Sei sulla pagina 1di 288

PowerLogicTM Ethernet Gateway EGX300

User Guide
63230-319-216B3
03/2013

Safety Information
Important Information
Read these instructions carefully and look at the equipment to become
familiar with the device before trying to install, operate, service or maintain it.
The following special messages may appear throughout this manual or on
the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of either symbol to a Danger or Warning safety label indicates that
an electrical hazard exists which will result in personal injury if the instructions are
not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury
or death.

DANGER indicates an imminently hazardous situation which, if not avoided, will


result in death or serious injury.

WARNING indicates a potentially hazardous situation which, if not avoided, can


result in death or serious injury.

CAUTION indicates a potentially hazardous situation which, if not avoided, can


result in minor or moderate injury.

NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this signal word.

Please note
Electrical equipment should be installed, operated, serviced and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.

Notices
FCC Part 15 Notice
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his
own expense. The Ringer Equivalence Number (REN) for the device optional
internal modem is 0.6. Connection to the device internal modem should be made
via an FCC Part 68 compliant telephone cord (not supplied). The device cannot be
used on a public coin phone service or party line services.
This Class A digital apparatus complies with Canadian ICES-003.

PowerLogicTM Ethernet Gateway EGX300


Table of Contents

63230-319-216B3
03/2013

Table of Contents
Introduction .......................................................................................................................... 1
Additional Resources ............................................................................................................. 1
Accessing the EGX Over a Network ................................................................................... 2
Logging in to the EGX ............................................................................................................ 2
EGX User Interface Overview .............................................................................................. 3
Setup ..................................................................................................................................... 4
Ethernet and TCP/IP Settings ................................................................................................ 4
Advanced Ethernet Settings ............................................................................................. 5
Duplicate IP Address Detection........................................................................................ 7
Serial Port .............................................................................................................................. 8
Advanced Serial Port Settings.......................................................................................... 9
Remote Device Connections ................................................................................................ 10
EGX Device List ................................................................................................................... 11
Connecting Devices to an EGX ...................................................................................... 11
Device List Setup............................................................................................................ 12
Device Discovery............................................................................................................ 14
Device Logging .................................................................................................................... 16
Interval Data Logging ..................................................................................................... 16
Set Up Interval Logging .................................................................................................. 17
Topics to Log .................................................................................................................. 18
Device Log Export ................................................................................................................ 19
E-mail Export .................................................................................................................. 19
FTP Export ..................................................................................................................... 20
HTTP Export................................................................................................................... 21
Date and Time ...................................................................................................................... 23
Network Time Synchronization....................................................................................... 23
SNMP Parameters ............................................................................................................... 24
Modbus TCP/IP Filtering ...................................................................................................... 25
Documentation Links ............................................................................................................ 26
User Accounts ...................................................................................................................... 27
Web Page Access ................................................................................................................ 28
Add/Remove Custom Web Pages.................................................................................. 29
Adding Web Pages Using FTP....................................................................................... 29
Deleting Web Pages Using FTP..................................................................................... 29
Add/Remove Web Pages to/from the Web Interface...................................................... 30
Preferences .......................................................................................................................... 30
Viewable Device Types ........................................................................................................ 31
Audit Trail ............................................................................................................................. 32
System Access Point ........................................................................................................... 35
Monitoring ........................................................................................................................... 36
Real Time Data .................................................................................................................... 36
Single Device Pages ...................................................................................................... 36
Basic Readings Settings................................................................................................. 36
Analog Gauge Range ..................................................................................................... 37
Summary Device Pages ................................................................................................. 37
Trending ......................................................................................................................... 38
Device Logging .................................................................................................................... 39
Single Device Pages ...................................................................................................... 39
Getting a Data Log ......................................................................................................... 40
Log Format ..................................................................................................................... 41
Error Codes for Data Logs.............................................................................................. 42
Getting an Interval Data Log using FTP ......................................................................... 42
Getting an Interval Data Log Using the Data Points Button ........................................... 42
2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300

63230-319-216B3
03/2013

Getting an Interval Data Log Using the Microsoft Web Query Feature .......................... 43
Getting an Interval Data Log Using E-mail ..................................................................... 43
Getting an Interval Data Log Using HTTP ...................................................................... 43
Summary Device Pages ................................................................................................. 43
Dashboards .......................................................................................................................... 45
Viewing a Dashboard ..................................................................................................... 45
Getting Dashboard Data Using the Data Points Button.................................................. 46
Saving a Dashboard Link ............................................................................................... 46
Saving a Dashboard as an Image .................................................................................. 47
System Access Point ........................................................................................................... 48
Documentation ................................................................................................................... 48
Control ................................................................................................................................ 49
Diagnostics ......................................................................................................................... 49
Statistics ............................................................................................................................... 49
Interpreting Statistics ...................................................................................................... 51
Read Device Registers ........................................................................................................ 54
Communications Check ....................................................................................................... 55
Automated Communications Check ............................................................................... 55
Manual Communications Check..................................................................................... 55
Maintenance ....................................................................................................................... 56
Firmware ............................................................................................................................. 56
Finding the Firmware Version .............................................................................................. 56
Executable Binary Component Firmware Version.......................................................... 57
Disk Image Version ........................................................................................................ 57
Getting New Firmware ......................................................................................................... 57
Updating the Firmware ......................................................................................................... 58
Appendix ASupported Ethernet Protocols .................................................................. 59
Hardware .............................................................................................................................. 59
Appendix BSupported Device Types ............................................................................ 60

ii

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Introduction

63230-319-216B3
03/2013

INTRODUCTION

The EGX300 is an Ethernet-based device providing a transparent interface


between Ethernet-based networks and field devices. Field devices include
meters, monitors, protective relays, PLCs, trip units, motor controls, and
other devices that communicate using Modbus, Jbus, or PowerLogic
protocol.
The EGX300 uses Modbus TCP/IP protocol to access field device
information across a local area network (LAN) or a wide area network
(WAN). This capability allows the use of monitoring software to access
information from devices for data collection, trending, alarm/event
management, analysis, and other functions.
The EGX300 supports real-time data reporting from many common device
types providing several device-specific features. Reports such as on-board
device and circuit summary pages, as well as on-board data logging and
real-time trending are available.
Figure 1:

EGX300 Overview
Real-Time Views

View device data


through a simple
browser - no software

Real-Time Trends
EGX300 Web Pages

Data Log Trends


Control Resets

EGX300

Pull information into


web pages from other
PowerLogic gateways
and Modbus TCP/IP
interfaces such as
ECC21s and PM8ECCs.

ION 6200

Additional Resources

2009-2013 Schneider Electric. All Rights Reserved.

PM800

EGX100

Micrologic

Sepam

Go to www.schneider-electric.com and enter EGX300 in the search field.


Navigate to the EGX Documents & Downloads.

PowerLogicTM Ethernet Gateway EGX300


Accessing the EGX Over a Network

ACCESSING THE EGX OVER A


NETWORK

63230-319-216B3
03/2013

After you set up the EGX Ethernet parameters (see the EGX installation
guide), you can access the EGX over an Ethernet LAN using any standard
web browser.

Logging in to the EGX


Action

Result

1. Launch the web browser.

Opens the web browser.

2. In the Address bar, type the address of


your EGX (169.254.0.10 is the default),
then press Enter.

Opens the Login dialog box.

3. Type your user name (Administrator is the Enters the user name and password, then
default) and password (Gateway is the
opens the EGX home page.
default) into the text boxes, then click OK.
NOTE: The user name and password are
case-sensitive.
4. Click the appropriate item from the Menu
bar.

Figure 2:

Opens the selected Menu item.

The EGX Home Page

Menu bar

We recommend logging out whenever you do not need access to the EGX.
To log out of the EGX session, click Log Out or just close your browser.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


EGX User Interface Overview

63230-319-216B3
03/2013

EGX USER INTERFACE


OVERVIEW

The EGX user interface consists of multiple web pages used for device
monitoring and control, and EGX diagnostics and setup. See Table 1 for a
description of each web page.
Table 1:

EGX Pages

EGX Web Page

Description

See
Page

Setup
Ethernet & TCP/IP

Configure Ethernet and TCP/IP communication settings.

Serial Port

Configure serial communication parameters.

Remote Device Connections Configure remote Modbus TCP/IP device connections.

10

Device List

11

Configure, identify, or verify local serial devices on the


daisy chain. Remote devices can only be configured or
verified.

Device Logging

Configure device logging parameters.

16

Device Log Export

Configure device logging export options.

19

Date and Time1

Set date and time manually or with SNTP parameters.

23

SNMP Parameters1

Configure Simple Network Management Protocol (SNMP).

24

Modbus TCP/IP Filtering1

Configure which IP addresses can access the EGX through


Modbus TCP/IP.

25

Documentation Links

Configure file and URL documentation links.

26

User Accounts1

Create and edit groups and users.

27

Web Page Access1

Configure web page access rights for each user group.

28

Preferences

Configure EGX preferences.

30

Viewable Device Types

Configure which supported device types are viewable in the


EGX Device List web page.

31

Audit Trail1

Configure the ways in which the EGX will report system


messages: via the maintenance log, e-mail, and remote
Syslog server.

32

System Access Point1

Enable and configure the group IP address for multiple


EGX300s, allowing them to discover each other, viewing
each others information.

35

Real Time Data

The Single Device Pages table view provides basic


readings of selected devices. The Summary Device Pages
table view provides summaries of one or more selected
devices. The Trending Page view provides
real-time graphic and table trending of common topics
across multiple devices.

36

Device Logging

The Single Device Pages provide graphic and table


trending logs of user-selectable quantities for selected
devices. The Summary Device Pages provide graphic
trending logs of multiple devices with a common topic.

39

Dashboards

The Dashboards provide graphic and table representations


of energy consumption information aggregated over time
for all devices enabled for data logging.

45

System Access Point

The System Access Point page displays EGX300s and


other networked system devices that are accessible from
this EGX300. Each line is a hyperlink to the EGX300 log-in
page.

48

Accesses relevant EGX documentation and user


configured documentation links.

48

Provides for the execution of resets defined for the device,


and displays the date and time each reset function was
performed.
Date and time resets are shown only when the device
supports them.

49

Monitoring

Documentation
Documentation
Control
Resets

2009-2013 Schneider Electric. All Rights Reserved.

Accessible by administrator only

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Table 1:

EGX Pages

EGX Web Page


Diagnostics
Statistics

Displays diagnostic data used to troubleshoot network


problems. This page also contains information about your
specific EGX, including the serial number, manufacturing
date, and Media Access Control (MAC) address.

49

Read Device Registers

Allows users to read register data from local and remote


devices connected to the EGX.

54

Communications Check

Verifies the communications health of all devices


configured on the EGX.

55

Shows the date, time, and user who last performed


maintenance on the equipment, and provides entry detail
on the maintenance performed

56

Maintenance
Maintenance Log

SETUP

See
Page

Description

Accessible by administrator only

To access the Setup web page links, click Setup on the EGX menu bar.

Ethernet and TCP/IP Settings


Action

Result

1. From the Setup menu, click Ethernet &


TCP/IP.

Opens the Ethernet & TCP/IP page.

2. Select your frame format and media type.


Contact your network administrator if you
do not know.

Selects the frame format and media type.

3. Enter your IP address, subnet mask, and


default gateway address assigned to your
EGX by your network administrator.

Enters the Ethernet parameters for the EGX.


NOTE: If you enter an IP address that is used
by another device, you will be prompted to
select a new IP address. See Duplicate IP
Address Detection on page 7.

4. Click Apply.

Updates the EGX Ethernet and TCP/IP


settings.

* See Table 2 below for a list of options.

Figure 3:

Ethernet & TCP/IP Page

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Table 2:

EGX Ethernet and TCP/IP Settings

Option

Description

Setting

Frame Format

Used to select the format for data sent over Ethernet II, 802.3 SNAP
an Ethernet connection.
Default: Ethernet II

Media Type

Used to define the physical Ethernet


connection or media type.

Obtain IP Address
Automatically

Used to automatically obtain an IP address Enabled or disabled


from a BootP server.
Default: Disabled
NOTE: Requires network administration
support.

IP Address

Used to enter the static IP address of the


EGX.

Subnet Mask

Used to enter the Ethernet IP subnet mask Default: 255.255.0.0


address of your network.

Default Gateway

Used to enter the gateway (router) IP


Default: 0.0.0.0
address used for wide area network (WAN)
communications.

10T/100Tx Auto
10BaseT-HD
10BaseT-FD
100BaseTX-HD
100BaseTX-FD

Default: 10T/100Tx Auto

Default: 169.254.0.10

Advanced Ethernet Settings


IMPAIRED NETWORK PERFORMANCE
Only qualified workers should modify the advanced Ethernet settings of
the EGX. Such modifications should be performed only after reading
about and understanding the advanced Ethernet settings.
Failure to follow these instructions can impair network performance.

Action

Result

1. Click Advanced on the Ethernet & TCP/IP Opens the Advanced Ethernet Settings page.
page.
2. Configure the advanced Ethernet settings
(see Table 3 on page 6 for available
options). Click Defaults to select the
default values for all options.

Sets up the advanced Ethernet settings.

3. Click Apply.

Updates the EGX Ethernet and TCP/IP


settings.

NOTE: Applying changes to the Advanced


Ethernet Settings page does not save
changes to the Ethernet & TCP/IP page.
4. Click OK to approve the changes and to
reset the EGX.

2009-2013 Schneider Electric. All Rights Reserved.

The EGX reboots.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 4:

Table 3:

Advanced Ethernet Settings Page

EGX Advanced Ethernet Settings

Option

Description

Setting

Time To Live

Identifies the number of routers a TCP packet 1 to 255 hops


can pass.
Default: 60 hops

TCP Keep Alive

A timer that detects when a connected device 0 to 65,000 seconds


on an idle connection becomes unavailable
Default: 30 seconds
due to events such as a reboot or shutdown.
A setting of 0 disables this setting.

BootP Timeout

Used to specify how long the EGX will wait for 0 to 60 seconds
a BootP server to assign its IP address. (The Default: 15 seconds
default IP address is used after timeout if no
IP address is assigned.)

ARP Cache Timeout

Used to specify how long entries in the


0 to 65,000 minutes
Address Resolution Protocol (ARP) table are Default: 15 minutes
kept.

FTP Server

Controls whether the FTP server initializes


during startup.

FTP Connection Idle


Time

A timer that closes the FTP connection after a 30 to 900 seconds


specified amount of idle time.
Default: 120 seconds

HTTP Connection Idle


Time

A timer that closes the HTTP connection after 0 to 65,000 seconds


a specified amount of idle time.
Default: 4 seconds

HTTP Port Number

The TCP port used for HTTP messages. The 0 to 65,000


following port numbers are reserved for other Default: 80
network protocols and cannot be used: 20
0 - disables HTTP port
and 21 (FTP) and 502 (Modbus TCP/IP).

HTTPS Port Number

The TCP port used for HTTPS messages.


1 to 65,000
The EGX comes with a self-signed certificate. Default: 443
To make the EGX a fully trusted server, you 0 - disables HTTPS port
must acquire a certificate from a Certificate
Authority (e.g., VeriSign Authentication
Services).

Disabled or Enabled
Default: Enabled

To add/install a digital certificate, manually


navigate to the certificate update page using
the URL http://x.x.x.x./update_certs_shtml,
where x.x.x.x is the IP address of the EGX.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Table 3:

EGX Advanced Ethernet Settings

Option
HTTP Maximum
Keepalives

Description
Used to specify the maximum number of
HTTP keepalives available.

Modbus TCP/IP Server Used to specify the number of Modbus


Connections
TCP/IP server connections available.

0 to 65,000
Default: 100
16 to 64
Default: 32

Modbus Broadcast

Determines how Modbus TCP/IP messages Disabled, Enabled, or


with Unit IDs of 0 are handled on the serial Enabled with Response
subnetwork. Disabled = all messages are
Default: Disabled
ignored. Enabled = all messages are treated
as broadcasts to serial ports with no response
expected. Enabled with Response = all
messages are treated as regular messages
to serial ports with a response expected back.

Modbus TCP Proxy

Setting that determines if Modbus TCP/IP


messages from remote clients will be routed
to remote Modbus TCP/IP devices that are
defined in the EGX.

Modbus TCP/IP Client


Timeout

Amount of time the EGX will wait for a remote 0.1 to 10


Modbus TCP/IP device to respond to a
Default: 5 seconds
Modbus TCP/IP request initiated by the EGX.

Modbus TCP/IP Client


Connection Timeout

Amount of time the EGX will wait for a remote 1 to 10


Modbus TCP/IP device to respond to a
Default: 2 seconds
Modbus TCP/IP connection request initiated
by the EGX.

Modbus TCP/IP Server A timer that closes the Modbus TCP/IP


Connection Idle Time
connection after a specified amount of idle
time. A setting of 0 disables this setting.

Duplicate IP Address Detection

Setting

Disabled or Enabled
Default: Enabled

0 to 32,767 seconds
Default: 0

While connected to your network, the EGX publishes its IP address. To


avoid any duplicate IP address conflicts, the EGX uses the Address
Resolution Protocol (ARP) to see if any other device on your network is
using the same IP address. Table 4 below explains how the EGX handles a
duplicate IP address when it is detected.
Table 4:

Duplicate IP Detection Scenarios

Scenario
Boot Process /
Power Restore
Ethernet Link Detected

Duplicate IP Detected

Power/Status LED

Reverts to the default EGX IP address, Four blinks, pause pattern


subnet mask, and gateway address.
ARP requests are sent every 15
seconds until the IP address is
available. When the IP address
becomes available, the EGX will use it.

Manual Address Change EGX keeps its previous IP address and


displays a message indicating that the
IP address is already in use by another
device.

Receives an ARP request Reverts to the default EGX IP address, Four blinks, pause pattern
subnet mask, and gateway address if a
connected device sends four ARP
requests for the EGXs IP address. The
EGX will send ARP requests every 15
seconds until the IP address is
available again. When the IP address
becomes available, the EGX will use it.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Serial Port
Action

Result

1. From the Setup menu, click Serial Port.

Opens the Serial Port page.

2. Select your physical interface,


Selects the serial port options.
transmission mode, baud rate, parity, and
response timeout (see Table 5 on page 8).
3. Click Apply.

Updates the EGX Serial Port settings.

Figure 5:

Serial Port Page

Table 5:

Serial Port Settings

Option

Description

Setting

Physical Interface

Used to select how the EGX serial port is


physically wired.

RS485 4-wire, RS485 2-wire,


or RS232
Default: RS485 2-wire

Transmission
Mode

Used to select how data is transmitted over


a serial connection.

Automatic
Modbus ASCII

NOTE: Automatic mode allows


you to communicate to
Modbus RTU, Jbus, and
PowerLogic (SY/MAX) slave
devices on the same daisy
chain.
Baud Rate

Used to select the data transmission speed 2400, 4800, 9600, 19200,
over a serial connection.
38400, 56000*, or 57600*
Default: 19200

Parity

Used to select the type of parity required to Even, Odd, or None


check data accuracy by using a parity bit. Default: Even

Response Timeout Used to select how long the EGX will wait 0.1 to 10 seconds
to receive a response from a serial device. Default: 3 seconds
* Available only if the physical interface and transmission mode is RS232/Modbus ASCII.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Advanced Serial Port Settings


IMPAIRED NETWORK PERFORMANCE
Only qualified workers should modify the advanced serial port settings of
the EGX. Such modifications should be performed only after reading
about and understanding the advanced serial port settings.
Failure to follow these instructions can impair serial communication
performance.

Action

Result

1. Click Advanced on the Serial Port page.

Opens the Advanced Serial Port Settings page.

2. Configure the advanced serial port settings Sets up the advanced serial port settings.
(see Table 6 on page 11 for available
options). Click Defaults to select the
default values for all options.
3. Click Apply.

Updates the EGX advanced serial port settings.

NOTE: Applying changes to the Advanced


Serial Port Settings page does not save
changes to the Serial Port page.

Figure 6:

Advanced Serial Port Page

Table 6:

Advanced Serial Port Settings

Option

Description

Setting

Delay Between
Frames

Defines the minimum silent time between


the end of a received response and the
beginning of a new request on the serial
line.

Silent Interval
Extension

Allows the silent interval used to signify the 0 to 15 characters


Default: 6 characters
end of a ModbusRTU packet to be
extended beyond the 3.5 characters
defined by the standard.

0 to 100 milliseconds
Default: 50 milliseconds

Modbus TCP/IP
Indicates the exception response code
0x0A or 0x0B
Timeout Exception returned when a serial device connected to Default: 0x0B
Code
the EGX does not respond before the serial
port timeout. Modbus TCP/IP uses 0x0B.
However, in some legacy software suites,
0x0A was used.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

Remote Device Connections

63230-319-216B3
03/2013

The EGX can open connections for up to 16 unique, user-defined remote


Modbus TCP/IP devices. You can enter connections manually or select
them from a table of System Access Point-discovered connections (see
Figure 7). These connections are made available to the Device List Setup
for remote device configuration.
Action

Result

1. From the Setup menu, click Remote


Device Connections.

Opens the Remote Device Connections page.

2. To manually add a connection, enter the IP Enters the IP addresses of the remote devices.
addresses for the remote devices to which
you want to connect.
3. To add a System Access Point-discovered Enters the IP address of the selected System
connection, click Add (to the right of the
Access Point-discovered connection.
desired connection in the Discovered
Connections table).
4. Click Apply.

Figure 7:

10

Updates the EGX Remote Device Connections


settings.

Remote Device Connections

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

EGX Device List

Before you begin, keep in mind that you must not use serial slave
addresses 1 or 16 in Automatic transmission mode on a daisy chain with
mixed protocols (for example, a single daisy chain with some devices using
PowerLogic protocol and others using Modbus RTU/Jbus protocol).

Connecting Devices to an EGX

Figure 8 and Figure 9 illustrate how devices can be connected to the EGX.
To add those devices to the Device List, follow the steps in Device List
Setup on page 12.
Figure 8:

Topology - Serial Slave Devices Only

Ethernet
Connection

EGX300 Web Pages

EGX

RS485 connection

Serial Slave Devices

Figure 9:

Topology - Serial Slave and Remote Devices


Ethernet
Connection

EGX300 Web Pages


EGX100 IP
address:
169.254.0.28

Up to 16 remote IP connections
are possible

EGX300 IP
address:
169.254.0.75

RS485
connection

Remote Slave Devices

2009-2013 Schneider Electric. All Rights Reserved.

RS485 connection

Serial Slave Devices

11

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Device List Setup


Action

Result

1. From the Setup menu, click Device List.

Opens the Device List page. (See Figure 10 for


local-only connections, or see Figure 11 if
remote connections are available.)

2. You can use Discover to find locally


connected devices (see Device
Discovery on page 14). If remote device
configuration is required, proceed to step
3.

Opens the Device Discovery page to discover


all locally connected devices.

3. Refer to Figure 11 on page 13 and select


the number of viewable devices (1 to 64).

Selects the number of viewable locations that


can be used to define devices connected to the
EGX.

4. Select the Connection from the


drop-down list.*

Selects the connection.

5. Select the Device Type from the


drop-down list.*

Selects the device type.

6. In the Device Name text box, type the


device name.

Enters the device name.

7. In the Local ID text box, type the address Enters the local address of the device.
of the serial slave device if it is on the serial
port, or type the address you want to use to
access a remote device.*
8. In the Remote ID text box, type the
address of the remote device.*

Enters the address of the remote device.

9. Repeat steps 4 through 8 until all of the


devices are entered.

Enters all of the connected devices.

10. Click Apply.

Updates the Device List settings.

* This configuration parameter can only be changed if data logging is disabled for the device
being updated. See Device Logging on page 16.

Figure 10:

12

Device List Page

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 11:

Table 7:

Device List Page with Remote Connections Supported

Device List Settings

Option

2009-2013 Schneider Electric. All Rights Reserved.

Description

Setting

Number of Viewable Selects the number of devices to be


Devices
displayed.

1 to 64
Default: 8

Connection

Serial Port or IP Address


Default: Serial Port

Selects the connection site.

Device Type

Selects the device type to appear in the list. Range of supported devices.

Device Name

Allows you to name individual devices.

Local ID

You must define the Local ID.

Remote ID

You must define the Remote ID

13

PowerLogicTM Ethernet Gateway EGX300


Setup

Device Discovery

63230-319-216B3
03/2013

The Device Discovery option enables the EGX to discover Modbus devices
residing on the serial port that are not in the Device List. Devices that have
been previously entered into the Device List are validated regardless of the
discovery range set.
Discovery
When you begin Device Discovery, the EGX queries the local serial port
using a user-defined address range (see Figure 12 on page 15). Modbus
ASCII or RTU protocol is used for discovery on the serial connection,
depending on the current serial port configuration. If the device replies to the
query, the Local ID is set to the current discovery address, and the device is
given a default device name. The EGX then tries to identify the device type.
If the EGX recognizes the device type of the discovered device, the EGX
enters the recognized device type name in the Device Type field. If the EGX
does not recognize the device type, the Device Type field is set to the
default Modbus. A status field displays the discovery status.
Validation
All previously defined Device List entries for all connections (serial and
remote, in and out of the discovery start and end address range) are
validated during the discovery process. The validation protocol on the serial
connection is determined by the current configuration of the device in the
device list. Modbus TCP/IP protocol is used for validation of remote devices.
The EGX displays the local ID, stored device name, and stored device type
from the Device List, then queries the device. The device type identified by
the query is displayed, then compared to what was previously defined. The
status will then show if there is a difference found, or if the previously
defined configuration is valid.
NOTE: You can edit the device name and device type, and individually
select which devices to store in the Device List. However, if logging is
enabled for a device, you can only modify the name.

Action

Result

1. From the Setup menu, click Device List.

Opens the Device List page.

2. To discover locally connected devices,


click Discover.

Opens the Device Discovery page.

3. Enter a Start Address and End Address. Enters the discovery address range.
NOTE: Devices previously entered in the
device list with addresses (Local IDs) outside
the discovery range will be validated.
4. Click Start Discover. (click Stop Discover Begins to discover all connected and defined
to stop the process)
devices.
NOTE: Discovery only finds local serial
Modbus devices connected to the EGX.
Remote devices must be added manually.
See Remote Device Connections on
page 10.
5. Enter a new device name in the Name text Renames the device.
box.
6. Check the Save checkbox next to the
Selects or deselects a device entry to be saved
device you want to save to the Device List. or removed.
7. Click Apply in the Device Discovery
page.

14

Saves to the device list the device configuration


for all devices that have been marked to be
saved.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 12:

Table 8:
Option

Device Discovery

Device Discovery Options


Description

Setting

Start/End Address Defines the Modbus address range that will 1 to 247
be used to discover devices on the EGX
Default: Start: 1 End: 10
serial port.

2009-2013 Schneider Electric. All Rights Reserved.

Save

Allows you to save the selected device to


the Device List.

Enabled or Disabled
Default: Enabled

Connection

Displays the connection on which the


device was discovered or validated.

Serial Port or IP Address (for


remote device validation).

Defined

Lists the device type that was defined for


this device.

Assigned

Allows you to assign the device type from


the drop-down list.

Name

Allows you to enter a custom name for the


device.

Local ID

Displays the Local ID.

Remote ID

Displays the Remote ID.

Status

Displays the discovery or validation status. Valid, Unknown, Failed,


Found, Discovering, or
Attempting

15

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Device Logging

Logging is available for every device type supported by the EGX. The EGX
can log data received from both local and remotely connected devices at
predefined intervals (5, 10, 15, 20, 30, and 60 minutes). Below is an
explanation of how the EGX logs data and how to set up logging for a
device.

Interval Data Logging

Many devices in a power monitoring system do not have the ability to record
data in non-volatile memory. The EGX300 provides this data logging at
predefined intervals for up to 64 serially and remotely connected devices.
The EGX stores the recorded data in non-volatile FIFO (First In First Out)
files.
The logging capacity for each data-log file is variable and dependent on the
selected logging interval. Logging capacity of each data-log file can be
calculated by dividing the maximum possible number of recorded intervals a
data-log file can contain (171,072) by the product of the number of topics
logged and the intervals recorded per day.
Log File Capacity = Intervals (max) / (topics per interval * intervals recorded
per day)
For example, the logging capacity for a device data-log recording three
topics every 10-minutes would be determined as follows:
Intervals Recorded Per Day = Minutes per day / Logging Interval (in
minutes)
= 1440 / 10
= 144 intervals
Log File Capacity = Maximum Possible Intervals / (Topics logged per
interval * Intervals recorded per day)
= 171072 / (3 * 144)
= 396 days

The logging capacity is dynamically calculated and displayed on the Topic


Selection Page (see Table 9 for samples).
Table 9:

Sample Recording intervals

# of Topics

16

Log Capacity (in Days) for Designated Logging Intervals


5 Min Interval

10 Min Interval

15 Min Interval

594

1188

1782

297

594

891

198

396

594

148

297

445

118

237

356

99

198

297

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Set Up Interval Logging

Each device in the device list may be independently enabled for logging.
Topics to log are unique to each device. To view interval data logs, see
Device Logging on page 39.
NOTE: To enable the Device Logging feature, there must be a time value
selected in the Logging Interval drop-down window. We recommend that
you disable the logging feature for the specific device being configured. To
do this, see Figure 13 on page 17, and uncheck the logging check box for
the device being selected.
Action
1. From the Setup menu, click Device
Logging (see Figure 13).
2. See Figure 13 and check Logging for the
device(s) you want to log.
To select all devices, click select all,
then click Apply.
To deselect all devices, click clear,
then click Apply.
3. Select the Logging Interval.

Result
Opens the Device Logging page.
Selects the devices to log.

4. Click Apply.
OPTIONS
To customize logging content, enable device
logging, then do the following:
1. Select a logging interval other than zero,
and uncheck the specific device logging
selection checkbox.
2. Click topics under Customize for the
device you want to configure.
3. See Figure 14 and check the topics you
want to log.

Selects the logging interval for the selected


devices.
Updates the EGX Device Logging settings.

Selects the device topics to be logged, then


returns to the main Device Logging page.
NOTE: If you change the default topics
logged for a device, an asterisk (*) appears
next to topics in the Customize column for
that device. Changing the topics of a device
log that has already been active will clear all
previously logged data for that device. If
needed, the data should be retrieved from
the EGX prior to the changes.

To select all topics, click select all, then


click Apply.
To deselect all topics, click clear, then
click Apply.
To select the default topics, click
Defaults at the bottom of the screen.
To delete a data log, check Purge Data for the Selects the data logs to purge.
one(s) you want to delete.
NOTE: To purge a data log, the device
1. To select all devices, click select all, then
must not have the Logging check box
click Apply.
enabled.
2. To deselect all devices, click clear, then
click Apply.
To disable logging, select a logging interval of Turns off the logging feature.
zero, ensure the logging selections are
unchecked, then click Apply.

Figure 13:

2009-2013 Schneider Electric. All Rights Reserved.

Device Logging Page

17

PowerLogicTM Ethernet Gateway EGX300


Setup

Topics to Log

63230-319-216B3
03/2013

Topics for each device may be individually selected for logging.


Action

Result

1. From the Device Logging page, click the


topics link for the desired device.

Opens the topics selection page.

2. See Figure 14 and check the topic(s) you


want to log.

Selects the topics to log.

To select all topics, click select all.


To deselect all topics, click clear.
To select the default topics, click
Defaults.

3. Click Apply.

Figure 14:

18

Saves the topic selection to log.

Topic Selection Page

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Device Log Export

This option allows you to export device logs in three ways: by E-Mail, FTP,
or HTTP. Each method is described in the following sections.
NOTE: If the E-Mail, FTP, or HTTP servers are not located on the same
Ethernet network segment as the EGX, be sure the EGX Default Gateway is
properly configured. See Ethernet and TCP/IP Settings on page 4.

E-mail Export
Action
1. From the Setup page, click Device Log
Export.

Result
Opens the Device Log Export page.

2. Select E-Mail as the mode of transport.

Opens the E-Mail device log export options.

3. Check the Incremental check box.

Selects only new interval data logged since the


last successful data export.

NOTE: If the transport is scheduled for


Hourly or Logging interval, the
incremental check box will be automatically
selected.
NOTE: If the Incremental check box is not
selected, the whole log file is sent via email attachment on each scheduled
interval.

4. Select Hourly, Daily, Weekly, Monthly, or Selects how often the data logs are sent.
Logging interval.
5. Depending on which options you selected Selects when the data logs are sent.
in the previous step, select the time of day,
day of the week, and/or the day of the
month.
6. In the From Address text box, type the e- Enters from whom the e-mail was sent.
mail address of the person administering
the device.
NOTE: A From e-mail address is required
because most SMTP servers require it.
7. In the To Addresses text boxes, type the Enters the e-mail addresses of the recipients
e-mail addresses (5 maximum) that will be
receiving the data logs (one address per
text box).
8. In the Server IP Address text boxes, enter Enters the address of the server delivering the
the address of the outgoing mail server
e-mail data logs.
(0.0.0.0 to 255.255.255.255).
NOTE: Contact your network administrator
if you do not know the address of the
Simple Mail Transfer Protocol (SMTP)
server.
9. In the Server TCP Port text box, enter the Enters the outgoing mail server delivery port.
outgoing mail server delivery port.
Default: 25
10. If the SMTP server requires login
information, enable the SMTP server
requires login check box.

Allows you to enter SMTP server login


information.

NOTE: The EGX supports Plain, Login,


CRAM-MD5, and Digest-MD5 access
authentication.
11. If you have checked the SMTP server
Records your SMTP server login information.
requires login check box, enter your
username and password in the text boxes.
12. Click Test E-mail to send a test e-mail
using the parameters you set, or click
Apply.

Sends a test e-mail, and/or applies the log


export e-mail settings.

NOTE: Clicking Test E-mail applies the


log export e-mail settings and sends a test
e-mail, and clicking Apply only applies the
settings.

2009-2013 Schneider Electric. All Rights Reserved.

19

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 15:

Device Log Export Page - E-mail

FTP Export
Action

Result

1. From the Setup page, click Device Log


Export.

Opens the Device Log Export page.

2. Select FTP as the mode of transport.

Opens the FTP device log export options.

3. Enable the Incremental check box.

Selects only new data logged since the last


good send interval to be sent.

NOTE: If the transport is scheduled for


Hourly or Logging interval, the
incremental check box will be automatically
selected.
NOTE: If the Incremental check box is not
selected, the whole log file is sent via FTP
on each scheduled interval.

4. Select Hourly, Daily, Weekly, Monthly, or Selects how often the data logs are
Logging interval.
transported.
5. Depending on which options you selected Selects when the data logs are transported.
in the previous step, select the time of day,
day of the week, and/or the day of the
month.
6. In the Server IP Address text boxes, enter Enters the address of the server transporting
the address of the outgoing FTP server
the data logs.
(0.0.0.0 to 255.255.255.255).
NOTE: Contact your network administrator
if you do not know the address of the File
Transfer Protocol (FTP) server.
7. In the Directory text box, enter the
directory.

Allows you to enter directory information for the


remote server.

8. Enter your username and password in the


text boxes.

Records your server login information.

9. Enable the Passive check box.

Sets FTP file transfer mode to passive.

10. Click Test to test the FTP parameters you


set, or click Apply.

Sends a test file to the FTP server and


directory, and/or applies the FTP settings.

NOTE: Clicking Test applies the log export


FTP settings and transfers a test file, and
clicking Apply only applies the settings.

20

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 16:

Device Log Export Page - FTP

NOTE: If the transport is scheduled for Hourly or Logging interval, the incremental check box
will automatically be selected.

HTTP Export
Action
1. From the Setup page, click Device Log
Export.

Result
Opens the Device Log Export page.

2. Select HTTP as the mode of transport.

Opens the HTTP device log export options.

3. Enable the Incremental check box.

Selects only new data logged since the last


good send interval to be sent.

NOTE: If the transport is scheduled for


Hourly or Logging interval, the
incremental check box will be automatically
selected.
NOTE: If the Incremental check box is not
selected, the whole log file is sent via
HTTP on each scheduled interval.

4. Select Hourly, Daily, Weekly, Monthly, or Selects how often the data logs are
Logging interval.
transported.
5. Depending on which options you selected Selects when the data logs are transported.
in the previous step, select the time of day,
day of the week, and/or day of the month.
6. In the Server IP Address text boxes, enter Enters the IP address of the server transporting
the address of the HTTP server.
the data logs.
NOTE: Contact your network administrator
if you do not know the address of the
Hyper Text Transfer Protocol (HTTP)
server.
7. In the Server TCP Port text box, enter the Enters the outgoing delivery TCP port.
HTTP server port.
Default: 80
NOTE: If you want to export using a secure
socket layer, enter the HTTPS Server TCP
Port number, normally 443.
8. If you are using a proxy server, enter the IP Enters the IP address of the proxy server
address in Proxy Server IP Address text
transporting the data logs.
boxes.
NOTE: Contact your network administrator
if you do not know the address of the proxy
server.

2009-2013 Schneider Electric. All Rights Reserved.

21

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Action

Result

9. In the Proxy Server TCP Port text box,


enter the HTTP server port.

Enters the outgoing delivery TCP port.


Default: 0

NOTE: If you want to export using a secure


socket layer, enter the HTTPS Server TCP
Port number, normally 443.
10. In the Path text box, enter the path to the Enters the server script path.
server script the web server will execute as
a result of the EGX posting data to it.
11. In the Field Name box, enter the name
Allows the EGX to push files to an existing
under which the web server will expect the WWW server script.
file name.
NOTE: If there is no such requirement, use
the default value datafile1.
12. In the Host Name box, enter the domain
name of the host.

Identifies a specific host on the WWW server if


it is hosting multiple domains on a single IP
address. (Blank by default)

13. Enter your user name and password in the Records your server login information.
text boxes.
14. If you want to export using a secure socket All device logs that are exported via HTTP will
layer, check SSL.
instead use the secure socket layer (HTTPS).
15. Click Test to test the HTTP parameters
you set, or click Apply.

Sends a test file to the HTTP server and


directory, and/or applies the HTTP settings.

NOTE: Clicking Test applies the log export


HTTP settings and transfers a test file.
Clicking Apply only applies the settings.

Figure 17:

22

Device Log Export Page - HTTP

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Date and Time

The Date and Time page allows you to set the date and time for the EGX.
Action

Result

1. From the Setup menu, click Date and


Time.

Opens the Date and Time page.

2. Configure the year, month, day, hour,


minutes, and seconds.

Sets up the date and time.

3. Select the Time Zone Offset.

Sets the clock to the selected time zone.

4. To set the clock to automatically adjust to Allows you to set the clock to adjust to Daylight
Daylight Savings Time, enable the Enable Savings Time automatically.
Automatic Daylight Savings Time
Adjustment check box.
5. Enter the number, day, month, and hour to Sets the beginning and end of the Daylight
begin and end Daylight Savings Time.
Savings Time adjustment.
6. Click Apply.

Figure 18:

Network Time Synchronization

Saves the Date and Time settings.

Date and Time Page

Enabling network time synchronization allows the time and date of the EGX
system clock to be set by a Network Time Protocol (NTP) server.
NOTE: If the NTP server is not located on the same Ethernet network
segment as the EGX, be sure the EGX Default Gateway is properly
configured.

Action

Result

1. Select the Enable Network Time


Reveals the SNTP Parameters section, and the
Synchronization check box in the Date and last successful time synchronization.
Time page.

2009-2013 Schneider Electric. All Rights Reserved.

2. Configure the time zone offset, poll


interval, and the primary and secondary
NTP server IP addresses (see Table 10).

Sets up the SNTP parameters.

3. Click Apply.

Saves the SNTP settings.

23

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 19:

Enable Network Time Synchronization

Table 10: SNTP Parameters Settings


Option

SNMP Parameters

Description

Setting

TIme Zone Offset

The time is set based on the Coordinated


Universal Time (UTC) value selected.

UTC-12:00 to UTC+13:00
Default: UTC (GMT)

Enable Automatic
Daylight Savings
Time Adjustment

Allows you to define when Daylight


Savings Time begins and ends.

First to Fifth or Final,


Sunday to Saturday,
January to December,
0:00 to 23:00
Default:
Begins Second Sunday of
March at 2:00.
Ends Second Sunday of
November at 2:00.

Poll Interval

Controls how often the EGX contacts the


NTP server for the correct time.

1 hour to 1 week
Default: 1 week

Primary NTP Server


IP Address

The IP address of the primary NTP server 0.0.0.0 to 255.255.255.255


the EGX contacts for the correct time.
Default: 0.0.0.0

Secondary NTP
Server IP Address

The IP address of the secondary NTP


server the EGX contacts for the correct
time.

0.0.0.0 to 255.255.255.255
Default: 0.0.0.0

The EGX supports SNMP, allowing a network administrator to remotely


access an EGX with an SNMP manager and view the networking status and
diagnostics of the EGX in the MIB-II format.

Action

Result

1. From the Setup menu, click SNMP Parameters. Opens the SNMP Parameters page.
2. Check Enable SNMP to turn ON the simple
network management protocol.

Activates SNMP.

3. Enter the system contact, system name, system Enters the SNMP system information and
location, read-only community name, and the
community access names.
read-write community name.
4. Click Apply.

24

Saves the SNMP settings.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 20:

Modbus TCP/IP Filtering

SNMP Parameters Page

This function allows the administrator to assign the level of access


Modbus TCP/IP clients have to the devices (local or remote) connected to
the EGX.
NOTE: There is an anonymous Modbus TCP/IP address (***.***.***.***) that
can be set to Read-only or None. Setting it to Read-only allows any
Modbus TCP/IP client not in the filtered list to access serial slave devices
with read-only access. Setting it to None blocks all Modbus TCP/IP clients
not in the filtered list.
Action
1. From the Setup menu, click Modbus
TCP/IP Filtering.

Result
Opens the Modbus TCP/IP Filtering page.

2. Check Enable Filtering.

Activates filtering.

3. In the IP address column, enter the


Modbus TCP/IP client address

Enters an IP address for a Modbus TCP/IP


client that will have access to the devices
connected to the EGX.

4. In the Access Level column, select Read- Selects the access level for the corresponding
only or Full.
IP address. When set to Read-only, the
following Modbus TCP/IP function codes are
allowed:
Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24,
43, 100
Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C,
11, 14, 18, 2B, 64

2009-2013 Schneider Electric. All Rights Reserved.

5. Repeat steps 3 and 4 to add more IP


addresses.

Continues adding IP addresses for filtering.

6. Click Apply.

Saves the Modbus TCP/IP address filtering list.

25

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 21:

Documentation Links

Modbus TCP/IP Filtering Page

The EGX supports two types of documentation links:


1. Local file access (documentation stored onboard the EGX)
2. External URL access.
NOTE: Local file documents you want to appear on the Documentation web
page must be placed in the EGX www/documentation folder using FTP.
Action

Result

1. From the Setup menu, click


Documentation Links.

Opens the Documentation Links page.

2. For File Access: Check Enabled for the


File Name link(s) you want to enable.

Checks which files and URLs appear on the


Documentation page.

For URL Access: Check Enabled for the


URL link(s) you want to enable.
3. Check New Window if you want the
selected files and URLs to open in a new
window when clicked.

Checks which files and URLs open in a new


window when clicked.

4. Name the documentation link title in the


Link Text text box.

Sets the documentation link title that will


appear on the Documentation page.

5. Click Apply.

Updates the EGX Documentation Link settings.

Figure 22:

Documentation Links Page

NOTE: For information on accessing the loaded documentation, see


Documentation on page 48.
26

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

User Accounts

EGX users are assigned user names and passwords. Each user belongs to
a group, and each group has access rights to the EGX Web pages assigned
by the EGX administrator.
NOTE: There are two default user accounts: Administrator (the default
password is Gateway) and Guest (the default password is Guest).
Action

Result

1. From the Setup menu, click User Accounts. Opens the User Accounts page.
2. If you want to change a group name, type a
new name in one of the Groups text boxes
(the Administrator group name cannot be
changed).

Enters a new group name.

3. In the Users section, enter a Name (1 to 24


characters) and Password (0 to 12
characters) for a new user.

Enters the name and password for a user.

NOTE: User names and passwords are


case-sensitive and can contain only
alphanumeric characters.

The EGX300 checks the strength of the


password, displaying both a color and textual
indication of strength:
Red = Blank Password/ Weak Password
Yellow = Medium Strength Password
Blue = Strong Password
Green = Very Strong Password

4. Select a group and the default language for


the new user.

Selects the group and language for a user.

5. Repeat steps 3 and 4 for each additional


user you want to add.

Continues adding users.

6. Click Apply.

Saves all of the user account settings.

Table 11: EGX accounts and passwords


Account
Administrator

Gateway

Guest

Guest

User-defined accounts (up to 11 accounts possible)

No default Password is user-defined

Figure 23:

2009-2013 Schneider Electric. All Rights Reserved.

Default Password

User Accounts Page

27

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Web Page Access


Action

Result

1. From the Setup menu, click Web Page Access. Opens the Web Page Access page.
2. Select the access level (None, Read-only, or
Full) that each user group will have for the web
pages.

See Table 12 below for an explanation of


access levels for each group.

3. To allow Guest access to the web page, select


Read-only under the Guest column.

Allows the default Guest group to access


the web page.

NOTE: If the Guest group is Read-only, other


groups may only be set to Read-only or Full.
4. Repeat steps 2 and 3 for the options in each
section.

Selects the access level for each web


page.

5. Click Apply.

Saves the password settings.

Table 12: Group Access


Group

Access

Administrator

Full access to all web pages


NOTE: We recommend that you change the default administrator
password for system security the first time you log in.

Guest

Read-only access to selected web pages.

Three user-defined
groups

Choosing from the following options, the administrator assigns web


page access for each group. Access levels are as follows:

Figure 24:

28

None: a group has no access to selected web page


Read-only: password grants a group read-only access to the
selected web page
Full: a group has the same access as the Administrator group to the
selected web page

Web Page Access Page

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Add/Remove Custom Web Pages

Custom web pages and other file types can be transferred from your
computer to the EGX via FTP. Files sent by FTP to the www/monitoring,
www/maintenance, or www/control directories with extensions of .htm,
.html, or .shtml will be automatically secured. Each folder has a
corresponding link on the menu bar in the web interface. When the link is
clicked on the menu bar, the web pages you added will appear in the menu
on the left side of the browser window under Custom Pages.
NOTE: You cannot create new folders inside of the Monitoring, Control, or
Maintenance folders.
After custom web pages or other files have been transferred to the EGX
with FTP, they can be added and removed from the web interface without
removing them from the EGX by using the Add/Remove Web Pages page.
This page is opened from the Web Page Access page.

Adding Web Pages Using FTP

Action

Result

1. Launch Windows Explorer, type ftp:// and


the IP address of the EGX (for example,
ftp://169.254.0.10) in the Address text box,
then press Enter.

Opens the Log On As dialog box.

2. Type the user name Administrator and the


administrator password in the text boxes,
then click Log On.

Opens an FTP session with the EGX.

3. Open a new Windows Explorer window,


locate the custom web page you want to
send to the EGX, right-click it, then click
Copy.

Copies the file to the clipboard.

4. Switch back to the EGX Windows Explorer


window you opened in Step 1, then open
the folder where the web page will be
copied (for example, /www/monitoring/).

Opens the folder where the web page will be


stored on the EGX.

5. Right-click in the right pane of the Windows Copies the custom web page to the EGX.
Explorer window, then click Paste.
NOTE: Instead of copying and pasting the
file, you can drag-and-drop the file into
Windows Explorer.
6. Click Close on the Windows Explorer
window.

Closes Windows Explorer.

Deleting Web Pages Using FTP


Action

Result

1. Launch Windows Explorer, type ftp:// and


the IP address of the EGX (for example,
ftp://169.254.0.10) in the Address text box,
then press Enter.

Opens the Log On As dialog box.

2. Type the user name Administrator and the


administrator password in the text boxes,
then click Log On.

Opens an FTP session with the EGX.

3. Open the folder where the custom web


Opens the folder where the custom web page
page is located, right-click the file you want is located, then deletes file.
to delete, then click Delete.
4. Click Close on the Windows Explorer
window.

2009-2013 Schneider Electric. All Rights Reserved.

Closes Windows Explorer.

29

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Add/Remove Web Pages to/from the Web


Interface

Action

Result

1. From the Setup menu, click Web Page


Access.

Opens the Web Page Access page.

2. Click Add/Remove Web Pages (see


Figure 25).

Opens the Add/Remove Web Pages page.

3. If you added custom web pages to any of


Selects or deselects a custom web page.
the EGX folders, you will see a list of file
names underneath the name of each folder.
Select the web pages you want your users
to see. Deselect web pages you do not
want your users to see.
NOTE: Deselecting a web page does not
delete it from the EGX.
4. Click Apply.

Figure 25:

Preferences

Adds or removes a custom web page from the


EGX web interface.

Add/Remove Web Pages Page

This option allows each EGX to be individually customized.


Action

Opens the Preferences page.

2. Enter the equipment name, default home


page, real time sample rate, and
communications check rate.

Sets the preferences.

3. Click Apply.

Updates the EGX Preferences settings.

Figure 26:

30

Result

1. From the Setup menu, click Preferences.

Preferences Page

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Table 13: Preferences Settings


Option

Description

Setting

Equipment Name

Allows you to enter a custom name for


Default: Powerlogic
the EGX and associated equipment. This EGX300
name will be used in the web interface
banner.

Default Home Page

Allows you to select the default


homepage.

Home,
Circuit Summary,
Load Current Summary,
Demand Current Summary,
Power Summary, or
Energy Summary
Default: Home

Real Time Sample Rate Controls how often data is read from the 5 to 60 seconds
device(s) in the standard Monitoring
Default: 5 seconds
Table views.
Communications Check Controls how often a communications
Rate
check is performed while the browser is
displaying real time readings in the
standard Monitoring Table views. This
function will attempt to automatically
bring any out of service devices back
into service.

Viewable Device Types

Disabled, 5 to 30 minutes
Default: 15 minutes

The Viewable Device Types page provides a means of managing the device
types available for user selection in the Device List Setup web page.
Because the EGX300 supports many different device types, removing
device types from the list of Available Device Types may simplify
configuration of the Device List Setup web page.
Action

Result

1. From the Setup menu, click Viewable


Device Types.

Opens the Viewable Device Types page.

2. Select the device types to make available


for the device list configuration.

Selects device types to be made available for


device list configuration.

NOTE: Click Select All to enable all


devices and Clear to disable all devices.
NOTE: Device Type Availability may not be
changed for devices that are currently in
use.
3. Click Apply.

2009-2013 Schneider Electric. All Rights Reserved.

Saves the Viewable Device Type settings.

31

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 27:

Audit Trail

Viewable Device Types Page

The Audit trail is a time-stamped sequence of records or messages. It


records configuration change, error, and failed authentication events; and it
identifies the user who initiated the event.
Use the Audit Trail page to set up the four report groups and message
channels. For each channel, you choose the report group(s) for which you
want to see messages. When you choose a report group for a channel, you
will see any of the messages that are generated in that report group.
The message channels are:

EGX on-board maintenance log file


Remote Syslog server (Syslog is a standard for logging messages)
E-Mail

All messages are date-time stamped, and they include the report group and
user identifying information.
The Audit Trail page is divided into three boxes that correspond to the three
message channels: Maintenance Log, Syslog, and E-Mail. (See Figure 28
on page 34.) You can independently configure the messages that are sent
to each channel.
From the Setup window, click Audit Trail. The Audit Trail page opens.
Follow instructions in the table below.

32

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Table 14: Audit Trail Setup


Option

Description

Setting

Maintenance Log
Controls the report types for
which you want messages to
display in the Message Log.

As messages are generated, they Check the report options


will display in the EGX on-board that you want to include.
maintenance log.
Default: no options checked

Syslog
Server IP Address.

As messages are generated, they Enter the IP address for the


will be forwarded to the server
remote server to which you
that you indicate.
want messages to be
forwarded.

Server UDP (user datagram


protocol) port

Syslog messages will be sent


from this server UDP port.

Enter the UDP port number


for this IP address. Default
= 514.

Report

The four report types for which


messages can be forwarded.

Check the report types for


which you want messages
to be forwarded.

Facility drop-down list

Provides a rough clue as to the


location in the system that
generated the message. Will
display in the Syslog.

Choose the appropriate


category.

Severity drop-down list

Tells the user the relative


importance of the message. You
must determine for your facility
the importance of each type.

Choose the appropriate


category.

When messages are generated,


the originator e-mail address will
display in the from field.

Enter the From e-mail


address (address of the
originator) for e-mails.
Maximum 49 characters.

E-Mail
From Address

The body of the e-mail will


include: EGX IP address, report
group name, user name, user IP
address, and the message from
the report group.

2009-2013 Schneider Electric. All Rights Reserved.

To Addresses

When messages are generated,


they will be sent to the recipient
e-mail address(es).

Enter the To e-mail


address (address of the
recipient of all message emails). Maximum 49
characters per address.

Server IP Address

This is the IP address for the


server where the e-mails will be
sent.

If you do not enter a server


IP address, no e-mails will
be sent.

Server TCP Port

This is the TCP port number for


the server IP address.

Enter the TCP port number.


The default is 25.

SMTP server requires login

Use this check box to enable


login for receiving e-mails. The
SMTP server requires login.

Check the box to begin


adding login information.

Username

This is the user name the EGX


will use to log on to the SMTP
server.

Type the username


required by the SMTP
server (max 31 characters).

Password

This is the password the EGX will Type the password required
use to log on to the SMTP server. by the SMTP server (max
31 characters).

Report

These are the report types for


which messages can be
forwarded. You can check as
many as you want.

Defaults/Apply

Click Apply to save the entries


Click Apply or Defaults.
you have made. Click Defaults to
return each field to its default
state.

Check the report types for


which you want messages.

33

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

Figure 28:

34

Audit Trail Setup

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3
03/2013

System Access Point

The system access point provides a means of discovering and linking to


other Schneider Electric devices connected to the network. This feature is
configured to run by default, with no need for additional configuration.
Use this setup screen to enter the group IP address and related information.
Action

Result

1. From the Setup menu, click System


Access Point.

Opens the System Access Point window.

2. Enabled

When checked, EGX300s with the same


Group IP Addresses will be able to discover
each other. Default = Enabled.

3. UDP Port

Type the port number (from 165535) for the


UDP port used by the System Access Point
discovery. Default = 59.

4. Group IP Address

Type the group IP address, which will support


multicast or unicast addresses. Default =
224.0.1.2.

5. Hello Time

This is the period of time between Hello


messages emitted by this EGX300 announcing
its presence to other Schneider Electric
System Access devices on the network. 1
65535 seconds, default = 300 seconds.

6. Hold TIme

This is the period of time that Hello messages


sent by this EGX300 should be held by
recipients before considering this EGX300
unavailable.
From 2 to 65535 seconds,
default = 600 seconds.

7. Multicast Time-to-Live

You can control how wide an area of the


network will be included to discover other
devices. This is controlled by the number of
times that the multicast is allowed to be
forwarded to others. The range of permitted
router hops is 1255. Default = 1.

8. Community

EGX300s in a group can be divided into


communities. EGX300s with the same group
IP address and community number are able to
discover each other.
Setting the community number to `0' allows an
EGX300 to discover all EGX300s with the
same group IP address without regard to the
community setting. Default: 0

9. Defaults/Apply

Figure 29:

2009-2013 Schneider Electric. All Rights Reserved.

Click Apply to save your entries; click Defaults


to return to the defaults that are listed.

System Access Point Setup Page

35

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

MONITORING

The EGX provides screen displays to view real-time data and trends along
with historical data log trends.

Real Time Data

The Real Time Data pages provide basic readings of selected devices in
real time, as well as device summaries.

Single Device Pages

To view a table of real time data, go to the Monitoring menu and select a
device under Real Time Data > Single Device Pages.

Basic Readings Settings


Action

Result

1. At the top of the display, select either Load Current, Selects the quantities to be displayed
Power, Voltage LL, or Voltage LN to be displayed on the Analog Gauge graphic display.
on the Analog Gauge graphic display.
NOTE: Analog gauges are not
available for all device types.
2. By default, the gauges will automatically adjust their Controls the display range of the
display range. For a fixed range, select Range.
Analog Gauges.
Instructions for configuring the analog gauge range
are listed in the next table.
3. Click Apply.

Figure 30:

36

Updates the Gauge selection for the


device page.

Basic Readings Page

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

Analog Gauge Range

The range of the Graphic Analog Gauges on the Basic Readings page may
be configured or set to scale automatically (Figure 31).
Action

Result

1. Under Enable Auto Scale, check the


Enables auto scale for selected devices.
devices you wish the gauges to auto-scale.
NOTE: Click Select All to enable auto
scale for all devices and Clear to disable
auto scale for all devices.
2. For devices with auto scale disabled, enter Set gauge range.
the Min and Max limits for each gauge
type.
3. Click Apply.

Figure 31:

Summary Device Pages

Updates the Auto Scale settings.

Range Setup Page

The Summary Device table views provide summaries of one or more


selected devices.
Action
1. From the Monitoring menu, click Summary Device
Pages.

Result
Expands tree for summary page
selection choices.

2. Select which summary page you want to view.

Opens the device selection list.

3. Select a device(s) from the Available Devices list,


then click Next (see Figure 32).

Selects a device(s) for the summary


options.

NOTE: Click >> to select all available devices.

2009-2013 Schneider Electric. All Rights Reserved.

Figure 32:

Device Selection Page

Figure 33:

Circuit Summary Page

37

PowerLogicTM Ethernet Gateway EGX300


Monitoring

Trending

63230-319-216B3
03/2013

To view a real time trend of multiple devices and topics, go to the Monitoring
Menu and select Real Time Data > Trending.
Action

Result

1. From the Monitoring menu, select Real Time Data.

Expands the data tree for real


time data option selection.

2. Select Trending.

Expands the data tree for time


trending option selection

3. Select Real Time Trending.

Opens the Real Time Trending


setup page.

4. Select up to four device from the Available Devices list.

Selects devices for trending.

5. Select a topic(s) from the Available Topics list.

Selects topics for trending.

NOTE: Only topics common to all selected devices are


available for trending. The maximum number of topics to
trend is dependent on the number of devices selected.
The product of the selected devices and topics must be 8
or less.
6. Click Next to open the Real Time Trending display page. Real Time Trending display
page opens.
7. To set the trending parameters, continue to the
procedure in the next table and refer to Figure 35.

Figure 34:

Allows trending parameters to


be set.

Select Devices and Topics

Action
1. Select Absolute or Relative trending.

Result
Selects graph mode.

NOTE: Absolute redraws the graphs x-axis after each


sample, filling it with all the data collected since the start of
the trend. Relative updates the graph with the latest data
after each sample while the x-axis stays constant to show
the overall trend time selected.
2. Choose a trend time of 1 to 15 minutes. This will be the
duration of the trend.

Selects the amount of time of


the trend.

NOTE: Data samples are taken as fast as possible but


may take longer depending on the communications load
on the serial sub-net and/or remote devices.
3. Select Start Sampling to start the trending of the selected Starts trending.
device topics.
NOTE: Trending may be stopped before reaching the
trend time by clicking Stop Sampling. If after stopping the
sampling, Start Sampling is pressed, a new trend is
started.

38

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

Action

Result

4. Press Data Points to view a log of all the sampled topics


recorded during the trend time.

Displays a log of all topic values


sampled during the trend.

NOTE: After each interval, the Present value of all topics


along with the calculated Min, Max, and Average value is
populated in the table below the graph.
5. Press New Topics to reselect devices and topics to trend. Navigates back to the Real
Time Trending setup page.

Figure 35:

Real Time Trending

Device Logging

Device Logging Pages provide graphic and table representations of


selected device log data. For more details on configuring device logging,
see Device Logging on page 16.

Single Device Pages

Single Device pages provide graphic and table representations of data


logged from a single device.
Action

Result

1. From the Monitoring menu, click Device


Logging.

Expands tree to show available device logging


choices.

2. Under Device Logging, click Single


Device Pages.

Expands tree to show available devices that


have logged data available for viewing.

3. Select a device from the Device Logging


list.

Displays the device log for the selected device.

4. To view a data range, select a range from


the data range drop down list.

Plots the selected data range.

5. Hold down the left mouse button and drag


a selection box around a graph area to
zoom in on it.

Zooms in on the selected graph area.

6. To return to the original full view, type Z on The view zooms out.
your keyboard, or double-click on the
graph.
7. Click Data Points to view the selected
interval data log table (see Figure 37
below).

Opens the selected Interval Data Log table.

8. To view different topics, click New


Enables the display of the selected topic(s).
Topic(s). Enable the check box(es) of the
topic(s) you wish to display, and then click
Apply.

2009-2013 Schneider Electric. All Rights Reserved.

39

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

The data logged from each device is displayed in a web page in a time-trend
chart format. The time-trend chart is preconfigured to display data from the
Last Full Day, Last Full Week, Last Full Month, or All Data.
Energy parameters are logged as accumulating values but are displayed as
incremental values on an interval basis. All other parameters are logged and
displayed as the actual value recorded.

Getting a Data Log

Figure 36:

Interval Data Log Graph

Figure 37:

Interval Data Log Data Points Table

Interval data logs can be retrieved using the methods in Table 15:
Table 15: Interval data log retrieval methods and file formats
Retrieval Method
FTP

File Format Retrieved


Comma separated variable (CSV)

Data points button

HTML

Microsoft WebQuery

HTML

E-mail

CSV

HTTP

CSV

To view a list of all available log files, follow steps 2 through 4 in the section
Getting an Interval Data Log using FTP on page 42. Files will be in the
format: Device Name_Local ID.csv where Device Name is the name
given to the slave device and Local ID is the numerical Local ID assigned
to it. For example, a device named Building 1 Utility Entrance with a Local
ID of 3 would be Building 1 Utility Entrance_3.csv.
When log files are exported the date and time are appended to the file name
in the following format: _YYYYMMDDHHMMSS. For example, Building 1
Utility Entrance_3_20100218115216.csv. This indicates that the file was
exported on 2010 February 18 at 11:52:16 AM.

40

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

Log Format

Data is logged in the following format (see Figure 38 on page 41):


Table 16: Interval data log format
Row

Data in CSV Format

Description

(BOM)Gateway Name,Gateway
This row contains the column headings
SN,Gateway Address,Device Name,Device for the information in row 2.
Local ID,Device Type Name,Logging Interval
NOTE: (BOM) The first three bytes of the file
will be a 3-character Byte Order Mark
indicating UTF-8.

EGX300SD,23227,157.198.184.116,Building This row contains the information about


1 Utility Entrance,3, CM4000,15
the EGX and the logged device.

This row is blank.

,,,Topic ID 1,Topic ID 2,Topic ID 3

This row contains the column headings


for the topic IDs in row 5. A topic ID is a
numerical reference to the quantity being
logged. The name given to a quantity
may differ slightly between devices and
languages. Topic IDs are used to identify
the quantity, regardless of the device or
language. The first three commas are
used for layout purposes in a
spreadsheet application.

,,,1617,1621,1625

This row contains the topic IDs of the


values logged.

This row is blank.

Error,UTC Offset (Minutes),Local Time


This row contains the column headings
Stamp,Apparent Energy (kVAh),Real Energy for the data logged in rows 8 and higher.
(kWh), Reactive Energy (kVARh)

8 and These rows contain the logged data.


higher
0,-300,2008-10-09 14:15:00,1400738.219,1201962.707,647069.906,15
0,-300,2008-10-09 14:20:00,1400758.260,1201980.725,647078.602,15
0,-300,2008-10-09 14:25:00,1400778.198,1201998.661,647087.233,15

If you use a spreadsheet application to view the CSV file, your data should
look similar to Figure 38 on page 41.
Figure 38:

2009-2013 Schneider Electric. All Rights Reserved.

Interval Data Log Opened in a Spreadsheet Application

41

PowerLogicTM Ethernet Gateway EGX300


Monitoring

Error Codes for Data Logs

63230-319-216B3
03/2013

The below error codes may be seen when troubleshooting data logs (see
Figure 36 on page 40 and Figure 37 on page 40):
Error
Code

Definition

Result

19

Communication Error occurred (for example: CRC,


protocol, or exception).

Logging is left enabled unless


the last interval was missed.

25

Timeout occurred when a request was sent without


receiving a corresponding response within the
allowed time.

Logging is left enabled unless


the last interval was missed.

38

Invalid data.

100

Interval time expired before data could be recorded. Missed interval.

Contact Technical Support if you need assistance in resolving these or other


error conditions.

Getting an Interval Data Log using FTP

You can use FTP to retrieve a data log file by connecting to the EGX via
FTP and transferring the .csv file, as shown in the steps below.
NOTE: If you want the EGX to automatically send the data log file via FTP,
the Device Log Export must be configured for FTP (see FTP Export on
page 20).
Action

Result

1. Create a folder on your computer, such as Creates a folder to store the EGX data log.
c:\egx_logs.
2. Launch Windows Explorer, type ftp:// and
the IP address of the EGX in the Address
text box (for example, ftp://169.254.0.10),
then press Enter.

Opens the Log On As dialog box.

3. Type the user name Administrator and the Opens an FTP session with the EGX and
administrator password in the text boxes, displays the files stored in the EGX.
then click Log On.
4. Navigate to the directory /logging/data on Opens the data logging directory on the EGX.
the EGX
5. Copy the log file, then paste it into the
folder you created in step 1.

Getting an Interval Data Log Using the Data


Points Button

42

Action

Copies the data log to your folder.

Result

1. From the Device Logging web page (see


Figure 36), click Data Points.

Opens a new window displaying the logged


data.

2. Press CTRL+A, then press CTRL+C.

Selects all of the data, then copies the data to


the clipboard.

3. Open Excel, then press CTRL+V.

Pastes the data into an Excel spreadsheet.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

Getting an Interval Data Log Using the


Microsoft Web Query Feature

Action
1. Launch your web browser.

Result
Opens the web browser.

2. Verify that the log file is available by typing Opens the data log page.
the EGX300 IP address followed by
/stream/devlog_data.html?device=x
(where x is the device local ID).
3. Launch Excel, then click Data > Import
External Data > New Web Query.

Opens the Excel New Web Query dialog box.

NOTE: The path shown is typical for


Microsoft Excel 2003.
4. In the New Web Query dialog box, type
the address of the log you entered in step
2, then click Go.

Opens the data log file.

5. Click the outer-most arrow to select all of


the data, then click Import.

Selects the data, then opens the Import Data


dialog box.

6. Click OK.

Imports the data.

NOTE: If you want to display the latest data each time you open the
spreadsheet, click Properties on the Import Data dialog and select Refresh
data on file open.

Getting an Interval Data Log Using E-mail

The EGX must be configured to deliver data logs to an e-mail address. For
more information, see E-mail Export on page 19.

Getting an Interval Data Log Using HTTP

The EGX must be configured to deliver data logs to a web server. For more
information, seeHTTP Export on page 21.

Summary Device Pages

The Summary Device views provide summaries of one or more selected


devices.
Action
1. From the Monitoring menu, click Device
Logging.

Result
Expands the tree for device logging choices.

2. Under Device Logging, click Summary


Device Pages.
3. Under Summary Device Pages, click
Multiple Devices, Single Topic.

Opens the setup page for the Multiple Devices,


Single Topic page.

4. Select a device from the Available


Devices list.

Selects the devices for the summary options.

NOTE: A maximum of four devices may be


selected.
5. Select a topic from the Available Topics
list.

Selects the topic to display for each selected


device.

NOTE: Only topics that are common


between the selected devices are
available.
6. Select Next.

Opens the Multiple Devices, Single Topic


display page

7. Hold down the left mouse button and drag


a selection box around a graph area to
zoom in on it.

Zooms in on the selected graph area.

8. To return to the original full view, type Z on The view zooms out.
your keyboard, or double-click on the
graph.

The topic logged from the selected devices is displayed in a web page in a
time-trend chart format. The time-trend chart is preconfigured to display
data from the Last Full Day, Last Full Week, Last Full Month, or All Data.

2009-2013 Schneider Electric. All Rights Reserved.

43

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

Energy parameters are displayed as incremental values on an interval


basis. All other parameters are logged and displayed as the actual value
recorded.

44

Figure 39:

Multiple Devices, Single Topic Setup Page

Figure 40:

Multiple Devices, Single Topic Trend Page

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

Dashboards

The EGX supports four categories of dashboards that display energy


consumption information aggregated over time. Table 17 lists the
dashboards and their subsets.
Table 17: Dashboard Types
Dashboard
By Hours

Subset
Past Day by Hours
Present Day by Hours
Present Day over Past Day by Hours

By Days

Past Week by Days


Present Week by Days
Present Week over Past Week by Days
Past Month by Days
Present Month by Days
Present Month over Past Month by Days

By Weeks

Past Quarter by Weeks


Present Quarter by Weeks
Present Quarter over Past Quarter by Weeks
Trailing 13 Weeks by Weeks

By Months

Past Year by Months


Present Year by Months
Present Year over Past Year by Months
NOTE: Requires each device data log file to have the capacity for
two years of historical data. See Interval Data Logging on page 16
for more information.
Trailing 12 Months by Month

Viewing a Dashboard
Action
1. From the Monitoring menu, click
Dashboards.

Result
Displays dashboard menu (see Figure 41).

2. Select a device from the Device drop-down Selects device for displaying data.
list.
NOTE: The dashboard displays data from a
single device.
3. Select a topic from the Topic Name dropdown list.

Selects topic to be graphed.

NOTE: Topics are limited to incremental


consumption topics provided by the device.
4. Select time parameters from the Time drop- Selects time range of logged data for selected
down list.
topic.
5. Click Apply.

Figure 41:

2009-2013 Schneider Electric. All Rights Reserved.

Opens the selected dashboard.

Dashboards Menu

45

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

The data from each dashboard displays in a web page in bar graph format.
As you hover over a bar in the graph, the data point value for the selected
interval displays (Figure 42).

Getting Dashboard Data Using the Data


Points Button

Figure 42:

Dashboard Graph

Figure 43:

Dashboard Table

You can save data from a dashboard in a spreadsheet application, as


shown in the steps below.
Action

Result

1. From the dashboard containing the desired Displays data points for the selected dashboard
data, click Data Points.
(Figure 43 on page 46).

Saving a Dashboard Link

2. Press CTRL+A, then press CTRL+C.

Selects all of the data, then copies the data to


the clipboard.

3. Open Excel, then press CTRL+V.

Pastes the data into an Excel spreadsheet.

You can save a dashboard link to avoid having to select from the main
menu each time you access the dashboard. Table 18 describes the
methods for saving dashboard link.
Table 18: Saving a Dashboard Link
Option

46

Description

Setting

Browser Bookmark

Allows users to access the saved


dashboard on the computer where
the bookmark is created.

Follow instructions for setting a


bookmark in your preferred
browser.

Documentation Link

Allows all EGX users to access a


saved dashboard from the
Documentation page.

See Documentation Links on


page 26 for setting URL access.

Email

Allows users to send a dashboard


URL in the body of an E-mail.

E-mail recipient must have an EGX


user account to view a dashboard.
See User Accounts on page 27.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Monitoring

63230-319-216B3
03/2013

Saving a Dashboard as an Image

You can save a dashboard graph as an image using the steps below.
Action

Result

1. Follow the steps in Viewing a Dashboard


on page 45.

Displays the dashboard graph.

2. Click Show as Image... in the top right


corner of the page (Figure 44).

Opens a new window with the dashboard


displayed as an image.

3. Right click on the image and select Save


image as...

Opens the Save As dialogue box.

4. Enter a file name, select a location to save Saves the image.


the file, and click Save.
NOTE: The default file type is PNG image.
To change the file type, replace .png in the
file name field with your preferred
extension.

NOTE: This feature is not available with Internet Explorer version 8 or


earlier.
Figure 44:

2009-2013 Schneider Electric. All Rights Reserved.

Saving a Dashboard Image

47

PowerLogicTM Ethernet Gateway EGX300


Documentation

System Access Point

63230-319-216B3
03/2013

The EGX can discover and provide links to EGX300s and other Schneider
Electric devices that are connected to the network. This provides an access
point to a system of networked Schneider Electric devices.
The System Access Point page lists each of the discovered Schneider
Electric devices as a hyperlink. As you hover over a device in the list,
additional details about the device displays to the left of the listing.
Click any device to go to the log-in page for that device.

Figure 45:

DOCUMENTATION

System Access Point Page, Showing Device Detail

The Documentation page allows you to access information that has been
stored as files on the EGX and as URL web links.
For information on loading documentation links, see Documentation Links
on page 26.
To open a documentation link, click the Documentation link at the top of the
page, then select the link you want.

Figure 46:

48

Documentation Page

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Control

63230-319-216B3
03/2013

CONTROL

The EGX has the ability to manually execute one or more of a set of
predefined reset commands per device type.
Action
1. From the Control menu, click Resets.

Result
Opens the Resets page.

2. Select a device in the Resets list you want Selects a device and shows its reset options,
to view or reset.
and the date and time of the last reset.
3. Select the device parameters you want to
reset.

Selects the reset operation to be performed on


the selected device.

4. Click Reset.

Send reset command(s) for the requested


reset(s) to the selected device, and displays
the status.

Figure 47:

Resets

NOTE: The date and time shown for the Date/Time parameter is the current
date and time in the selected device. If this parameter is selected to be
reset, the EGX date and time will be sent to the device.
Date/Time values are reported only when the device supports them. For
example, if a device does not support the Min/Max value for "Date/Time
Last Reset," the "Min/Max" value will not be populated here.

DIAGNOSTICS

To access the Diagnostics web page links, click Diagnostics on the EGX
menu bar.

Statistics

This page shows accumulated readings since the EGX was last activated. If
power to the EGX is lost or the device is reset due to a configuration change
or other event, all cumulative values reset to zero.
Action
1. From the Diagnostics menu, click
Statistics.

2009-2013 Schneider Electric. All Rights Reserved.

Result
Opens the Statistics page (see Figure 48
below).

2. View the data.

See Interpreting Statistics below.

3. Click Reset.

Resets the EGX cumulative diagnostic data


to 0.

49

PowerLogicTM Ethernet Gateway EGX300


Diagnostics

63230-319-216B3
03/2013

Figure 48:

50

Statistics Page

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Diagnostics

63230-319-216B3
03/2013

Interpreting Statistics
Statistic

Description

Ethernet
Link Status

A status string that represents the speed and


duplex setting being used to communicate with
the linking partner.

Frames Transmitted OK

A counter that increments each time a frame is


successfully transmitted.

Collisions

A counter that increments each time a frame is


retransmitted due to collision detection.

Excessive Collisions

A counter that increments each time a frame


is not able to be sent due to reaching the
maximum collision status based on the
Truncated Binary Exponential Backoff
algorithm.

Frames Received OK

A counter that increments each time a frame is


successfully received.

CRC Errors

A counter that increments each time a frame is


received that has a checksum/CRC that does
not match what is calculated.

Alignment Errors

A counter that increments each time a frame is


received that has a checksum/CRC error and
does not end on an 8-bit frame boundary.

Frames Too Long

A counter that increments each time a frame is


received that is larger than the allowed
maximum size defined in the standards (frames
larger than 1518 bytes).

Frames Too Short

A counter that increments each time a frame is


received that is smaller than the allowed
minimum size defined in the standards (frames
smaller than 64 bytes).

Modbus TCP/IP
Server
Frames Sent

A counter that increments each time a frame is


sent.

Frames Received

A counter that increments each time a frame is


received.

Protocol Errors

A counter that increments each time an


ill-formed message is received.

Active Connections1

A status value that represents the number of


connections that are active at the moment the
diagnostics page is refreshed. A maximum of
64 connections are supported. Clicking Active
Connections opens a new window with a list of
all of the active client connections.

Accumulative Connections

A counter that increments each time a


connection is made to the EGX.

Maximum Connections

A status value that represents the maximum


number of connections that were active at any
given moment.

Inbound Read Messages

A counter that increments each time a read


request message is received.

Inbound Write Messages

A counter that increments each time a write


request message is received.

Outbound Reply Messages

A counter that increments each time a reply


message is sent.

Client
Frames Sent

A counter that increments each time a frame is


sent.

Frames Received

A counter that increments each time a frame is


received.

Protocol Errors

A counter that increments each time an


ill-formed message is received.

2009-2013 Schneider Electric. All Rights Reserved.

Click the link for additional, detailed information.

51

PowerLogicTM Ethernet Gateway EGX300


Diagnostics

63230-319-216B3
03/2013

Statistic

Description

Timeouts

A counter that increments each time a request


message is sent without receiving a
corresponding response message within the
allowed time. Timeouts are typically the result
of configuration errors or a non-responsive
device.

Connection Timeouts

A counter that increments each time the


connection is lost.

Exceptions Received

A counter that increments each time an


exception is received.

Outbound Read Messages

A counter that increments each time a read


request message is sent.

Outbound Write Message

A counter that increments each time a write


request message is sent.

Inbound Reply Messages

A counter that increments each time a reply


message is received.

Details1

A detailed table providing remote and serial


statistics per device.

Serial Port
Frames Sent

A counter that increments each time a frame is


sent.

Frames Received

A counter that increments each time a frame is


received.

CRC Errors

A counter that increments each time a


message is received that has a CRC that does
not match what is calculated. Typically the
result of wiring issues.

Protocol Errors

A counter that increments each time an illformed message is received.

Timeouts

A counter that increments each time a request


message is sent without receiving a
corresponding response message within the
allowed time. Timeouts are typically the result
of configuration errors or a non-responsive
device.

Exceptions Received

A counter that increments each time an


exception is received.

Outbound Read Messages

A counter that increments each time a read


request message is sent.

Outbound Write Messages

A counter that increments each time a write


request message is sent.

Inbound Read Messages

A counter that increments each time a read


request message is received.

Inbound Write Messages

A counter that increments each time a write


request message is received.

Details1

A detailed table providing serial and remote


statistics per device.

HTTP Server
Frames Sent

A counter that increments each time a frame is


sent.

Frames Received

A counter that increments each time a frame is


received.

Active Connections1

A status value that represents the number of


connections that are active at the moment the
diagnostics page is refreshed. A maximum of
20 connections are supported. Click Active
Connections to open a new window with a list
of all of the active client connections.

Accumulative Connection1

A counter that increments each time a


connection is made to the EGX.

Maximum Connections

A status value that represents the maximum


number of connections that were active at any
given moment.

1Click

52

the link for additional, detailed information.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Diagnostics

63230-319-216B3
03/2013

Statistic

Description

Gateway Information
Firmware Version

The firmware version that is installed on the


EGX.

System Idle Time

A percentage from 0% to 100% indicating the


average processor time that is not being used.

MAC Address

The unique Ethernet hardware address of an


EGX.

Serial Number

The serial number of the EGX.

Model Number

The EGX model number.

Hardware Version

EGX hardware version.

Manufacture Date

Date the EGX was manufactured.

HTTP Client
Send OK

A counter that increments each time a file is


sent successfully to the HTTP server.

Connect Error

A counter that increments each time the EGX is


unable to connect to the HTTP server.

Authentication Error

A counter that increments each time the HTTP


server is unable to authenticate the user or
password credentials.

Send Error

A counter that increments each time a file is


unable to be transferred to the HTTP server.

General Error

A counter that increments each time a file is


unable to be transferred due to the inability of
the EGX to originate the transaction.

FTP Client
Send OK

A counter that increments after each successful


transfer to an FTP server.

Connect Error

A counter that increments each time the EGX is


unable to connect to the FTP server.

Authentication Error

A counter that increments each time the FTP


server is unable to authenticate the
User/Password credentials.

Directory Error

A counter that increments each time the FTP


server is unable to locate the requested
directory.

Send Error

A counter that increments each time a file is


unable to be transferred to the FTP server.

General Error

A counter that increments each time a file is


unable to be transferred due to the inability of
the EGX to originate the transaction.

SMTP Client
Send OK

A counter that increments each time an e-mail


is sent successfully to the SMTP server.

Connect Error

A counter that increments each time the EGX is


unable to connect to the SMTP server.

Authentication Error

A counter that increments each time the SMTP


server is unable to authenticate the user or
password credentials.

Send Error

A counter that increments each time an e-mail


is unable to be sent to the SMTP server.

General Error

A counter that increments each time an e-mail


is unable to be sent due to the inability of the
EGX to create the e-mail.

File System
Total Space

The total amount of the EGX disk space in


kilobytes.

Free Space

The total amount of unused disk space on the


EGX disk in kilobytes.

2009-2013 Schneider Electric. All Rights Reserved.

Click the link for additional, detailed information.

53

PowerLogicTM Ethernet Gateway EGX300


Diagnostics

Read Device Registers

63230-319-216B3
03/2013

This option allows the EGX to read from its local or remote devices.
Figure 49:

Read Device Registers Page

Action

Result

1. From the Diagnostics menu, click Read


Device Registers.

Opens the Read Device Registers page.

2. Enter local device ID (or choose from the


defined device list), starting data address,
and the number of registers to read.

Enters the registers to read from the specified


device.

3. Select a data type.

Selects the appropriate data type.

4. To change how the data is displayed in the Selects how the data values are displayed.
Value column, select Decimal,
Hexadecimal, Binary, or ASCII.
5. Click Read.

Reads the device registers according to the


selected configuration.

Table 19: EGX Read Device Register Settings


Option

Description

Device Name

Selects a device to read from the list of previously


added devices. A device not defined in the device
list can be read by entering its Local ID number.

Device ID

The address (Local ID) of the device that is to be


read.

Starting Register

The first register to read.

Number of Registers

The number of registers to read (1 to 125).

Register column

Lists the register numbers

Value column

Lists the data stored for a register. Values


retrieved depend on the device connected to the
EGX. Refer to the documentation for the
connected device for more information about
stored register values.

Data Type

Select Holding Registers, Input Registers, Output


Coils, Input Coils, or Device ID.

Holding Registers

Decimal, Hexadecimal, Select an option to specify how the Value column


Binary, or ASCII options data is displayed.

54

Default

1000
10

Decimal

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Diagnostics

63230-319-216B3
03/2013

Communications Check
Automated Communications Check

When browsing the Real Time Data views, the EGX has an automated
communications check that runs every 15 minutes by default. To change the
timing, see Preferences on page 30). This check will verify the
communications health of all devices configured on the EGX, and will
attempt to re-establish communication to any device marked Out of Service
within the current browser session.

Manual Communications Check

In certain cases, you may not want to wait for the automated
communications check interval and need to force the check to run manually.
Action
1. From the Diagnostics menu, click
Communications Check.

Opens the Communications Check page.

2. Click Check Device Status.

Runs a communications check.


Communicating devices display Passed in the
Comms column and In Service in the Status
column. A device that is not communicating
displays Failed in the Comms column and Out
of Service in the Status column, if it has failed
multiple times.

Figure 50:

2009-2013 Schneider Electric. All Rights Reserved.

Result

Communications Check Page

55

PowerLogicTM Ethernet Gateway EGX300


Maintenance

MAINTENANCE

63230-319-216B3
03/2013

The Maintenance Log provides you with a way to document maintenance


performed on the EGX, the connected equipment, or the system of which
the EGX is a part. Each entry is recorded with the date and time the entry
was made, and the name of the user who made it.
This log will also automatically list system activity, such as enabling or
disabling features. You do not need to add entries for these items.
Finally, this log will list all activities that are specified for the Maintenance
Log in the Audit Trail setup page (see Audit Trail on page 32).
Action

Result

1. From the Maintenance menu, click


Maintenance Log.

Opens the Maintenance Log page.

2. Select the Delete checkbox next to the


Deletes the selected entry.
entry you want to delete, then click Delete
Entries.
3. Click Delete Log to delete all entries in the Clears the maintenance log.
maintenance log.
4. To add a new log entry, click Add Log
Entry, then enter the maintenance text in
the Entry Detail text box (see Figure 52
below).

Figure 51:

Maintenance Log

Figure 52:

Add Log Entry

Opens the Add Log Entry page and allows the


user to enter maintenance details.

FIRMWARE

Firmware on the EGX can be updated using File Transfer Protocol (FTP).
Check www.schneider-electric.com or with your local sales representative
for the latest firmware update.

Finding the Firmware Version

The EGX consists of two firmware components: the executable binary


component and the disk image component.

56

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Firmware

63230-319-216B3
03/2013

Executable Binary Component Firmware


Version

Action

Result

1. Open the web browser and log into the


EGX.

Opens the EGX home page.

2. Locate the firmware version on the


bottom-left corner of the page.

Determines the firmware version of the EGX.

NOTE: If you recently updated your


firmware, press F5 to refresh the web page
and update the displayed firmware
number.
3. Alternatively, you can select Diagnostics Also determines the firmware version of the
> Statistics to find the firmware version in EGX.
the Gateway Information section.

Disk Image Version


Action

Result

1. Open the web browser and log into the


EGX.

Opens the EGX home page.

2. Locate the firmware version on the


bottom-left corner of the page.

Determines the disk image firmware version of


the EGX.

NOTE: If you recently updated your


firmware, press F5 to refresh the web page
and update the displayed firmware
number.
3. Alternatively, you can access the EGX
through FTP, locate the file version.txt,
then double-click the file to open it.

Determines the disk image firmware version of


the EGX.

Getting New Firmware


Action

Result

1. Launch the web browser, type


www.powerlogic.com in the Address text
box, then press Enter.

Opens the PowerLogic website.

2. Select your country, then click Go.

Opens the PowerLogic website for your


country.

NOTE: If you selected the United States,


continue to Step 3. Otherwise, follow the
country-specific website navigation to get
the EGX firmware.
3. Click Support > Downloads.

Opens the downloads page.

4. Click the EGX300 Firmware link.

Opens the EGX300 Firmware page.

5. Click the firmware file link (egxxxxx.bin,


where xxxx is the firmware version
number), then click Save.

Opens the File Download dialog box, then


opens the Save As dialog box.

6. In the Save As dialog box, select or create Saves the firmware file in the designated
a local directory/file folder where the
directory/folder.
firmware file will be stored, then click Save.
7. Click the egxxxxx.upd link (where xxxx is
the firmware number), then click Save.

Opens the File Download dialog box, then


opens the Save As dialog box.

8. In the Save As dialog box, select or create Saves the firmware .upd file in the designated
a local directory/file folder where the
directory/folder.
firmware file will be stored, then click Save.

2009-2013 Schneider Electric. All Rights Reserved.

57

PowerLogicTM Ethernet Gateway EGX300


Firmware

Updating the Firmware

63230-319-216B3
03/2013

Do not remove power from the EGX while firmware is being downloaded. If
power is removed during the programming process, the EGX will no longer
function. The Status LED will rapidly blink while programming is in progress.
When the flashing stops, programming is complete.
Action

Result

1. Launch Windows Explorer, type ftp:// and


the IP address of the EGX in the Address
text box (for example, ftp://169.254.0.10),
then press Enter.

Opens the Log On As dialog box.

2. Type the user name Administrator and the Opens an FTP session with the EGX.
administrator password in the text boxes,
then click Log On.
3. Locate the saved firmware file
Copies the firmware file to the clipboard.
(egxxxxx.bin) directory/folder on your
computer, right-click on the file name, then
click Copy.
4. Right-click in the Windows Explorer
window, then click Paste.
NOTE: Instead of copying and pasting the
firmware file, you can drag-and-drop the
firmware file into Window Explorer.

Copies the firmware to the EGX, and the EGX


reboots.
NOTE: The Power/Status light will blink
rapidly while the file is being transferred
and programmed to the EGX. Once the
programming is complete, the EGX will
reset. The amount of time for programming
is between 1.5 and 2 minutes.

5. Locate the saved disk update file


Copies the disk update file to the clipboard.
(egxxxxx.upd) on your computer, right-click
on the file name, then click Copy.
6. Right-click in the Windows Explorer
window, then click Paste.

Copies the file to the EGX, and the EGX


reboots.

NOTE: Instead of copying and pasting the


firmware file, you can drag-and-drop the
firmware file into Window Explorer.

58

7. To verify that the firmware version was


updated successfully, follow the steps in
Finding the Firmware Version on
page 56.

Verifies the updated firmware version.

8. Click Close on the Windows Explorer


window.

Closes Windows Explorer and ends the FTP


connection to the EGX.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Appendix ASupported Ethernet Protocols

63230-319-216B3
03/2013

APPENDIX ASUPPORTED
ETHERNET PROTOCOLS

The EGX supports the following Ethernet protocols:

Modbus TCP/IP: Modbus TCP/IP is a combination of the Modbus


protocol, which provides master-slave communication between devices,
and TCP/IP, which provides communications over an Ethernet
connection. Modbus TCP/IP is used to exchange data between the EGX
and other compatible Modbus TCP/IP devices via TCP port 502.

Hypertext Transfer Protocol (HTTP): HTTP is a network protocol that


handles the delivery of files and data on the World Wide Web. It
provides web server functionality via TCP port 80.

Hypertext Transfer Protocol Secure (HTTPS): HTTPS is a network


protocol that handles the encrypted delivery of files and data on the
World Wide Web with the use of SSL. It provides secure web server
functionality via TCP port 443.

File Transfer Protocol (FTP): FTP is a network protocol that provides


the ability to transfer files over the Internet from one computer to
another. Active and passive FTP modes are supported, primarily using
TCP port 21.

Simple Network Management Protocol (SNMP): Based on MIB2


format, SNMP provides the ability to store and send identifying and
diagnostic information used for network management purposes via UDP
port 161.

Address Resolution Protocol (ARP): ARP is used to convert IP


addresses to Ethernet addresses. ARP requests are sent by the EGX to
determine if its address is a duplicate IP address (see Duplicate IP
Address Detection on page 7).

Simple Network Time Protocol (SNTP): SNTP is a protocol used to


synchronize the clocks of networked devices using a NTP server via
UDP port 123.

Hardware
RJ45 Ethernet port
Control power

RS485 serial port


LEDs for Ethernet
and serial
communications

Power and
Status LED
Bias, termination,
and 2-wire/4-wire
jumper switches
Reset
button

2009-2013 Schneider Electric. All Rights Reserved.

RS232 serial port


(RJ45 connector)

59

PowerLogicTM Ethernet Gateway EGX300


Appendix BSupported Device Types

APPENDIX BSUPPORTED
DEVICE TYPES

63230-319-216B3
03/2013

The EGX supports the following device types. This list of supported devices
was accurate at the time this document was published. Check
www.schneider-electric.com for updates.
Table 20: EGX300-Supported Device Types
Device Group

Devices

Active Harmonic Filter


Circuit Breakers

Accusine
Compact NSX-A
Compact NSX-E
PowerPact - A
PowerPact - E
CM100/200
CM2000
CM3000
CM4000
ION7500
ION7550
ION7600
ION7650
DM6000
DM6300
Model 98
ATV61
ATV71
Energy Meter
Enercept
E5600
EM1200
EM1210
EM1250
EM1251
EM26-96
EM3550
EM3555
EM6400
EM6433
EM6436
EM6436DUAL
EM6438
EM7230
EM7280
iEM3150
iEM3155
iEM3250
iEM3255
ION8600
Vigilohm IM20
Vigilohm IM20-H
TeSys T
BCPM-Model A
BCPM-Model B
BCPM-Model C
BCM50A
BCM100A
MCM
MotorLogic Plus
MotorLogic Plus II
Varlogic
PM9c
PM200
PM300
PM500
PM600
PM700

Circuit Monitors

Digital Meters
Digital Temp Controller
Drives
Energy Meters

Insulation Monitoring Devices


Motor Management
Multi-Circuit Monitors

Overload Relays (SSOLR)


Power Factor Controller
Power Meters

60

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Appendix BSupported Device Types

63230-319-216B3
03/2013

Table 20: EGX300-Supported Device Types


Device Group

Protective Relays

Smart Interface Modules

Soft Starters
Temperature/Humidity/Light Sensors
Trip Units

Other

2009-2013 Schneider Electric. All Rights Reserved.

Devices
PM800
PM1000
PM3250
PM5350
PM5350BW
ION6200 (Standard and Mega)
ION7300
Sepam 2000
Sepam Series 10
Sepam Series 20
Sepam Series 40
Sepam Series 80
SIM10Z
SIM10M
SIM6BZ
ATS48
MVSS/RVSS
ZED-THL-M
Micrologic A
Micrologic E
Micrologic H
Micrologic P
Acti9 SmartLink

61

PowerLogicTM Ethernet Gateway EGX300


Appendix BSupported Device Types

62

63230-319-216B3
03/2013

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTMEthernet Gateway EGX300


Index

63230-319-216B3
03/2013

Index
A
access levels to the EGX 25
accessing the EGX over a network 2
additional resources 1
analog gauge range 37
ARP (address resolution protocol) 7
audit trail 32
maintenance log 33
Syslog box 33

B
basic readings settings 36

C
communications check 55
automated 55
manual 55
connecting devices 11
control 49
custom web pages
setup 29

D
dashboards 45
data log
error codes 42
retrieved via ftp 42
retrieving 40
data log format 41
data points button
interval data log 42
date and time
setup 23
device discovery 14
device list
EGX 11
device log export
setup 19
device logging 16, 39
device registers
reading 54
device types supported 60
diagnostics 49
documentation links
setup 26
documentation page 48
duplicate IP address detection 7

E
EGX
device list 11
login 2
user interface 3
e-mail
export device log 19
interval data log 43
error codes
data log 42
Ethernet and TCP/IP settings 4
Ethernet protocols 59
Ethernet settings

advanced 5
executable binary component firmware
version 57
exporting the device log 19

F
file image component firmware version 57
firmware
getting new 57
updating 58
updating via ftp 56
ftp
export device log 20
using to add web pages 29
using to delete web pages 29
using to retrieve data log 42

H
hardware 59
HTTP
export
device log 21
port number
setup 6
retrieving interval data log 43
HTTPS
port number
setup 6

I
interval data log
via data points button 42
via e-mail 43
via ftp 42
via HTTP 43
via Microsoft Web Query 43
intervals
logging 16
introduction 1
IP address
detecting duplicate 7

setup 23

P
password strength
color indication 27
preferences
customizing the EGX 30

R
read device registers 54
real-time data 36
remote device connections 10

S
serial port settings
advanced 9
serial port setup 8
setup
device list 12
EGX 4
single device pages 36, 39
SNMP parameters
setup 24
statistics 49
interpreting 51
summary device pages 37, 43
supported device types 60
supported ethernet protocols 59
Syslog
audit trails 33
system access point
links to other EGX300s 48
setup 35

T
TCP/IP settings 4
time synchronization
network 23
trending 38
trusted certificate
HTTPS port number 6

logging 16, 39
data format 41
topics 18
logging in to EGX 2
logging intervals 16

user accounts
setup 27
user interface
EGX 3

M
maintenance log 56
audit trail 33
Microsoft Web Query
interval data log 43
Modbus devices
discovering 14
Modbus TCP/IP filtering
setup 25
monitoring 36

V
viewable device types 31
viewing real-time data and trends 36

W
web pages
adding/removing from the web interface
30
setup 28
custom 29

N
network
access via 2
network time synchronization

2009-2013 Schneider Electric. All Rights Reserved.

63

PowerLogicTMEthernet Gateway EGX300


Index

64

63230-319-216B3
03/2013

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTMEthernet Gateway EGX300


User Guide

PowerLogic is a trademark or registered trademark of Schneider Electric in France, the USA and
other countries. Other trademarks used are the property of their respective owners.
This product must be installed, connected and used in compliance with prevailing standards
and/or installation regulations. As standards, specifications and designs change from time to time,
always ask for confirmation of the information given in this publication.

Schneider Electric
35 rue Joseph Monier
92500 Rueil-Malmaison, France
www.schneider-electric.com

63230-319-216B3 03/2013
Replaces 63230-319-216B2 11/2011
2009-2013 Schneider Electric. All Rights Reserved.

Pasarela Ethernet EGX300 de PowerLogicTM


Manual del usuario
63230-319-216B3_ES
03/2013

Informacin de seguridad
Informacin importante
Lea estas instrucciones atentamente y examine el equipo para
familiarizarse con el dispositivo antes de instalarlo, manipularlo, revisarlo o
realizar el mantenimiento de este. Los siguientes mensajes especiales
pueden aparecer a lo largo de este manual o en el equipo para advertir de
posibles riesgos o remitirle a otras informaciones que le ayudarn a aclarar
o simplificar los procedimientos.
La adicin de uno de estos dos smbolos a una etiqueta de seguridad del
tipo Peligro o Advertencia indica la existencia de un riesgo de descarga
elctrica que ocasionar lesiones si no se siguen las instrucciones.
Este es el smbolo de alerta de seguridad. Sirve para alertar de posibles
riesgos de lesiones. Siga las recomendaciones de todos los mensajes de
seguridad precedidos por este smbolo para evitar posibles lesiones e
incluso la muerte.

PELIGRO
PELIGRO indica una situacin de riesgo inmediato que, si no se evita,
causar la muerte o lesiones graves.

ADVERTENCIA
ADVERTENCIA indica una situacin de riesgo potencial que, si no se evita,
puede causar la muerte o lesiones graves.

PRECAUCIN
PRECAUCIN indica una situacin de riesgo potencial que, si no se evita,
puede causar lesiones moderadas o leves.

AVISO
AVISO sirve para indicar prcticas no relacionadas con lesiones fsicas.
El smbolo de alerta de seguridad no debe utilizarse junto con esta
advertencia impresa.

Por favor, tenga en cuenta lo siguiente


Slo el personal cualificado puede instalar, manipular y revisar el equipo
electrnico as como realizar el mantenimiento de este. Schneider Electric
no asume ninguna responsabilidad de las consecuencias que se deriven de
la utilizacin de este manual.
Por personal cualificado se entiende aquellas personas que poseen
destrezas y conocimientos sobre la estructura, la instalacin y el
funcionamiento de equipos elctricos y que han recibido formacin en
materia de seguridad para reconocer y prevenir los peligros implicados.

Avisos
Aviso sobre la seccin 15 de la normativa de la FCC
Este equipo ha sido probado y cumple los lmites establecidos para los
dispositivos digitales Clase A, segn la seccin 15 de la normativa de
la FCC (Comisin Federal de Comunicaciones de los EE. UU.). Estos
lmites se establecen para proporcionar la proteccin adecuada contra
interferencias que puedan daar el equipo cuando este se utiliza en un
entorno comercial. Este equipo genera, utiliza y puede emitir energa de
radiofrecuencia y, si no se instala y utiliza siguiendo las indicaciones del
manual de instrucciones, puede provocar interferencias que afecten a las
radiocomunicaciones. Si se utiliza en una zona residencial, las
interferencias podran causar daos. En tal caso, el usuario es el
responsable de corregir dichas interferencias por su propia cuenta y riesgo.
El nmero de equivalencia de dispositivos, o nmero REN (Ringer
Equivalence Number), del mdem interno opcional del dispositivo es 0,6.
La conexin al mdem interno del dispositivo se debe realizar por medio de
un cable para telfono (no se suministra) que cumpla la seccin 68 de la
normativa de la FCC. El dispositivo no se puede utilizar en un servicio de
telfono de monedas pblico ni en servicios de lnea compartida.
Este aparato digital Clase A cumple con la normativa canadiense ICES-003.

Pasarela Ethernet EGX300 de PowerLogicTM


Contenido

63230-319-216B3_ES
03/2013

Contenido
Introduccin .............................................................................................. 1
Otros recursos ............................................................................................. 1
Acceso a la EGX a travs de una red ...................................................... 2
Inicio de sesin en la EGX .......................................................................... 2
Descripcin general de la interfaz de usuario de la EGX ...................... 3
Configuracin ............................................................................................ 5
Configuracin de Ethernet y TCP/IP ........................................................... 5
Configuracin avanzada de Ethernet .................................................... 6
Deteccin de direcciones IP duplicadas................................................ 8
Puerto serie ................................................................................................. 8
Configuracin avanzada del puerto serie .............................................. 9
Conexiones con dispositivos remotos ....................................................... 10
Lista de dispositivos de la EGX ................................................................. 12
Conexin de dispositivos a una EGX .................................................. 12
Configuracin de la lista de dispositivos.............................................. 13
Deteccin de dispositivos .................................................................... 15
Registro de dispositivos ............................................................................ 17
Registro de datos de intervalo............................................................. 17
Configurar registro por intervalos ........................................................ 17
Temas que registrar ............................................................................ 18
Exportacin del registro de dispositivos .................................................... 19
Exportacin por correo electrnico...................................................... 19
Exportacin por FTP............................................................................ 21
Exportacin por HTTP ......................................................................... 22
Fecha y hora ............................................................................................. 23
Sincronizacin horaria de red.............................................................. 24
Parmetros del SNMP .............................................................................. 25
Filtrado de Modbus TCP/IP ....................................................................... 26
Vnculos de documentacin ...................................................................... 27
Cuentas de usuario ................................................................................... 28
Acceso a pgina Web ............................................................................... 29
Agregar o quitar pginas web personalizadas .................................... 30
Adicin de pginas web mediante FTP ............................................... 30
Eliminacin de pginas web mediante FTP ........................................ 30
Agregar o quitar pginas web a o de la interfaz web .......................... 31
Preferencias .............................................................................................. 32
Tipos de dispositivos visualizables ........................................................... 33
Historial de auditora ................................................................................. 33
Punto de acceso del sistema .................................................................... 35
Supervisin .............................................................................................. 37
Datos en tiempo real ................................................................................. 37
Pginas de dispositivo nico ............................................................... 37
Configuracin de lecturas bsicas....................................................... 37
Rango de los indicadores analgicos.................................................. 38
Pginas de resumen de dispositivos ................................................... 38
Tendencias .......................................................................................... 39

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Contenido

63230-319-216B3_ES
03/2013

Registro de dispositivos ............................................................................ 40


Pginas de dispositivo nico ............................................................... 41
Obtencin de registros cronolgicos de datos .................................... 42
Formato de registro ............................................................................. 42
Cdigos de error para los registros cronolgicos de datos ................. 43
Obtencin de un registro de datos de intervalo mediante FTP ........... 43
Obtencin de un registro de datos de intervalo mediante
el botn Puntos de datos..................................................................... 44
Obtencin de un registro de datos de intervalo mediante
la funcin de consulta Web de Microsoft............................................. 44
Obtencin de un registro de datos de intervalo mediante
correo electrnico ................................................................................ 44
Obtencin de un registro de datos de intervalo mediante HTTP......... 44
Pginas de resumen de dispositivos ................................................... 45
Panel de instrumentos .............................................................................. 46
Visualizacin de un panel de instrumentos ......................................... 47
Obtencin de los datos del panel de instrumentos mediante
el botn Puntos de datos..................................................................... 48
Guardar un enlace a un panel de instrumentos .................................. 48
Guardar un panel de instrumentos como imagen ............................... 48
Punto de acceso del sistema .................................................................... 49
Documentacin ....................................................................................... 50
Control ..................................................................................................... 50
Diagnsticos ............................................................................................ 51
Estadsticas ............................................................................................... 51
Interpretacin de las estadsticas ........................................................ 52
Lectura de registros de dispositivo ............................................................ 55
Comprobacin de las comunicaciones ..................................................... 56
Comprobacin de comunicaciones automatizada............................... 56
Comprobacin de comunicaciones manual......................................... 56
Mantenimiento ......................................................................................... 57
Firmware .................................................................................................. 57
Identificacin de la versin del firmware ................................................... 57
Versin del firmware del componente binario ejecutable .................... 58
Versin de imagen de disco ................................................................ 58
Obtencin de firmware nuevo ................................................................... 58
Actualizacin del firmware ........................................................................ 59
Apndice A: Protocolos Ethernet compatibles .................................... 60
Equipo fsico .............................................................................................. 60
Apndice B: Tipos de dispositivos admitidos ..................................... 61

ii

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Introduccin

63230-319-216B3_ES
03/2013

INTRODUCCIN

La EGX300 es un dispositivo basado en Ethernet que proporciona una


interfaz transparente entre redes basadas en Ethernet y dispositivos que
pueden ser instalados por el usuario. Entre estos ltimos se incluyen
medidores, monitores, rels protectores, autmatas programables (PLC),
unidades de control, controles de motores y otros dispositivos que se
comunican mediante protocolos Modbus, Jbus o PowerLogic.
La EGX300 utiliza el protocolo Modbus TCP/IP para acceder a informacin
de dispositivos que puede instalar el usuario a travs de una red de rea
local (LAN) o a travs de una red de rea extendida (WAN). Esta capacidad
permite utilizar software de supervisin para acceder a la informacin de los
dispositivos y recolectar datos, establecer tendencias, gestionar alarmas y
eventos, efectuar anlisis y ejecutar otras funciones.
La EGX300 permite generar informes de datos en tiempo real a partir de
muchos tipos de dispositivos corrientes y proporciona varias funciones
especficas de estos, tales como informes de pginas de resumen
incorporadas de dispositivos y circuitos, registro de datos incorporado y
establecimiento de tendencias en tiempo real.
Figura 1:

Descripcin general de la EGX300


Vistas en tiempo real

Ver datos del


dispositivo con un
sencillo navegador,
sin software

Tendencias en
tiempo real
Pginas web de la EGX300

Restablecimientos de control

EGX300

Extraiga a pginas web


informacin proveniente de
otras pasarelas PowerLogic
e interfaces TCP/IP
Modbus como ECC21
y PM8ECC.

ION6200

Otros recursos

PM800

Micrologic

Tendencias de los
registros de datos

EGX100

Sepam

Visite www.schneider-electric.com y escriba EGX300 en el campo de


bsqueda. Vaya a Documents & Downloads (Documentos y descargas) de
la EGX.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Acceso a la EGX a travs de una red

ACCESO A LA EGX A TRAVS DE


UNA RED

63230-319-216B3_ES
03/2013

Una vez que haya configurado los parmetros de Ethernet de la EGX


(consulte el manual de instalacin de esta), podr acceder a la EGX a
travs de una LAN Ethernet utilizando cualquier explorador web.

Inicio de sesin en la EGX


Accin

Resultado

1. Inicie el explorador web.

Abre el explorador web.

2. En la barra de direcciones, escriba la


direccin de la EGX (la direccin
predeterminada es 169.254.0.10) y, a
continuacin, pulse Intro.

Abre el cuadro de dilogo Iniciar sesin.

3. Escriba su nombre de usuario


Introduce el nombre de usuario y la contrasea
(Administrator es el valor predeterminado) y, a continuacin, abre la pgina de inicio de
y la contrasea (Gateway es la
la EGX.
predeterminada) en los cuadros de texto y
despus haga clic en Aceptar.
NOTA: El nombre de usuario y la
contrasea respetan maysculas y
minsculas.
4. Haga clic en el elemento correspondiente
de la barra de mens.

Figura 2:

Abre el elemento de men seleccionado.

Pgina de inicio de la EGX

Barra de
mens

Le aconsejamos que se desconecte cuando no necesite acceder a la EGX.


Para salir de la sesin de la EGX, haga clic en Desconexin o cierre el
explorador.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Descripcin general de la interfaz de usuario de la EGX

63230-319-216B3_ES
03/2013

DESCRIPCIN GENERAL DE LA
INTERFAZ DE USUARIO DE
LA EGX

La interfaz de usuario de la EGX consta de mltiples pginas web que se


utilizan en la supervisin y el control de dispositivos, as como el
diagnstico y la configuracin de la EGX. Consulte la Tabla 1 para ver una
descripcin de cada pgina web.
Tabla 1:

Pginas de la EGX

Pgina web de la EGX

Descripcin

Consulte
la pgina

Configuracin
Ethernet y TCP/IP

Configure los parmetros de las comunicaciones


Ethernet y TCP/IP.

Puerto serie

Configure los parmetros de las comunicaciones


serie.

Conexiones con
dispositivos remotos

Configure las conexiones de los dispositivos


Modbus TCP/IP remotos.

10

Lista de dispositivos

Configure, identifique o verifique los dispositivos


serie locales del bus de comunicaciones serie. Los
dispositivos remotos solamente se podrn
configurar o verificar.

12

Registro de dispositivos

Configure los parmetros de registro de los


dispositivos.

17

Exportacin del registro de


dispositivos

Configure las opciones de exportacin del registro


de dispositivos.

19

Fecha y hora1

Establezca la fecha y la hora manualmente o con


parmetros del SNTP.

23

Parmetros del SNMP1

Configure el Protocolo simple de administracin de


redes (SNMP).

25

Filtrado de Modbus
TCP/IP1

Configure las direcciones IP que podrn acceder a


la EGX a travs de Modbus TCP/IP.

26

Vnculos de documentacin Configure archivos y vnculos de documentacin


de URL.

27

Cuentas de usuario1

Cree y modifique grupos y usuarios.

28

Acceso a pgina Web1

Configure los derechos de acceso a las pginas


web para cada grupo de usuarios.

29

Preferencias

Configure las preferencias de la EGX.

32

Tipos de dispositivos
visualizables

Configure qu tipos de dispositivos admitidos se


podrn visualizar en la pgina web Lista de
dispositivos de la EGX.

33

Historial de auditora1

Configure la manera en que la EGX notificar los


mensajes del sistema: por medio del registro de
mantenimiento, por correo electrnico y por el
servidor Syslog remoto.

33

Punto de acceso del


sistema1

Habilite y configure la direccin IP de grupo para


varias EGX300, permitindolas que se detecten
entre s y vean la informacin de las dems.

35

Datos en tiempo real

La vista de tabla Pginas de dispositivo nico


proporciona lecturas bsicas de los dispositivos
seleccionados. La vista de tabla Pginas de
resumen de dispositivos facilita resmenes relativos
a uno o ms dispositivos seleccionados. La vista de
la pgina Tendencias ilustra tendencias en forma de
grficos y tablas en tiempo real correspondientes a
temas comunes de varios dispositivos.

37

Registro de dispositivos

Pginas de dispositivo nico proporciona registros


de tendencias en forma de grficos y tablas que
ilustran cantidades, seleccionables por el usuario,
correspondientes a los dispositivos seleccionados.
Pginas de resumen de dispositivos proporciona
registros de tendencias en forma de grficos de
varios dispositivos acerca de un tema especfico.

40

Supervisin

Slo el administrador tiene acceso.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Descripcin general de la interfaz de usuario de la EGX

63230-319-216B3_ES
03/2013

Tabla 1:

Pginas de la EGX
Descripcin

Consulte
la pgina

Panel de instrumentos

Los paneles de instrumentos proporcionan


representaciones en forma de grficos y tablas de la
informacin de consumo de energa recopilada a lo
largo del tiempo correspondiente a todos los
dispositivos a los que se ha habilitado para el
registro de datos.

46

Punto de acceso del


sistema

La pgina Punto de acceso del sistema muestra


las EGX300 y otros dispositivos en red del sistema
que son accesibles desde esta EGX300. Cada lnea
es un hipervnculo a la pgina de inicio de sesin de
la EGX300.

49

Accede a la documentacin pertinente de la EGX y


a vnculos de documentacin que podr configurar
el usuario.

50

Proporciona lo necesario para la ejecucin de los


restablecimientos definidos para el dispositivo y
muestra la fecha y la hora a las que se realiz cada
funcin de restablecimiento.
Los restablecimientos de fecha y hora se muestran
solo cuando el dispositivo los admite.

50

Estadsticas

Muestra datos de diagnstico que se utilizan para


resolver problemas de la red. Esta pgina contiene
tambin informacin acerca de la EGX especfica
del usuario, incluido el nmero de serie, la fecha de
fabricacin y la direccin de control de acceso de
medios (MAC).

51

Lectura de registros de
dispositivo

Permite que los usuarios lean datos de registro


procedentes de dispositivos locales y remotos
conectados a la EGX.

55

Comprobacin de las
comunicaciones

Verifica el buen estado de las comunicaciones de


todos los dispositivos configurados en la EGX.

56

Pgina web de la EGX

Documentacin
Documentacin

Control
Restablecimientos

Diagnsticos

Mantenimiento
Registro de mantenimiento Muestra la fecha, la hora y el usuario que ha
realizado el ltimo mantenimiento del equipo y
proporciona datos de entrada sobre el
mantenimiento realizado.
1

57

Slo el administrador tiene acceso.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

CONFIGURACIN

Para acceder a los vnculos de la pgina web Configuracin, haga clic en


Configuracin en la barra de mens de la EGX.

Configuracin de Ethernet y TCP/IP


Accin

Resultado

1. En el men Configuracin, haga clic en Abre la pgina Ethernet y TCP/IP.


Ethernet y TCP/IP.
2. Seleccione el formato de trama y el tipo Selecciona el formato de trama y el tipo de medio.
de medio. Si no los conoce, pngase en
contacto con el administrador de la red.
3. Introduzca su direccin IP, la mscara
de subred y la direccin predeterminada de la pasarela asignadas a
la EGX por el administrador de la red.

Introduce los parmetros de Ethernet para la EGX.


NOTA: Si introduce una direccin IP que ya est
siendo utilizada por otro dispositivo, se le pedir
que seleccione una direccin IP diferente.
Consulte Deteccin de direcciones IP duplicadas
en la pgina 8.

4. Haga clic en Aplicar.

Actualiza la configuracin de Ethernet y TCP/IP de


la EGX.

* Consulte la Tabla 2 a continuacin para ver una lista de opciones.

Figura 3:

Tabla 2:

Pgina Ethernet y TCP/IP

Configuracin de Ethernet y TCP/IP de la EGX

Opcin

Descripcin

Valor

Formato de
trama

Se utiliza para seleccionar el formato en Ethernet II, 802.3 SNAP


el que se envan los datos a travs de
Predeterminado: Ethernet II
una conexin Ethernet.

Tipo de medio

Se utiliza para definir la conexin fsica a


Ethernet o el tipo de medio.

10T/100Tx Auto
10BaseT-HD
10BaseT-FD
100BaseTX-HD
100BaseTX-FD

Predeterminado: 10T/100Tx Auto


Obtener una
Se utiliza para obtener automticamente Activado o desactivado
direccin IP
una direccin IP de un servidor BootP. Predeterminado: Desactivado
automticamente NOTA: Requiere apoyo de la
administracin de la red.
Direccin IP

Sirve para introducir la direccin IP


esttica de la EGX.

Predeterminado: 169.254.0.10

Mscara de
subred

Se utiliza para introducir la direccin de


la mscara de subred de la red.

Predeterminado: 255.255.0.0

Pasarela
predeterminada

Se utiliza para introducir la direccin IP


de la pasarela (router) que se usa para
las comunicaciones con la red de rea
extendida (WAN).

Predeterminado: 0.0.0.0

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Configuracin avanzada de Ethernet

AVISO
RENDIMIENTO REDUCIDO DE LA RED
Solo los trabajadores cualificados deben cambiar la configuracin
avanzada de Ethernet de la EGX. Tales modificaciones deben realizarse
solo despus de leer acerca de la configuracin avanzada de Ethernet y
comprenderla.
El incumplimiento de estas instrucciones puede reducir el
rendimiento de la red.

Accin
1. Haga clic en Avanzado en la pgina
Ethernet y TCP/IP.

Resultado
Abre la pgina Configuracin avanzada de
Ethernet.

2. Configure los parmetros avanzados de


Configura los parmetros avanzados de
Ethernet (consulte la Tabla 3 en la
Ethernet.
pgina 7 para ver las opciones
disponibles). Haga clic en
Predeterminados para asignar los valores
predeterminados a todas las opciones.
3. Haga clic en Aplicar.
NOTA: Al aplicar los cambios a la pgina
Configuracin avanzada de Ethernet,
no se guardan los cambios en la pgina
Ethernet y TCP/IP.
4. Haga clic en Aceptar para aceptar los
cambios y restablecer la EGX.

Figura 4:

Actualiza la configuracin de Ethernet


y TCP/IP de la EGX.

La EGX se reinicia.

Pgina Configuracin avanzada de Ethernet

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Tabla 3:

Configuracin avanzada de Ethernet de la EGX

Opcin

Descripcin

Valor

Perodo de vida

Identifica el nmero de routers (pasarelas) que


puede pasar un paquete TCP.

1 a 255 saltos
Predeterminado:
60 saltos

Mantenimiento de
conexin TCP

Un temporizador que detecta cundo un


0 a 65.000 segundos
dispositivo conectado o una conexin inactiva
Predeterminado:
pasa a no estar disponible debido a eventos tales 30 segundos
como un reinicio o apagado. El valor de 0
deshabilita esta opcin.

Tiempo de espera
de BootP

Se utiliza para especificar durante cunto tiempo 0 a 60 segundos


esperar la EGX a que un servidor BootP asigne Predeterminado:
sus direcciones IP. (La direccin IP
15 segundos
predeterminada se utiliza despus del tiempo de
espera si no se ha asignado ninguna direccin IP.)

Tiempo de espera
de la cach ARP

Se utiliza para especificar durante cunto tiempo


se mantendrn las entradas de la tabla ARP
(Protocolo de resolucin de direcciones).

Servidor FTP

Controla si se inicializa el servidor FTP durante el Desactivado o Activado


arranque.
Predeterminado:
Activado

Tiempo de
inactividad de
conexin FTP

Un temporizador que cierra la conexin FTP


30 a 900 segundos
despus de una cantidad especfica de tiempo de Predeterminado:
inactividad.
120 segundos

Tiempo de
inactividad de
conexin HTTP

Un temporizador que cierra la conexin HTTP


0 a 65.000 segundos
despus de una cantidad especfica de tiempo de Predeterminado:
inactividad.
4 segundos

Nmero de
puerto HTTP

El puerto TCP utilizado para los mensajes HTTP.


Los siguientes nmeros de puerto estn reservados
para otros protocolos de red y no pueden usarse: 20
y 21 (FTP) y 502 (Modbus TCP/IP).

0 a 65.000
Predeterminado: 80
0: Desactiva el
puerto HTTP.

Nmero de
puerto HTTPS

Puerto TCP utilizado para los mensajes HTTPS.


La EGX viene con un certificado autofirmado.
Para convertir la EGX en un servidor de plena
confianza, debe adquirir un certificado a una
entidad emisora de certificados (por ejemplo, los
servicios de autenticacin VeriSign).

De 1 a 65.000
Predeterminado: 443
0: Desactiva el
puerto HTTPS.

0 a 65.000 minutos
Predeterminado:
15 minutos

Para agregar/instalar un certificado digital,


desplcese manualmente a la pgina de
actualizacin de certificados empleando la URL
http://x.x.x.x./update_certs_shtml, donde x.x.x.x
es la direccin IP de la EGX.
Mximo de
Se utiliza para especificar el nmero mximo de
mantenimientos de mantenimientos de conexiones HTTP.
conexiones HTTP

0 a 65.000
Predeterminado: 100

Conexiones
servidor Modbus
TCP/IP

Se utiliza para especificar el nmero de


conexiones disponibles del servidor Modbus
TCP/IP.

16 a 64
Predeterminado: 32

Difusin Modbus

Determina cmo se tratan los mensajes TCP/IP


Modbus con ID de unidad de 0 en la subred serie.
Desactivado = se ignoran todos los mensajes.
Activado = se tratan todos los mensajes como
difusiones a puertos serie sin que se espere una
respuesta. Activado con respuesta = todos los
mensajes se tratan como mensajes regulares a
puerto serie para los que se espera una respuesta.

Desactivado, Activado
o Activado con
respuesta
Predeterminado:
Desactivado

Proxy
MODBUS/TCP

Parmetro que determina si los mensajes Modbus Desactivado o Activado


Predeterminado:
TCP/IP procedentes de clientes remotos se
encaminan a dispositivos remotos Modbus TCP/IP Activado
que estn definidos en la EGX.

Tiempo de espera Cantidad de tiempo que la EGX esperar a que un 0,1 a 10


de cliente Modbus dispositivo remoto Modbus TCP/IP responda a
Predeterminado:
TCP/IP
una solicitud Modbus TCP/IP iniciada por la EGX. 5 segundos
Tiempo de espera
de conexin de
cliente Modbus
TCP/IP

Cantidad de tiempo que la EGX esperar a que un De 1 a 10


dispositivo remoto Modbus TCP/IP responda a
Predeterminado:
una solicitud de conexin Modbus TCP/IP iniciada 2 segundos
por la EGX.

Tiempo de
inactividad de
conexin de
servidor Modbus
TCP/IP

Un temporizador que cierra la conexin Modbus


0 a 32.767 segundos
TCP/IP despus de una cantidad especificada de Predeterminado: 0
tiempo de inactividad. El valor de 0 deshabilita
esta opcin.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Deteccin de direcciones IP duplicadas

Mientras est conectada a la red, la EGX publica su direccin IP. Para


evitar conflictos de direcciones IP duplicadas, la EGX utiliza el protocolo de
resolucin de direcciones (ARP) para ver si algn dispositivo de la red
utiliza la misma direccin IP. En la Tabla 4 a continuacin se explica cmo
trata la EGX las direcciones duplicadas al detectarlas.
Tabla 4:

Situaciones de deteccin de IP duplicadas

Situacin

IP duplicada detectada

Proceso de inicio/restablecimiento de alimentacin


Enlace de Ethernet
detectado

Cambio manual de la
direccin

LED de
alimentacin/estado

Vuelve a la direccin IP, la mscara de Patrn de 4 parpadeos y


subred y la direccin de la pasarela
pausa
predeterminadas de la EGX. Las
solicitudes ARP se envan cada
15 segundos hasta que la direccin IP
queda disponible. Cuando la
direccin IP quede disponible, la EGX
la utilizar.
La EGX mantiene su direccin IP
anterior y muestra un mensaje que
indica que otro dispositivo ya la est
empleando.

Recibe una solicitud ARP Vuelve a la direccin IP, la mscara de Patrn de 4 parpadeos y
subred y la direccin de la pasarela
pausa
predeterminadas de la EGX si un
dispositivo conectado enva cuatro
solicitudes ARP de la direccin IP de
la EGX. La EGX enviar
solicitudes ARP cada 15 segundos
hasta que la direccin IP vuelva a
quedar disponible. Cuando la
direccin IP quede disponible, la EGX
la utilizar.

Puerto serie
Accin
1. En el men Configuracin, haga clic en
Puerto serie.

Abre la pgina Puerto serie.

2. Seleccione la interfaz fsica, el modo de


transmisin, la velocidad en baudios, la
paridad y el tiempo de espera de
respuesta (consulte la Tabla 5 en la
pgina 9).

Selecciona las opciones del puerto serie.

3. Haga clic en Aplicar.

Actualiza la configuracin del puerto serie de


la EGX.

Figura 5:

Resultado

Pgina Puerto serie

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Tabla 5:

Configuracin del puerto serie

Opcin

Descripcin

Valor

Interfaz fsica Sirve para seleccionar el modo de


cableado fsico del puerto serie de
la EGX.

RS485 4 hilos, RS485 2 hilos o RS232


Predeterminado: RS485 2 hilos

Modo de
transmisin

Se usa para seleccionar el modo de


transmitir datos en una conexin serie.

Automtico
Modbus ASCII

NOTA: El modo Automtico le permite


comunicarse con dispositivos esclavos
Modbus RTU, Jbus y PowerLogic
(SY/MAX) en el mismo bus de
comunicaciones serie.
Velocidad en Se usa para seleccionar la velocidad de 2400, 4800, 9600, 19200, 38400,
baudios
transmisin de datos en una conexin
56000* o 57600*
serie.
Predeterminado: 19200
Paridad

Se usa para seleccionar el tipo de


Par, Impar o Ninguna
paridad con que comprobar la precisin Predeterminado: Par
de los datos mediante un bit de paridad.

Tiempo de
espera de
respuesta

Sirve para seleccionar el tiempo que


esperar la EGX a recibir respuesta de
un dispositivo serie.

0,1 a 10 segundos
Predeterminado: 3 segundos

* Slo est disponible si la interfaz fsica y el modo de transmisin son RS232/Modbus ASCII.

Configuracin avanzada del puerto serie

AVISO
RENDIMIENTO REDUCIDO DE LA RED
Solo los trabajadores cualificados deben cambiar la configuracin
avanzada del puerto serie de la EGX. Tales modificaciones deben
realizarse solo despus de leer acerca de la configuracin avanzada del
puerto serie y comprenderla.
El incumplimiento de estas instrucciones puede reducir el
rendimiento de las comunicaciones serie.

Accin

Resultado

1. Haga clic en Avanzado en la pgina Puerto serie.

Abre la pgina Configuracin


avanzada del puerto serie.

2. Configure los parmetros avanzados del puerto serie (para


ver las opciones disponibles, consulte la Tabla 6 en la
pgina 10 en la pgina 11). Haga clic en Predeterminados
para asignar los valores predeterminados a todas las
opciones.

Configura los parmetros


avanzados del puerto serie.

3. Haga clic en Aplicar.

Actualiza la configuracin
avanzada del puerto serie de
la EGX.

NOTA: Al aplicar los cambios a la pgina Configuracin


avanzada del puerto serie, no se guardan los cambios en la
pgina Puerto serie.

Figura 6:

2009-2013 Schneider Electric. Reservados todos los derechos.

Pgina Configuracin avanzada del puerto serie

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Tabla 6:

Configuracin avanzada del puerto serie

Opcin

Conexiones con dispositivos


remotos

Descripcin

Valor

Retardo entre
tramas

Define el intervalo silencioso mnimo entre 0 a 100 milisegundos


el final de la respuesta recibida y el
Predeterminado:
comienzo de una nueva solicitud en la
50 milisegundos
lnea serie.

Extensin de
intervalo
silencioso

Permite que el intervalo silencioso utilizado 0 a 15 caracteres


Predeterminado: 6 caracteres
para marcar el final de un paquete
ModbusRTU se ample ms all de los
3,5 caracteres definidos por la norma.

Cdigo de
excepcin de
tiempo de espera
Modbus TCP/IP

Indica el cdigo de respuesta de excepcin 0x0A o 0x0B


Predeterminado: 0x0B
que se devuelve cuando un dispositivo
serie conectado a la EGX no responde
antes del tiempo de espera del puerto
serie. Modbus TCP/IP utiliza 0x0B. Sin
embargo, en algunas suites de software
anteriores se utilizaba 0x0A.

La EGX permite abrir conexiones para un mximo de 16 dispositivos nicos


Modbus TCP/IP definidos por el usuario. Podr introducirlas manualmente
o seleccionarlas a partir de una tabla que recoge las conexiones detectadas
por la funcin Punto de acceso del sistema (consulte la Figura 7 de la
pgina 11). Estas conexiones se ponen a disposicin de la configuracin de
la lista de dispositivos para la configuracin de dispositivos remotos.
Accin
1. En el men Configuracin, haga clic en
Conexiones con dispositivos remotos.

Resultado
Abre la pgina Conexiones con dispositivos
remotos.

2. Para agregar una conexin manualmente, Introduce las direcciones IP de los dispositivos
introduzca la direccin IP de los
remotos.
dispositivos remotos a los que desee
conectarse.
3. Para agregar una conexin detectada
Introduce la direccin IP correspondiente a la
gracias a la funcin Punto de acceso del
conexin detectada por la funcin Punto de
sistema, haga clic en Aadir (a la derecha acceso del sistema que haya seleccionado.
de la conexin que desee en la tabla de
conexiones detectadas).
4. Haga clic en Aplicar.

10

Actualiza la configuracin de las conexiones


con dispositivos remotos de la EGX.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Figura 7:

2009-2013 Schneider Electric. Reservados todos los derechos.

Conexiones con dispositivos remotos

11

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Lista de dispositivos de la EGX

Antes de comenzar, tenga en cuenta que no debe utilizar las direcciones


serie esclavas 1 o 16 en un modo de transmisin Automtico en un bus de
comunicaciones serie con protocolos mixtos (por ejemplo, una sola
conexin en bus de comunicaciones serie con algunos dispositivos que
usen el protocolo PowerLogic y otros que usen el protocolo Modbus
RTU/Jbus).

Conexin de dispositivos a una EGX

La Figura 8 y la Figura 9 ilustran la manera en que los dispositivos se


conectan a la EGX. Para agregar esos dispositivos a la Lista de
dispositivos, siga los pasos que se indican en Configuracin de la lista de
dispositivos en la pgina 13.
Figura 8:

Topologa: Slo dispositivos esclavos en serie

Conexin Ethernet
Pginas web de la EGX300
EGX

Conexin RS485

Dispositivos esclavos en serie

Figura 9:

Topologa: Dispositivos esclavos y remotos en serie


Conexin Ethernet

Pginas web de la EGX300


Direccin IP de
la EGX100:
169.254.0.28

Son posibles hasta


16 conexiones IP remotas

Direccin IP de
la EGX300:
169.254.0.75

Conexin
RS485

Dispositivos esclavos remotos

12

Conexin RS485

Dispositivos esclavos en serie

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Configuracin de la lista de dispositivos


Accin
1. En el men Configuracin, haga clic en
Lista de dispositivos.

Resultado
Abre la pgina Lista de dispositivos. (Consulte
la Figura 10 para conexiones exclusivamente
locales, o bien la Figura 11 si hay conexiones
remotas disponibles.)

2. Utilice Deteccin para localizar dispositivos Abre la pgina Deteccin de dispositivos para
detectar todos los dispositivos conectados
conectados localmente (consulte
localmente.
Deteccin de dispositivos en la
pgina 15). Si se requiere configuracin de
dispositivos remotos, contine en el
paso 3.
3. Consulte la Figura 11 de la pgina 14 y
seleccione el nmero de dispositivos
visualizables (1 a 64).

Selecciona el nmero de ubicaciones


visualizables que utilizar para definir los
dispositivos conectados a la EGX.

4. Seleccione la conexin en la lista


desplegable.*

Selecciona la conexin.

5. Seleccione el tipo de dispositivo en la


lista desplegable.*

Selecciona el tipo de dispositivo.

6. En el cuadro de texto Nombre del


dispositivo, escriba el nombre del
dispositivo.

Introduce el nombre del dispositivo.

7. En el cuadro de texto ID local, escriba la Introduce la direccin local del dispositivo.


direccin del dispositivo esclavo serie si
est en el puerto serie, o escriba la
direccin que desee utilizar para acceder a
un dispositivo remoto.*
8. En el cuadro de texto ID remoto, escriba la Introduce la direccin del dispositivo remoto.
direccin del dispositivo remoto.*
9. Repita los pasos 4 a 8 hasta introducir
todos los dispositivos.

Introduce todos los dispositivos conectados.

10. Haga clic en Aplicar.

Actualiza los valores de Lista de dispositivos.

* Este parmetro de configuracin slo se puede cambiar si est deshabilitado el registro de


datos para el dispositivo que se est actualizando. Consulte Registro de dispositivos en la
pgina 17.

Figura 10:

2009-2013 Schneider Electric. Reservados todos los derechos.

Pgina Lista de dispositivos

13

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Figura 11:

Tabla 7:

Pgina Lista de dispositivos con las conexiones remotas


admitidas

Configuracin de Lista de dispositivos

Opcin

14

Descripcin

Valor

Nmero de
dispositivos
visualizables

Selecciona el nmero de dispositivos que


se tienen que mostrar.

De 1 a 64
Predeterminado: 8

Conexin

Selecciona el sitio de la conexin.

Puerto serie o direccin IP


Predeterminado: Puerto
serie

Tipo de dispositivo

Selecciona el tipo de dispositivo que tiene


que aparecer en la lista.

Gama de dispositivos
admitidos

Nombre del
dispositivo

Le permite asignar nombres a dispositivos


individuales.

ID local

Debe definir el ID local.

ID remoto

Debe definir el ID remoto.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Deteccin de dispositivos

La opcin Deteccin de dispositivos permite a la EGX detectar dispositivos


Modbus residentes en el puerto serie que no figuran en Lista de dispositivos.
Los dispositivos previamente introducidos en Lista de dispositivos se validan
independientemente del intervalo de deteccin establecido.
Deteccin
Cuando inicia una deteccin de dispositivos, la EGX consulta el puerto serie
local utilizando un intervalo de direcciones definido por el usuario (consulte
la Figura 12 de la pgina 16). Para la deteccin en la conexin en serie, se
utiliza el protocolo Modbus ASCII o RTU, dependiendo de la configuracin
del puerto serie actual. Si el dispositivo contesta a la consulta, el ID local se
establece en la direccin de deteccin actual y se proporciona al dispositivo
un nombre de dispositivo predeterminado. La EGX intenta entonces
identificar el tipo de dispositivo. Si la EGX reconoce el tipo de dispositivo del
dispositivo detectado, la EGX introduce el tipo de dispositivo reconocido en
el campo Tipo de dispositivo. Si la EGX no reconoce el tipo de dispositivo, el
campo Tipo de dispositivo se establece al valor predeterminado Modbus.
Un campo de estado muestra el estado de deteccin.
Validacin
Todas las entradas de Lista de dispositivos previamente definidas para
todas las conexiones (serie y remotas), ya estn aquellas dentro o fuera del
intervalo de direcciones de comienzo y fin de deteccin, se validan durante
el proceso de deteccin. El protocolo de validacin en la conexin serie se
determina en funcin de la configuracin actual del dispositivo en la lista de
dispositivos. El protocolo TCP/IP se utiliza para la validacin de dispositivos
remotos. La EGX muestra el ID local, el nombre del dispositivo almacenado
y el tipo de dispositivo almacenado de Lista de dispositivos, y luego
consulta al dispositivo. Se muestra el tipo de dispositivo identificado por la
consulta, y luego se compara con lo que se ha definido previamente. El
estado mostrar entonces si se ha encontrado una diferencia o si es vlida
la configuracin previamente definida.
NOTA: Puede editar el nombre del dispositivo y el tipo de dispositivo y
seleccionar individualmente los dispositivos que se guardarn en Lista de
dispositivos. Sin embargo, si est habilitado el registro para un dispositivo,
slo podr modificar su nombre.
Accin

Resultado

1. En el men Configuracin, haga clic en Lista Abre la pgina Lista de dispositivos.


de dispositivos.
2. Para detectar dispositivos conectados
localmente, haga clic en Deteccin.

Abre la pgina Deteccin de dispositivos.

3. Introduzca una direccin de comienzo y una Introduce el intervalo de direcciones de


direccin de fin.
deteccin.
NOTA: Se validarn los dispositivos
introducidos previamente en la lista de
dispositivos con direcciones (ID locales)
fuera del intervalo de deteccin.
4. Haga clic en Iniciar deteccin. (Haga clic en Comienza por detectar todos los
Detener deteccin para detener el proceso.) dispositivos conectados y definidos.
NOTA: La deteccin slo busca dispositivos
serie Modbus locales conectados a la EGX.
Los dispositivos remotos se tienen que
agregar manualmente. Consulte Conexiones
con dispositivos remotos en la pgina 10.
5. Introduzca un nombre del dispositivo nuevo
en el cuadro de texto Nombre.

Cambia el nombre del dispositivo.

6. Marque la casilla de verificacin Guardar


Selecciona una entrada de dispositivo que
situada junto al dispositivo que desee guardar se tena que guardar o suprimir, o cancela la
en Lista de dispositivos.
seleccin de esta.
7. Haga clic en Aplicar en la pgina Deteccin
de dispositivos.

2009-2013 Schneider Electric. Reservados todos los derechos.

Guarda en la lista de dispositivos la


configuracin de todos los dispositivos que
se han marcado para ser guardados.

15

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Figura 12:

Tabla 8:
Opcin

16

Deteccin de dispositivos

Opciones de deteccin de dispositivos


Descripcin

Valor

Direccin de
comienzo/fin

Define el intervalo de direcciones Modbus


que se utilizar para detectar dispositivos
conectados al puerto serie de la EGX.

De 1 a 247
Predeterminado:
comienzo: 1; fin: 10

Guardar

Le permite guardar el dispositivo


seleccionado en Lista de dispositivos.

Activado o desactivado
Predeterminado: Activado

Conexin

Muestra la conexin en la que se ha


detectado o validado el dispositivo.

Puerto serie o direccin IP


(para validacin de
dispositivos remotos)

Definido

Muestra el tipo de dispositivo definido para


este dispositivo.

Asignado

Le permite asignar el tipo de dispositivo de


la lista desplegable.

Nombre

Le permite introducir un nombre


personalizado para el dispositivo.

ID local

Muestra el ID local del dispositivo.

ID remoto

Muestra el ID del dispositivo remoto.

Estado

Muestra el estado de deteccin o


validacin.

Vlido, Desconocido, Error,


Encontrado, Detectando o
Intentando

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Registro de dispositivos

El registro de datos est disponible para todos los tipos de dispositivos


admitidos por la EGX. La EGX es capaz de registrar a intervalos
predefinidos (5, 10, 15, 20, 30 y 60 minutos) datos procedentes de
dispositivos conectados tanto local como remotamente. A continuacin se
ofrece una explicacin de cmo registra datos la EGX y cmo se configura
el registro para un dispositivo.

Registro de datos de intervalo

Muchos de los dispositivos de un sistema de supervisin de potencia


no poseen la capacidad para registrar datos en una memoria no voltil.
La EGX300 proporciona este tipo de registro de datos a intervalos
predefinidos para un mximo de 64 dispositivos conectados en serie y
remotamente. Almacena los datos registrados en archivos FIFO (Primero
en entrar, primero en salir) no voltiles.
La capacidad de registro de cada archivo de registro cronolgico de datos
es variable y depende del intervalo de registro seleccionado. Dicha
capacidad se calcula dividiendo el nmero mximo de intervalos registrados
que puede albergar un archivo de registro (171.072) entre el producto del
nmero de temas registrados por los intervalos registrados diariamente.
Capacid. archivo de reg. = Intervs. (mx.)/(temas por interv. x intervalos reg. a diario)

Por ejemplo, la capacidad del registro cronolgico de datos de un


dispositivo que almacena tres temas cada 10 minutos se calculara de la
siguiente manera:
Intervalos registrados diariamente = Minutos del da/intervalo de registro (en min)
= 1140/10
= 144 intervalos
Capacidad del archivo de registro = Mximo de intervalos posibles/(temas
registrados por intervalo x intervalos registrados diariamente)
= 171072/(3 x 144)
= 396 das

La capacidad de registro se calcula dinmicamente y se muestra en la pgina


de seleccin de temas (consulte la Tabla 9 para ver algunos ejemplos).
Tabla 9:

Intervalos de registro de muestreos

N. de temas

Configurar registro por intervalos

Capacidad de registro (en das) de los intervalos de registro


designados
Intervalo de 5 min

Intervalo de 10 min

Intervalo de 15 min

594

1188

1782

297

594

891

198

396

594

148

297

445

118

237

356

99

198

297

Cada dispositivo incluido en la lista de dispositivos se puede habilitar


independientemente para registro de datos. Los temas que registrar son
exclusivos de cada dispositivo. Para ver los registros de datos de intervalo,
consulte Registro de dispositivos en la pgina 40.
NOTA: Para habilitar la funcin Registro de dispositivos, es necesario
seleccionar un valor de tiempo en la ventana desplegable Intervalo de
registro. Se recomienda que deshabilite la funcin de registro de
dispositivos correspondiente al dispositivo que se est configurando. Para
ello consulte la Figura 13 de la pgina 18 y desactive la casilla de
verificacin de registro relativa al dispositivo que se va a seleccionar.

2009-2013 Schneider Electric. Reservados todos los derechos.

17

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Accin

Resultado

1. En el men Configuracin, haga clic en Registro de


dispositivos (consulte la Figura 13).
2. Consulte la Figura 13 y marque Registro para los
dispositivos que desee registrar.
Para seleccionar todos los dispositivos, haga clic en
seleccionar todo y, a continuacin, haga clic en
Aplicar.
Para cancelar la seleccin de todos los dispositivos,
haga clic en borrar, y a continuacin, haga clic en
Aplicar.
3. Seleccione el intervalo de registro.

Abre la pgina Registro de


dispositivos.
Selecciona los dispositivos que se
tienen que registrar.

4. Haga clic en Aplicar.


OPCIONES
Si desea personalizar el contenido del registro, habilite el
registro de dispositivos y, a continuacin, lleve a cabo lo
siguiente:
1. Seleccione un intervalo de registro que no sea cero y
desactive la casilla Registro del dispositivo especfico.
2. Bajo Personalizar, haga clic en el vnculo temas
correspondiente al dispositivo que desee configurar.
3. Consulte la Figura 14 de la pgina 19 y marque los
temas que desee registrar.
Para seleccionar todos los temas, haga clic en
seleccionar todo y, a continuacin, haga clic en
Aplicar.
Para cancelar la seleccin de todos los temas, haga
clic en borrar, y a continuacin, haga clic en Aplicar.
Para seleccionar los temas predeterminados, haga
clic en Predeterminados en la parte inferior de la
pantalla.
Para borrar registros de datos, marque Purgar datos en
aquellos que desee borrar.
1. Para seleccionar todos los dispositivos, haga clic en
seleccionar todo y, a continuacin, en Aplicar.
2. Para cancelar la seleccin de todos los dispositivos, haga
clic en borrar, y a continuacin, haga clic en Aplicar.
Para deshabilitar el registro, seleccione el intervalo de
registro cero, asegrese de que no haya ninguna seleccin
de Registro marcada y, a continuacin, haga clic en Aplicar.

Figura 13:

Temas que registrar

Selecciona el intervalo de registro


para los dispositivos
seleccionados.
Actualiza la configuracin del
registro de dispositivos de la EGX.
Selecciona los temas de
dispositivos que se tienen que
registrar y luego vuelve a la pgina
principal Registro de dispositivos.
NOTA: Si cambia los temas
predeterminados registrados
relativos a un dispositivo,
aparece un asterisco (*) junto
a temas en la columna
Personalizar correspondiente
a ese dispositivo. El cambio de
los temas de un registro de
dispositivos que ya haya
estado activo borrar todos los
datos previamente registrados
para este dispositivo. Cuando
sea necesario, los datos deben
recuperarse de la EGX antes
de hacer los cambios.
Selecciona los registros de datos
que se tienen que purgar.
NOTA: Para purgar un registro
de datos, el dispositivo no debe
tener habilitada la casilla de
verificacin Registro.
Deshabilita la funcin de registro.

Pgina Registro de dispositivos

Es posible seleccionar individualmente los temas que se registrarn por


cada dispositivo.
Accin

Resultado

1. En la pgina Registro de dispositivos, haga clic en el vnculo


temas del dispositivo deseado.

Abre la pgina de seleccin


de temas.

2. Consulte la Figura 14 de la pgina 19 y marque los temas que Selecciona los temas que
debern registrarse.
desee registrar.
Para seleccionar todos los temas, haga clic en
seleccionar todo.
Para cancelar la seleccin de todos los temas, haga clic en
borrar.
Para seleccionar los temas predeterminados, haga clic en
Predeterminados.
3. Haga clic en Aplicar.

18

Guarda la seleccin de
temas que se registrarn.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Figura 14:

Exportacin del registro de


dispositivos

Pgina de seleccin de temas

Esta opcin le permite exportar registros de dispositivos de tres maneras:


por correo electrnico, por FTP o por HTTP. En las secciones siguientes se
describen dichos mtodos.
NOTA: Si los servidores de correo electrnico, FTP o HTTP no estn
situados en el mismo segmento de red Ethernet que la EGX, asegrese de
configurar correctamente la pasarela predeterminada de la EGX. Consulte
Configuracin de Ethernet y TCP/IP en la pgina 5.

Exportacin por correo electrnico


Accin

Resultado

1. En la pgina Configuracin, haga clic en Exportacin del Abre la pgina Exportacin del
registro de dispositivos.
registro de dispositivos.
2. Seleccione Correo electrnico como modo de
transporte.

Abre las opciones de


exportacin de registros de
dispositivos por correo
electrnico.

3. Marque la casilla de verificacin Incremental.

Selecciona slo datos de


intervalos nuevos registrados
desde la ltima exportacin de
datos realizada correctamente.

NOTA: Si el transporte se programa como Cada hora o


como Intervalo de registro, la casilla de verificacin
Incremental se seleccionar automticamente.
NOTA: Si no se selecciona la casilla de verificacin
Incremental, se enviar el archivo de registros completo
por correo electrnico en cada intervalo programado.
4. Seleccione Cada hora, Diariamente, Semanalmente,
Mensualmente o Intervalo de registro.

2009-2013 Schneider Electric. Reservados todos los derechos.

Selecciona la frecuencia con la


que se envan los registros de
datos.

19

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Accin

Resultado

5. Dependiendo de las opciones seleccionadas en el paso


anterior, seleccione la hora del da, el da de la semana
y/o el da del mes.

Selecciona cundo se envan


los registros de datos.

6. En el cuadro de texto Desde direccin, escriba la


direccin de correo electrnico de la persona que
administra el dispositivo.

Introduce desde qu direccin


se ha enviado el correo
electrnico.

NOTA: Se necesita una direccin de correo electrnico


del remitente porque la mayora de los servidores SMTP
as lo requieren.
Introduce las direcciones de
7. En los cuadros de texto A direcciones, escriba las
direcciones de correo electrnico (cinco como mximo) de correo electrnico de los
las personas que van a recibir los registros de datos (una receptores.
direccin por cada cuadro de texto).
8. En los cuadros de texto Direccin IP del servidor,
introduzca la direccin del servidor de correo saliente
(0.0.0.0 a 255.255.255.255).
NOTA: Pregunte al administrador de la red en caso de
que usted no conozca la direccin del servidor de
protocolo sencillo de transferencia de correo (SMTP).
9. En el cuadro de texto Puerto TCP del servidor,
introduzca el puerto de entrega del servidor de correo
saliente.

Introduce la direccin del


servidor que entrega los
registros de datos de correo
electrnico.

Introduce el puerto de entrega


del servidor de correo saliente.
Predeterminado: 25

10. Si el servidor SMTP requiere informacin de inicio de


Le permite introducir
sesin, habilite la casilla de verificacin El servidor SMTP informacin de inicio de
requiere iniciar sesin.
sesin del servidor SMTP.
NOTA: La EGX es compatible con autenticacin de
acceso Plain, Login, CRAM-MD5 y Digest-MD5.
11. Si ha marcado la casilla de verificacin El servidor SMTP Registra su informacin de
requiere iniciar sesin, introduzca su nombre de usuario inicio de sesin del
y su contrasea en los cuadros de texto correspondientes. servidor SMTP.
12. Haga clic en Correo electrnico de prueba para enviar Enva un correo electrnico de
un correo electrnico de prueba utilizando los parmetros prueba, aplica los valores de
establecidos por usted, o haga clic en Aplicar.
correo electrnico para exportar
registros o realiza ambas
NOTA: Al hacer clic en Correo electrnico de prueba, se
acciones.
aplican los valores de correo electrnico para exportar
registros y se enva un correo electrnico de prueba; y al
hacer clic en Aplicar, slo se aplican los valores.

Figura 15:

20

Pgina Exportacin de registros de dispositivos: Correo


electrnico

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Exportacin por FTP


Accin

Resultado

1. En la pgina Configuracin, haga clic en Exportacin Abre la pgina Exportacin del


del registro de dispositivos.
registro de dispositivos.
2. Seleccione FTP como modo de transporte.

Abre las opciones de exportacin


de registro de dispositivos por FTP.

Selecciona para su envo slo los


nuevos datos registrados desde el
NOTA: Si el transporte se programa como Cada hora
ltimo intervalo de envo correcto.
o como Intervalo de registro, la casilla de verificacin
Incremental se seleccionar automticamente.

3. Habilite la casilla de verificacin Incremental.

NOTA: Si no se selecciona la casilla de verificacin


Incremental, se enviar el archivo de registro
completo por FTP en cada intervalo programado.
4. Seleccione Cada hora, Diariamente, Semanalmente, Selecciona la frecuencia con la que
Mensualmente o Intervalo de registro.
se transportan los registros de
datos.
5. Dependiendo de las opciones seleccionadas en el
paso anterior, seleccione la hora del da, el da de la
semana y/o el da del mes.

Selecciona cundo se transportan


los registros de datos.

6. En los cuadros de texto Direccin IP del servidor,


introduzca la direccin del servidor FTP saliente
(0.0.0.0 a 255.255.255.255).

Introduce la direccin del servidor


que transporta los registros de
datos.

NOTA: Pregunte al administrador de la red en caso de


que usted no conozca la direccin del servidor de
protocolo de transferencia de archivos (FTP).
7. En el cuadro de texto Directorio, introduzca el
directorio.

Le permite introducir informacin


de directorio correspondiente al
servidor remoto.

8. Introduzca su nombre de usuario y contrasea en los


cuadros de texto.

Registra sus datos de inicio de


sesin en el servidor.

9. Habilite la casilla de verificacin Pasivo.

Establece la transferencia pasiva


de archivos por FTP.

10. Haga clic en Probar FTP para probar los parmetros


del FTP o haga clic en Aplicar.

Enva un archivo de prueba al


servidor y directorio FTP, aplica los
valores del FTP o realiza ambas
acciones.

NOTA: Al hacer clic en Probar FTP, se aplican los


valores del FTP para exportacin de registros y se
transfiere un archivo de prueba; y al hacer clic en
Aplicar, slo se aplican los valores.

Figura 16:

Pgina Exportacin de registro de dispositivos: FTP

NOTA: Si el transporte se programa como Cada hora o como Intervalo de registro, la casilla
de verificacin Incremental se seleccionar automticamente.

2009-2013 Schneider Electric. Reservados todos los derechos.

21

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Exportacin por HTTP


Accin

Resultado

1. En la pgina Configuracin, haga clic en


Exportacin del registro de
dispositivos.

Abre la pgina Exportacin del registro de


dispositivos.

2. Seleccione HTTP como modo de


transporte.

Abre las opciones de exportacin de registro


de dispositivos por HTTP.

3. Habilite la casilla de verificacin


Incremental.

Selecciona para su envo slo los nuevos


datos registrados desde el ltimo intervalo de
envo correcto.

NOTA: Si el transporte se programa como


Cada hora o como Intervalo de registro,
la casilla de verificacin Incremental se
seleccionar automticamente.
NOTA: Si no se selecciona la casilla de
verificacin Incremental, se enviar el
archivo de registro completo por HTTP en
cada intervalo programado.
4. Seleccione Cada hora, Diariamente,
Semanalmente, Mensualmente o
Intervalo de registro.

Selecciona la frecuencia con la que se


transportan los registros de datos.

5. Dependiendo de las opciones


seleccionadas en el paso anterior,
seleccione la hora del da, el da de la
semana y/o el da del mes.

Selecciona cundo se transportan los registros


de datos.

6. En los cuadros de texto Direccin IP del


servidor, introduzca la direccin del
servidor HTTP.

Introduce la direccin IP del servidor que


transporta los registros de datos.

NOTA: Pregunte al administrador de la red


en caso de que usted no conozca la
direccin del servidor del protocolo de
transferencia de hipertexto (HTTP).
7. En el cuadro de texto Puerto TCP del
servidor, introduzca el puerto del
servidor HTTP.

Introduce el puerto TCP de entrega saliente.


Predeterminado: 80

NOTA: Si desea exportar utilizando una


capa de sockets seguros (SSL), introduzca
el nmero de puerto TCP del
servidor HTTPS, que suele ser 443.
8. Si va a utilizar un servidor proxy,
Introduce la direccin IP del servidor proxy que
introduzca la direccin IP en los cuadros
transporta los registros de datos.
de texto Direccin IP del servidor proxy.
NOTA: Pregunte al administrador de la red
en caso de que usted no conozca la
direccin del servidor proxy.
9. En el cuadro de texto Puerto TCP del
servidor proxy, introduzca el puerto del
servidor HTTP.

Introduce el puerto TCP de entrega saliente.


Valor predeterminado: 0

NOTA: Si desea exportar utilizando una


capa de sockets seguros (SSL), introduzca
el nmero de puerto TCP del servidor
HTTPS, que suele ser 443.
10. En el cuadro de texto Ruta, introduzca la Introduce la ruta de secuencia de comandos
ruta de acceso a la secuencia de
del servidor.
comandos del servidor que ser ejecutada
por el servidor web cuando la EGX le enve
datos.
11. En el cuadro de texto Nombre de campo, Permite a la EGX insertar archivos a una
introduzca el nombre de archivo que el
secuencia de comandos existente de servidor
servidor web espera recibir.
web.
NOTA: Si no se requiere este dato, utilice
el valor predeterminado datafile1.

22

12. En el cuadro de texto Nombre de host,


introduzca el nombre de dominio del host.

Identifica un host especfico en el servidor web


en el caso de que aloje varios dominios en una
sola direccin IP. (Este cuadro est en blanco
de manera predeterminada.)

13. Introduzca su nombre de usuario y


contrasea en los cuadros de texto
dispuestos al efecto.

Registra sus datos de inicio de sesin en el


servidor.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Accin
14. Si desea exportar utilizando una capa de
sockets seguros, seleccione SSL.

Resultado
Todos los registros de dispositivos que se
exportan mediante HTTP, lo harn a travs de
una capa de sockets seguros (HTTPS).

15. Haga clic en Probar HTTP para probar los Enva un archivo de prueba al servidor y
valores del HTTP o haga clic en Aplicar. directorio HTTP, aplica los valores de HTTP o
realiza ambas acciones.
NOTA: Al hacer clic en Probar HTTP, se
aplican los valores de exportacin de
registros por HTTP y se transfiere un
archivo de prueba. Si se hace clic en
Aplicar, solamente se aplicarn los
valores.

Figura 17:

Fecha y hora

Pgina Exportacin del registro de dispositivos: HTTP

La pgina Fecha y hora le permite ajustar la fecha y la hora de la EGX.


Accin

Resultado

1. En el men Configuracin, haga clic en


Fecha y hora.

Abre la pgina Fecha y hora.

2. Configure ao, mes, da, hora, minutos y


segundos.

Establece la fecha y la hora.

3. Seleccione la Desviacin de zona


horaria.

Ajusta el reloj a la zona horaria seleccionada.

4. Para establecer que el reloj se ajuste


automticamente al horario de verano,
habilite la casilla de verificacin Habilitar
ajuste automtico del horario de
verano.

Le permite establecer que el reloj se ajuste


automticamente al horario de verano.

5. Introduzca nmero, da, mes y hora de


comienzo y fin del horario de verano.

Establece el comienzo y fin del ajuste del


horario de verano.

6. Haga clic en Aplicar.

Guarda la configuracin de Fecha y hora.

2009-2013 Schneider Electric. Reservados todos los derechos.

23

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Figura 18:

Sincronizacin horaria de red

Pgina Fecha y hora

La habilitacin de la sincronizacin de la hora de la red permite ajustar la


hora y la fecha del reloj del sistema EGX mediante un servidor de protocolo
de hora de la red (NTP).
NOTA: Si el servidor NTP no est situado en el mismo segmento de red
Ethernet que la EGX, asegrese de configurar correctamente la pasarela
predeterminada de la EGX.

Accin

Resultado

1. Seleccione la casilla de verificacin Activar Revela la seccin Parmetros de SNTP y la


sincronizacin horaria de red en la pgina ltima sincronizacin horaria realizada
Fecha y hora.
correctamente.
2. Configure la desviacin de zona horaria, el Configura los parmetros del SNTP.
intervalo de adquisicin y las
direcciones IP de los servidores principal y
secundario NTP (consulte la Tabla 10 en
la pgina 25).
3. Haga clic en Aplicar.

Figura 19:

24

Guarda la configuracin del SNTP.

Activar la sincronizacin horaria de red

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Tabla 10: Configuracin de los parmetros del SNTP


Opcin

Parmetros del SNMP

Descripcin

Valor

Desviacin de zona
horaria

La hora se establece sobre la base del


valor seleccionado de la hora universal
coordinada (UTC).

Habilitar ajuste
automtico del
horario de verano

Permite definir cundo comienza y termina Primer a Quinto o ltimo


el horario de verano.
Domingo a Sbado
Enero a Diciembre
0:00 a 23:00
Predeterminado:
Inicio del horario de verano:
Segundo Domingo de Marzo
a las 2:00.
Finalizacin del horario de
verano: Segundo Domingo
de Noviembre a las 2:00.

Intervalo de
adquisicin

Controla la frecuencia con la que la EGX


se pone en contacto con el NTP para
obtener la hora correcta.

De 1 hora a 1 semana
Predeterminado: 1 semana

Direccin IP del
servidor
principal NTP

La direccin IP del servidor principal NTP


con la que se pone en contacto la EGX
para obtener la hora correcta.

0.0.0.0 a 255.255.255.255
Predeterminado: 0.0.0.0

Direccin IP del
servidor
secundario NTP

La direccin IP del servidor secundario


NTP con la que se pone en contacto
la EGX para obtener la hora correcta.

0.0.0.0 a 255.255.255.255
Predeterminado: 0.0.0.0

UTC12:00 a UTC+13:00
Predeterminado: UTC
(GMT)

La EGX es compatible con el SNMP, lo cual permite que un administrador


de red acceda de manera remota a una EGX mediante un gestor de SNMP
y visualice el estado de la conexin y los diagnsticos de la EGX en
formato MIB-II.

Accin
1. En el men Configuracin, haga clic en
Parmetros del SNMP.

Resultado
Abre la pgina Parmetros del SNMP.

2. Marque la casilla de verificacin Activar SNMP Activa el SNMP.


para habilitar el protocolo simple de
administracin de redes.
3. Introduzca el contacto del sistema, el nombre
del sistema, su ubicacin, el nombre de la
comunidad de slo lectura y el nombre de la
comunidad de lectura y escritura.

Introduce la informacin del


sistema SNMP y los nombres de acceso
de las comunidades.

4. Haga clic en Aplicar.

Guarda los valores del SNMP.

Figura 20:

2009-2013 Schneider Electric. Reservados todos los derechos.

Pgina Parmetros del SNMP

25

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

Filtrado de Modbus TCP/IP

63230-319-216B3_ES
03/2013

Esta funcin permite al administrador asignar el nivel de acceso que los


clientes Modbus TCP/IP tienen a los dispositivos (locales o remotos)
conectados a la EGX.
NOTA: Existe una direccin Modbus TCP/IP annima (***.***.***.***) que se
puede configurar como Slo lectura o Ninguna. Si la configura como Slo
lectura, permitir que cualquier cliente Modbus TCP/IP que no est en la
lista de filtrado acceda a los dispositivos esclavos en serie con acceso de
slo lectura. Si la configura como Ninguna, bloquear a todos los clientes
Modbus TCP/IP que no estn en la lista de filtrado.
Accin

Resultado

1. En el men Configuracin, haga clic Abre la pgina Filtrado de Modbus TCP/IP.


en Filtrado de Modbus TCP/IP.
2. Marque la casilla de verificacin
Activar filtrado.

Activa el filtrado.

3. En la columna Direccin IP,


introduzca la direccin del cliente
Modbus TCP/IP.

Introduce la direccin IP de un cliente


Modbus TCP/IP que tendr acceso a los dispositivos
conectados a la EGX.

4. En la columna Nivel de acceso,


Selecciona el nivel de acceso para la correspondiente
seleccione Slo lectura o Completo. direccin IP. Cuando se establece como Slo lectura,
slo se permiten los siguientes cdigos de funcin
Modbus TCP/IP:
Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, 43, 100
Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C, 11, 14,
18, 2B, 64
5. Repita los pasos 3 y 4 para agregar Contina aadiendo direcciones IP para el filtrado.
ms direcciones IP.
6. Haga clic en Aplicar.

Figura 21:

26

Guarda la lista de filtrado de direcciones Modbus


TCP/IP.

Pgina Filtrado de Modbus TCP/IP

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Vnculos de documentacin

La EGX admite dos tipos de vnculos de documentacin:


1. acceso a archivo local (documentacin guardada incorporada en
la EGX);
2. acceso URL externo.
NOTA: Los documentos de archivos locales que desee que aparezcan en
la pgina web Documentacin deber colocarlos en la carpeta
www/documentation (documentacin) de la EGX utilizando FTP.
Accin

Resultado

1. En el men Configuracin, haga clic en


Vnculos de documentacin.

Abre la pgina Vnculos de documentacin.

2. Para acceso a archivo: Marque la casilla


de verificacin Activado correspondiente
a los vnculos de Nombre de archivo que
desee habilitar.

Define qu archivos y URL aparecen en la


pgina Documentacin.

Para acceso URL: Marque la casilla de


verificacin Activado correspondiente a
los vnculos de URL que desee habilitar.
3. Marque Ventana nueva si desea que los Define qu archivos y URL se abrirn en una
archivos y URL seleccionados se abran en ventana nueva cuando se haga clic en ellos.
una ventana nueva al hacer clic en ellos.
4. Asigne un nombre al ttulo del vnculo de
Establece el ttulo del vnculo de
documentacin en la casilla de verificacin documentacin que aparecer en la pgina
Texto del vnculo.
Documentacin.
5. Haga clic en Aplicar.

Figura 22:

Actualiza los valores de los vnculos de


documentacin de la EGX.

Pgina Vnculos de documentacin

NOTA: Para obtener informacin sobre la manera de acceder a la


documentacin cargada, consulte Documentacin en la pgina 50.

2009-2013 Schneider Electric. Reservados todos los derechos.

27

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

Cuentas de usuario

63230-319-216B3_ES
03/2013

A los usuarios de la EGX se les asignan nombres de usuario y contraseas.


Cada usuario pertenece a un grupo, cuyos derechos de acceso a las
pginas web de la EGX los asigna el administrador de la EGX.
NOTA: Existen dos cuentas de usuario predeterminadas: Administrator
(cuya contrasea predeterminada es Gateway) y Guest (cuya contrasea
predeterminada es Guest).
Accin

Resultado

1. En el men Configuracin, haga clic


en Cuentas de usuario.

Abre la pgina Cuentas de usuario.

2. Si desea cambiar el nombre de un


grupo, escriba el nuevo nombre en
uno de los cuadros de texto Grupos
(no se puede cambiar el nombre del
grupo Administradores).

Introduce un nuevo nombre de grupo.

3. En la seccin Usuarios, introduzca un Introduce el nombre y la contrasea de un usuario.


nombre (1 a 24 caracteres) y
contrasea (0 a 12 caracteres) para el La EGX300 comprueba el grado de la seguridad de
la contrasea, mostrando una indicacin cromtica
nuevo usuario.
y textual de su solidez:
NOTA: Los nombres de usuario y las
Rojo
= Contrasea en blanco/contrasea
contraseas respetan maysculas y
no segura
minsculas y slo pueden contener
Amarillo = Contrasea de seguridad media
caracteres alfanumricos.
Azul
= Contrasea segura
Verde = Contrasea muy segura
4. Seleccione un grupo y el idioma
Selecciona el grupo y el idioma para un usuario.
predeterminado para el nuevo usuario.
5. Repita los pasos 3 y 4 por cada
usuario adicional que desee agregar.

Contina aadiendo usuarios.

6. Haga clic en Aplicar.

Guarda toda la configuracin de las cuentas de


usuario.

Tabla 11: Cuentas y contraseas de la EGX


Cuenta

Gateway

Guest

Guest

Cuentas definidas por el usuario (hasta 11 cuentas)

Sin valor predeterminado. La contrasea


la define el usuario.

Figura 23:

28

Contrasea predeterminada

Administrator

Pgina Cuentas de usuario

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Acceso a pgina Web


Accin

Resultado

1. En el men Configuracin, haga clic en Acceso a Abre la pgina Acceso a pgina Web.
pgina Web.
2. Seleccione el nivel de acceso (Ninguna, Slo
lectura o Completo) que tiene cada grupo de
usuarios para las pginas web.

Consulte la Tabla 12 a continuacin para


ver una explicacin de los niveles de
acceso correspondientes a cada grupo.

3. Para permitir el acceso de invitados a la pgina


web, seleccione Slo lectura en la columna
Guest.

Permite que el grupo Guest


predeterminado acceda a la pgina web.

NOTA: Si el grupo Guest es de slo lectura, otros


grupos se pueden configurar como Slo lectura o
Completo.
4. Repita los pasos 2 y 3 para las opciones de cada Selecciona el nivel de acceso para cada
seccin.
pgina web.
5. Haga clic en Aplicar.

Guarda los valores de las contraseas.

Tabla 12: Acceso de grupo


Grupo

Acceso

Administrator

Acceso completo a todas las pginas web.


NOTA: Para garantizar la seguridad del sistema, le recomendamos que cambie
la contrasea predeterminada del administrador la primera vez que se conecte
al sistema.

Guest

Acceso de slo lectura a las pginas web seleccionadas.

Tres grupos
definidos por
el usuario

Al elegir entre las siguientes opciones, el administrador asigna el acceso a las


pginas web para cada grupo. Los niveles de acceso son los siguientes:

Figura 24:

2009-2013 Schneider Electric. Reservados todos los derechos.

Ninguna: el grupo no tiene acceso a la pgina web seleccionada.


Slo lectura: la contrasea le concede al grupo acceso de slo lectura a la
pgina web seleccionada.
Completo: el grupo tiene el mismo acceso que el grupo de administradores
a la pgina web seleccionada.

Pgina Acceso a pgina Web

29

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

Agregar o quitar pginas web personalizadas

63230-319-216B3_ES
03/2013

Las pginas web personalizadas y otros tipos de archivos pueden


transferirse desde su equipo a la EGX a travs de FTP. Los archivos
enviados a travs de FTP a los directorios www/monitoring (supervisin),
www/maintenance (mantenimiento) o www/control con extensiones .htm,
.html o .shtml se asegurarn automticamente. Cada carpeta cuenta con un
vnculo correspondiente en la barra de mens de la interfaz web. Cuando
se hace clic en el vnculo de la barra de mens, las pginas web que haya
agregado aparecern en el men en la parte izquierda de la ventana del
navegador bajo Pginas personalizadas.
NOTA: No se pueden crear nuevas carpetas dentro de las carpetas
Monitoring, Control o Maintenance.
Una vez que se hayan transferido las pginas web personalizadas u otros
archivos a la EGX con FTP, se pueden agregar y quitar de la interfaz web
sin eliminarlos de la EGX usando la pgina Agregar o quitar pginas Web.
Esta pgina se abre desde la pgina Acceso a pgina Web.

Adicin de pginas web mediante FTP


Accin

Resultado

1. Inicie el Explorador de Windows, escriba


Abre el cuadro de dilogo Iniciar sesin
ftp:// y la direccin IP de la EGX (por
como.
ejemplo, ftp://169.254.0.10) en el cuadro de
texto Direccin y luego pulse Intro.
2. Escriba el nombre de usuario Administrator Abre una sesin de FTP con la EGX.
y la contrasea de administrador en los
cuadros de texto, y luego haga clic en
Iniciar sesin.
3. Abra una nueva ventana del Explorador de Copia el archivo en el portapapeles.
Windows, ubique la pgina web
personalizada que desee enviar a la EGX,
haga clic sobre ella con el botn derecho
del ratn y despus haga clic en Copiar.
4. Vuelva a la ventana del Explorador de
Abre la carpeta donde se almacenar la
Windows de la EGX que abri en el paso 1 pgina web en la EGX.
y abra la carpeta en la que vaya a copiar la
pgina web (por ejemplo,
/www/monitoring/).
5. Haga clic con el botn derecho en el panel Copia la pgina web personalizada en la EGX.
derecho de la ventana del Explorador de
Windows, luego haga clic en Pegar.
NOTA: En vez de copiar y pegar el archivo,
puede arrastrarlo y soltarlo en el
Explorador de Windows.
6. Haga clic en Cerrar en la ventana del
Explorador de Windows.

Cierra el Explorador de Windows.

Eliminacin de pginas web mediante FTP


Accin

Resultado

1. Inicie el Explorador de Windows, escriba


Abre el cuadro de dilogo Iniciar sesin
ftp:// y la direccin IP de la EGX (por
como.
ejemplo, ftp://169.254.0.10) en el cuadro de
texto Direccin y luego pulse Intro.
2. Escriba el nombre de usuario Administrator Abre una sesin de FTP con la EGX.
y la contrasea de administrador en los
cuadros de texto, y luego haga clic en
Iniciar sesin.
3. Abra la carpeta que contiene la pgina web Abre la carpeta que contiene la pgina web
personalizada y despus borra el archivo.
personalizada, haga clic con el botn
derecho del ratn sobre el archivo que
quiera eliminar y despus haga clic en
Eliminar.
4. Haga clic en Cerrar en la ventana del
Explorador de Windows.

30

Cierra el Explorador de Windows.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Agregar o quitar pginas web a o de la


interfaz web

Accin

Resultado

1. En el men Configuracin, haga clic en


Acceso a pgina Web.

Abre la pgina Acceso a pgina Web.

2. Haga clic en Agregar o quitar pginas


Web (consulte la Figura 25).

Abre la pgina Agregar o quitar pginas Web.

3. Si ha agregado pginas web


Selecciona una pgina web personalizada o
personalizadas a cualquiera de las
anula la seleccin de esta.
carpetas de la EGX, ver una lista de los
nombres de archivo debajo del nombre de
cada carpeta. Seleccione las pginas web
que desee que vean los usuarios. Anule la
seleccin de las pginas web que no desee
que vean los usuarios.
NOTA: Al anular la seleccin de una pgina
web, esta no se borra de la EGX.
4. Haga clic en Aplicar.

Figura 25:

2009-2013 Schneider Electric. Reservados todos los derechos.

Agrega una pgina web personalizada a la


interfaz web de la EGX o la quita de esta.

Pgina Agregar o quitar pginas Web

31

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

Preferencias

63230-319-216B3_ES
03/2013

Esta opcin permite personalizar individualmente cada EGX.


Accin

Resultado

1. En el men Configuracin, haga clic en


Preferencias.

Abre la pgina Preferencias.

2. Introduzca el nombre del equipo, la pgina Establece las preferencias.


de inicio predeterminada, la velocidad de
muestreo en tiempo real y de velocidad de
comprobacin de las comunicaciones.
3. Haga clic en Aplicar.

Figura 26:

Actualiza la configuracin de Preferencias de


la EGX.

Pgina Preferencias

Tabla 13: Valores de las preferencias


Opcin

32

Descripcin

Valor

Nombre del equipo

Le permite introducir un nombre


Predeterminado:
personalizado para la EGX y para el equipo Powerlogic EGX300
asociado. Este nombre se utilizar en el
encabezado de la interfaz web.

Pgina de inicio
predeterminada

Le permite seleccionar la pgina de inicio


predeterminada.

Inicio,
Resumen de circuito,
Resumen de intensidad
de carga,
Resumen de la demanda
de intensidad, Resumen
de potencia o Resumen
de energa.
Predeterminado: Inicio

Velocidad de muestreo Controla la frecuencia con la que se leen


en tiempo real
los datos procedentes de los dispositivos
de las vistas estndar de Tabla de
supervisin.

5 a 60 segundos
Predeterminado:
5 segundos

Velocidad de
comprobacin de las
comunicaciones

Desactivado, 5 a
30 minutos
Predeterminado:
15 minutos

Controla la frecuencia con la que se realiza


la comprobacin de las comunicaciones
mientras el navegador est mostrando
lecturas en tiempo real en las vistas
estndar de Tabla de supervisin. Esta
funcin intentar poner de nuevo en
servicio automticamente cualquier
dispositivo que se encuentre fuera de
servicio.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Tipos de dispositivos visualizables

La pgina Tipos de dispositivos visualizables proporciona una manera de


gestionar los tipos de dispositivos disponibles para que el usuario pueda
seleccionarlos en la pgina web de configuracin de la lista de dispositivos.
Dado que la EGX300 admite muchos tipos diferentes de dispositivos,
retirarlos de la lista de tipos de dispositivos disponibles quizs simplifique el
ajuste de la pgina web de configuracin de la lista de dispositivos.
Accin

Resultado

1. En el men Configuracin, haga clic en Tipos de dispositivos Abre la pgina Tipos de


visualizables.
dispositivos visualizables.
2. Seleccione los tipos de dispositivos que estarn disponibles
para la configuracin de la lista de dispositivos.
NOTA: Haga clic en seleccionar todo para habilitar todos los
dispositivos y en borrar para deshabilitar todos ellos.

Selecciona los tipos de


dispositivos que estarn
disponibles para
configurar la lista de
dispositivos.

NOTA: Es posible que no se pueda cambiar la disponibilidad


del tipo de dispositivo de aquellos dispositivos que ya se estn
utilizando.
3. Haga clic en Aplicar.

Figura 27:

Historial de auditora

Guarda los valores de


Tipos de dispositivos
visualizables.

Pgina Tipos de dispositivos visualizables

El historial de auditora consiste en una secuencia de registros o mensajes


con una marca horaria. Graba los eventos de cambio de configuracin,
error o fallo de autenticacin; tambin identifica al usuario que
desencaden el evento.
La pgina Historial de auditora permite configurar los cuatro grupos de
informes y canales de mensajes. Por cada canal, elija los grupos de informes
cuyos mensajes desee ver. Cuando asigne un grupo de informes a un canal,
ver todos los mensajes que se generen en ese grupo de informes.
Los canales de mensajes son los siguientes:

Archivo de registro de mantenimiento incorporado de la EGX

Correo electrnico

Servidor Syslog remoto (Syslog es un estndar para el registro de


mensajes)

Todos los mensajes llevan una marca de fecha y hora e incluyen


informacin de grupo de informes y de identificacin del usuario.
2009-2013 Schneider Electric. Reservados todos los derechos.

33

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

La pgina Historial de auditora se divide en tres cuadros que corresponden


a los tres canales de mensajes: Registro de mantenimiento, Syslog y Correo
electrnico. (Consulte la Figura 28 de la pgina 35.) Es posible configurar de
manera independiente los mensajes que se envan a cada canal.
En la ventana Configuracin, haga clic en Historial de auditora. Se abre la
pgina Historial de auditora. Siga las instrucciones de la tabla siguiente.
Tabla 14: Configuracin de Historial de auditora
Opcin

Descripcin

Valor

Registro de mantenimiento
Controla los tipos de
informes cuyos mensajes
desea que se visualicen en
el registro de mensajes.

A medida que se generen los


mensajes, estos aparecern en
el registro de mantenimiento
incorporado de la EGX.

Marque las opciones de informe


que desee incluir.
Predeterminado: No hay
ninguna opcin marcada

A medida que se generen los


mensajes, estos se reenviarn al
servidor que indique.
Los mensajes de Syslog se
enviarn desde este puerto UDP
del servidor.

Introduzca la direccin IP del


servidor remoto al que quiere
reenviar los mensajes.
Introduzca el nmero de
puerto UDP correspondiente a
esta direccin IP.
Predeterminado = 514.
Marque los tipos de informes
cuyos mensajes desee reenviar.
Elija la categora adecuada.

Syslog
Direccin IP del servidor
Puerto UDP del servidor
(protocolo de datagramas
de usuario)
Informe
Lista desplegable
Instalacin
Lista desplegable
Gravedad

Cuatro tipos de informes cuyos


mensajes se pueden reenviar.
Proporciona una idea
aproximada de la ubicacin del
sistema donde se gener el
mensaje. Aparece en Syslog.
Le indica al usuario la importancia Elija la categora adecuada.
relativa del mensaje. Debe
determinar, para su instalacin, la
importancia de cada tipo.

Correo electrnico
Desde direccin

A direcciones

Cuando se generan mensajes, la


direccin de correo electrnico
del emisor aparece en el campo
del remitente.
El cuerpo del correo electrnico
incluir la direccin IP de la EGX,
el nombre del grupo de informes,
el nombre de usuario, la
direccin IP del usuario y el
mensaje del grupo de informes.
Cuando se generan los
mensajes, se envan a las
direcciones de correo electrnico
de los destinatarios.

Introduzca la direccin del


remitente (emisor) para los
correos electrnicos. Mximo
de 49 caracteres.

Introduzca las direcciones de los


destinatarios (destinatario de
todos los correos electrnicos de
mensaje). Mximo de
49 caracteres por direccin.
Direccin IP del servidor
Esta es la direccin IP del
Si no introduce una direccin IP
servidor al que se enviarn los
de un servidor, no se enviar
correos electrnicos.
ningn correo electrnico.
Puerto TCP del servidor
Este es el nmero del
Introduzca el nmero del
puerto TCP de la direccin IP del puerto TCP. El valor
servidor.
predeterminado es 25.
El servidor SMTP requiere Esta casilla de verificacin sirve Marque la casilla para empezar
iniciar sesin
para activar el inicio de sesin a a aadir datos de inicio de
fin de recibir correos electrnicos. sesin.
El servidor SMTP requiere que
se inicie una sesin.
Nombre de usuario
Nombre de usuario que utilizar Escriba el nombre de usuario
la EGX para iniciar sesin en el que requiera el servidor SMTP
servidor SMTP.
(mx. 31 caracteres).
Contrasea
Clave que utilizar la EGX para Escriba la contrasea que
iniciar sesin en el
requiera el servidor SMTP
servidor SMTP.
(mx. 31 caracteres).
Informe
Se trata de los cuatro tipos de
Marque los tipos de informe
informes cuyos mensajes se
cuyos mensajes desee reenviar.
pueden reenviar. Se pueden
marcar todos los que desee.
Predeterminados/Aplicar
Haga clic en Aplicar para guardar Haga clic en Aplicar o
las entradas que haya
Predeterminados.
completado. Haga clic en
Predeterminados para devolver
cada campo a su estado
predeterminado.

34

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Figura 28:

Punto de acceso del sistema

Configuracin de Historial de auditora

El punto de acceso del sistema proporciona un medio de detectar otros


dispositivos Schneider Electric conectados a la red y vincularse a estos.
Esta funcin est configurada para su ejecucin de manera predeterminada,
por lo que no es necesario configurar ningn parmetro adicional.
Esta pantalla de configuracin le permitir introducir la direccin IP del
grupo y su informacin asociada.

Accin

Resultado

1. En el men Configuracin, haga clic Abre la ventana Punto de acceso del sistema.
en Punto de acceso del sistema.
2. Activado

Cuando se marca esta casilla, las EGX300 con la


misma direccin IP del grupo podrn detectarse entre
s. Predeterminado = Activado.

3. Puerto UDP

Escriba el nmero de puerto (de 1 a 65535)


correspondiente al puerto UDP que utiliza la deteccin
de la funcin Punto de acceso del sistema.
Predeterminado = 59.

4. Direccin IP del grupo

Escriba la direccin IP del grupo, que admitir


direcciones de unidifusin o multidifusin.
Predeterminado = 224.0.1.2.

5. Intervalo de introduccin

Periodo de tiempo transcurrido entre mensajes de


bienvenida emitidos por esta EGX300 con que se
anuncia su presencia a otros dispositivos de punto de
acceso del sistema de Schneider Electric que se
encuentren en red. De 1 a 65535 segundos.
Predeterminado = 300 segundos.

2009-2013 Schneider Electric. Reservados todos los derechos.

35

Pasarela Ethernet EGX300 de PowerLogicTM


Configuracin

63230-319-216B3_ES
03/2013

Accin

Resultado

6. Tiempo de espera

Periodo de tiempo durante el cual los mensajes de


bienvenida que emite esta EGX300 deberan ser
retenidos por los destinatarios antes de considerar
que esta no est disponible.
De 2 a 65535 segundos.
Predeterminado = 600 segundos.

7. Perodo de vida de multidifusin

Es posible controlar la amplitud del rea de la red para


detectar otros dispositivos. Se controla mediante el
nmero de veces que se permite el reenvo de la
multidifusin a otros. El intervalo de saltos de router
permitidos es de 1 a 255. Predeterminado = 1.

8. Comunidad

Las EGX300 de un grupo pueden dividirse en


comunidades. Aquellas pasarelas que tengan la
misma direccin IP del grupo y el mismo nmero de
comunidad podrn detectarse entre s.
Si se configura el nmero de comunidad como 0,
ello permitir que una EGX300 detecte todas
las EGX300 con la misma direccin IP de grupo
independientemente del valor del parmetro de
comunidad. Predeterminado = 0.

9. Predeterminados/Aplicar

Figura 29:

36

Haga clic en Aplicar para guardar las entradas; haga


clic en Predeterminados para volver a los valores
predeterminados que se enumeran.

Pgina de configuracin Punto de acceso del sistema

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

63230-319-216B3_ES
03/2013

SUPERVISIN

La EGX proporciona pantallas en las que muestra datos y tendencias en


tiempo real, adems de tendencias histricas de registros de datos.

Datos en tiempo real

Las pginas Datos en tiempo real proporcionan lecturas bsicas de


dispositivos seleccionados en tiempo real as como resmenes de
dispositivos.

Pginas de dispositivo nico

Para ver una tabla de datos en tiempo real, vaya al men Supervisin y
seleccione un dispositivo bajo Datos en tiempo real > Pginas de
dispositivo nico.

Configuracin de lecturas bsicas


Accin

Resultado

1. En la parte superior de la pantalla, seleccione


Selecciona las cantidades que se
Intensidad, Potencia, Tensin L-L o Tensin L-N mostrarn en la pantalla grfica de
para que aparezcan en la pantalla grfica de
indicadores analgicos.
indicadores analgicos.
NOTA: Los indicadores
analgicos no estn disponibles
en todos los tipos de dispositivos.
2. De manera predeterminada, los indicadores
ajustarn automticamente el rango de
visualizacin. Si desea un rango fijo, seleccione
Rango. Las instrucciones para configurar el rango
de los indicadores analgicos se encuentran en la
tabla siguiente.

Controla el rango de visualizacin de


los indicadores analgicos.

3. Haga clic en Aplicar.

Actualiza la seleccin de rango en la


pgina del dispositivo.

Figura 30:

2009-2013 Schneider Electric. Reservados todos los derechos.

Pgina Lecturas bsicas

37

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

Rango de los indicadores analgicos

63230-319-216B3_ES
03/2013

Es posible configurar el rango de los indicadores grficos analgicos de la


pgina Lecturas bsicas, o bien establecer que se ajuste automticamente
(Figura 31).
Accin

Resultado

1. En Activar escala automtica, marque los dispositivos en los que Habilita la escala
desea que la escala de los indicadores se ajuste automticamente. automtica en los
dispositivos
NOTA: Haga clic en seleccionar todo para habilitar la escala
seleccionados.
automtica en todos los dispositivos y en borrar para deshabilitarla
en todos ellos.
2. En los dispositivos en los que se haya deshabilitado la escala
automtica, introduzca los lmites Mn. y Mx. de cada tipo de
indicador.

Establece el rango de
los indicadores.

3. Haga clic en Aplicar.

Actualiza los valores


de escala automtica.

Figura 31:

Pginas de resumen de dispositivos

Pgina de configuracin de rangos

Las vistas de tablas Resumen de dispositivos proporcionan resmenes de


uno o ms dispositivos seleccionados.
Accin

Resultado

1. En el men de Supervisin, haga clic en Pginas


de resumen de dispositivos.

Ampla el rbol para posibilidades de


seleccin de pginas de resumen.

2. Seleccione la pgina de resumen que desee ver.

Abre la lista de seleccin de


dispositivos.

3. Seleccione uno o varios dispositivos en la lista


Dispositivos disponibles y luego haga clic en
Siguiente (consulte la Figura 32).

Selecciona uno o varios dispositivos


para las opciones de resumen.

NOTA: Haga clic en >> para seleccionar todos los


dispositivos disponibles.

38

Figura 32:

Pgina Seleccin de dispositivo

Figura 33:

Pgina Resumen de circuito

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

63230-319-216B3_ES
03/2013

Tendencias

Para visualizar una tendencia en tiempo real de varios dispositivos y temas,


vaya al men Supervisin y seleccione Datos en tiempo real > Tendencias.
Accin

Resultado

1. En el men Supervisin, seleccione Datos en tiempo


real.

Ampla el rbol de datos para


seleccionar opciones de datos
en tiempo real.

2. Seleccione Tendencias.

Ampla el rbol de datos para


seleccionar opciones de tiempo
real correspondientes a las
tendencias.

3. Seleccione Tendencias en tiempo real.

Abre la pgina de configuracin


Tendencias en tiempo real.

4. Seleccione hasta cuatro dispositivos de la lista


Dispositivos disponibles.

Selecciona los dispositivos


cuyas tendencias se mostrarn.

5. Seleccione uno o varios temas en la lista Temas


disponibles.

Selecciona los temas cuyas


tendencias se mostrarn.

NOTA: Solamente estarn disponibles para el clculo de


tendencias aquellos temas comunes a todos los
dispositivos seleccionados. El nmero mximo de temas
cuyas tendencias se calcularn depende del nmero de
dispositivos seleccionados. El producto de los
dispositivos y los temas seleccionados no podr ser
mayor de 8.
6. Haga clic en Siguiente para abrir la pgina de
visualizacin Tendencias en tiempo real.

Abre la pagina de visualizacin


Tendencias en tiempo real.

7. Para establecer los parmetros relativos a las


Permite configurar los
tendencias, contine con el procedimiento descrito en la parmetros de las tendencias.
tabla que figura a continuacin y consulte la Figura 35 de
la pgina 40.

Figura 34:

2009-2013 Schneider Electric. Reservados todos los derechos.

Seleccionar dispositivos y temas

39

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

63230-319-216B3_ES
03/2013

Accin
1. Seleccione la tendencia Absoluto o Relativo.

Resultado
Selecciona el modo de grfico.

NOTA: Absoluto redibuja el eje X del grfico despus de


cada muestreo y lo rellena con todos los datos recopilados
desde el inicio de la tendencia. Relativo actualiza el
grfico con los datos ms recientes despus de cada
muestreo y mantiene el eje X constante para mostrar el
tiempo general de la tendencia seleccionado.
2. Seleccione un tiempo de tendencia comprendido entre 1
y 15 minutos. Esta ser la duracin de la tendencia.

Selecciona la duracin de la
tendencia.

NOTA: Los muestreos de datos se toman lo ms rpido


posible, pero el proceso puede requerir ms tiempo
dependiendo de la carga de comunicaciones en la subred
serie, en los dispositivos remotos o en ambos.
3. Seleccione Iniciar muestreo para iniciar la generacin de Inicia la generacin de
tendencias de los temas de los dispositivos
tendencias.
seleccionados.
NOTA: Para detener la generacin de tendencias antes
de que transcurra el tiempo de tendencia, haga clic en
Detener muestreo. Si pulsa Iniciar muestreo despus
de detener el muestreo, se iniciar una nueva tendencia.
4. Pulse Puntos de datos para visualizar un registro de
todos los temas muestreados que quedaron registrados
durante el tiempo de tendencia.
NOTA: Despus de cada intervalo, se aaden a la tabla
que aparece bajo el grfico el valor Actual de todos los
temas as como los valores Mn., Mx. y Media
calculados.
5. Pulse Tema(s) nuevo(s) para volver a seleccionar los
dispositivos y los temas cuyas tendencias se deben
generar.

Figura 35:

Registro de dispositivos

40

Muestra un registro de todos


los valores de los temas
muestreados durante la
tendencia.

Le lleva de nuevo a la pgina


de configuracin Tendencias
en tiempo real.

Tendencias en tiempo real

Las pginas de Registro de dispositivos proporcionan representaciones en


forma de grficos y tablas de los datos de registro de los dispositivos
seleccionados. Para obtener ms detalles acerca de la configuracin del
registro de dispositivos, consulte Registro de dispositivos en la pgina 17.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

63230-319-216B3_ES
03/2013

Pginas de dispositivo nico

Las pginas de dispositivo nico proporcionan representaciones en forma


de grficos y tablas de los datos registrados de un nico dispositivo.
Accin

Resultado

1. En el men Supervisin, haga clic en


Registro de dispositivos.

Ampla el rbol para mostrar las opciones


disponibles de registro de dispositivos.

2. En Registro de dispositivos, haga clic en


Pginas de dispositivo nico.

Ampla el rbol para mostrar los dispositivos


disponibles cuyos datos registrados se pueden
visualizar.

3. Seleccione un dispositivo de la lista


Registro de dispositivos.

Muestra el registro de dispositivo


correspondiente al dispositivo seleccionado.

4. Para ver un rango de datos, seleccinelo Elabora un grfico correspondiente al rango de


en la lista desplegable de rangos de datos. datos seleccionado.
5. Mantenga pulsado el botn izquierdo del
ratn y arrastre un cuadro de seleccin
alrededor de una zona del grfico para
ampliarla.

Aumenta la zona del grfico seleccionada.

6. Para volver a la vista completa original,


escriba Z en el teclado o haga doble clic
sobre el grfico.

Se reduce el zoom de la vista.

7. Haga clic en Puntos de datos para


visualizar la tabla del registro de datos del
intervalo seleccionado (consulte ms
adelante la Figura 37).

Abre la tabla del registro de datos del


intervalo seleccionado.

8. Para visualizar otros temas, haga clic en


Habilita la visualizacin de los temas
Tema(s) nuevo(s). Habilite las casillas de seleccionados.
verificacin de los temas que desea
visualizar y, a continuacin, haga clic en
Aplicar.

Los datos registrados de cada dispositivo aparecen en una pgina web en


un formato de grfico de tendencia del tiempo. El grfico de tendencia del
tiempo est preconfigurado para mostrar los datos del ltimo da completo,
la ltima semana completa, el ltimo mes completo o todos los datos.
Los parmetros de la energa se registran como valores acumulativos pero
se visualizan como valores incrementales por intervalo. Los otros
parmetros se registran y visualizan como el valor real registrado.
Figura 36:

Grfico Registro de datos del intervalo

Figura 37:

Tabla de puntos de datos del registro de datos del


intervalo

2009-2013 Schneider Electric. Reservados todos los derechos.

41

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

Obtencin de registros cronolgicos de datos

63230-319-216B3_ES
03/2013

Se pueden recuperar registros de datos de intervalo utilizando los mtodos


descritos en la Tabla 15.
Tabla 15: Mtodos de recuperacin de registros de datos de intervalo
y formatos de archivo
Mtodo de recuperacin

Formato de archivo recuperado

FTP

Variable separada por coma (CSV)

Botn Puntos de datos

HTML

Consulta Web de Microsoft

HTML

Correo electrnico

CSV

HTTP

CSV

Para ver una lista de todos los archivos de registros disponibles, siga los
pasos 2 a 4 de la seccin Obtencin de un registro de datos de intervalo
mediante FTP en la pgina 43. Los archivos tendrn el siguiente formato:
Nombre del dispositivo_ID local.csv, donde Nombre del dispositivo es el
nombre dado al dispositivo esclavo, e ID local es el identificador local
numrico asignado a este. Por ejemplo, un dispositivo llamado Entrada de
servicios del edificio 1 con un identificador local de 3 sera Entrada de
servicios del edificio 1_3.csv.
Cuando se exportan archivos de registros, la fecha y la hora se aaden al
nombre del archivo en el formato siguiente: _AAAAMMDDHHMMSS. Por
ejemplo, Entrada de servicios del edificio 1_3_20100218115216.csv. Esto
indica que el archivo se export el 18 de febrero de 2010 a las 11:52:16 a. m.
Formato de registro

Los datos se registran en el siguiente formato (consulte la Figura 38 de la


pgina 43):
Tabla 16: Formato de registro de datos de intervalo
Fila

Datos en formato CSV

Descripcin

Esta fila contiene los encabezamientos


(BOM)Nombre de pasarela,N. de serie de
de las columnas para la informacin de la
pasarela,Direccin de pasarela,Nombre del
dispositivo,ID local de dispositivo,Nombre del fila 2.
tipo de dispositivo,Intervalo de registro
NOTA: (BOM): Los tres primeros bytes del
archivo constituyen una marca de orden de
bytes (BOM, Byte Order Mark) de
3 caracteres, lo cual indica UTF-8.

EGX300SD,23227,157.198.184.116,Entrada
de servicios del edificio 1,3,CM4000,15

Esta fila est en blanco.

,,,ID del tema 1,ID del tema 2,ID del tema 3

Esta fila contiene los encabezamientos de


las columnas de los ID de los temas de la
fila 5. Un ID de tema es una referencia
numrica de la cantidad que se est
registrando. El nombre dado a una
cantidad puede diferir ligeramente entre
dispositivos e idiomas. Los ID de temas
se utilizan para identificar la cantidad
independientemente del dispositivo y del
idioma. Las tres primeras comas se
utilizan con fines de disposicin en una
aplicacin de hoja de clculo.

,,,1617,1621,1625

Esta fila contiene los ID de temas de los


valores registrados.

Esta fila est en blanco.

Error,Desviacin de la UTC (Minutos),Indica- Esta fila contiene los encabezamientos


dor de hora local,Energa aparente (kVAh),
de las columnas para los datos
Energa real (kWh),Energa reactiva (kVARh) registrados en las filas 8 y superiores.

Esta fila contiene la informacin acerca


de la EGX y el dispositivo registrado.

8y
Estas filas contienen los datos registrados.
superiores 0,-300,2008-10-09 14:15:00,1400738.219,1201962.707,647069.906,15
0,-300,2008-10-09 14:20:00,1400758.260,1201980.725,647078.602,15
0,-300,2008-10-09 14:25:00,1400778.198,1201998.661,647087.233,15

Si utiliza una aplicacin de hoja de clculo para ver el archivo CSV, sus
datos tendrn un aspecto similar al de la Figura 38 de la pgina 43.
42

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

63230-319-216B3_ES
03/2013

Figura 38:

Cdigos de error para los registros


cronolgicos de datos

Registro de datos de intervalo abierto en una aplicacin


de hoja de clculo

Al resolver problemas en los registros cronolgicos de datos, nos


encontraremos con los cdigos de error que aparecen a continuacin
(consulte la Figura 36 de la pgina 41 y la Figura 37 de la pgina 41):
Cdigo
de error

Definicin

Resultado

19

Ha ocurrido un error de comunicaciones (por


ejemplo: CRC, protocolo o excepcin).

25

El tiempo de espera se produjo cuando se envi una Se deja habilitado el registro a


solicitud sin recibir la respuesta correspondiente
menos que se haya perdido el
durante el tiempo permitido.
ltimo intervalo.

38

Datos no vlidos.

100

Intervalo de tiempo transcurrido antes de que se


pudieran registrar los datos

Se deja habilitado el registro a


menos que se haya perdido el
ltimo intervalo.

Intervalo perdido.

Pngase en contacto con el soporte tcnico si necesita ayuda para resolver


estas u otras condiciones de error.

Obtencin de un registro de datos de


intervalo mediante FTP

Puede utilizar FTP para recuperar un archivo de registro de datos


conectndose a la EGX a travs de FTP y transfiriendo el archivo .csv,
como se indica en los pasos siguientes.
NOTA: Si desea que la EGX enve automticamente el archivo de registro de
datos a travs de FTP, el parmetro Exportacin del registro de dispositivos
tiene que configurarse para FTP (consulte Exportacin por FTP en la
pgina 21).
Accin

Resultado

1. Cree una carpeta en su equipo, como


c:egx_logs.

Crea una carpeta para almacenar el registro de


datos de la EGX.

2. Inicie el Explorador de Windows, escriba


ftp:// y la direccin IP de la EGX en el
cuadro Direccin (por ejemplo,
ftp://169.254.0.10), y luego pulse Intro.

Abre el cuadro de dilogo Iniciar sesin


como.

3. Escriba el nombre de usuario


Administrator y la contrasea de
administrador en los cuadros de texto, y
luego haga clic en Iniciar sesin.

Inicia una sesin de FTP con la EGX y muestra


los archivos almacenados en la EGX.

4. Vaya al directorio /logging/data en


la EGX.

Abre el directorio de registro de datos en


la EGX.

5. Copie el archivo de registros y luego


Copia el registro de datos en la carpeta.
pguelo en la carpeta creada en el paso 1.

2009-2013 Schneider Electric. Reservados todos los derechos.

43

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

Obtencin de un registro de datos de


intervalo mediante el botn Puntos de datos

Obtencin de un registro de datos de


intervalo mediante la funcin de consulta
Web de Microsoft

63230-319-216B3_ES
03/2013

Accin

Resultado

1. En la pgina web Registro de dispositivos


(consulte la Figura 36 de la pgina 41),
haga clic en Puntos de datos.

Abre una nueva ventana en la que se muestran


los datos registrados.

2. Pulse CTRL+A y luego pulse CTRL+C.

Selecciona todos los datos y luego copia los


datos en el portapapeles.

3. Inicie Excel y luego pulse CTRL+V.

Pega los datos en una hoja de clculo de


Excel.

Accin
1. Inicie el explorador web.

Resultado
Abre el explorador web.

2. Verifique que el archivo de registro est


Abre la pgina de registros de datos.
disponible escribiendo la direccin IP de la
EGX300 seguida de
/stream/devlog_data.html?device=x,
donde x es el ID local del dispositivo.
3. Inicie Excel y haga clic en Datos >
Importar datos externos > Nueva
consulta Web.
NOTA: Esta ruta de acceso es tpica de
Microsoft Excel 2003.

Abre el cuadro de dilogo Nueva consulta


Web de Excel.

4. En el cuadro de dilogo Nueva consulta


Web, escriba la direccin del registro
introducido en el paso 2 y luego haga clic
en Ir.

Abre el archivo del registro de datos.

5. Haga clic en la flecha ms exterior para


seleccionar todos los datos y luego haga
clic en Importar.

Selecciona los datos y luego abre el cuadro de


dilogo Importar datos.

6. Haga clic en Aceptar.

Importa los datos.

NOTA: Si desea mostrar los datos ms recientes cada vez que abra la hoja
de clculo, haga clic en Propiedades en el cuadro de dilogo Importar
datos y seleccione Actualizar al abrir archivo.

Obtencin de un registro de datos de


intervalo mediante correo electrnico

La EGX se tiene que configurar para enviar los registros de datos a una
direccin de correo electrnico. Para obtener ms informacin, consulte
Exportacin por correo electrnico en la pgina 19.

Obtencin de un registro de datos de


intervalo mediante HTTP

Es necesario configurar la EGX para que pueda entregar registros


cronolgicos de datos a un servidor web. Para obtener ms informacin,
consulte Exportacin por HTTP en la pgina 22.

44

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

63230-319-216B3_ES
03/2013

Pginas de resumen de dispositivos

Las vistas de Resumen de dispositivos proporcionan resmenes de uno o


ms dispositivos seleccionados.
Accin

Resultado

1. En el men Supervisin, haga clic en Registro de Ampla el rbol para mostrar las
dispositivos.
opciones de registro de dispositivos.
2. En Registro de dispositivos, haga clic en Pginas
de resumen de dispositivos.
3. En Pginas de resumen de dispositivos, haga clic Abre la pgina de configuracin de la
en Varios dispositivos, nico tema.
pgina Varios dispositivos, nico tema.
4. Seleccione un dispositivo de la lista Dispositivos Selecciona los dispositivos para las
disponibles.
opciones de resumen.
NOTA: Se pueden seleccionar cuatro dispositivos
como mximo.
5. Seleccione un tema de la lista Temas
disponibles.

Selecciona el tema que se visualizar


para cada dispositivo seleccionado.

NOTA: Solo estarn disponibles aquellos temas


que sean comunes a los dispositivos
seleccionados.
6. Seleccione Siguiente.

Abre la pgina de tendencias de Varios


dispositivos, nico tema.

7. Mantenga pulsado el botn izquierdo del ratn y


arrastre un cuadro de seleccin alrededor de una
zona del grfico para ampliarla.

Aumenta la zona del grfico


seleccionada.

8. Para volver a la vista completa original, escriba Z


en el teclado o haga doble clic sobre el grfico.

Se reduce el zoom de la vista.

El tema registrado de los dispositivos seleccionados se muestra en una


pgina web en un formato de grfico de tendencia del tiempo. El grfico de
tendencia del tiempo est preconfigurado para mostrar los datos del ltimo
da completo, la ltima semana completa, el ltimo mes completo o todos
los datos.
Los parmetros de la energa se visualizan como valores incrementales por
intervalo. Los otros parmetros se registran y visualizan como el valor real
registrado.

Figura 39:

2009-2013 Schneider Electric. Reservados todos los derechos.

Pgina de configuracin de Varios dispositivos, nico


tema

45

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

63230-319-216B3_ES
03/2013

Figura 40:

Panel de instrumentos

Pgina de tendencias de Varios dispositivos, nico tema

La EGX admite cuatro categoras de paneles de instrumentos que


muestran la informacin de consumo de energa recopilada a lo largo del
tiempo. La Tabla 17 enumera los paneles de instrumentos y sus
subconjuntos.
Tabla 17: Tipos de paneles de instrumentos
Panel de instrumentos
Por horas

Subconjunto
Da anterior por horas
Da actual por horas
Da actual con da anterior por horas

Por das

Semana anterior por das


Semana actual por das
Semana actual con semana anterior por das
Mes anterior por das
Mes actual por das
Mes actual con mes anterior por das

Por semanas

Trimestre anterior por semanas


Trimestre actual por semanas
Trimestre actual con trimestre anterior por semanas
13 semanas anteriores por semanas

Por meses

Ao anterior por meses


Ao actual por meses
Ao actual con ao anterior por meses
NOTA: Requiere que el archivo de datos de cada
dispositivo pueda almacenar dos aos de datos
histricos. Consulte Registro de datos de intervalo en
la pgina 17 para obtener ms informacin.
12 meses anteriores por meses

46

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

63230-319-216B3_ES
03/2013

Visualizacin de un panel de instrumentos


Accin

Resultado

1. En el men Supervisin, haga clic en


Panel de instrumentos.

Muestra el men del panel de instrumentos


(consulte la Figura 41).

2. Seleccione un dispositivo en la lista


desplegable Dispositivo.

Selecciona el dispositivo para mostrar sus


datos.

NOTA: El panel de instrumentos muestra


los datos de un solo dispositivo.
3. Seleccione un tema en la lista desplegable Selecciona los temas que se mostrarn
Nombre tema.
grficamente.
NOTA: Los temas estn limitados a los
temas de consumo incremental
proporcionados por el dispositivo.
4. Seleccione los parmetros de tiempo en la Selecciona el rango de tiempo de los datos
lista desplegable Hora.
registrados correspondientes al tema
seleccionado.
5. Haga clic en Aplicar.

Figura 41:

Abre el panel de instrumentos seleccionado.

Men Panel de instrumentos

Los datos de cada panel de instrumentos se muestran en una pgina web


en formato de grfico de barras. Al desplazar el puntero del ratn sobre una
barra del grfico, se muestra el valor del punto de datos del intervalo
seleccionado (Figura 42).
Figura 42:

Grfico del panel de instrumentos

Figura 43:

Tabla del panel de instrumentos

2009-2013 Schneider Electric. Reservados todos los derechos.

47

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

Obtencin de los datos del panel de


instrumentos mediante el botn Puntos de
datos

63230-319-216B3_ES
03/2013

Los datos de un panel de instrumentos se pueden guardar en una


aplicacin de hoja de datos, tal como se muestra en los pasos que se
indican a continuacin.
Accin

Guardar un enlace a un panel de instrumentos

Resultado

1. En el panel de instrumentos que contiene


los datos deseados, haga clic en Puntos
de datos.

Muestra los puntos de datos del panel de


instrumentos deseado (Figura 43 de la
pgina 47).

2. Pulse CTRL+A y luego pulse CTRL+C.

Selecciona todos los datos y luego los copia en


el portapapeles.

3. Inicie Excel y luego pulse CTRL+V.

Pega los datos en una hoja de clculo de


Excel.

Se puede guardar un enlace a un panel de instrumentos para evitar tener


que hacer selecciones desde el men principal cada vez que se accede a
uno de dichos paneles. La Tabla 18 describe los mtodos para guardar un
enlace a un panel de instrumentos.
Tabla 18: Guardar un enlace a un panel de instrumentos
Opcin

Guardar un panel de instrumentos como


imagen

Descripcin

Valor

Marcador del explorador Permite a los usuarios acceder al


web
panel de instrumentos guardado
desde el equipo donde se cre el
marcador.

Siga las instrucciones para


configurar un marcador en el
explorador web que utilice.

Vnculo de
documentacin

Permite a los usuarios de la EGX


acceder a un panel de instrumentos
guardado desde la pgina
Documentacin.

Para configurar el acceso URL,


consulte Vnculos de
documentacin en la
pgina 27.

Correo electrnico

Permite a los usuarios enviar


la URL de un panel de instrumentos
en el cuerpo de un mensaje de
correo electrnico.

Para que el destinatario del


mensaje pueda ver un panel de
instrumentos, debe tener una
cuenta de usuario de la EGX.
Consulte Cuentas de usuario
en la pgina 28.

Se puede guardar un grfico del panel de instrumentos como imagen


siguiendo los pasos que se indican a continuacin.
Accin

Resultado

1. Siga los pasos indicados en Visualizacin Muestra el grfico del panel de instrumentos.
de un panel de instrumentos en la
pgina 47.
2. Haga clic en Mostrar como imagen en
la esquina superior derecha de la pgina
(Figura 44 de la pgina 49).

Abre una nueva ventana con el panel de


instrumentos mostrado en forma de imagen.

3. Haga clic con el botn derecho del ratn


sobre la imagen y seleccione Guardar
imagen como

Abre el cuadro de dilogo Guardar como.

4. Escriba un nombre para el archivo,


Guarda la imagen.
seleccione una ubicacin en la que
guardar el archivo y haga clic en Guardar.
NOTA: El tipo de archivo predeterminado
es de imagen PNG. Para cambiar el tipo
de archivo, sustituya .png en el campo
del nombre de archivo por la extensin que
desee.

NOTA: Esta funcin no est disponible en Internet Explorer versin 8 y


anteriores.

48

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Supervisin

63230-319-216B3_ES
03/2013

Figura 44:

Punto de acceso del sistema

Guardar una imagen del panel de instrumentos

La EGX es capaz de detectar pasarelas EGX300 y otros dispositivos


Schneider Electric que estn conectados a la red as como de proporcionar
enlaces a estos. Se obtiene as un punto de acceso a un sistema de
dispositivos Schneider Electric en red.
La pgina Punto de acceso del sistema enumera en forma de hipervnculo
todos los dispositivos Schneider Electric detectados. Al desplazar el ratn
por encima de cualquier dispositivo de la lista, se ven datos adicionales de
este a la izquierda de la lista.
Haga clic sobre cualquier dispositivo para ir a su pgina de inicio de sesin.

Figura 45:

2009-2013 Schneider Electric. Reservados todos los derechos.

Pgina Punto de acceso del sistema: visualizacin de


datos de dispositivo

49

Pasarela Ethernet EGX300 de PowerLogicTM


Documentacin

DOCUMENTACIN

63230-319-216B3_ES
03/2013

La pgina Documentacin le permite acceder a informacin que se ha


almacenado como archivos en EGX y como vnculos web URL.
Para obtener informacin sobre la carga de vnculos de documentacin,
consulte Vnculos de documentacin en la pgina 27.
Si desea abrir un vnculo de documentacin, haga clic en el enlace
Documentacin, situado en la parte superior de la pgina, y despus
seleccione el vnculo que le interese.

Figura 46:

CONTROL

Pgina Documentacin

La EGX tiene la propiedad de poder ejecutar manualmente uno o varios


conjuntos de comandos de restablecimiento predefinidos por tipo de
dispositivo.
Accin

Resultado

1. En el men Control, haga clic en


Restablecimientos.

Abre la pgina Restablecimientos.

2. Seleccione un dispositivo de la lista


Restablecimientos que desee ver o
restablecer.

Selecciona un dispositivo y muestra las


opciones de restablecimiento as como la fecha
y hora del ltimo restablecimiento.

3. Seleccione los parmetros del dispositivo


que desee restablecer.

Selecciona la operacin de restablecimiento


que se tiene que realizar en el dispositivo
seleccionado.

4. Haga clic en Restablecer.

Enva un comando (o varios) para los


restablecimientos solicitados al dispositivo
seleccionado y muestra el estado.

Figura 47:

Restablecimientos

NOTA: La fecha y hora mostradas para el parmetro Fecha/Hora son la


fecha y hora actuales en el dispositivo seleccionado. Si se ha seleccionado
este parmetro para restablecerlo, se enviar al dispositivo la fecha y hora
de la EGX.
Se informar de los valores de fecha/hora nicamente si el dispositivo los
admite. Por ejemplo, si el dispositivo no admite el valor de Mn./Mx.
correspondiente a Fecha/hora ltimo restablecimiento, este valor
no aparecer relleno.
50

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Diagnsticos

63230-319-216B3_ES
03/2013

DIAGNSTICOS

Para acceder a los vnculos de la pgina web Diagnsticos, haga clic en


Diagnsticos en la barra de mens de la EGX.

Estadsticas

Esta pgina ilustra las lecturas acumuladas desde la ltima vez que se
activ la EGX. Si se interrumpe la alimentacin a la EGX o si se restablece
el dispositivo debido a un cambio de configuracin u otro evento, todos los
valores acumulativos se ponen a cero.
Accin

Resultado

1. En la pgina Diagnsticos, haga clic en


Estadsticas.

Abre la pgina Estadsticas (consulte ms


adelante la Figura 48).

2. Observe los datos.

Consulte Interpretacin de las estadsticas en


la pgina 52.

3. Haga clic en Restablecer.

Restablece los datos de diagnstico


acumulativos de la EGX a 0.

Figura 48:

2009-2013 Schneider Electric. Reservados todos los derechos.

Pgina Estadsticas

51

Pasarela Ethernet EGX300 de PowerLogicTM


Diagnsticos

63230-319-216B3_ES
03/2013

Interpretacin de las estadsticas


Estadstica

Descripcin

Ethernet
Estado de conexin

Cadena de estado que representa la velocidad y la


configuracin bidireccional que se utiliza para
comunicarse con el dispositivo conectado.

Tramas transmitidas satisfactoriamente

Contador que aumenta cada vez que se enva una


trama correctamente.

Colisiones

Contador que aumenta cada vez que se reenva una


trama debido a deteccin de colisiones.

Colisiones excesivas

Contador que aumenta cada vez que no se puede


enviar una trama porque ha alcanzado el estado de
colisin mxima basado en el algoritmo de retroceso
exponencial binario truncado.

Tramas recibidas satisfactoriamente

Contador que aumenta cada vez que se recibe una


trama correctamente.

Errores de CRC de tramas

Contador que aumenta cada vez que se recibe una


trama que contiene una suma de verificacin/CRC
que no coincide con la calculada.

Errores de alineacin

Contador que aumenta cada vez que se recibe una


trama que contiene un error de suma de
verificacin/CRC y que no termina en un borde de
trama de 8 bits.

Tramas demasiado largas

Contador que aumenta cada vez que se recibe una


trama que excede el tamao mximo definido en las
normas (tramas de ms de 1518 bytes).

Tramas demasiado cortas

Contador que aumenta cada vez que se recibe una


trama que no alcanza el tamao mnimo definido en
las normas (tramas de menos de 64 bytes).

Modbus TCP/IP
Servidor
Tramas enviadas

Contador que aumenta cada vez que se enva una


trama.

Tramas recibidas

Contador que aumenta cada vez que se recibe una


trama.

Errores de protocolo

Contador que aumenta cada vez que se recibe un


mensaje mal formado.

Conexiones activas1

Valor de estado que representa el nmero de


conexiones activas en el momento de actualizacin
de la pgina de diagnsticos. Se admite un mximo
de 64 conexiones. Al hacer clic en Conexiones
activas, se abre una ventana nueva con una lista de
todas las conexiones clientes activas.

Conexiones acumuladas

Contador que aumenta cada vez que se realiza una


conexin a la EGX.

Mximo de conexiones

Valor de estado que representa el nmero mximo de


conexiones que pueden estar activas en un momento
dado.

Mensajes entrantes de lectura

Contador que aumenta cada vez que se recibe un


mensaje de solicitud de lectura.

Mensajes entrantes de escritura

Contador que aumenta cada vez que se recibe un


mensaje de solicitud de escritura.

Mensajes salientes de respuesta

Contador que aumenta cada vez que se enva un


mensaje de respuesta.

Cliente
Tramas enviadas

Contador que aumenta cada vez que se enva una


trama.

Tramas recibidas

Contador que aumenta cada vez que se recibe una


trama.

Errores de protocolo

Contador que aumenta cada vez que se recibe un


mensaje mal formado.

Haga clic en el vnculo para obtener informacin adicional en detalle.

52

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Diagnsticos

63230-319-216B3_ES
03/2013

Estadstica

Descripcin

Tiempos de espera

Contador que aumenta cada vez que se enva un


mensaje de solicitud sin recibir el mensaje de
respuesta correspondiente durante el tiempo
permitido. Los tiempos de espera de respuesta
suelen ser el resultado de errores de configuracin o
un dispositivo que no responde.

Tiempos de espera de conexin

Contador que aumenta cada vez que se pierde la


conexin.

Recibidas excepciones

Contador que aumenta cada vez que se recibe una


excepcin.

Mensajes salientes de lectura

Contador que aumenta cada vez que se enva un


mensaje de solicitud de lectura.

Mensajes salientes de escritura

Contador que aumenta cada vez que se enva un


mensaje de solicitud de escritura.

Mensajes entrantes de respuesta

Contador que aumenta cada vez que se recibe un


mensaje de respuesta.

Detalles1

Tabla detallada que proporcionar estadsticas


remotas y serie por dispositivo.

Puerto serie
Tramas enviadas

Contador que aumenta cada vez que se enva una


trama.

Tramas recibidas

Contador que aumenta cada vez que se recibe una


trama.

Errores de CRC de tramas

Contador que aumenta cada vez que se recibe un


mensaje que contiene una CRC que no coincide con
la calculada. Suele ser el resultado de problemas de
cableado.

Errores de protocolo

Contador que aumenta cada vez que se recibe un


mensaje mal formado.

Tiempos de espera

Contador que aumenta cada vez que se enva un


mensaje de solicitud sin recibir el mensaje de
respuesta correspondiente durante el tiempo
permitido. Los tiempos de espera de respuesta
suelen ser el resultado de errores de configuracin o
un dispositivo que no responde.

Recibidas excepciones

Contador que aumenta cada vez que se recibe una


excepcin.

Mensajes salientes de lectura

Contador que aumenta cada vez que se enva un


mensaje de solicitud de lectura.

Mensajes salientes de escritura

Contador que aumenta cada vez que se enva un


mensaje de solicitud de escritura.

Mensajes entrantes de lectura

Contador que aumenta cada vez que se recibe un


mensaje de solicitud de lectura.

Mensajes entrantes de escritura

Contador que aumenta cada vez que se recibe un


mensaje de solicitud de escritura.

Detalles1

Tabla detallada que proporcionar estadsticas


remotas y serie por dispositivo.

Servidor HTTP
Tramas enviadas

Contador que aumenta cada vez que se enva una


trama.

Tramas recibidas

Contador que aumenta cada vez que se recibe una


trama.

Conexiones activas1

Valor de estado que representa el nmero de


conexiones activas en el momento de actualizacin
de la pgina de diagnsticos. Se admite un mximo
de 20 conexiones. Haga clic en Conexiones activas
para abrir una ventana nueva con una lista de todas
las conexiones clientes activas.

Conexiones acumulativas1

Contador que aumenta cada vez que se realiza una


conexin a la EGX.

Mximo de conexiones

Valor de estado que representa el nmero mximo de


conexiones que pueden estar activas en un momento
dado.

Haga clic en el vnculo para obtener informacin adicional en detalle.

2009-2013 Schneider Electric. Reservados todos los derechos.

53

Pasarela Ethernet EGX300 de PowerLogicTM


Diagnsticos

63230-319-216B3_ES
03/2013

Estadstica

Descripcin

Informacin de pasarela
Versin del firmware

Versin del firmware que est instalada en la EGX.

Tiempo de inactividad del sistema

Porcentaje del 0% al 100% que indica el tiempo


medio de procesador que no se utiliza.

Direccin MAC

Direccin exclusiva del hardware Ethernet de


una EGX.

Nmero de serie

Nmero de serie de la EGX.

Nmero de modelo

Nmero de modelo de la EGX.

Versin del hardware

Versin del hardware de la EGX.

Fecha de fabricacin

Fecha de fabricacin de la EGX.

Cliente HTTP
Envo correcto

Contador que aumenta cada vez que se enva un


archivo correctamente al servidor HTTP.

Error de conexin

Contador que aumenta cada vez que la EGX


no puede conectarse al servidor HTTP.

Error de autenticacin

Contador que aumenta cada vez que el


servidor HTTP no puede autenticar las credenciales
del usuario o contrasea.

Error de envo

Contador que aumenta cada vez que no se puede


transferir un archivo al servidor HTTP.

Error general

Contador que aumenta cada vez que no se puede


transferir un archivo debido a la incapacidad de
la EGX para originar la transaccin.

Cliente FTP
Envo correcto

Contador que aumenta despus de cada


transferencia con xito a un servidor FTP.

Error de conexin

Contador que aumenta cada vez que la EGX


no puede conectarse al servidor FTP.

Error de autenticacin

Contador que aumenta cada vez que al servidor FTP


no puede autenticar las credenciales del usuario o
contrasea.

Error de directorio

Contador que aumenta cada vez que el servidor FTP


no puede localizar el directorio solicitado.

Error de envo

Contador que aumenta cada vez que no se puede


transferir un archivo al servidor FTP.

Error general

Contador que aumenta cada vez que no se puede


transferir un archivo debido a la incapacidad de
la EGX para originar la transaccin.

Cliente SMTP
Envo correcto

Contador que aumenta cada vez que se enva un


correo electrnico con xito al servidor SMTP.

Error de conexin

Contador que aumenta cada vez que la EGX


no puede conectarse al servidor SMTP.

Error de autenticacin

Contador que aumenta cada vez que el


servidor SMTP no puede autenticar las credenciales
del usuario o contrasea.

Error de envo

Contador que aumenta cada vez que no se puede


enviar un correo electrnico al servidor SMTP.

Error general

Contador que aumenta cada vez que no se puede


enviar un correo electrnico debido a la incapacidad
de la EGX para crear el correo electrnico.

Sistema de archivos
Espacio total

La cantidad total de espacio de disco de la EGX en


kilobytes.

Espacio libre

La cantidad total de espacio de disco no utilizado en


el disco de la EGX en kilobytes.

Haga clic en el vnculo para obtener informacin adicional en detalle.

54

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Diagnsticos

63230-319-216B3_ES
03/2013

Lectura de registros de dispositivo

Esta opcin permite a la EGX leer desde sus dispositivos locales o remotos.
Figura 49:

Pgina Lectura de registros de dispositivo

Accin
1. En el men Diagnsticos, haga clic en
Lectura de registros de dispositivo.

Resultado
Abre la pgina Lectura de registros de
dispositivo.

2. Introduzca el ID local del dispositivo (o


Introduce los registros que se deben leer
eljalo en la lista de dispositivos definidos), desde el dispositivo especificado.
la direccin datos de comienzo y el
nmero de registros que se deben leer.
3. Seleccione un tipo de datos.

Selecciona el tipo de datos apropiado.

4. Para modificar la visualizacin de los datos Selecciona el modo de visualizacin de los


de la columna Valor, seleccione Decimal, valores de los datos.
Hexadecimal, Binario o ASCII.
5. Haga clic en Lectura.

Lee los registros del dispositivo segn la


configuracin seleccionada.

Tabla 19: Parmetros de lectura de registros de dispositivo de la EGX


Opcin

Descripcin

Predet.

Nombre del dispositivo

Selecciona un dispositivo que leer de la lista de


dispositivos aadidos previamente. Para leer un
dispositivo no definido en la lista de dispositivos,
introduzca el ID local de este.

ID local

La direccin del dispositivo que se tiene que leer.

Registro de inicio

El primer registro para leer.

Nmero de registros

El nmero de registros para leer (1 a 125).

10

Columna Registro

Muestra una lista con los nmeros de los


registros.

Columna Valor

Muestra una lista de los datos almacenados en


un registro. Los valores recuperados dependen
del dispositivo conectado a la EGX. Consulte la
documentacin correspondiente al dispositivo
conectado para obtener ms informacin acerca
de los valores de los registros almacenados.

Tipo de datos

Seleccione Registros de retencin, Registros de


entrada, Bobinas de salida, Bobinas de entrada o
ID de dispositivo.

Registros de
retencin

Opciones Decimal,
Hexadecimal, Binario
o ASCII

Seleccione una opcin para especificar el modo


de visualizacin de los datos de la columna
Valor.

Decimal

2009-2013 Schneider Electric. Reservados todos los derechos.

1
1000

55

Pasarela Ethernet EGX300 de PowerLogicTM


Diagnsticos

63230-319-216B3_ES
03/2013

Comprobacin de las
comunicaciones
Comprobacin de comunicaciones
automatizada

Cuando se examinan las vistas Datos en tiempo real, la EGX tiene una
comprobacin de comunicaciones automatizada que se ejecuta de forma
predeterminada cada 15 minutos. (Para cambiar la frecuencia, consulte
Preferencias en la pgina 32.) Esta comprobacin verificar el buen
estado de las comunicaciones de todos los dispositivos configurados en
la EGX e intentar restablecer la comunicacin con cualquier dispositivo
marcado como Fuera de servicio dentro de la sesin actual del navegador.

Comprobacin de comunicaciones manual

En ciertos casos, es posible que no quiera esperar el tiempo necesario para


comprobar las comunicaciones de forma automatizada y necesite forzar la
comprobacin en ejecucin manual.
Accin

Abre la pgina Comprobacin de las


comunicaciones.

2. Haga clic en Comprobar estado del


dispositivo.

Ejecuta una comprobacin de las comunicaciones. Los dispositivos en comunicacin


muestran Aprobado en la columna Comunicaciones y En servicio en la columna Estado. Un
dispositivo que no est comunicando mostrar
Error en la columna Comunicaciones y Fuera
de servicio en la columna Estado, si ha fallado
varias veces.

Figura 50:

56

Resultado

1. En la pgina Diagnsticos, haga clic en


Comprobacin de las comunicaciones.

Pgina Comprobacin de las comunicaciones

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Mantenimiento

63230-319-216B3_ES
03/2013

MANTENIMIENTO

El registro de mantenimiento le proporciona una manera de documentar el


mantenimiento realizado en la EGX, los equipos conectados o el sistema
del cual la EGX forma parte. Cada entrada se registra con la fecha y hora
en la que se hizo la entrada y el nombre del usuario que la hizo.
Este registro tambin enumerar automticamente la actividad del sistema,
como las funciones de activacin o desactivacin. No tendr que aadir
entradas para estos elementos.
Por ltimo, este registro enumerar todas las actividades que se
especifican para el registro de mantenimiento en la pgina de configuracin
Historial de auditora (consulte Historial de auditora en la pgina 33).
Accin

Resultado

1. En el men Mantenimiento, haga clic en


Registro de mantenimiento.

Abre la pgina Registro de mantenimiento.

2. Seleccione la casilla de verificacin


Eliminar situada junto a la entrada que
desee eliminar y luego haga clic en
Eliminar entradas.

Elimina la entrada seleccionada.

3. Haga clic en Eliminar registro para borrar Borra el registro de mantenimiento.


todas las entradas del registro de
mantenimiento.
4. Para agregar una nueva entrada de
registro, haga clic en Aadir entrada de
registro y luego introduzca el texto de
mantenimiento en el cuadro de texto
Detalle de entrada (consulte ms
adelante la Figura 52).

Abre la pgina Aadir entrada de registro y


permite al usuario introducir los detalles de
mantenimiento.

Figura 51:

Registro de mantenimiento

Figura 52:

Aadir entrada de registro

FIRMWARE

El firmware de la EGX se puede actualizar utilizando el protocolo de


transferencia de archivos (FTP). Consulte con el sitio
www.schneider-electric.com o con su distribuidor local para obtener la
ltima actualizacin del firmware.

Identificacin de la versin del


firmware

La EGX consta de dos componentes de firmware: el componente binario


ejecutable y el componente de imagen de disco.

2009-2013 Schneider Electric. Reservados todos los derechos.

57

Pasarela Ethernet EGX300 de PowerLogicTM


Firmware

Versin del firmware del componente binario


ejecutable

63230-319-216B3_ES
03/2013

Accin

Resultado

1. Abra el explorador web e inicie una sesin Abre la pgina de inicio de la EGX.
en la EGX.
2. Localice la versin del firmware en la parte Seala la versin del firmware de la EGX.
inferior izquierda de la pgina.
NOTA: Si ha actualizado el firmware
recientemente, pulse F5 para actualizar la
pgina web y actualizar el nmero de
firmware que aparece en ella.
3. Tambin puede seleccionar Diagnsticos Tambin seala la versin del firmware de
> Estadsticas para ver la versin del
la EGX.
firmware en la seccin Informacin de
pasarela.

Versin de imagen de disco


Accin

Resultado

1. Abra el explorador web e inicie una sesin Abre la pgina de inicio de la EGX.
en la EGX.
2. Localice la versin del firmware en la parte Determina la versin del firmware de la imagen
de disco de la EGX.
inferior izquierda de la pgina.
NOTA: Si ha actualizado el firmware
recientemente, pulse F5 para actualizar la
pgina web y actualizar el nmero de
firmware que aparece en ella.
3. Tambin puede seleccionar la EGX
mediante FTP, localizar el archivo
version.txt y hacer doble clic en l para
abrirlo.

Determina la versin del firmware de la imagen


de disco de la EGX.

Obtencin de firmware nuevo


Accin
1. Inicie el explorador web, escriba
www.powerlogic.com en la barra de
direcciones y luego pulse Intro.

Resultado
Abre el sitio web de PowerLogic.

2. Seleccione su pas y luego haga clic en Go Abre el sitio web PowerLogic de su pas.
(Ir).
NOTA: Si ha seleccionado Estados
Unidos, vaya al paso 3. De lo contrario,
siga la navegacin del sitio web especfico
del pas para obtener el firmware de
la EGX.
3. Haga clic en Support > Downloads
(Asistencia > Descargas).

Abre la pgina de descargas.

4. Haga clic en el vnculo EGX300 Firmware Abre la pgina Firmware de la EGX300.


(Firmware de la EGX300).
5. Haga clic en el vnculo del archivo de
firmware (egxxxx.bin, donde xxxx es el
nmero de la versin del firmware), luego
haga clic en Guardar.

Abre el cuadro de dilogo Descarga de


archivos y, a continuacin, el cuadro de dilogo
Guardar como.

6. En el cuadro de dilogo Guardar como,


Guarda el archivo de firmware en el directorio o
seleccione o cree un directorio o carpeta
la carpeta indicados.
local en el que se almacenar el archivo de
firmware y haga clic en Guardar.
7. Haga clic en el vnculo egxxxx.upd (donde Abre el cuadro de dilogo Descarga de
xxxx es el nmero del firmware), luego
archivos y, a continuacin, el cuadro de dilogo
haga clic en Guardar.
Guardar como.
Guarda el archivo de firmware con la extensin
8. En el cuadro de dilogo Guardar como,
.upd en el directorio o la carpeta indicados.
seleccione o cree un directorio o carpeta
local en el que se almacenar el archivo de
firmware y haga clic en Guardar.

58

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Firmware

63230-319-216B3_ES
03/2013

Actualizacin del firmware

No corte la alimentacin elctrica a la EGX mientras se est descargando


firmware. Si se corta la alimentacin elctrica durante el proceso de
programacin, la EGX dejar de funcionar. Estando en curso la
programacin, el indicador LED de estado parpadear rpidamente.
Cuando cesa el parpadeo, la programacin est terminada.
Accin

Resultado

1. Inicie el Explorador de Windows, escriba


ftp:// y la direccin IP de la EGX en el
cuadro Direccin (por ejemplo,
ftp://169.254.0.10), y luego pulse Intro.

Abre el cuadro de dilogo Iniciar sesin


como.

2. Escriba el nombre de usuario


Administrator y la contrasea de
administrador en los cuadros de texto, y
luego haga clic en Iniciar sesin.

Abre una sesin de FTP con la EGX.

3. Localice el directorio o la carpeta del


Copia el archivo de firmware en el
equipo donde se ha guardado el archivo
portapapeles.
de firmware (egxxxxx.bin), haga clic con el
botn derecho en el archivo y, a
continuacin, haga clic en Copiar.
4. Haga clic con el botn derecho en la
ventana del Explorador de Windows y
luego haga clic en Pegar.
NOTA: En vez de copiar y pegar el archivo
del firmware, puede arrastrarlo y soltarlo
en el Explorador de Windows.

Copia el firmware en la EGX y luego se reinicia


la EGX.
NOTA: La luz de alimentacin/estado
parpadear rpidamente mientras se est
transfiriendo y programando el archivo a
la EGX. Una vez terminada la
programacin, se restablecer la EGX.
El tiempo necesario para la programacin
est comprendido entre 1,5 y 2 minutos.

5. Localice el archivo de actualizacin del


disco guardado en su equipo
(egxxxxx.upd), haga clic con el botn
derecho en el nombre del archivo y, a
continuacin, haga clic en Copiar.

Copia el archivo de actualizacin del disco en


el portapapeles.

6. Haga clic con el botn derecho en la


ventana del Explorador de Windows y
luego haga clic en Pegar.

Copia el archivo en la EGX y luego se reinicia


la EGX.

NOTA: En vez de copiar y pegar el archivo


del firmware, puede arrastrarlo y soltarlo
en el Explorador de Windows.
7. Para verificar que se ha actualizado
Verifica la versin actualizada del firmware.
correctamente la versin del firmware, siga
los pasos de Identificacin de la versin
del firmware en la pgina 57.
8. Haga clic en Cerrar en la ventana del
Explorador de Windows.

2009-2013 Schneider Electric. Reservados todos los derechos.

Cierra el Explorador de Windows y termina la


conexin FTP con la EGX.

59

Pasarela Ethernet EGX300 de PowerLogicTM


Apndice A: Protocolos Ethernet compatibles

APNDICE A: PROTOCOLOS
ETHERNET COMPATIBLES

63230-319-216B3_ES
03/2013

La EGX acepta los siguientes protocolos Ethernet:

Modbus TCP/IP: Modbus TCP/IP es una combinacin del protocolo


Modbus, que proporciona comunicacin maestro-esclavo entre
dispositivos, y TCP/IP, que proporciona comunicacin a travs de una
conexin Ethernet. Se utiliza Modbus TCP/IP para intercambiar datos
entre la EGX y otros dispositivos compatibles con Modbus TCP/IP a
travs del puerto TCP 502.

Protocolo de transferencia de hipertexto (HTTP): HTTP es un


protocolo de red que realiza los envos de archivos y datos en Internet.
Proporciona funcionalidad de servidor web a travs del puerto TCP 80.

Protocolo de transferencia de hipertexto seguro (HTTPS): HTTPS


es un protocolo de red que realiza los envos cifrados de archivos y
datos en Internet mediante SSL. Proporciona funcionalidad de servidor
web a travs del puerto TCP 443.

Protocolo de transferencia de archivos (FTP): FTP es un protocolo


de redes que ofrece la capacidad de transferir archivos por Internet de
un ordenador a otro. Se admiten los modos FTP activo y pasivo,
principalmente a travs del puerto TCP 21.

Protocolo simple de administracin de redes (SNMP): SNMP se


basa en el formato MIB2 y proporciona la capacidad de almacenar y
enviar informacin de identificacin y diagnstico utilizada en la red por
razones de administracin por medio del puerto UDP 161.

Protocolo de resolucin de direccin (ARP): ARP se utiliza para


convertir las direcciones IP en direcciones Ethernet. Las solicitudes
de ARP se envan a travs de la EGX para determinar si su direccin es
el duplicado de una direccin IP (consulte Deteccin de direcciones IP
duplicadas en la pgina 8).

Protocolo simple de hora de la red (SNTP): SNTP es un protocolo


que se usa para sincronizar los relojes de los dispositivos en red
utilizando un servidor NTP por medio del puerto UDP 123.

Equipo fsico
Puerto Ethernet RJ45
Alimentacin

LED para
Ethernet y
comunicaciones
en serie

LED de
alimentacin
y estado

Botn de
restablecim.

60

Puerto serie RS485

Interruptores de
puentes para
polaridad, resistencia
de final de lnea y
2 hilos/4 hilos
Puerto serie RS232
(conector RJ45)

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Apndice B: Tipos de dispositivos admitidos

63230-319-216B3_ES
03/2013

APNDICE B: TIPOS DE
DISPOSITIVOS ADMITIDOS

La EGX acepta los siguientes tipos de dispositivos: La presente lista de


dispositivos compatibles es exacta a fecha de publicacin de este
documento. Para obtener actualizaciones, visite el sitio web
www.schneider-electric.com.
Tabla 20: Tipos de dispositivos admitidos por la EGX300
Grupo de dispositivos

Dispositivos

Filtro de harmnicos activos


Interruptores

Accusine
Compact NSX-A
Compact NSX-E
PowerPact - A
PowerPact - E
CM100/200
CM2000
CM3000
CM4000
ION7500
ION7550
ION7600
ION7650
DM6000
DM6300
Modelo 98

Circuit Monitors

Medidores digitales
Controladores digitales de
temperatura
Variadores
Medidores de energa

Dispositivos de supervisin de
aislamiento
Administracin de motores
Multi-Circuit Monitors

Rels de sobrecarga (SSOLR)


Controlador de factor de potencia

2009-2013 Schneider Electric. Reservados todos los derechos.

ATV61
ATV71
Energy Meter
Enercept
E5600
EM1200
EM1210
EM1250
EM1251
EM26-96
EM3550
EM3555
EM6400
EM6433
EM6436
EM6436DUAL
EM6438
EM7230
EM7280
iEM3150
iEM3155
iEM3250
iEM3255
ION8600
Vigilohm IM20
Vigilohm IM20-H
TeSys T
BCPM tipo A
BCPM tipo B
BCPM tipo C
BCM50A
BCM100A
MCM
MotorLogic Plus
MotorLogic Plus II
Varlogic

61

Pasarela Ethernet EGX300 de PowerLogicTM


Apndice B: Tipos de dispositivos admitidos

63230-319-216B3_ES
03/2013

Tabla 20: Tipos de dispositivos admitidos por la EGX300


Grupo de dispositivos

Dispositivos

Centrales de medida

PM9c
PM200
PM300
PM500
PM600
PM700
PM800
PM1000
PM3250
PM5350
PM5500
ION6200 (Standard y Mega)
ION7300
Sepam 2000
Sepam Serie 10
Sepam Serie 20
Sepam Serie 40
Sepam Serie 80
SIM10Z
SIM10M
SIM6BZ
ATS48
MVSS/RVSS
ZED-THL-M

Rels protectores

Mdulos de interfaz inteligentes

Arranques suaves
Sensores de
temperatura/humedad/luz
Unidades de control

Otros

62

Micrologic A
Micrologic E
Micrologic H
Micrologic P
Acti9 SmartLink

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


ndice alfabtico

63230-319-216B3_ES
03/2013

ndice alfabtico
A
acceso a la EGX a travs de una red 2
ARP (protocolo de resolucin
de direcciones) 8

B
botn Puntos de datos
registro de datos de intervalo 44

C
certificado de confianza
nmero de puerto HTTPS 7
cdigos de error
registro cronolgico de datos 43
comprobacin de las comunicaciones 56
automatizada 56
manual 56
conexin de dispositivos 12
conexiones con dispositivos remotos 10
configuracin
de Ethernet
avanzada 6
de Ethernet y TCP/IP 5
de lecturas bsicas 37
de los puertos serie 8
del puerto serie
avanzada 9
EGX 5
lista de dispositivos 13
consulta Web de Microsoft
registro de datos de intervalo 44
control 50
correo electrnico
exportacin del registro
de dispositivos 19
registro de datos de intervalo 44
cuentas de usuario
configuracin 28

F
fecha y hora
configuracin 23
filtrado de Modbus TCP/IP
configuracin 26
firmware
actualizacin 59
actualizacin mediante FTP 57
obtencin de nuevo 58
formato de registro de datos 42
FTP
exportacin del registro
de dispositivos 21
para aadir pginas web 30
para eliminar pginas web 30
para recuperar registros cronolgicos de
datos 43

H
hardware 60
historial de auditora 33
cuadro Syslog 34
registro de mantenimiento 34
HTTP
exportacin
registro de dispositivos 22
nmero de puerto
configuracin 7
recuperacin de registros de datos de
intervalo 44
HTTPS
nmero de puerto
configuracin 7

I
inicio de sesin en la EGX 2
interfaz de usuario
EGX 3
intervalos de registro 17
introduccin 1

datos en tiempo real 37


deteccin de direcciones IP duplicadas 8
deteccin de dispositivos 15
diagnsticos 51
dispositivos Modbus
deteccin 15

lectura de registros de dispositivo 55


lista de dispositivos
EGX 12

paneles de instrumentos 46
parmetros del SNMP
configuracin 25
preferencias
personalizacin de la EGX 32
protocolos Ethernet compatibles 60
punto de acceso del sistema
configuracin 35
enlaces a otras EGX300 49

R
rango de los indicadores analgicos 38
red
acceso a travs de una 2
registro 17, 40
cronolgico de datos
cdigos de error 43
recuperacin 42
recuperacin mediante FTP 43
de datos de intervalo
mediante botn Puntos de datos 44
mediante correo electrnico 44
mediante FTP 43
mediante funcin de consulta Web
de Microsoft 44
mediante HTTP 44
de dispositivos 17, 40
de mantenimiento 57
historial de auditora 34
formato de datos 42
temas 18
registros de dispositivo
lectura 55

S
seguridad de la contrasea
indicacin cromtica 28
sincronizacin horaria de red
configuracin 24
supervisin 37
Syslog
historiales de auditora 34

tendencias 39
tipos de dispositivos admitidos 61
tipos de dispositivos visualizables 33

niveles de acceso a la EGX 26

EGX
inicio de sesin 2
interfaz de usuario 3
lista de dispositivos 12
estadsticas 51
interpretacin 52
exportacin del registro de dispositivos 19
configuracin 19

otros recursos 1

versin del firmware del componente binario


ejecutable 58
versin del firmware del componente de
imagen de archivo 58
vnculos de documentacin
configuracin 27
visualizacin de datos y tendencias en
tiempo real 37

P
pgina de documentacin 50
pginas
de dispositivo nico 37, 41
de resumen de dispositivos 38, 45
web
adicin a/eliminacin de
la interfaz web 31
configuracin 29
personalizadas
configuracin 30

2009-2013 Schneider Electric. Reservados todos los derechos.

63

Pasarela Ethernet EGX300 de PowerLogicTM


ndice alfabtico

64

63230-319-216B3_ES
03/2013

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM


Manual del usuario

PowerLogic es una marca comercial o una marca comercial registrada de Schneider Electric en
Francia, EE. UU. y otros pases. Todas las dems marcas comerciales utilizadas son propiedad
de sus respectivos propietarios.
Este producto se deber instalar, conectar y utilizar de conformidad con las normas y/o los
reglamentos de instalacin vigentes. Debido a la evolucin constante de las normas y del
material, deber solicitar siempre confirmacin previa de las caractersticas y dimensiones.

Schneider Electric
35 rue Joseph Monier
92500 Rueil-Malmaison (Francia)
www.schneider-electric.com

63230-319-216B3_ES 03/2013
Sustituye a 63230-319-216B2_ES 11/2011.
2009-2013 Schneider Electric. Reservados todos los derechos.

Passerelle Ethernet PowerLogicTM EGX300


Manuel dutilisation
63230-319-216B3_FR
03/2013

Informations de scurit
Informations importantes
Lisez attentivement lensemble de ces instructions et examinez le matriel
pour vous familiariser avec lui avant toute installation, utilisation, rparation
ou intervention de maintenance. Les messages spciaux qui suivent
peuvent apparatre dans ce document ou sur lappareillage. Ils vous
avertissent de dangers potentiels ou attirent votre attention sur des
renseignements pouvant claircir ou simplifier une procdure.
Lajout dun de ces symboles une tiquette de scurit Danger ou
Avertissement indique quil existe un danger lectrique qui peut
entraner des blessures si les instructions ne sont pas respectes.
Ceci est le symbole dalerte de scurit. Il sert vous avertir dun danger
potentiel de blessures corporelles. Respectez toutes les consignes de
scurit accompagnant ce symbole pour viter tout risque potentiel de
blessure ou de mort.

DANGER
DANGER indique une situation de danger imminent qui, si elle nest pas
vite, entranera la mort ou des blessures graves.

AVERTISSEMENT
AVERTISSEMENT indique un danger potentiel qui, sil nest pas vit, peut
entraner la mort ou des blessures graves.

ATTENTION
ATTENTION indique un danger potentiel qui, sil nest pas vit, peut
entraner des blessures lgres ou de gravit moyenne.

NOTE
NOTE concerne des questions non lies des blessures corporelles. Le
symbole dalerte de scurit ne doit pas tre utilis avec cette mention.

Veuillez noter
Seul un personnel qualifi doit effectuer linstallation, lutilisation, lentretien
et la maintenance du matriel lectrique. Schneider Electric nassume
aucune responsabilit des consquences ventuelles dcoulant de
lutilisation de cette documentation.
Par personne qualifie, on entend un technicien comptent en matire de
construction, dinstallation et dutilisation des quipements lectriques et
form aux procdures de scurit, donc capable de dtecter et dviter les
risques associs.

Avis
Avis FCC section 15
Cet appareil a subi des essais et a t reconnu conforme aux limites
imposes aux appareils numriques de classe A, selon le paragraphe 15 de
la rglementation FCC (Commission fdrale des communications des
tats-Unis). Ces limites sont conues pour fournir une protection
raisonnable contre les interfrences nuisibles lorsquun appareil est
employ dans un environnement commercial. Cet appareil produit, utilise et
peut mettre de lnergie radiofrquence et, sil nest pas install ou utilis
conformment au mode demploi, il peut provoquer des interfrences
nuisibles aux communications radio. Le fonctionnement de cet appareil
dans une zone rsidentielle est susceptible de provoquer des interfrences
nuisibles, auquel cas lutilisateur devra corriger les interfrences ses
propres frais. La puissance dalimentation de sonnerie (REN, Ringer
Equivalence Number) du modem interne en option de lappareil est de 0,6.
Le raccordement du modem interne de lappareil doit tre effectu avec un
cordon tlphonique conforme la section 68 de la rglementation FCC
(non fourni). Lappareil ne peut pas tre utilis avec un service tlphonique
public payant ou avec un service ligne partage.
Cet appareil numrique appartient la Classe A et est conforme la norme
ICES-003 du Canada.

Passerelle Ethernet PowerLogicTM EGX300


Table des matires

63230-319-216B3_FR
03/2013

Table des matires


Introduction ............................................................................................... 1
Ressources supplmentaires ...................................................................... 1
Accs la passerelle EGX via un rseau ............................................... 2
Connexion la passerelle EGX .................................................................. 2
Prsentation de linterface utilisateur EGX ............................................ 3
Configuration ............................................................................................. 5
Paramtres Ethernet et TCP/IP .................................................................. 5
Paramtres Ethernet avancs ............................................................... 6
Dtection des adresses IP identiques ................................................... 8
Port srie ..................................................................................................... 8
Paramtres avancs du port srie......................................................... 9
Connexions dappareils distants ............................................................... 10
Liste des appareils EGX ............................................................................ 12
Connexion dappareils une passerelle EGX ..................................... 12
Configuration de la liste des appareils................................................. 13
Dtection des appareils ....................................................................... 15
Journaux dappareil ................................................................................... 17
Enregistrement des donnes par intervalle ......................................... 17
Configuration de lintervalle denregistrement ..................................... 17
Grandeurs consigner ........................................................................ 18
Exporter le journal de lappareil ................................................................. 19
Exportation par courrier lectronique .................................................. 19
Exportation par FTP ............................................................................ 21
Exportation par HTTP.......................................................................... 22
Date et heure ............................................................................................ 23
Synchronisation de lheure rseau ...................................................... 24
Paramtres SNMP .................................................................................... 25
Filtrage Modbus TCP/IP ............................................................................ 26
Liens vers la documentation ..................................................................... 27
Comptes utilisateur ................................................................................... 28
Accs aux pages Web .............................................................................. 29
Ajout/Suppression de pages Web personnalises .............................. 30
Ajout de pages Web personnalises par FTP ..................................... 30
Suppression de pages Web personnalises par FTP ......................... 30
Ajout/Suppression de pages Web personnalises laide
de linterface Web................................................................................ 31
Prfrences ............................................................................................... 32
Types dappareil affichables ...................................................................... 33
Piste daudit ............................................................................................... 33
Point daccs systme .............................................................................. 35
Surveillance ............................................................................................. 37
Donnes en temps rel ............................................................................. 37
Pages dappareil unique ...................................................................... 37
Paramtres des mesures de base....................................................... 37
Plage des cadrans analogiques .......................................................... 38
Pages rcapitulatives appareils........................................................... 38
Calcul de tendance.............................................................................. 39

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Table des matires

63230-319-216B3_FR
03/2013

Journaux dappareil ................................................................................... 40


Pages dappareil unique ...................................................................... 41
Obtention dun journal de donnes...................................................... 42
Format des journaux............................................................................ 42
Codes derreur des journaux de donnes ........................................... 43
Obtention dun journal de donnes dintervalle via FTP ...................... 43
Obtention dun journal de donnes dintervalle par le biais
du bouton Accs aux donnes ............................................................ 44
Obtention dun journal de donnes dintervalle par le biais
dune requte Web Microsoft............................................................... 44
Obtention dun journal de donnes dintervalle par courrier
lectronique ......................................................................................... 44
Obtention dun journal de donnes dintervalle par HTTP................... 44
Pages rcapitulatives appareils........................................................... 45
Tableaux de bord ...................................................................................... 46
Affichage dun tableau de bord............................................................ 47
Accs aux donnes de tableau de bord par le biais
du bouton Accs aux donnes ............................................................ 48
Enregistrement dun lien de tableau de bord....................................... 48
Enregistrement dun tableau de bord sous forme dimage .................. 48
Point daccs systme .............................................................................. 49
Documentation ........................................................................................ 50
Commande ............................................................................................... 50
Diagnostics .............................................................................................. 51
Statistiques ................................................................................................ 51
Interprtation des statistiques.............................................................. 52
Lecture de registres dappareils ................................................................ 55
Vrification des communications ............................................................... 56
Vrification automatique des communications .................................... 56
Vrification manuelle des communications ......................................... 56
Maintenance ............................................................................................ 57
Logiciel embarqu (firmware) ................................................................ 57
Recherche de la version du logiciel embarqu ......................................... 57
Version du composant binaire excutable du logiciel embarqu ........ 58
Version de limage disque ................................................................... 58
Obtention du dernier logiciel embarqu .................................................... 58
Mise jour du logiciel embarqu (firmware) ............................................. 59
Annexe A Protocoles Ethernet pris en charge .................................. 60
Matriel ..................................................................................................... 60
Annexe B Types dappareil pris en charge ........................................ 61

ii

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Introduction

63230-319-216B3_FR
03/2013

INTRODUCTION

LEGX300 est un composant Ethernet qui constitue une interface


transparente entre les rseaux Ethernet et les appareils situs sur le
terrain : compteurs, appareils de mesure, relais de protection, automates
programmables, units de contrle, commandes de moteur et autres
appareils qui communiquent au moyen des protocoles Modbus, Jbus ou
PowerLogic.
La passerelle EGX300 utilise le protocole Modbus TCP/IP pour accder aux
informations des appareils sur site via un rseau local (LAN) ou un rseau
tendu (WAN). Cette fonctionnalit permet dutiliser un logiciel de
surveillance qui accde aux informations des appareils et ralise les
fonctions de collecte de donnes, courbes de tendances, gestion
dalarmes/vnements, analyses et autres.
LEGX300 prend en charge la communication des donnes en temps rel
de nombreux types dappareil courants et offre plusieurs fonctionnalits
spcifiques. Les rapports disponibles prsentent par exemple des pages de
rcapitulatifs internes sur lappareil et le circuit, des calculs de tendances en
temps rel ou des journaux de donnes internes.
Figure 1 :

Prsentation de lEGX300
Affichage en temps rel

Affichage des donnes dappareil


laide dun simple navigateur
pas de logiciel spcial

Tendances
en temps rel

Pages Web de lEGX300

Rinitialisation
des commandes

EGX300

Affiche sous forme de pages


Web les informations dautres
passerelles PowerLogic et
dinterfaces Modbus TCP/IP
comme les modules ECC21 et
PM8ECC.

ION6200

Ressources supplmentaires

2009-2013 Schneider Electric. Tous droits rservs.

PM800

Micrologic

Tendances des
journaux de
donnes

EGX100

Sepam

Sur le site www.schneider-electric.com, saisissez EGX300 dans le


champ de recherche. Naviguez jusquaux documents et tlchargements
EGX.

Passerelle Ethernet PowerLogicTM EGX300


Accs la passerelle EGX via un rseau

ACCS LA PASSERELLE
EGX VIA UN RSEAU

63230-319-216B3_FR
03/2013

Aprs avoir configur les paramtres Ethernet de la passerelle EGX (voir le


manuel dinstallation EGX), vous pouvez accder la passerelle EGX sur
un rseau local Ethernet au moyen dun navigateur Web standard.

Connexion la passerelle EGX


Action

Rsultat

1. Lancez le navigateur Web.

Ouvre le navigateur Web.

2. Dans la barre dadresses, tapez ladresse Ouvre la bote de dialogue de connexion.


IP de la passerelle EGX (169.254.0.10 par
dfaut) et appuyez sur Entre.
3. Tapez votre nom dutilisateur
(Administrator par dfaut) et votre mot de
passe (Gateway par dfaut) dans les
zones appropries, puis cliquez sur OK.

Saisit le nom dutilisateur et le mot de passe,


puis ouvre la page daccueil EGX.

REMARQUE : Le nom dutilisateur et le


mot de passe doivent respecter les
majuscules/minuscules.
4. Cliquez sur llment appropri dans la
barre de menus.

Figure 2 :

Ouvre llment de menu slectionn.

Page daccueil EGX

Barre de
menus

Nous vous recommandons de vous dconnecter ds que vous navez plus


besoin daccder la passerelle EGX.
Pour fermer la session EGX, cliquez sur Dconnexion ou fermez le
navigateur.

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Prsentation de linterface utilisateur EGX

63230-319-216B3_FR
03/2013

PRSENTATION DE
LINTERFACE UTILISATEUR EGX

Linterface utilisateur EGX comporte plusieurs pages Web destines la


surveillance et la commande dappareils, ainsi qu la configuration et au
diagnostic de la passerelle EGX. Voir le Tableau 1 pour la description de
chaque page.
Tableau 1 : Pages EGX
Description

Voir
page

Ethernet et TCP/IP

Configure les paramtres des communications Ethernet


et TCP/IP.

Port srie

Configure les paramtres de communication srie.

Connexions dappareils
distants

Configure les connexions dappareils Modbus TCP/IP


distants.

10

Liste des appareils

Configure, identifie ou vrifie les appareils srie locaux


raccords la guirlande. Les appareils distants peuvent
uniquement tre configurs et vrifis.

12

Journaux dappareil

Configure les paramtres denregistrement des journaux


dappareil.

17

Exporter le journal de
lappareil

Configure les options dexportation des journaux


denregistrement.

19

Date et heure1

Permet de dfinir la date et lheure manuellement ou par


le biais de paramtres SNTP.

23

Paramtres SNMP1

Configure le protocole SNMP (Simple Network


Management Protocol).

25

Filtrage Modbus TCP/IP1

Configure les adresses IP qui peuvent accder la


passerelle EGX via le protocole Modbus TCP/IP.

26

Page Web EGX


Configuration

Liens vers la documentation Configure les fichiers et liens de documentation.

27

Comptes utilisateur1

Permet de crer ou modifier les noms de groupe.

28

Accs aux pages Web1

Configure les droits daccs aux pages Web pour


chaque groupe dutilisateurs.

29

Prfrences

Configure les prfrences de la passerelle EGX.

32

Types dappareil affichables Configure les types dappareil compatibles qui peuvent
tre affichs dans la page Liste des appareils EGX.

33

Piste daudit1

Configure la communication des messages systme par


lEGX : via le journal de maintenance, par courrier
lectronique ou via le serveur Syslog distant.

33

Point daccs systme1

Active et configure ladresse IP de groupe pour plusieurs


passerelles EGX300, ce qui leur permet de se dtecter
entre elles et daccder mutuellement aux informations.

35

Donnes en temps rel

Les Pages dappareil unique affichent les mesures de


base provenant dune slection dappareils sous forme
de tableaux. Les Pages rcapitulatives appareils
affichent le rcapitulatif dun ou de plusieurs appareils
slectionns sous forme de tableaux. La page Calcul de
tendance offre une vue en temps rel de grandeurs
communes pour plusieurs appareils, sous forme de
graphiques ou de tableaux.

37

Journaux dappareil

Les Pages dappareil unique fournissent des tendances,


sous forme de graphiques et de tableaux, des valeurs
slectionnes par lutilisateur pour les appareils choisis.
Les Pages rcapitulatives appareils fournissent des
tendances pour plusieurs appareils et une grandeur
commune, sous forme de graphiques.

40

Tableaux de bord

Les tableaux de bord offrent des reprsentations


graphiques et tabulaires des donnes de consommation
dnergie agrges sur la priode considre et pour
tous les appareils o lenregistrement des donnes est
activ.

46

Point daccs systme

La page Point daccs systme affiche les EGX300 et


autres appareils systmes en rseau accessibles depuis
cette EGX300. Chaque ligne comporte un hyperlien vers
la page de connexion EGX300.

49

Surveillance

2009-2013 Schneider Electric. Tous droits rservs.

Uniquement accessible par un administrateur

Passerelle Ethernet PowerLogicTM EGX300


Prsentation de linterface utilisateur EGX

63230-319-216B3_FR
03/2013

Tableau 1 : Pages EGX


Description

Voir
page

Permet daccder la documentation EGX pertinente et


aux liens de documentation utilisateur.

50

Prvoit lexcution des rinitialisations dfinies pour


lappareil et affiche la date et lheure laquelle chaque
opration a t excute.
Les rinitialisations de date et heure napparaissent que
si lappareil offre cette fonction.

50

Statistiques

Affiche les donnes de diagnostic utilises pour


rechercher des problmes sur le rseau. Cette page
contient galement des informations sur votre passerelle
EGX, notamment le numro de srie, la date de
fabrication et ladresse MAC (Media Access Control
contrle daccs au support).

51

Lecture de registres
dappareils

Permet aux utilisateurs de lire les donnes de registres


des appareils connects la passerelle EGX localement
et distance.

55

Vrification des
communications

Effectue une vrification des communications de tous


les appareils configurs sur la passerelle EGX.

56

Affiche la date et lheure de la dernire maintenance


ralise sur lquipement, lutilisateur qui la effectue
ainsi que des dtails concernant lobjet de cette
maintenance.

57

Page Web EGX


Documentation
Documentation
Commande
Rinitialisations

Diagnostics

Maintenance
Journal de maintenance

Uniquement accessible par un administrateur

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

CONFIGURATION

Pour accder aux liens de la page Configuration, cliquez sur Configuration


dans la barre de menus de la passerelle EGX.

Paramtres Ethernet et TCP/IP


Action

Rsultat

1. Dans le menu Configuration, cliquez


sur Ethernet et TCP/IP.

Ouvre la page Ethernet et TCP/IP.

2. Slectionnez le format de trame et le


type de support. Contactez votre
administrateur rseau si vous ne
connaissez pas ces informations.

Slectionne le format de trame et le type de support.

3. Entrez ladresse IP, le masque de


sous-rseau et ladresse de
passerelle attribus la passerelle
EGX par votre administrateur rseau.

Configure les paramtres Ethernet de la passerelle


EGX.
REMARQUE : Si vous saisissez une adresse IP
dj utilise par un autre appareil, le systme vous
demande den saisir une autre. Voir Dtection des
adresses IP identiques , page 8.

4. Cliquez sur Appliquer.

Met jour les paramtres Ethernet et TCP/IP de la


passerelle EGX.

* Voir le Tableau 2 ci-dessous pour la liste des options.

Figure 3 :

Page Ethernet et TCP/IP

Tableau 2 : Paramtres Ethernet et TCP/IP de la passerelle EGX


Option

Description

Valeur

Format de trame

Slection du format des donnes


envoyes travers une connexion
Ethernet.

Ethernet II, 802.3 SNAP


Par dfaut : Ethernet II

Type de support

Dfinition de la connexion Ethernet


physique ou du type de support.

Obtenir une
adresse IP
automatiquement

Obtention automatique dune adresse IP Option active ou dsactive


partir dun serveur BootP.
Par dfaut : Dsactiv
REMARQUE : Impose la prise en charge
de ladministration rseau.

Adresse IP

Saisie de ladresse IP statique de la


passerelle EGX.

Masque de sousrseau

Saisie de ladresse IP Ethernet du masque Par dfaut : 255.255.0.0


de sous-rseau.

Passerelle par
dfaut

Saisie de ladresse IP de la passerelle


(routeur) utilise pour les communications
sur rseau tendu.

10T/100Tx Auto
10BaseT-HD
10BaseT-FD
100BaseTx-HD
100BaseTx-FD

Par dfaut : 10T/100Tx Auto

2009-2013 Schneider Electric. Tous droits rservs.

Par dfaut : 169.254.0.10

Par dfaut : 0.0.0.0

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Paramtres Ethernet avancs

NOTE
MAUVAISES PERFORMANCES DU RSEAU
Les paramtres Ethernet avancs de la passerelle EGX ne doivent tre
modifis que par des techniciens qualifis qui ont lu et assimil la
documentation relative ces paramtres.
Le non-respect de ces instructions pourrait entraner une baisse des
performances du rseau.

Action

Rsultat

1. Cliquez sur Avanc la page Ethernet et Ouvre la page des paramtres Ethernet
TCP/IP.
avancs.
2. Configurez les paramtres Ethernet
Dfinit les paramtres Ethernet avancs.
avancs (voir le Tableau 3, page 7 pour les
options disponibles). Cliquez sur Valeurs
par dfaut pour slectionner les valeurs
par dfaut pour toutes les options.
3. Cliquez sur Appliquer.
REMARQUE : La modification des
donnes de la page Paramtres Ethernet
avancs ne valide aucune des
modifications apportes la page Ethernet
et TCP/IP.
4. Cliquez sur OK pour valider les
modifications et rinitialiser la passerelle
EGX.

Figure 4 :

Met jour les paramtres Ethernet et TCP/IP


de la passerelle EGX.

La passerelle EGX redmarre.

Page Paramtres Ethernet avancs

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Tableau 3 : Paramtres Ethernet avancs de la passerelle EGX


Option

Description

Valeur

Dure de vie

Dtermine le nombre de routeurs par lesquels un


paquet TCP peut passer.

1 255 sauts
Par dfaut : 60
sauts

Maintien de la
connexion TCP

Dcompte permettant de dtecter lorsquun appareil 0 65 000 s


Par dfaut :
sur une connexion inactive devient indisponible du
fait dun redmarrage, dune mise hors tension, etc. 30 secondes
Entrez la valeur 0 pour dsactiver cette fonction.

Dlai dattente
BootP

Permet de spcifier le temps pendant lequel la


passerelle EGX doit attendre lassignation de son
adresse IP par un serveur BootP (ladresse IP par
dfaut est utilise si aucune adresse IP nest
attribue aprs le dlai dattente).

Dlai dattente du
cache ARP

Permet de spcifier le temps pendant lequel les


0 65 000 minutes
entres sont conserves dans la table ARP (Address Par dfaut :
Resolution Protocol).
15 minutes

Serveur FTP

Dtermine si le serveur FTP sinitialise pendant le


dmarrage.

Dlai dinactivit de
la connexion FTP

Dcompte permettant de fermer une connexion FTP 30 900 s


aprs le temps dinactivit dfini.
Par dfaut :
120 secondes

Dlai dinactivit de
la connexion HTTP

Dcompte permettant de fermer une connexion


HTTP aprs le temps dinactivit dfini.

0 65 000 s
Par dfaut :
4 secondes

Numro de port
HTTP

Port TCP utilis pour les messages HTTP. Les


numros de port suivants sont rservs dautres
protocoles rseau et ne sont donc pas disponibles :
20 et 21 (FTP) et 502 (Modbus TCP/IP).

0 65 000
Par dfaut : 80
0 dsactive le port
HTTP

Numro de port
HTTPS

Port TCP utilis pour les messages HTTPS.


La passerelle EGX est fournie avec un certificat autosign. Pour authentifier lEGX comme serveur, vous
devez obtenir un certificat dune autorit de
certification (par exemple VeriSign Authentication
Services).

1 65 000
Par dfaut : 443
0 dsactive le port
HTTPS

0 60 s
Par dfaut :
15 secondes

Dsactiv ou Activ
Par dfaut : Activ

Pour ajouter ou installer un certificat numrique,


ouvrez la page de mise jour du certificat,
ladresse http://x.x.x.x./update_certs_shtml (o
x.x.x.x correspond ladresse IP de lEGX).
Tentatives de
maintien de la
connexion HTTP

Permet de spcifier le nombre maximal de tentatives 0 65 000


de maintien de la connexion HTTP.
Par dfaut : 100

Connexions serveur Permet de spcifier le nombre de connexions


Modbus TCP/IP
serveur Modbus TCP/IP disponibles.

16 64
Par dfaut : 32

Diffusion Modbus

Dsactiv, Activ
ou Activ avec
rponse
Par dfaut :
Dsactiv

Dtermine le traitement par le sous-rseau srie des


messages Modbus TCP/IP de type Unit ID = 0.
Dsactiv = tous les messages sont ignors. Activ =
tous les messages sont traits comme des
messages diffusion gnrale en direction des ports
srie nappelant pas de rponse. Activ avec
rponse = tous les messages sont traits comme des
messages ordinaires en direction des ports srie
avec rponse attendue.

Proxy Modbus/TCP Dtermine si les messages Modbus TCP/IP


provenant de clients distants seront achemins aux
appareils Modbus TCP/IP distants dfinis dans la
passerelle EGX.
Dlai dattente du
client Modbus
TCP/IP

Dsactiv ou Activ
Par dfaut : Activ

0,1 10
Temps que doit attendre la passerelle EGX pour
quun appareil Modbus TCP/IP distant rponde une Par dfaut :
5 secondes
demande Modbus TCP/IP lance par la passerelle
EGX.

Dlai dattente de la Temps que doit attendre la passerelle EGX pour


1 10
connexion client
quun appareil Modbus TCP/IP distant rponde une Par dfaut :
Modbus TCP/IP
demande de connexion Modbus TCP/IP lance par 2 secondes
la passerelle EGX.
Dlai dinactivit de
la connexion
serveur Modbus
TCP/IP

2009-2013 Schneider Electric. Tous droits rservs.

Dcompte permettant de fermer une connexion


Modbus TCP/IP aprs le temps dinactivit dfini.
Entrez la valeur 0 pour dsactiver cette fonction.

0 32 767 s
Par dfaut : 0

Passerelle Ethernet PowerLogicTM EGX300


Configuration

Dtection des adresses IP identiques

63230-319-216B3_FR
03/2013

Lorsquelle est connecte au rseau, la passerelle EGX publie son adresse


IP. Pour viter les conflits dadresses, la passerelle EGX utilise le protocole
ARP (Address Resolution Protocol) pour vrifier si un autre appareil du
rseau utilise la mme adresse IP. Le Tableau 4 ci-dessous dcrit comment
la passerelle EGX ragit en cas de dtection dune adresse IP identique.
Tableau 4 : Scnarios de dtection des adresses IP identiques
Scnario

Adresse IP en double dtecte

Voyant LED
dalimentation / tat

Redmarrage /
Rtablissement de
lalimentation

Rtablit ladresse IP, le masque de


Quatre clignotements,
sous-rseau et ladresse par dfaut de pause
la passerelle EGX. Les demandes ARP
sont envoyes toutes les 15 secondes
Liaison Ethernet dtecte
jusqu ce que ladresse IP soit
disponible. Lorsque ladresse est
disponible, la passerelle EGX lutilise.
Modification manuelle
des adresses

La passerelle EGX conserve son


adresse IP prcdente et affiche un
message qui indique que ladresse IP
est dj utilise par un autre appareil.

Rception dune
demande ARP

Rtablit ladresse IP, le masque de


Quatre clignotements,
sous-rseau et ladresse par dfaut de pause
la passerelle EGX si un appareil
connect envoie quatre demandes
ARP pour ladresse IP de la passerelle
EGX. La passerelle EGX envoie des
demandes ARP toutes les 15 secondes
jusqu ce que ladresse IP soit
nouveau disponible. Lorsque ladresse
est disponible, la passerelle EGX
lutilise.

Port srie
Action

Rsultat

1. Dans le menu Configuration, cliquez sur


Port srie.

Ouvre la page Port srie.

2. Slectionnez linterface physique, le mode Slectionne les options de port srie.


de transmission, la vitesse, la parit et le
dlai de rponse (voir le Tableau 5,
page 9).
3. Cliquez sur Appliquer.

Figure 5 :

Met jour les paramtres du port srie de la


passerelle EGX.

Page Port srie

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Tableau 5 : Paramtres de port srie


Option

Description

Valeur

Interface
physique

Permet de slectionner le cblage


physique du port srie de la passerelle
EGX.

RS-485 4 fils, RS-485 2 fils ou RS-232


Par dfaut : RS-485 2 fils

Mode de
transmission

Permet de dterminer comment les


donnes sont transmises travers une
connexion srie.

Vitesse de
transmission

Permet de slectionner la vitesse de


transmission travers une connexion
srie.

2400, 4800, 9600, 19200, 38400,


56000* ou 57600*
Par dfaut : 19200

Parit

Permet de slectionner le type de parit Paire, Impaire ou Aucune


requise pour vrifier lexactitude des
Par dfaut : Paire
donnes laide dun bit de parit.

Dlai
dattente de
rponse

0,1 10 s
Permet de slectionner le temps
pendant lequel la passerelle EGX attend Par dfaut : 3 secondes
une rponse dun appareil srie.

Automatique
Modbus ASCII

REMARQUE : Le mode automatique


permet simultanment de
communiquer avec les appareils
esclaves Modbus RTU, PowerLogic
(SY/MAX) et Jbus sur la mme
guirlande.

* Disponible uniquement si linterface physique et le mode de transmission sont RS-232/Modbus


ASCII.

Paramtres avancs du port srie

NOTE
MAUVAISES PERFORMANCES DU RSEAU
Les paramtres Ethernet avancs de la passerelle EGX ne doivent tre
modifis que par des techniciens qualifis qui ont lu et assimil la
documentation relative ces paramtres.
Le non-respect de ces instructions pourrait entraner une baisse des
performances de linterface srie.

Action

Ouvre la page des paramtres


avancs du port srie.

2. Configurez les paramtres de port srie avancs (voir le


Tableau 6, page 10 pour les options disponibles). Cliquez
sur Valeurs par dfaut pour slectionner les valeurs par
dfaut pour toutes les options.

Permet de dfinir les


paramtres avancs du port
srie.

3. Cliquez sur Appliquer.

Met jour les paramtres


avancs du port srie de la
passerelle EGX.

REMARQUE : La modification des donnes de la page


Paramtres avancs du port srie ne valide aucune des
modifications apportes la page Port srie.

Figure 6 :

2009-2013 Schneider Electric. Tous droits rservs.

Rsultat

1. Cliquez sur Avanc dans la page Port srie.

Page des paramtres avancs du port srie

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Tableau 6 : Paramtres avancs du port srie


Option

Connexions dappareils distants

Description

Valeur

Dlai dattente
entre trames

Dfinit lintervalle de silence minimal entre 0 100 millisecondes


la fin de la rponse reue et le dbut dune Par dfaut : 50 millisecondes
nouvelle requte sur la ligne srie.

Extension de
lintervalle de
silence

Permet dtendre au-del des


3,5 caractres normaux lintervalle de
silence charg de marquer la fin dun
paquet Modbus RTU.

Code derreur de
dlai dattente
Modbus TCP/IP

Indique le code derreur renvoy lorsquun 0x0A ou 0x0B


Par dfaut : 0x0B
appareil srie connect la passerelle
EGX ne rpond pas dans le dlai prvu
pour le port srie. Pour Modbus TCP/IP, ce
code est 0x0B. Dans certaines suites
logicielles plus anciennes, le code tait
0x0A.

0 15 caractres
Par dfaut : 6 caractres

LEGX peut tablir des connexions pour un maximum de 16 appareils


Modbus TCP/IP distants uniques dfinis par lutilisateur. Vous pouvez entrer
les connexions manuellement ou les slectionner dans le tableau des
connexions dtectes par le Point daccs systme (voir Figure 7, page 11).
Ces connexions seront ajoutes la configuration de la liste des appareils
pour la configuration dappareils distants.
Action

Rsultat

1. Dans le menu Configuration, cliquez sur


Connexions dappareils distants.

Ouvre la page Connexions dappareils distants.

2. Pour ajouter manuellement une connexion, Configure les adresses IP des appareils
entrez les adresses IP des appareils
distants.
distants auxquels vous souhaitez vous
connecter.
3. Pour ajouter une connexion dtecte par le Entre ladresse IP de la connexion slectionne
Point daccs systme, cliquez sur Ajouter parmi les connexions dtectes par le Point
( droite de la connexion souhaite dans le daccs systme.
tableau des connexions dtectes).
4. Cliquez sur Appliquer.

10

Met jour les paramtres de connexions


dappareils distants de la passerelle EGX.

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Figure 7 :

2009-2013 Schneider Electric. Tous droits rservs.

Connexions dappareils distants

11

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Liste des appareils EGX

Avant de commencer, gardez lesprit que vous ne devez pas utiliser les
adresses esclaves srie 1 16 en mode de transmission automatique sur
une guirlande utilisant plusieurs protocoles (par exemple, une guirlande qui
comporte des appareils utilisant le protocole PowerLogic et dautres utilisant
le protocole Modbus RTU/Jbus).

Connexion dappareils une passerelle EGX

La Figure 8 et la Figure 9 montrent les possibilits de connexion des


appareils la passerelle EGX. Pour ajouter ces appareils la liste des
appareils, suivez la procdure dcrite la section Configuration de la liste
des appareils , page 13.
Figure 8 :

Topologie Appareils esclaves srie uniquement

Connexion Ethernet
Pages Web de lEGX300
EGX

Connexion RS-485

Appareils esclaves srie

Figure 9 :

Topologie Appareils esclaves srie et appareils distants


Connexion Ethernet

Pages Web de lEGX300


EGX100 Adresse
IP : 169.254.0.28

16 connexions IP distantes
sont possibles

EGX300 Adresse
IP : 169.254.0.75

Connexion
RS-485

Appareils esclaves distants

12

Connexion RS-485

Appareils esclaves srie

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Configuration de la liste des appareils


Action
1. Dans le menu Configuration, cliquez sur
Liste des appareils.

Rsultat
Ouvre la page Liste des appareils. (Voir
Figure 10 pour les connexions locales
uniquement ; Figure 11 si des connexions
distantes sont disponibles.)

Ouvre la page Dtection des appareils pour


2. Vous pouvez utiliser la dtection des
dtecter tous les appareils connects
appareils pour dtecter les appareils
connects localement (voir Dtection des localement.
appareils , page 15) puis passer
ltape 3 pour configurer les appareils
distants si ncessaire.
3. Reportez-vous la Figure 11, page 14 et
slectionnez le nombre dappareils
affichables (1 64).

Slectionne le nombre demplacements


affichables qui peuvent servir dfinir des
appareils connects la passerelle EGX.

4. Slectionnez la Connexion dans la liste


droulante.*

Slectionne la connexion.

5. Slectionnez le Type dappareil dans la


liste droulante.*

Slectionne le type dappareil.

6. Dans la zone de texte Nom dappareil,


tapez le nom de lappareil.

Saisit le nom de lappareil.

7. Dans la zone de texte Identification


Configure ladresse locale de lappareil.
locale, tapez ladresse de lappareil
esclave srie sil est raccord au port srie
ou saisissez ladresse que vous voulez
utiliser pour accder un appareil distant.*
8. Dans la zone de texte Identification
distante, tapez ladresse de lappareil
distant.*

Configure ladresse de lappareil distant.

9. Recommencez les tapes 4 8 jusqu ce Saisit tous les appareils connects.


que tous les appareils soient configurs.
10. Cliquez sur Appliquer.

Actualise la liste des appareils.

* Ce paramtre de configuration peut tre modifi uniquement si lenregistrement des donnes


est dsactiv pour lappareil mis jour. Voir Journaux dappareil , page 17.

Figure 10 : Page Liste des appareils

2009-2013 Schneider Electric. Tous droits rservs.

13

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Figure 11 : Page Liste des appareils avec connexions distantes


prises en charge

Tableau 7 : Paramtres de la liste des appareils


Option

14

Description

Valeur

Nombre dappareils
afficher

Slectionne le nombre dappareils


afficher.

1 64
Par dfaut : 8

Connexion

Slectionne le site de connexion.

Port srie ou adresse IP


Par dfaut : Port srie

Type dappareil

Slectionne le type dappareil apparaissant Ensemble des appareils pris


dans la liste.
en charge

Nom dappareil

Permet dattribuer un nom chaque


appareil.

Identification locale

Vous devez dfinir lidentification locale.

Identification
distante

Vous devez dfinir lidentification distante.

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Dtection des appareils

Loption Dtection des appareils permet la passerelle EGX de dtecter les


appareils Modbus connects au port srie qui ne sont pas dans la liste des
appareils. Les appareils saisis prcdemment dans la liste sont valids
quelle que soit la plage de dtection configure.
Dtection
Lorsque vous lancez la dtection des appareils, la passerelle EGX interroge
le port srie local sur une plage dadresses dfinie par lutilisateur (voir la
Figure 12, page 16). La dtection sur la connexion srie utilise le protocole
Modbus ASCII ou RTU, selon la configuration active du port srie. Si
lappareil rpond la requte, lidentification locale prend ladresse dtecte
et lappareil reoit un nom par dfaut. La passerelle EGX essaie alors
didentifier le type dappareil. Si la passerelle EGX reconnat le type de
lappareil dtect, elle indique le nom correspondant dans la zone Type
dappareil. Si la passerelle EGX ne reconnat pas le type dappareil, la zone
Type dappareil prend la valeur par dfaut Modbus . Une zone dtat
affiche ltat de la dtection.
Validation
Toutes les entres dfinies prcdemment dans la liste des appareils pour
lensemble des connexions (srie et distantes), quelles soient ou non
comprises dans la plage dadresses de la dtection, sont valides pendant
le processus de dtection. Sur la connexion srie, le protocole de validation
est dtermin par la configuration actuelle de lappareil dans la liste des
appareils. Le protocole Modbus TCP/IP est utilis pour la validation des
appareils distants. La passerelle EGX affiche lidentification locale, le nom
dappareil et le type dappareil mmoriss partir de la liste des appareils,
puis elle interroge lappareil. Elle affiche alors le type dappareil identifi par
cette requte, puis le compare au type dfini prcdemment. Ltat indique
alors sil existe une diffrence ou si la configuration dfinie prcdemment
est valide.
REMARQUE : Vous pouvez modifier le nom et le type de lappareil, et
slectionner individuellement les appareils stocker dans la liste des
appareils. Nanmoins, si lenregistrement de journaux est activ pour un
appareil, vous ne pouvez modifier que son nom.

Action

Rsultat

1. Dans le menu Configuration, cliquez sur


Liste des appareils.

Ouvre la page Liste des appareils.

2. Pour dtecter les appareils connects


localement, cliquez sur Dtection.

Ouvre la page Dtection des appareils.

3. Saisissez ladresse de dbut et ladresse Dfinit la plage dadresses de dtection.


de fin.
REMARQUE : Les appareils saisis
prcdemment dans la liste des appareils et
dont les adresses (identifications locales) se
trouvent en dehors de la plage de dtection
seront valids.
4. Cliquez sur Lancer la dtection. (Cliquez Dbute la dtection de tous les appareils
sur Arrter la dtection pour arrter le
connects et dfinis.
processus.)
REMARQUE : La dtection ne dtecte que
les appareils Modbus srie connects
localement la passerelle EGX. Les
appareils distants doivent tre ajouts
manuellement. Voir Connexions
dappareils distants , page 10.
5. Saisissez un nouveau nom dappareil dans Renomme lappareil.
la zone de texte Nom.

2009-2013 Schneider Electric. Tous droits rservs.

15

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Action

Rsultat

6. Slectionnez la case cocher Enregistrer Slectionne ou dslectionne une entre


en regard de lappareil que vous souhaitez dappareil enregistrer ou renommer.
enregistrer dans la liste des appareils.
7. Cliquez sur le bouton Appliquer de la
page Dtection des appareils.

Enregistre dans la liste des appareils la


configuration de tous les appareils
slectionns.

Figure 12 : Dtection des appareils

Tableau 8 : Options de dtection des appareils


Option

16

Description

Valeur

Adresse dbut/fin

Dfinit la plage dadresses Modbus utilise 1 247


pour dtecter des appareils sur le port srie Par dfaut : dbut, 1 ; fin, 10
de lEGX.

Enregistrer

Permet denregistrer lappareil slectionn


dans la liste des appareils.

Activ ou Dsactiv
Par dfaut : Activ

Connexion

Affiche la connexion sur laquelle lappareil


a t dtect ou valid.

Port srie ou adresse IP (pour


la validation des appareils
distants)

Dfini

Affiche le type dappareil dfini pour cet


appareil.

Attribu

Permet de slectionner le type dappareil


dans la liste droulante.

Nom

Permet de personnaliser le nom de


lappareil.

Identification
locale

Affiche lidentification locale.

Identification
distante

Affiche lidentification distante.

tat

Affiche ltat de la dtection ou de la


validation.

Valide, Inconnu, chec,


Dtect, Dtection ou Essai

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Journaux dappareil

Lenregistrement des journaux est disponible pour tous les types dappareils
pris en charge par la passerelle EGX. La passerelle EGX peut enregistrer
dans un journal, des intervalles prdfinis (5, 10, 15, 20, 30 et
60 minutes), les donnes transmises par des appareils connects
localement et distance. Cette section dcrit comment la passerelle EGX
enregistre les donnes dans les journaux et comment configurer
lenregistrement des journaux pour un appareil.

Enregistrement des donnes par intervalle

Dans un systme de surveillance de lnergie, de nombreux appareils ne


peuvent pas conserver les donnes dans une mmoire non volatile. La
passerelle EGX300 peut enregistrer des donnes des intervalles
prdfinis en provenance de 64 appareils connects en srie et distance.
La passerelle EGX enregistre les donnes dans des fichiers FIFO (premier
entr, premier sorti) non volatiles.
La capacit de chaque fichier journal varie selon lintervalle
denregistrement slectionn. Pour calculer la capacit denregistrement
dun fichier journal, il faut diviser le nombre maximum possible dintervalles
enregistrs que peut contenir le fichier (171 072) par le produit du nombre
de grandeurs enregistres et des intervalles enregistrs en un jour.
Capacit du journal = intervalles (max) / (grandeurs par intervalle * intervalles
enregistrs en un jour)

Par exemple, la capacit denregistrement dun fichier qui enregistre trois


grandeurs toutes les 10 minutes serait calcule comme suit :
Intervalles enregistrs par jour = minutes par jour / intervalle denregistrement (en
minutes)
= 1440 / 10
= 144 intervalles
Capacit du journal = maximum intervalles possibles / (grandeurs par intervalle *
intervalles enregistrs en un jour)
= 171072 / (3 * 144)
= 396 jours

La capacit denregistrement est calcule de faon dynamique et affiche


dans la page Slection de grandeur (voir les exemples du Tableau 9).
Tableau 9 : Exemples dintervalles denregistrement
Nombre de
grandeurs

Capacit du journal (en jours) pour les intervalles indiqus


Intervalle 5 min

Intervalle 10 min

Intervalle 15 min

594

1188

1782

297

594

891

198

396

594

148

297

445

118

237

356

99

198

297

Configuration de lintervalle denregistrement

Lenregistrement peut tre activ individuellement sur chaque appareil de la


liste. Les grandeurs consigner sont spcifiques chaque appareil. Pour
afficher les journaux de donnes dintervalle, voir Journaux dappareil ,
page 40.
REMARQUE : Pour activer la fonction Journaux dappareil, vous devez
slectionner une valeur dans la fentre Intervalle denregistrement. Nous
vous recommandons de dsactiver la fonction denregistrement sur
lappareil que vous configurez. Il suffit pour cela de dcocher loption
correspondante pour lappareil slectionn (voir Figure 13, page 18).

2009-2013 Schneider Electric. Tous droits rservs.

17

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Action

Rsultat

1. Dans le menu Configuration, cliquez sur Journaux


dappareil (voir Figure 13).
2. Reportez-vous la Figure 13 et cochez loption
Enregistrement du ou des appareils dont vous
voulez enregistrer les donnes.
Pour slectionner tous les appareils, cliquez sur
slectionner tout, puis sur Appliquer.
Pour dslectionner tous les appareils, cliquez
sur effacer, puis sur Appliquer.
3. Slectionnez lintervalle denregistrement.
4. Cliquez sur Appliquer.

Ouvre la page Journaux dappareil.


Slectionne les appareils dont les
donnes doivent tre enregistres.

Dfinit lintervalle denregistrement


pour les appareils slectionns.
Met jour les paramtres
denregistrement des journaux
dappareil de la passerelle EGX.

OPTIONS
Slectionne les grandeurs dappareils
Pour personnaliser le contenu enregistr, activez
enregistrer, puis revient la page
lenregistrement puis procdez comme suit :
Journaux dappareil principale.
1. Slectionnez un intervalle denregistrement non nul
REMARQUE : Si vous modifiez
puis dcochez loption denregistrement pour
les grandeurs par dfaut
lappareil en question.
enregistres pour un appareil, un
2. Cliquez sur grandeurs sous Personnaliser pour
astrisque (*) apparat ct des
lappareil que vous souhaitez configurer.
grandeurs dans la colonne
3. Reportez-vous la Figure 14, page 19 et cochez les
Personnaliser pour chaque
grandeurs que vous souhaitez enregistrer.
appareil. La modification des
Pour slectionner toutes les grandeurs, cliquez
grandeurs dun journal dappareil
dj activ a pour consquence
sur slectionner tout, puis cliquez sur
deffacer toutes les donnes
Appliquer.
prcdemment enregistres pour
Pour dslectionner toutes les grandeurs, cliquez
cet appareil. Si ncessaire, il
sur effacer, puis cliquez sur Appliquer.
convient de rcuprer les
Pour slectionner les grandeurs par dfaut,
donnes de lEGX avant les
cliquez sur Valeurs par dfaut en bas de lcran.
modifications.
Slectionne les journaux de donnes
Pour supprimer un journal de donnes, cochez loption
purger.
Purge donnes du ou des journaux en question.
1. Pour slectionner tous les appareils, cliquez sur
slectionner tout, puis sur Appliquer.
2. Pour dslectionner tous les appareils, cliquez sur
effacer, puis sur Appliquer.
Pour dsactiver lenregistrement, slectionnez un
intervalle denregistrement nul, assurez-vous que les
options denregistrement sont dcoches, puis cliquez
sur Appliquer.

REMARQUE : Pour purger un


journal de donnes, il est impratif
que loption Enregistrement de
journaux soit dsactive.
Dsactive la fonction
denregistrement.

Figure 13 : Page Journaux dappareil

Grandeurs consigner

Vous pouvez slectionner individuellement les grandeurs consigner pour


chaque appareil.
Action

Rsultat

1. la page Journaux dappareil, cliquez sur le lien grandeurs pour Ouvre la page de
lappareil en question.
slection des grandeurs.
2. Reportez-vous la Figure 14, page 19 et cochez les grandeurs Permet de slectionner
que vous souhaitez enregistrer.
les grandeurs
enregistrer.
Pour slectionner toutes les grandeurs, cliquez sur
slectionner tout.
Pour dslectionner toutes les grandeurs, cliquez sur effacer.
Pour slectionner les grandeurs par dfaut, cliquez sur
Valeurs par dfaut.
3. Cliquez sur Appliquer.

18

Enregistre dans le
journal les grandeurs
slectionnes.

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Figure 14 : Page de slection des grandeurs

Exporter le journal de lappareil

Cette fonction permet dexporter les journaux dappareils de trois faons :


par courrier lectronique, FTP ou HTTP. Chaque mthode est dcrite dans
les sections suivantes.
REMARQUE : Si les serveurs de courrier lectronique, FTP ou HTTP ne se
trouvent pas sur le mme segment de rseau Ethernet que la passerelle
EGX, assurez-vous que les paramtres de passerelle EGX par dfaut sont
correctement configurs. Voir Paramtres Ethernet et TCP/IP , page 5.

Exportation par courrier lectronique


Action

Rsultat

1. Dans la page Configuration, cliquez sur Exporter le


journal de lappareil.

Ouvre la page Exporter le journal


de lappareil.

2. Slectionnez Courrier lectronique comme mode


dacheminement.

Affiche les options dexportation


des journaux dappareil par
courrier lectronique.

3. Cochez loption Incrmentale.

Slectionne uniquement les


nouvelles donnes enregistres
REMARQUE : Si lacheminement est rgl sur les options
depuis la dernire exportation de
Horaire ou Intervalle denregistrement , la case
donnes russie.
cocher Incrmentale est automatiquement slectionne.
REMARQUE : Si loption Incrmentale est dsactive, la
totalit du fichier journal est envoye en fichier joint
chaque intervalle dfini.

4. Slectionnez Horaire, Quotidien, Hebdomadaire,


Mensuel ou Intervalle denregistrement.

2009-2013 Schneider Electric. Tous droits rservs.

Slectionne la frquence denvoi


des journaux de donnes.

19

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Action

Rsultat

5. Selon les options spcifies ltape prcdente,


Spcifie quel moment les
slectionnez lheure, le jour de la semaine et/ou le jour du journaux de donnes sont
mois.
envoys.
6. Dans la zone de texte De ladresse, tapez ladresse
lectronique de la personne responsable de lappareil.

Dfinit lexpditeur du courrier


lectronique.

REMARQUE : Ladresse lectronique de lexpditeur est


indispensable car la plupart des serveurs SMTP la
demandent.
7. Dans les zones de texte Aux adresses, tapez les
adresses lectroniques (5 maximum) des destinataires
des journaux de donnes (une adresse par zone).

Dfinit les adresses


lectroniques des destinataires.

8. Dans les zones de texte Adresse IP du serveur,


saisissez ladresse du serveur de courrier sortant (de
0.0.0.0 255.255.255.255).

Dfinit ladresse du serveur qui


envoie les journaux.

REMARQUE : Contactez votre administrateur rseau si


vous ne connaissez pas ladresse du serveur SMTP
(Simple Mail Transfer Protocol).
9. Dans la zone de texte Port TCP du serveur, saisissez le Dfinit le port dexpdition du
port dexpdition du serveur de courrier sortant.
serveur de courrier sortant.
Par dfaut : 25
10. Si le serveur SMTP exige une authentification, activez
loption Connexion au serveur SMTP via
authentification.

Permet de saisir les identifiants


de connexion au serveur SMTP.

REMARQUE : La passerelle EGX prend en charge les


types dauthentification Plain, Login, CRAM-MD5 et
Digest-MD5.
11. Si vous avez coch loption Connexion au serveur
SMTP via authentification, saisissez votre nom
dutilisateur et votre mot de passe dans les zones de
texte.

Mmorise vos identifiants de


connexion au serveur SMTP.

12. Cliquez sur Courrier lectronique de test pour envoyer Envoie un courrier lectronique
un message test avec les paramtres que vous avez
de test et/ou applique les
dfinis ou cliquez sur Appliquer.
paramtres dexportation du
journal par courrier lectronique.
REMARQUE : Le bouton Courrier lectronique de test
valide les paramtres dexportation du journal par courrier
lectronique et envoie un courrier de test ; le bouton
Appliquer valide uniquement les paramtres.

Figure 15 : Page Exporter le journal de lappareil par courrier


lectronique

20

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Exportation par FTP


Action

Rsultat

1. Dans la page Configuration, cliquez sur Exporter le


journal de lappareil.

Ouvre la page Exporter le


journal de lappareil.

2. Slectionnez FTP comme mode dacheminement.

Affiche les options dexportation


des journaux dappareil par FTP.

3. Activez loption Incrmentale.


REMARQUE : Si lacheminement est rgl sur les options
Horaire ou Intervalle denregistrement , la case
cocher Incrmentale est automatiquement slectionne.
REMARQUE : Si loption Incrmentale est dsactive, la
totalit du fichier journal est envoye par FTP chaque
intervalle dfini.

Permet de slectionner
uniquement les nouvelles
donnes enregistres depuis la
dernire exportation de donnes
russie.

4. Slectionnez Horaire, Quotidien, Hebdomadaire,


Mensuel ou Intervalle denregistrement.

Permet de slectionner la
frquence dacheminement des
journaux de donnes.

5. Selon les options spcifies ltape prcdente,


Spcifie quel moment les
slectionnez lheure, le jour de la semaine et/ou le jour du journaux de donnes sont
mois.
achemins.
6. Dans les zones de texte Adresse IP du serveur,
saisissez ladresse du serveur FTP sortant (de 0.0.0.0
255.255.255.255).
REMARQUE : Contactez votre administrateur rseau si
vous ne connaissez pas ladresse du serveur FTP (File
Transfer Protocol).

Dfinit ladresse du serveur


acheminant les journaux de
donnes.

7. Saisissez le rpertoire dans la zone de texte Rpertoire.

Permet de saisir les informations


relatives au rpertoire du
serveur distant.

8. Saisissez votre nom dutilisateur et votre mot de passe


dans les zones de texte.

Mmorise vos identifiants de


connexion au serveur.

9. Activez loption Passif.

Permet de slectionner le mode


passif pour le transfert FTP.

10. Cliquez sur Test FTP pour effectuer un test des paramtres Envoie un fichier de test au
FTP que vous avez dfinis ou cliquez sur Appliquer.
serveur et rpertoire FTP et/ou
REMARQUE : Le bouton Test FTP valide les paramtres applique les paramtres FTP.
dexportation du journal par FTP et transfre un fichier de
test ; le bouton Appliquer valide uniquement les
paramtres.

Figure 16 : Page Exporter le journal de lappareil par FTP

REMARQUE : Si lacheminement est rgl sur les options Horaire ou Intervalle


denregistrement , la case cocher Incrmentale est automatiquement slectionne.

2009-2013 Schneider Electric. Tous droits rservs.

21

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Exportation par HTTP


Action

Rsultat

1. Dans la page Configuration, cliquez sur


Exporter le journal de lappareil.

Ouvre la page Exporter le journal de lappareil.

2. Slectionnez HTTP comme mode


dacheminement.

Affiche les options dexportation des journaux


dappareil par HTTP.

3. Cochez loption Incrmentale.

Permet de slectionner uniquement les


nouvelles donnes enregistres depuis la
REMARQUE : Si lacheminement est rgl
sur les options Horaire ou Intervalle dernire exportation de donnes russie.
denregistrement , la case cocher
Incrmentale est automatiquement
slectionne.

REMARQUE : Si loption Incrmentale est


dsactive, la totalit du fichier journal est
envoye par HTTP chaque intervalle
dfini.
4. Slectionnez Horaire, Quotidien,
Hebdomadaire, Mensuel ou Intervalle
denregistrement.

Permet de slectionner la frquence


dacheminement des journaux de donnes.

5. Selon les options spcifies ltape


Spcifie quel moment les journaux de
prcdente, slectionnez lheure, le jour de donnes sont achemins.
la semaine et/ou le jour du mois.
6. Dans les zones de texte Adresse IP du
serveur, saisissez ladresse du serveur
HTTP.

Dfinit ladresse IP du serveur acheminant les


journaux de donnes.

REMARQUE : Contactez votre


administrateur rseau si vous ne
connaissez pas ladresse du serveur
HTTP.
7. Dans la zone de texte Port TCP du
serveur, saisissez le port du serveur
HTTP.

Dfinit le port TCP dexpdition.


Par dfaut : 80

REMARQUE : Si vous souhaitez utiliser


une connexion SSL pour lexportation,
entrez le numro de port TCP du serveur
HTTPS (habituellement 443).
8. Si vous utilisez un serveur proxy, saisissez Dfinit ladresse IP du serveur proxy
son adresse IP dans les zones de texte
acheminant les journaux de donnes.
Adresse IP du serveur proxy.
REMARQUE : Consultez ladministrateur
du rseau si vous ne connaissez pas
ladresse du serveur proxy.
9. Dans la zone de texte Port TCP du
serveur proxy, saisissez le port du
serveur HTTP.

Dfinit le port TCP dexpdition.


Par dfaut : 0

REMARQUE : Si vous souhaitez utiliser


une connexion SSL pour lexportation,
entrez le numro de port TCP du serveur
HTTPS (habituellement 443).
10. Dans la zone de texte Chemin, saisissez
le chemin du script serveur que le serveur
Web doit excuter lorsque la passerelle
EGX lui transmet des donnes.

Insre le chemin du script serveur.

11. Dans le champ Nom de champ, saisissez Permet la passerelle EGX de passer des
le nom sous lequel le serveur Web doit
fichiers un script de serveur Web existant.
attendre le nom de fichier.
REMARQUE : Si ce critre est sans objet,
utilisez la valeur par dfaut datafile1 .

22

12. Dans le champ Nom dhte, saisissez le


nom de domaine de lhte.

Identifie un hte spcifique sur le serveur Web


si ce serveur hberge plusieurs domaines pour
une mme adresse IP. (Vide par dfaut.)

13. Saisissez votre nom dutilisateur et votre


mot de passe dans les zones de texte.

Mmorise vos identifiants de connexion au


serveur.

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Action

Rsultat

14. Si vous souhaitez utiliser une connexion


SSL pour lexportation, cochez cette
option.

Tous les journaux dappareil exports via HTTP


seront dsormais exports via SSL (HTTPS).

15. Cliquez sur Test HTTP pour effectuer un


test des paramtres HTTP que vous avez
dfinis ou cliquez sur Appliquer.

Envoie un fichier de test au serveur et


rpertoire HTTP et/ou applique les
paramtres HTTP.

REMARQUE : Lorsque vous cliquez sur


Test HTTP, les paramtres dexportation
du journal par HTTP sont appliqus et un
fichier de test est transfr. Lorsque vous
cliquez sur Appliquer, les paramtres sont
simplement appliqus.

Figure 17 : Page Exporter le journal de lappareil par HTTP

Date et heure

La page Date et heure permet de rgler la date et lheure de la passerelle


EGX.
Action
1. Dans le menu Configuration, cliquez sur
Date et heure.

Rsultat
Ouvre la page Date et heure.

2. Rglez lanne, le mois, le jour, lheure, les Rgle la date et lheure.


minutes et les secondes.
3. Slectionnez le dcalage horaire.

Rgle lhorloge sur le fuseau horaire


slectionn.

4. Pour que lhorloge passe automatiquement Permet lhorloge de passer automatiquement


lheure dt, slectionnez la case
lheure dt.
cocher Activer le rglage automatique
de lheure dt.
5. Saisissez lordinal, le jour de la semaine, le Dfinit le dbut et la fin de lheure dt.
mois et lheure de dbut et de fin de lheure
dt.
6. Cliquez sur Appliquer.

2009-2013 Schneider Electric. Tous droits rservs.

Enregistre les paramtres de date et dheure.

23

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Figure 18 : Page Date et heure

Synchronisation de lheure rseau

La synchronisation de lheure rseau permet de rgler la date et lheure de


lhorloge du systme EGX laide dun serveur NTP (Network Time
Protocol).
REMARQUE : Si le serveur NTP ne se trouve pas sur le mme segment de
rseau Ethernet que la passerelle EGX, assurez-vous que les paramtres de
passerelle EGX par dfaut sont correctement configurs.

Action

Rsultat

1. Slectionnez la case cocher Activer


synchronisation de lheure rseau de la
page Date et heure.

Affiche les paramtres SNTP ainsi que la


dernire synchronisation horaire russie.

2. Configurez le dcalage horaire, la priode


de scrutation et ladresse IP des serveurs
NTP primaire et secondaire (voir le
Tableau 10, page 25).

Rgle les paramtres SNTP.

3. Cliquez sur Appliquer.

Enregistre la configuration SNTP.

Figure 19 : Activation de la synchronisation de lheure rseau

24

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Tableau 10 : Paramtres SNTP


Option

Paramtres SNMP

Description

Valeur

Dcalage horaire

Lheure est dfinie en fonction de la valeur UTC12:00 UTC+13:00


de temps universel coordonn (UTC
Par dfaut : UTC (GMT)
Universal Time Coordinated) slectionne.

Activer le rglage
automatique de
lheure dt

Permet de dfinir le dbut et la fin de


lheure dt.

Premier Cinquime ou
Dernier,
Dimanche Samedi,
Janvier Dcembre,
0:00 23:00
Par dfaut :
Dbute le deuxime
dimanche de mars 2:00.
Termine le deuxime
dimanche de novembre
2:00.

Priode de scrutation Contrle la frquence laquelle la


passerelle EGX contacte le serveur NTP
pour obtenir lheure correcte.

1 heure 1 semaine
Par dfaut : 1 semaine

Adresse IP du
Adresse IP du serveur NTP primaire que
serveur NTP primaire la passerelle EGX contacte pour obtenir
lheure correcte.

0.0.0.0 255.255.255.255
Par dfaut : 0.0.0.0

Adresse IP du
serveur NTP
secondaire

0.0.0.0 255.255.255.255
Par dfaut : 0.0.0.0

Adresse IP du serveur NTP secondaire


que la passerelle EGX contacte pour
obtenir lheure correcte.

La passerelle EGX prend en charge le protocole SNMP qui permet un


administrateur rseau daccder distance la passerelle EGX au moyen
dun gestionnaire SNMP et dafficher le statut rseau et les diagnostics de la
passerelle au format MIBII.
Action

Rsultat

1. Dans le menu Configuration, cliquez sur


Paramtres SNMP.

Ouvre la page Paramtres SNMP.

2. Slectionnez loption Activer SNMP pour


activer le protocole SNMP.

Active le protocole SNMP.

3. Saisissez le contact systme, le nom et


lemplacement du systme, le nom de la
communaut en lecture seule et le nom de la
communaut en lecture/criture.

Saisit les informations SNMP du systme


et les noms daccs des communauts.

4. Cliquez sur Appliquer.

Enregistre la configuration SNMP.

Figure 20 : Page Paramtres SNMP

2009-2013 Schneider Electric. Tous droits rservs.

25

Passerelle Ethernet PowerLogicTM EGX300


Configuration

Filtrage Modbus TCP/IP

63230-319-216B3_FR
03/2013

Cette fonction permet ladministrateur de dfinir le niveau daccs des


clients Modbus TCP/IP aux appareils (locaux ou distants) connects la
passerelle EGX.
REMARQUE : Il existe une adresse anonyme Modbus TCP/IP
(***.***.***.***) quil est possible de configurer en lecture seule ou sans droit
daccs. La configuration en Lecture seule permet nimporte quel client
Modbus TCP/IP ne figurant pas dans la liste filtre daccder en lecture
seule aux appareils srie esclave. La configuration sans droit daccs
(Aucun) bloque tous les clients Modbus TCP/IP qui ne figurent pas dans la
liste filtre.
Action

Rsultat

1. Dans le menu Configuration, cliquez sur


Filtrage Modbus TCP/IP.

Ouvre la page Filtrage Modbus TCP/IP.

2. Slectionnez loption Activer le filtrage.

Active le filtrage.

3. Dans la colonne Adresse IP, saisissez


ladresse client Modbus TCP/IP.

Saisit ladresse IP dun client Modbus TCP/IP


qui accdera aux appareils srie connects
la passerelle EGX.

4. Dans la colonne Niveau daccs,


slectionnez Lecture seule ou Complet.

Slectionne le niveau daccs pour chaque


adresse IP correspondante. En Lecture seule,
les codes de fonctions Modbus TCP/IP
suivants sont autoriss :
Dcimal : 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24,
43, 100
Hexadcimal : 01, 02, 03, 04, 07, 08, 0B, 0C,
11, 14, 18, 2B, 64

5. Recommencez les tapes 3 et 4 pour


ajouter dautres adresses IP.

Ajoute dautres adresses IP filtrer.

6. Cliquez sur Appliquer.

Enregistre la liste de filtrage des adresses


Modbus TCP/IP.

Figure 21 : Page Filtrage Modbus TCP/IP

26

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Liens vers la documentation

La passerelle EGX prend en charge deux types de liens vers la


documentation :
1. Accs aux fichiers locaux (documentation stocke en interne sur la
passerelle EGX).
2. Accs des URL externes.
REMARQUE : Les documents locaux que vous voulez faire apparatre sur
la page Web Documentation doivent tre placs dans le dossier EGX
www/documentation par FTP.
Action
1. Dans le menu Configuration, cliquez sur
Liens vers la documentation.

Rsultat
Affiche la page Liens vers la documentation.

2. Pour laccs aux fichiers : slectionnez la Dfinit quels fichiers et URL apparaissent la
case cocher Activ du ou des liens vers page Documentation.
les noms de fichiers que vous voulez
activer.
Pour laccs aux URL : slectionnez la
case cocher Activ du ou des liens URL
que vous voulez activer.
3. Activez loption Nouvelle fentre si vous Dfinit quels fichiers et URL souvrent dans une
voulez que les fichiers et URL slectionns nouvelle fentre lorsquils sont cliqus.
souvrent dans une nouvelle fentre
lorsque lutilisateur clique dessus.
4. Dfinit le titre du lien vers la documentation Dfinit le titre du lien vers la documentation qui
dans la zone de texte Texte du lien.
apparat sur la page Documentation.
5. Cliquez sur Appliquer.

Met jour les paramtres des liens vers la


documentation EGX.

Figure 22 : Page Liens vers la documentation

REMARQUE : Pour des informations sur la documentation charge, voir


Documentation , page 50.

2009-2013 Schneider Electric. Tous droits rservs.

27

Passerelle Ethernet PowerLogicTM EGX300


Configuration

Comptes utilisateur

63230-319-216B3_FR
03/2013

Les utilisateurs de la passerelle EGX reoivent un nom dutilisateur et un


mot de passe. Chaque utilisateur appartient un groupe et chaque groupe
a des droits daccs aux pages Web EGX qui lui sont attribus par
ladministrateur EGX.
REMARQUE : Il existe deux comptes utilisateur par dfaut : Administrator
(administrateur, mot de passe : Gateway) et Guest (invit, mot de passe :
Guest).
Action

Rsultat

1. Dans le menu Configuration, cliquez sur Comptes


utilisateur.

Ouvre la page Comptes utilisateur.

2. Si vous voulez modifier le nom dun groupe, tapez le


nouveau nom dans lune des zones de texte de la
zone Groupes (vous ne pouvez pas modifier le nom
du groupe Administrator).

Entrez le nom du nouveau groupe.

3. Dans la zone Utilisateurs, saisissez le nom (1 24


caractres) et le mot de passe (0 12 caractres) du
nouvel utilisateur.
REMARQUE : Les noms et les mots de passe des
utilisateurs distinguent les majuscules et les
minuscules ; ils peuvent contenir uniquement des
caractres alphanumriques.

Dfinit le nom et le mot de passe


dun utilisateur.
LEGX300 indique par une couleur
et une mention textuelle le niveau
de scurit du mot de passe :
Rouge = Mot de passe vide / Mot
de passe faible
Jaune = Mot de passe moyen
Bleu
= Mot de passe fort
Vert
= Mot de passe trs fort

4. Slectionnez le groupe ainsi que la langue par dfaut


du nouvel utilisateur.

Slectionne le nom et la langue de


lutilisateur.

5. Recommencez les oprations 3 et 4 pour chaque


utilisateur que vous voulez ajouter.

Ajoute dautres utilisateurs.

6. Cliquez sur Appliquer.

Enregistre tous les paramtres dun


compte utilisateur.

Tableau 11 : Comptes et mots de passe EGX


Compte

Mot de passe par dfaut

Administrator

Gateway

Guest

Guest

Comptes personnaliss (jusqu 11 comptes)

Aucune valeur par dfaut Le mot de passe


personnalis est dfini par lutilisateur.

Figure 23 : Page Comptes utilisateur

28

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Accs aux pages Web


Action

Rsultat

1. Dans le menu Configuration, cliquez sur Accs aux


pages Web.

Ouvre la page Accs aux pages


Web.

2. Slectionnez le niveau daccs aux pages Web (Aucun,


Lecture seule ou Complet) de chaque groupe
dutilisateurs.

Voir le Tableau 12 pour une


explication des niveaux daccs
de chaque groupe.

3. Pour autoriser le compte Guest accder la page Web, Permet au groupe par dfaut
slectionnez Lecture seule sous la colonne Guest.
Guest daccder la page Web.
REMARQUE : Si le groupe Guest est en lecture seule,
les autres groupes peuvent tre configurs uniquement
en lecture seule ou en accs complet.
4. Recommencez les tapes 2 et 3 pour rgler les options
de chaque section.

Slectionne le niveau daccs


chaque page Web.

5. Cliquez sur Appliquer.

Enregistre la configuration des


mots de passe.

Tableau 12 : Accs des groupes


Groupe
Administrator

Accs
Accs complet toutes les pages Web.
REMARQUE : Il est recommand de changer le mot de passe par
dfaut du compte Administrateur lors de la premire connexion.

Guest

Accs en lecture seule aux pages Web slectionnes.

Trois groupes
personnaliss dfinis
par lutilisateur

En choisissant parmi les options ci-dessous, ladministrateur attribue


des niveaux daccs aux pages Web pour chaque groupe. Les niveaux
daccs sont les suivants :
Aucun : le groupe ne peut pas accder la page Web slectionne.
Lecture seule : le mot de passe autorise laccs en lecture seule du
groupe la page Web slectionne.
Complet : le groupe a le mme droit daccs que le groupe
Administrator la page Web slectionne.

Figure 24 : Page Accs aux pages Web

2009-2013 Schneider Electric. Tous droits rservs.

29

Passerelle Ethernet PowerLogicTM EGX300


Configuration

Ajout/Suppression de pages Web


personnalises

63230-319-216B3_FR
03/2013

Les pages Web personnalises et autres fichiers peuvent tre transfrs de


votre ordinateur vers la passerelle EGX par FTP. Les fichiers placs via
FTP dans les rpertoires www/monitoring (surveillance), www/maintenance
ou www/control (commande), sils sont dots de lextension .htm, .html ou
.shtml, sont automatiquement scuriss. La barre de menus de linterface
Web comporte un lien vers chacun de ces dossiers. Lorsque vous cliquez
sur lun de ces liens, les pages personnalises que vous ajoutez
apparaissent dans le menu, dans la partie gauche de la fentre du
navigateur, sous Pages personnalises.
REMARQUE : Vous ne pouvez pas crer de nouveaux dossiers dans les
dossiers prdfinis Monitoring, Control et Maintenance.
Une fois les pages Web personnalises ou autres fichiers transfrs vers la
passerelle EGX par FTP, il est possible de les ajouter ou de les retirer de
linterface Web, sans avoir les supprimer de la passerelle EGX, par le
biais de la page Ajouter/supprimer des pages Web. Cette page est
accessible depuis la page Accs aux pages Web.

Ajout de pages Web personnalises par FTP


Action

Rsultat

1. Lancez lExplorateur Windows, tapez ftp://


suivi de ladresse IP de la passerelle EGX
(ex. ftp://169.254.0.10) dans la barre
dadresses, puis appuyez sur Entre.

Ouvre la bote de dialogue Connexion en tant


que.

2. Tapez le nom dutilisateur Administrator et


le mot de passe correspondant dans les
zones de texte appropries, puis cliquez
sur Connexion.

Ouvre une session FTP avec la


passerelle EGX.

3. Ouvrez une autre fentre de lExplorateur


Copie le fichier dans le Presse-papiers.
Windows, localisez la page Web
personnalise que vous souhaitez envoyer
la passerelle EGX, cliquez dessus avec le
bouton droit, puis choisissez Copier.
4. Revenez lExplorateur Windows de lEGX Ouvre le dossier dans lequel la page sera
(fentre affiche ltape 1), puis ouvrez le stocke sur la passerelle EGX.
dossier dans lequel la page doit tre copie
( /www/monitoring/ , par exemple).
5. Cliquez avec le bouton droit dans le volet
Copie la page personnalise sur la passerelle
droit de la fentre de lExplorateur Windows EGX.
et cliquez sur Coller.
REMARQUE : Au lieu de copier-coller le
fichier, vous pouvez le faire glisser vers
lExplorateur Windows.
6. Cliquez sur le bouton Fermer de la fentre Ferme la fentre de lExplorateur Windows.
de lExplorateur Windows.

Suppression de pages Web personnalises


par FTP

Action

Rsultat

1. Lancez lExplorateur Windows, tapez ftp://


suivi de ladresse IP de la passerelle EGX
(ex. ftp://169.254.0.10) dans la barre
dadresses, puis appuyez sur Entre.

Ouvre la bote de dialogue Connexion en tant


que.

2. Tapez le nom dutilisateur Administrator et


le mot de passe correspondant dans les
zones de texte appropries, puis cliquez
sur Connexion.

Ouvre une session FTP avec la


passerelle EGX.

3. Ouvrez le dossier dans lequel la page Web Ouvre le dossier contenant la page Web
est stocke, cliquez avec le bouton droit sur personnalise, puis supprime le fichier.
le fichier supprimer, puis choisissez
Supprimer.
4. Cliquez sur le bouton Fermer de la fentre Ferme la fentre de lExplorateur Windows.
de lExplorateur Windows.

30

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Ajout/Suppression de pages Web


personnalises laide de linterface Web

Action
1. Dans le menu Configuration, cliquez sur
Accs aux pages Web.

Rsultat
Ouvre la page Accs aux pages Web.

2. Cliquez sur Ajouter/supprimer des pages Ouvre la page Ajouter/supprimer des pages
Web (voir la Figure 25).
Web.
3. Si vous avez ajout des pages Web
Slectionne ou dslectionne une page Web
personnalises aux dossiers EGX, la liste personnalise.
de ces fichiers apparat sous chaque nom
de dossier. Slectionnez les pages Web
que vous souhaitez rendre disponibles pour
les utilisateurs. Dslectionnez les pages
qui ne doivent pas tre visibles.
REMARQUE : Lorsque vous
dslectionnez une page Web, elle nest
pas supprime de la passerelle EGX.
4. Cliquez sur Appliquer.

Ajoute ou supprime une page personnalise


de linterface Web EGX.

Figure 25 : Page Ajouter/Supprimer des pages Web

2009-2013 Schneider Electric. Tous droits rservs.

31

Passerelle Ethernet PowerLogicTM EGX300


Configuration

Prfrences

63230-319-216B3_FR
03/2013

Cette option permet de personnaliser les passerelles EGX individuellement.


Action

Rsultat

1. Dans le menu Configuration, cliquez sur


Prfrences.

Ouvre la page Prfrences.

2. Saisissez le nom de lquipement, la page Dfinit les prfrences.


daccueil par dfaut, la frquence
dchantillonnage en temps rel, ainsi que
la frquence de vrification des
communications.
3. Cliquez sur Appliquer.

Met jour les paramtres de prfrences de la


passerelle EGX.

Figure 26 : Page Prfrences

Tableau 13 : Paramtres de prfrences


Option

32

Description

Valeur

Nom de lquipement

Permet de personnaliser le nom de lEGX et Par dfaut : Powerlogic


de lquipement associ. Ce nom sera
EGX300
utilis dans la bannire de linterface Web.

Page daccueil par


dfaut

Permet de slectionner la page daccueil


par dfaut.

Frquence
dchantillonnage en
temps rel

Dfinit la frquence de lecture des donnes 5 60 s


Par dfaut : 5 secondes
du ou des appareils dans laffichage
standard des tableaux de surveillance.

Frquence de
vrification des
communications

Dfinit la frquence laquelle les


Dsactiv, 5 30 minutes
communications sont vrifies lorsque le
Par dfaut : 15 minutes
navigateur affiche des mesures en temps
rel dans laffichage standard des tableaux
de surveillance. Cette fonction essaie de
remettre automatiquement en service tout
appareil hors service.

Accueil,
Rcapitulatif circuit,
Rsum du courant de
charge,
Rcapitulatif des val.
moyennes du courant,
Rcapitulatif puissance ou
Rcapitulatif nergie.
Par dfaut : Accueil

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Types dappareil affichables

La page Types dappareil affichables permet de grer les types dappareil


slectionnables par lutilisateur dans la page Liste des appareils. tant donn
le nombre de types dappareil pris en charge par la passerelle EGX300, le fait
de supprimer certaines entres de la liste des types disponibles permet de
simplifier la configuration dans la page Liste des appareils.
Action

Rsultat

1. Dans le menu Configuration, cliquez sur Types


dappareil affichables.

Ouvre la page Types dappareil


affichables.

2. Slectionnez les types dappareil qui doivent tre


disponibles dans la liste de configuration.

Permet de slectionner les types


dappareil qui doivent tre
disponibles dans la liste de
configuration.

REMARQUE : Cliquez sur slectionner tout pour


activer tous les appareils et sur effacer pour
dsactiver tous les appareils.
REMARQUE : Vous ne pouvez changer la
disponibilit des types dappareil correspondant des
appareils en cours dutilisation.
3. Cliquez sur Appliquer.

Enregistre les paramtres de Types


dappareil affichables.

Figure 27 : Page Types dappareil affichables

Piste daudit

La piste daudit est une squence horodate denregistrements ou de


messages. Elle consigne les changements de configuration, les erreurs et
les checs dauthentification, et indique lutilisateur lorigine de chaque
vnement.
Utilisez la page Piste daudit pour configurer les groupes de rapports et
canaux de messages. Pour chaque canal, vous choisissez le ou les
groupes de rapports qui pourront afficher les messages. Lorsque vous
slectionnez un groupe de rapports pour un canal, vous voyez safficher les
messages gnrs dans ce groupe de rapports.
Les canaux de messages sont les suivants :

Fichier journal de maintenance interne de lEGX

Courrier lectronique

Serveur Syslog distant (Syslog est un protocole pour les messages de


journalisation)

Tous les messages sont horodats et identifient le groupe de rapports et


lutilisateur.
2009-2013 Schneider Electric. Tous droits rservs.

33

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

La page Piste daudit est divise en trois sections correspondant aux trois
canaux de messages : Journal de maintenance, Syslog, Courrier
lectronique. (Voir Figure 28, page 35.) Vous pouvez configurer
sparment les messages envoys sur chaque canal.
Dans la fentre Configuration, cliquez sur Piste daudit. La page Piste
daudit saffiche. Suivez les instructions du tableau ci-dessous.
Tableau 14 : Configuration de la piste daudit
Option

Description

Valeur

Journal de maintenance
Contrle les types de
Les messages gnrs apparaissent
rapport pour lesquels
dans le journal de maintenance
vous souhaitez voir
interne de lEGX.
apparatre des messages
dans le journal des
messages.

Cochez les options de rapport


que vous souhaitez inclure.
Par dfaut, aucune option
nest coche.

Syslog
Adresse IP du serveur.
Port UDP (User
Datagram Protocol) du
serveur
Rapport
Liste droulante
Installation
Liste droulante Gravit

Les messages gnrs sont


rexpdis au serveur que vous
spcifiez.
Les messages Syslog seront
envoys depuis ce port UDP du
serveur.
Les quatre types de rapport pour
lesquels des messages peuvent tre
rexpdis.
Donne une indication approximative
de lorigine du message au sein du
systme. Cette information
apparatra dans le journal Syslog.
Indique lutilisateur limportance
relative du message. Vous devez
dterminer limportance de chaque
type pour votre site.

Entrez ladresse IP du serveur


distant auquel vous souhaitez
rexpdier les messages.
Entrez le numro de port UDP
pour cette adresse IP. Par
dfaut = 514.
Cochez les types de rapport
pour lesquels vous souhaitez
rexpdier des messages.
Slectionnez la catgorie
approprie.

Ladresse lectronique de
lexpditeur apparatra dans le
champ De des messages
gnrs.
Le corps du message contiendra les
informations suivantes : adresse IP
de lEGX, nom du groupe de
rapports, nom de lutilisateur, adresse
IP de lutilisateur et message du
groupe de rapports.
Les messages gnrs seront
envoys la ou aux adresses
destinataires spcifies.

Spcifiez ladresse de
lexpditeur des courriers
lectroniques dans le champ
prvu cet effet. Maximum =
49 caractres.

Slectionnez la catgorie
approprie.

Courrier lectronique
De ladresse

Aux adresses

Adresse IP du serveur

Port TCP du serveur


Connexion au serveur
SMTP via
authentification
Nom dutilisateur
Mot de passe

34

Spcifiez ladresse de
lexpditeur des courriers
lectroniques dans le champ
prvu cet effet. Maximum =
49 caractres par adresse.
Adresse IP du serveur o les
Si vous ne spcifiez pas
courriers lectroniques seront
ladresse IP du serveur, aucun
envoys.
courrier lectronique ne sera
envoy.
Numro de port TCP pour ladresse Saisissez le numro de port
TCP. La valeur par dfaut est
IP du serveur.
25.
Cochez cette case pour activer la
Cochez cette option pour
connexion pour la rception des
entrer les informations de
courriers lectroniques. La connexion connexion.
au serveur SMTP exige une
authentification.
Nom dutilisateur que lEGX utilisera Tapez le nom dutilisateur
pour accder au serveur SMTP.
exig par le serveur SMTP
(maximum 31 caractres).
Mot de passe que lEGX utilisera
Tapez le mot de passe exig
pour accder au serveur SMTP.
par le serveur SMTP
(maximum 31 caractres).

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Option
Rapport

Valeurs par dfaut /


Appliquer

Description

Valeur

Types de rapport pour lesquels des


messages peuvent tre rexpdis.
Vous pouvez en cocher autant que
vous le souhaitez.
Cliquez sur Appliquer pour
enregistrer vos slections. Cliquez
sur Valeurs par dfaut pour rtablir la
valeur initiale dun champ.

Cochez les types de rapport


pour lesquels vous souhaitez
envoyer des messages.
Cliquez sur Appliquer ou
Valeurs par dfaut.

Figure 28 : Configuration de la piste daudit

Point daccs systme

Le Point daccs systme sert dtecter et relier la passerelle les autres


appareils Schneider Electric connects au rseau. Cette fonction est
active par dfaut et ne ncessite pas dautre configuration.
Utilisez cet cran de configuration pour entrer ladresse IP de groupe et
dautres informations connexes.

Action

2009-2013 Schneider Electric. Tous droits rservs.

Rsultat

1. Dans le menu Configuration, cliquez sur


Point daccs systme.

Affiche la fentre Point daccs systme.

2. Activ

Lorsque cette option est coche, les


passerelles EGX300 affectes la mme
adresse IP pourront se dtecter entre elles.
Valeur par dfaut = Activ.

3. Port UDP

Entrez le numro (entre 1 et 65535) du port


UDP utilis pour la dtection par Point daccs
systme. Valeur par dfaut = 59.

35

Passerelle Ethernet PowerLogicTM EGX300


Configuration

63230-319-216B3_FR
03/2013

Action

Rsultat

4. Adresse IP de groupe

Tapez ladresse IP du groupe. Il peut sagir


dune adresse pour multidiffusion ou
monodiffusion. Valeur par dfaut = 224.0.1.2.

5. Intervalle Hello

Intervalle entre deux messages Hello


envoys par cette passerelle EGX300 pour
annoncer sa prsence aux autres appareils
Schneider Electric dtects par le Point
daccs systme sur le rseau.
Plage = 1-65535 secondes. Valeur par dfaut
= 300 secondes.

6. Temps de retenue

Dlai dattente maximum aprs le dernier


message Hello envoy par cette EGX300
avant que les autres appareils ne la
considrent comme indisponible.
Plage = 2-65535 secondes. Valeur par dfaut
= 600 secondes.

7. Dure de vie pour multidiffusion

Vous pouvez spcifier la portion du rseau sur


laquelle portera la dtection des autres
appareils. Cette valeur est dtermine par le
nombre de fois que la multidiffusion peut tre
rexpdie aux autres appareils.
Plage = 1-255 sauts de routeur. Valeur par
dfaut = 1.

8. Communaut

Les passerelles EGX300 dun groupe peuvent


tre rparties en communauts. Les
passerelles EGX300 affectes la mme
adresse IP et au mme numro de
communaut pourront se dtecter entre elles.
Si vous rglez le numro de communaut sur
0, la passerelle pourra dtecter toutes les
autres passerelles EGX300 ayant la mme
adresse IP, quel que soit le paramtre de
communaut. Valeur par dfaut = 0.

9. Valeurs par dfaut / Appliquer

Cliquez sur Appliquer pour enregistrer vos


slections. Cliquez sur Valeurs par dfaut pour
rtablir les valeurs initiales.

Figure 29 : Page de configuration du Point daccs systme

36

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

63230-319-216B3_FR
03/2013

SURVEILLANCE

La passerelle EGX permet dafficher des donnes et tendances en temps


rel ainsi que des tendances historiques.

Donnes en temps rel

Les pages de donnes en temps rel affichent les mesures de base des
appareils slectionns en temps rel ainsi que les rsums des appareils.

Pages dappareil unique

Pour afficher les donnes en temps rel dans un tableau, accdez au menu
Surveillance et slectionnez un appareil sous Donnes en temps rel >
Pages dappareil unique.

Paramtres des mesures de base


Action

Rsultat

1. En haut de lcran, slectionnez Courant de


charge, Puissance, Tension L-L ou Tension L-N
pour afficher la grandeur en question sur le
graphique cadran analogique.

Permet de slectionner les grandeurs


afficher sur le graphique cadran
analogique.
REMARQUE : Les cadrans
analogiques ne sont pas
disponibles pour tous les types
dappareil.

2. Par dfaut, les cadrans ajustent automatiquement la Permet de contrler la plage affiche
plage affiche. Pour utiliser une plage fixe,
par les cadrans analogiques.
slectionnez Plage. Le tableau ci-dessous explique
comment configurer la plage des cadrans
analogiques.
3. Cliquez sur Appliquer.

Met jour la slection des cadrans pour


la page de lappareil.

Figure 30 : Page Mesures de base

2009-2013 Schneider Electric. Tous droits rservs.

37

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

Plage des cadrans analogiques

63230-319-216B3_FR
03/2013

La plage affiche sur les cadrans analogiques de la page Mesures de base


peut tre configure ou mise lchelle automatiquement (voir Figure 31).
Action

Rsultat

1. Sous Activer la mise lchelle automatique , cochez


les appareils dont les cadrans doivent tre rgls
automatiquement.

Active la mise lchelle


automatique pour les appareils
slectionns.

REMARQUE : Cliquez sur slectionner tout pour activer


la mise lchelle automatique pour tous les appareils et
sur effacer pour la dsactiver pour tous les appareils.
2. Pour les appareils sans mise lchelle automatique,
entrez les limites Min et Max de chaque type de cadran.

Spcifie la plage du cadran.

3. Cliquez sur Appliquer.

Met jour les paramtres Mise


lchelle automatique.

Figure 31 : Page de configuration de plage

Pages rcapitulatives appareils

Les vues Pages rcapitulatives appareils affichent des tableaux


rcapitulatifs concernant un appareil ou une slection dappareils.
Action

Rsultat

1. Dans le menu Surveillance, cliquez sur Pages


rcapitulatives appareils.

Dveloppe larborescence permettant


de slectionner les pages de
rcapitulatif.

2. Slectionnez la page de rcapitulatif afficher.

Ouvre la liste de slection dappareil.

3. Slectionnez un ou plusieurs appareils dans la liste Slectionne un ou plusieurs appareils


des appareils disponibles, puis cliquez sur Suivant en vue de laffichage des rcapitulatifs.
(voir la Figure 32).
REMARQUE : Cliquez sur >> pour slectionner tous
les appareils disponibles.

Figure 32 : Page Slection des appareils

38

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

63230-319-216B3_FR
03/2013

Figure 33 : Page Rcapitulatif circuit

Calcul de tendance

Pour afficher une tendance en temps rel pour plusieurs appareils et


plusieurs grandeurs, allez dans le menu Surveillance et slectionnez
Donnes en temps rel > Calcul de tendance.
Action

Rsultat

1. Dans le menu Surveillance, slectionnez Donnes en


temps rel.

Dveloppe larborescence des


options de donnes en temps
rel.

2. Slectionnez Calcul de tendance.

Dveloppe larborescence des


options de tendance en temps
rel.

3. Slectionnez Calcul de tendance en temps rel.

Ouvre la page de configuration


Calcul de tendance en temps
rel.

4. Slectionnez jusqu quatre appareils dans la liste


Appareils disponibles.

Permet de slectionner les


appareils pour le calcul de
tendance.

5. Slectionnez une ou plusieurs grandeurs dans la liste


des grandeurs disponibles.

Permet de slectionner les


grandeurs pour le calcul de
tendance.

REMARQUE : Seules les grandeurs communes tous


les appareils slectionns sont disponibles pour le calcul
de tendance. Le nombre maximum de grandeurs
prendre en compte dpend du nombre dappareils
slectionns. Le produit des appareils et grandeurs
slectionns doit tre gal ou infrieur 8.
6. Cliquez sur Suivant pour ouvrir la page daffichage
Calcul de tendance en temps rel.

La page daffichage Calcul de


tendance en temps rel souvre.

7. Pour configurer les paramtres de tendance, poursuivez Permet de dfinir les paramtres
la procdure du tableau suivant en vous reportant la
de calcul de tendance.
Figure 35, page 40.

Figure 34 : Slectionner les appareils et les grandeurs

2009-2013 Schneider Electric. Tous droits rservs.

39

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

63230-319-216B3_FR
03/2013

Action

Rsultat

1. Slectionnez le type de tendance : Absolue ou Relative.

Permet de slectionner le mode


du graphique.

REMARQUE : En mode Absolue, laxe des abscisses est


gnr nouveau aprs chaque chantillon et comporte
toutes les donnes recueillies depuis le dbut de la
tendance. En mode Relative, le graphique est mis jour
avec les donnes les plus rcentes aprs chaque
chantillon tandis que laxe des abscisses reste constant
et affiche toute la priode de tendance slectionne.

2. Slectionnez la dure de la tendance, de 1 15 minutes. Il Permet de slectionner la


priode considre pour le
sagit de la dure de la tendance.
calcul de tendance.
REMARQUE : Les donnes sont chantillonnes aussi
vite que possible mais la vitesse de transmission dpend
de la charge de communication sur le sous-rseau srie
et/ou sur les appareils distants.
3. Slectionnez Commencer lchantillonnage pour lancer Permet de lancer le calcul de
le calcul de tendance sur les grandeurs et appareils
tendance.
slectionns.
REMARQUE : Pour arrter le calcul de tendance avant la
fin de la priode, cliquez sur Arrter lchantillonnage. Si
vous arrtez lopration puis cliquez nouveau sur
Commencer lchantillonnage, un nouveau calcul de
tendance commence.
4. Cliquez sur Accs aux donnes pour afficher le journal
de toutes les grandeurs chantillonnes enregistres au
cours du calcul de tendance.
REMARQUE : Aprs chaque intervalle, la valeur actuelle
de chaque grandeur ainsi que les valeurs Min, Max et
Moyenne calcules sont insres dans le tableau sous le
graphique.
5. Cliquez sur Nouvelle(s) grandeur(s) pour slectionner
dautres appareils et grandeurs pour le calcul de
tendance.

Permet dafficher le journal de


toutes les valeurs
chantillonnes au cours du
calcul de tendance.

Rouvre la page de
configuration Calcul de
tendance en temps rel.

Figure 35 : Calcul de tendance en temps rel

Journaux dappareil

40

Les pages Journaux dappareil fournissent des reprsentations graphiques


et tabulaires des donnes enregistres pour lappareil slectionn. Pour
plus de dtails sur la configuration de lenregistrement des journaux
dappareil, voir Journaux dappareil , page 17.

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

63230-319-216B3_FR
03/2013

Pages dappareil unique

Les Pages dappareil unique fournissent des reprsentations graphiques et


tabulaires des donnes enregistres pour un seul appareil.
Action

Rsultat

1. Dans le menu Surveillance, cliquez sur


Journaux dappareil.

Dveloppe larborescence des options


Journaux dappareil disponibles.

2. Sous Journaux dappareil, cliquez sur


Pages dappareil unique.

Dveloppe larborescence pour afficher les


appareils dont les journaux de donnes
peuvent tre consults.

3. Slectionnez un appareil dans la liste


Journaux dappareil.

Affiche le journal de lappareil slectionn.

4. Slectionnez la plage de donnes


afficher dans la liste droulante.

Permet de slectionner la plage de donnes


tracer.

5. Maintenez le bouton gauche de la souris


enfonc et tracez une zone de slection
sur la partie du graphique agrandir.

Agrandit la partie du graphique slectionne.

6. Pour revenir laffichage dorigine,


appuyez sur la touche Z du clavier ou
double-cliquez sur le graphique.

Laffichage rtrcit.

7. Cliquez sur Accs aux donnes pour


afficher le journal de donnes dintervalle
slectionn (voir la Figure 37 ci-dessous).

Ouvre le tableau du Journal de donnes


dintervalle slectionn.

8. Pour afficher dautres grandeurs, cliquez


Permet dafficher les grandeurs slectionnes.
sur Nouvelle(s) grandeur(s). Cochez les
valeurs afficher puis cliquez sur le bouton
Appliquer.

Les donnes enregistres pour chaque appareil saffichent dans une page
Web sous forme dun graphique temporel. Ce graphique est prconfigur
pour afficher les donnes de la dernire journe complte, de la dernire
semaine complte, du dernier mois complet ou toutes les donnes.
Les paramtres dnergie sont enregistrs comme valeurs cumules mais
affichs sous forme de valeurs incrmentales par intervalle. Tous les autres
paramtres sont enregistrs et affichs comme la valeur relle enregistre.
Figure 36 : Graphique du journal de donnes dintervalle

Figure 37 : Tableau des accs aux donnes du journal dintervalle

2009-2013 Schneider Electric. Tous droits rservs.

41

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

Obtention dun journal de donnes

63230-319-216B3_FR
03/2013

Vous pouvez rcuprer un journal de donnes dintervalle laide des


mthodes indiques dans le Tableau 15 :
Tableau 15 : Mthodes de rcupration des journaux de donnes par
intervalle Formats des fichiers
Mthode de rcupration

Format du fichier rcupr

FTP

CSV (valeurs spares par des virgules)

Bouton Accs aux donnes

HTML

Requte Web Microsoft

HTML

Courrier lectronique

CSV

HTTP

CSV

Pour afficher la liste des journaux disponibles, effectuez la procdure


dcrite aux tapes 2 4 de la section Obtention dun journal de donnes
dintervalle via FTP , page 43. Les fichiers seront dnomms ainsi : Nom
dappareil_Identification locale.csv o Nom dappareil correspond au
nom donn lappareil esclave et Identification locale lidentification
numrique locale qui lui est attribue. Par exemple, un appareil appel
Arrive services Btiment et dot de lidentification locale 3 donnera
le fichier Arrive services Btiment_3.csv .
En cas dexportation des journaux de donnes, la date et lheure sont
ajoutes au nom du fichier sous la forme : _AAAAMMJJHHMMSS Par
exemple : Arrive services Btiment 1_3_20100218115216.csv . Ce
nom indique que le fichier a t export le 18 fvrier 2010 11:52:16.
Format des journaux

Les donnes sont enregistres au format suivant (voir Figure 38, page 43) :
Tableau 16 : Format des journaux de donnes dintervalle
Ligne

Donnes au format CSV

Description

(BOM)Nom passerelle,N srie


passerelle,Adresse passerelle,Nom
appareil,ID appareil local,Nom type
appareil,Intervalle enregistrement
REMARQUE : (BOM) Les trois premiers
octets du fichier forment une marque
dordre des octets (Byte Order Mark)
dnotant le format UTF-8.

Cette ligne contient les en-ttes de colonne


des informations affiches la ligne 2.

EGX300SD,23227,157.198.184.116,
Arrive services Btiment 1,3,
CM4000,15

Cette ligne contient les informations relatives


la passerelle EGX et lappareil
enregistr.

Cette ligne est vide.

,,,Identification grandeur 1,Identification


grandeur 2,Identification grandeur 3

Cette ligne contient les en-ttes de colonne


des identifications de grandeurs affiches
la ligne 5. Lidentification dune grandeur est
une rfrence numrique la grandeur sur
laquelle porte lenregistrement. Le nom
attribu une grandeur peut diffrer selon
les appareils et la langue. Les identifications
de grandeurs permettent didentifier les
grandeurs, indpendamment de lappareil ou
de la langue. Les trois premires virgules
servent la mise en page dans un tableur.

,,,1617,1621,1625

Cette ligne contient les identifications de


grandeurs des valeurs consignes.

Cette ligne est vide.

Erreur,Dcalage par rapport temps


universel UTC (minutes),Horodatage
local,nergie apparente (kVAh),nergie
active (kWh),nergie ractive (kVArh)

Cette ligne contient les en-ttes de colonne


des donnes enregistres prsentes ligne 8
et suivantes.

partir Ces lignes contiennent les donnes enregistres.


de la
ligne 8 0,-300,2008-10-09 14:15:00,1400738.219,1201962.707,647069.906,15
0,-300,2008-10-09 14:20:00,1400758.260,1201980.725,647078.602,15
0,-300,2008-10-09 14:25:00,1400778.198,1201998.661,647087.233,15

Si vous affichez le fichier CSV dans un tableur, la prsentation des donnes


devrait ressembler celle de la Figure 38, page 43.
42

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

63230-319-216B3_FR
03/2013

Figure 38 : Journal de donnes dintervalle ouvert dans un tableur

Codes derreur des journaux de donnes

Les codes derreur ci-dessous peuvent apparatre lorsque vous


diagnostiquez les journaux de donnes (voir Figure 36, page 41 et
Figure 37, page 41) :
Code
derreur

Dfinition

Rsultat

19

Erreur de communication (par exemple : CRC


[contrle par redondance cyclique], protocole ou
exception).

25

Expiration du dlai dattente en cas de non-rponse Lenregistrement reste activ


une requte dans le temps imparti.
moins que le dernier
intervalle nait t manqu.

38

Donnes incorrectes.

100

Expiration de la priode de scrutation avant que les


donnes puissent tre enregistres.

Lenregistrement reste activ


moins que le dernier
intervalle ait t manqu.

Intervalle manqu.

Contactez le support technique pour obtenir de laide dans la rsolution de


ces problmes ou dautres erreurs.

Obtention dun journal de donnes


dintervalle via FTP

Vous pouvez utiliser le protocole FTP pour rcuprer un journal de donnes


en vous connectant la passerelle EGX par FTP et en transfrant le fichier
CSV suivant les instructions ci-aprs.
REMARQUE : Si vous souhaitez que la passerelle EGX envoie
automatiquement le journal de donnes par FTP, les options dexportation du
journal de lappareil doivent tre configures pour FTP (voir Exportation par
FTP , page 21).
Action
1. Crez un dossier sur votre ordinateur, par
exemple c:\journaux_egx.

Rsultat
Cre un dossier pour conserver les journaux
de donnes de la passerelle EGX.

2. Lancez lExplorateur Windows, tapez ftp:// Ouvre la bote de dialogue Connexion en tant
et ladresse IP de la passerelle EGX dans la que.
barre dadresses (ex. : ftp://169.254.0.10),
puis appuyez sur Entre.
3. Tapez le nom dutilisateur Administrator et Ouvre une session FTP avec la passerelle
le mot de passe correspondant dans les
EGX et affiche les fichiers enregistrs dans la
zones de texte appropries, puis cliquez sur passerelle.
Connexion.
4. Ouvrez le rpertoire /logging/data de la
passerelle EGX.

Ouvre le rpertoire des journaux de donnes


sur la passerelle EGX.

5. Copiez le journal et collez-le dans le dossier Copie le journal dans votre dossier.
cr ltape 1.

2009-2013 Schneider Electric. Tous droits rservs.

43

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

Obtention dun journal de donnes


dintervalle par le biais du bouton Accs aux
donnes

Obtention dun journal de donnes


dintervalle par le biais dune requte Web
Microsoft

63230-319-216B3_FR
03/2013

Action

Rsultat

1. Dans la page Web Journaux dappareil


(voir la Figure 36, page 41), cliquez sur
bouton Accs aux donnes.

Une nouvelle fentre affiche les donnes


enregistres.

2. Appuyez sur CTRL+A, puis sur CTRL+C.

Slectionne toutes les donnes, puis les copie


dans le Presse-papiers.

3. Ouvrez Excel et appuyez sur CTRL+V.

Colle les donnes dans une feuille de calcul


Excel.

Action

Rsultat

1. Lancez votre navigateur Web.

Ouvre le navigateur Web.

2. Vrifiez que le journal est disponible en


Ouvre la page des journaux de donnes.
tapant ladresse IP de la passerelle
EGX300 suivie de
/stream/devlog_data.html?device=x (o
x correspond lidentification locale de
lappareil).
3. Lancez Excel et cliquez sur Donnes >
Donnes externes > Nouvelle requte
sur le Web.
REMARQUE : Le chemin daccs indiqu
correspond Microsoft Excel 2003.

Ouvre la bote de dialogue Nouvelle requte


sur le Web de Microsoft Excel.

4. Dans la bote de dialogue Nouvelle


requte sur le Web, tapez ladresse du
journal que vous avez saisie ltape 2,
puis validez.

Ouvre le journal des donnes.

5. Cliquez sur la flche la plus lextrieur


Slectionne les donnes, puis ouvre la bote de
pour slectionner toutes les donnes, puis dialogue Importer des donnes.
cliquez sur le bouton Importer.
6. Cliquez sur OK.

Importe les donnes.

REMARQUE : Si vous voulez afficher les donnes les plus rcentes chaque
fois que vous ouvrez la feuille de calcul, cliquez sur le bouton Proprits
dans la bote de dialogue Importer des donnes, puis slectionnez
Actualiser louverture du fichier .

Obtention dun journal de donnes


dintervalle par courrier lectronique

La passerelle EGX doit tre configure de manire envoyer des journaux


une adresse lectronique. Pour plus dinformations, voir Exportation par
courrier lectronique , page 19.

Obtention dun journal de donnes


dintervalle par HTTP

La passerelle EGX doit tre configure de manire envoyer des journaux


un serveur Web. Pour plus dinformations, voir Exportation par HTTP ,
page 22.

44

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

63230-319-216B3_FR
03/2013

Pages rcapitulatives appareils

Les vues Pages rcapitulatives appareils affichent des rcapitulatifs


concernant un appareil ou une slection dappareils.
Action
1. Dans le menu Surveillance, cliquez sur
Journaux dappareil.

Rsultat
Dveloppe larborescence des options
Journaux dappareil disponibles.

2. Sous Journaux dappareil, cliquez sur


Pages rcapitulatives appareils.
3. Sous Pages rcapitulatives appareils,
cliquez sur Plusieurs appareils, une
seule grandeur.

Ouvre la page de configuration Plusieurs


appareils, une seule grandeur.

4. Slectionnez un appareil dans la liste


Appareils disponibles.

Permet de slectionner les appareils pour les


options de rcapitulatif.

REMARQUE : Vous pouvez slectionner


jusqu 4 appareils.
5. Slectionnez une grandeur dans la liste
Grandeurs disponibles.

Permet de slectionner la grandeur afficher


pour chaque priphrique slectionn.

REMARQUE : Seules les grandeurs


communes tous les appareils
slectionns sont disponibles.
6. Slectionnez Suivant.

Ouvre la page de calcul de tendance Plusieurs


appareils, une seule grandeur.

7. Maintenez le bouton gauche de la souris


enfonc et tracez une zone de slection
sur la partie du graphique agrandir.

Agrandit la partie du graphique slectionne.

8. Pour revenir laffichage dorigine,


appuyez sur la touche Z du clavier ou
double-cliquez sur le graphique.

Laffichage rtrcit.

La grandeur enregistre pour les appareils slectionns saffiche dans une


page Web sous forme de graphique temporel. Ce graphique est prconfigur
pour afficher les donnes de la dernire journe complte, de la dernire
semaine complte, du dernier mois complet ou toutes les donnes.
Les paramtres dnergie sont affichs sous forme de valeurs
incrmentales par intervalle. Tous les autres paramtres sont enregistrs et
affichs comme la valeur relle enregistre.

Figure 39 : Page de configuration Plusieurs appareils, une seule


grandeur

2009-2013 Schneider Electric. Tous droits rservs.

45

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

63230-319-216B3_FR
03/2013

Figure 40 : Page de calcul de tendance Plusieurs appareils, une


seule grandeur

Tableaux de bord

La passerelle EGX prend en charge quatre catgories de tableau de bord


affichant des informations de consommation dnergie agrges sur la
priode. Le Tableau 17 liste les tableaux de bord disponibles et leurs sousensembles.
Tableau 17 : Types de tableau de bord
Tableau de bord
Par heure

Sous-ensemble
Jour prcdent, par heure
Jour courant, par heure
Jour courant sur jour prcdent, par heure

Par jour

Semaine prcdente, par jour


Semaine courante, par jour
Semaine courante sur semaine prcdente, par jour
Mois prcdent, par jour
Mois courant, par jour
Mois courant sur mois prcdent, par jour

Par semaine

Trimestre prcdent, par semaine


Trimestre courant, par semaine
Trimestre courant sur trimestre prcdent, par
semaine
13 dernires semaines, par semaine

Par mois

Anne prcdente, par mois


Anne courante, par mois
Anne courante sur anne prcdente, par mois
REMARQUE : Le fichier journal de chaque appareil
doit pouvoir contenir deux ans de donnes historiques.
Voir Enregistrement des donnes par intervalle ,
page 17 pour plus dinformations.
12 derniers mois, par mois

46

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

63230-319-216B3_FR
03/2013

Affichage dun tableau de bord


Action

Rsultat

1. Depuis le menu Surveillance, cliquez sur


Tableaux de bord.

Affiche le menu de tableau de bord (voir


Figure 41).

2. Slectionnez un appareil dans la liste


droulante Appareil.

Slectionne le priphrique dont les donnes


seront affiches.

REMARQUE : Chaque tableau de bord


affiche les donnes dun mme appareil.
3. Slectionnez une grandeur dans la liste
droulante Nom de grandeur.

Slectionne les grandeurs tracer.

REMARQUE : Seules les grandeurs de


consommation incrmentales fournies par
lappareil sont concernes ici.
4. Slectionnez les paramtres temporels
dans la liste droulante Heure.

Slectionne la priode de donnes


enregistres pour la grandeur slectionne.

5. Cliquez sur Appliquer.

Ouvre le tableau de bord slectionn.

Figure 41 : Menu de tableau de bord

Les donnes de chaque tableau de bord saffichent sur une page Web sous
la forme dun graphique barres. Lorsque vous survolez lune des barres
du graphique avec la souris, la valeur du point de donnes saffiche pour
lintervalle slectionn (Figure 42).
Figure 42 : Graphique de tableau de bord

Figure 43 : Tableau de tableau de bord

2009-2013 Schneider Electric. Tous droits rservs.

47

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

Accs aux donnes de tableau de bord par le


biais du bouton Accs aux donnes

63230-319-216B3_FR
03/2013

Procdez comme suit pour exporter les donnes dun tableau de bord sous
la forme dune feuille de calcul.
Action

Rsultat

1. Depuis le tableau de bord contenant les


Affiche les points de donnes pour le tableau
donnes, cliquez sur Accs aux donnes. de bord slectionn (Figure 43, page 47).

Enregistrement dun lien de tableau de bord

2. Appuyez sur CTRL+A, puis sur CTRL+C.

Slectionne toutes les donnes, puis les copie


dans le Presse-papiers.

3. Ouvrez Excel et appuyez sur CTRL+V.

Colle les donnes dans une feuille de calcul


Excel.

Si vous souhaitez viter de passer par le menu principal chaque fois que
vous accdez un tableau de bord, vous pouvez enregistrer un lien vers le
tableau de bord selon lune des mthodes dcrites dans le Tableau 18.
Tableau 18 : Enregistrement dun lien de tableau de bord
Option

Enregistrement dun tableau de bord sous


forme dimage

Description

Valeur

Favori de navigateur

Permet aux utilisateurs daccder


Suivez les instructions pour
au tableau de bord enregistr sur
crer un favori dans le
lordinateur sur lequel le favori a t navigateur de votre choix.
cr.

Lien vers la
documentation

Permet tous les utilisateurs EGX


daccder un tableau de bord
enregistr depuis la page
Documentation.

Voir Liens vers la


documentation , page 27 pour
configurer laccs par URL.

Courrier lectronique

Permet aux utilisateurs denvoyer


lURL dun tableau de bord dans le
corps dun message lectronique.

Chaque destinataire du
message lectronique doit
disposer dun compte utilisateur
EGX pour afficher le tableau de
bord. Voir Comptes
utilisateur , page 28.

La procdure suivante permet denregistrer un graphique de tableau de


bord sous forme dimage.
Action

Rsultat

1. Suivez les tapes de la section Affichage


dun tableau de bord, page 47.

Affiche le graphique de tableau de bord.

2. Cliquez sur Afficher sous forme dimage


en haut droite de la page (Figure 44,
page 49).

Affiche le tableau de bord sous forme dimage


dans une nouvelle fentre.

3. Cliquez avec le bouton sur limage et


choisissez Enregistrer limage sous.

Ouvre la bote de dialogue Enregistrer sous.

4. Saisissez le nom du fichier, slectionnez un Enregistre limage.


emplacement pour lenregistrer, puis
cliquez sur Enregistrer.
REMARQUE : Le type de fichier par dfaut
est le format dimage PNG. Pour changer le
type de fichier, remplacez .png par
lextension voulue dans le champ Nom de
fichier.

REMARQUE : Cette fonction nest pas disponible avec Internet Explorer


version 8 ou antrieure.

48

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B3_FR
03/2013

Passerelle Ethernet PowerLogicTM EGX300


Surveillance

Figure 44 : Enregistrement dune image de tableau de bord

Point daccs systme

LEGX peut dtecter et fournir des liens vers les passerelles EGX300 et
autres appareils Schneider Electric connects au rseau. Le Point daccs
systme ainsi cr permet daccder aux appareils Schneider Electric mis
en rseau.
La page Point daccs systme fournit un hyperlien vers chaque appareil
Schneider Electric dtect. Lorsque vous survolez un hyperlien avec la
souris, des informations supplmentaires sur lappareil saffichent gauche
de la liste.
Cliquez sur un appareil pour afficher la page de connexion cet appareil.

Figure 45 : Page Point daccs systme, avec dtails de lappareil

2009-2013 Schneider Electric. Tous droits rservs.

49

Passerelle Ethernet PowerLogicTM EGX300


Documentation

DOCUMENTATION

63230-319-216B3_FR
03/2013

La page Documentation permet daccder aux informations qui ont t


stockes sous forme de fichiers sur la passerelle EGX et de liens Web.
Pour des informations sur le chargement de liens vers la documentation,
voir Liens vers la documentation , page 27.
Pour ouvrir un lment de documentation, cliquez sur le lien Documentation
en haut de la page puis slectionnez le lien qui vous intresse.

Figure 46 : Page Documentation

COMMANDE

La passerelle EGX peut excuter manuellement une ou plusieurs


commandes de rinitialisation prdfinies pour chaque type dappareil.
Action

Rsultat

1. Depuis le menu Commande, cliquez sur


Rinitialisations.

Ouvre la page Rinitialisations.

2. Slectionnez lappareil afficher ou


rinitialiser dans la liste Rinitialisations.

Slectionne lappareil et affiche les options de


rinitialisation correspondantes, avec la date et
lheure de la dernire rinitialisation.

3. Slectionnez les paramtres de lappareil


que vous voulez rinitialiser.

Slectionne la rinitialisation effectuer sur


lappareil slectionn.

4. Cliquez sur Rinitialiser.

Envoie lappareil slectionn une ou


plusieurs commandes de rinitialisation pour la
ou les oprations souhaites et en affiche
ltat.

Figure 47 : Rinitialisations

REMARQUE : Le paramtre Date/Heure indique la date et lheure actuelles


de lappareil slectionn. Si vous choisissez de rinitialiser ce paramtre, la
date et lheure de la passerelle EGX seront envoyes lappareil.
Les valeurs de date et dheure ne sont rapportes que si lappareil offre
cette fonction. Par exemple, si le priphrique ne prend pas en charge la
valeur Min/Max pour Date/heure de la dernire rinitialisation , la valeur
Min/Max napparat pas ici.

50

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Diagnostics

63230-319-216B3_FR
03/2013

DIAGNOSTICS

Pour accder aux liens de la page Web Diagnostics, cliquez sur


Diagnostics dans la barre de menus EGX.

Statistiques

Cette page affiche les mesures cumules depuis la dernire activation de la


passerelle EGX. En cas de perte de lalimentation de la passerelle EGX, de
rinitialisation de lappareil suite une modification de la configuration ou
autre vnement, toutes les valeurs cumules sont remises zro.
Action

Rsultat

1. Dans le menu Diagnostics, cliquez sur


Statistiques.

Ouvre la page Statistiques (voir Figure 48 cidessous).

2. Affichez les donnes.

Voir Interprtation des statistiques , page 52


ci-dessous.

3. Cliquez sur Rinitialiser.

Remet zro les donnes de diagnostic de la


passerelle EGX.

Figure 48 : Page Statistiques

2009-2013 Schneider Electric. Tous droits rservs.

51

Passerelle Ethernet PowerLogicTM EGX300


Diagnostics

63230-319-216B3_FR
03/2013

Interprtation des statistiques


Statistiques

Description

Ethernet
tat de liaison

Chane de caractres qui reprsente la vitesse de


transmission et le paramtre duplex utiliss pour
communiquer avec un autre appareil.

Trames transmises avec succs

Compteur qui augmente dune unit chaque fois


quune trame est envoye sans problme.

Collisions

Compteur qui augmente dune unit chaque fois


quune trame est retransmise cause de la dtection
dune collision.

Excs de collisions

Compteur qui augmente dune unit chaque fois quil


est impossible denvoyer une trame car le nombre
maximal de collisions bas sur lalgorithme de repli
exponentiel binaire par troncature est atteint.

Trames reues avec succs

Compteur qui augmente dune unit chaque fois


quune trame est reue sans problme.

Erreurs CRC

Compteur qui augmente dune unit chaque


rception dune trame dont la somme de contrle /
CRC (contrle par redondance cyclique) ne
correspond pas la valeur calcule.

Erreurs dalignement

Compteur qui augmente dune unit chaque


rception dune trame dont la somme de contrle /
CRC (contrle par redondance cyclique) est errone
et qui ne se termine pas sur une limite sur 8 bits.

Longueur de trame excessive

Compteur qui augmente dune unit chaque


rception dune trame suprieure la taille maximale
autorise dfinie dans les normes (trames suprieures
1518 octets).

Longueur de trame insuffisante

Compteur qui augmente dune unit chaque


rception dune trame infrieure la taille minimale
autorise dfinie dans les normes (trames infrieures
64 octets).

Modbus TCP/IP
Serveur
Trames envoyes

Compteur qui augmente dune unit chaque envoi


dune trame.

Trames reues

Compteur qui augmente dune unit chaque


rception dune trame.

Erreurs de protocole

Compteur qui augmente dune unit chaque


rception dun message de format incorrect.

Connexions actives1

Valeur qui indique le nombre de connexions actives


lors de la mise jour de la page de diagnostics. Prise
en charge de 64 connexions maximum. Cliquez sur
Connexions actives pour ouvrir une nouvelle fentre
qui affiche la liste de toutes les connexions client
actives.

Connexions cumules

Compteur qui augmente dune unit chaque


connexion tablie avec la passerelle EGX.

Nombre maximal de connexions

Valeur qui indique le nombre maximal de connexions


qui taient actives un instant donn.

Messages de lecture en arrive

Compteur qui augmente dune unit chaque


rception dun message de demande de lecture.

Messages dcriture en arrive

Compteur qui augmente dune unit chaque


rception dun message de demande dcriture.

Messages de rponse en partance

Compteur qui augmente dune unit chaque envoi


dun message de rponse.

Client
Trames envoyes

Compteur qui augmente dune unit chaque envoi


dune trame.

Trames reues

Compteur qui augmente dune unit chaque


rception dune trame.

Erreurs de protocole

Compteur qui augmente dune unit chaque


rception dun message de format incorrect.

Cliquez sur le lien pour plus dinformations.

52

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Diagnostics

63230-319-216B3_FR
03/2013

Statistiques

Description

Dlais dattente

Compteur qui augmente dune unit chaque fois


quun message ne reoit aucune rponse dans le
temps imparti. Il sagit en gnral de la consquence
derreurs de configuration ou dun appareil dfaillant.

Dlai dattente connexion

Compteur qui augmente dune unit chaque fois que


la connexion a t perdue.

Exceptions reues

Compteur qui augmente dune unit chaque


rception dune exception.

Messages de lecture en partance

Compteur qui augmente dune unit chaque envoi


dun message de demande de lecture.

Messages dcriture en partance

Compteur qui augmente dune unit chaque envoi


dun message de demande dcriture.

Messages de rponse en arrive

Compteur qui augmente dune unit chaque


rception dun message de rponse.

Dtails1

Tableau dtaill prsentant des statistiques srie et


distantes par appareil.

Port srie
Trames envoyes

Compteur qui augmente dune unit chaque envoi


dune trame.

Trames reues

Compteur qui augmente dune unit chaque


rception dune trame.

Erreurs CRC

Compteur qui augmente dune unit chaque


rception dun message dont le contrle par
redondance cyclique (CRC) ne correspond pas la
valeur calcule. Indique gnralement des problmes
de cblage.

Erreurs de protocole

Compteur qui augmente dune unit chaque


rception dun message de format incorrect.

Dlais dattente

Compteur qui augmente dune unit chaque fois


quun message ne reoit aucune rponse dans le
temps imparti. Il sagit en gnral de la consquence
derreurs de configuration ou dun appareil dfaillant.

Exceptions reues

Compteur qui augmente dune unit chaque


rception dune exception.

Messages de lecture en partance

Compteur qui augmente dune unit chaque envoi


dun message de demande de lecture.

Messages dcriture en partance

Compteur qui augmente dune unit chaque envoi


dun message de demande dcriture.

Messages de lecture en arrive

Compteur qui augmente dune unit chaque


rception dun message de demande de lecture.

Messages dcriture en arrive

Compteur qui augmente dune unit chaque


rception dun message de demande dcriture.

Dtails1

Tableau dtaill prsentant des statistiques srie et


distantes par appareil.

Serveur HTTP
Trames envoyes

Compteur qui augmente dune unit chaque envoi


dune trame.

Trames reues

Compteur qui augmente dune unit chaque


rception dune trame.

Connexions actives1

Valeur qui indique le nombre de connexions actives


lors de la mise jour de la page de diagnostics. Prise
en charge de 20 connexions maximum. Cliquez sur
Connexions actives pour ouvrir une nouvelle fentre
qui affiche la liste de toutes les connexions client
actives.

Connexions cumules1

Compteur qui augmente dune unit chaque


connexion tablie avec la passerelle EGX.

Nombre maximal de connexions

Valeur qui indique le nombre maximal de connexions


qui taient actives un instant donn.

1Cliquez

2009-2013 Schneider Electric. Tous droits rservs.

sur le lien pour plus dinformations.

53

Passerelle Ethernet PowerLogicTM EGX300


Diagnostics

63230-319-216B3_FR
03/2013

Statistiques

Description

Informations sur la passerelle


Version du logiciel embarqu

Version du logiciel embarqu install sur la passerelle


EGX.

Dlai dinactivit du systme

Priode moyenne dinactivit du processeur exprime


en pourcentage (0 100 %).

Adresse MAC

Adresse matrielle Ethernet dune passerelle EGX.

Numro de srie

Numro de srie de la passerelle EGX.

Numro de modle

Numro du modle de la passerelle EGX.

Version de matriel

Version matrielle de la passerelle EGX.

Date de fabrication

Date de fabrication de la passerelle EGX.

Client HTTP
Envoi : OK

Compteur qui augmente dune unit chaque fois quun


fichier est envoy sans problme au serveur HTTP.

Erreur de connexion

Compteur qui augmente dune unit chaque fois que


la passerelle EGX ne parvient pas tablir la
connexion avec le serveur HTTP.

Erreur dauthentification

Compteur qui augmente dune unit chaque fois que


le serveur HTTP ne parvient pas authentifier les
identifiants Utilisateur / Mot de passe.

Envoi : erreur

Compteur qui augmente dune unit chaque chec


de transfert dun fichier vers le serveur HTTP.

Erreur gnrale

Compteur qui augmente dune unit chaque fois quun


fichier ne peut tre envoy parce que la passerelle
EGX ne parvient pas mettre la transaction.

Client FTP
Envoi : OK

Compteur qui augmente dune unit aprs chaque


transfert russi vers un serveur FTP.

Erreur de connexion

Compteur qui augmente dune unit chaque fois que


la passerelle EGX ne parvient pas tablir la
connexion avec le serveur FTP.

Erreur dauthentification

Compteur qui augmente dune unit chaque fois que


le serveur FTP ne parvient pas authentifier les
identifiants Utilisateur / Mot de passe.

Erreur de rpertoire

Compteur qui augmente dune unit chaque fois que


le serveur FTP ne parvient pas localiser le rpertoire
demand.

Envoi : erreur

Compteur qui augmente dune unit chaque chec


de transfert dun fichier vers le serveur FTP.

Erreur gnrale

Compteur qui augmente dune unit chaque fois quun


fichier ne peut tre envoy parce que la passerelle
EGX ne parvient pas mettre la transaction.

Client SMTP
Envoi : OK

Compteur qui augmente dune unit chaque fois quun


courrier lectronique est envoy sans problme au
serveur SMTP.

Erreur de connexion

Compteur qui augmente dune unit chaque fois que


la passerelle EGX ne parvient pas tablir la
connexion avec le serveur SMTP.

Erreur dauthentification

Compteur qui augmente dune unit chaque fois que


le serveur SMTP ne parvient pas authentifier les
identifiants Utilisateur / Mot de passe.

Envoi : erreur

Compteur qui augmente dune unit chaque fois quun


courrier lectronique ne peut pas tre envoy au
serveur SMTP.

Erreur gnrale

Compteur qui augmente dune unit chaque fois quun


courrier lectronique ne peut tre envoy parce que la
passerelle EGX ne parvient pas crer le message.

Systme de fichiers
Espace total

Espace disque total de lEGX en kilo-octets.

Espace libre

Volume total despace libre sur le disque de lEGX en


kilo-octets.

Cliquez sur le lien pour plus dinformations.

54

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Diagnostics

63230-319-216B3_FR
03/2013

Lecture de registres dappareils

Cette option permet la passerelle EGX de lire les donnes en provenance


de appareils locaux ou distants qui lui sont connects.
Figure 49 : Page Lecture de registres dappareils

Action

Rsultat

1. Dans le menu Diagnostics, cliquez sur


Lecture de registres dappareils.

Ouvre la page Lecture de registres dappareils.

2. Saisissez lidentification locale de lappareil Permet dentrer les registres lire sur lappareil
spcifi.
(ou effectuez une slection dans la liste
des appareils dfinis), ladresse de dpart
et le nombre de registres lire.
3. Slectionnez un type de donnes.

Slectionne le type de donnes appropri.

Slectionne le mode daffichage des valeurs.


4. Pour modifier laffichage des donnes
dans la colonne Valeur, slectionnez
Dcimal, Hexadcimal, Binaire ou ASCII.
5. Cliquez sur Lire.

Lit les registres dappareils en fonction de la


configuration slectionne.

Tableau 19 : Paramtres de lecture de registres dappareils EGX


Option

Description

Nom dappareil

Slectionne un appareil lire dans la liste des appareils


ajouts prcdemment. Pour lire un appareil non dfini
dans la liste des appareils, entrez son numro
didentification locale.

Identification de
lappareil

Adresse (identification locale) de lappareil lire.

Registre de dpart

Premier registre lire.

Nombre de registres

Nombre de registres lire (1 125).

Colonne Registre

Liste des numros de registres.

Colonne Valeur

Liste des donnes enregistres dans un registre. Les


valeurs rcupres dpendent de lappareil connect la
passerelle EGX. Reportez-vous la documentation de
lappareil connect pour plus dinformations sur les
valeurs stockes dans un registre.

Type de donnes

Permet de slectionner les registres de maintien, les


registres dentre, les bobines de sortie, les bobines
dentre ou lidentification dappareil.

Options Dcimal,
Slection dune option pour spcifier laffichage des
Hexadcimal, Binaire donnes de la colonne Valeur.
ou ASCII

2009-2013 Schneider Electric. Tous droits rservs.

Valeur par
dfaut

1
1000
10

Registres de
maintien
Dcimal

55

Passerelle Ethernet PowerLogicTM EGX300


Diagnostics

63230-319-216B3_FR
03/2013

Vrification des communications


Vrification automatique des
communications

Lorsque vous parcourez les affichages de donnes en temps rel, la


passerelle EGX effectue une vrification automatique des communications
toutes les 15 minutes par dfaut. (Pour changer la frquence, voir
Prfrences , page 32.) Cette opration vrifie ltat des
communications de tous les appareils configurs sur la passerelle EGX et
essaie de rtablir la communication avec tous les appareils marqus hors
service dans la session de navigation actuelle.

Vrification manuelle des communications

Dans certains cas, il peut savrer prfrable de ne pas attendre lintervalle


de vrification automatique des communications et dexcuter la vrification
manuellement.
Action

Rsultat

1. Dans le menu Diagnostics, cliquez sur


Vrification des communications.

Ouvre la page Vrification des


communications.

2. Cliquez sur Vrification de ltat des


appareils.

Effectue une vrification des communications.


Pour les appareils communicants, les valeurs
Russite et En service saffichent dans les
colonnes Communications et tat,
respectivement. Pour les appareils qui ne
communiquent pas, ces colonnes indiquent
respectivement chec et Hors service si
lchec se reproduit plusieurs fois.

Figure 50 : Page Vrification des communications

56

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Maintenance

63230-319-216B3_FR
03/2013

MAINTENANCE

Le journal de maintenance permet de consigner les oprations de


maintenance effectues sur la passerelle EGX, les quipements qui y sont
connects ou le systme dont elle fait partie. Chaque entre est enregistre
avec la date et lheure de consignation, ainsi que le nom de lutilisateur qui
la ralise.
Ce journal indique galement lactivit systme, par exemple les activations
et dsactivations de fonctions. Vous navez pas besoin dajouter des
entres pour ces lments.
Enfin, le journal liste aussi les activits spcifies pour le Journal de
maintenance dans la page de configuration Piste daudit (voir Piste
daudit , page 33).
Action

Rsultat

1. Dans le menu Maintenance, cliquez sur


Journal de maintenance.

Ouvre la page Journal de maintenance.

2. Slectionnez la case cocher Supprimer


en regard de lentre supprimer, puis
cliquez sur Supprimer des entres.

Supprime lentre slectionne.

3. Cliquez sur Effacer le journal pour


supprimer toutes les entres contenues
dans le journal de maintenance.

Efface le journal de maintenance.

4. Pour ajouter une nouvelle entre au


Ouvre la page Ajouter une entre de journal et
journal, cliquez sur Ajouter une entre de permet lutilisateur de saisir les dtails de la
journal, puis saisissez le texte de
maintenance.
maintenance dans la zone de texte Dtail
entre (voir Figure 52 ci-dessous).

Figure 51 : Journal de maintenance

Figure 52 : Ajouter une entre de journal

LOGICIEL EMBARQU
(FIRMWARE)

Vous pouvez mettre niveau le logiciel embarqu (firmware) de la


passerelle EGX au moyen du protocole FTP (File Transfer Protocol).
Rendez-vous sur le site www.schneider-electric.com ou consultez votre
reprsentant local pour obtenir la dernire mise jour du logiciel embarqu.

Recherche de la version du logiciel


embarqu

LEGX comprend deux composants de logiciel embarqu : le composant


binaire excutable et le composant image disque.

2009-2013 Schneider Electric. Tous droits rservs.

57

Passerelle Ethernet PowerLogicTM EGX300


Logiciel embarqu (firmware)

Version du composant binaire excutable du


logiciel embarqu

63230-319-216B3_FR
03/2013

Action

Rsultat

1. Ouvrez le navigateur Internet et


connectez-vous la passerelle EGX.

Ouvre la page daccueil EGX.

2. Recherchez la version du logiciel


Dtermine la version du logiciel embarqu de la
embarqu dans le coin infrieur gauche de passerelle EGX.
la page.
REMARQUE : Si vous avez rcemment
mis jour le logiciel embarqu, appuyez
sur la touche F5 pour actualiser la page et
afficher le nouveau numro de version.
3. Vous pouvez galement slectionner
Dtermine galement la version du logiciel
Diagnostics > Statistiques pour
embarqu de la passerelle EGX.
rechercher la version du logiciel embarqu
dans la section Informations sur la
passerelle.

Version de limage disque


Action

Rsultat

1. Ouvrez le navigateur Internet et


connectez-vous la passerelle EGX.

Ouvre la page daccueil EGX.

2. Recherchez la version du logiciel


embarqu en bas gauche de la page.

Dtermine la version du composant image


disque du logiciel embarqu de la passerelle
EGX.

REMARQUE : Si vous avez rcemment


mis jour le logiciel embarqu, appuyez
sur la touche F5 pour actualiser la page et
afficher le nouveau numro de version.
3. Vous pouvez galement accder lEGX
via FTP, localiser le fichier version.txt ,
puis double-cliquer dessus pour louvrir.

Obtention du dernier logiciel


embarqu

Action

Dtermine la version du composant image


disque du logiciel embarqu de la passerelle
EGX.

Rsultat

1. Lancez le navigateur Web. Dans la barre


dadresses tapez www.powerlogic.com et
appuyez sur Entre.

Ouvre le site Web de PowerLogic.

2. Slectionnez votre pays, puis cliquez sur


Go (atteindre).

Affiche le site PowerLogic de votre pays.

REMARQUE : Si vous slectionnez les


tats-Unis, allez ltape 3. Dans le cas
contraire, suivez les tapes spcifiques
chaque pays pour obtenir le logiciel
embarqu de la passerelle EGX.
3. Cliquez sur Support > Downloads
(support > tlchargements).

Ouvre la page de tlchargement.

4. Cliquez sur le lien EGX300 Firmware


(logiciel embarqu EGX300).

Affiche la page du logiciel embarqu de


lEGX300.

5. Cliquez sur le lien menant au fichier du


Ouvre la bote de dialogue de tlchargement,
logiciel embarqu (egxxxxx.bin, o xxxx
puis la bote de dialogue Enregistrer sous.
correspond au numro de la version), puis
cliquez sur Enregistrer.
6. Dans la bote de dialogue Enregistrer
Sous, slectionnez ou crez le rpertoire
local dans lequel le fichier doit tre
enregistr, puis cliquez sur Enregistrer.

Enregistre le fichier du logiciel embarqu dans


le rpertoire slectionn.

7. Cliquez sur le lien menant au fichier du


Ouvre la bote de dialogue de tlchargement,
logiciel embarqu (egxxxxx.upd, o xxxx
puis la bote de dialogue Enregistrer sous.
correspond au numro de la version), puis
cliquez sur Enregistrer.
8. Dans la bote de dialogue Enregistrer
Sous, slectionnez ou crez le rpertoire
local dans lequel le fichier doit tre
enregistr, puis cliquez sur Enregistrer.

58

Enregistre le fichier UPD du logiciel embarqu


dans le rpertoire slectionn.

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Logiciel embarqu (firmware)

63230-319-216B3_FR
03/2013

Mise jour du logiciel embarqu


(firmware)

Ne coupez pas lalimentation de la passerelle EGX pendant le


tlchargement du logiciel embarqu. Si lalimentation est coupe pendant
le processus de programmation, la passerelle EGX ne fonctionnera plus. Le
voyant LED dtat clignote rapidement pendant la programmation. Lorsque
le voyant se fige, la programmation est acheve.
Action

Rsultat

1. Lancez lExplorateur Windows, tapez ftp:// Ouvre la bote de dialogue Connexion en tant
et ladresse IP de la passerelle EGX dans la que.
barre dadresses (ex. : ftp://169.254.0.10),
puis appuyez sur Entre.
2. Tapez le nom dutilisateur Administrator et Ouvre une session FTP avec la
passerelle EGX.
le mot de passe correspondant dans les
zones de texte appropries, puis cliquez
sur Connexion.
3. Localisez le rpertoire du fichier de logiciel Copie le fichier dans le Presse-papiers.
embarqu sur votre ordinateur
(egxxxxx.bin), cliquez avec le bouton droit
sur le fichier, puis cliquez sur Copier.
4. Cliquez avec le bouton droit de la souris
dans la fentre de lExplorateur Windows,
puis cliquez sur Coller.
REMARQUE : Au lieu de copier-coller le
fichier, vous pouvez le faire glisser vers
lExplorateur Windows.

Copie le logiciel embarqu dans la passerelle


EGX, qui redmarre.
REMARQUE : Le voyant Alimentation/tat
clignote rapidement pendant que le fichier
est transfr et programm sur la
passerelle EGX. la fin de la
programmation, lEGX redmarre. Le temps
ncessaire la programmation est de 1,5
2 minutes.

5. Localisez le fichier de mise jour


Copie le fichier de mise jour dans le Presse(egxxxxx.upd) sur votre ordinateur, cliquez papiers.
avec le bouton droit sur le fichier, puis
choisissez Copier.
6. Cliquez avec le bouton droit de la souris
dans la fentre de lExplorateur Windows,
puis cliquez sur Coller.

Copie le fichier sur la passerelle EGX, qui


redmarre.

REMARQUE : Au lieu de copier-coller le


fichier, vous pouvez le faire glisser vers
lExplorateur Windows.
7. Pour vrifier que la mise jour a russi,
suivez la procdure dcrite la section
Recherche de la version du logiciel
embarqu , page 57.

Vrifie la mise jour du logiciel embarqu.

8. Cliquez sur le bouton Fermer de la fentre Ferme lExplorateur Windows et met fin la
de lExplorateur Windows.
connexion FTP avec la passerelle EGX.

2009-2013 Schneider Electric. Tous droits rservs.

59

Passerelle Ethernet PowerLogicTM EGX300


Annexe A Protocoles Ethernet pris en charge

ANNEXE A PROTOCOLES
ETHERNET PRIS EN CHARGE

63230-319-216B3_FR
03/2013

La passerelle EGX prend en charge les protocoles Ethernet suivants :

Modbus TCP/IP : Modbus TCP/IP est une combinaison du protocole


Modbus qui permet les communications matre/esclave entre des
appareils et de TCP/IP qui permet de communiquer par le biais dune
connexion Ethernet. Modbus TCP/IP permet dchanger des donnes
entre la passerelle EGX et dautres appareils compatibles Modbus
TCP/IP via le port TCP 502.

Hypertext Transfer Protocol (HTTP) : HTTP est un protocole rseau


qui gre la remise de fichiers et de donnes sur le Web. La
fonctionnalit de service Web est assure via le port TCP 80.

HTTP scuris (HTTPS) : HTTPS est un protocole rseau qui gre le


transfert crypt de fichiers et de donnes sur le Web via la technologie
SSL. La fonctionnalit de service Web scuris est assure via le port
TCP 443.

File Transfer Protocol (FTP) : FTP est un protocole rseau qui permet
de transfrer des fichiers dun ordinateur un autre sur Internet. Les
modes FTP actif et passif sont pris en charge, principalement via le port
TCP 21.

Simple Network Management Protocol (SNMP) : Bas sur le format


MIB2, SNMP permet denregistrer et didentifier des informations de
diagnostic utilises pour la gestion du rseau via le port UDP 161.

ARP (Address Resolution Protocol) : ARP convertit des adresses IP


en adresses Ethernet. La passerelle EGX envoie des requtes ARP
pour vrifier si son adresse IP est dj utilise (voir Dtection des
adresses IP identiques , page 8).

Simple Network Time Protocol (SNTP) : Le protocole SNTP permet


de synchroniser les horloges des appareils en rseau laide dun
serveur SNTP, via le port UDP 123.

Matriel
Port Ethernet RJ-45
Alimentation

Voyant LED
dalimentation
et dtat
Port srie RS-485
Voyant LED
pour les
communications
Ethernet et srie

Cavaliers de
polarit, de
terminaison et
2/4 fils
Bouton de
rinitialisation

60

Port srie RS-232


(connecteur RJ-45)

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Annexe B Types dappareil pris en charge

63230-319-216B3_FR
03/2013

ANNEXE B TYPES DAPPAREIL


PRIS EN CHARGE

La passerelle EGX prend en charge les types dappareil suivants. La liste


des appareils pris en charge tait exacte au moment de la publication de ce
document. Reportez-vous au site www.schneider-electric.com pour les
mises jour.
Tableau 20 : EGX300 Types dappareil pris en charge
Groupe dappareils

Appareils

Filtre dharmoniques actif


Disjoncteurs

Accusine
Compact NSX-A
Compact NSX-E
PowerPact A
PowerPact E
Circuit Monitors
CM100/200
CM2000
CM3000
CM4000
ION7500
ION7550
ION7600
ION7650
Appareils de mesure logiques
DM6000
DM6300
Rgulateur de temprature numrique Modle 98
Variateurs
ATV61
ATV71
Appareils de mesure dnergie
Energy Meter
Enercept
E5600
EM1200
EM1210
EM1250
EM1251
EM26-96
EM3550
EM3555
EM6400
EM6433
EM6436
EM6436DUAL
EM6438
EM7230
EM7280
iEM3150
iEM3155
iEM3250
iEM3255
ION8600
Appareils de surveillance disolement Vigilohm IM20
Vigilohm IM20-H
Gestion de moteur
TeSys T
MCM (Multi-Circuit Monitors)
BCPM modle A
BCPM modle B
BCPM modle C
BCM50A
BCM100A
MCM
Relais de surcharge (SSOLR)
MotorLogic Plus
MotorLogic Plus II
Contrleur de facteur de puissance
Varlogic

2009-2013 Schneider Electric. Tous droits rservs.

61

Passerelle Ethernet PowerLogicTM EGX300


Annexe B Types dappareil pris en charge

63230-319-216B3_FR
03/2013

Tableau 20 : EGX300 Types dappareil pris en charge


Groupe dappareils

Appareils

Power Meters

PM9c
PM200
PM300
PM500
PM600
PM700
PM800
PM1000
PM3250
PM5350
PM5500
ION6200 (Standard et Mega)
ION7300
Sepam 2000
Sepam srie 10
Sepam srie 20
Sepam srie 40
Sepam srie 80
SIM10Z
SIM10M
SIM6BZ
ATS48
MVSS/RVSS
ZED-THL-M

Relais de protection

Modules dinterface intelligents

Dispositifs de dmarrage en douceur


Capteurs de temprature, dhumidit
ou de lumire
Units de contrle

Autre

62

Micrologic A
Micrologic E
Micrologic H
Micrologic P
Acti9 SmartLink

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Index

63230-319-216B3_FR
03/2013

Index

ftp
exporter le journal de lappareil 21
pour ajouter des pages Web 30
pour obtenir un journal de donnes 43
pour supprimer des pages Web 30

A
accs la passerelle EGX via un rseau 2
adresse IP
dtection des adresses identiques 8
affichage des donnes et tendances en
temps rel 37
appareils Modbus
dtection 15
ARP (Address Resolution Protocol) 8

B
bouton Accs aux donnes
journal de donnes dintervalle 44

H
HTTP
exporter
journal de lappareil 22
numro de port
configuration 7
obtention dun journal de donnes
dintervalle 44
HTTPS
numro de port
configuration 7

calcul de tendance 39
certificat dauthentification
numro de port HTTPS 7
codes derreur
journal de donnes 43
commande 50
comptes utilisateurs
configuration 28
configuration
EGX 5
liste des appareils 13
ports srie 8
synchronisation de lheure rseau 24
connexion lEGX 2
connexions
dappareils 12
dappareils distants 10
courrier lectronique
exporter le journal de lappareil 19
journal de donnes dintervalle 44

date et heure
configuration 23
dtection des adresses IP identiques 8
dtection des appareils 15
diagnostics 51
donnes en temps rel 37

lecture de registres dappareils 55


liens vers la documentation
configuration 27
liste des appareils
EGX 12
logiciel embarqu (firmware)
mise jour 59
mise jour par ftp 57
obtention de la dernire version 58

E
EGX
connexion 2
interface utilisateur 3
liste des appareils 12
enregistrement 17, 40
format de donnes 42
grandeurs 18
intervalles 17
exportation du journal de lappareil 19
configuration 19

F
filtrage Modbus TCP/IP
configuration 26
format des journaux de donnes 42

interface utilisateur
EGX 3
intervalles denregistrement 17
introduction 1

J
journal de donnes
codes derreur 43
obtenir via ftp 43
obtention 42
journal de donnes dintervalle
laide dune requte Web Microsoft 44
par courrier lectronique 44
via ftp 43
via HTTP 44
via le bouton daccs aux donnes 44
journal de maintenance 57
piste daudit 34
journaux dappareil 17, 40

M
matriel 60

N
niveaux daccs lEGX 26

P
page Documentation 50
pages dappareil unique 37, 41
pages rcapitulatives appareils 38, 45

2009-2013 Schneider Electric. Tous droits rservs.

pages Web
ajout/suppression dans linterface
Web 31
configuration 29
personnalisation 30
paramtres
de port srie avancs 9
des mesures de base 37
Ethernet avancs 6
Ethernet et TCP/IP 5
SNMP
configuration 25
TCP/IP 5
piste daudit 33
journal de maintenance 34
section Syslog 34
plage des cadrans analogiques 38
point daccs systme
configuration 35
liens dautres passerelles EGX300 49
prfrences
personnalisation de lEGX 32
prise en charge des types dappareil 61
protocoles Ethernet 60
pris en charge 60

R
registres dappareils
lecture 55
requte Web Microsoft
journal de donnes dintervalle 44
rseau
accs via 2
ressources supplmentaires 1

S
scurit du mot de passe
indication couleur 28
statistiques 51
interprtation 52
surveillance 37
synchronisation de lheure
rseau 24
Syslog
pistes daudit 34

T
tableaux de bord 46
types dappareils
affichables 33
pris en charge 61

V
vrification des communications 56
automatique 56
manuel 56
version du composant binaire excutable du
logiciel embarqu 58
version du composant image de fichier de
logiciel embarqu 58

63

Passerelle Ethernet PowerLogicTM EGX300


Index

64

63230-319-216B3_FR
03/2013

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300


Manuel dutilisation

PowerLogic est une marque commerciale ou une marque dpose de Schneider Electric aux
tats-Unis, en France et dans dautres pays. Les autres marques commerciales sont la proprit
de leurs dtenteurs respectifs.
Ce produit doit tre install, raccord et utilis conformment aux normes et/ou aux rglements
dinstallation en vigueur. En raison de lvolution des normes et du matriel, les caractristiques
indiques par le texte et les images de ce document ne nous engagent quaprs confirmation par
nos services.

Schneider Electric
35 rue Joseph Monier
92500 Rueil-Malmaison, France
www.schneider-electric.com

63230-319-216B3_FR, 03/2013
Remplace 63230-319-216B2_FR, 11/2011
2009-2013 Schneider Electric. Tous droits rservs.

PowerLogicTM Ethernet Gateway EGX300


Benutzerhandbuch
63230-319-216B3_DE
03/2013

Sicherheitshinweise
Wichtige Informationen
Lesen Sie die Anweisungen sorgfltig durch und sehen Sie sich die
Ausrstung genau an, um sich mit dem Gert vor der Installation, dem
Betrieb oder der Wartung vertraut zu machen. In dieser Publikation oder auf
dem Gert knnen sich folgende Hinweise befinden, die vor potenziellen
Gefahren warnen oder die Aufmerksamkeit auf Informationen lenken, die
eine Prozedur erklren oder vereinfachen.
Der Zusatz eines Symbols zu den Sicherheitshinweisen Gefahr oder
Warnung deutet auf eine elektrische Gefahr hin, die zu schweren
Verletzungen fhren kann, wenn die Anweisungen nicht befolgt werden.
Dieses Symbol steht fr eine Sicherheitswarnung. Es macht auf die
potenzielle Gefahr eines Personenschadens aufmerksam. Beachten Sie
alle Sicherheitshinweise mit diesem Symbol, um schwere Verletzungen
oder Todesflle zu vermeiden.

GEFAHR
GEFAHR weist auf eine unmittelbar gefhrliche Situation hin, die bei
Nichtbeachtung zu schweren Verletzungen oder Todesfllen fhrt.

WARNUNG
WARNUNG weist auf eine potenziell gefhrliche Situation hin, die bei
Nichtbeachtung zu schweren Verletzungen oder Todesfllen fhren kann.

ACHTUNG
ACHTUNG weist auf eine potenziell gefhrliche Situation hin, die bei
Nichtbeachtung zu leichten Verletzungen fhren kann.

HINWEIS
HINWEIS wird verwendet, um Verfahren zu beschreiben, die nicht mit einer
Verletzungsgefahr verbunden sind. Das Warnsymbol darf nicht mit diesem
Signalwort verwendet werden.

Bitte beachten
Elektrisches Gert sollte stets von qualifiziertem Personal installiert,
betrieben und gewartet werden. Schneider Electric bernimmt keine
Verantwortung fr jegliche Konsequenzen, die sich aus der Verwendung
dieser Publikation ergeben knnen.
Eine qualifizierte Person ist jemand, der Fertigkeiten und Wissen im
Zusammenhang mit dem Aufbau, der Installation und der Bedienung von
elektrischen Gerten und eine entsprechende Schulung zur Erkennung und
Vermeidung der damit verbundenen Gefahren absolviert hat.

Hinweise
Hinweis zum Teil 15 der FCC-Bestimmungen
Dieses Gert wurde getestet und erfllt die Anforderungen fr digitale
Gerte der Klasse A gem Teil 15 der FCC-Bestimmungen. Diese
Bestimmungen sollen bei der gewerblichen Nutzung des Gerts einen
angemessenen Schutz gegen schdliche Funkstrungen sicherstellen.
Dieses Gert erzeugt und nutzt Energie im Funkfrequenzspektrum und
kann solche auch abstrahlen. Wird es nicht der Anleitung entsprechend
installiert, kann es schdliche Funkstrungen verursachen. Die
Verwendung dieses Gerts in einem Wohngebiet kann schdliche
Funkstrungen verursachen. In diesem Fall ist der Benutzer dafr
verantwortlich, die Strungen auf eigene Kosten zu beseitigen. Die RENNummer (Ringer Equivalence Number) fr das optionale interne Modem
des Gerts lautet 0.6. Der Anschluss am internen Modem des Gerts muss
ber ein Telefonkabel gem FCC Teil 68 erfolgen (nicht im Lieferumfang
enthalten). Das Gert kann nicht in Verbindung mit ffentlichen
Mnztelefonen oder Gemeinschaftsanschlssen eingesetzt werden.
Dieses digitale Gert der Klasse A erfllt die Anforderungen der
kanadischen Norm ICES-003 (Interference-Causing Equipment Standard).

PowerLogicTM Ethernet Gateway EGX300


Inhaltsverzeichnis

63230-319-216B3_DE
03/2013

Inhaltsverzeichnis
Einfhrung ................................................................................................. 1
Zustzliche Ressourcen .............................................................................. 1
Zugang zum EGX ber ein Netzwerk ....................................................... 2
Anmelden beim EGX ................................................................................... 2
EGX-Benutzeroberflche berblick ..................................................... 3
Setup .......................................................................................................... 5
Ethernet- und TCP/IP-Einstellungen ........................................................... 5
Erweiterte Ethernet-Einstellungen ......................................................... 6
Erkennung identischer IP-Adressen ...................................................... 8
Serielle Schnittstelle .................................................................................... 8
Erweiterte Einstellungen der seriellen Schnittstelle............................... 9
Verbindungen zu entfernten Gerten ........................................................ 10
EGX-Gerteliste ........................................................................................ 12
Anschluss von Gerten an ein EGX .................................................... 12
Gerteliste einrichten........................................................................... 13
Gerteerkennung................................................................................. 15
Gerteaufzeichnung .................................................................................. 17
Intervalldatenaufzeichnung.................................................................. 17
Intervallaufzeichnung einrichten .......................................................... 17
Aufzuzeichnende Gren.................................................................... 18
Gerteprotokollexport ................................................................................ 19
E-Mail-Export....................................................................................... 19
FTP-Export .......................................................................................... 21
HTTP-Export........................................................................................ 22
Datum und Uhrzeit .................................................................................... 23
Netzwerkzeitsynchronisation ............................................................... 24
SNMP-Parameter ...................................................................................... 25
Modbus-TCP/IP-Filter ............................................................................... 26
Unterlagenlinks ......................................................................................... 27
Benutzerkonten ......................................................................................... 28
Webseitenzugriff ....................................................................................... 29
Benutzerdefinierte Webseiten hinzufgen/entfernen........................... 30
Hinzufgen von Webseiten mit FTP .................................................... 30
Lschen von Webseiten mit FTP......................................................... 30
Webseiten zur Webschnittstelle hinzufgen oder aus ihr entfernen.... 31
Prferenzen ............................................................................................... 31
Anzeigbare Gertetypen ........................................................................... 32
Prfpfad ..................................................................................................... 33
Systemzugangspunkt ................................................................................ 35
berwachung .......................................................................................... 37
Echtzeitdaten ............................................................................................ 37
Einzelgerteseiten ............................................................................... 37
Grundmesswerteinstellungen .............................................................. 37
Analogmessgertbereich..................................................................... 38
bersichtsgerteseiten........................................................................ 38
Trendverfolgung .................................................................................. 39

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Inhaltsverzeichnis

63230-319-216B3_DE
03/2013

Gerteaufzeichnung .................................................................................. 40
Einzelgerteseiten ............................................................................... 41
Abrufen eines Datenprotokolls ............................................................ 42
Protokollformat .................................................................................... 42
Fehlercodes fr Datenprotokolle ......................................................... 43
Abrufen eines Intervalldatenprotokolls mit FTP................................... 43
Abrufen eines Intervalldatenprotokolls mit der
Schaltflche Datenpunkte ................................................................. 44
Abrufen eines Intervalldatenprotokolls mit Microsoft WebQuery......... 44
Abrufen eines Intervalldatenprotokolls ber E-Mail ............................. 44
Abrufen eines Intervalldatenprotokolls ber HTTP.............................. 44
bersichtsgerteseiten........................................................................ 45
Instrumententafeln .................................................................................... 46
Anzeigen einer Instrumententafel........................................................ 47
Abrufen von Instrumententafeldaten mit der
Schaltflche Datenpunkte ................................................................. 48
Speichern eines Instrumententafel-Links ............................................ 48
Speichern einer Instrumententafel als ein Bild .................................... 48
Systemzugangspunkt ................................................................................ 49
Unterlagen ............................................................................................... 50
Steuerung ................................................................................................ 50
Diagnose .................................................................................................. 51
Statistik ...................................................................................................... 51
Statistik auswerten .............................................................................. 52
Gerteregister lesen .................................................................................. 55
Kommunikationsprfung ........................................................................... 56
Automatische Kommunikationsprfung ............................................... 56
Manuelle Kommunikationsprfung ...................................................... 56
Wartung .................................................................................................... 57
Firmware .................................................................................................. 57
Firmwareversion feststellen ...................................................................... 57
Firmwareversion der ausfhrbaren Binrkomponente ........................ 58
Datentrgerabbildkomponente ............................................................ 58
Neue Firmware herunterladen .................................................................. 58
Firmware aktualisieren .............................................................................. 59
Anhang A Untersttzte Ethernet-Protokolle ...................................... 60
Hardware ................................................................................................... 60
Anhang B Untersttzte Gertetypen .................................................. 61

ii

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B3_DE
03/2013

PowerLogicTM Ethernet Gateway EGX300


Einfhrung

EINFHRUNG

Das EGX300 ist ein Ethernet-basiertes Gert, welches eine transparente


Schnittstelle zwischen Ethernet-Netzen und Feldgerten bereitstellt. Zu den
Feldgerten gehren Mess- und berwachungsgerte, Schutzrelais, SPSEinheiten, Auslsesysteme, Motorsteuerungen und andere Gerte, die mit
Modbus-, Jbus- oder PowerLogic-Protokollen kommunizieren.
Das EGX300 benutzt das Modbus-TCP/IP-Protokoll fr den Zugriff auf
Feldgertedaten in einem LAN- oder WAN-Netz. Diese Fhigkeit ermglicht
den Einsatz von berwachungssoftware fr den Zugriff auf Gertedaten fr
Datenerfassung, Trendverfolgung, Alarm- und Ereignisverwaltung, Analyse
und andere Funktionen.
Das EGX300 untersttzt die Echtzeitdatenanzeige fr viele gebruchliche
Gertetypen und stellt verschiedene gertespezifische Funktionen bereit.
Es stehen z. B. Onboard-Gerte- und Schaltkreisbersichtsseiten sowie
Onboard-Datenaufzeichnung und Echtzeit-Trendverfolgung zur Verfgung.
Abbildung 1: berblick ber das EGX300
Echtzeitansichten

Betrachten von
Gertedaten mit einem
einfachen Browser ohne
zustzliche Software

EchtzeitTrendkurven

EGX300-Webseiten

Steuerungsrcksetzungen

EGX300

Auslesen von Daten von


anderen PowerLogicGateways und ModbusTCP/IP-Schnittstellen, z. B.
ECC21- und PM8ECCGerte, in Webseiten.

ION6200

Zustzliche Ressourcen

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PM800

Micrologic

DatenprotokollTrendkurven

EGX100

Sepam

Rufen Sie die Website www.schneider-electric.com auf und geben Sie


EGX300 in das Suchfeld ein. Navigieren Sie zu EGX Documents &
Downloads (EGX-Unterlagen und Downloads).

PowerLogicTM Ethernet Gateway EGX300


Zugang zum EGX ber ein Netzwerk

ZUGANG ZUM EGX BER EIN


NETZWERK

63230-319-216B3_DE
03/2013

Nachdem Sie die EGX-Ethernet-Parameter eingerichtet haben (siehe EGXInstallationshandbuch), knnen Sie ber ein Ethernet-LAN mit jedem
gngigen Webbrowser auf das EGX zugreifen.

Anmelden beim EGX


Manahme

Ergebnis

1. Starten Sie den Webbrowser.

Einblendung des Webbrowsers.

2. Geben Sie in die Adressenleiste die


Adresse Ihres EGX ein (169.254.0.10 ist
die Werkeinstellung) und drcken Sie die
Eingabetaste.

Einblendung des Anmelde-Dialogfeldes.

3. Geben Sie in die Textfelder Ihren


Benutzernamen (Werkeinstellung:
Administrator) und das Kennwort
(Werkeinstellung: Gateway) ein und
klicken Sie auf OK.

Eingabe des Benutzernamens und des


Kennwortes und Einblendung der EGXStartseite.

HINWEIS: Beim Benutzernamen und


Kennwort wird zwischen Gro- und
Kleinschreibung unterschieden.
4. Klicken Sie auf den entsprechenden
Menpunkt in der Menleiste.

Einblendung des ausgewhlten Menpunkts.

Abbildung 2: EGX-Startseite

Menleiste

Wir empfehlen, dass Sie sich immer dann abmelden, wenn Sie keinen
Zugang zum EGX bentigen.
Klicken Sie auf Logout oder schlieen Sie einfach Ihren Browser, um sich
von der EGX-Sitzung abzumelden.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


EGX-Benutzeroberflche berblick

63230-319-216B3_DE
03/2013

EGX-BENUTZEROBERFLCHE
BERBLICK

Die EGX-Benutzeroberflche besteht aus mehreren Webseiten, die fr die


Gerteberwachung und -steuerung sowie fr die EGX-Diagnose und
-Einrichtung benutzt werden. Tabelle 1 enthlt eine Beschreibung jeder
Webseite.
Tabelle 1: EGX-Seiten
EGX-Webseite

Beschreibung

Siehe
Seite

Setup
Ethernet & TCP/IP

Konfiguration der Ethernet- und TCP/IP-Einstellungen.

Serielle Schnittstelle

Konfiguration der Parameter fr die serielle


Kommunikation.

Verbindungen zu entfernten Konfiguration der Modbus-TCP/IP-Verbindungen zu


Gerten
entfernten Gerten.

10

Gerteliste

Konfiguration, Erkennung oder berprfung von lokalen


seriellen Gerten in der Gertekette. Entfernte Gerte
knnen nur konfiguriert oder berprft werden.

12

Gerteaufzeichnung

Konfiguration der Parameter fr die


Gerteaufzeichnung.

17

Gerteprotokollexport

Konfiguration der Optionen fr den


Gerteprotokollexport.

19

Datum und Uhrzeit1

Einstellung des Datums und der Uhrzeit entweder


manuell oder mit SNTP-Parametern.

23

SNMP-Parameter1

Konfiguration des Simple Network Management


Protocol (SNMP).

25

Modbus-TCP/IP-Filter1

Festlegung der IP-Adressen, die auf das EGX ber


Modbus-TCP/IP zugreifen knnen.

26

Unterlagenlinks

Konfiguration der Datei- und URL-Links der Unterlagen.

27

Benutzerkonten1

Erstellung und Bearbeitung von Gruppen und


Benutzern.

28

Webseitenzugriff1

Konfiguration der Webseiten-Zugriffsrechte fr jede


Benutzergruppe.

29

Prferenzen

Konfiguration der EGX-Prferenzen.

31

Anzeigbare Gertetypen

Konfiguration der untersttzten Gertetypen, die auf der


Webseite EGX-Gerteliste anzeigbar sind.

32

Prfpfad1

Konfiguration der Weiterleitung von Systemmeldungen


durch das EGX: ber das Wartungsprotokoll, per E-Mail
oder ber den entfernten Syslog-Server.

33

Systemzugangspunkt1

Aktivierung und Konfiguration der Gruppen-IP-Adresse


fr mehrere EGX300-Gerte, damit sie sich gegenseitig
erkennen und ihre Daten lesen knnen.

35

Echtzeitdaten

Die Tabellenansicht Einzelgerteseiten zeigt


Grundmesswerte der ausgewhlten Gerte an. Die
Tabellenansicht bersichtsgerteseiten zeigt
bersichten ber ein oder mehrere ausgewhlte Gerte
an. Die Ansicht Trendverfolgungsseite zeigt grafisch
und tabellarisch die Echtzeit-Trendverfolgung von
Gren an, die mehrere Gerte gemeinsam haben.

37

Gerteaufzeichnung

Die Einzelgerteseiten zeigen grafische und


tabellarische Trendaufzeichnungen in
benutzerdefinierbaren Gren fr ausgewhlte Gerte
an. Die bersichtsgerteseiten zeigen grafische
Trendaufzeichnungen mehrerer Gerte mit einer
gemeinsamen Gre an.

40

Instrumententafeln

Die Instrumententafeln enthalten grafische und


tabellarische Darstellungen von zeitlich summierten
Energieverbrauchsdaten aller Gerte, fr die die
Datenaufzeichnung aktiviert ist.

46

Systemzugangspunkt

Die Seite Systemzugangspunkt zeigt EGX300-Gerte


und andere Systemgerte im Netzwerk an, auf die vom
jeweiligen EGX300 zugegriffen werden kann. Jede Zeile
ist ein Hyperlink zur EGX300-Anmeldeseite.

49

berwachung

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Nur fr den Administrator zugnglich

PowerLogicTM Ethernet Gateway EGX300


EGX-Benutzeroberflche berblick

63230-319-216B3_DE
03/2013

Tabelle 1: EGX-Seiten
Beschreibung

Siehe
Seite

Zugriff auf relevante EGX-Unterlagen und vom Benutzer


konfigurierte Unterlagenlinks.

50

Sorgt fr die Ausfhrung von Rckstellungen, die fr das


Gert festgelegt sind, und zeigt das Datum und die
Uhrzeit der Durchfhrung jeder Rcksetzfunktion an.
Die Datums- und Uhrzeit-Rckstellungen werden nur
angezeigt, wenn das Gert diese Funktionen untersttzt.

50

Statistik

Anzeige von Diagnosedaten zur Fehlersuche und behebung bei Netzwerkproblemen. Diese Seite enthlt
ebenfalls spezifische Informationen ber Ihr EGX,
einschlielich Seriennummer, Herstellungsdatum und
MAC-Adresse.

51

Gerteregister lesen

Damit knnen Benutzer Registerdaten von lokalen und


entfernten Gerten, die an das EGX angeschlossen
sind, lesen.

55

Kommunikationsprfung

berprfung der strungsfreien Kommunikation mit allen


im EGX konfigurierten Gerten.

56

Anzeige des Datums, der Uhrzeit und des Benutzers,


der zuletzt Wartungsarbeiten am Gert durchgefhrt hat,
sowie der Eintrge ber die durchgefhrte Wartung.

57

EGX-Webseite
Unterlagen
Unterlagen
Steuerung
Resets

Diagnose

Wartung
Wartungsprotokoll

Nur fr den Administrator zugnglich

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

SETUP

Fr den Zugang zu den Links der Setup-Webseiten klicken Sie auf Setup in
der EGX-Menleiste.

Ethernet- und TCP/IP-Einstellungen


Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf Ethernet & Einblendung der Ethernet & TCP/IP-Seite.
TCP/IP.
2. Whlen Sie Ihr Rahmenformat und das
bertragungsmedium aus. Falls Sie diese
Informationen nicht kennen, wenden Sie
sich an Ihren Netzwerkadministrator.

Auswahl von Rahmenformat und


bertragungsmedium.

3. Geben Sie Ihre IP-Adresse, die


Subnetzmaske und die dem EGX durch
Ihren Netzwerkadministrator zugewiesene
Standard-Gateway-Adresse ein.

Eingabe der Ethernet-Parameter fr das EGX.


HINWEIS: Wenn Sie eine IP-Adresse
eingeben, die bereits in Verwendung ist,
werden Sie zur Auswahl einer anderen IPAdresse aufgefordert. Siehe Erkennung
identischer IP-Adressen auf Seite 8.

4. Klicken Sie auf bernehmen.

Aktualisierung der Ethernet- und TCP/IPEinstellungen fr das EGX.

* Tabelle 2 enthlt eine Liste der Optionen.

Abbildung 3: Ethernet & TCP/IP-Seite

Tabelle 2: EGX-Ethernet- und TCP/IP-Einstellungen


Option

Beschreibung

Einstellung

Rahmenformat Auswahl des Formats, in dem Daten ber eine Ethernet II, 802.3 SNAP
Ethernet-Verbindung gesendet werden.
Werkeinstellung: Ethernet II
bertragungs- Festlegung der physikalischen
medium
Ethernet-Verbindung oder
des bertragungsmediums.

10T/100Tx Auto
10BaseT-HD
10BaseT-FD
100BaseTX-HD
100BaseTX-FD

Werkeinstellung:
10T/100Tx Auto
IP-Adresse
automatisch
erhalten

Fr den automatischen Abruf einer IP-Adresse Aktiviert oder Deaktiviert


von einem BootP-Server.
Werkeinstellung: Deaktiviert
HINWEIS: Erfordert die Untersttzung der
Netzwerkadministration.

IP-Adresse

Eingabe der statischen IP-Adresse des EGX.

Subnetzmaske Eingabe der Ethernet-IP-Subnetzmaskenadresse Ihres Netzwerks.


StandardGateway

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Werkeinstellung:
169.254.0.10
Werkeinstellung: 255.255.0.0

Eingabe der Gateway-IP-Adresse (Router) fr Werkeinstellung: 0.0.0.0


WAN-Kommunikation.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Erweiterte Ethernet-Einstellungen

HINWEIS
BEEINTRCHTIGTE LEISTUNGSFHIGKEIT DES NETZWERKS
Die erweiterten Ethernet-Einstellungen des EGX drfen nur von
qualifiziertem Personal vorgenommen werden. Diese nderungen drfen
grundstzlich erst vorgenommen werden, wenn die Informationen ber
die erweiterten Einstellungen vollstndig gelesen und verstanden wurden.
Durch Nichtbeachtung dieser Anweisungen kann die
Leistungsfhigkeit des Netzwerks beeintrchtigen.

Manahme

Ergebnis

1. Klicken Sie auf der Seite Ethernet &


TCP/IP auf Erweitert.

Einblendung der Seite Erweiterte EthernetEinstellungen.

2. Konfigurieren Sie die erweiterten Ethernet- Einrichtung der erweiterten EthernetEinstellungen (Tabelle 3 auf Seite 7 enthlt Einstellungen.
die verfgbaren Optionen). Klicken Sie auf
Standardwerte, um die Standardwerte fr
alle Optionen auszuwhlen.
3. Klicken Sie auf bernehmen.
HINWEIS: Beim bernehmen von
nderungen auf die Seite Erweiterte
Ethernet-Einstellungen werden diese
nderungen nicht auf der Seite Ethernet &
TCP/IP gespeichert.

Aktualisierung der Ethernet- und TCP/IPEinstellungen fr das EGX.

4. Klicken Sie auf OK, um die nderungen zu Das EGX startet neu.
besttigen und das EGX zurckzusetzen.

Abbildung 4: Seite Erweiterte Ethernet-Einstellungen

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Tabelle 3: Erweiterte Ethernet-Einstellungen des EGX


Option

Beschreibung

Einstellung

Gltigkeitsdauer

Legt die Anzahl der Router fest, die ein TCPPaket durchlaufen kann.

1 bis 255 Hops


Werkeinstellung:
60 Hops

TCP Keep-Alive

0 bis 65.000 Sekunden


Ein Timer, der feststellt, wenn ein ber eine
Werkeinstellung:
unbelegte Verbindung angeschlossenes Gert
30 Sekunden
aufgrund von Ereignissen wie Neustart oder
Ausschalten nicht mehr verfgbar ist. Der Wert 0
deaktiviert diese Einstellung.

BootPZeitberschreitung

Legt fest, wie lange das EGX auf die Zuweisung


seiner IP-Adresse durch einen BootP-Server
wartet. (Wenn nach Ablauf der Zeit keine IPAdresse zugewiesen wurde, wird die
voreingestellte IP-Adresse verwendet.)

0 bis 60 Sekunden
Werkeinstellung:
15 Sekunden

ARP-CacheTimeout

Legt fest, wie lange Eintrge in der ARP-Tabelle


(Address Resolution Protocol) verbleiben.

0 bis 65.000 Minuten


Werkeinstellung:
15 Minuten

FTP-Server

Steuert die Aktivierung der Initialisierung des


FTP-Servers beim Start.

Deaktiviert oder
Aktiviert
Werkeinstellung:
Aktiviert

FTP-Verbindungsleerlaufzeit

Ein Timer, der eine FTP-Verbindung nach einer


festgelegten Leerlaufzeit schliet.

30 bis 900 Sekunden


Werkeinstellung:
120 Sekunden

HTTP-Verbindungs- Ein Timer, der eine HTTP-Verbindung nach einer 0 bis 65.000 Sekunden
leerlaufzeit
festgelegten Leerlaufzeit schliet.
Werkeinstellung:
4 Sekunden
HTTP-Port-Nr.

Der fr HTTP-Meldungen verwendete TCP-Port.


Die folgenden Portnummern sind fr andere
Netzwerkprotokolle reserviert und knnen nicht
verwendet werden: 20 und 21 (FTP) und 502
(Modbus TCP/IP).

0 bis 65.000
Werkeinstellung: 80
0 HTTP-Port
deaktiviert

HTTPS-Port-Nr.

Der fr HTTPS-Meldungen verwendete TCP-Port.


Das EGX wird mit einem selbstsignierten
Zertifikat ausgeliefert. Damit aus dem EGX ein
vertrauenswrdiger Server wird, mssen Sie ein
Zertifikat von einer Zertifizierungsstelle erwerben
(z. B. VeriSign Authentication Services).

1 bis 65.000
Werkeinstellung: 443
0 HTTPS-Port
deaktiviert

Um ein digitales Zertifikat hinzuzufgen bzw. zu


installieren, rufen Sie manuell mit der URL
http://x.x.x.x./update_certs_shtml (wobei x.x.x.x
fr die IP-Adresse des EGX steht) die
Zertifikataktualisierungsseite auf.
Max. Anzahl der
HTTP-Keep-AliveVersuche

Legt die maximale Anzahl der HTTP-Keep-Alive- 0 bis 65.000


Versuche fest.
Werkeinstellung: 100

Modbus-TCP/IPSerververbindungen

Legt die verfgbare Anzahl an Modbus-TCP/IPServer-Verbindungen fest.

16 bis 64
Werkeinstellung: 32

Modbus-Broadcast

Legt fest, wie Modbus-TCP/IP-Meldungen mit


Unit-ID = 0 im seriellen Subnetzwerk behandelt
werden. Deaktiviert = alle Meldungen werden
ignoriert. Aktiviert = alle Meldungen werden als
Broadcasts an serielle Schnittstellen behandelt,
fr die keine Antwort erwartet wird. Aktiviert mit
Rckmeldung = alle Meldungen werden als
normale Meldungen an serielle Schnittstellen
behandelt, fr die eine Antwort erwartet wird.

Deaktiviert, Aktiviert
oder Aktiviert mit
Rckmeldung
Werkeinstellung:
Deaktiviert

Modbus TCPProxyserver

Diese Einstellung legt fest, ob Modbus-TCP/IPMeldungen von entfernten Clients an entfernte


Modbus-TCP/IP-Gerte, die im EGX definiert
sind, weitergeleitet werden.

Deaktiviert oder
Aktiviert
Werkeinstellung:
Aktiviert

Timeout ModbusTCP/IP-Client

0,1 bis 10
Die Zeit, whrend der das EGX auf die Antwort
eines entfernten Modbus-TCP/IP-Gerts auf eine Werkeinstellung:
5 Sekunden
durch das EGX eingeleitete Modbus-TCP/IPAnforderung wartet.

Timeout ModbusTCP/IP-ClientVerbindung

1 bis 10
Die Zeit, whrend der das EGX auf die Antwort
eines entfernten Modbus-TCP/IP-Gerts auf eine Werkeinstellung:
2 Sekunden
durch das EGX eingeleitete Modbus-TCP/IPVerbindungsanforderung wartet.

Modbus-TCP/IPEin Timer, der eine Modbus-TCP/IP-Verbindung 0 bis 32.767 Sekunden


Server-Verbindung nach einer festgelegten Leerlaufzeit schliet. Der Werkeinstellung: 0
Leerlaufzeit
Wert 0 deaktiviert diese Einstellung.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

Erkennung identischer IP-Adressen

63230-319-216B3_DE
03/2013

Whrend das EGX an Ihr Netzwerk angeschlossen ist, verffentlicht es


seine IP-Adresse. Zur Vermeidung von Konflikten aufgrund doppelt
vergebener IP-Adressen wird vom EGX das ARP-Protokoll (Address
Resolution Protocol) benutzt. Damit wird festgestellt, ob ein anderes Gert
in Ihrem Netzwerk die gleiche IP-Adresse verwendet. In der nachstehenden
Tabelle 4 wird erlutert, wie das EGX mit einer doppelt vergebenen IPAdresse umgeht, sobald es sie erkannt hat.
Tabelle 4: Szenarien der Erkennung doppelter IP-Adressen
Szenario
Boot-Prozess/Wiederherstellung der
Spannungsversorgung
Ethernet-Verbindung
erkannt

Doppelte IP-Adresse erkannt

Spannungsversorgungs/Status-LED

Das EGX kehrt zur voreingestellten Muster aus vier Blinkzeichen


IP-Adresse, Subnetzmaske und
und einer Pause
Gateway-Adresse zurck. ARPAnfragen werden alle 15 Sekunden
gesendet, bis die IP-Adresse
verfgbar ist. Sobald die IPAdresse verfgbar ist, wird sie vom
EGX verwendet.

Manuelle
Adressennderung

Das EGX behlt seine vorherige


IP-Adresse und zeigt eine Meldung
an, die darauf hinweist, dass die IPAdresse bereits von einem anderen
Gert verwendet wird.

Erhalt einer ARP-Anfrage

Rckkehr zur im EGX


Muster aus vier Blinkzeichen
voreingestellten IP-Adresse,
und einer Pause
Subnetzmaske und GatewayAdresse, wenn ein
angeschlossenes Gert vier ARPAnfragen bezglich der IP-Adresse
des EGX sendet. Das EGX sendet
alle 15 Sekunden ARP-Anfragen,
bis die IP-Adresse wieder
verfgbar ist. Sobald die IPAdresse verfgbar ist, wird sie vom
EGX verwendet.

Serielle Schnittstelle
Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf Serielle


Schnittstelle.

Einblendung der Seite Serielle Schnittstelle.

2. Whlen Sie die physische Schnittstelle,


Auswahl der Optionen fr die serielle
den bertragungsmodus, die Baudrate, die Schnittstelle.
Paritt und die Antwort-Zeitberschreitung
aus (siehe Tabelle 5 auf Seite 9).
3. Klicken Sie auf bernehmen.

Aktualisierung der Einstellungen fr die serielle


EGX-Schnittstelle.

Abbildung 5: Seite Serielle Schnittstelle

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Tabelle 5: Einstellungen der seriellen Schnittstelle


Option

Beschreibung

Einstellung

Physische
Schnittstelle

Auswahl der physischen Verdrahtung der


seriellen EGX-Schnittstelle.

RS485 4-Leiter, RS485


2-Leiter oder RS232
Werkeinstellung:
RS485 2-Leiter

bertragungsmodus

Hier wird festgelegt, wie Daten ber die


serielle Verbindung bertragen werden.

Automatisch
Modbus ASCII

HINWEIS: Im Automatikmodus
kann das Gert mit Modbus
RTU-, Jbus- und PowerLogic
(SY/MAX)-Slave-Gerten in
der gleichen Gertekette
kommunizieren.
Baudrate

Hier wird die Geschwindigkeit der


Datenbertragung ber die serielle
Verbindung festgelegt.

2400, 4800, 9600, 19200,


38400, 56000* oder 57600*
Werkeinstellung: 19200

Paritt

Hier wird die Art der Paritt festgelegt, die Gerade, Ungerade oder Keine
fr die berprfung der Richtigkeit der
Werkeinstellung: Gerade
Daten mit einem Paritts-Bit erforderlich ist.

AntwortDieser Parameter legt fest, wie lange das


Zeitberschreitung EGX auf den Empfang einer Antwort von
einem seriellen Gert wartet.

0,1 bis 10 Sekunden


Werkeinstellung: 3 Sekunden

* Nur verfgbar, wenn die physische Schnittstelle bzw. der bertragungsmodus auf
RS232/Modbus ASCII eingestellt ist.

Erweiterte Einstellungen der seriellen


Schnittstelle

HINWEIS
BEEINTRCHTIGTE LEISTUNGSFHIGKEIT DES NETZWERKS
Die erweiterten Einstellungen der seriellen Schnittstelle des EGX drfen
nur von qualifiziertem Personal vorgenommen werden. Diese
nderungen drfen grundstzlich erst vorgenommen werden, wenn die
Informationen ber die erweiterten Einstellungen der seriellen
Schnittstelle vollstndig gelesen und verstanden wurden.
Durch Nichtbeachtung dieser Anweisungen kann die
Leistungsfhigkeit der seriellen Kommunikation beeintrchtigen.
Manahme
1. Klicken Sie auf der Seite Serielle Schnittstelle auf
Erweitert.

Ergebnis
Einblendung der Seite Erweiterte
Einstellungen der seriellen
Schnittstelle.

2. Konfigurieren Sie die erweiterten Einstellungen der


Einrichtung der erweiterten
seriellen Schnittstelle (Tabelle 6 auf Seite 10 enthlt die Einstellungen der seriellen
verfgbaren Optionen). Klicken Sie auf Standardwerte, Schnittstelle.
um die Standardwerte fr alle Optionen auszuwhlen.
3. Klicken Sie auf bernehmen.

Aktualisierung der erweiterten


Einstellungen der seriellen
HINWEIS: Beim bernehmen von nderungen auf der
Schnittstelle fr das EGX.
Seite Erweiterte Einstellungen der seriellen
Schnittstelle werden diese nderungen nicht auf der
Seite Serielle Schnittstelle gespeichert.

Abbildung 6: Seite Erweiterte Einstellungen der seriellen Schnittstelle

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Tabelle 6: Erweiterte Einstellungen der seriellen Schnittstelle


Option

Beschreibung

Verzgerung
Hier wird das Mindeststilleintervall
zwischen Rahmen zwischen dem Ende einer empfangenen
Antwort und dem Beginn einer neuen
Anfrage auf der seriellen Leitung
festgelegt.

Verbindungen zu entfernten Gerten

Verlngerung des
Stilleintervalls

Erlaubt die Verlngerung des


0 bis 15 Zeichen
Stilleintervalls zur Kennzeichnung des
Werkeinstellung: 6 Zeichen
Endes eines Modbus RTU-Pakets ber die
standardmig festgelegten 3,5 Zeichen
hinaus.

Ausnahmefehlercode ModbusTCP/IP-Timeout

Hier wird der Ausnahmefehlercode


0x0A oder 0x0B
festgelegt, der zurckgesendet wird, wenn Werkeinstellung: 0x0B
ein an das EGX angeschlossenes serielles
Gert nicht vor der Zeitberschreitung der
seriellen Schnittstelle antwortet. Modbus
TCP/IP verwendet 0x0B. Allerdings wurde
bei einigen lteren Software-Suites 0x0A
verwendet.

Das EGX kann Verbindungen fr bis zu 16 eindeutige, benutzerdefinierte


entfernte Modbus-TCP/IP-Gerte herstellen. Verbindungen knnen manuell
eingegeben oder aus einer Tabelle mit vom Systemzugangspunkt
erkannten Verbindungen ausgewhlt werden (siehe Abbildung 7 auf
Seite 11). Diese Verbindungen werden auf der Seite zum Einrichten der
Gerteliste fr die Konfiguration entfernter Gerte zur Verfgung gestellt.
Manahme

10

Einstellung
0 bis 100 Millisekunden
Werkeinstellung:
50 Millisekunden

Ergebnis

1. Klicken Sie im Setup-Men auf


Verbindungen zu entfernten Gerten.

Anzeige der Seite Verbindungen zu entfernten


Gerten.

2. Manuelles Hinzufgen einer Verbindung:


Geben Sie die IP-Adressen fr die
entfernten Gerte ein, mit denen Sie eine
Verbindung herstellen mchten.

Eingabe der IP-Adressen der entfernten


Gerte.

3. Hinzufgen einer vom


Systemzugangspunkt erkannten
Verbindung: Klicken Sie auf Hinzufgen
(rechts neben der gewnschten
Verbindung in der Tabelle der erkannten
Verbindungen).

Eingabe der IP-Adresse der ausgewhlten,


vom Systemzugangspunkt erkannten
Verbindung.

4. Klicken Sie auf bernehmen.

Aktualisierung der EGX-Einstellungen fr


Verbindungen zu entfernten Gerten.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B3_DE
03/2013

PowerLogicTM Ethernet Gateway EGX300


Setup

Abbildung 7: Verbindungen zu entfernten Gerten

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

11

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

EGX-Gerteliste

Bedenken Sie vor Beginn, dass Sie die seriellen Slave-Adressen 1 bzw. 16
nicht im automatischen bertragungsmodus in einer Gertekette mit
gemischten Protokollen benutzen drfen (beispielsweise bei einer
Gertekette mit Gerten, von denen einige das PowerLogic-Protokoll und
andere ein Modbus RTU/Jbus-Protokoll verwenden).

Anschluss von Gerten an ein EGX

Abbildung 8 und Abbildung 9 zeigen, wie Gerte an das EGX


angeschlossen werden knnen. Um diese Gerte zur Gerteliste
hinzuzufgen, fhren Sie die unter Gerteliste einrichten auf Seite 13
beschriebenen Schritte aus.
Abbildung 8: Topologie nur serielle Slave-Gerte

EthernetVerbindung

EGX300-Webseiten

EGX

RS485-Verbindung

Serielle Slave-Gerte

Abbildung 9: Topologie serielle Slave- und entfernte Gerte


EthernetVerbindung

EGX300-Webseiten
IP-Adresse des
EGX100:
169.254.0.28

Es sind bis zu 16 IPFernverbindungen mglich.

IP-Adresse des
EGX300:
169.254.0.75

RS485Verbindung

Entfernte Slave-Gerte

12

RS485-Verbindung

Serielle Slave-Gerte

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Gerteliste einrichten
Manahme
1. Klicken Sie im Setup-Men auf
Gerteliste.

Ergebnis
Einblendung der Seite Gerteliste.
(Abbildung 10 zeigt lokale Verbindungen und
Abbildung 11 zeigt entfernte Verbindungen
sofern verfgbar.)

2. Fr die Suche nach lokal angeschlossenen Einblendung der Seite Gerteerkennung fr


die Erkennung aller lokal angeschlossenen
Gerten knnen Sie Erkennung
verwenden (siehe Gerteerkennung auf Gerte.
Seite 15). Wenn die Konfiguration
entfernter Gerte erforderlich ist, fahren
Sie mit Schritt 3 fort.
3. Beachten Sie Abbildung 11 auf Seite 14
und whlen Sie die Anzahl der
anzeigbaren Gerte aus (1 bis 64).

Auswahl der Anzahl sichtbarer Standorte, die


zur Definition der an das EGX angeschlossenen Gerte benutzt werden knnen.

4. Whlen Sie die Verbindung aus der


Dropdown-Liste aus.*

Auswahl der Verbindung.

5. Whlen Sie den Gertetyp aus der


Dropdown-Liste aus.*

Auswahl des Gertetyps.

6. Geben Sie in das Textfeld


Gertebezeichnung den Namen des
Gerts ein.

Eingabe der Gertebezeichnung.

7. Geben Sie in das Textfeld Lokale ID die


Eingabe der lokalen Adresse des Gerts.
Adresse des seriellen Slave-Gertes ein,
wenn es am seriellen Port angeschlossen
ist, bzw. die Adresse, die Sie fr den
Zugriff auf ein entferntes Gert verwenden
mchten.*
8. Geben Sie in das Textfeld Fern-ID die
Adresse des entfernten Gerts ein.*

Eingabe der Adresse des entfernten Gerts.

9. Wiederholen Sie die Schritte 4 bis 8, bis


alle Gerte eingegeben sind.

Eingabe aller angeschlossenen Gerte.

10. Klicken Sie auf bernehmen.

Aktualisierung der Einstellungen in der


Gerteliste.

* Dieser Konfigurationsparameter kann nur verndert werden, wenn die Datenaufzeichnung fr


das zu aktualisierende Gert deaktiviert ist. Siehe Gerteaufzeichnung auf Seite 17.

Abbildung 10: Seite Gerteliste

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

13

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Abbildung 11: Seite Gerteliste mit untersttzten Fernverbindungen

Tabelle 7: Gertelisteneinstellungen
Option

Beschreibung

Auswahl der Anzahl anzuzeigender Gerte. 1 bis 64


Werkeinstellung: 8

Verbindung

Auswahl des Verbindungsstandortes.

Serielle Schnittstelle oder IPAdresse


Werkeinstellung:
Serielle Schnittstelle

Gertetyp

Auswahl des Gertetyps, der in der Liste


erscheinen soll.

Bereich untersttzter Gerte

Gertebezeichnung Ermglicht die Bezeichnung einzelner


Gerte.

14

Einstellung

Anzahl
anzuzeigende
Gerte

Lokale ID

Sie mssen die Lokale ID festlegen.

Fern-ID

Sie mssen die Fern-ID festlegen.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Gerteerkennung

Mit der Option Gerteerkennung kann das EGX an der seriellen


Schnittstelle angeschlossene Modbus-Gerte erkennen, die nicht in der
Gerteliste enthalten sind. Gerte, die vorher in die Gerteliste eingetragen
wurden, werden unabhngig vom eingestellten Erkennungsbereich berprft.
Erkennung
Zu Beginn der Gerteerkennung fragt das EGX den lokalen seriellen Port
mit einem benutzerdefinierten Adressenbereich ab (siehe Abbildung 12 auf
Seite 16). Fr die Erkennung an der seriellen Schnittstelle wird je nach
deren aktueller Konfiguration das Modbus ASCII- oder das RTU-Protokoll
benutzt. Wenn das Gert auf die Anfrage antwortet, wird die lokale ID auf
die aktuelle Erkennungsadresse gesetzt und dem Gert wird ein
voreingestellter Gertename zugewiesen. Das EGX versucht dann, den
Gertetyp zu erkennen. Wenn das EGX den Typ des erkannten Gerts
identifiziert, wird die Bezeichnung des erkannten Gertetyps in das Feld
Gertetyp eingetragen. Kann das EGX den Gertetyp nicht identifizieren,
wird das Feld Gertetyp auf die Werkeinstellung Modbus gesetzt. Ein
Statusfeld zeigt den Erkennungsstatus an.
berprfung
Whrend des Erkennungsvorgangs werden alle vorher definierten Eintrge
in der Gerteliste fr alle Verbindungen (serielle und Fernverbindungen
innerhalb und auerhalb des Erkennungsbereichs zwischen Start- und
Endadresse) berprft. Das berprfungsprotokoll der seriellen Verbindung
wird durch die aktuelle Konfiguration des Gerts in der Gerteliste
bestimmt. Fr die berprfung entfernter Gerte wird das Modbus-TCP/IPProtokoll benutzt. Das EGX zeigt die lokale ID, die gespeicherte
Gertebezeichnung sowie den gespeicherten Gertetyp aus der Gerteliste
an und fragt danach das Gert ab. Der durch die Abfrage erkannte
Gertetyp wird angezeigt und danach mit der vorangegangenen Definition
verglichen. Der Status zeigt dann an, ob eine Abweichung erkannt wurde
oder ob die vorher definierte Konfiguration gltig ist.
HINWEIS: Sie knnen die Gertebezeichnung und den Gertetyp
bearbeiten und einzeln auswhlen, welche Gerte in der Gerteliste
gespeichert werden sollen. Wenn allerdings die Aufzeichnung fr ein Gert
aktiviert ist, knnen Sie nur die Bezeichnung ndern.
Manahme
1. Klicken Sie im Setup-Men auf Gerteliste.

Ergebnis
Einblendung der Seite Gerteliste.

2. Klicken Sie fr die Erkennung lokal angeschlossener Einblendung der Seite


Gerte auf Erkennung.
Gerteerkennung.
3. Geben Sie eine Startadresse und eine Endadresse Eingabe des Adressenbereichs fr
ein.
die Erkennung.
HINWEIS: Gerte, die zuvor in die
Gerteliste mit Adressen (lokale IDs)
auerhalb des Erkennungsbereichs
eingetragen wurden, werden
berprft.
4. Klicken Sie auf Erkennung starten (um den Prozess Beginn der Erkennung aller
anzuhalten, klicken Sie auf Erkennung anhalten).
angeschlossenen und definierten
Gerte.
HINWEIS: Mit der Erkennungsfunktion werden nur
lokale, serielle Modbus-Gerte, die an das EGX
angeschlossen sind, gefunden. Entfernte Gerte
mssen manuell hinzugefgt werden. Siehe
Verbindungen zu entfernten Gerten auf Seite 10.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

5. Geben Sie eine neue Gertebezeichnung in das


Textfeld Name ein.

Damit wird das Gert umbenannt.

6. Aktivieren Sie das Kontrollkstchen Speichern


neben dem Gert, das Sie in der Gerteliste
speichern mchten.

Auswahl der zu speichernden oder zu


entfernenden Gerteeintrge bzw.
Aufheben dieser Auswahl.

7. Klicken Sie auf der Seite Gerteerkennung auf


bernehmen.

Damit wird die Gertekonfiguration


aller fr die Speicherung markierten
Gerte in der Gerteliste gespeichert.

15

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Abbildung 12: Gerteerkennung

Tabelle 8: Optionen der Gerteerkennung


Option

16

Beschreibung

Einstellung

Start-/Endadresse Legt den Modbus-Adressenbereich fest,


der fr die Erkennung von Gerten am
seriellen Port des EGX benutzt wird.

1 bis 247
Werkeinstellung: Start: 1
Ende: 10

Speichern

Damit knnen Sie das ausgewhlte Gert


in der Gerteliste speichern.

Aktiviert oder Deaktiviert


Werkeinstellung: Aktiviert

Verbindung

Anzeige der Verbindung, auf der das Gert Serielle Schnittstelle oder IPerkannt oder berprft wurde.
Adresse (fr die berprfung
entfernter Gerte).

Definiert

Anzeige des Gertetyps, der fr das


entsprechende Gert festgelegt wurde.

Zugewiesen

Damit knnen Sie den Gertetyp aus einer


Dropdown-Liste zuweisen.

Name

Hier knnen Sie einen benutzerdefinierten


Namen fr das Gert eingeben.

Lokale ID

Anzeige der lokalen ID.

Fern-ID

Anzeige der Fern-ID.

Status

Anzeige des Erkennungs- oder


berprfungsstatus.

Gltig, Unbekannt,
Fehlgeschlagen, Gefunden,
Erkennung oder Versuch

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Gerteaufzeichnung

Die Aufzeichnung ist fr jeden durch das EGX untersttzten Gertetyp


verfgbar. Das EGX kann Daten aufzeichnen, die von angeschlossenen
lokalen und entfernten Gerten in vordefinierten Intervallen (5, 10, 15, 20, 30
und 60 Minuten) empfangen werden. Nachfolgend wird erlutert, wie das EGX
Daten aufzeichnet und wie die Aufzeichnung fr ein Gert eingerichtet wird.

Intervalldatenaufzeichnung

Viele Gerte in einem Leistungsberwachungssystem knnen keine Daten


in einem nichtflchtigen Speicher ablegen. Das EGX300 bietet
Datenaufzeichnung fr bis zu 64 seriell und entfernt angeschlossenen
Gerten in vordefinierten Intervallen. Das EGX legt die aufgezeichneten
Daten in nichtflchtigen FIFO-Dateien (First In First Out) ab.
Die Aufzeichnungskapazitt jeder Datenprotokolldatei ist unterschiedlich
und hngt vom ausgewhlten Aufzeichnungsintervall ab. Die
Aufzeichnungskapazitt jeder Datenprotokolldatei kann durch Division der
maximal mglichen Anzahl von Aufzeichnungsintervallen, die eine
Datenprotokolldatei enthalten kann (171.072), durch das Produkt aus der
Anzahl der aufgezeichneten Gren und den pro Tag aufgezeichneten
Intervallen berechnet werden.
Protokolldateikapazitt = Intervalle (max.) / (Gren pro Intervall * pro Tag
aufgezeichnete Intervalle)

Beispiel: Die Aufzeichnungskapazitt fr ein Gertedatenprotokoll mit


Aufzeichnung von drei Gren alle 10 Minuten wrde wie folgt bestimmt:
Pro Tag aufgezeichnete Intervalle = Minuten pro Tag / Aufzeichnungsintervalle (in
Minuten)
= 1440 / 10
= 144 Intervalle
Protokolldateikapazitt = maximal mgliche Intervalle / (aufgezeichnete Gren pro
Intervall * pro Tag aufgezeichnete Intervalle)
= 171072 / (3 * 144)
= 396 Tage

Die Aufzeichnungskapazitt wird dynamisch berechnet und auf der


Grenauswahlseite (fr Beispiele siehe Tabelle 9) angezeigt.
Tabelle 9: Beispiele fr Aufzeichnungsintervalle
Anzahl der
Gren

Aufzeichnungskapazitt (in Tagen) fr bestimmte


Aufzeichnungsintervalle
5-Minuten-Intervall 10-Minuten-Intervall 15-Minuten-Intervall

Intervallaufzeichnung einrichten

594

1188

1782

297

594

891

198

396

594

148

297

445

118

237

356

99

198

297

Fr jedes Gert in der Gerteliste kann die Aufzeichnung separat aktiviert


werden. Die aufzuzeichnenden Gren sind fr jedes Gert eindeutig.
Informationen ber die Anzeige der Intervalldatenprotokolle finden Sie unter
Gerteaufzeichnung auf Seite 40.
HINWEIS: Fr die Aktivierung der Gerteaufzeichnung muss im DropdownFenster Aufzeichnungsintervall ein Zeitwert ausgewhlt werden. Es wird
empfohlen, die Aufzeichnungsfunktion whrend der Konfiguration eines
Gerts zu deaktivieren. Beachten Sie dazu Abbildung 13 auf Seite 18 und
deaktivieren Sie das Kontrollkstchen Protokollierung fr das
ausgewhlte Gert.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

17

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Manahme
1. Klicken Sie im Setup-Men auf
Gerteaufzeichnung (siehe Abbildung 13).

Ergebnis
Einblendung der Seite fr die
Gerteaufzeichnung.

2. Beachten Sie Abbildung 13 und aktivieren Sie die


Auswahl der zu protokollierenden
Option Protokollierung bei den Gerten, die Sie
Gerte.
protokollieren mchten:
Um alle Gerte auszuwhlen, klicken Sie auf Alle
auswhlen und anschlieend auf bernehmen.
Um die Auswahl aller Gerte aufzuheben, klicken
Sie auf Lschen und anschlieend auf
bernehmen.
3. Whlen Sie das Aufzeichnungsintervall aus.

Auswahl des Aufzeichnungsintervalls


fr die ausgewhlten Gerte.

4. Klicken Sie auf bernehmen.

Aktualisierung der EGX-Einstellungen


fr die Gerteaufzeichnung.

OPTIONEN
Um den Aufzeichnungsinhalt anzupassen, aktivieren Sie
die Gerteaufzeichnung und fhren Sie anschlieend
folgende Schritte aus:
1. Whlen Sie ein Aufzeichnungsintervall ungleich null
aus und deaktivieren Sie das jeweilige
Kontrollkstchen Gerteaufzeichnung des Gerts.
2. Klicken Sie fr das Gert, das Sie konfigurieren
mchten, unter Anpassen auf Gren.
3. Beachten Sie Abbildung 14 auf Seite 19 und aktivieren
Sie die Gren, die Sie aufzeichnen mchten:
Um alle Gren auszuwhlen, klicken Sie auf Alle
auswhlen und anschlieend auf bernehmen.
Um die Auswahl aller Gren aufzuheben, klicken
Sie auf Lschen und anschlieend auf
bernehmen.
Um die Standardgren auszuwhlen, klicken Sie
auf Standardwerte unten im Bildschirm.

Damit werden die aufzuzeichnenden


Gertegren ausgewhlt. Danach
erfolgt die Rckkehr zur Seite
Gerteaufzeichnung.
HINWEIS: Wenn Sie die
Standardgren ndern, die fr
ein Gert aufgezeichnet werden,
erscheint neben Gren in der
Spalte Anpassen fr dieses
Gert ein Sternchen (*). Durch die
Vernderung der Gren eines
bereits aktiven Gerteprotokolls
werden alle vorher aufgezeichneten Daten fr dieses Gert
gelscht. Bei Bedarf sollten die
Daten vor den nderungen aus
dem EGX abgerufen werden.

Auswahl der zu lschenden


Um ein Datenprotokoll zu lschen, aktivieren Sie Daten
lschen fr die Datenprotokolle, die Sie lschen mchten: Datenprotokolle.
HINWEIS: Damit ein
1. Um alle Gerte auszuwhlen, klicken Sie auf Alle
Datenprotokoll gelscht werden
auswhlen und anschlieend auf bernehmen.
kann, darf das Kontrollkstchen
2. Um die Auswahl aller Gerte aufzuheben, klicken Sie
Protokollierung des Gerts nicht
auf Lschen und anschlieend auf bernehmen.
aktiviert sein.
Damit wird die Aufzeichnungsfunktion
Um die Aufzeichnung zu deaktivieren, whlen Sie ein
ausgeschaltet.
Aufzeichnungsintervall gleich null aus. Die
Aufzeichnungsoptionen mssen deaktiviert sein. Klicken
Sie anschlieend auf bernehmen.

Abbildung 13: Seite Gerteaufzeichnung

Aufzuzeichnende Gren

Gren fr die Aufzeichnung knnen fr jedes Gert einzeln ausgewhlt


werden.
Manahme

Ergebnis

1. Klicken Sie auf der Seite Gerteaufzeichnung auf den Link Anzeige der
Gren fr das gewnschte Gert.
Grenauswahlseite.

18

2. Beachten Sie Abbildung 14 auf Seite 19 und aktivieren Sie


die Gre(n), die Sie aufzeichnen mchten:
Um alle Gren auszuwhlen, klicken Sie auf Alle
auswhlen.
Um die Auswahl aller Gren aufzuheben, klicken Sie
auf Lschen.
Um die voreingestellten Gren auszuwhlen, klicken
Sie auf Standardwerte.

Auswahl der zu
protokollierenden Gren.

3. Klicken Sie auf bernehmen.

Speicherung der Auswahl der


zu protokollierenden Gren.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Abbildung 14: Grenauswahlseite

Gerteprotokollexport

Mit dieser Option knnen Sie Gerteprotokolle auf dreierlei Art exportieren:
ber E-Mail, FTP oder HTTP. In den folgenden Abschnitten werden beide
Methoden beschrieben.
HINWEIS: Wenn sich die E-Mail-, FTP- oder HTTP-Server nicht auf
demselben Ethernet-Netzsegment wie das EGX befinden, muss das EGXStandard-Gateway ordnungsgem konfiguriert sein. Siehe Ethernet- und
TCP/IP-Einstellungen auf Seite 5.

E-Mail-Export
Manahme

Ergebnis

1. Klicken Sie auf der Setup-Seite auf


Gerteprotokollexport.

Einblendung der Seite fr den


Gerteprotokollexport.

2. Whlen Sie E-Mail als bertragungsart.

Anzeige der Exportoptionen fr


das Gerteprotokoll ber E-Mail.

3. Aktivieren Sie das Kontrollkstchen Inkrementell.

Hiermit werden nur neue, seit dem


letzten erfolgreichen Datenexport
HINWEIS: Wenn die bertragung Stndlich oder zum
aufgezeichnete Intervalldaten
Aufzeichnungsintervall geplant ist, wird das
ausgewhlt.
Kontrollkstchen Inkrementell automatisch aktiviert.
HINWEIS: Wenn das Kontrollkstchen Inkrementell
nicht aktiviert ist, wird die gesamte Protokolldatei in
jedem geplanten Intervall ber einen E-Mail-Anhang
bertragen.

4. Whlen Sie Stndlich, Tglich, Wchentlich,


Monatlich oder Aufzeichnungsintervall aus.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Festlegung, wie oft


Datenprotokolle bertragen
werden sollen.

19

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Manahme

Ergebnis

5. Whlen Sie je nach Auswahl der Optionen im


vorangegangenen Schritt die Tageszeit, den
Wochentag und/oder den Tag des Monats.

Festlegung, wann Datenprotokolle


bertragen werden sollen.

6. Geben Sie in das Textfeld Von Adresse die E-MailAdresse der Person ein, die das Gert verwaltet.

Eingabe des Absenders der


E-Mail.

HINWEIS: Eine Absenderadresse ist notwendig, weil


die meisten SMTP-Server sie verlangen.
7. Geben Sie in die Textfelder Zu Adresse die E-MailAdressen (max. 5) der Empfnger der Datenprotokolle
ein (eine Adresse pro Textfeld).

Eingabe der E-Mail-Adressen der


Empfnger.

8. Geben Sie in die Textfelder Server-IP-Adresse die


Adresse des Ausgangs-E-Mail-Servers (0.0.0.0 bis
255.255.255.255) ein.

Eintrag der Adresse des Servers,


der Datenprotokolle ber E-Mail
versendet.

HINWEIS: Wenden Sie sich an Ihren


Netzwerkadministrator, wenn Sie die Adresse des
SMTP-Servers nicht kennen.
9. Geben Sie im Textfeld Server-TCP-Port die
Eintrag der Sendeschnittstelle des
Sendeschnittstelle fr den Ausgangs-E-Mail-Server ein. Ausgangs-E-Mail-Servers.
Werkeinstellung: 25
10. Wenn der SMTP-Server Anmeldedaten erfordert,
aktivieren Sie das Kontrollkstchen SMTP-Server
erfordert Anmeldung.

Ermglicht die Eingabe von


Anmeldedaten fr den SMTPServer.

HINWEIS: Das EGX untersttzt die


Zugangsauthentifizierungen Plain, Login, CRAMMD5 und Digest-MD5.
11. Wenn Sie das Kontrollkstchen SMTP-Server erfordert Aufzeichnung Ihrer Anmeldedaten
Anmeldung aktiviert haben, geben Sie den
fr den SMTP-Server.
Benutzernamen und das Kennwort in die Textfelder ein.
12. Klicken Sie auf Test-E-Mail, um eine Test-E-Mail mit
den von Ihnen eingestellten Parametern zu versenden,
oder klicken Sie auf bernehmen.
HINWEIS: Durch das Anklicken von Test-E-Mail
werden die E-Mail-Einstellungen fr den Export des
Protokolls bernommen und eine Test-E-Mail gesendet.
Wird bernehmen angeklickt, werden nur die
Einstellungen bernommen.

Senden einer Test-E-Mail


und/oder bernehmen der E-MailEinstellungen fr den
Protokollexport.

Abbildung 15: Seite Gerteprotokollexport E-Mail

20

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

FTP-Export
Manahme

Ergebnis

1. Klicken Sie auf der Setup-Seite auf


Gerteprotokollexport.

Einblendung der Seite fr den


Gerteprotokollexport.

2. Whlen Sie FTP als bertragungsart.

Einblendung der Optionen fr den


Export des Gerteprotokolls ber FTP.

3. Aktivieren Sie das Kontrollkstchen Inkrementell.


HINWEIS: Wenn die bertragung Stndlich oder
zum Aufzeichnungsintervall geplant ist, wird das
Kontrollkstchen Inkrementell automatisch
aktiviert.
HINWEIS: Wenn das Kontrollkstchen Inkrementell
nicht aktiviert ist, wird die gesamte Protokolldatei in
jedem geplanten Intervall ber FTP bertragen.

Hiermit werden nur neue, seit dem


letzten erfolgreichen Datenexport
aufgezeichnete Daten fr das Senden
ausgewhlt.

4. Whlen Sie Stndlich, Tglich, Wchentlich,


Monatlich oder Aufzeichnungsintervall aus.

Festlegung, wie oft Datenprotokolle


bertragen werden sollen.

5. Whlen Sie je nach Auswahl der Optionen im


vorangegangenen Schritt die Tageszeit, den
Wochentag und/oder den Tag des Monats.

Festlegung, wann Datenprotokolle


bertragen werden sollen.

Eintrag der Adresse des Servers, der


6. Geben Sie in die Textfelder Server-IP-Adresse
die Adresse des Ausgangs-FTP-Servers (0.0.0.0 die Datenprotokolle bertrgt.
bis 255.255.255.255) ein.
HINWEIS: Wenden Sie sich an Ihren
Netzwerkadministrator, wenn Sie die Adresse des
FTP-Servers nicht kennen.
7. Geben Sie im Textfeld Verzeichnis das
Verzeichnis ein.

Eingabe von Verzeichnisinformationen


fr den entfernten Server.

8. Geben Sie in die Textfelder Ihren Benutzernamen Aufzeichnung Ihrer Serverund das Kennwort ein.
Anmeldedaten.
9. Aktivieren Sie das Kontrollkstchen Passiv.

Passiveinstellung des FTPDateibertragungsmodus.

10. Klicken Sie auf FTP prfen, um die von Ihnen


eingestellten FTP-Parameter zu berprfen, oder
klicken Sie auf bernehmen.
HINWEIS: Durch das Anklicken von FTP prfen
werden die FTP-Einstellungen fr den Export des
Protokolls bernommen und eine Testdatei
bertragen. Wird bernehmen angeklickt, werden
nur die Einstellungen bernommen.

bertragung einer Testdatei an den


FTP-Server und das Verzeichnis
und/oder bernehmen der FTPEinstellungen.

Abbildung 16: Seite Gerteprotokollexport FTP

HINWEIS: Wenn die bertragung Stndlich oder zum Aufzeichnungsintervall geplant ist,
wird das Kontrollkstchen Inkrementell automatisch aktiviert.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

21

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

HTTP-Export
Manahme

Ergebnis

1. Klicken Sie auf der Setup-Seite auf


Gerteprotokollexport.

Einblendung der Seite fr den


Gerteprotokollexport.

2. Whlen Sie HTTP als bertragungsart.

Einblendung der Optionen fr den Export des


Gerteprotokolls ber HTTP.

3. Aktivieren Sie das Kontrollkstchen


Inkrementell.

Hiermit werden nur neue, seit dem letzten


erfolgreichen Datenexport aufgezeichnete
Daten fr das Senden ausgewhlt.

HINWEIS: Wenn die bertragung


Stndlich oder zum
Aufzeichnungsintervall geplant ist, wird
das Kontrollkstchen Inkrementell
automatisch aktiviert.
HINWEIS: Wenn das Kontrollkstchen
Inkrementell nicht aktiviert ist, wird die
gesamte Protokolldatei in jedem geplanten
Intervall ber HTTP bertragen.
4. Whlen Sie Stndlich, Tglich,
Wchentlich, Monatlich oder
Aufzeichnungsintervall aus.

Festlegung, wie oft Datenprotokolle bertragen


werden sollen.

5. Whlen Sie je nach Auswahl der Optionen Festlegung, wann Datenprotokolle bertragen
im vorangegangenen Schritt die Tageszeit, werden sollen.
den Wochentag und/oder den Tag des
Monats.
6. Geben Sie in die Textfelder Server-IPAdresse die Adresse des HTTP-Servers
ein.

Eintrag der IP-Adresse des Servers, der die


Datenprotokolle bertrgt.

HINWEIS: Wenden Sie sich an Ihren


Netzwerkadministrator, wenn Sie die
Adresse des HTTP-Servers nicht kennen.
7. Geben Sie im Textfeld Server-TCP-Port
die HTTP-Server-Schnittstelle ein.

Eingabe des Ausgangs-TCP-Ports.


Werkeinstellung: 80

HINWEIS: Wenn Sie mit SSLVerschlsselung exportieren mchten,


geben Sie die TCP-Port-Nummer des
HTTPS-Servers ein, die normalerweise
443 lautet.
8. Wenn Sie einen Proxyserver verwenden, Eintrag der IP-Adresse des Proxyservers, der
geben Sie die IP-Adresse in die Textfelder die Datenprotokolle bertrgt.
fr die IP-Adresse des Proxyservers ein.
HINWEIS: Wenden Sie sich an Ihren
Netzwerkadministrator, wenn Sie die
Adresse Ihres Proxyservers nicht kennen.
9. Geben Sie im Textfeld Proxyserver-TCP- Eingabe des Ausgangs-TCP-Ports.
Port die HTTP-Server-Schnittstelle ein.
Werkeinstellung: 0
HINWEIS: Wenn Sie mit SSLVerschlsselung exportieren mchten,
geben Sie die TCP-Port-Nummer des
HTTPS-Servers ein, die normalerweise
443 lautet.
10. Geben Sie im Textfeld Pfad den Pfad zu
Eingabe des Server-Script-Pfads.
dem Server-Script ein, das der Webserver
ausfhrt, nachdem das EGX Daten an ihn
gesendet hat.
11. Geben Sie in das Feld Feldname den
Mglichkeit der bertragung von Dateien vom
Namen ein, unter dem der Webserver den EGX an ein vorhandenes WWW-Server-Script.
Dateinamen erwartet.
HINWEIS: Ist das nicht erforderlich,
verwenden Sie den Standardwert
datafile1.

22

12. Geben Sie in das Feld Hostname den


Domnennamen des Hosts ein.

Erkennung eines bestimmten Hosts auf dem


WWW-Server, wenn er mehrere Domnen
unter einer einzigen IP-Adresse aufnimmt
(Voreinstellung ist leer).

13. Geben Sie in die Textfelder Ihren


Benutzernamen und das Kennwort ein.

Aufzeichnung Ihrer Server-Anmeldedaten.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Manahme

Ergebnis

14. Wenn Sie mit SSL-Verschlsselung


Alle Gerteprotokolle, die ber HTTP exportiert
exportieren mchten, aktivieren Sie SSL. werden, verwenden dann die SSLVerschlsselung (HTTPS).
15. Klicken Sie auf HTTP prfen, um die von
Ihnen eingestellten HTTP-Parameter zu
berprfen, oder klicken Sie auf
bernehmen.

bertragung einer Testdatei an den HTTPServer und das Verzeichnis und/oder


bernehmen der HTTP-Einstellungen.

HINWEIS: Durch Anklicken von HTTP


prfen werden die HTTP-Einstellungen fr
den Protokollexport bernommen und es
wird eine Testdatei bertragen. Mit dem
Klicken auf bernehmen werden nur die
Einstellungen bernommen.

Abbildung 17: Seite Gerteprotokollexport HTTP

Datum und Uhrzeit

Mit der Seite Datum und Uhrzeit knnen Sie das Datum und die Uhrzeit fr
das EGX einstellen.
Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf Datum und Einblendung der Seite Datum und Uhrzeit.
Uhrzeit.
2. Konfigurieren Sie Jahr, Monat, Tag,
Stunden, Minuten und Sekunden.

Einstellung des Datums und der Uhrzeit des


Systems.

3. Whlen Sie den Zeitzonenausgleich.

Einstellung der Uhr auf die gewhlte Zeitzone.

4. Damit sich die Uhr automatisch auf die


Sommerzeit umstellt, aktivieren Sie das
Kontrollkstchen Automatische
Sommerzeiteinstellung aktivieren.

Einstellung der Uhr auf automatische


Umstellung auf Sommerzeit.

5. Geben Sie den Tag im Monat, den


Einstellung des Beginns und Endes der
Wochentag, den Monat und die Stunde fr Sommerzeitumstellung.
Beginn und Ende der Sommerzeit ein.
6. Klicken Sie auf bernehmen.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Speicherung der Datums- und


Uhrzeiteinstellungen.

23

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Abbildung 18: Seite Datum und Uhrzeit

Netzwerkzeitsynchronisation

Mit der Aktivierung der Netzwerkzeitsynchronisation kann die Uhrzeit und


das Datum der EGX-Systemuhr durch einen NTP-Server (Network Time
Protocol) eingestellt werden.
HINWEIS: Wenn sich der NTP-Server nicht auf demselben EthernetNetzsegment wie das EGX befindet, achten Sie auf die richtige Konfiguration
des EGX-Standard-Gateway.

Manahme
1. Markieren Sie das Kontrollkstchen
Netzwerkzeitsynchronisation aktivieren auf der
Seite Datum und Uhrzeit.

Ergebnis
Einblendung des SNTPParameterabschnitts und der letzten
erfolgreichen Zeitsynchronisation.

2. Konfigurieren Sie die Zeitzonenabweichung, das Einstellung der SNTP-Parameter.


Aufrufintervall und die IP-Adresse des primren
und sekundren NTP-Servers
(siehe Abbildung 10 auf Seite 25).
3. Klicken Sie auf bernehmen.

Speicherung der SNTP-Einstellungen.

Abbildung 19: Netzwerkzeitsynchronisation aktivieren

24

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Tabelle 10: Einstellung der SNTP-Parameter


Option

SNMP-Parameter

Beschreibung

Einstellung

Zeitzonenausgleich

Zeiteinstellung auf der Basis des


gewhlten Werts der Coordinated
Universal Time (UTC).

UTC12:00 bis UTC+13:00


Werkeinstellung:
UTC (GMT)

Automatische
Sommerzeiteinstellung aktivieren

Damit knnen Sie den Beginn und das


Ende der Sommerzeit festlegen.

Erster bis Fnfter oder


letzter,
Sonntag bis Samstag,
Januar bis Dezember,
0:00 bis 23:00
Werkeinstellung:
Beginn am zweiten Sonntag
im Mrz um 2:00 Uhr
Ende am zweiten Sonntag
im November um 2:00 Uhr

Abrufintervall

Steuerung, wie oft das EGX den NTPServer wegen der richtigen Uhrzeit
kontaktiert.

1 Stunde bis 1 Woche


Werkeinstellung: 1 Woche

IP-Adresse des
primren NTPServers

Die IP-Adresse des primren NTPServers, den das EGX nach der richtigen
Uhrzeit fragt.

0.0.0.0 bis 255.255.255.255


Werkeinstellung: 0.0.0.0

IP-Adresse des
sekundren NTPServers

Die IP-Adresse des sekundren NTPServers, den das EGX nach der richtigen
Uhrzeit fragt.

0.0.0.0 bis 255.255.255.255


Werkeinstellung: 0.0.0.0

Das EGX untersttzt das Protokoll SNMP, mit dem der


Netzwerkadministrator mit einem SNMP-Manager auf ein entferntes EGX
zugreifen und den Netzwerkstatus sowie die Diagnosedaten des EGX im
MIB-II-Format anzeigen kann.
Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf SNMP-Parameter. Einblendung der SNMPParameterseite.


2. Markieren Sie SNMP aktivieren, um das Simple
Network Management Protocol einzuschalten.

Aktivierung von SNMP.

3. Geben Sie den Systemverantwortlichen, die


Eingabe der SNMPSystembezeichnung, den Systemstandort, den
Systeminformationen und der
Community-Namen mit schreibgeschtztem Zugriff Community-Zugriffsnamen.
und den Community-Namen mit Lese- und
Schreibzugriff ein.
4. Klicken Sie auf bernehmen.

Speicherung der SNMP-Einstellungen.

Abbildung 20: Seite SNMP-Parameter

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

25

PowerLogicTM Ethernet Gateway EGX300


Setup

Modbus-TCP/IP-Filter

63230-319-216B3_DE
03/2013

Mit dieser Funktion kann der Administrator die Zugangsstufe zuweisen, die
Modbus-TCP/IP-Clients auf die an das EGX angeschlossenen Gerte (lokal
oder entfernt) haben.
HINWEIS: Der anonymen Modbus-TCP/IP-Adresse (***.***.***.***) knnen
die Zugriffsberechtigungen Schreibgeschtzt oder Keine zugewiesen
werden. Die Einstellung Schreibgeschtzt erlaubt jedem Modbus-TCP/IPClient, der nicht in der Filterliste enthalten ist, den Zugriff auf serielle SlaveGerte mit der Zugriffsberechtigung Schreibgeschtzt. Die Einstellung
Keine blockiert alle Modbus-TCP/IP-Clients, die nicht in der Filterliste
enthalten sind.
Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf ModbusTCP/IP-Filter.

Einblendung der Seite Modbus-TCP/IP-Filter.

2. Markieren Sie Filter aktivieren.

Aktivierung der Filterung.

3. Geben Sie in der Spalte IP-Adresse die


Modbus-TCP/IP-Client-Adresse ein.

Eingabe einer IP-Adresse fr einen ModbusTCP/IP-Client, der Zugriff auf die an das EGX
angeschlossenen Gerte haben soll.

4. Whlen Sie in der Spalte


Auswahl der Zugriffsberechtigung fr die
Zugriffsberechtigung entweder
entsprechende IP-Adresse. Fr die Einstellung
Schreibgeschtzt oder Vollstndig aus. Schreibgeschtzt sind die folgenden ModbusTCP/IP-Funktionen erlaubt:
Dezimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24,
43, 100
Hexadezimal: 01, 02, 03, 04, 07, 08, 0B, 0C,
11, 14, 18, 2B, 64
5. Wiederholen Sie die Schritte 3 und 4, um
weitere IP-Adressen hinzuzufgen.

Hinzufgen weiterer IP-Adressen fr den Filter.

6. Klicken Sie auf bernehmen.

Speicherung der Modbus-TCP/IP-AdressenFilterliste.

Abbildung 21: Seite Modbus-TCP/IP-Filter

26

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Unterlagenlinks

Das EGX untersttzt zwei Arten von Unterlagenlinks:


1. Zugriff auf lokale Dateien (im EGX gespeicherte Onboard-Unterlagen)
2. Zugriff auf externe URLs
HINWEIS: Lokale Dateiunterlagen, die auf der Unterlagenwebseite
erscheinen sollen, mssen mit FTP in den EGX-Ordner
www/documentation (Unterlagen) bertragen werden.
Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf


Unterlagenlinks.

Einblendung der Seite Unterlagenlinks.

2. Fr Dateizugriff: Aktivieren Sie das


Kontrollkstchen Aktiviert fr die
Dateinamenlinks, die Sie aktivieren
mchten.

Aktivierung der Dateien und URLs, die auf der


Unterlagenseite erscheinen sollen.

Fr URL-Zugriff: Aktivieren Sie das


Kontrollkstchen Aktiviert fr die URLLinks, die Sie aktivieren mchten.
3. Aktivieren Sie das Kontrollkstchen Neues Aktivierung derjenigen Dateien und URLs, die
Fenster, wenn die ausgewhlten Dateien nach dem Anklicken in einem neuen Fenster
und URLs nach dem Anklicken in einem
angezeigt werden sollen.
neuen Fenster angezeigt werden sollen.
4. Geben Sie in das Textfeld Link-Text einen Einstellung des Unterlagenlinktitels, der auf der
Titel des Unterlagenlinks ein.
Unterlagenseite erscheinen soll.
5. Klicken Sie auf bernehmen.

Aktualisierung der Einstellungen fr die EGXUnterlagenlinks.

Abbildung 22: Seite Unterlagenlinks

HINWEIS: Informationen ber den Zugriff auf die geladenen Unterlagen


finden Sie unter Unterlagen auf Seite 50.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

27

PowerLogicTM Ethernet Gateway EGX300


Setup

Benutzerkonten

63230-319-216B3_DE
03/2013

EGX-Benutzern werden Benutzernamen und Kennwrter zugewiesen. Jeder


Benutzer gehrt zu einer Gruppe, und jede Gruppe besitzt Zugriffsrechte auf
die EGX-Webseiten, die vom EGX-Administrator zugewiesen wurden.
HINWEIS: Zwei Benutzerkonten sind voreingestellt: Administrator
(voreingestelltes Kennwort: Gateway) und Guest (Gast, voreingestelltes
Kennwort: Guest).
Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf


Benutzerkonten.

Einblendung der Seite Benutzerkonten.

2. Wenn Sie einen Gruppennamen ndern wollen,


geben Sie den neuen Namen in eines der
Textfelder Gruppen ein (der AdministratorGruppenname kann nicht gendert werden).

Eingabe eines neuen Gruppennamens.

3. Geben Sie im Bereich Benutzer einen Namen


(1 bis 24 Zeichen) und ein Kennwort (0 bis
12 Zeichen) fr einen neuen Benutzer ein.

Eingabe des Namens und des


Kennwortes fr einen Benutzer.
Das EGX300 berprft die Sicherheit des
Kennworts und zeigt diese durch einen
HINWEIS: Benutzernamen und Kennwrter
bercksichtigen Gro- und Kleinschreibung und Farb- sowie einen Textcode an:
= kein Kennwort/Kennwort mit
knnen nur alphanumerische Zeichen enthalten. Rot
niedriger Sicherheit
Gelb
= Kennwort mit mittlerer
Sicherheit
Blau
= Kennwort mit hoher Sicherheit
Grn
= Kennwort mit sehr hoher
Sicherheit

4. Whlen Sie eine Gruppe und die


Standardsprache fr den neuen Benutzer aus.

Auswahl der Gruppe und der Sprache fr


einen Benutzer.

5. Wiederholen Sie die Schritte 3 und 4 fr jeden


zustzlichen Benutzer, den Sie hinzufgen
wollen.

Hinzufgen weiterer Benutzer.

6. Klicken Sie auf bernehmen.

Sicherung aller
Benutzerkonteneinstellungen.

Tabelle 11: EGX-Konten und -Kennwrter


Konto

Werkeingestelltes Kennwort

Administrator

Gateway

Guest

Guest

Benutzerdefinierte Konten (bis zu 11 Konten mglich) Keine Werkeinstellung Kennwort ist


benutzerdefiniert

Abbildung 23: Seite Benutzerkonten

28

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Webseitenzugriff

Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf


Webseitenzugriff.

Einblendung der Seite Webseitenzugriff.

2. Whlen Sie die Zugriffsberechtigung (Keine,


Schreibgeschtzt oder Vollstndig) aus, die
jede Benutzergruppe auf die Webseiten haben
soll.

Fr eine Erluterung der


Zugriffsberechtigungen fr jede Gruppe
siehe die nachstehende Tabelle 12.

3. Um einem Gast den Zugriff auf die Webseite zu Erlaubt der werkeingestellten Gruppe
ermglichen, whlen Sie in der Spalte Guest die Guest den Zugriff auf die Webseite.
Zugriffsberechtigung Schreibgeschtzt aus.
HINWEIS: Wenn fr die Gruppe Guest die
Zugriffsberechtigung Schreibgeschtzt
eingestellt ist, kann als Zugriffsberechtigung fr
die anderen Gruppen nur Schreibgeschtzt
oder Vollstndig ausgewhlt werden.
4. Wiederholen Sie die Schritte 2 und 3 fr die
Optionen in jedem Abschnitt.

Auswahl der Zugriffsberechtigung fr jede


Webseite.

5. Klicken Sie auf bernehmen.

Speicherung der Kennworteinstellungen.

Tabelle 12: Gruppenzugriff


Gruppe

Zugriff

Administrator

Vollstndiger Zugriff auf alle Webseiten.


HINWEIS: Aus Systemsicherheitsgrnden wird empfohlen, das werkeingestellte Administratorkennwort nach der ersten Anmeldung zu ndern.

Guest

Schreibgeschtzter Zugriff auf ausgewhlte Webseiten.

Drei benutzerdefi- Durch Auswahl aus folgenden Optionen weist der Administrator jeder
nierte Gruppen
Gruppe bestimmte Webseiten-Zugriffsrechte zu. Es gibt folgende
Zugriffsberechtigungen:
Keine: eine Gruppe hat keinen Zugriff auf die ausgewhlte Webseite
Schreibgeschtzt: das Kennwort gewhrt einer Gruppe nur Lesezugriff
auf die ausgewhlte Webseite
Vollstndig: eine Gruppe hat den gleichen Zugriff wie die AdministratorGruppe auf die ausgewhlte Webseite

Abbildung 24: Seite Webseitenzugriff

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

29

PowerLogicTM Ethernet Gateway EGX300


Setup

Benutzerdefinierte Webseiten
hinzufgen/entfernen

63230-319-216B3_DE
03/2013

Benutzerdefinierte Webseiten und andere Dateien knnen von Ihrem


Computer ber FTP auf das EGX bertragen werden. ber FTP in die
Verzeichnisse www/monitoring (berwachung), www/maintenance
(Wartung) oder www/control (Steuerung) bertragene Dateien mit den
Erweiterungen .htm, .html oder .shtml werden automatisch gesichert. Fr
jeden Ordner ist auf der Menleiste der Webschnittstelle ein
entsprechender Link vorhanden. Wenn in der Menleiste der Link angeklickt
wird, erscheinen die von Ihnen hinzugefgten Webseiten auf der linken
Seite des Browserfensters unter Benutzerdefinierte Seiten.
HINWEIS: In den Ordnern berwachung, Steuerung oder Wartung
knnen keine neuen Ordner erstellt werden.
Nach der bertragung von benutzerdefinierten Webseiten oder anderen
Dateien ber FTP in das EGX knnen die Webseiten und Dateien mithilfe der
Seite Webseiten hinzufgen/entfernen zur Webschnittstelle hinzugefgt
werden bzw. von der Webschnittstelle entfernt werden, ohne sie im EGX zu
lschen. Diese Seite wird von der Seite Webseitenzugriff aus geffnet.

Hinzufgen von Webseiten mit FTP


Manahme

Ergebnis

1. Starten Sie Windows Explorer, geben Sie ftp:// und die Einblendung des Dialogfelds
IP-Adresse des EGX (zum Beispiel ftp://169.254.0.10) in Anmelden als.
das Adressentextfeld ein und drcken Sie die
Eingabetaste.
2. Geben Sie in die Textfelder den Benutzernamen
Administrator und das Administratorkennwort ein und
klicken Sie auf Anmelden.

Erffnung einer FTP-Sitzung mit


dem EGX.

3. ffnen Sie ein neues Fenster in Windows Explorer,


Kopiert die Datei in die
gehen Sie zur benutzerdefinierten Webseite, die Sie an Zwischenablage.
das EGX senden mchten, klicken Sie mit der rechten
Maustaste darauf und klicken Sie anschlieend auf
Kopieren.
4. Wechseln Sie zum EGX-Fenster in Windows Explorer,
das Sie in Schritt 1 geffnet haben, und ffnen Sie
anschlieend den Ordner, in den die Webseite kopiert
werden soll (z. B. /www/monitoring/).

ffnet den Ordner, in dem die


Webseite auf dem EGX
gespeichert wird.

5. Klicken Sie mit der rechten Maustaste in das rechte


Fenster in Windows Explorer und anschlieend auf
Einfgen.

Kopiert die benutzerdefinierte


Webseite in das EGX.

HINWEIS: Anstelle von Kopieren und Einfgen knnen


Sie die Datei auch per Drag-and-Drop in Windows
Explorer bertragen.
6. Klicken Sie im Windows-Explorer-Fenster auf
Schlieen.

Schlieen von Windows Explorer.

Lschen von Webseiten mit FTP


Manahme

Ergebnis

1. Starten Sie Windows Explorer, geben Sie ftp:// und die Einblendung des Dialogfelds
IP-Adresse des EGX (zum Beispiel ftp://169.254.0.10) in Anmelden als.
das Adressentextfeld ein und bettigen Sie
anschlieend die Eingabetaste.
2. Geben Sie in die Textfelder den Benutzernamen
Administrator und das Administratorkennwort ein und
klicken Sie auf Anmelden.

Erffnung einer FTP-Sitzung mit


dem EGX.

3. ffnen Sie den Ordner, in dem die benutzerdefinierte


ffnet den Ordner, in dem sich die
Webseite gespeichert ist, klicken Sie mit der rechten
benutzerdefinierte Webseite
Maustaste auf die zu lschende Datei und anschlieend befindet, und lscht die Datei.
auf Lschen.
4. Klicken Sie im Windows-Explorer-Fenster auf
Schlieen.

30

Schlieen von Windows Explorer.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Webseiten zur Webschnittstelle hinzufgen


oder aus ihr entfernen

Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf


Webseitenzugriff.

Einblendung der Seite Webseitenzugriff.

2. Klicken Sie auf Webseiten


hinzufgen/entfernen (siehe
Abbildung 25).

Einblendung der Seite Webseiten


hinzufgen/entfernen.

3. Wenn Sie benutzerdefinierte Webseiten zu Auswahl oder Deaktivierung einer


einem EGX-Ordner hinzugefgt haben,
benutzerdefinierten Webseite.
sehen Sie unter der jeweiligen
Ordnerbezeichnung eine Liste mit den
entsprechenden Dateinamen. Whlen Sie
die Webseiten aus, die die Benutzer sehen
sollen. Deaktivieren Sie die Webseiten, die
Sie Ihren Benutzern nicht zeigen mchten.
HINWEIS: Das Deaktivieren einer
Webseite lscht diese nicht aus dem EGX.
4. Klicken Sie auf bernehmen.

Hinzufgen einer benutzerdefinierten


Webseite zur EGX-Webschnittstelle oder
Entfernen einer benutzerdefinierten Webseite
von der EGX-Webschnittstelle.

Abbildung 25: Seite Webseiten hinzufgen/entfernen

Prferenzen

Mit dieser Option kann jedes EGX einzeln angepasst werden.


Manahme

Ergebnis

1. Klicken Sie im Setup-Men auf


Prferenzen.

Einblendung der Seite Prferenzen.

2. Geben Sie den Gertenamen, die


voreingestellte Startseite, die EchtzeitAbtastrate und die Hufigkeit der
Kommunikationsprfung ein.

Einstellung der Prferenzen.

3. Klicken Sie auf bernehmen.

Aktualisierung der EGXPrferenzeinstellungen.

Abbildung 26: Seite Prferenzen

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

31

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Tabelle 13: Prferenzeinstellungen


Option

Beschreibung

Einstellung

Gertename

Hier knnen Sie einen benutzerdefinierten


Namen fr das EGX und dazugehrige
Gerte eingeben. Dieser Name wird im
Banner der Webschnittstelle benutzt.

Werkeinstellung:
Powerlogic EGX300

Voreingestellte
Startseite

Mglichkeit der Auswahl einer


voreingestellten Startseite.

Startseite,
Schaltkreisbersicht,
Laststrombersicht,
Strommittelwertbersicht,
Leistungsbersicht oder
Energiebersicht
Werkeinstellung:
Startseite

Echtzeit-Abtastrate

Steuert die Hufigkeit, mit der Daten aus


den Gerten in die normalen
berwachungstabellenansichten
ausgelesen werden.

5 bis 60 Sekunden
Werkeinstellung:
5 Sekunden

Hufigkeit der Kommu- Steuert, wie oft eine Kommunikationsnikationsprfung


prfung durchgefhrt wird, whrend der
Browser Echtzeitmesswerte in den
normalen berwachungstabellenansichten
anzeigt. Mit dieser Funktion wird versucht,
alle auer Betrieb befindlichen Gerte
automatisch wieder in Betrieb zu setzen.

Anzeigbare Gertetypen

Deaktiviert,
5 bis 30 Minuten
Werkeinstellung:
15 Minuten

Auf der Seite Anzeigbare Gertetypen knnen die Gertetypen verwaltet


werden, die fr den Benutzer auf der Setup-Webseite Gerteliste zur
Auswahl stehen. Da das EGX300 viele verschiedene Gertetypen
untersttzt, kann das Entfernen von Gertetypen aus der Liste Verfgbare
Gerte u. U. die Konfiguration der Setup-Webseite Gerteliste
vereinfachen.
Manahme
1. Klicken Sie im Setup-Men auf Anzeigbare
Gertetypen.

Ergebnis
Einblendung der Seite
Anzeigbare Gertetypen.

2. Whlen Sie die Gertetypen aus, die fr die Konfiguration Auswahl von Gertetypen, die fr
der Gerteliste verfgbar sein sollen.
die Konfiguration der Gerteliste
verfgbar sein sollen.
HINWEIS: Klicken Sie auf Alle auswhlen, um alle
Gerte zu aktivieren, bzw. auf Lschen, um alle Gerte
zu deaktivieren.
HINWEIS: Die Verfgbarkeit des Gertetyps kann bei
gerade verwendeten Gerten nicht gendert werden.
3. Klicken Sie auf bernehmen.

32

Speichern der Einstellungen fr


Anzeigbare Gertetypen.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Abbildung 27: Seite Anzeigbare Gertetypen

Prfpfad

Der Prfpfad besteht aus einer Folge von Aufzeichnungen oder Meldungen
mit Zeitstempel. Er zeichnet Konfigurationsnderungen, Fehler und
fehlgeschlagene Authentifizierungen auf. Auerdem identifiziert er den
Benutzer, der das Ereignis ausgelst hat.
Verwenden Sie die Seite Prfpfad, um die vier Berichtsgruppen und die
Meldungskanle einzurichten. Fr jeden Kanal sind die Berichtsgruppen
auszuwhlen, fr die Meldungen angezeigt werden sollen. Wenn Sie eine
Berichtsgruppe fr einen Kanal auswhlen, sehen Sie alle Meldungen, die
in dieser Berichtsgruppe generiert werden.
Folgende Meldungskanle stehen zur Verfgung:

Onboard-Wartungsprotokolldatei fr das EGX

E-Mail

Entfernter Syslog-Server (Syslog ist ein Standard fr die Protokollierung


von Meldungen)

Alle Meldungen werden mit einem Zeitstempel versehen und enthalten die
Berichtsgruppe sowie die Benutzeridentifikation.
Die Seite Prfpfad ist in drei Bereiche unterteilt, die den drei
Meldungskanlen entsprechen: Wartungsprotokoll, Syslog und E-Mail.
(Siehe Abbildung 28 auf Seite 35.) Sie knnen die auf jedem Kanal
bertragenen Meldungen separat konfigurieren.
Klicken Sie im Fenster Setup auf Prfpfad. Die Seite Prfpfad wird
angezeigt. Befolgen Sie die Anweisungen in der nachstehenden Tabelle.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

33

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Tabelle 14: Prfpfadeinrichtung


Option

Beschreibung

Einstellung

Wartungsprotokoll
Steuerung der
Meldungen werden im OnboardBerichtstypen, fr Wartungsprotokoll des EGX angezeigt,
die Meldungen im sobald sie generiert werden.
Meldungsprotokoll
angezeigt werden
sollen.

Aktivieren Sie die Optionen, die


im Bericht enthalten sein sollen.
Werkeinstellung: keine
Optionen aktiviert

Syslog
Server-IP-Adresse Meldungen werden zu dem hier
angegebenen Server weitergeleitet,
sobald sie generiert werden.
Server-UDP-Port
(User Datagram
Protocol)
Bericht
Dropdown-Liste
Anlage
Dropdown-Liste
Schwere

Geben Sie die IP-Adresse fr


den entfernten Server ein, zu
dem die Meldungen
weitergeleitet werden sollen.
Syslog-Meldungen werden ber diesen
Geben Sie die UDP-PortServer-UDP-Port bertragen.
Nummer fr diese IP-Adresse
ein. Werkeinstellung = 514
Hier werden die vier Berichtstypen, fr die Aktivieren Sie die Berichtstypen,
Meldungen weitergeleitet werden knnen, fr die Meldungen weitergeleitet
werden sollen.
ausgewhlt.
Liefert einen groben Anhaltspunkt zum
Whlen Sie die entsprechende
Standort der Anlage, die die Meldung
Kategorie aus.
generiert hat. Diese Information wird im
Syslog angezeigt.
Informiert den Benutzer ber die Wichtigkeit Whlen Sie die entsprechende
der Meldung. Sie mssen fr Ihre Anlage
Kategorie aus.
die Wichtigkeit jedes Typs bestimmen.

E-Mail
Von Adresse

Zu Adresse

Wenn Meldungen generiert werden, wird


die E-Mail-Adresse des Absenders im
Feld Von angezeigt.
Der Hauptteil der E-Mail enthlt folgende
Informationen: IP-Adresse des EGX,
Berichtsgruppenname, Benutzername, IPAdresse des Benutzers und die Meldung
von der Berichtsgruppe.
Wenn Meldungen generiert werden,
werden sie an die E-Mail-Adresse(n) des
Empfngers bertragen.

Geben Sie unter Von Adresse


die E-Mail-Adresse des
Absenders fr E-Mails ein. Es
drfen maximal 49 Zeichen
verwendet werden.

Geben Sie unter Zu Adresse


die E-Mail-Adresse des
Empfngers aller Meldungs-EMails ein. Pro Adresse drfen
maximal 49 Zeichen verwendet
werden.
Server-IP-Adresse Das ist die IP-Adresse des Servers, an
Wenn keine Server-IP-Adresse
den die E-Mails bertragen werden.
eingegeben wird, werden keine
E-Mails gesendet.
Server-TCP-Port
Das ist die TCP-Port-Nummer fr die
Geben Sie die TCP-PortServer-IP-Adresse.
Nummer ein. Die
Werkeinstellung lautet 25.
SMTP-Server
Aktivieren Sie dieses Kontrollkstchen,
Markieren Sie das
erfordert
um die Anmeldung fr den Empfang von Kontrollkstchen, um mit dem
Anmeldung
E-Mails zu aktivieren. Der SMTP-Server
Hinzufgen von Anmeldedaten
erfordert eine Anmeldung.
zu beginnen.
Benutzername
Das ist der Benutzername, den das EGX Geben Sie den fr den SMTPverwendet, um sich beim SMTP-Server
Server erforderlichen Benutzeranzumelden.
namen ein (max. 31 Zeichen).
Kennwort
Das ist das Kennwort, welches vom EGX Geben Sie das fr den SMTPverwendet wird, um sich beim SMTPServer erforderliche Kennwort
Server anzumelden.
ein (max. 31 Zeichen).
Bericht
Das sind die Berichtstypen, fr die
Aktivieren Sie die
Meldungen weitergeleitet werden knnen. Berichtstypen, fr die Sie
Sie knnen beliebig viele auswhlen.
Meldungen haben mchten.
Standardwerte/
Klicken Sie auf bernehmen, um die von Klicken Sie auf bernehmen
bernehmen
Ihnen vorgenommenen Eintrge zu
oder auf Standardwerte.
speichern. Klicken Sie auf
Standardwerte, um jedes Feld auf seine
Werkeinstellung zurckzusetzen.

34

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Abbildung 28: Prfpfadeinrichtung

Systemzugangspunkt

Mit dem Systemzugangspunkt knnen andere, an das Netzwerk


angeschlossene Schneider Electric-Gerte erkannt und Verbindungen zu
ihnen hergestellt werden. Diese Funktion ist so konfiguriert, dass sie
standardmig ausgefhrt wird und keine weitere Konfiguration bentigt.
Verwenden Sie diesen Setup-Bildschirm fr die Eingabe der Gruppen-IPAdresse und zugehriger Informationen.

Manahme

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Ergebnis

1. Klicken Sie im Setup-Men auf


Systemzugangspunkt.

Das Fenster Systemzugangspunkt wird


angezeigt.

2. Aktiviert

Ist dieses Kontrollkstchen aktiviert, knnen


sich EGX300-Gerte mit denselben GruppenIP-Adressen untereinander erkennen.
Werkeinstellung = Aktiviert

3. UDP-Port

Geben Sie die Port-Nummer (von 1 bis 65535)


des UDP-Ports ein, der fr die Erkennung ber
den Systemzugangspunkt verwendet wird.
Werkeinstellung = 59

4. Gruppen-IP-Adresse

Geben Sie die Gruppen-IP-Adresse ein, die


Multicast- oder Unicast-Adressen untersttzt.
Werkeinstellung = 224.0.1.2

5. Meldungsintervall

Das ist die Zeit zwischen den HalloMeldungen, die vom EGX300 ausgegeben
werden, um anderen Systemzugangsgerten
von Schneider Electric seine Anwesenheit im
Netzwerk mitzuteilen. 165535 Sekunden,
Werkeinstellung = 300 Sekunden

35

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216B3_DE
03/2013

Manahme

Ergebnis

6. Haltezeit

Das ist die Zeit, fr die vom jeweiligen EGX300


gesendete Hallo-Meldungen von Empfngern
gehalten werden mssen, bevor dieses
EGX300 als nicht verfgbar angesehen wird.
Von 2 bis 65535 Sekunden,
Werkeinstellung = 600 Sekunden

7. Multicast-Gltigkeitsdauer

Sie knnen die Gre des Netzwerkbereichs


festlegen, der zur Erkennung von anderen
Gerte verwendet wird. Das wird durch die
zulssige Anzahl der Multicast-Weiterleitungen
an andere Gerte geregelt. Der Bereich der
zulssigen Router-Sprnge betrgt 1255.
Werkeinstellung = 1

8. Gemeinschaft

EGX300-Gerte in einer Gruppe knnen in


Gemeinschaften unterteilt werden. EGX300Gerte mit derselben Gruppen-IP-Adresse und
Gemeinschaftsnummer knnen sich
untereinander erkennen.
Durch Einstellung der Gemeinschaftsnummer
auf 0 kann ein EGX300 alle EGX300-Gerte
mit derselben Gruppen-IP-Adresse ohne
Bercksichtigung der Gemeinschaftseinstellung erkennen. Werkeinstellung: 0

9. Standardwerte/bernehmen

Klicken Sie auf bernehmen, um Ihre


Eintrge zu speichern bzw. auf
Standardwerte, um zu den aufgelisteten
Werkeinstellungen zurckzukehren.

Abbildung 29: Setup-Seite fr den Systemzugangspunkt

36

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


berwachung

63230-319-216B3_DE
03/2013

BERWACHUNG

Das EGX bietet Bildschirmanzeigen fr die Anzeige von Echtzeitdaten und


-Trendkurven zusammen mit historischen Datenprotokoll-Trendkurven.

Echtzeitdaten

Die Seite Echtzeitdaten stellt grundlegende Messwerte ausgewhlter


Gerte in Echtzeit sowie Gertebersichten bereit.

Einzelgerteseiten

Um eine Tabelle mit Echtzeitdaten zu betrachten, wechseln Sie in das


berwachungsmen und whlen Sie ein Gert unter Echtzeitdaten >
Einzelgerteseiten aus.

Grundmesswerteinstellungen
Manahme
1. Whlen Sie oben auf der Anzeige entweder
Laststrom, Leistung, L-L-Spannung oder L-NSpannung fr die Anzeige in der grafischen
Darstellung des Analogmessgerts aus.

Ergebnis
Auswahl der Gren, die in der
grafischen Darstellung des
Analogmessgerts angezeigt werden
sollen.
HINWEIS: Analogmessgertdarstellungen stehen nicht fr alle
Gertetypen zur Verfgung.

2. Standardmig passen die Messgerte ihren


Anzeigebereich automatisch an. Whlen Sie
Bereich aus, wenn ein fester Bereich gewnscht
wird. Anweisungen fr die Konfiguration des
Bereichs der Analogmessgerte sind in der
nachstehenden Tabelle aufgefhrt.

Steuerung des Anzeigebereichs der


Analogmessgerte.

3. Klicken Sie auf bernehmen.

Aktualisierung der Messgertauswahl


fr die Seite Gert.

Abbildung 30: Seite Grundmesswerte

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

37

PowerLogicTM Ethernet Gateway EGX300


berwachung

Analogmessgertbereich

63230-319-216B3_DE
03/2013

Der Bereich der grafischen Analogmessgerte auf der Seite


Grundmesswerte kann konfiguriert oder auf automatische Skalierung
eingestellt werden (siehe Abbildung 31).
Manahme
1. Aktivieren Sie unter Automatische Skalierung
aktivieren die Gerte, die automatisch skaliert
werden sollen.

Ergebnis
Aktivierung der automatischen
Skalierung fr ausgewhlte Gerte.

HINWEIS: Klicken Sie auf Alle auswhlen, um die


automatische Skalierung fr alle Gerte zu aktivieren,
bzw. auf Lschen, um die automatische Skalierung
fr alle Gerte zu deaktivieren.
2. Geben Sie fr Gerte mit deaktivierter automatischer Festlegung des Messgertbereichs.
Skalierung die unteren und oberen Grenzwerte fr
jeden Messgerttyp ein.
3. Klicken Sie auf bernehmen.

Aktualisierung der Einstellungen fr


die automatische Skalierung.

Abbildung 31: Setup-Seite Bereich

bersichtsgerteseiten

Auf den bersichtsgerteseiten befinden sich tabellarische bersichten


ber ein oder mehrere ausgewhlte Gerte.
Manahme

Ergebnis

1. Klicken Sie im berwachungsmen auf


bersichtsgerteseiten.

Erweiterung der Baumdarstellung fr


die Auswahl der bersichtsseiten.

2. Whlen Sie die bersichtsseite aus, die Sie


betrachten mchten.

Einblendung der
Gerteauswahlliste.

3. Whlen Sie Gerte aus der Liste Verfgbare Gerte Auswahl von Gerten fr die
aus und klicken Sie auf Weiter (siehe Abbildung 32). bersichtsoptionen.
HINWEIS: Klicken Sie auf >>, um alle verfgbaren
Gerte auszuwhlen.

Abbildung 32: Seite Gerteauswahl

38

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


berwachung

63230-319-216B3_DE
03/2013

Abbildung 33: Seite Schaltkreisbersicht

Trendverfolgung

Um eine Echtzeit-Trenddarstellung mehrerer Gerte anzuzeigen, rufen Sie


das berwachungsmen auf und whlen Sie Echtzeitdaten >
Trendverfolgung aus.
Manahme

Ergebnis

1. Whlen Sie im berwachungsmen Echtzeitdaten aus.

Erweiterung der Datenbaumansicht fr die Auswahl der


Echtzeit-Datenoptionen.

2. Whlen Sie Trendverfolgung aus.

Erweiterung der
Datenbaumansicht fr die
Auswahl der EchtzeitTrendverfolgungsoptionen.

3. Whlen Sie Echtzeit-Trendverfolgung aus.

Einblendung der Setup-Seite fr


die Echtzeit-Trendverfolgung.

4. Whlen Sie bis zu vier Gerte aus der Liste Verfgbare


Gerte aus.

Auswahl von Gerten fr die


Trendverfolgung.

5. Whlen Sie ein oder mehrere Gren aus der Liste


Verfgbare Gren aus.

Auswahl von Gren fr die


Trendverfolgung.

HINWEIS: Es stehen nur die Gren zur


Trendverfolgung zur Verfgung, die alle ausgewhlten
Gerte gemeinsam haben. Die maximale Anzahl der
Gren fr die Trendverfolgung hngt von der Anzahl der
ausgewhlten Gerte ab. Das Produkt aus der Anzahl
der ausgewhlten Gerte und Gren muss kleiner als
oder gleich 8 sein.
6. Klicken Sie auf Weiter, um die Anzeigeseite EchtzeitTrendverfolgung einzublenden.

Einblendung der Anzeigeseite


Echtzeit-Trendverfolgung.

7. Um die Trendverfolgungsparameter festzulegen, fahren Mglichkeit zur Einstellung der


Sie mit dem Verfahren in der nachstehenden Tabelle fort Parameter fr die
und beachten Sie dazu Abbildung 35 auf Seite 40.
Trendverfolgung.

Abbildung 34: Auswahl von Gerten und Gren

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

39

PowerLogicTM Ethernet Gateway EGX300


berwachung

63230-319-216B3_DE
03/2013

Manahme

Ergebnis

1. Whlen Sie die Trendverfolgungsoption Absolutwert oder Auswahl des Diagrammmodus.


Relativwert aus.
HINWEIS: Mit der Option Absolutwert wird die X-Achse
des Diagramms nach jeder Abtastung neu gezeichnet und
das Diagramm wird mit allen Daten gefllt, die seit dem
Start der Trendkurve erfasst wurden. Mit der Option
Relativwert wird das Diagramm nach jeder Abtastung mit
den neuesten Daten aktualisiert, wobei die X-Achse
konstant bleibt, um die ausgewhlte Gesamttrendzeit
anzuzeigen.
2. Whlen Sie eine Trendzeit zwischen 1 und 15 Minuten
aus. Das ist die Dauer der Trenddarstellung.

Auswahl der Dauer der


Trenddarstellung.

HINWEIS: Datenabtastungen werden so schnell wie


mglich vorgenommen, knnen aber je nach
Kommunikationslast im seriellen Subnetz und/oder auf
den entfernten Gerten lnger dauern.
3. Whlen Sie Abtastung starten aus, um die
Trendverfolgung der ausgewhlten Gertegren zu
starten.

Start der Trendverfolgung.

HINWEIS: Die Trendverfolgung kann vor dem Ablauf der


Trendzeit durch Klicken auf Abtastung anhalten
angehalten werden. Wenn nach dem Anhalten der
Abtastung Abtastung starten angeklickt wird, wird eine
neue Trendkurve gestartet.
4. Klicken Sie auf Datenpunkte, um ein Protokoll aller
abgetasteten Gren anzuzeigen, die whrend der
Trendzeit aufgezeichnet wurden.
HINWEIS: Nach jedem Intervall werden die Angaben
Aktueller Wert fr alle Gren sowie die berechneten
Werte Min., Max. und Mittelwert in die Tabelle unter
dem Diagramm eingetragen.
5. Klicken Sie auf Neue Gre(n), um Gerte und Gren
fr die Trendverfolgung neu auszuwhlen.

Anzeige eines Protokolls aller


Grenwerte, die whrend der
Trendverfolgung abgetastet
wurden.

Navigation zurck zur SetupSeite EchtzeitTrendverfolgung.

Abbildung 35: Echtzeit-Trendverfolgung

Gerteaufzeichnung

40

Die Seiten Gerteaufzeichnung enthalten grafische und tabellarische


Darstellungen der ausgewhlten Gerteaufzeichnungsdaten. Weitere
Details zur Konfiguration der Gerteaufzeichnung finden Sie unter
Gerteaufzeichnung auf Seite 17.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


berwachung

63230-319-216B3_DE
03/2013

Einzelgerteseiten

Einzelgerteseiten enthalten grafische und tabellarische Darstellungen der


Daten, die von einem einzelnen Gert aufgezeichnet wurden.
Manahme

Ergebnis

1. Klicken Sie im berwachungsmen auf


Gerteaufzeichnung.

Erweiterung der Baumansicht fr die


Anzeige der verfgbaren Auswahlmglichkeiten fr die Gerteaufzeichnung.

2. Klicken Sie unter Gerteaufzeichnung auf


Einzelgerteseiten.

Erweiterung der Baumansicht zur Anzeige


der verfgbaren Gerte, die Daten fr die
Betrachtung aufgezeichnet haben.

3. Whlen Sie ein Gert aus der Liste


Gerteaufzeichnung aus.

Anzeige des Gerteprotokolls fr das


ausgewhlte Gert.

4. Um einen Datenbereich anzuzeigen, whlen Sie Auftragung des ausgewhlten


den Bereich aus der Dropdown-Liste
Datenbereichs.
Datenbereich aus.
5. Halten Sie die linke Maustaste gedrckt und
ziehen Sie einen Auswahlrahmen um den
Diagrammbereich, der vergrert dargestellt
werden soll.

Vergrerte Darstellung des


ausgewhlten Diagrammbereichs.

6. Um zur ursprnglichen Vollansicht


zurckzukehren, geben Sie Z auf Ihrer Tastatur
ein oder doppelklicken Sie auf das Diagramm.

Die Ansicht wird verkleinert.

7. Klicken Sie auf Datenpunkte, um die Tabelle fr


das ausgewhlte Intervalldatenprotokoll
anzuzeigen (siehe nachstehende Abbildung 37).

Einblendung der Tabelle fr das


ausgewhlte Intervalldatenprotokoll.

8. Um andere Gren anzuzeigen, klicken Sie auf


Neue Gre(n). Aktivieren Sie die
Kontrollkstchen der Gren, die Sie anzeigen
mchten, und klicken Sie auf bernehmen.

Aktivierung der Anzeige ausgewhlter


Gren.

Die von jedem Gert aufgezeichneten Daten werden auf einer Webseite in
einem Zeitgang-Diagrammformat dargestellt. Das Zeitgang-Diagramm ist
fr die Anzeige der Daten vom letzten vollstndigen Tag, von der letzten
vollstndigen Woche, vom letzten vollstndigen Monat oder aller Daten
vorkonfiguriert.
Energieparameter werden als kumulierte Werte aufgezeichnet, aber als
inkrementelle Werte auf der Basis von Intervallen angezeigt. Alle anderen
Parameter werden als aufgezeichneter Istwert protokolliert und angezeigt.
Abbildung 36: Diagramm des Intervalldatenprotokolls

Abbildung 37: Datenpunkttabelle des Intervalldatenprotokolls

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

41

PowerLogicTM Ethernet Gateway EGX300


berwachung

Abrufen eines Datenprotokolls

63230-319-216B3_DE
03/2013

Intervalldatenprotokolle knnen mit den Methoden in Tabelle 15 abgerufen


werden:
Tabelle 15: Methoden zum Abrufen von Intervalldatenprotokollen und
Dateiformate
Abrufmethode

Abgerufenes Dateiformat

FTP

CSV-Format (Variablen durch Komma getrennt)

Schaltflche Datenpunkte

HTML

Microsoft WebQuery

HTML

E-Mail

CSV

HTTP

CSV

Um eine Liste aller vorhandenen Protokolldateien anzuzeigen, fhren Sie


die Schritte 2 bis 4 im Abschnitt Abrufen eines Intervalldatenprotokolls
mit FTP auf Seite 43 aus. Die Dateien haben das Format
Gertename_Lokale ID.csv, wobei Gertename der dem Slave-Gert
zugewiesene Name und Lokale ID die ihm zugewiesene lokale IDNummer ist. Beispielsweise wrde ein Gert mit der Bezeichnung
Building 1 Utility Entrance mit der lokalen ID 3 eine Datei mit dem Namen
Building 1 Utility Entrance_3.csv erzeugen.
Werden Protokolldateien exportiert, werden das Datum und die Uhrzeit im
folgenden Format an den Dateinamen angehngt: _JJJJMMTTSSMMSS.
Beispiel: Building 1 Utility Entrance_3_20100218115216.csv. Damit wird
angezeigt, dass die Datei am 18. Februar 2010 um 11:52:16 Uhr exportiert
wurde.
Protokollformat

Die Daten werden in folgendem Format aufgezeichnet (siehe Abbildung 38


auf Seite 43):
Tabelle 16: Intervalldaten-Protokollformat
Zeile

Daten im CSV-Format

Beschreibung

(BOM)Gateway-Bezeichnung,
Diese Zeile enthlt die Spaltenberschriften fr
Gateway SN,Gateway-Adresse,
die Daten in Zeile 2.
Gertebezeichnung,lokale Gerte-ID,
Gertetypbezeichnung,Aufzeichnungsintervall
HINWEIS: (BOM) Die ersten drei
Bytes der Datei sind von einer
3-Zeichen-BOM (Byte Order Mark)
belegt (UTF-8-Codierung).

EGX300SD,23227,157.198.184.116, Diese Zeile enthlt die Daten ber das EGX und
Building 1 Utility Entrance,3,
das protokollierte Gert.
CM4000,15

Diese Zeile ist leer.

,,,Gren-ID 1,Gren-ID 2,
Gren-ID 3

Diese Zeile enthlt die Spaltenberschriften fr


die Gren-IDs in Zeile 5. Eine Gren-ID ist die
numerische Bezeichnung der aufzuzeichnenden
Gre. Der einer Gre zugewiesene Name
kann sich zwischen Gerten und Sprachen
geringfgig unterscheiden. Gren-IDs werden
fr die Identifizierung der Gre unabhngig von
Gert oder Sprache benutzt. Die ersten drei
Kommas dienen Layoutzwecken in einer
Tabellenkalkulations-anwendung.

,,,1617,1621,1625

Diese Zeile enthlt die Gren-IDs der


aufgezeichneten Werte.

Diese Zeile ist leer.

Fehler,UTC-Abweichung (Minuten), Diese Zeile enthlt die Spaltenberschriften der


lokale Uhrzeit,Scheinenergie (kVAh), aufgezeichneten Daten in Zeile 8 und darber.
Wirkenergie (kWh),Blindenergie
(kVArh)

8 und
Diese Zeilen enthalten die aufgezeichneten Daten.
darber 0,-300,2008-10-09 14:15:00,1400738.219,1201962.707,647069.906,15
0,-300,2008-10-09 14:20:00,1400758.260,1201980.725,647078.602,15
0,-300,2008-10-09 14:25:00,1400778.198,1201998.661,647087.233,15

Wenn Sie eine Tabellenkalkulationsanwendung fr die Betrachtung der


CSV-Datei benutzen, sollten die Daten wie in Abbildung 38 auf Seite 43
dargestellt werden.

42

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


berwachung

63230-319-216B3_DE
03/2013

Abbildung 38: Intervalldatenprotokoll geffnet in einer


Tabellenkalkulationsanwendung

Fehlercodes fr Datenprotokolle

Die nachstehenden Fehlercodes sind u. U. bei der Fehlerbehebung von


Datenprotokollen zu sehen (siehe Abbildung 36 auf Seite 41 und
Abbildung 37 auf Seite 41):
Fehlercode

Definition

Ergebnis

19

Ein Kommunikationsfehler ist aufgetreten (z. B.:


CRC-Fehler, Protokollfehler oder Ausnahme).

Die Aufzeichnung bleibt


eingeschaltet, sofern das
letzte Intervall nicht fehlt.

25

Zeitberschreitung; nach Sendung einer Anfrage


wurde innerhalb der zulssigen Zeit keine
entsprechende Antwort empfangen.

Die Aufzeichnung bleibt


eingeschaltet, sofern das
letzte Intervall nicht fehlt.

38

Ungltige Daten.

100

Die Intervallzeit ist abgelaufen, bevor Daten


aufgezeichnet werden konnten.

Intervall fehlt.

Wenden Sie sich an die technische Untersttzung, wenn Sie bei der Lsung
dieser oder anderer Fehlerbedingungen Hilfe brauchen.

Abrufen eines Intervalldatenprotokolls


mit FTP

Sie knnen FTP fr das Abrufen einer Datenprotokolldatei benutzen, indem


Sie ber FTP eine Verbindung mit dem EGX herstellen und die CSV-Datei
bertragen, wie es in den nachfolgenden Schritten dargestellt wird.
HINWEIS: Wenn Sie mchten, dass das EGX die Datenprotokolldatei
automatisch ber FTP bertrgt, muss der Gerteprotokollexport fr FTP
konfiguriert werden (siehe FTP-Export auf Seite 21).
Manahme

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Ergebnis

1. Erstellen Sie auf Ihrem Computer einen


Ordner, z. B. c:\egx_logs.

Erstellung eines Ordners zum Ablegen des


EGX-Datenprotokolls.

2. Starten Sie Windows Explorer, geben Sie


ftp:// und die IP-Adresse des EGX in die
Adressenleiste ein (z. B.
ftp://169.254.0.10) und drcken Sie die
Eingabetaste.

Einblendung des Dialogfelds Anmelden als.

3. Geben Sie in die Textfelder den


Benutzernamen Administrator und das
Administratorkennwort ein und klicken Sie
auf Anmelden.

Erffnung einer FTP-Sitzung mit dem EGX und


Einblendung der im EGX gespeicherten
Dateien.

4. Navigieren Sie zum Verzeichnis


/logging/data im EGX.

Einblendung des Datenprotokollverzeichnisses


im EGX.

5. Kopieren Sie die Protokolldatei und fgen


Sie diese dann in den im Schritt 1
erstellten Ordner ein.

Kopieren des Datenprotokolls in Ihren Ordner.

43

PowerLogicTM Ethernet Gateway EGX300


berwachung

Abrufen eines Intervalldatenprotokolls mit


der Schaltflche Datenpunkte

63230-319-216B3_DE
03/2013

Manahme

Ergebnis

1. Klicken Sie auf der Webseite


Einblendung eines neues Fensters mit Anzeige
Gerteaufzeichnung (siehe Abbildung 36 der aufgezeichneten Daten.
auf Seite 41) auf die Schaltflche
Datenpunkte.

Abrufen eines Intervalldatenprotokolls mit


Microsoft WebQuery

2. Fhren Sie die Tastenkombinationen


STRG+A und danach STRG+C aus.

Auswahl aller Daten und Kopieren der Daten in


die Zwischenablage.

3. ffnen Sie Excel und fhren Sie dann die


Tastenkombination STRG+V aus.

Einfgen der Daten in eine Excel-Tabelle.

Manahme

Ergebnis

1. Starten Sie den Webbrowser.

Einblendung des Webbrowsers.

2. berprfen Sie, ob die Protokolldatei


verfgbar ist. Geben Sie dazu die IPAdresse des EGX300 gefolgt von
/stream/devlog_data.html?device=x ein,
wobei x fr die lokale ID des Gerts steht.

Einblendung der Datenprotokoll-Seite.

3. Starten Sie Excel und klicken Sie auf


Einblendung des Excel-Dialogfeldes
Daten > Externe Daten importieren >
Neue Webabfrage.
Neue Webabfrage.
HINWEIS: Der dargestellte Pfad ist typisch
fr Microsoft Excel 2003.
4. Geben Sie im Dialogfeld Neue
ffnen der Datenprotokoll-Datei.
Webabfrage die in Schritt 2 eingegebene
Adresse des Protokolls ein und klicken Sie
auf Start.
5. Klicken Sie auf den uersten Pfeil, um
alle Daten zu markieren, und klicken Sie
dann auf Importieren.

Auswahl der Daten und Einblendung des


Dialogfelds Daten importieren.

6. Klicken Sie auf OK.

Import der Daten.

HINWEIS: Wenn Sie jedes Mal beim ffnen der Excel-Tabelle die neuesten
Daten anzeigen mchten, klicken Sie auf Eigenschaften im Dialogfeld
Daten importieren und whlen Sie Aktualisieren beim ffnen der Datei
aus.

Abrufen eines Intervalldatenprotokolls ber


E-Mail

Das EGX muss fr die Sendung von Datenprotokollen an eine E-MailAdresse konfiguriert sein. Fr weitere Informationen hierzu siehe E-MailExport auf Seite 19.

Abrufen eines Intervalldatenprotokolls ber


HTTP

Das EGX muss so konfiguriert werden, dass es Datenprotokolle an einen


Webserver bertrgt. Fr weitere Informationen hierzu siehe HTTP-Export
auf Seite 22.

44

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


berwachung

63230-319-216B3_DE
03/2013

bersichtsgerteseiten

Auf den bersichtsgerteseiten befinden sich bersichten ber ein oder


mehrere ausgewhlte Gerte.
Manahme
1. Klicken Sie im berwachungsmen auf
Gerteaufzeichnung.

Ergebnis
Erweiterung der Baumansicht fr die
Auswahlmglichkeiten der
Gerteaufzeichnung.

2. Klicken Sie unter Gerteaufzeichnung auf


bersichtsgerteseiten.
3. Klicken Sie unter bersichtsgerteseiten Einblendung der Setup-Seite fr Mehrere
auf Mehrere Gerte, Einzelgre.
Gerte, Einzelgre.
4. Whlen Sie ein Gert aus der Liste
Verfgbare Gerte aus.

Auswahl der Gerte fr die bersichtsoptionen.

HINWEIS: Es knnen maximal vier Gerte


ausgewhlt werden.
5. Whlen Sie eine Gre aus der Liste
Verfgbare Gren aus.

Auswahl der anzuzeigenden Gre fr jedes


ausgewhlte Gert.

HINWEIS: Es sind nur Gren verfgbar,


die alle ausgewhlten Gerte gemeinsam
haben.
6. Klicken Sie auf Weiter.

Einblendung der Trendseite Mehrere Gerte,


Einzelgre.

7. Halten Sie die linke Maustaste gedrckt


und ziehen Sie einen Auswahlrahmen um
den Diagrammbereich, der vergrert
dargestellt werden soll.

Vergrerte Darstellung des ausgewhlten


Diagrammbereichs.

8. Um zur ursprnglichen Vollansicht


Die Ansicht wird verkleinert.
zurckzukehren, geben Sie Z auf Ihrer
Tastatur ein oder doppelklicken Sie auf das
Diagramm.

Die von den ausgewhlten Gerten aufgezeichnete Gre wird auf einer
Webseite in einem Zeitgang-Diagrammformat dargestellt. Das ZeitgangDiagramm ist fr die Anzeige der Daten vom letzten vollstndigen Tag, von
der letzten vollstndigen Woche, vom letzten vollstndigen Monat oder aller
Daten vorkonfiguriert.
Energieparameter werden als inkrementelle Werte auf der Basis von
Intervallen angezeigt. Alle anderen Parameter werden als aufgezeichneter
Istwert protokolliert und angezeigt.
Abbildung 39: Setup-Seite Mehrere Gerte, Einzelgre

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

45

PowerLogicTM Ethernet Gateway EGX300


berwachung

63230-319-216B3_DE
03/2013

Abbildung 40: Trendseite Mehrere Gerte, Einzelgre

Instrumententafeln

Das EGX untersttzt vier Kategorien von Instrumententafeln, die zeitlich


summierte Energieverbrauchsdaten anzeigen. Die Instrumententafeln und
ihre Teilstze sind in Tabelle 17 aufgelistet.
Tabelle 17: Instrumententafelarten
Instrumententafel
Nach Stunden

Teilsatz
Vortag nach Stunden
Aktueller Tag nach Stunden
Aktueller Tag ber Vortag nach Stunden

Nach Tagen

Vorwoche nach Tagen


Aktuelle Woche nach Tagen
Aktuelle Woche ber Vorwoche nach Tagen
Vormonat nach Tagen
Aktueller Monat nach Tagen
Aktueller Monat ber Vormonat nach Tagen

Nach Wochen

Vorquartal nach Wochen


Aktuelles Quartal nach Wochen
Aktuelles Quartal ber Vorquartal nach Wochen
Zurckliegende 13 Wochen nach Wochen

Nach Monaten

Vorjahr nach Monaten


Aktuelles Jahr nach Monaten
Aktuelles Jahr ber Vorjahr nach Monaten
HINWEIS: Bei dieser Option muss jede
Gertedatenprotokolldatei gengend Kapazitt fr die
Verlaufsdaten von zwei Jahren haben. Fr weitere
Informationen siehe Intervalldatenaufzeichnung auf
Seite 17.
Zurckliegende 12 Monate nach Monat

46

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


berwachung

63230-319-216B3_DE
03/2013

Anzeigen einer Instrumententafel


Manahme

Ergebnis

1. Klicken Sie im berwachungsmen auf


Instrumententafeln.

Anzeige des Instrumententafelmens (siehe


Abbildung 41).

2. Whlen Sie ein Gert aus der DropdownListe Gert aus.

Auswahl des Gerts zur Anzeige von Daten.

HINWEIS: Die Instrumententafel zeigt


Daten eines Einzelgerts an.
3. Whlen Sie eine Gre aus der Dropdown- Auswahl der grafisch darzustellenden Gre.
Liste Grenbezeichnung aus.
HINWEIS: Die Grenauswahl ist auf
inkrementelle Verbrauchsgren des
Gerts beschrnkt.
4. Whlen Sie die Zeitparameter aus der
Dropdown-Liste Uhrzeit aus.

Auswahl des Zeitbereichs der aufgezeichneten


Daten fr die ausgewhlte Gre.

5. Klicken Sie auf bernehmen.

Anzeige der ausgewhlten Instrumententafel.

Abbildung 41: Men Instrumententafeln

Die Daten jeder Instrumententafel werden als Balkendiagramme auf einer


Webseite angezeigt. Wenn Sie mit dem Mauszeiger ber einen Balken im
Diagramm gehen, wird der Datenpunktwert fr das ausgewhlte Intervall
angezeigt (Abbildung 42).
Abbildung 42: Instrumententafeldiagramm

Abbildung 43: Instrumententafeltabelle

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

47

PowerLogicTM Ethernet Gateway EGX300


berwachung

Abrufen von Instrumententafeldaten mit der


Schaltflche Datenpunkte

63230-319-216B3_DE
03/2013

Sie knnen Daten einer Instrumententafel wie nachstehend beschrieben in


einer Tabellenkalkulationsanwendung speichern.
Manahme

Ergebnis

1. Klicken Sie in der Instrumententafel mit


Anzeige der Datenpunkte fr die ausgewhlte
den gewnschten Daten auf Datenpunkte. Instrumententafel (Abbildung 43 auf Seite 47).
2. Drcken Sie STRG+A und dann STRG+C. Auswahl aller Daten und Kopieren der Daten in
die Zwischenablage.
3. ffnen Sie Excel und drcken Sie dann
STRG+V.

Speichern eines Instrumententafel-Links

Einfgen der Daten in eine Excel-Tabelle.

Sie knnen einen Link zu einer Instrumententafel speichern, um diese nicht


jedesmal vom Hauptmen aus aufrufen zu mssen. Tabelle 18 beschreibt
die Methoden fr die Speicherung eines Instrumententafel-Links.
Tabelle 18: Speichern eines Instrumententafel-Links
Option

Speichern einer Instrumententafel als ein Bild

Beschreibung

Einstellung

Browser-Lesezeichen

Damit knnen Benutzer ber den


Computer auf die gespeicherte
Instrumententafel zugreifen, auf
dem das Lesezeichen erstellt wurde.

Befolgen Sie die Anweisungen


zum Erstellen eines
Lesezeichens in Ihrem
bevorzugten Browser.

Unterlagenlink

Damit knnen EGX-Benutzer ber


die Unterlagenseite auf eine
gespeicherte Instrumententafel
zugreifen.

Fr das Erstellen eines URLZugriffs siehe Unterlagenlinks


auf Seite 27.

E-Mail

Damit knnen Benutzer eine


Der E-Mail-Empfnger muss
Instrumententafel-URL im Hauptteil zum Anzeigen einer
einer E-Mail versenden.
Instrumententafel ein EGXBenutzerkonto haben. Siehe
Benutzerkonten auf Seite 28.

Mit den folgenden Schritten knnen Sie ein Instrumententafeldiagramm als


ein Bild speichern.
Manahme

Ergebnis

1. Befolgen Sie die Schritte unter Anzeigen


einer Instrumententafel auf Seite 47.

Anzeige des Instrumententafeldiagramms.

2. Klicken Sie auf Als Bild anzeigen... in der


rechten oberen Ecke der Seite
(Abbildung 44 auf Seite 49).

ffnen eines neuen Fensters, in dem die


Instrumententafel als Bild angezeigt wird.

3. Rechtsklicken Sie auf das Bild und whlen


Sie Bild speichern unter... aus.

ffnen des Dialogfeldes Speichern unter.

4. Geben Sie einen Dateinamen ein, whlen


Sie einen Speicherort aus und klicken Sie
auf Speichern.

Speicherung des Bildes.

HINWEIS: PNG-Bild ist der voreingestellte


Dateityp. Um den Dateityp zu ndern,
ersetzen Sie .png im Dateinamenfeld durch
Ihre bevorzugte Erweiterung.

HINWEIS: Diese Funktion ist bei Internet Explorer, Version 8 und frheren
Versionen nicht verfgbar.

48

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B3_DE
03/2013

PowerLogicTM Ethernet Gateway EGX300


berwachung

Abbildung 44: Speichern eines Instrumententafelbildes

Systemzugangspunkt

Das EGX kann andere EGX300-Gerte und andere Schneider ElectricGerte, die am Netzwerk angeschlossen sind, erkennen und
entsprechende Links zur Verfgung stellen. Damit wird ein Zugangspunkt
fr ein System vernetzter Schneider Electric-Gerte bereitgestellt.
Die Seite Systemzugangspunkt listet jedes erkannte Schneider ElectricGert in Form eines Hyperlinks auf. Wenn Sie mit dem Mauszeiger ber ein
Gert in der Liste gehen, werden links neben der Liste zustzliche Details
zum Gert angezeigt.
Klicken Sie auf ein Gert, um die Anmeldeseite fr dieses Gert aufzurufen.

Abbildung 45: Seite Systemzugangspunkt mit Detailanzeige

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

49

PowerLogicTM Ethernet Gateway EGX300


Unterlagen

UNTERLAGEN

63230-319-216B3_DE
03/2013

ber die Unterlagen-Seite knnen Sie auf Informationen zugreifen, die in


Form von Dateien und URL-Links im EGX gespeichert sind.
Informationen ber das Laden von Unterlagenlinks finden Sie unter
Unterlagenlinks auf Seite 27.
Um einen Unterlagenlink zu ffnen, klicken Sie auf den Link Unterlagen
oben auf der Seite und whlen Sie danach den gewnschten Link aus.

Abbildung 46: Unterlagenseite

STEUERUNG

Das EGX kann manuell eine oder mehrere Gruppen vordefinierter


Rckstellbefehle pro Gertetyp ausfhren.
Manahme

Ergebnis

1. Klicken Sie im Men Steuerung auf


Resets.

Einblendung der Seite Resets.

2. Whlen Sie in der Liste unter Resets das Auswahl eines Gerts und Anzeige seiner
Rckstelloptionen sowie des Datums und der
Gert aus, das Sie betrachten oder
Uhrzeit der letzten Rckstellung.
zurckstellen mchten.
3. Whlen Sie die Gerteparameter aus, die
Sie zurckstellen mchten.

Festlegung des am ausgewhlten Gert


durchzufhrenden Rckstellvorgangs.

4. Klicken Sie auf Rcksetzen.

Senden der Rcksetzbefehle fr die


geforderten Rckstellvorgnge an das
ausgewhlte Gert und Anzeige des Status.

Abbildung 47: Resets

HINWEIS: Das Datum und die Uhrzeit, die fr den Parameter


Datum/Uhrzeit angezeigt werden, entsprechen dem Datum und der
Uhrzeit im ausgewhlten Gert. Wenn dieser Parameter fr eine
Rckstellung ausgewhlt ist, werden das Datum und die Uhrzeit des EGX
an das Gert bertragen.
Die Werte fr Datum/Uhrzeit werden nur dann gemeldet, wenn das Gert
sie untersttzt. Wenn beispielsweise das Gert den Min/Max-Wert fr
Datum/Uhrzeit letzter Reset nicht untersttzt, wird hier kein Eintrag fr den
Wert Min/Max angezeigt.

50

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Diagnose

63230-319-216B3_DE
03/2013

DIAGNOSE

Fr den Zugang auf die Diagnose-Webseiten-Links klicken Sie auf


Diagnose in der EGX-Menleiste.

Statistik

Diese Seite zeigt seit der letzten Aktivierung des EGX kumulierte Werte an.
Wenn die Stromversorgung des EGX ausfllt, oder das Gert wegen einer
Konfigurationsnderung oder eines anderen Ereignisses zurckgestellt
wird, werden alle kumulierten Werte auf null zurckgestellt.
Manahme

Ergebnis

1. Klicken Sie im Diagnose-Men auf


Statistik.

Einblendung der Statistikseite (siehe


nachstehende Abbildung 48).

2. Zeigen Sie die Daten an.

Weitere Informationen hierzu finden Sie


nachstehend unter Statistik auswerten auf
Seite 52.

3. Klicken Sie auf Rcksetzen.

Rcksetzung der kumulativen Diagnosedaten


des EGX auf 0.

Abbildung 48: Seite Statistik

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

51

PowerLogicTM Ethernet Gateway EGX300


Diagnose

63230-319-216B3_DE
03/2013

Statistik auswerten
Statistik

Beschreibung

Ethernet
Verbindungsstatus

Status-Zeichenkette, die die Geschwindigkeit und die


Duplex-Einstellung darstellt, die zur Kommunikation mit
dem Verbindungspartner benutzt werden.

Rahmen ohne Fehler gesendet

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen erfolgreich gesendet wird.

Kollisionen

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen aufgrund der Erkennung einer Kollision neu
bertragen wird.

Zu hohe Anzahl an Kollisionen

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen aufgrund der Erreichung des maximalen
Kollisionsstatus auf der Basis des Truncated Binary
Exponential Backoff-Algorithmus nicht gesendet werden
kann.

Rahmen ohne Fehler empfangen

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen erfolgreich empfangen wird.

CRC-Fehler

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen empfangen wird, dessen Prfsumme/CRC nicht
mit dem berechneten Wert bereinstimmt.

Synchronisierfehler

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen empfangen wird, dessen Prfsumme/CRC nicht
mit einer 8-Bit-Rahmenbegrenzung endet.

Rahmen zu lang

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen empfangen wird, der die in den
Standardeinstellungen festgelegte maximale Lnge
berschreitet (Rahmen lnger als 1518 Byte).

Rahmen zu kurz

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen empfangen wird, der die in den
Standardeinstellungen festgelegte minimale Lnge
unterschreitet (Rahmen krzer als 64 Byte).

Modbus-TCP/IP
Server
Rahmen gesendet

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen gesendet wird.

Rahmen empfangen

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen empfangen wird.

Protokollfehler

Zhler, der sich jedes Mal um eins erhht, wenn eine


Nachricht mit einem falschen Format empfangen wird.

Aktive Verbindungen1

Statuswert, der die Anzahl der Verbindungen darstellt, die


zum Zeitpunkt der Aktualisierung der Diagnoseseite aktiv
sind. Es werden maximal 64 Verbindungen untersttzt.
Durch Klicken auf Aktive Verbindungen wird ein neues
Fenster mit einer Liste aller aktiven Client-Verbindungen
geffnet.

Summe der Verbindungen

Zhler, der sich jedes Mal um eins erhht, wenn eine


Verbindung zum EGX aufgebaut wird.

Maximale Anzahl Verbindungen

Statuswert, der die maximale Anzahl von Verbindungen


darstellt, die aufgebaut werden.

Eingegangene Lesenachrichten

Zhler, der sich jedes Mal um eins erhht, wenn eine


Lesenachricht empfangen wird.

Eingegangene Schreibnachrichten

Zhler, der sich jedes Mal um eins erhht, wenn eine


Schreibnachricht empfangen wird.

Abgegangene Antwortnachrichten

Zhler, der sich jedes Mal um eins erhht, wenn eine


Antwortnachricht gesendet wird.

Client
Rahmen gesendet

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen gesendet wird.

Rahmen empfangen

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen empfangen wird.

Protokollfehler

Zhler, der sich jedes Mal um eins erhht, wenn eine


Nachricht mit einem falschen Format empfangen wird.

Klicken Sie fr weitere ausfhrliche Informationen auf den Link.

52

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Diagnose

63230-319-216B3_DE
03/2013

Statistik

Beschreibung

Zeitberschreitungen

Zhler, der sich jedes Mal um eins erhht, wenn eine


Anforderungsnachricht gesendet wird, ohne dass eine
entsprechende Antwortnachricht innerhalb der zulssigen
Zeit empfangen wird. Zeitberschreitungen sind
normalerweise das Ergebnis von Konfigurationsfehlern
oder einer fehlenden Reaktion des Gerts.

Verbindungszeitberschreitungen

Zhler, der sich bei jedem Verbindungsausfall um eins


erhht.

Ausnahmen empfangen

Zhler, der sich jedes Mal um eins erhht, wenn eine


Ausnahme empfangen wird.

Abgegangene Lesenachrichten

Zhler, der sich jedes Mal um eins erhht, wenn eine


Lesenachricht gesendet wird.

Abgegangene Schreibnachrichten

Zhler, der sich jedes Mal um eins erhht, wenn eine


Schreibnachricht gesendet wird.

Eingegangene Antwortnachrichten

Zhler, der sich jedesmal um eins erhht, wenn eine


Antwortnachricht empfangen wird.

Details1

Ausfhrliche Tabelle mit Fern- und seriellen Statistiken pro


Gert.

Serielle Schnittstelle
Rahmen gesendet

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen gesendet wird.

Rahmen empfangen

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen empfangen wird.

CRC-Fehler

Zhler, der sich jedes Mal um eins erhht, wenn eine


Nachricht empfangen wird, deren CRC nicht mit dem
berechneten Wert bereinstimmt. Dies ist normalerweise
die Folge von Verdrahtungsproblemen.

Protokollfehler

Zhler, der sich jedes Mal um eins erhht, wenn eine


Nachricht mit einem falschen Format empfangen wird.

Zeitberschreitungen

Zhler, der sich jedes Mal um eins erhht, wenn eine


Anforderungsnachricht gesendet wird, ohne dass eine
entsprechende Antwortnachricht innerhalb der zulssigen
Zeit empfangen wird. Zeitberschreitungen sind
normalerweise das Ergebnis von Konfigurationsfehlern
oder einer fehlenden Reaktion des Gerts.

Ausnahmen empfangen

Zhler, der sich jedes Mal um eins erhht, wenn eine


Ausnahme empfangen wird.

Abgegangene Lesenachrichten

Zhler, der sich jedes Mal um eins erhht, wenn eine


Lesenachricht gesendet wird.

Abgegangene Schreibnachrichten

Zhler, der sich jedes Mal um eins erhht, wenn eine


Schreibnachricht gesendet wird.

Eingegangene Lesenachrichten

Zhler, der sich jedes Mal um eins erhht, wenn eine


Lesenachricht empfangen wird.

Eingegangene Schreibnachrichten

Zhler, der sich jedes Mal um eins erhht, wenn eine


Schreibnachricht empfangen wird.

Details1

Ausfhrliche Tabelle mit Fern- und seriellen Statistiken pro


Gert.

HTTP-Server
Rahmen gesendet

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen gesendet wird.

Rahmen empfangen

Zhler, der sich jedes Mal um eins erhht, wenn ein


Rahmen empfangen wird.

Aktive Verbindungen1

Statuswert, der die Anzahl der Verbindungen darstellt, die


zum Zeitpunkt der Aktualisierung der Diagnoseseite aktiv
sind. Es werden maximal 20 Verbindungen untersttzt.
Klicken Sie auf Aktive Verbindungen, um ein neues
Fenster mit einer Liste aller aktiven Client-Verbindungen zu
ffnen.

Summe der Verbindungen1

Zhler, der sich jedes Mal um eins erhht, wenn eine


Verbindung zum EGX aufgebaut wird.

Maximale Anzahl Verbindungen

Statuswert, der die maximale Anzahl von Verbindungen


darstellt, die aufgebaut werden.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Klicken Sie fr weitere ausfhrliche Informationen auf den Link.

53

PowerLogicTM Ethernet Gateway EGX300


Diagnose

63230-319-216B3_DE
03/2013

Statistik

Beschreibung

Gateway-Informationen
Firmwareversion

Das ist die Firmwareversion, die im EGX installiert ist.

System-Leerlaufzeit

Prozentsatz von 0 % bis 100 %, der die durchschnittliche


ungenutzte Prozessorzeit anzeigt.

MAC-Adresse

Unverwechselbare Ethernet-Hardware-Adresse eines EGX

Seriennummer

Seriennummer des EGX

Modellnummer

Modellnummer des EGX

Hardwareversion

EGX-Hardwareversion

Herstellungsdatum

Datum, an dem das EGX hergestellt wurde.

HTTP-Client
Senden OK

Zhler, der sich jedes Mal um eins erhht, wenn eine Datei
erfolgreich an den HTTP-Server gesendet wird.

Verbindungsfehler

Zhler, der sich jedes Mal um eins erhht, wenn das EGX
keine Verbindung zum HTTP-Server herstellen kann.

Authentifizierungsfehler

Zhler, der sich jedes Mal um eins erhht, wenn der HTTPServer den Benutzernamen bzw. das Kennwort nicht
authentifizieren kann.

Sendefehler

Zhler, der sich jedes Mal um eins erhht, wenn eine Datei
nicht zum HTTP-Server gesendet werden kann.

Allgemeiner Fehler

Zhler, der sich jedes Mal um eins erhht, wenn eine Datei
nicht gesendet werden kann, weil das EGX den Vorgang
nicht einleiten kann.

FTP-Client
Senden OK

Zhler, der sich nach jeder erfolgreichen bertragung an


einen FTP-Server um eins erhht.

Verbindungsfehler

Zhler, der sich jedes Mal um eins erhht, wenn das EGX
keine Verbindung zum FTP-Server herstellen kann.

Authentifizierungsfehler

Zhler, der sich jedes Mal um eins erhht, wenn der FTPServer den Benutzernamen bzw. das Kennwort nicht
authentifizieren kann.

Verzeichnisfehler

Zhler, der sich jedes Mal um eins erhht, wenn der FTPServer das angeforderte Verzeichnis nicht lokalisieren
kann.

Sendefehler

Zhler, der sich jedes Mal um eins erhht, wenn eine Datei
nicht zum FTP-Server gesendet werden kann.

Allgemeiner Fehler

Zhler, der sich jedes Mal um eins erhht, wenn eine Datei
nicht gesendet werden kann, weil das EGX den Vorgang
nicht einleiten kann.

SMTP-Client
Senden OK

Zhler, der sich jedes Mal um eins erhht, wenn eine


E-Mail erfolgreich an den SMTP-Server gesendet wird.

Verbindungsfehler

Zhler, der sich jedes Mal um eins erhht, wenn das EGX
keine Verbindung zum SMTP-Server herstellen kann.

Authentifizierungsfehler

Zhler, der sich jedes Mal um eins erhht, wenn der


SMTP-Server den Benutzernamen bzw. das Kennwort
nicht authentifizieren kann.

Sendefehler

Zhler, der sich jedes Mal um eins erhht, wenn eine


E-Mail nicht an den SMTP-Server gesendet werden kann.

Allgemeiner Fehler

Zhler, der sich jedes Mal um eins erhht, wenn das


Erstellen einer E-Mail durch das EGX fehlschlgt und die
E-Mail nicht gesendet werden kann.

Dateisystem
Kapazitt insgesamt

Gesamtkapazitt des EGX-Speichers in Kilobyte.

Freie Kapazitt

Gesamter ungenutzter Speicherplatz im EGX in Kilobyte.

1Klicken

54

Sie fr weitere ausfhrliche Informationen auf den Link.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Diagnose

63230-319-216B3_DE
03/2013

Gerteregister lesen

Diese Option ermglicht es, angeschlossene lokale und entfernte Gerte


mit dem EGX auszulesen.
Abbildung 49: Seite Gerteregister lesen

Manahme

Ergebnis

1. Klicken Sie im Diagnose-Men auf


Gerteregister lesen.

Einblendung der Seite Gerteregister lesen.

2. Geben Sie die lokale Gerte-ID ein (oder


whlen Sie sie aus der definierten
Gerteliste aus). Geben Sie die
Startdatenadresse und die Anzahl der zu
lesenden Register ein.

Eingabe der vom angegebenen Gert zu


lesenden Register.

3. Whlen Sie einen Datentyp aus.

Auswahl des entsprechenden Datentyps.

4. Um die Art der Datenanzeige in der Spalte Auswahl der Art der Datenanzeige.
Wert zu ndern, whlen Sie Dezimal,
Hexadezimal, Binr oder ASCII aus.
5. Klicken Sie auf Lesen.

Lesen der Gerteregister gem der


ausgewhlten Konfiguration.

Tabelle 19: Einstellungen des EGX zum Lesen von Gerteregistern


Option

Beschreibung

Werkeinstellung

Gertebezeichnung Damit wird ein zu lesendes Gert aus der Liste


vorher hinzugefgter Gerte ausgewhlt. Ein Gert,
das nicht in der Gerteliste definiert ist, kann durch
Eingabe seiner lokalen ID gelesen werden.
Gerte-ID

Adresse (lokale ID) des auszulesenden Gerts.

Startregister

Erstes zu lesendes Register.

Anzahl Register

Anzahl der zu lesenden Register (1 bis 125).

Spalte Register

Auflistung der Registernummern.

Spalte Wert

Auflistung der fr ein Register gespeicherten Daten.


Die abgerufenen Werte hngen vom Gert ab, das
mit dem EGX verbunden ist. Weitere Informationen
ber gespeicherte Registerwerte finden Sie in den
Unterlagen des verbundenen Gerts.

Datentyp

Auswahl von Halteregister, Eingangsregister,


Ausgangsspulen, Eingangsspulen bzw. Gerte-ID.

Optionen Dezimal, Legt fest, wie Daten in der Spalte Wert angezeigt
Hexadezimal, Binr werden sollen.
bzw. ASCII

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

1
1000
10

Halteregister
Dezimal

55

PowerLogicTM Ethernet Gateway EGX300


Diagnose

63230-319-216B3_DE
03/2013

Kommunikationsprfung
Automatische Kommunikationsprfung

Whrend der Anzeige der Echtzeitdatenansichten fhrt das EGX standardmig alle 15 Minuten eine automatische Kommunikationsprfung aus. (Um
die Zeitsteuerung zu verndern, siehe Prferenzen auf Seite 31.) Damit
wird die Strungsfreiheit der Kommunikation mit allen Gerten berprft, die
im EGX konfiguriert sind, und innerhalb der Browsersitzung der
Wiederaufbau der Kommunikation zu jedem Gert versucht, das mit
Auer Betrieb gekennzeichnet ist.

Manuelle Kommunikationsprfung

In bestimmten Fllen mchten Sie mglicherweise nicht auf die


automatische Kommunikationsprfung warten und mssen die Ausfhrung
der Prfung manuell erzwingen.
Manahme

Ergebnis

1. Klicken Sie im Diagnose-Men auf


Kommunikationsprfung.

Einblendung der Seite


Kommunikationsprfung.

2. Klicken Sie auf Gertestatus berprfen. Damit wird eine Kommunikationsprfung


ausgefhrt. Gerte, mit denen eine
Kommunikation mglich ist, zeigen Bestanden
in der Spalte Kommunikation und In Betrieb
in der Spalte Status an. Gerte, mit denen
keine Kommunikation mglich ist, zeigen
Fehlgeschlagen in der Spalte
Kommunikation und Auer Betrieb in der
Spalte Status an, wenn die
Verbindungsaufnahme mehrmals
fehlgeschlagen ist.

Abbildung 50: Seite Kommunikationsprfung

56

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Wartung

63230-319-216B3_DE
03/2013

WARTUNG

Mit dem Wartungsprotokoll knnen die Wartungsarbeiten dokumentiert


werden, die am EGX, an den angeschlossenen Gerten oder an der
Anlage, zu der das EGX gehrt, durchgefhrt werden. Jeder Eintrag wird
mit Datum und Uhrzeit und dem Namen des betreffenden Benutzers
protokolliert.
Dieses Protokoll listet auch automatisch Systemaktivitten auf, zum
Beispiel die Aktivierung bzw. Deaktivierung von Funktionen. Sie mssen
dafr keine Eintrge vornehmen.
Zudem listet dieses Protokoll alle Aktivitten auf, die fr das
Wartungsprotokoll auf der Setup-Seite Prfpfad festgelegt wurden
(siehe Prfpfad auf Seite 33).
Manahme

Ergebnis

1. Klicken Sie im Wartungsmen auf


Wartungsprotokoll.

Einblendung der Seite Wartungsprotokoll.

2. Aktivieren Sie das Kontrollkstchen


Lschen neben dem Eintrag, den Sie
lschen mchten. Klicken Sie danach auf
Eintrge lschen.

Lschen des ausgewhlten Eintrags.

3. Klicken Sie auf Protokoll lschen, um alle Lschen des Wartungsprotokolls.


Eintrge im Wartungsprotokoll zu lschen.
4. Klicken Sie auf Protokolleintrag
hinzufgen und geben Sie den
Wartungstext in das Textfeld
Eingabedetail ein (siehe nachstehende
Abbildung 52), um einen neuen
Protokolleintrag hinzuzufgen.

Einblendung der Seite Protokolleintrag


hinzufgen, in die der Benutzer
Wartungsdetails eingeben kann.

Abbildung 51: Wartungsprotokoll

Abbildung 52: Protokolleintrag hinzufgen

FIRMWARE

Die Firmware der EGX-Gerte kann mit FTP (File Transfer Protocol)
aktualisiert werden. Das neueste Firmware-Update finden Sie unter
www.schneider-electric.com, oder fragen Sie Ihren zustndigen
Vertriebsmitarbeiter danach.

Firmwareversion feststellen

Das EGX enthlt zwei Firmware-Komponenten: die ausfhrbare


Binrkomponente und die Datentrgerabbildkomponente.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

57

PowerLogicTM Ethernet Gateway EGX300


Firmware

Firmwareversion der ausfhrbaren


Binrkomponente

63230-319-216B3_DE
03/2013

Manahme

Ergebnis

1. ffnen Sie den Webbrowser und melden Sie


sich beim EGX an.

Einblendung der EGX-Startseite.

2. Suchen Sie die Firmwareversion in der


unteren linken Ecke der Seite.

Feststellung der Firmware-Version des


EGX.

HINWEIS: Wenn Sie die Firmware krzlich


aktualisiert haben, drcken Sie F5, um die
Webseite und die angezeigte
Firmwarenummer zu aktualisieren.
3. Alternativ knnen Sie auf Diagnose >
Statistik klicken, um die Firmwareversion im
Abschnitt Gateway-Informationen zu finden.

Alternative Feststellung der


Firmwareversion des EGX.

Datentrgerabbildkomponente
Manahme

Ergebnis

1. ffnen Sie den Webbrowser und melden Sie


sich beim EGX an.

Einblendung der EGX-Startseite.

2. Suchen Sie die Firmwareversion in der


unteren linken Ecke der Seite.

Feststellung der DatentrgerabbildFirmware-Version des EGX.

HINWEIS: Wenn Sie die Firmware krzlich


aktualisiert haben, drcken Sie F5, um die
Webseite und die angezeigte
Firmwarenummer zu aktualisieren.
3. Alternativ knnen Sie ber FTP auf das EGX
zugreifen. Suchen Sie die Datei version.txt
und doppelklicken Sie anschlieend auf die
Datei, um sie zu ffnen.

Feststellung der DatentrgerabbildFirmware-Version des EGX.

Neue Firmware herunterladen


Manahme

Ergebnis

1. Starten Sie den Webbrowser, geben Sie


www.powerlogic.com in das
Adressentextfeld ein und drcken Sie die
Eingabetaste.

Einblendung der PowerLogic-Website.

2. Whlen Sie Ihr Land aus und klicken Sie auf


Go (Start).

Einblendung der PowerLogic-Website fr Ihr


Land.

HINWEIS: Wenn Sie United States


ausgewhlt haben, fahren Sie mit Schritt 3
fort. Anderenfalls folgen Sie der
lnderspezifischen Navigation, um die EGXFirmware zu erhalten.

58

3. Klicken Sie auf Support > Downloads.

Einblendung der Download-Seite.

4. Klicken Sie auf den Link EGX300 Firmware.

Einblendung der Seite EGX300 Firmware.

5. Klicken Sie auf den Link mit der FirmwareDatei (egxxxxx.bin, wobei xxxx die FirmwareVersionsnummer ist) und dann auf
Speichern.

Einblendung des Dialogfelds fr den DateiDownload und dann des Dialogfeldes


Speichern unter.

6. Whlen Sie im Dialogfeld Speichern unter


das lokale Verzeichnis bzw. den Dateiordner
aus, in dem die Firmwaredatei gespeichert
werden soll, oder erstellen Sie ein lokale
Verzeichnis bzw. einen Dateiordner, und
klicken Sie auf Speichern.

Speicherung der Firmwaredatei im


angegebenen Verzeichnis bzw. Ordner.

7. Klicken Sie auf den Link egxxxxx.upd (wobei


xxxx die Firmware-Nummer ist) und dann auf
Speichern.

Einblendung des Dialogfelds fr den DateiDownload und dann des Dialogfeldes


Speichern unter.

8. Whlen Sie im Dialogfeld Speichern unter


das lokale Verzeichnis bzw. den Dateiordner
aus, in dem die Firmwaredatei gespeichert
werden soll, oder erstellen Sie ein lokale
Verzeichnis bzw. einen Dateiordner, und
klicken Sie auf Speichern.

Speicherung der Firmwaredatei (.upd) im


angegebenen Verzeichnis bzw. Ordner.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Firmware

63230-319-216B3_DE
03/2013

Firmware aktualisieren

Whrend die Firmware heruntergeladen wird, darf die Stromversorgung des


EGX nicht unterbrochen werden. Wenn whrend des Programmiervorgangs
die Stromversorgung unterbrochen wird, funktioniert das EGX nicht mehr.
Die Status-LED blinkt whrend des Programmiervorgangs schnell. Wenn
das Blinken aufhrt, ist die Programmierung abgeschlossen.
Manahme

Ergebnis

1. Starten Sie Windows Explorer, geben Sie


ftp:// und die IP-Adresse des EGX in das
Adressentextfeld ein (z. B.
ftp://169.254.0.10) und drcken Sie die
Eingabetaste.

Einblendung des Dialogfelds Anmelden als.

2. Geben Sie in die Textfelder den


Benutzernamen Administrator und das
Administratorkennwort ein und klicken Sie
auf Anmelden.

Erffnung einer FTP-Sitzung mit dem EGX.

3. Suchen Sie das Verzeichnis bzw. den


Ordner, in dem die Firmwaredatei
(egxxxxx.bin) auf Ihrem Computer
gespeichert ist, rechtsklicken Sie auf die
Datei und klicken Sie dann auf Kopieren.

Kopieren der Firmware-Datei in die


Zwischenablage.

4. Rechtsklicken Sie in das WindowsExplorer-Fenster und klicken Sie


anschlieend auf Einfgen.

Kopieren der Firmware auf das EGX und


Neustart des EGX.

HINWEIS: Anstelle von Kopieren und


Einfgen knnen Sie die Datei auch per
Drag-and-Drop in Windows Explorer
bertragen.

HINWEIS: Die LED


Spannungsversorgung/Status blinkt
schnell, whrend die Datei auf das EGX
bertragen und programmiert wird. Nach
Beendigung der Programmierung wird das
EGX zurckgestellt. Die Programmierung
dauert zwischen 1,5 und 2 Minuten.

5. Suchen Sie die gespeicherte


Kopiert die Aktualisierungsdatei in die
Aktualisierungsdatei (egxxxxx.upd) auf
Zwischenablage.
Ihrem Computer, rechtsklicken Sie auf den
Dateinamen und klicken Sie dann auf
Kopieren.
6. Rechtsklicken Sie in das WindowsExplorer-Fenster und klicken Sie
anschlieend auf Einfgen.

Kopieren der Datei in das EGX und Neustart


des EGX.

HINWEIS: Anstelle von Kopieren und


Einfgen knnen Sie die Datei auch per
Drag-and-Drop in Windows Explorer
bertragen.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

7. Um zu kontrollieren, ob die
Firmwareversion erfolgreich aktualisiert
wurde, fhren Sie die Schritte unter
Firmwareversion feststellen auf Seite 57
aus.

berprfung der aktualisierten


Firmwareversion.

8. Klicken Sie im Windows-Explorer-Fenster


auf Schlieen.

Schlieen von Windows Explorer und Beenden


der FTP-Verbindung zum EGX.

59

PowerLogicTM Ethernet Gateway EGX300


Anhang A Untersttzte Ethernet-Protokolle

ANHANG A UNTERSTTZTE
ETHERNET-PROTOKOLLE

63230-319-216B3_DE
03/2013

Das EGX untersttzt folgende Ethernet-Protokolle:

Modbus-TCP/IP: Modbus TCP/IP ist eine Kombination aus dem


Modbus-Protokoll, das die Master-Slave-Kommunikation zwischen
Gerten ermglicht, und TCP/IP, das fr die Kommunikation ber
eine Ethernet-Verbindung sorgt. Modbus TCP/IP wird fr den
Datenaustausch zwischen dem EGX und anderen kompatiblen ModbusTCP/IP-Gerten ber TCP-Port 502 verwendet.

Hypertext Transfer Protocol (HTTP): HTTP ist ein Netzwerkprotokoll,


das die bertragung von Dateien und Daten im Internet abwickelt. Es
stellt Webserver-Funktionen ber den TCP-Port 80 zur Verfgung.

Hypertext Transfer Protocol Secure (HTTPS): HTTPS ist ein


Netzwerkprotokoll, das die verschlsselte bertragung von Dateien und
Daten mithilfe von SSL abwickelt Es stellt sichere WebserverFunktionen ber den TCP-Port 443 zur Verfgung.

File Transfer Protocol (FTP): FTP ist ein Netzwerkprotokoll, mit dem
Dateien ber das Internet von einem Computer zum anderen bertragen
werden knnen. Sowohl der aktive als auch der passive FTP-Modus
werden untersttzt hauptschlich ber TCP-Port 21.

Simple Network Management Protocol (SNMP): SNMP basiert auf


dem MIB-II-Format und ermglicht das Speichern und bertragen von
Identifikations- und Diagnosedaten, die fr Netzwerkverwaltungszwecke
ber den UDP-Port 161 benutzt werden.

Address Resolution Protocol (ARP): ARP wird zur Konvertierung von


IP-Adressen in Ethernet-Adressen verwendet. ARP-Anfragen werden
vom EGX gesendet, um festzustellen, ob seine IP-Adresse bereits
benutzt wird (siehe Erkennung identischer IP-Adressen auf Seite 8).

Simple Network Time Protocol (SNTP): SNTP ist ein Protokoll, mit
dem die Uhrzeit von Netzwerkgerten mithilfe eines NTP-Servers ber
UDP-Port 123 synchronisiert werden kann.

Hardware
Ethernet-RJ45-Anschluss
Steuerspannung

LEDs fr Ethernet
und serielle
Kommunikationsschnittstelle

Spannungsversorgungs-/
Status-LED

Rcksetztaste

60

Serielle RS485Schnittstelle

DIP-Schalter zur
Konfiguration von
Vorspannung,
Leitungsabschluss
und 2-/4-LeiterVerbindung
Serielle
RS232-Schnittstelle
(RJ45-Anschluss)

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Anhang B Untersttzte Gertetypen

63230-319-216B3_DE
03/2013

ANHANG B UNTERSTTZTE
GERTETYPEN

Das EGX untersttzt folgende Gertetypen: Die Auflistung der untersttzten


Gerte entspricht dem aktuellen Stand zum Zeitpunkt der Verffentlichung
dieses Dokuments.
Fr Aktualisierungen siehe www.schneider-electric.com.
Tabelle 20: Vom EGX untersttzte Gertetypen
Gertegruppe

Gerte

Oberwellenaktivfilter

Accusine

Leistungsschalter

Compact NSX-A
Compact NSX-E
PowerPact A
PowerPact E

Circuit Monitore

CM100/200
CM2000
CM3000
CM4000
ION7500
ION7550
ION7600
ION7650

Digitalmessgerte

DM6000
DM6300

Digitaler Temperaturregler

Modell 98

Antriebe

ATV61
ATV71

Energiemessgerte

Energy Meter
Enercept
E5600
EM1200
EM1210
EM1250
EM1251
EM26-96
EM3550
EM3555
EM6400
EM6433
EM6436
EM6436DUAL
EM6438
EM7230
EM7280
iEM3150
iEM3155
iEM3250
iEM3255
ION8600

Isolationsberwachungsgerte

Vigilohm IM20
Vigilohm IM20-H

Motorsteuerung

TeSys T

Multi-Circuit Monitore (MCM)

BCPM-Modell A
BCPM-Modell B
BCPM-Modell C
BCM50A
BCM100A
MCM

berlastrelais (SSOLR)

MotorLogic Plus
MotorLogic Plus II

Leistungsfaktorregler

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Varlogic

61

PowerLogicTM Ethernet Gateway EGX300


Anhang B Untersttzte Gertetypen

63230-319-216B3_DE
03/2013

Tabelle 20: Vom EGX untersttzte Gertetypen


Gertegruppe

Gerte

Power Meter

PM9c
PM200
PM300
PM500
PM600
PM700
PM800
PM1000
PM3250
PM5350
PM5500
ION6200 (Standard und Mega)
ION7300

Schutzrelais

Sepam 2000
Sepam Serie 10
Sepam Serie 20
Sepam Serie 40
Sepam Serie 80

Intelligente Schnittstellenmodule

SIM10Z
SIM10M
SIM6BZ

Sanftanlasser

ATS48
MVSS/RVSS

Temperatur-/Feuchte- und
Lichtsensoren

ZED-THL-M

Auslsesysteme

Micrologic A
Micrologic E
Micrologic H
Micrologic P

Sonstiges

62

Acti9 SmartLink

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Index

63230-319-216B3_DE
03/2013

Index
A
Analogmessgertbereich 38
Anmelden beim EGX 2
Anschluss von Gerten 12
Anzeigbare Gertetypen 32
Anzeige von Echtzeitdaten und
Trendkurven 37
ARP (Address Resolution Protocol) 8
Aufzeichnung 17, 40
Datenformat 42
Gren 18
Aufzeichnungsintervalle 17

B
Benutzerdefinierte Webseiten
Einrichten 30
Benutzerkonten
Einrichten 28
Benutzeroberflche
EGX 3

Firmwareversion
Ausfhrbaren Binrkomponente 58
Datei-Image-Komponente 58
FTP
Datenprotokollabruf 43
Gerteprotokollexport 21
Hinzufgen von Webseiten 30
Lschen von Webseiten 30

G
Gerteaufzeichnung 17, 40
Gerteerkennung 15
Gerteliste
EGX 12
Gerteprotokollexport
Einrichten 19
Gerteregister
Lesen 55
Gertetypen, untersttzt 61
Grundmesswerteinstellungen 37

Datenprotokoll
Abrufen 42
Fehlercodes 43
FTP-Abruf 43
Datenprotokollformat 42
Datum und Uhrzeit
Einrichten 23

Hardware 60
HTTP
Abrufen eines Intervalldatenprotokolls 44
Export
Gerteprotokoll 22
Port-Nummer
Einrichten 7
HTTPS
Port-Nummer
Einrichten 7

Echtzeitdaten 37
EGX
Anmeldung 2
Benutzeroberflche 3
Gerteliste 12
Einfhrung 1
Einrichten
EGX 5
Gerteliste 13
Einstellungen der seriellen Schnittstelle
Erweitert 9
Einzelgerteseiten 37, 41
E-Mail
Gerteprotokollexport 19
Intervalldatenprotokoll 44
Erkennung identischer IP-Adressen 8
Ethernet- und TCP/IP-Einstellungen 5
Ethernet-Einstellungen
Erweitert 6
Ethernet-Protokolle 60
Exportieren des Gerteprotokolls 19

Instrumententafeln 46
Intervalldatenprotokoll
E-Mail 44
FTP 43
HTTP 44
Microsoft Web Query 44
Schaltflche Datenpunkte 44
Intervalle
Aufzeichnung 17
IP-Adresse
Erkennung identischer Adressen 8

F
Fehlercodes
Datenprotokoll 43
Firmware
Aktualisieren 59
Aktualisieren ber FTP 57
Neu herunterladen 58

K
Kennwortsicherheit
Farbcode 28
Kommunikationsprfung 56
Automatisch 56
Manuell 56

L
Lesen
Gerteregister 55

M
Microsoft Web Query
Intervalldatenprotokoll 44
Modbus-Gerte
Erkennung 15
Modbus-TCP/IP-Filter
Einrichten 26

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

N
Netzwerk
Zugang ber 2
Netzwerkzeitsynchronisation
Einrichten 24

P
Prferenzen
Anpassen des EGX 31
Prfpfad 33
Syslog-Feld 34
Wartungsprotokoll 34
Prfung 51

S
Schaltflche Datenpunkte
Intervalldatenprotokoll 44
Serielle Schnittstelle einrichten 8
SNMP-Parameter
Einrichten 25
Statistik 51
Auswerten 52
Steuerung 50
Syslog
Prfpfade 34
Systemzugangspunkt
Einrichten 35
Links zu anderen EGX300-Gerten 49

T
TCP/IP-Einstellungen 5
Trendverfolgung 39

U
bersichtsgerteseiten 38, 45
berwachung 37
Unterlagenlinks
Einrichten 27
Unterlagenseite 50
Untersttzte Ethernet-Protokolle 60
Untersttzte Gertetypen 61

V
Verbindungen zu entfernten Gerten 10
Vertrauenswrdiges Zertifikat
HTTPS-Port-Nr. 7

W
Wartungsprotokoll 57
Prfpfad 34
Webseiten
Einrichten 29
Benutzerdefiniert 30
Hinzufgen zur/Entfernen aus
Webschnittstelle 31

Z
Zeitsynchronisation
Netzwerk 24
Zugang zum EGX ber ein Netzwerk 2
Zugriffsberechtigungen fr das EGX 26
Zustzliche Ressourcen 1

63

PowerLogicTM Ethernet Gateway EGX300


Index

64

63230-319-216B3_DE
03/2013

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300


Benutzerhandbuch

PowerLogic ist eine Marke oder eingetragene Marke von Schneider Electric in Frankreich, den
USA und anderen Lndern. Alle anderen verwendeten Marken sind das Eigentum ihrer jeweiligen
Inhaber.
Installierung, Anschluss und Verwendung dieses Produkts mssen unter Einhaltung der gltigen
Normen und Montagevorschriften erfolgen. Aufgrund der stndigen Weiterentwicklung der
Normen, Richtlinien und Materialien sind die technischen Daten und Angaben in dieser
Publikation erst nach Besttigung durch unsere technischen Abteilungen verbindlich.

Schneider Electric
35 rue Joseph Monier
92500 Rueil-Malmaison, France
www.schneider-electric.com

63230-319-216B3_DE, 03/2013
Ersetzt 63230-319-216B2_DE 11/2011
2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Potrebbero piacerti anche