACK OFFICE

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

35.2

Jul 1400

2395

4.8

1043.0

2.30

Page 26 of 78

Air System Design Load Summary for 5.BACK OFFICE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 107.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
756 ft
2371
756 ft
1063
1043 ft
22228
1043 ft
3766
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
904 ft
1612
904 ft
0
0 ft
0
0 ft
0
969 W
3306
0
0
0W
0
0
0
0W
0
0
0
9
2205
1845
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
3172
92
0%
0
0
34894
1937
4830
0
34169
1937
4841
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
2395 CFM
0
2395 CFM
0
140 CFM
5158
583
140 CFM
2413
0
2395 CFM
0
2395 CFM
0
0
0
0%
0
0%
0
39328
2521
7255
0
39328
2522
0
0
0
7255
39328
2522
7255
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 27 of 78

Zone Design Load Summary for 5.BACK OFFICE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
756 ft
2334
756 ft
1063
1043 ft
22516
1043 ft
3766
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
904 ft
1597
904 ft
0
0 ft
0
0 ft
0
969 W
3306
0
0
0W
0
0
0
0W
0
0
0
9
2205
1845
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
3196
92
0%
0
0
35153
1937
4830
0

Page 28 of 78

System Psychrometrics for 5.BACK OFFICE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

July DESIGN COOLING DAY, 1500

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
107.0
74.8
59.6
59.6
59.6
59.6
72.8
72.8

Specific
Humidity
(lb/lb)
0.01129
0.01046
0.01024
0.01024
0.01024
0.01024
0.01041
0.01041

Airflow
(CFM)
140
2395
2395
2395
2395
2395
2395
2395

CO2 Level
(ppm)
400
969
969
969
969
969
1004
1004

Sensible
Heat
(BTU/hr)
5158
39328
0
0
34169
0

Latent
Heat
(BTU/hr)
583
2522
1937
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
34894

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
34169

Zone
Temp
(F)
72.8

Zone
Airflow
(CFM)
2395

CO2
Level
(ppm)
1004

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 29 of 78

System Psychrometrics for 5.BACK OFFICE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
69.1
69.1
71.9
71.9
71.9
70.0
70.0

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
140
2395
2395
2395
2395
2395
2395
2395

CO2 Level
(ppm)
400
553
553
553
553
553
562
562

Sensible
Heat
(BTU/hr)
-2413
0
7255
0
-4841
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-4830

Zone
T-stat
Cond
Mode (BTU/hr)
Deadband
-4841

Zone
Temp
(F)
70.0

Zone
Airflow
(CFM)
2395

CO2
Level
(ppm)
562

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 30 of 78

Air System Sizing Summary for 6.PRAY AREA WOMEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

6.PRAY AREA WOMEN


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
406.9 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Aug 1500
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

4.0
47.9
38.3
1990
1990
1990
0.799
101.9
117.8
9.59

Tons
MBH
MBH
CFM
CFM
CFM

8.0
1990
1990
0.80

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Aug 1500
107.0 / 75.0
77.7 / 66.5
59.8 / 58.8
57.9
0.100
65
58.0
0 of 1
0.1

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
19.6
67.8 / 71.5 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

1990 CFM
1989 CFM
4.89 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

0.00 BHP
0.00 kW
0.00 in wg

264 CFM
0.65 CFM/ft

CFM/person

5.87 CFM/person

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

Page 31 of 78

Zone Sizing Summary for 6.PRAY AREA WOMEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

6.PRAY AREA WOMEN


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
406.9 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
29.2

Design
Airflow
(CFM)
1990

Minimum
Airflow
(CFM)
1990

Time of
Peak Load
Aug 1500

Maximum
Heating
Load
(MBH)
3.4

Zone
Floor
Area
(ft)
406.9

Zone
CFM/ft
4.89

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
6.PRAY AREA WOMEN

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

29.2

Aug 1500

1990

3.4

406.9

4.89

Page 32 of 78

Air System Design Load Summary for 6.PRAY AREA WOMEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 107.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
1381 ft
4635
1381 ft
1944
407 ft
8493
407 ft
1469
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
624 ft
1113
624 ft
0
0 ft
0
0 ft
0
378 W
1290
0
0
0W
0
0
0
0W
0
0
0
45
11025
9225
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
2656
461
0%
0
0
29212
9686
3413
0
28667
9686
3453
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
1990 CFM
0
1990 CFM
0
264 CFM
9642
-79
264 CFM
4527
0
1990 CFM
0
1990 CFM
0
0
0
0%
0
0%
0
38309
9607
7980
0
38309
9608
0
0
0
7980
38309
9608
7980
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 33 of 78

Zone Design Load Summary for 6.PRAY AREA WOMEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 107.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
1381 ft
4635
1381 ft
1944
407 ft
8493
407 ft
1469
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
624 ft
1113
624 ft
0
0 ft
0
0 ft
0
378 W
1290
0
0
0W
0
0
0
0W
0
0
0
45
11025
9225
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
2656
461
0%
0
0
29212
9686
3413
0

Page 34 of 78

System Psychrometrics for 6.PRAY AREA WOMEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

August DESIGN COOLING DAY, 1500

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
107.0
77.7
59.8
59.8
59.8
59.8
73.2
73.2

Specific
Humidity
(lb/lb)
0.01129
0.01135
0.01033
0.01033
0.01033
0.01033
0.01135
0.01135

Airflow
(CFM)
264
1990
1990
1990
1990
1990
1990
1990

CO2 Level
(ppm)
400
2093
2093
2093
2093
2093
2352
2352

Sensible
Heat
(BTU/hr)
9642
38309
0
0
28667
0

Latent
Heat
(BTU/hr)
-79
9608
9686
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
29212

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
28667

Zone
Temp
(F)
73.2

Zone
Airflow
(CFM)
1990

CO2
Level
(ppm)
2352

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 35 of 78

System Psychrometrics for 6.PRAY AREA WOMEN


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
67.8
67.8
71.5
71.5
71.5
69.9
69.9

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
264
1990
1990
1990
1990
1990
1990
1990

CO2 Level
(ppm)
400
463
463
463
463
463
472
472

Sensible
Heat
(BTU/hr)
-4527
0
7980
0
-3453
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-3413

Zone
T-stat
Cond
Mode (BTU/hr)
Heating
-3453

Zone
Temp
(F)
69.9

Zone
Airflow
(CFM)
1990

CO2
Level
(ppm)
472

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 36 of 78

Air System Sizing Summary for 7.ADMIN OFFICE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

7.ADMIN OFFICE 2
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1304.6 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Jun 1400
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

4.4
53.0
51.1
3331
3331
3331
0.964
295.6
40.6
10.60

Tons
MBH
MBH
CFM
CFM
CFM

9.3
3331
3331
0.93

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Jun 1400
105.5 / 74.9
73.9 / 63.9
59.7 / 58.7
58.1
0.100
60
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
7.1
69.6 / 72.1 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

3331 CFM
3329 CFM
2.55 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

109 CFM
0.08 CFM/ft

CFM/person

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

18.19 CFM/person

Page 37 of 78

Zone Sizing Summary for 7.ADMIN OFFICE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

7.ADMIN OFFICE 2
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
1304.6 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
48.9

Design
Airflow
(CFM)
3331

Minimum
Airflow
(CFM)
3331

Time of
Peak Load
Jul 1500

Maximum
Heating
Load
(MBH)
7.3

Zone
Floor
Area
(ft)
1304.6

Zone
CFM/ft
2.55

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
7.ADMIN OFFICE

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

48.9

Jul 1500

3331

7.3

1304.6

2.55

Page 38 of 78

Air System Design Load Summary for 7.ADMIN OFFICE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jun 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 105.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
237 ft
2986
237 ft
958 ft
2996
958 ft
1348
1305 ft
28047
1305 ft
4710
237 ft
2432
237 ft
1266
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
118 ft
206
118 ft
0
0 ft
0
0 ft
0
1212 W
4135
0
0
0W
0
0
0
500 W
1706
0
0
6
1470
1230
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
4398
62
0%
0
0
48376
1292
7325
0
47237
1292
7373
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
3331 CFM
0
3331 CFM
0
109 CFM
3850
586
109 CFM
1894
1
3331 CFM
0
3331 CFM
0
0
0
0%
0
0%
0
51087
1878
9268
1
51087
1881
0
0
0
9268
51087
1881
9268
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 39 of 78

Zone Design Load Summary for 7.ADMIN OFFICE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 107.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
237 ft
3513
237 ft
958 ft
3053
958 ft
1348
1305 ft
27802
1305 ft
4710
237 ft
2557
237 ft
1266
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
118 ft
211
118 ft
0
0 ft
0
0 ft
0
1212 W
4135
0
0
0W
0
0
0
500 W
1706
0
0
6
1470
1230
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
4445
62
0%
0
0
48893
1292
7325
0

Page 40 of 78

System Psychrometrics for 7.ADMIN OFFICE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

June DESIGN COOLING DAY, 1400

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
105.5
73.9
59.7
59.7
59.7
59.7
72.8
72.8

Specific
Humidity
(lb/lb)
0.01152
0.01043
0.01031
0.01031
0.01031
0.01031
0.01039
0.01039

Airflow
(CFM)
109
3331
3331
3331
3331
3331
3331
3331

CO2 Level
(ppm)
400
808
808
808
808
808
822
822

Sensible
Heat
(BTU/hr)
3850
51087
0
0
47237
0

Latent
Heat
(BTU/hr)
586
1881
1292
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
48376

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
47237

Zone
Temp
(F)
72.8

Zone
Airflow
(CFM)
3331

CO2
Level
(ppm)
822

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 41 of 78

System Psychrometrics for 7.ADMIN OFFICE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
69.6
69.6
72.1
72.1
72.1
70.1
70.1

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
109
3331
3331
3331
3331
3331
3331
3331

CO2 Level
(ppm)
400
687
687
687
687
687
696
696

Sensible
Heat
(BTU/hr)
-1894
0
9268
0
-7373
0

Latent
Heat
(BTU/hr)
-1
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-7325

Zone
T-stat
Cond
Mode (BTU/hr)
Deadband
-7373

Zone
Temp
(F)
70.1

Zone
Airflow
(CFM)
3331

CO2
Level
(ppm)
696

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 42 of 78

Air System Sizing Summary for 81.STORAGE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

81.STORAGE 1
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
587.7 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Jun 1400
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

1.4
16.3
15.8
1011
1011
1011
0.972
433.7
27.7
3.25

Tons
MBH
MBH
CFM
CFM
CFM

3.2
1011
1011
0.32

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Jun 1400
105.5 / 74.9
74.0 / 63.8
59.5 / 58.5
57.9
0.100
60
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
5.5
69.2 / 72.1 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

1011 CFM
1010 CFM
1.72 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

40 CFM
0.07 CFM/ft

CFM/person

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

40.05 CFM/person

Page 43 of 78

Zone Sizing Summary for 81.STORAGE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

81.STORAGE 1
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
587.7 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
14.8

Design
Airflow
(CFM)
1011

Minimum
Airflow
(CFM)
1011

Time of
Peak Load
Jul 1400

Maximum
Heating
Load
(MBH)
2.5

Zone
Floor
Area
(ft)
587.7

Zone
CFM/ft
1.72

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
81.STORAGE 1

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

14.8

Jul 1400

1011

2.5

587.7

1.72

Page 44 of 78

Air System Design Load Summary for 81.STORAGE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jun 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 105.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
759 ft
2235
759 ft
1068
393 ft
8446
393 ft
1419
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
323 ft
560
323 ft
0
0 ft
0
0 ft
0
546 W
1863
0
0
0W
0
0
0
0W
0
0
0
1
245
205
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
1335
10
0%
0
0
14685
215
2487
0
14388
215
2531
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
1011 CFM
0
1011 CFM
0
40 CFM
1418
237
40 CFM
683
0
1011 CFM
0
1011 CFM
0
0
0
0%
0
0%
0
15806
452
3214
0
15806
454
0
0
0
3214
15806
454
3214
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 45 of 78

Zone Design Load Summary for 81.STORAGE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
759 ft
2332
759 ft
1068
393 ft
8481
393 ft
1419
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
323 ft
570
323 ft
0
0 ft
0
0 ft
0
546 W
1863
0
0
0W
0
0
0
0W
0
0
0
1
245
205
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
1349
10
0%
0
0
14841
215
2487
0

Page 46 of 78

System Psychrometrics for 81.STORAGE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

June DESIGN COOLING DAY, 1400

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
105.5
74.0
59.5
59.5
59.5
59.5
72.7
72.7

Specific
Humidity
(lb/lb)
0.01152
0.01032
0.01023
0.01023
0.01023
0.01023
0.01027
0.01027

Airflow
(CFM)
40
1011
1011
1011
1011
1011
1011
1011

CO2 Level
(ppm)
400
796
796
796
796
796
812
812

Sensible
Heat
(BTU/hr)
1418
15806
0
0
14388
0

Latent
Heat
(BTU/hr)
237
454
215
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
14685

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
14388

Zone
Temp
(F)
72.7

Zone
Airflow
(CFM)
1011

CO2
Level
(ppm)
812

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 47 of 78

System Psychrometrics for 81.STORAGE 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
69.2
69.2
72.1
72.1
72.1
69.8
69.8

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
40
1011
1011
1011
1011
1011
1011
1011

CO2 Level
(ppm)
400
637
637
637
637
637
646
646

Sensible
Heat
(BTU/hr)
-683
0
3214
0
-2531
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-2487

Zone
T-stat
Cond
Mode (BTU/hr)
Heating
-2531

Zone
Temp
(F)
69.8

Zone
Airflow
(CFM)
1011

CO2
Level
(ppm)
646

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 48 of 78

Air System Sizing Summary for 82.SHOPPING AREA PART 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

82.SHOPPING AREA PART 1


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
5929.8 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Aug 1500
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

24.3
291.6
249.2
11957
11957
11957
0.855
244.0
49.2
58.35

Tons
MBH
MBH
CFM
CFM
CFM

53.5
11957
11957
5.35

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Aug 1500
107.0 / 75.0
78.4 / 65.8
59.1 / 57.9
56.9
0.100
62
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
9.0
67.3 / 71.4 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

11957 CFM
11950 CFM
2.02 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

2031 CFM
0.34 CFM/ft

CFM/person

12.31 CFM/person

Page 49 of 78

Zone Sizing Summary for 82.SHOPPING AREA PART 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

82.SHOPPING AREA PART 1


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
5929.8 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
175.5

Design
Airflow
(CFM)
11957

Minimum
Airflow
(CFM)
11957

Time of
Peak Load
Jul 1500

Maximum
Heating
Load
(MBH)
18.5

Zone
Floor
Area
(ft)
5929.8

Zone
CFM/ft
2.02

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
82. SHOPING AREA PART 1

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

175.5

Jul 1500

11957

18.5

5929.8

2.02

Page 50 of 78

Air System Design Load Summary for 82.SHOPPING AREA PART 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 107.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
377 ft
7268
377 ft
2370 ft
7308
2370 ft
3336
3635 ft
75877
3635 ft
13125
377 ft
4067
377 ft
2014
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
527 ft
941
527 ft
0
0 ft
0
0 ft
0
5509 W
18796
0
0
0W
0
0
0
1000 W
3412
0
0
165
40424
33825
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
15809
1691
0%
0
0
173903
35516
18475
0
173570
35516
18476
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
11957 CFM
0
11957 CFM
0
2031 CFM
75603
6885
2031 CFM
35032
0
11957 CFM
0
11957 CFM
0
0
0
0%
0
0%
0
249174
42401
53508
0
249174
42410
0
0
0
53509
249174
42410
53509
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 51 of 78

Zone Design Load Summary for 82.SHOPPING AREA PART 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 107.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
377 ft
7147
377 ft
2370 ft
7310
2370 ft
3336
3635 ft
77466
3635 ft
13125
377 ft
4067
377 ft
2014
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
527 ft
941
527 ft
0
0 ft
0
0 ft
0
5509 W
18796
0
0
0W
0
0
0
1000 W
3412
0
0
165
40424
33825
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
15956
1691
0%
0
0
175519
35516
18475
0

Page 52 of 78

System Psychrometrics for 82.SHOPPING AREA PART 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

August DESIGN COOLING DAY, 1500

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
107.0
78.4
59.1
59.1
59.1
59.1
72.5
72.5

Specific
Humidity
(lb/lb)
0.01129
0.01070
0.00995
0.00995
0.00995
0.00995
0.01058
0.01058

Airflow
(CFM)
2031
11957
11957
11957
11957
11957
11957
11957

CO2 Level
(ppm)
400
1165
1165
1165
1165
1165
1322
1322

Sensible
Heat
(BTU/hr)
75603
249174
0
0
173570
0

Latent
Heat
(BTU/hr)
6885
42410
35516
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
173903

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
173570

Zone
Temp
(F)
72.5

Zone
Airflow
(CFM)
11957

CO2
Level
(ppm)
1322

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 53 of 78

System Psychrometrics for 82.SHOPPING AREA PART 1


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
67.3
67.3
71.4
71.4
71.4
70.0
70.0

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
2031
11957
11957
11957
11957
11957
11957
11957

CO2 Level
(ppm)
400
443
443
443
443
443
452
452

Sensible
Heat
(BTU/hr)
-35032
0
53509
0
-18476
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-18475

Zone
T-stat
Cond
Mode (BTU/hr)
Deadband
-18476

Zone
Temp
(F)
70.0

Zone
Airflow
(CFM)
11957

CO2
Level
(ppm)
452

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 54 of 78

Air System Sizing Summary for 83.SHOPPING AREA PART 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

83.SHOPPING AREA PART 2


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
6152.7 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Jul 1600
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

23.7
284.5
240.7
11138
11138
11138
0.846
259.6
46.2
56.92

Tons
MBH
MBH
CFM
CFM
CFM

60.7
11138
11138
6.07

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Jul 1600
106.5 / 74.9
79.0 / 66.1
59.0 / 57.8
56.8
0.100
62
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
9.9
66.9 / 71.9 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

11138 CFM
11132 CFM
1.81 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

2107 CFM
0.34 CFM/ft

CFM/person

12.29 CFM/person

Page 55 of 78

Zone Sizing Summary for 83.SHOPPING AREA PART 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

83.SHOPPING AREA PART 2


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
6152.7 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
163.5

Design
Airflow
(CFM)
11138

Minimum
Airflow
(CFM)
11138

Time of
Peak Load
Jul 1500

Maximum
Heating
Load
(MBH)
25.2

Zone
Floor
Area
(ft)
6152.7

Zone
CFM/ft
1.81

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
83. SHOPING AREA PART 2

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

163.5

Jul 1500

11138

25.2

6152.7

1.81

Page 56 of 78

Air System Design Load Summary for 83.SHOPPING AREA PART 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1600
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
527 ft
9295
527 ft
11974 ft
36839
11974 ft
16852
1534 ft
30773
1534 ft
5538
527 ft
5667
527 ft
2820
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
431 ft
766
431 ft
0
0 ft
0
0 ft
0
5716 W
19503
0
0
0W
0
0
0
1000 W
3412
0
0
172
42017
35158
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
14827
1758
0%
0
0
163099
36915
25210
0
163667
36915
24629
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
11138 CFM
0
11138 CFM
0
2107 CFM
77023
6850
2107 CFM
36050
0
11138 CFM
0
11138 CFM
0
0
0
0%
0
0%
0
240689
43765
60680
0
240689
43770
0
0
0
60680
240689
43770
60680
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 57 of 78

Zone Design Load Summary for 83.SHOPPING AREA PART 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 107.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
527 ft
7825
527 ft
11974 ft
36736
11974 ft
16852
1534 ft
32688
1534 ft
5538
527 ft
5694
527 ft
2820
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
431 ft
768
431 ft
0
0 ft
0
0 ft
0
5716 W
19503
0
0
0W
0
0
0
1000 W
3412
0
0
172
42017
35158
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
14864
1758
0%
0
0
163507
36915
25210
0

Page 58 of 78

System Psychrometrics for 83.SHOPPING AREA PART 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

July DESIGN COOLING DAY, 1600

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
106.5
79.0
59.0
59.0
59.0
59.0
72.6
72.6

Specific
Humidity
(lb/lb)
0.01129
0.01074
0.00991
0.00991
0.00991
0.00991
0.01061
0.01061

Airflow
(CFM)
2107
11138
11138
11138
11138
11138
11138
11138

CO2 Level
(ppm)
400
1153
1153
1153
1153
1153
1328
1328

Sensible
Heat
(BTU/hr)
77023
240689
0
0
163667
0

Latent
Heat
(BTU/hr)
6850
43770
36915
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
163099

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
163667

Zone
Temp
(F)
72.6

Zone
Airflow
(CFM)
11138

CO2
Level
(ppm)
1328

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 59 of 78

System Psychrometrics for 83.SHOPPING AREA PART 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
66.9
66.9
71.9
71.9
71.9
69.8
69.8

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
2107
11138
11138
11138
11138
11138
11138
11138

CO2 Level
(ppm)
400
440
440
440
440
440
449
449

Sensible
Heat
(BTU/hr)
-36050
0
60680
0
-24629
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-25210

Zone
T-stat
Cond
Mode (BTU/hr)
Heating
-24629

Zone
Temp
(F)
69.8

Zone
Airflow
(CFM)
11138

CO2
Level
(ppm)
449

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 60 of 78

Air System Sizing Summary for 84.SMALL STORAGE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

84.SMALL STORAGE
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
36.6 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Aug 1400
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

0.2
2.6
2.4
147
147
147
0.908
169.1
71.0
0.52

Tons
MBH
MBH
CFM
CFM
CFM

0.5
147
147
0.05

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Aug 1400
106.5 / 74.9
74.7 / 64.6
59.8 / 58.9
58.2
0.100
62
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
14.1
68.9 / 72.1 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

147 CFM
147 CFM
4.01 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

0.00 BHP
0.00 kW
0.00 in wg

8 CFM
0.21 CFM/ft

CFM/person

7.63 CFM/person

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

Page 61 of 78

Zone Sizing Summary for 84.SMALL STORAGE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

84.SMALL STORAGE
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
36.6 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
2.2

Design
Airflow
(CFM)
147

Minimum
Airflow
(CFM)
147

Time of
Peak Load
Aug 1400

Maximum
Heating
Load
(MBH)
0.4

Zone
Floor
Area
(ft)
36.6

Zone
CFM/ft
4.01

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
84. SMALL STORAGE

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

2.2

Aug 1400

147

0.4

36.6

4.01

Page 62 of 78

Air System Design Load Summary for 84.SMALL STORAGE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
196 ft
613
196 ft
276
37 ft
778
37 ft
132
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
118 ft
209
118 ft
0
0 ft
0
0 ft
0
34 W
116
0
0
0W
0
0
0
0W
0
0
0
1
245
205
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
196
10
0%
0
0
2157
215
408
0
2083
215
386
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
147 CFM
0
147 CFM
0
8 CFM
276
22
8 CFM
129
0
147 CFM
0
147 CFM
0
0
0
0%
0
0%
0
2359
237
516
0
2359
238
0
0
0
516
2359
238
516
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 63 of 78

Zone Design Load Summary for 84.SMALL STORAGE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
196 ft
613
196 ft
276
37 ft
778
37 ft
132
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
118 ft
209
118 ft
0
0 ft
0
0 ft
0
34 W
116
0
0
0W
0
0
0
0W
0
0
0
1
245
205
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
196
10
0%
0
0
2157
215
408
0

Page 64 of 78

System Psychrometrics for 84.SMALL STORAGE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

August DESIGN COOLING DAY, 1400

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
106.5
74.7
59.8
59.8
59.8
59.8
73.0
73.0

Specific
Humidity
(lb/lb)
0.01129
0.01071
0.01037
0.01037
0.01037
0.01037
0.01068
0.01068

Airflow
(CFM)
8
147
147
147
147
147
147
147

CO2 Level
(ppm)
400
1515
1515
1515
1515
1515
1577
1577

Sensible
Heat
(BTU/hr)
276
2359
0
0
2083
0

Latent
Heat
(BTU/hr)
22
238
215
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
2157

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
2083

Zone
Temp
(F)
73.0

Zone
Airflow
(CFM)
147

CO2
Level
(ppm)
1577

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 65 of 78

System Psychrometrics for 84.SMALL STORAGE


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
68.9
68.9
72.1
72.1
72.1
69.7
69.7

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
8
147
147
147
147
147
147
147

CO2 Level
(ppm)
400
580
580
580
580
580
590
590

Sensible
Heat
(BTU/hr)
-129
0
516
0
-386
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-408

Zone
T-stat
Cond
Mode (BTU/hr)
Heating
-386

Zone
Temp
(F)
69.7

Zone
Airflow
(CFM)
147

CO2
Level
(ppm)
590

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 66 of 78

Air System Sizing Summary for 85.STORAGE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

85.STORAGE 2
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
846.0 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Jun 1500
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

1.7
20.1
19.5
1220
1220
1220
0.972
505.1
23.8
4.02

Tons
MBH
MBH
CFM
CFM
CFM

3.7
1220
1220
0.37

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Jun 1500
106.0 / 75.0
74.1 / 63.7
59.3 / 58.3
57.6
0.100
60
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
4.3
69.2 / 72.0 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

1220 CFM
1220 CFM
1.44 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

55 CFM
0.07 CFM/ft

CFM/person

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

55.30 CFM/person

Page 67 of 78

Zone Sizing Summary for 85.STORAGE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

85.STORAGE 2
UNDEF
SZCAV

Number of zones
Floor Area
Location

1
846.0 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
17.9

Design
Airflow
(CFM)
1220

Minimum
Airflow
(CFM)
1220

Time of
Peak Load
Jul 1400

Maximum
Heating
Load
(MBH)
2.6

Zone
Floor
Area
(ft)
846.0

Zone
CFM/ft
1.44

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
85. STORAGE 2

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

17.9

Jul 1400

1220

2.6

846.0

1.44

Page 68 of 78

Air System Design Load Summary for 85.STORAGE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jun 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
628 ft
2049
628 ft
883
476 ft
10073
476 ft
1718
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
603 ft
1057
603 ft
0
0 ft
0
0 ft
0
786 W
2682
0
0
0W
0
0
0
0W
0
0
0
1
245
205
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
1611
10
0%
0
0
17716
215
2601
0
17533
215
2702
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
1220 CFM
0
1220 CFM
0
55 CFM
1995
354
55 CFM
950
0
1220 CFM
0
1220 CFM
0
0
0
0%
0
0%
0
19528
569
3653
0
19528
571
0
0
0
3653
19528
571
3653
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 69 of 78

Zone Design Load Summary for 85.STORAGE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
628 ft
2024
628 ft
883
476 ft
10270
476 ft
1718
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
603 ft
1065
603 ft
0
0 ft
0
0 ft
0
786 W
2682
0
0
0W
0
0
0
0W
0
0
0
1
245
205
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
1629
10
0%
0
0
17914
215
2601
0

Page 70 of 78

System Psychrometrics for 85.STORAGE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

June DESIGN COOLING DAY, 1500

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
106.0
74.1
59.3
59.3
59.3
59.3
72.6
72.6

Specific
Humidity
(lb/lb)
0.01152
0.01023
0.01013
0.01013
0.01013
0.01013
0.01017
0.01017

Airflow
(CFM)
55
1220
1220
1220
1220
1220
1220
1220

CO2 Level
(ppm)
400
791
791
791
791
791
810
810

Sensible
Heat
(BTU/hr)
1995
19528
0
0
17533
0

Latent
Heat
(BTU/hr)
354
571
215
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
17716

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
17533

Zone
Temp
(F)
72.6

Zone
Airflow
(CFM)
1220

CO2
Level
(ppm)
810

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 71 of 78

System Psychrometrics for 85.STORAGE 2


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
69.2
69.2
72.0
72.0
72.0
69.9
69.9

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
55
1220
1220
1220
1220
1220
1220
1220

CO2 Level
(ppm)
400
609
609
609
609
609
619
619

Sensible
Heat
(BTU/hr)
-950
0
3653
0
-2702
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-2601

Zone
T-stat
Cond
Mode (BTU/hr)
Heating
-2702

Zone
Temp
(F)
69.9

Zone
Airflow
(CFM)
1220

CO2
Level
(ppm)
619

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 72 of 78

Air System Sizing Summary for 86.SHOPPING AREA PART 3


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

86.SHOPPING AREA PART 3


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
4459.5 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load
Total coil load
Sensible coil load
Coil CFM at Jun 1500
Max block CFM
Sum of peak zone CFM
Sensible heat ratio
ft/Ton
BTU/(hr-ft)
Water flow @ 10.0 F rise

17.9
214.7
182.3
8851
8851
8851
0.849
249.2
48.2
42.97

Tons
MBH
MBH
CFM
CFM
CFM

40.5
8851
8851
4.05

MBH
CFM
CFM
gpm

gpm

Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation

Jun 1500
106.0 / 75.0
78.5 / 66.1
59.4 / 58.2
57.3
0.100
62
58.0
1 of 1
0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load
Coil CFM at Des Htg
Max coil CFM
Water flow @ 20.0 F drop

Load occurs at
BTU/(hr-ft)
Ent. DB / Lvg DB

Des Htg
9.1
67.2 / 71.5 F

Supply Fan Sizing Data


Actual max CFM
Standard CFM
Actual max CFM/ft

8851 CFM
8846 CFM
1.98 CFM/ft

Fan motor BHP


Fan motor kW
Fan static

1526 CFM
0.34 CFM/ft

CFM/person

0.00 BHP
0.00 kW
0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM
CFM/ft

Hourly Analysis Program v4.80

12.30 CFM/person

Page 73 of 78

Zone Sizing Summary for 86.SHOPPING AREA PART 3


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

Air System Information


Air System Name
Equipment Class
Air System Type

86.SHOPPING AREA PART 3


UNDEF
SZCAV

Number of zones
Floor Area
Location

1
4459.5 ft
Sharjah, United Arab Emirates

Sizing Calculation Information


Calculation Months
Sizing Data

Jan to Dec
Calculated

Zone CFM Sizing


Space CFM Sizing

Sum of space airflow rates


Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
129.9

Design
Airflow
(CFM)
8851

Minimum
Airflow
(CFM)
8851

Time of
Peak Load
Jul 1400

Maximum
Heating
Load
(MBH)
14.1

Zone
Floor
Area
(ft)
4459.5

Zone
CFM/ft
1.98

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
86. SHOPPING AREA PART 3

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

129.9

Jul 1400

8851

14.1

4459.5

1.98

Page 74 of 78

Air System Design Load Summary for 86.SHOPPING AREA PART 3


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jun 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.0 F / 75.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
366 ft
2793
366 ft
1657 ft
5350
1657 ft
2331
2713 ft
57428
2713 ft
9794
366 ft
3829
366 ft
1957
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
4143 W
14136
0
0
0W
0
0
0
1000 W
3412
0
0
124
30380
25420
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
11733
1271
0%
0
0
129060
26691
14082
0
127519
26691
14224
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
8851 CFM
0
8851 CFM
0
1526 CFM
54751
5783
1526 CFM
26292
0
8851 CFM
0
8851 CFM
0
0
0
0%
0
0%
0
182271
32474
40516
0
182271
32478
0
0
0
40516
182271
32478
40516
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 75 of 78

Zone Design Load Summary for 86.SHOPPING AREA PART 3


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

04/05/2016
11:06AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 106.5 F / 74.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
OCCUPIED T-STAT 71.6 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
366 ft
2465
366 ft
1657 ft
5294
1657 ft
2331
2713 ft
58555
2713 ft
9794
366 ft
3882
366 ft
1957
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
4143 W
14136
0
0
0W
0
0
0
1000 W
3412
0
0
124
30380
25420
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
11812
1271
0%
0
0
129935
26691
14082
0

Page 76 of 78

System Psychrometrics for 86.SHOPPING AREA PART 3


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

June DESIGN COOLING DAY, 1500

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
106.0
78.5
59.4
59.4
59.4
59.4
72.8
72.8

Specific
Humidity
(lb/lb)
0.01152
0.01086
0.01009
0.01009
0.01009
0.01009
0.01072
0.01072

Airflow
(CFM)
1526
8851
8851
8851
8851
8851
8851
8851

CO2 Level
(ppm)
400
1165
1165
1165
1165
1165
1324
1324

Sensible
Heat
(BTU/hr)
54751
182271
0
0
127519
0

Latent
Heat
(BTU/hr)
5783
32478
26691
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
129060

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
127519

Zone
Temp
(F)
72.8

Zone
Airflow
(CFM)
8851

CO2
Level
(ppm)
1324

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 77 of 78

System Psychrometrics for 86.SHOPPING AREA PART 3


Project Name: SHARJAH SHOPPING MALL
Prepared by: Oman Technical

04/05/2016
11:06AM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
54.0
67.2
67.2
71.5
71.5
71.5
70.0
70.0

Specific
Humidity
(lb/lb)
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441
0.00441

Airflow
(CFM)
1526
8851
8851
8851
8851
8851
8851
8851

CO2 Level
(ppm)
400
441
441
441
441
441
450
450

Sensible
Heat
(BTU/hr)
-26292
0
40516
0
-14224
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)
Site Altitude = 16.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
-14082

Zone
T-stat
Cond
Mode (BTU/hr)
Heating
-14224

Zone
Temp
(F)
70.0

Zone
Airflow
(CFM)
8851

CO2
Level
(ppm)
450

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 78 of 78