Contents
Introduction ........................................................................................................................... 4
Index.................................................................................................................................... 60
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect
installation of the motor, frequency converter or fieldbus may cause damage to the equipment,
serious personal injury or death. Consequently, the instructions in this manual, as well as
national and local rules and safety regulations, must be complied with.
Safety Regulations
1. The frequency converter must be disconnected from mains if repair work is to be carried out. Check
that the mains supply has been disconnected and that the necessary time has passed before removing
motor and mains plugs.
2. The [OFF] key on the control panel of the frequency converter does not disconnect the equipment
from mains and is thus not to be used as a safety switch.
3. Correct protective earthing or grounding of the equipment must be established, the user must be
protected against supply voltage, and the motor must be protected against overload in accordance
with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is not included in the factory setting. If this function is desired,
set par. 1-90 to data value ETR trip or data value ETR warning.
Note: The function is initialised at 1.16 x rated motor current and rated motor frequency. For the
North American market; the ETR functions provide class 20 motor overload protection in accordance
with NEC.
6. Do not remove the plugs for the motor and mains supply while the frequency converter is
connected to mains. Check that the mains supply has been disconnected and that the necessary time
has passed before removing motor and mains plugs.
7. Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when load
sharing (linking of DC intermediate circuit) and external 24 V DC have been installed. Check that all
voltage inputs have been disconnected and that the necessary time has passed before commencing
repair work.
Warning against Unintended Start
1. The motor can be brought to a stop by means of digital commands, bus commands, references or a
local stop, while the frequency converter is connected to mains.
If personal safety considerations make it necessary to ensure that no unintended start occurs, these
stop functions are not sufficient.
2. While parameters are being changed, the motor may start. Consequently, the [OFF] key must
always be activated.
3. A motor that has been stopped may start if faults occur in the electronics of the frequency
converter, or if a temporary overload or a fault in the supply mains or the motor connection ceases.
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected
from mains.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load
sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back up.
Please take note of discharge times and further safety guidelines from the section: Safety and
conformity, in the respective Design Guide (MG.33.Ax.yy).
First time users can obtain the most essential information for quick installation and set-up in these
chapters:
Introduction
How to Install
How to Configure the System
For more detailed information including the full range of set-up options and diagnosis tools please
refer to the chapters:
How to Configure the System
How to Control the FC 100/200/300
How to Access FC 100/200/300 Parameters
Parameters
Troubleshooting
Terminology:
In this manual several terms for Ethernet is used.
- EtherNet/IP, is the term used to describe the CIP/ODVA application protocol.
- Ethernet, is a common term used to describe the physical layer of the network and does not
relate to the application protocol.
I n t r o d u c t i o n -
Technical Overview
EtherNet/IP was introduced in 2001 and today is the most developed, proven and complete
industrial Ethernet network solution available for manufacturing automation.
EtherNet/IP is a member of a family of networks that implements the Common Industrial Protocol
(CIP) at its upper layers. CIP encompasses a comprehensive suite of messages and services for a
variety of manufacturing automation applications, including control, safety, synchronization, motion,
configuration and information. As a truly media-independent protocol that is supported by hundreds of
vendors from around the world, CIP provides users with unified communication architecture
throughout the manufacturing enterprise.
EtherNet/IP provides users with the network tools to deploy standard Ethernet technology for
manufacturing applications while enabling Internet and enterprise connectivity.
Assumptions
These operating instructions are under the conditions that the Danfoss EtherNet/IP option is used in
conjunction with a Danfoss FC 100/200/300 frequency converter, inclusive that the installed controller
supports the interfaces described in this document and that all the requirements stipulated in the
controller, as well as the frequency converter, are strictly observed along with all limitations herein.
Hardware
This manual relates to the EtherNet/IP option MCA121, type no. 130B1119 (un-coated) and 130B1219
(coated).
Background Knowledge
The Danfoss EtherNet/IP Option Card is designed to communicate with any system complying with the
CIP EtherNet/IP standard. Familiarity with this technology is assumed.
Issues regarding hardware or software produced by other manufacturers, including commissioning
tools, are beyond the scope of this manual, and are not the responsibility of Danfoss.
For information regarding commissioning tools, or communication to a non-Danfoss node, please
consult the appropriate manuals.
FC 300-related Literature
Literature no.
MG.33.Ax.yy
MG.33.Bx.yy
ODVA Conformance
The EtherNet/IP option is tested to conform to the ODVA standards, and is certified, towards
conformance test level version 3.
I n t r o d u c t i o n -
Abbreviations
API
CC
CIP
CTW
DHCP
EIP
EMC
I/O
IP
LCP
LED
LSB
MAR
MAU
MAV
MSB
MRV
N/A
ODVA
PC
PLC
PNU
REF
RTC
STP
STW
Instructions:
- Remove LCP panel from the FC 100/200/300.
- Remove the frame located beneath and discard it.
- Push the option into place. The Ethernet connectors must be facing upwards.
- Remove both knock-outs on the fieldbus option adaptor frame.
- Push the fieldbus option adaptor frame for the FC 100/200/300 into place.
- Replace the LCP and attach cable
N.B.:
Do not strip the Ethernet cable and ground it via the strain relief-plate!
The grounding of screened Ethernet cable is done through the RJ-45 connector on the option.
N.B.:
After installing the MCA121 option, be aware of the following parameter settings:
Par. 8-01 Control Site
[2] Controlword only or [0] Digital and ctrl. word
Par. 8-02 Control Word Source [3] Option A
Description
MS
NS1
NS2
Module Status
Network Status Ethernet Port 1
Network Status Ethernet Port 2
State
LED
No power
Description
Off
Device
operational
Green:
Solid green
Standby
Green:
Flashing green
Minor fault
Red:
Flashing red
Major fault
Red:
Red:
Green:
Solid red
Self test
Flashing red/green
State
LED
No IP-address
(no power)
Description
Off
No connections
Green:
Flashing green
Connected
Green:
Steady green
Connection
time-out
Red:
Flashing red
Duplicate IP
Red:
Steady red
Green:
Flashing red/green
Self test
Red:
During normal operation the MS and at least one NS LED will show a constant green light.
Topology
The MCA121 features a build-in Ethernet-switch, thus having two Ethernet RJ-45 connectors.
This enables the possibility for connecting several EtherNet/IP options in a line topology as an
alternative to the typical star-topology.
The two ports are equal, in the sense that they are transparent for the option. If only one connector is
used, either port can be used.
Star topology
Line topology
10
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
For this type of topology it is crucial that the network switch supports Spanning Tree
Protocol (STP), and that STP is enabled.
For more information on Spanning Tree please refer to section IP traffic.
N.B.:
Network
It is of high importance that the media chosen for Ethernet data transmission are suitable.
Usually CAT 5e and 6 cables are recommended for industrial applications. Both types of cable are
available as Unshielded Twisted Pair and Shielded Twisted Pair.
Generally shielded cables are recommended for use in industrial environments and with frequency
converters.
A maximum cable-length of 100 m is allowed between switches.
Optical fibres can be used for gapping longer distances and providing galvanic isolation.
For connecting EtherNet/IP devices both hubs and switches can be used.
It is, however, recommended always to use suitable industrial graded Ethernet switches.
For more information regarding IP-switching, please refer to section: IP Traffic in this manual.
11
While designing Ethernet networks special attention and caution must be taken regarding active
network components.
While designing a network for line topology it is important to notice that a small delay is added with
each every switch in the line.
For EtherNet/IP the maximum number of drives in a line is dependent of the API speed of the
connected scanner:
According to the graph above, the network should thus be segmented with the use of external
Ethernet switches.
It is not recommended to connect more than 32 drives in a line at any API.
Exceeding the recommended design rules, may result in failing communication.
12
The following EMC precautions are recommended in order to achieve interference-free operation of the
Ethernet network. Additional EMC information is available in the FC 100/200/300 series Design Guide.
N.B.:
Relevant national and local regulations, for example regarding protective earth connection,
must be observed.
The Ethernet communication cable must be kept away from motor and brake resistor cables to avoid
coupling of high frequency noise from one cable to the other. Normally a distance of 200 mm (8
inches) is sufficient, but maintaining the greatest possible distance between the cables is
recommended, especially where cables run in parallel over long distances. When crossing is
unavoidable, the Ethernet cable must cross motor and brake resistor cables at an angle of 90 degrees.
VLT
AutomationDrive
min. 200 mm
Ethernet cable
90 crossing
13
IP Settings
IP Address Assignment
IP Address
Subnet Mask
Default Gateway
DHCP Server
12-05
12-06
12-07
12-08
12-09
Lease Expires
Name Servers
Domain Name
Host Name
Physical Address
12-00
12-01
12-02
12-03
Name
IP Address Assignment
IP Address
Subnet Mask
Default Gateway
Value
[0] MANUAL
192.168.0.xxx*
255.255.255.0*
optional
N.B.:
14
12-00
12-01
12-02
12-03
Name
IP Address Assignment
IP Address
Subnet Mask
Default Gateway
Value
By IP address assigned by DHCP/BOOTP server, the assigned IP Address and Subnet Mask can be
read out in par. 12-01 and 12-02.
In par. 12-04 DHCP Server, the IP address of the found DHCP or BOOTP server is displayed.
For DHCP only: The remaining lease-time can be read-out in par. 12-05 Lease Expires.
Par. 12-09 Physical Address reads out the MAC address of option, which is also printed on the label
of the option. If using fixed leases together with DHCP or BOOTP, the physical MAC address is linked
with a fixed IP address.
N.B.:
If no DHCP or BOOTP reply has been received after 4 attempts (e.g. if the DHCP/BOOTP server
has been powered off), the option will fallback to the last good known IP address.
Par. 12-03 Default Gateway is optional and only used in routed networks.
Par. 12-06 Name Servers
Par. 12-07 Domain Name
Par. 12-08 Host Name
Are used with Domain Name Server systems and are all optional. If DHCP or BOOTP is selected as IP
address assignment, these parameters are read only.
N.B.:
1.0.0.1 - 126.255.255.254
128.1.0.1 - 191.255.255.254
192.0.1.1 - 223.255.254.254
15
Link Status
Link Duration
Auto Negotiation
Link Speed
Link Duplex
Please note the Ethernet Link Parameters are unique per port.
Par. 12-10 Link Status and par. 12-11 Link Duration displays information on the link status, per
port.
Par. 12-10 Link Status will display Link or No Link according to the status of the present port.
Par. 12-11 Link Duration will display the duration of the link on the present port. If the link is broken
the counter will be reset.
Par. 12-12 Auto Negotiation is a feature that enables two connected Ethernet devices to choose
common transmission parameters, such as speed and duplex mode. In this process, the connected
devices first share their capabilities as for these parameters and then choose the fastest transmission
mode they both support.
By default this function is enabled.
Incapability between the connected devices, may lead to decreased communication performance.
To prevent this Auto Negotiation can be disabled.
If par. 12-12 is set to OFF, link speed and duplex mode can be configured manually in par. 12-13 and
12-14.
Par. 12-13 Link Speed displays/sets the link speed per port. None is displayed if no link is
present.
Par. 12-14 Link Duplex displays/sets the duplex mode per port.
Half-duplex provides communication in both directions, but only in one direction at a time (not
simultaneously).
Full-duplex allows communication in both directions, and unlike half-duplex, allows for this to happen
simultaneously.
16
Danfoss Drives provides a generic English EDS (Electronic Data Sheet) file covering all voltage and
power sizes, for off-line configuration.
The EDS file can be downloaded from:
http://www.danfoss.com/BusinessAreas/DrivesSolutions/Softwaredownload/DDFieldbus_Setup_Files.htm
N.B.:
The current version of the major EtherNet/IP configuration tools does not support EDS-files for
EtherNet/IP devices.
Configuring a Rockwell Master
For configuring a FC 100/200/300 with MCA121 for operation with a Rockwell (Allen-Bradley) Scanner
via EtherNet/IP, the FC 100/200/300 must be added as a Generic Ethernet Module.
Under the General -tab, enter information about: Name of device, IP Address, Assembly Instance and
Data size.
N.B.:
17
N.B.:
For more information on the CIP class 1 Forward Open command, please refer to section:
EtherNet/IP Connections under the How to Control -chapter.
18
The use of Ethernet based network for industrial automation purposes, calls for careful and thorough
network design.
Especially the use of active network components like switches and routers requires detailed know-how
about the behaviour of IP traffic.
Some important issues:
Multicast
IGMP
For an Ethernet network to function properly, only one active path can exist between two nodes.
Spanning-Tree Protocol is a link management protocol that provides path redundancy while preventing
undesirable loops in the network.
When loops occur, some switches see stations appear on both sides of it self. This condition confuses
the forwarding algorithm and allows for duplicate frames to be forwarded.
To provide path redundancy, Spanning-Tree Protocol defines a tree that spans all switches in an
extended network. Spanning-Tree Protocol forces certain redundant data paths into a standby
(blocked) state. If one network segment in the Spanning-Tree Protocol becomes unreachable, or if
Spanning-Tree Protocol costs change, the spanning-tree algorithm reconfigures the spanning-tree
topology and re-establishes the link by activating the standby path.
Spanning-Tree Protocol operation is necessary if the FC 100/200/300s are running in a
ring/redundant line topology.
19
(par. 8-10)
Instance
Direction
Size
(decimal) (bytes)
20
4
21
4
70
4
71
4
100
4
101
8
103
20
150
4
151
8
153
20
Data
20
par.
EtherNet/IP connections
Transport Type:
Data Size:
Specified (in bytes) for both directions: Originator -> Target / Target -> Originator.
The data-size depends on the assembly-instance chosen in: Destination.
Instances (decimal):
Originator -> Target ->
Target
Originator
20, 21, 100 70, 71, 150
101
151
103
153
Data size:
4 bytes
8 bytes
20 bytes
Packet Rate:
Specified (in milliseconds) for both directions: Originator -> Target / Target -> Originator.
Minimum packet rate supported: 1 ms
Trigger:
Connection points:
Specified for both directions: Originator -> Target / Target -> Originator.
Profile
Direction
(par. 8-10)
Originator -> Target
ODVA
Target -> Originator
Originator -> Target
FC
Target -> Originator
Connection points
(decimal)
20, 21
70, 71
100, 101, 103
150, 151, 153
21
Connection Name:
Message Parameters:
-
Service Code
Class
Instance
Attribute
Member
Request Data
Message Parameters:
- Service Code
- Class
- Instance
- Attribute
- Member
- Request Data
Please refer to section Appendix for information on accessing CIP objects explicitly.
22
It is only possible to change the Control profile while the drive is stopped.
Control word and reference will not be recalculated to match the selected profile, but are kept
at the last good known value.
Change of State, COS
23
slave
CTW
Speed ref.
Bit
no.:
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit value = 0
Bit value = 1
Programmed Parameter
ref. value
1
2
3
4
N.B.:
3-10 [0]
3-10 [1]
3-10 [2]
3-10 [3]
Bit
01
0
0
1
1
Bit
00
0
1
0
1
N.B.:
N.B.:
N.B.:
24
1
2
3
4
Bit 14
0
0
1
1
Bit 15 Reverse:
Bit 15 = 0 causes no reversing.
Bit 15 = 1 causes reversing.
Note: In the factory setting reversing is set to
digital in par. 8-54 Reversing select.
Bit 15 causes reversing only when Ser.
communication, Logic AND or Logic OR is
selected.
Bit 13
0
1
0
1
The function is only possible when Multi-Setups is selected in par. 0-10 Active Set-up.
N.B.:
25
Output freq.
Bit
no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit Bit = 0
00 Control not ready
01 Drive not ready
02
Coasting
03
No error
04
No error
05
Reserved
06
No error
07
No warning
Speed
08
reference
09 Local operation
frequency
10 Out oflimit
11
No operation
12
Drive ok
13
Voltage ok
14
Torque ok
15
Thermal ok
Bit =1
Control ready
Drive ready
Enable
Trip
Error (no trip)
Trip lock
Warning
Speed = reference
Bus control
Frequency limit ok
In operation
Stopped, auto
start
Voltage exceeded
Torque exceeded
Thermal exceeded
26
27
t o
C o n t r o l
t h e
F C
3 0 0 -
slave
CTW
Bit
no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
N.B.:
00
01
02
03
04
05
06
0715
Instance 20
Bit = 0
Bit =1
Stop
No
function
-
Run
Fwd
Fault
reset
-
Instance 21
Bit = 0
Bit =1
Run
Stop
Fwd
Stop Run Rev
No
Fault
function reset
Net Ctrl
Net Ref
-
.
For the Speed reference, see section Bus speed
X
28
t o
C o n t r o l
Actual RPM
Bit
no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
00
01
02
03
04
05
06
07
0815
Instance 70
Bit = 0
Bit =1
Instance 71
Bit = 0
Bit =1
Fault
Warning
Running
1 Fwd
Running
2 Rev.
Ready
Ctrl from
Net
Ref.
from Net
At ref.
State Attribute
Bit 0, Fault:
Bit 0 = "0" means that there is no fault in the
frequency converter.
Bit 0 = "1" means that there is a fault in the
frequency converter.
Bit 1, Warning:
Bit 0 = "0" means that there is no unusual
situation.
Bit 0 = "1" means that an abnormal condition
has occurred.
Bit 2, Running 1:
Bit 2 = "0" means that the drive is not in one
of these states or that Run 1 is not set.
Bit 2 = "1" means that the drive state attribute
is enabled or stopping, or that Fault-Stop and
t h e
F C
3 0 0
Meaning
(Vendor specific)
Start up
Not ready
Ready
Enabled
Stopping
Fault stop
Faulted
29
t o
C o n t r o l
t h e
F C
3 0 0
Reference Handling
Bus Speed Reference Value under Instances 100-101-103/150-151-153
In FC-Profile (par. 8-10 = [0] FC profile) the reference is scaled as a normalized relative value in
percent. The value is transmitted in hexadecimal:
0% = 0hex
100% = 4000hex
-100% = C000hex
Depending of the setting of par. 3-00 Reference Range, the reference is scaled from Max. to + Max.
or from Min. to Max.
The actual reference [Ref. %] in the VLT depends on the settings in the following parameters:
Parameter 1-23 Motor frequency
Parameter 1-25 Motor nominal speed
Parameter 3-02 Minimum reference
Parameter 3-03 Maximum reference
All references provided to the frequency converter are added to the total reference value.
If a reference is to be controlled by the fieldbus only, ensure that all other reference inputs are zero.
This means that digital and analogue input terminals should not be used for reference signals.
The default setting (0%) should be maintained for preset references in par. 3-10 Preset Reference.
Note that if the bus speed reference is negative, and the control word contains a run reverse signal,
the drive will run clockwise
(- - is +).
MAV is scaled in the same way as the reference.
30
t o
C o n t r o l
t h e
F C
3 0 0
Master
slave
16 bit
CTW
The speed reference value should be transmitted to the VLT frequency converter in the form of a 16bit word. The value is transmitted directly in RPM.
31
Parameters
[0]
[1]
[2]
Function:
Function:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
Function:
[0]
[1]
[2]
[3]
[4]
[5]
[7]
[8]
[9]
[10]
Function:
32
-Parameters
[0]
[1]
[2]
Function:
[0]
[5]
Function:
Function:
*Hold set-up
Resume set-up
[0]
[1]
Function:
[0]
[1]
No function
* Profile Default
Alarm 68 Only
Trip excl Alarm 68
T18 DI status
T19 DI status
T27 DI status
T29 DI status
T32 DI status
T33 DI status
T37 DI status
Thermal warning
Brake fault (IGBT)
Out of ref range
Comparator 0
Comparator 1
Comparator 2
Comparator 3
Comparator 4
Comparator 5
Logic Rule 0
Logic Rule 1
Logic Rule 2
Logic Rule 3
Logic Rule 4
[0]
[1]
[2]
[3]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[21]
[30]
[40]
[60]
[61]
[62]
[63]
[64]
[65]
[70]
[71]
[72]
[73]
[74]
33
-Parameters
Logic Rule 5
SL digital out A
SL digital out B
SL digital out C
SL digital out D
SL digital out E
SL digital out F
[75]
[80]
[81]
[82]
[83]
[84]
[85]
Function:
Digital input
Bus
Logic AND
*Logic OR
[0]
[1]
[2]
[3]
Function:
Digital input
Bus
Logic AND
*Logic OR
[0]
[1]
[2]
[3]
Function:
Digital input
Bus
Logic AND
*Logic OR
Function:
Option:
Digital input
Bus
Logic AND
*Logic OR
[0]
[1]
[2]
[3]
Function:
Digital input
Bus
Logic AND
*Logic OR
[0]
[1]
[2]
[3]
Function:
[0]
[1]
[2]
[3]
34
-Parameters
Digital input
Bus
Logic AND
*Logic OR
[0]
[1]
[2]
[3]
Function:
Select control of the frequency converter setup selection via the terminals (digital input)
and/or via the fieldbus.
N.B. This parameter is active only when
par. 8-01 Control site is set to [0] Digital
and control word.
Digital input
Bus
Logic AND
*Logic OR
[0]
[1]
[2]
[3]
Function:
35
-Parameters
[0]
[1]
[2]
Function:
(12-01) IP Address
Range:
*000.000.000.000 - 255.255.255.255
Function:
Function:
Read only.
Displays the lease-time left for the current
DHCP-assigned IP address.
Function:
*000.000.000.000 - 255.255.255.255
Function:
*000.000.000.000 255.255.255.255
Function:
(Max. 19 chars.)
*blank
Function:
Function:
Function:
Function:
*000.000.000.000 255.255.255.255
Read only.
Displays the IP address of the found DHCP or
BOOTP server.
00:1B:08:00:00:00 00:1B:08:FF:FF:FF
Read only
Displays the Physical (MAC) address of the
option.
N.B.:
36
-Parameters
[0]
[1]
Function:
Read only.
Displays the link status of the Ethernet ports.
[0]
[1]
Function:
(dd:hh:mm:ss)
Function:
Read only.
Displays the duration of the present link on
each port in dd:hh:mm:ss.
[0]
[1]
Function:
[0]
[1]
[2]
Function:
37
-Parameters
Function:
Function:
Read only.
Displays the originator-to-target connection
point. If no CIP connection is present None is
displayed.
*Off
Store All set-ups
[0]
[1]
Function:
*Off
On
[0 - 9] PCD read 0 - 9
Function:
[0]
[1]
Function:
22.
38
-Parameters
Function:
Read only.
Displays the EtherNet/IP specific 16-bit Statusword.
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
Owned
Configured
Not used
*Off
On
Function:
(FC 302)
(FC 301)
Function:
Read only.
Displays the CIP product code.
Function:
[0]
[1]
Read only.
Displays the reference source in Instance
21/71.
- Off: Reference from the network is not
active.
- On: Reference from the network is active.
*Off
On
Read only.
Displays the CIP-version of the option
software.
0 9999
*1100
*1110
Function:
Function:
Not used
Not used
Not used
Not used
Not used
Minor recoverable fault
Minor unrecoverable fault
Major recoverable fault
Major unrecoverable fault
Not used
Not used
Not used
Not used
(00 - 99)
(00 - 99)
Read only
Change-Of-State inhibit timer.
If the option is configured for COS operation,
this inhibit timer can be configured in the
Forward Open telegram to prevent that
continuously changing PCD data generates
extensive network traffic.
The inhibit time is in milliseconds, 0 =
disabled.
Function:
[0]
[1]
Read only.
Displays the control source in Instance 21/71.
- Off: Control via the network is not active..
- On: Control via the network is active
39
-Parameters
*Disable
Enable
[0]
[1]
Function:
*Disable
Enable
[0]
[1]
Function:
*Disable
Enable
[0]
[1]
Function:
0 9999
*0
Function:
40
-Parameters
[0]
[1]
Function:
[0]
[1]
Function:
[0]
[1]
Function:
(*Off 20%)
(*Off 20%)
Function:
[0]
[1]
Function:
(0 200m)
(0 200m)
Function:
41
-Parameters
In Octets
In Unicast Packets
In Non-Unicast Packets
In Discards
In Errors
In Unknown Protocols
Out Octets
Out Unicast Packets
Out Non-Unicast Packets
Out Discards
Out Errors
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
Function:
Read only.
Advanced Interface counters, from build-in
switch, can be used for low-level troubleshooting,
The parameter shows a sum of port 1 + port 2.
(12-99) Media Counters
Range:
Alignment Errors
FCS Errors
Single Collisions
Multiple Collisions
SQE Test Errors
Deferred Errors
Late Collisions
Excessive Collisions
MAC Transmit Errors
Carrier Sense Errors
Frame Too Long
MAC Receive Errors
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
Function:
Read only.
Advanced Interface counters, from build-in
switch, can be used for low-level troubleshooting,
The parameter shows a sum of port 1 + port 2.
42
Parameter List
PNU
8-0x
8-01
8-02
8-03
8-04
Parameter Name
Default value
Range
8-05
8-06
8-07
8-10
8-13
8-50
8-51
8-52
8-53
8-54
8-55
8-56
Coasting Select
Quick Stop Select
DC Brake Select
Start Select
Reversing Select
Set-up Select
Preset Reference Select
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
12-00
12-01
12-02
12-03
12-04
12-05
12-06
12-07
12-08
12-09
IP Address Assignment
IP Address
Subnet Mask
Default Gateway
DHCP Server
Lease Expires
Name Servers
Domain Name
Host Name
Physical Address
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
00:00:00:00
0.0.0.0
00:1B:08:00:00:00
12-10
12-11
12-12
12-13
12-14
Link Status
Link Duration
Auto Negotiation
Link Speed
Link Duplex
No Link [0]
00:00:00:00
On [1]
None [0]
Full Duplex [1]
12-20
12-21
12-22
12-28
12-29
Control Instance
Process Data Config Write
Process Data Config Read
Store Data Values
Store Always
None
Off [0]
Off [0]
12-30
12-31
12-32
12-33
12-34
12-37
12-38
Warning Parameter
Net Control
Net Reference
CIP Revision
CIP Product Code
COS Inhibit Timer
COS Filters
0000 hex
Off [0]
Off [0]
00
0
0
0000
12-80
12-81
12-82
12-89
FTP Server
HTTP Server
SMTP Service
Transp. Socket Channel Port
Disable [0]
Disable [0]
Disable [0]
Disable [0]
12-90
12-91
12-92
12-93
12-94
12-95
12-98
12-99
Cable Diagnostics
Auto Cross-Over
IGMP Snooping
Cable Error Length
Broadcast Storm Protection
Broadcast Storm Filter
Interface Counters
Media Counters
Disable [0]
Enable [0]
Enable [0]
0
0
Enable [1]
0
0
12-0x
12-1x
12-2x
12-3x
12-8x
12-9x
Data Type
Array
[0 - 2]
[0 - 4]
0.1 - 18000
[0 - 10]
-1
-
Unsigned 8
Unsigned 8
Unsigned 32
Unsigned 8
[0 - 1]
[0 - 1]
[0 - 3]
[0 - 5]
[0 85]
Unsigned 8
Unsigned 8
Unsigned 8
Unsigned 8
Unsigned 8
[12-15]
[0 - 3]
[0 - 3]
[0 - 3]
[0 - 3]
[0 - 3]
[0 - 3]
[0 - 3]
Unsigned 8
Unsigned 8
Unsigned 8
Unsigned 8
Unsigned 8
Unsigned 8
Unsigned 8
0 - 255
0 255
0 255
0 - 255
0 - 255
0 - 255
max. 19 ch.
max. 19 ch.
-
Unsigned 8
Oct. string 4
Oct. string 4
Oct. string 4
Oct. string 4
Time diff. w/date
Oct. string 4
Visible string 48
Visible string 48
Visible string 17
[0 - 1]
[0 - 1]
[0 - 2]
[0 - 1]
Unsigned 8
Time diff. w/date
Unsigned 8
Unsigned 8
Unsigned 8
[0-1]
[0-1]
[0-1]
[0-1]
[0-1]
20 - 103
[0 1]
[0 - 1]
Unsigned 8
Unsigned 16
Unsigned 16
Unsigned 8
Unsigned 8
[0-9]
[0-9]
-
0000FFFF
[0 - 1]
[0 - 1]
0 99
9999
0 - 65535
0000-FFFF
0
-
Unsigned 16
Unsigned 8
Unsigned 8
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
[0-1]
[0-1]
[0-9]
[0 1]
[0 1]
[0 1]
[0 1]
Unsigned 8
Unsigned 8
Unsigned 8
Unsigned 8
[0 - 1]
[0 - 1]
[0 - 1]
0 - 200
Off 20%
[0 - 1]
0 - 65535
0 - 65535
0
-
Unsigned 8
Unsigned 8
Unsigned 8
Unsigned 16
Unsigned 16
Unsigned 8
Unsigned 16
Unsigned 16
[0-1]
[0-1]
[0-1]
[0-10]
[0-11]
Control Site
Control Word Source
Control Word Timeout Time
Control Word Timeout
Function
End-of-timeout Function
Reset Control Word Timeout
Diagnosis Trigger
Control Word Profile
Configurable Status Word
8-5x
Conv. Index
Digital/Bus
IP settings
Process Data
EtherNet/IP
43
This number to the left refers to a conversion figure on the right to be used when writing or reading
parameters.
Conversion
Conversion
index
factor
67
6
5
4
3
2
1
0
-1
-2
-3
-4
-5
-6
1/60
1000000
100000
10000
1000
100
10
1
0.1
0.01
0.001
0.0001
0.00001
0.000001
44
Step-by-step troubleshooting
Check: LEDs
The option contains two LEDs to indicate the state of the device and the network.
During normal operation the MS and at least one NS LED will show a constant green light.
State
LED
Description
Standby
Green:
Flashing green
Device
operational
Major
recoverable
fault
Major
unrecoverable
fault
Self test
Green:
Solid green
Flashing red
Steady red
Red:
Red:
Red:
Green:
Flashing red/green
No connections
Green:
Connected
Green:
Connection
time-out
Red:
Duplicate IP
Red:
Steady red
Self test
Red:
Flashing red/green
Green:
Flashing green
Steady green
Flashing red
45
The status of the Ethernet link cannot be directly identified by means of the LEDs, if no CIP
connection is established.
Use par. 12-10 Link Status to verify presents of the link.
Use par. 12-11 Link Duration to verify that the link is steady present. The parameter will show the
duration of the present link, and preset to 00:00:00:00 if the link is broken.
Check: Cabling
In rare cases of cabling mis-configuration, the option might show the presents of a link, but no
communication is running. Exchange the cable in doubt.
Check: IP address
Verify that the option has a valid IP address (please refer to section: IP Settings) in par. 12-01 IP
Address. If the option has identified a duplicate IP Address NS LEDs will light steady red.
If the option is set up for BOOTP or DHCP, verify that a BOOTP or DHCP server is connected in par.
12-04 DHCP Server. If no server is connected, the parameter will show: 000.000.000.000.
Alarm word and warning word are shown in the display in Hex format. If there is more than one
warning or alarm, a sum of all warnings or alarms will be shown. Warning word and alarm word are
displayed in par. 16-90 to 16-95.
For more information on the individual alarms and warnings, please refer to: FC 100/200/300 Design
Guide
N.B.
Please note that the availability of the individual alarms and warnings are dependent on the drive
type: FC100/200/300 series.
There is a clear distinction between alarms and warnings. In the event of an alarm, the frequency
converter will enter a fault condition. After the cause for the alarm has been cleared, the master must
acknowledge the alarm message in order to start operation of the frequency converter again. A
warning, on the other hand, may appear when a warning condition arises, then disappear when
conditions return to normal without interfering with the process.
Warnings
All warnings within the frequency converter are represented by a single bit within a warning word. A
warning word is always an action parameter. Bit status FALSE [0] means no warning, while bit status
TRUE [1] means warning. Each bit status has a corresponding text string message. In addition to the
warning word message the master will also be notified via a change in the status word.
Alarms
Following an alarm message the frequency converter will enter a fault condition. Only after the fault
has been rectified and the master has acknowledged the alarm message by a bit in the Control Word,
can the VLT resume operation. All alarms within the VLT are represented by a single bit within an
alarm word. An alarm word is always an action parameter. Bit status FALSE [0] means no alarm, while
bit status TRUE [1] means alarm.
In CIP, Alarms are divided in to two categories:
- Major Recoverable Faults
- Major Unrecoverable Faults
Please refer to the following sections for a classification of the specific faults.
46
Alarm word
(Par. 16-90)
00000001
00000002
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
CIP
Classification
Brake check
Power card over temperature
Earth fault
Ctrl. card over temperature
Control word timeout
Over current
Torque limit
Motor thermistor over temp.
Motor ETR over temperature
Inverter overloaded
DC link under voltage
DC link over voltage
Short circuit
Inrush fault
Mains phase loss
AMA not OK
Live zero error
Internal fault
Brake overload
Motor phase U is missing
Motor phase V is missing
Motor phase W is missing
Fieldbus fault
24V supply fault
Mains failure
1.8V supply fault
Brake resistor short circuit
Brake chopper fault
Option change
Drive initialized
Safe Stop
Mech. Brake low
MAR
MAU
MAR
MAU
MAR
MAR
MAR
MAR
MAR
MAR
MAU
MAR
MAU
MAR
MAR
MAU
MAU
MAU
MAU
MAU
MAR
MAU
MAR
MAU
MAR
MAR
MAR
-
47
Bit
(Hex)
00000001
00000002
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
Alarm word 2
(Par 16-91)
Service Trip, Read/Write
Reserved
Service Trip, Typecode/Sparepart
Reserved
Reserved
No Flow
Dry Pump
End of Curve
Broken Belt
Discharge high
Start failed
Speed limit
Reserved
Reserved
Reserved
Reserved
Reserved
KTY error
Fans error
ECB error
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
PTC thermistor
Dangerous failure
Bit
(Hex)
00000001
00000002
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
Warning word
(Par 16-92)
Brake check
Power card over temperature
Earth fault
Control card over temperature
Control word timeout
Over current
Torque limit
Motor thermistor over temp.
Motor ERT over temperature
Inverter overloaded
DC link under voltage
DC link over voltage
DC link voltage low
DC link voltage high
Mains phase loss
No motor
Live zero error
10V low
Brake resistor power limit
Brake resistor short circuit
Brake chopper fault
Speed limit
Fieldbus comm. fault
24V supply fault
Mains failure
Current limit
Low temperature
Voltage limit
Encoder loss
Output frequency limit
Safe stop
Extended status word
48
Bit
Warning word 2
Bit
(Par 16-93)
(Hex)
00000001
00000002
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
Start Delayed
Stop Delayed
Clock Failure
Firemode was active
Reserved
No Flow
Dry Pump
End of Curve
Broken Belt
Discharge high
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
KTY warning
Fans warning
ECB warning
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
PTC thermistor
Reserved
(Hex)
00000001
00000002
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
FC 100 only !!
Ramping
AMA Running
Start CW/CCW
Slow Down
Catch Up
Feedback high
Feedback low
Output current high
Output current low
Output frequency high
Output frequency low
Brake check OK
Braking max
Braking
Out of speed range
OVC active
AC brake
Password Timelock
Password Protection
Reference high
Reference low
Local Ref./Remote Ref.
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
49
Bit
(Hex)
00000001
00000002
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
FC 100 only !!
Off
Hand/Auto
PROFIbus OFF1 active
PROFIbus OFF2 active
PROFIbus OFF3 active
Relay 123 active
Start Prevented
Control ready
Drive ready
Quick Stop
DC Brake
Stop
Stand By
Freeze Output Request
Freeze Output
Jog Request
Jog
Start Request
Start
Start Applied
Start Delay
Sleep
Sleep Boost
Running
Bypass
Fire Mode
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
50
Appendix
Supported CIP Objects
Access
Get
Get
Get
Get
Get
Get
Get
Get
Vendor
Device Type
Product Code
Revision
Status
Serial Number
Product Name
State
Get
Conf. consistency
value
1
2
3
4
5
6
7
8
Name
Data type
UINT
UINT
UINT
Struct
WORD
UDINT
String
UINT
UINT
Description
Access
21
Set
70
Get
71
Get
100
Set
101
Set
103
Set
150
Get
151
Get
153
Get
20
Set
Name
Size
2 Words
Description
2 Words
2 Words
2 Words
2 Words
4 Words
10 Words
2 Words
4 Words
10 Words
51
Instance Attributes
Attribute
Access
Get
Open Requests
Get
UINT
Get
UINT
Get
UINT
Get
Close Requests
UINT
Get
UINT
Get
UINT
8
9
Get
Get
Connection Timeouts
Connection Entry List
NumConnEntries
ConnOpenBits
UINT
Struct of:
INT
ARRAY of
BOOL
Name
Data Type
UINT
Description
Instance Attributes
Attribute
Access
Get
Get/Set
Number of Attributes
supported
List of attributes
supported
Motor Type
6
7
8
9
12
15
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Rated Current
Rated Voltage
Rated Power
Rated Frequency
Pole Count
Base Speed
Get
Name
Data Type
Parameter
-
Array of
USINT
USINT
3,6,7,8,9,12,15
1-10
UINT
UINT
UDINT
UINT
UINT
UINT
1-24
1-22
1-20
1-23
1-39
1-25
USINT
Description
N.B.
52
Instance Attributes
Attribute
Access
Get
Get/Set
Number of Attributes
supported
List of supported
Attributes
Run 1 (forward)
Get/Set
Run 2 (reverse)
Boolean
5
6
7
8
9
Get/Set
Get
Get
Get
Get
Network Control
State
Running 1
Running 2
Ready
Boolean
USINT
Boolean
Boolean
Boolean
10
11
12
13
Get
Get
Get/Set
Get
Faulted
Warning
Fault reset
Fault Code
Boolean
Boolean
Boolean
UINT
15
Get
Boolean
Get
Name
Data Type
Description
USINT
12
Array of
USINT
Boolean
3,4,4,5,6,7,8,9,10,11,12,13,15
FC CTW Bit 6 = Run1 XOR Run2
FC CTW Bit15 = 0
FC CTW Bit 6 = Run1 XOR Run2
FC CTW Bit15 = 1
Parameter 12-32 value written from option
The state of the CIP state-machine
Run1 AND bit 11 in FC STW
Run2 AND bit 11 in FC STW
STATE_ENABLED or STATE_STOPPING or
STATE_FAULT_STOP from state-machine
Bit 3 in FC STW
Bit 7 in FC STW
Bit 7 in FC CTW
Mapping of par. 16-90 Alarm Word to CIP
specific fault codes
Parameter 12-31 value written from option
VLT-Code
Alarmword
0
0
4210
No alarm
unused
Drive over temperature
0000 0000
0000 0001
0000 0002
2240
0
8100
2310
8302
4310
Earth fault
unused
Controlword timeout
Overcurrent
Torque limit
Motor thermistor
0000 0004
0000 0008
0000 0010
0000 0020
0000 0040
0000 0080
4310
0000 0100
2311
Inverter overloaded
0000 0200
3220
DC Link undervoltage
0000 0400
3210
DC Link overvoltage
0000 0800
2130
2213
3130
5210
1000
6100
7110
3300
3300
3300
8100
5112
3100
5110
Short circuiting
Inrush fault
Mains phase loss
AMT fail
Live zero fault
Internal fault
Brake resistor power limit
Motor phase U missing
Motor phase V missing
Motor phase W missing
Fieldbus Comm. fault
24V supply fault
Mains failure
1,8V supply fault
0000 1000
0000 2000
0000 4000
0000 8000
0001 0000
0002 0000
0004 0000
0008 0000
0010 0000
0020 0000
0040 0000
0080 0000
0100 0000
0200 0000
7110
7110
0400 0000
0800 0000
CIP Malfunction
Meaning
No fault
No fault
Excessive Device
Temperature
Short to earth
No fault
Communication
Continuous Overcurrent
Torque limiting
Excess Drive
Temperature
Excess Drive
Temperature
Current inside the
device, No. 1
Undervoltage inside the
Device
Overvoltage inside the
device
Short Circuit
Overcurr. during startup
Phase Failure
Measurement Circuit
General fault
Internal software fault
Brake Chopper
Output voltage
Output voltage
Output voltage
Communication
+24V Power supply
Mains Voltage
Low voltage power
supp.
Brake chopper
Brake chopper
CIP
Classification
mar
mau
mir
mau
mar
mar
mar
mar
mar
mar
mau
mar
mau
mir
mar
mau
mau
mau
mau
mau
mir
mau
mar
mau
mar
mar
53
unused
unused
unused
unused
Services supported:
Service Code
1000 0000
2000 0000
4000 0000
8000 0000
Service Name
0Eh
10h
05h
No fault
No fault
No fault
No fault
Service Description
Get_Attribute_Single
Set_Attribute_Single
Reset
N.B.
Attribute
Access
Rule
Get
Get
3
4
6
7
8
18
19
20
21
22
28
29
Information
about
0
1
2
3
4
5
Contents
USINT
12
USINT
3,4,6,7,8,18,19,20,21,22,28,29
Get
Get/Set
Get/Set
Get
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Number of
Attributes
Supported
List of Attributes
Supported
At Reference
Network Reference
Drive Mode
Actual Speed
Reference Speed
Acceleration Time
Deceleration time
Low Speed Limit
High Speed Limit
Speed Scale
Boolean
Boolean
USINT
INT
INT
UINT
UINT
UINT
UINT
SINT
Get/Set
Get
Time Scale
Ref From Net
SINT
Boolean
Bit 8 of FC STW
value written to parameter "Net Reference"
Mapping of values from parameter 1-00
See Attribute 22
See Attribute 22
Scaled with Attribute 28 and written to Parameter 341
Scaled with Attribute 28 and written to Parameter 342
Scaled with Attribute 22 and written to Parameter 411
Scaled with Attribute 22 and written to Parameter 413
Forms the "Speed Reference" and "Main Actual
Value" for the Drive together with Attribute 7 and 8
Scaling factor for all time attributes
value of parameter "Net Reference"
Value of
Attribute 6
Data
Type
ODVA Text
FC Text
Vendor specific
Open loop speed ctr.
Closed loop speed ctr.
Torque Control
Process Control
Position Control
?
Speed open loop
Speed closed loop
NA
NA
NA
N.B.
54
Instance Attributes
Attribute Access
Rule
1
2
Get
Get
Get/Set
Get
Get/Set
Get/Set
Name
Status
Configuration
Capability
Configuration
Control
Physical Link Object
Path size
Path
Interface
Configuration
IP Address
Network Mask
Gateway Address
Name Server
Name Server 2
Domain Name
Host Name
Data Type
Description of Attribute
Parameter In
Drive
DWORD
STRUCT of:
UINT
Padded
EPATH
STRUCT of:
DWORD
DWORD
UDINT
UDINT
UDINT
UDINT
UDINT
STRING
STRING
Interface status
Interface capability flags
12-01
12-02
12-03
12-06 [0]
12-06 [0]
12-07
12-08
Get
2
3
4
Get
Get
Get
Get
Name
Interface Speed
Data Type
UDINT
Description of Attribute
Parameter in
drive
55
Set
7
8
9
Get
Get
Get
Single Collisions
UDINT
Multiple Collisions
UDINT
UDINT
Deferred
Transmissions
UDINT
Late Collisions
UDINT
Excessive
Collisions
MAC Transmit
Errors
UDINT
Carrier Sense
Errors
UDINT
UDINT
MAC Receive
Errors
UDINT
Interface Control
STRUCT of:
Control Bits
Forced Interface
Speed
WORD
UINT
Interface Label
Link List Size
Link List
SHORT_STRING
USINT
ARRAY OF UINT
UDINT
Services supported:
Service
Supported
Code
Class Instance Service Name
01h
0Eh
10h
43h
Yes
Yes
-
Yes
Yes
Yes
Yes
Get_Attribute_All
Get_Attribute_Single
Set_Attribute_Single
Get_and_Clear
12-99 [2]
12-99 [3]
12-99 [4]
12-99 [5]
12-99 [6]
12-99 [7]
12-99 [8]
12-99 [9]
12-99 [10]
12-99 [11]
-
Description of Service
Attribute Access
Rule
1
2
3
Get
Get
Get
Get
Get
10
Get/Set
Name
Revision
Max Instance
Number of
instances
Parameter
Class
Descriptor
Configuration
Assembly
Instance
Native Language
Data
Type
Description of Attribute
Contents
UINT
UINT
UINT
revision of object
max instance number
amount of instances
01
variable
variable
WORD
Parameter description
0x03
UINT
USINT
56
Attribute Access
Rule
Name
Data type
Description
Value
data type
described in Attr.
5
Value of parameter
from drive
USINT
variable
ARRAY:
BYTE
variable
Description of parameter
Data type code
Number of bytes in parameter
value
human readable text string
representing parameter name
human readable text string
representing parameter unit
human readable text string
representing short online help.
Generic min valid value
See Standard
variable
Parameter Attribute
From drive
Parameter Attribute
From drive
Set/Get
Parameter
Value
Get
Get
Link path
size
Link path
Segment
type/port
Segment
Address
Descriptor
Data Type
Data size
path
4
5
6
Get
Get
Get
Get
Get
Parameter
name string
Units string
Get
Help String
10
Get
min value
11
Get
max value
12
Get
default value
13
Get
UINT
14
15
16
17
Get
Get
Get
Get
Scaling
multiplier
Scaling divisor
Scaling base
Scaling offset
Multiplier link
UINT
UINT
INT
UINT
1
0
0
0
18
Get
divisor link
UINT
19
20
Get
Get
base link
offset link
UINT
UINT
21
Get
decimal
precision
USINT
Services supported
Service
Code
WORD
EPATH
USINT
SHORT
STRING
SHORT
STRING
SHORT
STRING
data type
described in Attr.
5
data type
described in Attr.
5
data type
described in Attr.
5
Implemented
Class
Instance
Parameter Attribute
From drive
Parameter Attribute
From drive
Parameter Attribute
From drive
Parameter Attribute
From drive
0
0
0
variable
Service Name
Service Description
returns contents of specified attribute
returns predefined listing of object
attributes
modifies attribute
reads enumerated strings from
parameter instance
0Eh
01h
Yes
Yes
Yes
Yes
Get_Attribute_Single
Get_Attributes_All
10h
4Bh
No
No
Yes
Yes
Set_Attribute_Single
Get_Enum_String
Attribute Access
Rule
Name
Data Type
Description
Get
Get
Number of group
members
UINT
amount of parameters in
group
Contents
Name of Group
from Drive
value of n
57
Get
Get
n+2
Get
Get
UINT
UINT
UINT
UINT
instance number of
Parameter Object
instance number of
Parameter Object
instance number of
Parameter Object
variable
variable
variable
variable
58
The CIP Class ID 100 to 199 (0x64 to 0xC7) gives access to all drive parameters.
199
0-01 - 0-99
1-00 1-99
2-00 2-99
3-00 3-99
4-00 4-99
5-00 5-99
6-00 6-99
7-00 7-99
8-00 8-99
9-00 9-99
10-00 10-99
11-00 11-99
99-00 99-99
Implemented
Class
Instance
Yes
No
No
No
Yes
Yes
Yes
Yes
Service Name
Service Description
Get_Attribute_Single
Set_Attribute_Single
Get_Att_Scattered
Set_Att_Scattered
59
M
Master
Motor data object
Multicast
17
52
19
N
Network
10
O
Object model
ODVA conformance
ODVA profile
Overview (technical)
51
5
28
5
P
Parameter access
Parameter group object
Parameter object
Parameters
59
57
56
3243
R
Reference
Rockwell master
30
17
59
44
E
EDS
EMC precautions
Ethernet
EtherNet/IP
S
Safety
Spanning Tree
3
19
17
13
4, 14
4, 14
T
Topology
Trouble shooting
10
45
F
FC profile
Forward Open
24
21
U
Unconnected message
22
H
Hardware
W
Warning word
48-50
5, 7
I
I/O
Identity object
IGMP
Installation
Interface object
IP settings
IP traffic
20
51
19
8
55
14
19
L
Link object
Literature
LEDs
55
5
9
A
Abbreviations
AC/DC drive object
Alarm word
Appendix
Assembly object
Assembly instances
Assumptions
6
54
46-50
51
51
20
5
B
Background Knowledge
C
Cable length
Cabling
Change-Of-State
CIP objects
Class 1 connection
Class 3 connection
Configuration
Conversion index
Control supervisor object
11
11
23
51
21
22
14-19
44
53
D
Danfoss objects
Data types
60