Sei sulla pagina 1di 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 1 of 139

PROCURMENT AND FINANCE (P.F) OF


312 SUB-TRANSMISSION SUBSTATION
(TECHNICAL DATA SHEET FOR
63/20 kV AIS SUBSTATIONS)

VOLUME 2 OF 4

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 2 of 139

ITEM
DESCRIPTION
PAGE
(TECHNICAL DATA SHEET FOR .......................................................................................... 1
63/20 kV AIS SUBSTATIONS) ............................................................................................ 1
1-GENERAL SCHEDULE DATA (I) ....................................................................................... 3
2- CIRCUIT BREAKER SCHEDULE DATA(I) ........................................................................... 7
3- DS/ES SCHEDULE DATA (I) ............................................................................................. 9
4- CT SCHEDULE DATA (I) ................................................................................................ 11
5- CVT SCHEDULE DATA (I) .............................................................................................. 13
6- LA SCHEDULE DATA (I) ................................................................................................ 14
7- INSULATOR SCHEDULE DATA (I) .................................................................................. 16
8- BUS WORK SCHEDULE DATA (I) .................................................................................. 18
9- EARTH SYSTEM SCHEDULE DATA (I) ............................................................................ 23
10- CAPACITOR SCHEDULE DATA (I) ................................................................................ 25
11- LIGHT SCHEDULE DATA (I) ......................................................................................... 31
12-METAL CLAD SCHEDULE(I) ......................................................................................... 33
13- STEEL STRUCTURE ..................................................................................................... 36
14- LVAC SCHEDULE DATA (I) .......................................................................................... 37
15- LVDC SCHEDULE DATA (I) .......................................................................................... 40
16- CABLE CHEDULE (I) .................................................................................................... 45
17-PROTECTION, CONTROL SCHEDULE PC (I) ................................................................. 48
18- RTU SCHEDULE DATA (I) ............................................................................................ 66
19- POWER TRANSFORMER SCHEDULE DATA (I) ............................................................ 69
20- AX/GRN TRANSFORMER SCHEDULE DATA (I) ........................................................... 74
21- DCS SCHEDULE DATA (I) ............................................................................................ 78
22- PLC SCHEDULE DATA (I) ............................................................................................ 84
23- SCHEDULE LINE TRAP AND LMU (I) ......................................................................... 113
24- SCHEDULE PABX (I).................................................................................................. 113
25- TELEPHONE SCHEDULE DATA (I) ............................................................................. 134
26- SCHEDULE OPTICAL ACCESS MULTIPLEXER (I) ........................................................ 135

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 3 of 139

1-GENERAL SCHEDULE DATA (I)


ITEM

DESCRIPTION

Applicable standard

Altitude above the sea level

Ambient temperatures:

TECHNICAL PARTICULARS
IEC
m

1800

3.1

Maximum

55

3.2

Minimum

-20

Relative humidity

More than 80

Maximum mean wind velocity

m/s

45

Seismic acceleration

m/sec2

0.45g

Pollution level

L/M/H/VH

25 mm/kV, H

Ice coating thickness

mm

20

# : Line data on next sheets.

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 4 of 139

Rev- 0

CONTINUE OF SCHEDULE GS (I)


GENERAL RATING AND CHARACTERISTICS
ITEM

DESCRIPTION

TECHNICAL
PARTICULARS

UNIT

72.5 KV

24 KV

Applicable standard

IEC standard of ministry

Substation name

Location of site

Nominal service voltage

KV

63

20

Max. system voltage

KV

72.5

24

Rating of busbars at site condition

2000

2000

Rating of switchgear at site condition:

of energy

7.1

Line bays

1250

1250

7.2

Transformer bays

1250

1250

7.3

Bus section

2000

2000
Via
grounding
Transformer

System Earthing

Rated frequency

10

Three phase short circuit:

10.1

Rated value

10.2

Dynamic value

109.3

Duration

11

Number and rating of transformers

12

Transformer ratio

13

Number and rating of aux-earthing transformers

14

Bus bar arrangement

15

Number of feeders:

15.1

Line feeders

Solidly

HZ

50

KA

40

25

KApeak

100

62.5

Sec

NoMVA

ACC.
to single line
1

KV

ACC.diagram
to single line

NoMVA

ACC.diagram
to single line
ACC.diagram
to single line
ACC. to single line
diagram

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 5 of 139

Rev- 0

UNIT

TECHNICAL
PARTICULARS

15.2

Trans feeders

ACC. to single line

15.3

Capacitor feeders

ACC.diagram
to single line

16

Rated LIW voltage at site condition

17

Rated one min PFW voltage at site condition

KV

140

50

18

Min external insulation creepage distance

mm

2250

744

19

Colour of Porcelain Insulator

20

Max. Radio. interference level measured at 1.1


highest system voltage

KVpeak

325 diagram125

Brown

ACC. TO IEC
RECOMMENDATION

21

Min clearance from ground level to the base of

mm

2500

insulation
22

Min clearance between live metal of different


phases in bay

23

Station service auxiliary AC supply:

mm

1500

500

23.1

Rated voltage

400/230

23.2

Voltage variation

10

23.3

Phases and wire

23.4

Frequency

23.5

Neutral earthing

24

3ph,4wires
HZ

50
Solid

Station service auxiliary DC supply :

24.1

Rated voltage

110

24.2

Voltage variation

-15,+10

24.3

Wires

24.4

Earthing

25

Min mechanical load of equipment terminals:

2
Un-earthed

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 6 of 139

Rev- 0

UNIT

TECHNICAL
PARTICULARS

25.1

Static

2000

1000

25.2

Dynamic

3000

2000

26

Protection degree of cubicles:

26.1

Outdoor

IP54

26.2

Indoor

IP43

27

Current Transformer Secondary Current

Unless otherwise specified the General Rating and Characteristics should be considered for all equipment.

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 7 of 139

2- CIRCUIT BREAKER SCHEDULE DATA(I)


RATING AND CHARACTERISTICS OF CIRCUIT BREAKER
TECHNICAL PARTICULARS
ITEM

DESCRIPTION

UNIT

72.5 KV

Class (outdoor/indoor)

Outdoor

Type of circuit breaker

SF6

No. of poles

Rated voltage

KV

63

Rated normal current at IEC condition

1250

Rated line-charge breaking current

50

Rated cable charge breaking current

125

Rated small inductive breaking current

10

Rated short circuit breaking current :

9.1

AC component at rated voltage (Iscn)

KA

40

9.2

DC component

35

10

First pole-to-clear factor

11

Rated transient recovery voltage for terminal faults

KV

124

12

Rated
(TRV) short circuit making current

KA

2.5 Iscn

13

Rated operating sequence

14

Rated out of phase breaking current

15

Rated break time

16

Single pole or 3 pole operation

17

Requirement for simultaneity of poles:

1.5

O-0.3Sec-CO 3min-CO
KArms

0.25 Iscn

ms

<= 50
3poles

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 8 of 139

ITEM

DESCRIPTION

UNIT

TECHNICAL PARTICULARS

17.1

Max. time interval between closure of the first and

msec

msec

last pole
17.2

Max. time interval between opening of the first and


last pole

18

Washable in service?

(Yes/No)

Yes

19

High speed auto reclosing

(Yes/No)

Yes

20

Operating mechanism:

20.1

Type of operating mechanism

Spring

20.2

Type of operating mechanism motors

20.3

No. of independent trip coil

20.4

No. of independent closing coil

20.5

Variation of DC (aux. control) voltage required to

(AC/DC)

As Required

85-110
close C.B.
20.6

Variation of DC (aux. control) voltage required to


70-110
trip C.B.

20.7

Variation of AC supply voltage to trip and close C.B.

20.8

Number of auxiliary switches:

85-110

20.8.1

Normally open

12

20.8.2

Normally close

12

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 9 of 139

3- DS/ES SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF DISCONNECTING & EARTHING SWITCHES
ITEM

DESCRIPTION

UNIT

TECHNICAL PARTICULARS
72.5 KV

Disconnecting Switch

1.1

Number of poles

1.2

Class (outdoor, indoor)

1.3

Rated voltage

1.4

Rated LIW voltage across the isolating distance at IEC


condition

1.5

3
outdoor
KV

63
325

KVpeak

Rated PFW voltage across the isolating distance at IEC


condition

KV

140

1.6

Rated normal current at IEC condition

1250

1.7

Type vertical, pantograph, double break, center

Center Break

break
1.8

Operating mechanism:

1.8.1

Method of operation

1.8.2

Number and type of spare auxiliary switches:

Motor & Manual

a) Normally open

b) Normally close

c) No. Of easily contacts

d) No. Of late contacts

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

ITEM

DESCRIPTION

1.8.3

Max. operating time

1.8.4

Type of motors

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 11 of 139

UNIT

TECHNICAL PARTICULARS

Secs

15

AC/DC

As Required

1.9

Control box

1.10

Max. inductive current breaking capacity

1.11

Max. capacitive current breaking capacity

Earthing Switch

2.1

Number of poles

2.2

Class (indoor, outdoor)

2.3

Rated voltage

2.4

Rated LIW voltage across the isolating distance at IEC


Condition

2.5

Rated PFW voltage across the isolating distance at IEC

Common for 3 phase

3
outdoor
KV

63

KVpeak

325

KV

140

condition
2.6

Operating mechanism :

2.6.1

Method of operation

2.6.2

Number and type of spare auxiliary switches:

manual

a) Normally open

b) Normally close

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 11 of 139

Rev- 0

4- CT SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF CURRENT TRANSFORMER
ITEM

DESCRIPTION

UNIT

TECHNICAL PARTICULARS
72.5 KV

Class (outdoor/indoor)

Type

Rated voltage

KV

63

Rated primary current at IEC condition

Rated secondary current

Rated continuous thermal current

Number of cores:

Accuracy class for measuring cores

Accuracy class for protection cores

10

Rated output :

10.1

For measuring

10.2

For protection

11

Max. temperature rise at rated continuous thermal

Outdoor
Oil Immersed

1.2Inp

current

As per IEC, considering site


condition

12

Capacitive terminal provided

Yes/No

YES

13

Current terminal provided

Yes/No

YES

* : Detailed requirement of each CT is mentioned on item 13.

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 12 of 139

14- Current & Output Data for Current transformers


Item No.

Core No.

Application

CT ratio

Rated burden

Accuracy
class

14.1

Incoming Feeder
1
2
3

14.2

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

AS PER SLD

Outgoing Feeder
1
2

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 13 of 139

Rev- 0

5- CVT SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF CAPACITIVE VOLTAGE TRANSFORMER
ITEM

DESCRIPTION

UNIT

TECHNICAL PARTICULARS
72.5 KV

Class (outdoor/indoor)

Outdoor

Connection in system

Phase to earth

Type

Rated primary voltage

KV

Rated secondary voltage

Rated voltage factor :

Oil immersed, Capacitor


63
3

110 / 3

6.1

Continuous

1.2

6.2

30 sec.

1.9

Number of secondary windings

Accuracy class of each winding

0.2+3P

Rated output of each winding

10

Capacitive voltage divider :

10.1

Min. coupling capacitance

10.2

Natural frequency

10.3

VA

50

PF

Later

MHZ

Equivalent series resistance

40

11

Short circuit impedance of CVT

0.25

12

Power frequency test voltage on secondary

KV

13

CVT designed for mounting of line trap on it?

Yes/No

Yes

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 14 of 139

Rev- 0

6- LA SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF LIGHTNING ARRESTER
ITEM

DESCRIPTION

UNIT

TECHNICAL PARTICULARS
72.5 KV

24 KV

Arrester Duty

1.1

Class (outdoor/indoor)

Outdoor

1.2

Connection in system

Phase to Earth

1.3

Type of equipment being protected

Power transformer /
Switchgear

Characteristics of Arresters

2.1

Location of arrester

2.2

Rated voltage

2.3

Insulation Material

2.4

Line discharge class according to IEC 60099-4

2.5

Continuous operating voltage

2.6

Nominal discharge current with 8/20 micro-second

2.7

Residual
voltage :
wave shape

Line Entrance &


Near to Power Transformer
KV

60

20
Porcelain

72.5
3

24

KV
KApeak

10

2.7.1

Lightning impulse protection level at 10KA (LIPL)

KVpeak

290

70

2.7.2

Switching impulse protection level at 1KA (SIPL)

KVpeak

122

55

2.7.3

Max. steep current impulse protection level at 10KA

KVpeak

160

68

2.8

Pressure relief class

KA-Sec

40/0.2

25/0.2

2.9

External insulation level of Silicon at IEC condition:

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Page 15 of 139

Rev- 0

UNIT

2.9.1

LIWL (1.2/50s)

KVpeak

2.9.2

One min. PFWL

KVrms

2.10

Washable in service

2.11

Additional equipment :

2.11.

Surge counter

2.11.
1

Portable leakage current detector provided?

2.11.
2

Corona ring

Tehran Regional Electric


Company (T.R.E.C)

TECHNICAL PARTICULARS

325

95
140
Yes

Yes/No

Yes
One unit for each

Yes/No

Yes
substation

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 16 of 139

7- INSULATOR SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF INSULATORS
ITEM

DESCRIPTION

UNIT

TECHNICAL PARTICULARS

Post Insulator :

1.1

Insulation material

1.2

Min. dry LIWL at IEC conditions

KVpeak

325

1.3

Min. wet PFWL at IEC conditions

KV

140

1.5

Electro-mechanical or mechanical failing load

10000

1.6

color

1.7

Top metal fitting pitch circle diameter

mm

127

1.8

Bottom metal fitting pitch circle diameter

mm

225

Porcelain

Brown

Suspension Insulator Unit

2.1

Type

2.2

Insulation Material

2.3

Min. dry LIWL at IEC conditions

KVpeak

110

2.4

Min. wet PFWL at IEC conditions

KVpeak

40

2.5

Min. power frequency puncture voltage

KV

110

2.6

Min. electro-mechanical or mechanical failing load

KN

70

2.7

Creepage distance

mm

295

2.8

Nominal spacing

mm

146

2.8

Ball and socket size

3
3.1

Ball & Socket


Porcelain

According to IEC 60120

Insulator Suspension Set


Insulation Material

Porcelain

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

3.2

Number of units per string

3.3

String arrangement

3.4

Min. tensile strength for string set fittings

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

UNIT

Page 17 of 139

TECHNICAL PARTICULARS

As required
Suspension /Tension set
KN

70

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 18 of 139

Rev- 0

8- BUS WORK SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF HIGH VOLTAGE TERMINALS &
CONDUCTORS
UNIT

TECHNICAL

ITEM

DESCRIPTION

System Characteristics

1.1

Nominal service voltage

kV

63

1.2

Highest system voltage

kV

72.5

1.3

Rated frequency

Hz

50

1.4

Number of phases

3 phase

1.5

Type of neutral grounding

Effective

General

2.1

Basic insulation level of equipment at site Condition

kV peak

325

2.2

Rated one minute power frequency withstand voltage


at site Condition

kV rms

140

2.3

Rated short circuit withstand current & it's duration

kA/ S

40 / 1

Acc. To SLD & Lay


out

(C)

85

(C)

85

REQUIRMENT

Rated current of:


Line feeders
2.4

Transformer feeders
Busbars

2.5
2.6

Maximum permissible temperature of stranded


conductors at rated current and max. ambient
temperature
Maximum permissible temperature of Tubular at
rated current and max. ambient temperature

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

2.7
2.7
2.9
2.10

DESCRIPTION
Minimum assumed tension for each stranded
conductor of incoming and outgoing over head lines
(per phase )
Minimum tension of incoming and outgoing shield
wires
Maximum permissible surface gradient at IEC
condition
Maximum permissible angle for incoming and
outgoing over head lines
Ambient conditions:

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 19 of 139

TECHNICAL
REQUIRMENT

% of UTS

20

% of UTS

10

kV/cm

21

Degree

30

Minimum ambient temperature


Maximum ambient temperature
2.11

Solar radiation

Acc. To section 1

Seismic acceleration
Wind speed
Ice thickness
Minimum Clearances
3

(Not applicable for equipment subject to impulse


voltage tests )

3.1

Height of base of post insulator from ground

mm

2500

3.2

Clearance between live parts and ground (Basic value )

mm

700

3.3

Minimum Spacing between different phases in bays

mm

1500

3.4

Minimum Spacing between phases of rigid buses

mm

1500

3.5

Minimum height of energized parts above ground

mm

3200

3.6

Height of energized parts above access roads

mm

6000

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 21 of 139

TECHNICAL

ITEM

DESCRIPTION

UNIT

3.7

Minimum Distance between over-span phases

mm

2500

3.8

Shield wire clearance over bus conductors

mm

3000

Insulators

4.1

Insulator Units

4.1.1

Wet power frequency withstand voltage

kV

40

4.1.2

lightning impulse withstand voltage

kV

110

4.1.3

Electromechanical failing load

kN

120

4.1.4

Power Frequency Puncture Voltage

kV

110

4.1.5

Creepage distance

mm

295

4.1.6

Nominal spacing

mm

146

4.1.7

IEC coupling ball

mmA

16

4.1.8

Type

Ball & socket

4.1.9

Material

Glazed porcelain

4.2

Complete Insulator String (if any)

4.2.1

Nominal phase to phase voltage

4.2.2

Min number of units

4.2.3

Power frequency withstand voltage at site condition

kV

140

4.2.4

Lightning impulse withstand voltage at site condition

kV

325

REQUIRMENT

Standard Profile

kV

63
8

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 21 of 139

TECHNICAL

ITEM

DESCRIPTION

UNIT

4.2.5

Total Creepage distance

mm

2250

Post Insulator

5.1

Nominal phase to phase voltage

kV

63

5.2

Rated lightning impulse voltage at site condition

kV

325

5.3

Rated Power frequency voltage at site condition

kV

140

5.4

Minimum Electromechanical failing load

KN

5.5

Minimum creepage distance

mm

2250

5.6

Maximum R.I.V. at 100 KHz

500

5.7

Whether corona ring for high voltage terminal


required?

Overhead Shield Wire

6.1

Type of material

6.2

Cross-section

Stranded conductor

7.1

Type of material

AAC

7.2

Minimum cross section of conductor

Outgoing : 1*1000
Copular : 2*625
Incoming: 2*625

Rigid conductor

8.1

Type of material

REQUIRMENT

No

Al. clad steel


mm

58.56 (7no.8)

Aluminum alloy

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

8.2

DESCRIPTION

Rev- 0

UNIT

Minimum cross section of Tubular*

Note: The layout and section drawing also shall be consider.

Tehran Regional Electric


Company (T.R.E.C)
Page 22 of 139

TECHNICAL
REQUIRMENT
Busbar : 160/8
Incoming: 100/6
Coupler: 100/6
Outgoing : 80/6

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 23 of 139

Rev- 0

9- EARTH SYSTEM SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF EARTHING SYSTEM
ITEM

DESCRIPTION

UNIT

TECHNICAL PARTICULARS

Sec

Maximum shock duration

Percentage of fault current through shield wire

30

Depth of ground grid

0.8

Assumption for calculation

4.1

Step length

4.2

Body resistance

1000

4.3

Weight

Kg

70

Earthing grid conductors :

5.1

Type

5.2

Material

5.3

Min cross section*

Riser conductors :

6.1

Type

6.2

Material

Stranded
Copper
mm2

120
Stranded
Copper

Earthing rod :

7.1

Material

Copper clad steel

7.2

Min length/diameter

L=3m, =20mm

8
8.1

Control

building

8.2

Type
conductors :
Material

8.3

Cross section

&

cable

trench

earthing
Stranded
Copper
mm2

50

Type of connectors & Joints :

9.1

Under ground connectors & joints

Exothermic weld

9.2

Over ground connectors & joints

Bolted-Pressure type

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 24 of 139

UNIT

TECHNICAL PARTICULARS

10

Rock surface height

Cm

15

11

Rock surface resistivity

.m

3000

* : calculation based on IEEE 80 shall be delivered for approval.

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 25 of 139

Rev- 0

10- CAPACITOR SCHEDULE DATA (I)


RATING AND CHRACTERISTICS OF CAPACITOR BANKS
ITEM
1

DESCRIPTION

UNIT

TECHNICAL PARTICULARS

Particular of systems

1.1

Nominal system voltage

kV

20/33

1.2

Highest system voltage

kV

24/36

1.3

Nominal system frequency

Hz

50

1.4

Type of system neutral grounding

1.5

Rated short circuit current in capacitor


unit place

1.6

Number of phases

Service condition

Non effectively earthed


kArms

*
3

2.1

Max. ambient temperature

40/45/50/55

2.2

Min. ambient temperature

-25/-30/-35/-40

2.3

Max. value of daily temperature

2.4

Altitude above sea level

1000/1500/2000/2500

2.5

Relative humidity

90/95/more than 95

2.6
2.7

Seismic acceleration
Pollution level

0.2/0.25/0.3/0.35/.45
Low/medium/high/
very high/special

2.8

Max. wind velocity

m/s

30/40/45

2.9

Wind velocity in ice condition

m/s

20

2.10

Ice coating thickness

mm

5 / 10 / 20 / 25

3
3.1

Capacitor
Rated voltage

kV

20 / 3

3.2

Insulation level:

3.2.1

Power frequency

kVrms

50 / 70

3.2.2

Lightning impulse

kVpeak

125 / 170

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 26 of 139

Rev- 0

UNIT

TECHNICAL PARTICULARS

3.3

Rated capacity of unit

kVAR

100/125/150/200/250/300/4
00

3.4

Rated capacity of capacitor bank

kVAR

Depends on necessity and


bank's arrangement-Acc to
SLD

3.5

Method of fuse protection


(Internal/External fuse)

3.6

Banks arrangement type (single star with


external fuse/ single star with internal
fuse/ double star with external fuse/
double star with internal fuse)

3.7

One /Two bushings

3.8
3.8.1
3.8.2
3.8.3
3.8.4
3.8.5
3.8.6
3.9

Capacitor units considering with bushing


(One bushing/ Two bushings)
Type of protection for capacitor bank:
O/C protection
O/L protection
E/F protection
O/V protection
U/V protection
Unbalance Protection
Discharging resistor

3.10

Thermal class

3.11
3.11.1
3.11.2
3.11.3

Bushing of unit capacitors:


Material
Rated one minute power frequency
withstand voltage
Rated lightning impulse voltage at site
condition

Internal / External

Yes/No

Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
C

Yes
Yes
Yes
Yes
Yes
Yes
Yes
Depends on service condition
of installation place

kVrms

Porcelain
50/70

kVpeak

125/170

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 27 of 139

ITEM

DESCRIPTION

UNIT

TECHNICAL PARTICULARS

3.11.4
4
4.1
4.2
4.3
4.3.1

Min. creepage distance


Series Reactor
One phase or three phase
Type of core
Insulation level (at site conditions):
One min. power frequency withstand
voltage of post insulator
Lightning impulse
Inductance
Continuous rated current (in site
condition)
Current Transformer
Class
Type
Rated insulation levels (at site conditions):
One min. power frequency withstand
voltage
Lightning impulse
Rated primary current
Rated secondary current
Rated short time current
Rated dynamic current
Rated continuous thermal current (% of
rated primary current)
Number of secondary cores
Accuracy class (protection/measurement)
Burden
Creepage distance
Type of mounting
Neutral CT specification

mm/kV

620

4.3.2
4.4
4.5
5
5.1
5.2
5.3
5.3.1
5.3.2
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
5.13
5.14

One phase
Air core
kVrms

50/70

kVpeak
mH
Arms

125/170
*
*

Outdoor
Dry type
kVrms

50/70

kVpeak
Arms
Arms
kArms
kApeak

125/170
275/2150/2250
1/5
*
2.5 Isc
100%

VA
mm/kV

2
0.5/5P
15/30
*
Mounted on structure
*

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

ITEM
6
6.1
6.2
6.3
6.4
6.5
6.5.1
6.5.2
6.6
6.7
6.8
6.9
6.10
6.11
6.12
7
7.1
7.2
7.3
7.4

DESCRIPTION
Voltage transformer
Class
Type
Rated primary voltage
Rated secondary voltage
Rated insulation level in standard
condition:
One min. power frequency withstand
voltage
Lightning impulse
Number of secondary cores
Accuracy class
Rated output
Type of outer insulation
Creepage distance
Type of mounting
Neutral PT specification
Over voltage relay
Rated DC voltage
Rated AC voltage
Setting range of voltage
Number of phases

7.5
8

Time characteristic
Zero voltage relay

8.1
8.2

Rated DC voltage
Rated AC voltage

8.3

Setting range of voltage

8.4

Number of phases

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 28 of 139

UNIT

TECHNICAL PARTICULARS

kV
V

Outdoor
Dry type
20/33
100/110

kVrms

50/70

kVpeak

125/170
1
0.2+3P
50
Porcelain/resin insulator
*
On metal structure
*

VA
mm/kV

V
Vrms

110/125
100/110
90% to 130% Un, continues
Connected between two
phases
Inverse characteristic

V
Vrms

110/125
100/110
20% to 90% Un, continues
Connected between two

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 29 of 139

Rev- 0

UNIT

TECHNICAL PARTICULARS

phases
8.5
9

Time setting

0.2 sec. to 9.9 sec.

Over current relay

9.1

Rated DC voltage

110/125

9.2

Rated AC voltage

Vrms

9.3

Setting range of current (Inverse)

9.4
9.5

Setting range of current (Instantaneous)


Number of phases

10

Earth fault relay

10.1

Rated DC voltage

110/125

10.2

Rated AC current

Arms

10.3

Setting range of current (Inverse)

10.4

Setting range of current (Instantaneous)

11

Unbalance protection relay (for double


stars capacitor banks)

0.5 to 2.5 In
3 Is and more
2 phase

0.2 to 1.0 In
3 Is and more

11.1

Rated DC voltage

110/125

11.2

Rated AC current

Arms

1/5

11.3

Setting range of current (First stage)

0.2 to 1.0 / 0.5 to 2.0 / 2.0 to


5.0

11.4

Time setting range (First stage)

sec

0.0 to 3.0

11.5

Setting range of current (Second stage of


any)

0.2 to 1.0 / 0.5 to 2.0 / 2.0 to


5.0

11.6

Time setting range (Second stage)

sec

0.0 to 3.0

12

Unbalance protection relay (for single


stars capacitor banks)

12.1

Rated DC voltage

110/125

12.2

Rated AC current

100/110

12.3

Setting range of voltage (First stage)

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

ITEM

DESCRIPTION

12.4

Time setting range (First stage)

12.5

Setting range of voltage (Second stage if


any)

12.6

Time setting range (Second stage)

13

Tehran Regional Electric


Company (T.R.E.C)
Page 31 of 139

Rev- 0

UNIT

TECHNICAL PARTICULARS

sec

0.0 to 3.0

sec

0.0 to 3.0

110/125

Tripping relays

13.1

Rated DC voltage

13.2

Resetting type

13.3

Number of contacts

13.4

Contact rating:

13.4.1

Breaking

13.4.2
14

Operating time
Time delay relays

14.1

Rated DC voltage

14.2

Time setting range

14.3

Number of contacts

15

Load Break Switch

Hand reset
At least two N.O. and one
N.C.
10 A for L / R=<40 ms
=<20 msec
V

110/125

sec

0.02 to 0.99 / 1.0 to 99


At least two

15-1

Rated voltage

kV (rms)

24 non-effectively earthed

15-2

Rated current

A (rms)

Acc. to SLD

15-3

Rated short circuit current and duration

KA(rms)/s

Acc. to SLD

15-4

Type designation

Outdoor/ restrike free / single


pole

16

Lightning arrester

Acc. To L.A (I)

17

Post insulator

Acc. To P.I (I)

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 31 of 139

11- LIGHT SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF LIGHTING
ITEM
1

DESCRIPTION

UNIT

TECHNICAL PARTICULARS

Minimum Illumination Levels

1.1

Switchyard at ground level horizontal

Lux

30

1.2

Vertical surfaces of main equipment

Lux

30

1.3

Streets & parking

Lux

20

1.4

Main entrance & streets around control building

Lux

50

1.5

Fence

Lux

15

1.6

Out side of fence (10m)

Lux

10

1.7

Transformers area

Lux

40

1.8

Cable gallery

Lux

200

1.9

Control building normal lighting

Lux

300

1.10

Switchgear building emergency lighting

Lux

50

Max. to Min. of illumination in each area


(uniformity factor) less than

Power factor not less than

0.8

Maintenance factor

0.7

Reflector

Type of AC lamps

Type of lighting fixture

Cut-Off
High pressure sodium
Aluminum weather & dust
proof flood light

8
8.1

Position of ballasts :
For switchyard lighting

Separate

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
8.2

DESCRIPTION

Rev- 0

UNIT

For streets & fence lighting

Efficiency of lamps not less than

10

LAMP life not less than

11

Min conductor size of buried cables

Tehran Regional Electric


Company (T.R.E.C)
Page 32 of 139

TECHNICAL PARTICULARS
Built-In

LM/W

100

hr

20000

mm2

16

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 33 of 139

Rev- 0

12-METAL CLAD SCHEDULE(I)


RATING AND CHRACTERISTICS OF METAL CLAD SWITCHGEAR AND
COMPONENTS
ITEM
1

DESCRIPTION

UNIT

TECHNICAL

PARTICMPRS

Particulars of the installation and its components

1.1

Indoor or outdoor installation

1.2

Number of phases

1.3

Number of busbars

1.4

Rated voltage

1.5

Rated insulation levels

1.5.1

Lightning impulse withstand voltage

1.5.2

1 min. power frequency withstand voltage

1.6

Indoor

KV

24

KVpeak

125

KV

50

Rated normal currents (at standard


conditions):

1.6.1

Busbar

2000

1.6.2

Transformer feeder circuit

1250

1.6.3

Capacitor bank and line feeder circuit

1250

1.7

Rated short time withstand current

KA

25

1.8

Rated duration of short circuit

Sec

1.9

Rated dynamic withstand current

KApeak

40

1.10

Degree of protection:

1.10.1 With the door closed

IP42

1.10.2 Between LV and HV compartments

IP42

1.10.3 Between HV compartments

IP42

Auxiliary voltages

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 34 of 139

Rev- 0

UNIT

TECHNICAL

PARTICMPRS

2.1

Motor of circuit breaker

2.2

Heaters and lights

V AC

220/230

2.3

Control circuits

V DC

110

DC

Power Circuit Breaker

3.1

Fix or drawout

Draw out

3.2

Type

Vacuum

3.3

Number of trip/close coils

3.4

Rated normal current at standard

1/1
A

1250

conditions
3.5

Rated short circuit breaking current

KA

20

3.6

Rated short circuit making current

KApeak

2.5 Isc

3.7

Rated cable charging breaking current

40

3.8

Rated operating sequence

3.9

Break time

3.10

First pole to clear factor

3.11

Operating counter is required

0-0.3sec-Co-3 min. Co
ms

65
1.5

Yes/No

Yes

Current Transformers

4.1

Type

4.2

Rated primary current

Arms

Refer to item 4.9

4.3

Rated secondary current

Arms

4.4

Rated continuous thermal current


(% of rated primary current)

120

4.5

Dry with Epoxy

Number of secondary cores:

4.5.1

For metering

Refer to item 4.9

4.5.2

For protection

Refer to item 4.9

4.6

Accuracy class:

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 35 of 139

Rev- 0

UNIT

TECHNICAL

PARTICMPRS

4.6.1

For metering

Refer to item 4.9

4.6.2

For protection

Refer to item 4.9

4.7

Burden:

4.7.1

For metering

VA

Refer to item 4.9

4.7.2

For protection
Max. temperature rise at rated Continuous
thermal current

VA
0
C

Refer to item 4.9


Acc. to IEC considering site
conditions

4.8
5

Voltage Transformer

5.1

Type

Dry with Epoxy resin conditions

5.2

Rated primary voltage

KV

20 / 3

5.3

Rated secondary voltage

110 / 3

5.4

Number of secondary windings

5.4.1

Incoming feeder

5.4.2

Busbar

5.5

Accuracy class

5.6

Rated output

5.7

Rated voltage factor:

5.7.1

Continuous

0.5+3P
VA

100

1.2

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 36 of 139

Rev- 0

13- STEEL STRUCTURE


RATINGS AND CHARACTERISTICS OF STRUCTURES AND LOADING
ITEM

DESCRIPTION

Steel type

Minimum thickness of principal members in dry


conditions and without corrosion

UNIT

TECHNICAL PARTICULARS
St 37 or higher

mm

Conditions

mm

Minimum thickness of redundant members

mm

Expansion coefficient/C

11.510-6

Bolts and nuts shape

Hexagon

Specification of welding

AWS D1.1

Minimum thickness of galvanization

Minimum thickness of principal members in other

8.1

Steel structure

90

8.2

Bolts and nuts

65

g/m2

500

Minimum weight of galvanization

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 37 of 139

14- LVAC SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF LVAC SYSTEM (LOW VOLTAGE AC)
ITEM
1

DESCRIPTION

UNIT

TECHNICAL PARTICULARS

LVAC Main Switch Board


LVAC Essential and
Nonessential System

1.1

Application

1.2

Rated voltage

1.3

Location

Indoor

1.4

Type of mounting

Floor

1.5

Finishing colour:

1.5.1

Outside

1.5.2

Inside

400/230

RAL 7035
Enamel White

1.6

Short time withstand rating

1.7

Continuous rating of main buses and incomings

1.8

Number
MCCBs of out going feeders

Acc. to single line diagram

1.9

Rating of outgoing feeders

Acc. to single line diagram

1.10

Fully drawout/semidrawout/fixed type

1.11

Padlocking facility required

KA/sec

16/1

400

Fully Drawout
Yes/No

Yes

400/230

LVAC Distribution Board

2.1

Rated voltage

2.2

Location

2.3

Type of mounting

2.4

Finishing colour:

2.4.1

Outside (indoor board/outdoor board)

2.4.2

Inside

Outdoor/Indoor
Floor
RAL 7035/ RAL 7038
Enamel White

2.5

Short time withstand rating

KA/sec

16/1

2.6

Continuous rating of busbars

400

2.7

Fully drawout/semi drawout/fixed type

Fixed

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 38 of 139

UNIT

TECHNICAL PARTICULARS

2.8

Padlocking facility is required?

Yes/No

Yes

2.9

Is back access required?

Yes/No

2.10

Number and rating of feeders

Yes
acc.to LVAC single line
diagram

400/230
outdoor
Floor

Auxiliary And Grounding Transformer Board

3.1
3.2
3.3
3.4
3.4.1
3.4.2
3.5
3.6
3.7
3.8
4

Rated voltage
Location
Type of mounting
Finishing colour:
Outside
Inside
Short time withstand rating
Continuous rating of busbars and MCCBs
Fully drawout/fixed type
Padlocking facility is required?
ACB-Moulded Case Circuit Breakers (MCCB)

4.1
4.2
4.2.1
4.2.2
4.2.3
4.2.4
4.3
4.4
4.5
4.6

Number of poles
Type of operation
On main switchboard incomming & bus coupler
On main switch board outgoing
On distribution board incomming
On aux. transformer board
Rated breaking capacity
Type of releases for auto control MCCBs
Number of aux. Contacts
Max. breaking time for fault condition

5
5.1
5.2
5.3
5.4

KA/sec
A
Yes/No

RAL 7038/
Enamel White
16/1
400
Fixed
Yes
4
Remot/Auto/Manual
control
with shunt
trip
Auto/Manual
control

KA
NO/NC
msec

Manual control
Auto/Manual control
16
Over load and over current
As per scheme
25

Lighting Board
Rated voltage
Location
Type of mounting
Finishing colour:

400/230
Indoor
Wall or Floor

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
5.4.1
5.4.2
5.5
5.6
5.7

DESCRIPTION
Outside
Inside
Short time withstand rating of busbar
Continuous rating of busbar and outgoing feeders
Padlocking facility is required?

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Page 39 of 139

UNIT

TECHNICAL PARTICULARS

KA/sec
A
Yes/No

RAL 7035
Enamel white
16/1
As required
Yes

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 41 of 139

Rev- 0

15- LVDC SCHEDULE DATA (I)


RATINGS AND CHARACTERISTICS OF LVDC SYSTEM (LOW VOLTAGE DC)
ITEM

DESCRIPTION

UNIT

TECHNICAL PARTICULARS
110 V

48V

Battery Charger And Accessories

1.1

Type

Composite Float and Boost

1.2

Number required

1.3

Out put current

1.4

Period adjustable for boost charging

1.5

2 set

1 set

120

20

Hour

8 to 12

Supply voltage

400

1.6

Variation in supply voltage

10

1.7

Variation in supply frequency

1.8

Combined

10

KA

16

1.9
1.10

variation

in

supply

voltage

and

frequency
Short circuit level of 400V supply at charger
terminals for 1 seconds
Charger output voltage:

1.10.1

Boost mode

Acc. to battery

1.10.2

Float mode

Requirement

1.10.3

Equalize mode

1.11

Charging current of the battery

1.11.1

Boost mode

Acc. to battery

1.11.2

Float mode

Requirement

1.11.3

Equalize mode
Whether automatic device for changing the
charging current of the battery from high level to
low and further, to very low level is required?

1.12

Yes/No

Yes

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

Tehran Regional Electric


Company (T.R.E.C)
Page 41 of 139

Rev- 0

1.13

DESCRIPTION
Maximum permissible variation in output DC
voltage
(No load to full load)

1.14

Type of tap changer for rectifier transformers

Off load

1.15

Cable entry
Contacts for the event recording, scada and alarm
system required

Bottom

1.16
1.17

TECHNICAL PARTICULARS

0.5%

Yes/No

Yes

Finishing colour :

1.17.1

Outside

1.17.2

Inside

UNIT

2 set
RAL 7035
Enamel white

Stationary Lead Acid Battery

2.1

Number of battery banks required

2.2

Number of cells in each bank in series

55

24

2.3

DC system voltage

110

48

2.4

Rated voltage of each cell

2.5

No load voltage of each cell

2.1

2.6

Max. float charging cell voltage

2.23

2.7

2.8

Max. boost charging time of battery


Ampere hour capacity of each cell at 15 deg. Cen.
And 8 hour rate to give final cell voltage of 1.85 V

2.9

Discharge Duty :

AH

300

200

2.9.1

Continuous load and duration

A/H

Acc. load calculation

2.9.2

Emergency load and duration

A/H

Acc. load calculation

2.9.3

Momentary load and duration

A/sec

Acc. load calculation

2.9.4

Final cell voltage

2.10

Type of cables to connect battery to external circuit

1.85
Single core copper PVC
insulated unarmored

2.11

Charging method required

DC Switchgear

Boost and float

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

UNIT

Page 42 of 139

TECHNICAL PARTICULARS

3.1

Location

Indoor

3.2

Type of mounting

Floor

3.3

Rated voltage

110

3.4

Maximum working voltage

125

3.5

Busbar material

Copper

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 43 of 139

SCHEDULE LVDC (I)


RATINGS AND CHARACTERISTICS OF LVDC SYSTEM (LOW VOLTAGE DC)
ITEM

DESCRIPTION

UNIT

TECHNICAL
PARTICULARS

3.6

Continuous current rating

3.7

Short time rating and duration

3.8

Single front/double front

Single

3.9

Fully drawout/semi drawout/fixed

Fixed

3.10

Number and rating of incomming feeders

See single line

3.11

Number and rating of outgoing feeders

Seediagram
single line

3.12

Type of outgoing feeders

MCCB
diagram

3.13

Type of incoming feeders

MCCB

3.14

Finishing colour :

3.14.1

Outside

3.14.2

Inside

125

KA/sec

20/1

RAL 7035
Enamel white

DC Emergency Lighting Board

4.1

Location

Indoor

4.2

Type of mounting

4.3

Rated voltage

110

4.4

Maximum working voltage

125

4.5

Busbar material

4.6

Continuous current rating

4.7

Short time rating and duration

4.8

Single front/double front

4.9

Fully drawout/semi drawout/fixed

4.10

Number and rating of incomming feeders

See single line

4.11

Number and rating of outgoing feeders

Seediagram
single line

4.12

Type of incomming feeders

Floor

Copper
A

200

KA/sec

10/1
Single front
Fixed

MCCB
diagram

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 44 of 139

TECHNICAL
PARTICULARS

4.13

Type of outgoing feeders

4.14

Finishing colour :

4.14.1

Outside

4.14.2

Inside

MCCB
RAL 7035
Enamel white

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 45 of 139

16- CABLE CHEDULE (I)


RATINGS AND CHARACTERISTICS OF MEDIUM VOLTAGE, LOW VOLTAGE,
PROTECTION AND CONTROL CABLES
ITEM
1

DESCRIPTION

UNIT

TECHNICAL
PARTICULARS

Low Voltage Power Cable

1.1

Voltage designation

1.2

Number of cores/size

KV

0.6/1
According to
Design

1.3

Conductor material

1.4

Type of conductor

1.5
1.6

Type of insulation
Type of armour and material

1.7

Type of sheath material

1.8

High voltage test

1.9
1.10
2

(Al/Cu)

Cu
Stranded
P.V.C
Galvanised steel
wire for multicore
cables and
aluminium strip
for single core
cables
Extruded P.V.C

KV

3.5

Conductor short circuit withstand current/time

KA/sec

16/1

Armour short circuit withstand current/time

KA/sec

16/0.5

Control And Protection Cables

2.1

Voltage grade :

2.1.1

VT and CT cable

KV

0.6/1

2.1.2

Control cable

450/750

2.2

Conductor material

Cu

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
2.3

DESCRIPTION

Rev- 0

UNIT

Number of cores/size

Tehran Regional Electric


Company (T.R.E.C)
Page 46 of 139

TECHNICAL
PARTICULARS
According to
design

2.4

Type of conductor

Stranded

2.5

Type of insulation

P.V.C

2.6

Inner insulation

Extruded P.V.C

2.7

Type of shield

Lead or Copper

2.8

Outer insulation around sheath

Extruded P.V.C

2.9

Type of armour material

2.10

Outer sheath

2.11

High voltage test for 5 min:

Galvanised steel
P.V.C
wire

2.11.1 VT and CT cable

KV

3.5

2.11.2 Control cable

KV

2.5

2.12

Conductor short circuit withstand current/time

KA/sec

16/1

2.13

Metal sheath short circuit withstand current/time

KA/sec

16/0.5

2.14

Armour short circuit withstand current/time

KA/sec

16/0.5

20KV Power Cable


Single core
copper conductor,
XLPE insulated,
screened and DT
armoured

3.1

Type of cable

3.2

Voltage designation

3.3

Conductor material

CU

3.4

Type of conductor

Standard

3.5

Material of shield

Lead or copper

3.6

Material of screen

Copper

3.7

High voltage test for 5 min.

KV

KV

12/20

30

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

3.8

Basic insulation level

3.9

Short circuit withstand:

3.9.1

Symmetrical current

3.9.2

Dynamic current

3.9.3

Time duration

3.10

Short circuit withstand of sheald and armour

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 47 of 139

TECHNICAL
PARTICULARS

KVpeak

125

KA

16

KApeak

40

Sec

KA/Sec

16/0.5

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 48 of 139

17-PROTECTION, CONTROL SCHEDULE PC (I)


RATINGS AND CHARACTERISTICS OF PROTECTION, CONTROL, MEASUREMENT
AND RECORDING EQUIPMENT & SYSTEM
ITEM

DESCRIPTION

Line Protection

1.1

Distance Relay :

1.1.1

Method of starting

1.1.2

Whether direction discrimination for zone 3 unit

UNIT

TECHNICAL
PARTICULARS

under-impedance
Yes/No

Yes

required
1.1.3

Distance protection shall be suitable for lines with


following details:
- Line length

Later

- Line conductor
- Line impedance :
* Positive sequence

/Km

* Zero sequence

/Km

* Zero sequence mutual impedance

/Km

- Line characteristic angle


1.1.4

Inter-tripping scheme

Degress
Permissive under
reach

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
1.1.5

DESCRIPTION

Rev- 0

UNIT

Tripping mode

Tehran Regional Electric


Company (T.R.E.C)
Page 49 of 139

TECHNICAL
PARTICULARS
3 phase and 1
phase

1.1.6

Test switch required

1.1.7

Number of zones :

- Forward reaching

Yes

- Reverse reaching

No

1.1.8

1.2

ms

<25

- Zone 2

0.1 to 1

- Zone 3

0.3 to 3

Yes/No

Yes

Single and three phase voltage supervision required


Directional earth fault relay

1.2.1

Maximum torque phase angle in degree lagging

1.2.2

Current setting range

1.2.3

Required characteristic of current unit

1.2.4

Yes

Time setting range


Maximum zone 1 operating time

1.1.9

Yes/No

40 to 70
A

0.1 to 0.3

- Instantaneous

Yes/No

Yes

- Inverse time

Yes/No

Yes

Less than 1

Transient over reach

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
1.2.5
1.3

DESCRIPTION

Page 51 of 139

TECHNICAL
PARTICULARS
97

Directional Over Current Relay


Maximum torque phase angle in degree lagging

1.3.2

Current setting range

1.3.3

Required characteristic of current unit

40 to 70
A

0.1 tp 0.3

- Instantaneous

Yes/No

Yes

- Inverse time

Yes/No

Yes

Less than 1

1.3.4

Transient over each

1.3.5

Drop-off/pick-up ratio

1.4

Zero Voltage Relay :

1.4.1

Resetting ratio in percent of nominal voltage

1.4.2

Resetting time

1.4.3

Time delay range

1.4.4

Contact data :

1.5

UNIT

Drop off/pick-up ratio

1.3.1

1.4.5

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)

97

79
Very short
S

2 to 10

- NC

On inst. U/V unit

- NO

On timer unit

Indicator required
Single And Three Phase Auto-Reclosing Equipment:

Yes/No

Yes on timer unit

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
1.5.1

DESCRIPTION

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 51 of 139

TECHNICAL
PARTICULARS

Speed of the auto-reclosing scheme :


- High speed

Yes/No

No

- Slow speed

Yes/No

No

- Slow and high speed

Yes/No

Yes

1.5.2

Number of auto-reclosing shots (one or two)

1.5.3

Manual close inhibit time

1.5.4

Whether hand reset lockout feature on permanent trip


Required

1.5.5

Two
Sec

3 to 5

Yes/No

Yes

Range of reclaim time adjustment

20 to 120

1.5.6

C.B closing pulse time

0.2 to 0.3

1.5.7

Trip pulse time

0 to 0.4

1.5.8

Whether heavy duty contacts with magnetic blow out


required for closing C.B

Yes/No

Yes

1.5.9

Operation indicator

Yes/No

Yes

1.5.10

Operation counter

Yes/No

Yes

1.5.11

Whether features for annunciation of C.B.


maintenance after preset number of A/R scheme
operation is required

Yes/No

Yes

1.5.12

Method of Reclosing :
- Single phase (SPAR)

Yes/No

No

- Three phase (TPAR)

Yes/No

Yes

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

1.5.13

DESCRIPTION

PARTICULARS
No

- Single and three phase (SPAR and TPAR)

Yes/No

No

Whether provision is provided for blocking and


switching-in the A/R equipment from:

Yes

- Control relay panel

Yes/No

Yes

- Remote control

Yes/No

Yes

0.25 to 3

- Synchronising check

Yes/No

Yes

- Live line/dead bus

Yes/No

Yes

- Live bus/dead line

Yes/No

Yes

15 to 50

Yes/No

Yes

15 to 50

5 to 200

Sec

0.1 to 99

1.5.15

Whether following features is required for each C.B:

Power Transformer Protection


Differential Relay:

2.1.1

Setting range

2.1.4

Hand reset operation indicator required

2.1.5

Bias setting reange

2.2

TECHNICAL

Yes/No

Range of dead time adjustment

2.1

UNIT

Page 52 of 139

- Single or three phase (SPAR or TPAR)

1.5.14

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)

Restricted Earth Fault Relay:

2.2.1

Voltage setting range

2.2.2

Time setting range

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

2.2.3

Resetting ratio

2.2.4

Metrosil :
- Whether metrosil required

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 53 of 139

TECHNICAL
PARTICULARS

95

Yes/No

Yes

- Characteristics of metrosil

To suit relay
scheme

2.3

Inverse Time Over Current Relay With Instantaneous


Unit

2.3.1

Current setting range

1 to 5

2.3.2

Current setting range of the instantaneous unit

4 to 20

0.2 to 2

2.4

Neutral Inverse Time Over Current Relay

2.4.1

Current setting range

2.5

Under Voltage Relay :

2.5.1

Resetting ratio in percent of nominal voltage

2.5.2

Resetting time

2.5.3

Time delay range

2.5.4

Contact data :

2.5.5

79
Very short
S

2 to 10

- NC

On inst. U/V unit

- NO

On timer unit

Indicator required

Yes/No

Yes on timer unit

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
2.6

DESCRIPTION

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 54 of 139

TECHNICAL
PARTICULARS

Over Voltage Relay

2.6.1

Voltage setting range in percent of rated voltage

80 to 110

2.6.2

Resetting ratio

125

2.6.3

Time setting range

Sec

2 to 10

3
3.1

Circuit Breaker Protection


Breaker Failure Relay:

3.1.1

Number of instantaneous over current unit per phase

3.1.2

Current setting range in percent of correponding class of


accuracy in percent

2
20 to 300 (+10, 10)

3.1.3

Drop off current as percent of pick up current

3.1.4

Resetting time

msec

10

3.1.5

Operating time for current detectors at 2 times


minimum operating current

msec

10

3.1.6

Number of timers

3.1.7

Timer setting range

3.2

2
msec

20 to 500

mA

30

Trip coil supervision relay :

3.2.1

Circuit breaker trip coil current

3.2.2

Supervision for both open and close position of circuit


breaker required

3.3

Msec than 98

Fuse Failure Relay :

Yes

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
3.3.1

DESCRIPTION

Rev- 0

UNIT

Application

Tehran Regional Electric


Company (T.R.E.C)
Page 55 of 139

TECHNICAL
PARTICULARS
One & three phase
monitoring

3.3.2

Operating time

3.3.3

Operating voltage

3.3.4

Resetting time

3.4

<8

20 (Ph-N)

msec

25

Self Reset Trip Relay :

3.4.1

Number of contacts

3.4.2

Pick up time :

3.4.3

msec

8 pairs of 12 paires

a) make contact (No)

ms

b) beak contact (No)

ms

- pick up value

50 to 120

- drop out value

5 to 20

- 200 msec/1 sec

90/50

- continuously

30/10

Contact details :
a) duty range in percent of rated voltage:

b) current carrying capacity (for already closed contact):

c) making capacity:
- 200 msec/1 sec

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION
- for 0.5 sec

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 56 of 139

TECHNICAL
PARTICULARS

- AC PF>0.1 max. 250V

10

- DC L/R<40 msec

- single contacts

0.4

d) Breaking capacity :

3.5

Elec/Hand Reset Trip Relay (Lock Out) :

3.5.1

Number of contacts

3.5.2

Pick up time :

3.5.3

3.5.4

8,12,14 or 18 pairs

a) make contact

msec

10

b) break contact

msec

10

- pick up

50 to 120

- reset

80 to 120

- within a contact set

450/400

- between sets of contact

900/800

Voltage for :

Contact details :
a) max. System voltage:

b) current carrying capacity for already closed contact:

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 57 of 139

TECHNICAL
PARTICULARS

- 200 msec/1 sec

90/50

- continuously

10

- 200 msec/1 sec

30/20

- 1 sec 2 contacts in paraller

20

- AC PF>0.1 max. 250V

20

- DC L/R<40 msec

- single contacts

c) making capacity (L/R > 10 m.sec):

d) Breaking capacity :

20KV Outgoing Feeders Buscoupler and Capacitor


Bank Protection

4.1

Inverse Time Over Current Relay With Instantaneous


Unit:

4.1.1

Current setting range

1 to 5

4.1.2

Current setting range of the instantaneous unit

4 to 20

4.2

Neutral Inverse Time Over Current Relay with instantaneous unit :

4.2.1

Current setting range

0.2 to 2

4.2.2

Current setting range of the instantaneous unit

1 to 8

4.3

Auto-Reclosing Equipment:

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
4.3.1

DESCRIPTION

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 58 of 139

TECHNICAL
PARTICULARS

Speed of the auto-reclosing scheme:


- High speed

Yes/No

No

- Slow speed

Yes/No

No

- Slow and high speed

Yes/No

Yes

4.3.2

Number of auto-reclosing shots (one or two)

4.3.3

Manual close inhibit time

4.3.4

Whether hand reset lockout feature on permanent trip


required

4.3.5

Two
Sec

3 to 5

Yes/No

Yes

Range of reclaim time adjustment

20 to 120

4.3.6

C.B closing pulse time

0.2 to 0.3

4.3.7

Trip pulse time

0 to 0.4

4.3.8

Whether heavy duty contacts with magnetic blow out


required for closing C.B

Yes/No

Yes

4.3.9

Operation indicator

Yes/No

Yes

4.3.10

Operation counter

Yes/No

Yes

4.3.11

Whether features for annunciation of C.B


maintenance after preset number of A/R scheme
operation is required

Yes/No

Yes

4.3.12

Method of reclosing:
- Single phase (SPAR)

Yes/No

No

- Three phase (TPAR)

Yes/No

Yes

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

4.3.13

DESCRIPTION

UNIT

Page 59 of 139

TECHNICAL
PARTICULARS

- Single or three phase (SPAR or TPAR)

Yes/No

No

- Single and three phase (SPAR and TPAR)

Yes/No

No

- Control relay panel

Yes/No

Yes

- Remote control

Yes/No

Yes

0.25 to 3

- Synchronising check relay

Yes/No

No

- Live line/dead bus

Yes/No

Yes

- Live bus/dead line

Yes/No

Yes

Whether provision is provided for blocking and


switching-in the A/R equipment from:

4.3.14

Range of dead time adjustment

4.3.15

Following features is required for each C.B:

4.4

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)

Over Voltage Relay

4.4.1

Voltage setting range in percent of rated voltage

80 to 110

4.4.2

Resetting ratio

125

4.4.3

Time setting range

Sec

2 to 10

4.5

Zero Voltage Relay

4.5.1

Voltage setting range in percent of rated voltage

30 to 60

4.5.2

Resetting ratio

125

4.5.3

Time setting range

Sec

2 to 10

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
4.6

DESCRIPTION

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 61 of 139

TECHNICAL
PARTICULARS

Capacitor Star-Point O/C Relay

4.6.1

Rated D.C voltage

110

4.6.2

Setting range of current

0.2-5A

4.6.3

Time setting range

Sec

0.0 to 3.0

4.7

Sensitive earth fault relay

4.7.1

Min current setting range

5
5.1

%1In

Check-Synchronising Equipment/Relay
Check-Synchronsiing Relay

5.1.1

Maximum phase difference at which circuit breaker


closure is permitted

Degrees

30

5.1.2

Accuracy of phase difference in item 5.1.1 above

Degrees

+0%, -5%

5.1.3

Maximum slip frequency at which circuit breaker closure


is permitted

HZ

0.003

5.1.4

Setting of undervoltage inhibit elements

5.1.5

Pick-up/drop off ratio of undervoltage inhibit elements

5.1.6

Rated P.T secondary voltage

5.1.7

Contacts details

5.2
5.2.1

80 to 90% of Un
80%
Volts

110/3
2 No

Check-Synchronsiing Guard Relay


Application

To guard C.B
closing such that
C.B can not be
closed by check

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

6
6.1

DESCRIPTION

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 61 of 139

TECHNICAL
PARTICULARS
relay alone, both
check relay &
operator must to
close C.B

Control, relay and other associated indoor/outdoor panels


Type of sheet steel

Cold rolled mild


steel

6.2

Thickness of sheet steel:

6.2.1

Front

mm

6.2.2

Rear

mm

6.2.3

Sides

mm

6.3

Type of panels required:

6.3.1

Control panels

Yes/No

Yes

6.3.2

Relay panels

Yes/No

Yes

6.3.3

Energy meter panels

Yes/No

Yes

6.3.4

Fault recorder/locator panels

Yes/No

No

6.3.5

Event recorder panels

Yes/No

No

6.3.6

Interface panels for scada

Yes/No

Yes

6.3.7

AVR panel

Yes/No

Yes

6.4

Cable galanding for all panels or boxes required

Yes/No

Yes

6.5

Test socket for current and voltage feeders required

Yes

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
7
7.1
7.1.1

DESCRIPTION

Rev- 0

UNIT

TECHNICAL
PARTICULARS

Measuring Center :
Functions should be mesured :
- Amper (A)

Yes/No

Yes

- Voltage (V)

Yes/No

Yes

- Active power (MW)

Yes/No

Yes

- Reactive power (MVAR)

Yes/No

Yes

- Active energy (MWH)

Yes/No

Yes

- Reactive energy (MVARH)

Yes/No

Yes
4

- Accuracy class of MWH & MVARH

7.2.1

Page 62 of 139

Measurement Equipment

- Min No. of rates (TRAFF) for MWH & MVARH

7.2

Tehran Regional Electric


Company (T.R.E.C)

0.5

Ammeter :
Range
- 63 Trans feeder

1250

- 20KV Outgoing

1250

7.2.2

Accuracy class

1.5

7.2.3

Continuous overload rating of current coil in percent of


rated current

200

7.2.4

Short time rating in percent of rated current for 5 sec

1000

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
7.2.5

DESCRIPTION

Rev- 0

UNIT

CT ratio

Tehran Regional Electric


Company (T.R.E.C)
Page 63 of 139

TECHNICAL
PARTICULARS
See single line
diagram

7.3
7.3.1

Volt Meter :
Range
- 63 KV

KV

0 to 72.5

7.3.2

Accuracy class

1.5

7.3.3

Continuous over voltage rating of voltage coil in percent


of rated voltage

120

7.3.4

Short time rating in percent of rated voltage for 5 sec

200

8
8.1

Indication equipment
Annunciator

8.1.1

Speed of operation of the annunciator

8.1.2

Whether urgent and non urgent alarm discrimination


required :

8.1.3

msec

10

- Audible alarm

Yes/No

Yes

- Visible alarm

Yes/No

Yes

Colour of visible alarm for :


- Urgent alarm
- Non urgent alarm

8.1.4

Number of alarm window per feeder

Red
Orange
acc. Spec.

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

8.1.5

Number of lamps in each annunciator window

8.1.6

Type of reset (manual/self)

UNIT

Number of channels

9.2

Individual recording channel for each event input is


required

Page 64 of 139

TECHNICAL
PARTICULARS
2
Manual

Event Recorder

9.1

9.3

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)

As required
Acc. spec

Yes/No

Yes

Method of recording for indication:


- Function
- Time

In the form of line


In the form of
point

10
10.1

10.2

10.3

Fault Recorder

As required

Number of recording channels:


- number of analog channels

Acc. spec

- number of contact channels

Acc. spec

Number of DC analog channels per feeder:


- Line

Acc. spec

- Transformer

Acc. spec

Number of DC contact channels per feeder:


- Line

Acc. spec

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Rev- 0

UNIT

- Transformer
10.4

10.5

10.6

Page 65 of 139

TECHNICAL
PARTICULARS
Acc. spec

Number of current recorder channels per feeder:


- Line

- Transformer

Number of voltage recorder channels per feeder:


- Line

- Transformer

---

Duration of timing for which the recorder shall be


reading after the appearance of fault

10.7

Tehran Regional Electric


Company (T.R.E.C)

Sec

Sec

0.5

Duration of timing for which the recorder shall be


reading before the appearance of fault

10.8

Data, time (hour, minute & second) marker required

Yes/No

Yes

10.9

End of paper alarm contact required

Yes/No

Yes

10.10

Recorder In operation indication required

Yes/No

Yes

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 66 of 139

Rev- 0

18- RTU SCHEDULE DATA (I)


ITEM

DESCRIPTION

TECHNICAL
PARTICULARS

CLOCK :
- Accuracy

2 PPM. 7.2msec per


hour or better

- Resolution

1 msec

Resolution of time tag for RTU inputs

1 msec

Time-tagged sequential memory to store

Each pulse counter input

Power supply voltage

Interruption of power supply voltage

Ambient temperature

From -20c to +55c

Relative humidity

From -10% to 95%

512 events
16-bit counter
48 VDC+20%, -15%
< 20 msec

DC analog inputs :

- The Total number of AI

89 input *

- A/D conversion linearity

1/2 LSB *

- A/D quantizing error

1/2 LSB *

- Accuracy from input terminal

<0.1% of full scale at


25c

- To digital value

<0.005% per c
temperature error

- Common mode rejection

90 dB dc to 50HZ

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

Tehran Regional Electric


Company (T.R.E.C)
Page 67 of 139

Rev- 0

DESCRIPTION

TECHNICAL
PARTICULARS

- Normal mode rejection

60 dB at 50HZ

- Rang of analog inputs

0-10mA , 4-40mA
20mA, 5volts,
10volts

10

DC analog outputs resolution of the D/A

11

The Total number of digital output

12

The total number of digital inputs

13

14

Number of communication ports (for scada center)


- Number of communication ports (for communication with
RTU)

12bits plus sign


> 152 output *
> 528 input *
14 (expandable up to
2)
1

15

-Protocol for communication with Scada center

IEC 60870-5-101

16

- Protocol for communication with Other RTU

IEC 60870-5-101

17

Rate of these ports

from 100 to 9600 bps

MODEM :
- Type of modem
18

- Terminal impedance
- Transmit level
- Receive level

Multi, four wire (data


and voice)
60010%
0dBm nominal
adjustable to 12dBm
0 to 30 dBm

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

DESCRIPTION

Page 68 of 139

TECHNICAL
PARTICULARS

19

- Bit error rate

10-5 if S/N = 15 dB

The total number of pulse input

> 53 *

* : Specified values are the minimum requirement and the exact values will be
finalized during project progress.

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 69 of 139

Rev- 0

19- POWER TRANSFORMER SCHEDULE DATA (I)


RATING AND CHARACTERISTIC OF POWER TRANSFORMER
Item

Description (POWER TRANSFORMER)

Unit

Type I

Substation name(s)

Substation.............

2 Installation ( outdoor indoor)

Item
(POWER
Unit
3 Three Description
phase or Single
phase TRANSFORMER)
No.
415Separate
winding
auto-transformer
Max.
Tempor
rise
at rated power
5 Number
of transformers
(corrected
for ambined condition as chapter
DATA
and
IEC
60076-2)
6 Rated Frequency
Hz
1-winding
deg. C
7 Rated full2-Top
load power
oil output
deg. C
deg. C
HV3-Hot spot
MVA
16
OFF
circuit
tap
changer
(YES
1
NO)
LV
MVA
1-Winding Location
TV2-Rated current
MVA
Amp
3-Tapping
%
8 Rated Voltage
(UN) Range
17
ON-Load
tap
changer
HV
kVrms
1-winding Location
LV 2-Rated current
kVrms
Amp
3-Voltage
class
(
I
or
II
)
TV
kVrms
4-Position
of
tappings
9 Highest voltage for equipment ( Um )
5-Tapping Range (+a% ....... -b%)
%
HV6-Number Of Steps
kVrms
LV 7-Mid tap position
kVrms
TV
kVrms
8-Remote OL TC Control panel
10 Cooling system(Air cooled or Water cooled)
9-Parallel
operation control required for
required(Yes/No)
11 of
System
grounding:
transformers
number
voltage regulator
HV10-Automatic
system
required(Yes/No)
LV11-Line
system Drop Compensation
18
Vector
group (HV/LV)
required(Yes/No)
TV system voltage on principal tap
19
Impedance
1-Reference
power
MVA
12 Evaluation
rate of
no load loss
2-HV/LV
%(a)
-Foreign
currency
portion
(a) If no value
indicated
it
shall
be
designed
by
manufacturer
to
3-HV/TV
(a)limit
the short-Rial
circuit
strength
of
TV
system
ace.
To
chapter
DATA.
portion
RLS/KW
4-LV/TV
(a)

Outdoor

TypeThree
I Phase
Separate
2

56
51
69
No

50
40
40
N.A

Yes
63
HV-N
>=635 20
I
N.A
HV-N
(+-9*1.67%)
19(+-9) 72.5
63/20 24
N.A
Yes
Cooled
2
Yes
Solid
No
G.T.r
YNd11
N.A

40
13.5
N.A
N.A

- Total Converted
13 Evaluation rate of load loss
-Foreign currency portion
-Rial portion
- Total Converted
14 Nominal rating (HV/LV)
1-0NAN
2-0NAN/ONAF(ONAF1 if No oil pump)
3-0NAN/ONAF/OFAF(ONAF2 if No oil
pump)

RLS/KW

MVA
MVA

40/40

MVA

N.A

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Item
No.
15

Description (POWER TRANSFORMER)

Tehran Regional Electric


Company (T.R.E.C)
Page 71 of 139

Rev- 0

Unit

Type I

Max. Temp rise at rated power


(corrected for ambient condition as chapter
DATA and IEC 60076-2)

16

17

1-winding
2-Top oil
3-Hot spot
OFF circuit tap changer (YES NO)
1-Winding Location
2-Rated current
3-Tapping Range

ON-Load tap changer


1-winding Location
2-Rated current
3-Voltage class ( I or II )
4-Position of tappings
5-Tapping Range (+a% ....... -b%)

deg. C
deg. C
deg. C

56
51
69
No

Amp
%

Amp

Yes
HV-N
>=635
I
HV-N
(+-9*1.67%)

6-Number Of Steps

19(+-9)

7-Mid tap position

63/20

8-Remote OL TC Control panel


required(Yes/No)
9-Parallel operation control required for
number
of transformers

Yes
2

10-Automatic voltage regulator


required(Yes/No)

Yes

11-Line Drop Compensation


required(Yes/No)

No

18

Vector group (HV/LV)

19

Impedance voltage on principal tap


1-Reference power
2-HV/LV
3-HV/TV
4-LV/TV

YNd11
MVA
%(a)
(a)
(a)

40
13.5
N.A
N.A

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Item
20
No.

21

21.1

21.2

Description (POWER TRANSFORMER)


INSULATION LEVELS AT SEA LEVEL AND
STANDARD
1-Lightning Impulse withstand voltage
ATMOSPHERE.(WINDING/BUSHING)
-LIWV(HV)
-LIWV(LV)
-LIWV(TV)
-LIWV(N)
2-Switching Impulse withstand voltage
-SIWV(HV)
-SIWV(LV)
-SIWV(TV)
-SIWV(N)
3-One minute power frequency
-PFWV(HV)
withstand
voltage
-PFWV(LV)
-PFWV(TV)
-PFWV(N)
Bushing Data
Min. Rated Current(HV/LV)
Min. Short Circuit Current(HV/LV)
test tap required (Yes/No)
Oil level indicator (Magnetic/Prismatic)
Bushing type current transformers
1-Required ( Yes / No )
2-No of cores (HV-LV-HVN)
3-Specification
Inside HV Bushings
A) Core 1

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Unit

Type I

kVpeak
kVpeak
kVpeak
kVpeak

325/450
125/170
N.A
125/170

kVpeak
kVpeak
kVpeak
kVpeak
(a)
kVrms
kVrms
kVrms
kVrms

N.A
N.A
N.A
N.A

Amp
kA

140/185
50/70
N.A
50/70
>=635/>= 2000
40/25
Yes
Magnetic
Yes
N.A-3-N.A

N.A

B) Core 2

N.A

C) Core 3

N.A

Inside LV Bushings
A) Core 1

N.A

B) Core 2

N.A

C) Core 3

N.A

(a) The separate-source power frequency voltage withstand test


for the winding is the same as for the graded insulated neutral
end 50 kVrms

Page 71 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Item Description (POWER TRANSFORMER)

Rev- 0

Unit

22 Minimum external creepage distance


-HV bushing
mm
-LV bushing
mm
-TV bushing
mm
-Neutral bushing
mm
23 Sound level (ace, To IEC 60076-10)
dBA
24 Max vibration (at rated condition) P-P
micron
25 Type of tank ( bell or conventional)
26 Wheels are required (Yes / No)
(a)
27 Winding and Oil temp. (Dial Type Indicator or Temp. Monitoring)

Tehran Regional Electric


Company (T.R.E.C)
Page 72 of 139

Type I

2250
744
N.A
744
<75
100
Conv.
Yes
Dial Type

(see clause 11-5 of chapter PRTR)

Indicator

28 Magnetic oil level indicator for main tank


required
(see clause 11-4 of chapter PRTR)

Yes

29 Type of conservator ( Air bag / Conventional)


30
31
32
33

35

36
37
38
39
40

Hydraulic jacks required (Yes / No)


Oil test kit required ( Yes / No)
Oil purification plant required ( Yes / No)
Is On Line Gas Monitoring(OLGM)
required?(Yes/No)
If
no, is there need to provision for OLGM
prediction(Yes/No)
-HV
-LV
-TV
Lightning arrester supports (required)
-HV ( Yes / No)
-LV (Yes / No)
-TV (Yes / No)
For all cable boxes lightning arrester shall also be in scope of supply.
Access ladder required ( Yes / No )
Fire protection system required ( Yes / No )
Oil ( Class ace. To IEC 60296)
(b)
Whether Radiators shall be seperately
mounted(Yes/No)
Radiators ( painted or Hot dip Galvanized)
(c)

Air Bag
Yes
No
No
No

Air Bushing
Cable Box
N.A
Yes
Yes
No
Yes
No

Hot dip
Galvanized
>=185

41 Size of copper ground conductor


sq. mm
42 ACSD test Required (Yes/No)
(d)
43 Short circuit mechanical test shall be consider as
optional ( Yes / No)
(d)

YES

44 Test with LI Chopped on tail included (Yes / No) (d)

YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Note:
(a) Only for pulling on foundation
(b) The oil selected should have the characteristics of class I and class II oils.
(c) Acc to MFG practice but Hot dip galvanized, spray galvanized are preffered
respectively. (d) All above tests shall be regarded as optional and prices shall be
indicated in schedule of prices for type test and at the option of owner shall be
performed.

Page 73 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

20- AX/GRN TRANSFORMER SCHEDULE DATA (I)


RATING AND CHARACTERISTIC OF AX/GRN TRANSFORMER

Item Descripti (AX/GRN TRANSFORMER) Uni


1No.Substation
onname(s)
t
2 Instaliation(lndoor/Outdoor)
3 Three phase or Single phase
4 Type (Core or Shell)
5 Number of transformers
6 Pollution
7 Rated
Hz
level
8 Nominal service voltage of windings
kVr
frequency
9 Highest
of windings ( Um )
kVr
ms
10
Type of
voltage
ms
11
Vector
cooling
12
INSULATION LEVELS AT SEA LEVEL
m
group
AND
STANDARD
1-Lightning
Impulse
withstand
ATMOSPHERE.(WINDING/BUSHING)
voltage kVp
kVp
LIWV(eak
2-One
minute
power
frequency
(a)
LIWV(
eak
HV)
kVr
withstand voltage
LV)kVr
PFWVms
13
External
secondary
load
kVA
PFWV
ms
(HV)
14
(LV) Evaluation rate of no load loss
-Foreign currency portion
$/k
-Rial portion
RLS
W
- Total Converted
$/k
/k
15
Evaluation rate of load loss
W
-Foreign currency portion
$/k
-Rial portion
RLS
W
- Total Converted
$/k
/k
16
Rated interconnected star winding
W
A
current(short time)
A
Phases
Neutr17
Off circuit Tap changer
Durat
al
ion- Total range
Locati
on

Substation ...........
Outdoor
Three Phase
Core
2
Heavy
50
20/0.4
24/1.1
ONAN
ZNyn11
1500
125/170
N.A
50/70
3/250

385
1154
30
HV-N
+- 2*2.5%

(a) The separate-source power frequency voltage withstand


test for the winding is the same as for the graded insulated
neutral end 50 kVrms

Page 74 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Item Description (AX/GRN TRANSFORMER)


18 Max. temperature rise at rated power
No.
prefault
ambient temp. of :
output and
1-winding
2-Top oil
3-Hot
19 Impedance
voltage, at rated current
spot
low
voltage
referred at side power rating ( HV Il V )
20 Zero sequence impedance of HV winding
21 Sound level (ace, To IEC 60076-10)
22 Oil ( Class ace. To IEC 60296)
23 Method of terminal connections:
-HV terminals (Air bushing or Cable box)
-HV
(Air bushing or Cable box)
-LV
neutral (Air bushing or Cable box)
terminals
24 Bushing
Data
Min. Rated Current(HV/HV Neutral /LV)
Min. Short Circuit Current(HV)

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Uni
t
deg
deg
.C
deg
.C
.C
%
O/
dB
ph
(a)
A

57
52
70
4to 6
40
<=55
Cable Box
Air Bushing
Cable Box

Am
p
kA

test tap required (Yes/No)


Bushing type current transformers
-Required ( Yes 1 No )
-No of cores (HV-HVN-LV)
Inside
HV-N Bushings
Specificat
ion

1000
25
Yes
Yes
N.A-2-N.A

N.A

A) Core 1
N.A
B) Core 2
25
26
27
28
29

Minimum external creepage distance


-HV
-Neutral
bushing bushing
Max vibration (at rated condition) P-P
Type of tank ( bell or conventional)
Wheels are required (Yes 1 No)
Type of conservator ( Air bag /
Conventional)

m
m
mic
m
ron
(b)

600
600
50
Conv.
Yes
Conv.

Page 75 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

30

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Lightning arrester supports (required)


-HV ( Yes 1 No)
-LV (Yes 1 No)
For all cable boxes lightning arrester shall also
be in scope of supply.

No
No

31

Access ladder required ( Yes 1 No )

No

32

Radiators ( painted or Hot dip


Galvanized)

(c)

Hot dip
Galvanized

Page 76 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

(a) The oil selected should have the characteristics of class I and class II oils.
(b) Only for pulling on foundation
(c)Acc to MFG practice but Hot dip galvanized, spray galvanized are preffered
respectively.

Page 77 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 78 of 139

Rev- 0

21- DCS SCHEDULE DATA (I)


RATING AND CHARACTERISTICS OF DISTRIBUTED CONTROL SYSTEM
ITEM
1
1-1
1-2

DESCRIPTION

UNIT

TECHNICAL
PARTICULARS

System functional requirements


Capability of levels of system access
protection
Multiple passwords available within each level
of system access

1-3

Single line display

1-4
1-5

Event processing facility


Alarm processing facility

1-6

Analogue measurement handling (e.g.


"change of state or other methods"

Yes/No

Yes

Yes/No
Yes/No

Yes
Yes

Yes/No
Yes/No

Yes
Yes

Yes/No
Yes/No

Yes
Yes

Yes/No

Yes
Yes

1-7

Scheduled logging facility

1-8
1-9

Page logging facility to hard copy color printer


Sequence display

1-10

Plant database schedule

Yes/No
Yes/No

1-11
1-12

Operator manual entry facility


Equipment status display

Yes/No
Yes/No

Yes
Yes

1-13

Fault incident record facility

Yes/No

Yes

1-14
1-15

Tap position by binary or digital input


Provision of simple method of database and
display updating, also system manager tasks.
Details of proposals included?

Yes

Both is possible

Yes/No
Yes/No

1-16
1-17

Tagging facility
Interlocking /redundancy feature

1-18

Synchro check

Yes/No
Yes/No

1-19

Automatic and manual tap changer control

Yes/No

Yes
Yes
Optional
Yes
Yes

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
2

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 79 of 139

Rev- 0

UNIT

TECHNICAL
PARTICULARS

Hardware and software

2-1

Computer equipping for ultimate system

Yes/No

Yes

2-2

Editing tools for sequential/logic functions


Analogue accuracy form bay unit to display
Automatic/manual diagnostics provided for all
SCS & SMS equipment
Automatic system restart following power
interruption
Fault/event recorder files auto upload to
SCMS
Redundant station computer configuration
Station computer
Type
Architecture
Hard disc storage
Peripheral server
Type
AC voltage working range
Service conditions
Power consumption
Number of LAN connections
Number of peripheral ports
Protocols supported
Operator workstation
Type
Architecture
Operating system software
Method of processor expansion
Supplied size main memory
Hard disc storage
Clock
Drift per day (when not synchronized master
clock)
Method of synchronization with master clock

Yes/No

Yes
<0.5%

Yes/No

Yes

Yes/No

Yes

2-3
2-4
2-5
2-6
2-7
3
3-1
3-2
3-3
4
4-1
4-2
4-3
4-4
4-5
4-6
4-7
5
5-1
5-2
5-3
5-4
5-5
5-6
5-7
5-7-1
5-7-2

Yes/No
Yes/No

Yes
Optional
industrial
*
*

volts

Acc .to topology


Acc .to topology
Acc .to topology
Acc .to topology
2
Acc .to requirement
TCP/IP
Industrial/Normal pc
Acc .to topology
*
*
*
*
*
3 sec/day
by servers

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
5-8
5-8-1
5-8-2
5-9
5-9-1
5-9-2
6
6-1
6-2
6-3
6-4
6-5
6-6
6-7
6-8
6-9
7
8

DESCRIPTION
Processing system intercommunications
interface
Number supported
Speed
VDU
Number to be supplied at a workstation
Complacence with recognized EMC and safety
standards
Laptop workstation and SCS & SMS dial in
fault analysis facility
Service conditions
Method of processor expansion
Amount of main memory
Size of hard disc
Processor speed
Operating system software
SCS & SMS application software
Relay and fault recorder analysis software
Details of SCS gateway
Event printer
Master clock
type

9-2

Drift per day

9-3

Local alarms and contacts for alarms to SCS &


SMS.

10

Furniture

10-1
11

Workstation desk
Workstation LAN

11-1
11-2

Type
Coaxial/ optical fiber cable

11-3

Operating speed

Page 81 of 139

Rev- 0

UNIT

TECHNICAL
PARTICULARS
LAN
*
*
*
*
Yes
Acc .to topology
*
*
*
*
*
*
*
*
*

Yes/No

Hard copy color laser printer

9
9-1

Tehran Regional Electric


Company (T.R.E.C)

Yes
Yes
Yes/NTP/SNTP
*
*

Yes/No

Yes

Yes/No

*
Acc .to topology
LAN

HZ

*
*

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

11-4

Protocols

11-5

Network management software

11-6
12

Dual redundant configuration


Real time LAN

12-1

Type

12-2
12-3

Coaxial optical fiber cable


Operating speed

12-4

Dual redundant configuration

13
13-1

Page 81 of 139

Rev- 0

UNIT

TECHNICAL
PARTICULARS
TCP/IP-IEC61850
*
YES
Acc .to topology
Ethernet
Fiber optic

HZ
Yes/No

*
optional

Communications
Protocol between station commputer and
BCU/BCPU

13-1-1 Info. transfer efficiency (data bits/total bits)


13-1-2 Security of control messages

IEC61850
No loss of data
Yes/No

13-1-3 Interface
13-1-4 Transmission rate
13-2 Type and No. of communication cables to
BCU/BCPU
13-3 Type & No. of communication cables to
protection relay and disturbance recorder
13-4

Tehran Regional Electric


Company (T.R.E.C)

Yes
Fiber optic/RJ45 Cat6
*
*
*

Laptop workstation and SCS & SMS fault


analysis

13-5

Communications with adjacent SCS & SMS


system
13-5-1 protocol
13-5-2 Transmission rate
14
BCU
14-1 DC voltage working range
14-2 service conditions
14-3 Architecture
14-4 System bus interface/speed

*
*
*
volts

*
*
*
*

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
14-5
14-6
14-8
14-8-1
14-8-2

DESCRIPTION

Provision of two redundant interfaces to LAN


Logic functions & sequences
Digital inputs
Number of inputs per module
Digital/software filtering to suppress plant
contact bounce
14-8-3 Time tagging resolution
14-9 Digital outputs
14-9-1 Number of inputs per module
14-9-2 Select/check back/ execute facility
15
System software
15-1 Make and version of operating system(s)
15-2 Details of programming language(s)
15-3 Release versions of software
16
Performance/availability
16-1 Compliance with performance requirements
(start and restart)
16-2 Time for redundant station computer to
assume online duties
16-3 Time for full updating of information
16-4 Inclusion of availability calculations
17
Inverter
17-1 Type
17-2 Input dc voltage and range
17-3 Output Ac voltage range.
17-4 Output rating
18
Static switch
18-1 Type
18-2 Input dc voltage and range
18-3 Input frequency range
18-4 Services conditions (temperature and RH)
18-5 Rating
19
Power supply housing
19-1 Forced cooling/alarming

Tehran Regional Electric


Company (T.R.E.C)
Page 82 of 139

Rev- 0

UNIT
Yes/No
Yes/No

TECHNICAL
PARTICULARS
Optional
Yes
*

Yes/ No

Yes/No

Yes
*
*
Yes
*
*
Latest version

Yes/No

Yes
*
*
*

volts
volts
watts

online
*
*
*

Amps

Static
*
*
*
*

Yes/No

Yes

volts
Hz

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM
20

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 83 of 139

Rev- 0

UNIT

TECHNICAL
PARTICULARS

BCR

20-1

Dimension

20-2
21

Number of BCRS
Fiber optics

21-1

Type

21-2

Class

21-3

Band width

21-4

Min. loss at nominal wavelength

21-5

Min. breaking strength

*
These will be specified by engineer

*
Acc. to requirement
*
*

MHZ

dB/km

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 84 of 139

22- PLC SCHEDULE DATA (I)


RATING AND CHARACTERISTICS OF PLC
UNIT

TECHNICAL

ITEM

DESCRIPTION

Power supply

1.1

Nominal supply voltage (Grounded positive pole)

HF

2.1

Carrier

2.1.1

Frequency Range

2.1.2

Number of HF frequency modules in the total range

2.1.3

Frequency allocation step

kHz

2.1.4

Frequency tuning by software and jumper setting


without additional hardware

YES/No

YES

2.2

Power output

- Single unit

Watt

2,10,20,40

- With additional stage

Watt

80

REQUIRMENT

VDC

-48 15%

kHz

40 ~ 500
Max 2 modules

Tx power output available:


2.2.1

2.2.2

Harmonic distortion

2%

2.2.3

Return loss on line

dB

14

2.2.4

HF Impedance

50 / 75 / 125 / 150

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 85 of 139

TECHNICAL

ITEM

DESCRIPTION

2.3

HF Oscillator

2.3.1

Frequency stability

Hz

10 (-5 ~ +45 C)

2.3.2

Frequency accuracy

Hz

2 (@200 kHz)

2.4

HF receiver selectivity

2.4.1

300 Hz Out of band

dB

65

2.4.2

4000 Hz Out of band

dB

75

2.4.3

6000 Hz Out of band

dB

100

2.5

Receiver

2.5.1

Minimum receiver S / N

dB

10

2.5.2

Receiver sensitivity

dBm

-30

2.5.3

Maximum level receiver

dBr

2.6

Line Filter

REQUIRMENT

2.6.1

Adjustable in the full band

YES/No

Yes

2.6.2

Adjustable at site

YES/No

Yes

YES/No

Yes

LF

3.1

Voice

3.1.1

2W/4W E & M

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 86 of 139

TECHNICAL

ITEM

DESCRIPTION

UNIT

3.1.2

Balanced Impedance

600

3.1.3

Return Loss

dB

14

dBm

-7 / 3.5
0 / -3.5

dBm

0 ~ -20 / 0 ~ +20
0 ~ -20 / -20 ~ +8

REQUIRMENT

Nominal Level 2W/4W


3.1.4

Input
Output

Level Range 2W/4W


3.1.5

Input
Output

Programming level rang:


2-wire Tx
3.1.6

2-wire Rx

0 to -10
dBm

0 to -15

4-wire Tx

0 to -20

4-wire Rx

+8 to -10

3.2

Compandor

3.2.1

Compression and Expansion Ratio Compliant

ITU-T , G.162

3.2.2

Distortion OF 800 Hz Test Tone Over Link

2%

3.2.3

Absolute signal level without compression input /


output

dBm

-8 / 0

3.2.4

Level range input / output

dBm

-5 ~ -20 /

3.2.5

Impedance

600

3.2.6

Equalized

YES/No

Yes

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Tehran Regional Electric


Company (T.R.E.C)
Page 87 of 139

TECHNICAL

ITEM

DESCRIPTION

UNIT

3.2.7

Inherent noise without compandor

dBm0p

-55

3.2.8

NEAREND and FAREND Crosstalk Without


Compandor

dBm0p

-50

3.2.9

Inter channel cross talk

dBm0p

-60

Software Facilities
YES/No

YES

4.1

Platform:
UNIX / WINDOWS XP or 2000

REQUIRMENT

4.2

Equipment Monitoring

YES/No

YES

4.3

Performance Monitoring

YES/No

YES

4.4

Fault Localization

YES/No

YES

Local telephone set

Environmental conditions for operation and storage

Provided

Temperature range:
6.1

Operation
Storage

0 to + 45
- 5 to + 55

6.2

Relative humidity

95% at 40C

6.3

Class of standard for mechanical

IEC-721-3-3
Class 3K5

Electromagnetic and insulation

7.1

HF Disturbance

IEC-255-22-1

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 88 of 139

TECHNICAL

ITEM

DESCRIPTION

7.2

Fast transient burst

IEC-801-4

7.3

Electrostatic discharge

IEC-801-2

7.4

Impulse voltage withstand

IEC-255-4

7.5

Insulation resistance

IEC255-5

7.6

ACCORDING TO IEC-60495 OR OTHER RELATIVE


STANDARDS

AGC

8.1

REQUIRMENT

YES/No

YES

OPERATION RANGE

dB

50

8.2

ACCURACY

dB

DIAGNOSTIC

9.1

TEST FACILITIES :

9.1.1

LOCAL TEST

YES/No

YES

9.1.2

REMOTE LOOP TEST

YES/No

YES

9.1.3

ONLINE MAINTENANCE AND DIAGNOSTIC

YES/No

YES

9.2

Checking Facilities:

9.2.1

Power Supply

YES/No

YES

9.2.2

CPU

YES/No

YES

9.3

Measurement :

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Rev- 0

ITEM

DESCRIPTION

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 89 of 139

TECHNICAL
REQUIRMENT

9.3.1

Tx HF POWER

YES/No

YES

9.3.2

Rx CARRIER LEVEL

YES/No

YES

9.3.3

S/N RATIO

YES/No

YES

9.3.3

SUPPLY TOLERANCE

YES/No

YES

YES/No

YES

PABX

YES/No

YES

2 wire (telephone set or PABX)

YES/No

YES

10
10.1

CAPABILITY OF CONNECTIONG TO OTHER EQUIPMENT


a)

Tele-protection signaling equipment


b)

10.2
10.3

c)

10.4

d)

Synchronous data

YES/No

YES

10.5

e)

Asynchronous data

YES/No

YES

10.6

f)

Telegraphy channels

YES/No

YES

Alarms

YES/No

YES

Service terminal

YES/No

YES

g)

10.7
10.8
11

h)

Interfaces

11.1

Fiber optic interface

YES/No

YES

11.2

Asynchronous data interface

YES/No

YES

11.3

Synchronous data interface

YES/No

YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

Page 91 of 139

TECHNICAL

ITEM

DESCRIPTION

11.4

G.703 data interface

YES/No

YES

11.5

LAN data interface

YES/No

YES

11.6

E1 interface for VOIP

YES/No

YES

11.7

Serial data interface

YES/No

YES

11.8

Four wire line interface

YES/No

YES

11.9

Two wire line interface

YES/No

YES

11.10

Programming and supervision interface

YES/No

YES

11.11

Support V.35 protocol

YES/No

YES

11.12

FAX recognition

YES/No

YES

11.13

VF telephone channel

YES/No

YES

11.14

VF data channel (4-wire)

YES/No

YES

12

Mechanical protection class

13

Upgradable software

14

Full configuration software license

15

Analogue PLC

15.1

Channel transceiver

15.1.1

Single channel extendable to double channel

UNIT

Tehran Regional Electric


Company (T.R.E.C)

REQUIRMENT

IP42
YES/No

YES
Provided

YES/No

YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

ITEM

DESCRIPTION

15.2

Minimum Channeling Requirement

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 91 of 139

TECHNICAL
REQUIRMENT

300 ~ 2000 Hz Voice


15.2.1

2160 ~ 3400 Hz Data

YES/No

YES

YES/No

YES

3660 Hz 30 Hz FSK Signaling


15.2.2

300 ~ 3400 Hz Voice


3660 Hz 30 Hz FSK Signaling

15.2.3

300 ~ 3400 Hz Data

YES/No

YES

15.2.4

300 ~ 3720 Hz Wideband Transit

YES/No

YES

15.2.5

Nominal level input/output

dBm

-12 / -15

15.2.6

Level range input / output

dBm

-5 / -20

15.2.7

Balanced impedance

600

15.2.8

Return loss

dB

14

15.3

E & M Signaling

15.3.1

Modulation

FSK

15.3.2

Bandwidth

120 Hz

15.3.3

Pulse Distortion

5%

16

Standard RS232 interface facility for diagnostic and


maintenance purposes

17

Digital PLC

YES/No

YES

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Rev- 0

ITEM

DESCRIPTION

17.1

Multiplexing Method in DPLC's

17.2

Automatic Frequency Control (AFC)

17.3

Signal transmission time

17.4

Data Transmission:
a)

TECHNICAL
REQUIRMENT

TDM

ms

Elimination VF
variation
< 5 (single purpose
mode)

bps

Interface

50,100,200,600,1
200
FSK
ITU T, V.24 /
EIA RS 232

Synchronous data transmission

17.4.2

Bit rate
Modulation

b)

Page 92 of 139

Asynchronous:

17.4.1

UNIT

Tehran Regional Electric


Company (T.R.E.C)

Bit rate

Bps

Modulation

Interface

Bit rate

ITU T, V.24 / EIA


RS 232
1200 , 2400
QPSK

Bps

4800,9600
QAM

Modulation

17.5

Real-time clock integrated and synchronizable

YES/No

YES

17.6

Direct connection to SDH & PDH multiplexer

YES/No

YES

17.7

Capability of Baud Rate changes according to signal to


noise ratio

YES/No

YES

18

Alarms
YES/No

YES

18.1

Power supply failure

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

Rev- 0

DESCRIPTION

UNIT

Tehran Regional Electric


Company (T.R.E.C)
Page 93 of 139

TECHNICAL
REQUIRMENT

18.2

Door open / Cabinet alarm

YES/No

YES

18.3

Link alarm

YES/No

YES

18.4

Low S/N ratio on data channels

YES/No

YES

18.5

Interface alarm

YES/No

YES

18.6

Warning feature

YES/No

YES

18.7

Absence of transmit signal output

YES/No

YES

18.8

Absence of receive signal input

YES/No

YES

18.9

Fuse break

YES/No

YES

18.10

Power amplifier failure

YES/No

YES

18.11

Excessive receive level

YES/No

YES

18.12

Low receive level

YES/No

YES

18.13

Frequency synthesizer failure

YES/No

YES

18.14

Loss of synchronism

YES/No

ESY

18.15

Card out

YES/No

YES

18.16

BER < 10-3

YES/No

YES

18.17

Failure of auto-test

YES/No

YES

18.18

Pilot signal level low or fail

YES/No

YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

Page 94 of 139

Rev- 0

DESCRIPTION

18.19

Tehran Regional Electric


Company (T.R.E.C)

Any disconnection between terminals

UNIT

YES/No

TECHNICAL
REQUIRMENT

YES

PABX SCHEDULE DATA (I)


RATING AND CHARACTERISTICS OF DISTRIBUTED CONTROL SYSTEM
PABX
TECHNICAL
NO

DESCRIPTION
REQUIRMENT

GENERAL

1.1

Manufacturer (Name & Country)

1.2
1.3

Manufacturer's Model Designation


Designation technology

1.4

PABX basis

1.5

Call processing performance

1.6

Hardware cards Hot-plugging

Converged
technology
TDM-PCM
& IP & ISDN
Nonblocking
Yes

1.7

Redundancy

1.8

1.9

DC-DC converter

Yes

Other (must be mentioned)

Yes

System remoting
Relative to central switch

Yes

Unrelated to central switch

Yes

Busy Hour Call Attempts (BHCA)

250000

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

1.10
1.11

Stand alone extending up to 5000


port
PABX Operating System (OS) :
Basis
Man Machine Interface (MMI)

1.12

Supported Carriers :
E1

Rev- 0

Yes
Open
Source
Windows

o Input VF level

optical
& electrical
IEEE 802.3
6 wire and 2
wire
0 dBm

o Output VF level

0 dBm

Ethernet
Cable

Microwave
o Input VF level

6 wire
-16dBm

QSIG

Yes

R2

Yes

CAS
1.13

IP trunking protocols

1.14

Time limitation for trunk access

1.15

Automatic attendant

Yes
must be
mentioned
Yes
(programm
able)
Yes

1.16

Voice mail

Yes

1.17

Cabinet color code

1.18

Cabinet painting type

1.19

IP code for cabinet

RAL 7032
as
mentioned
in tender
doc
must be
mentioned

Tehran Regional Electric


Company (T.R.E.C)
Page 95 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

1.20

Dimensions (HxWxD) in cm

Management and accounting

2.1
2.2
2.3

Supervision and programming for


digital trunks
List Cost Routing (LCR)
Accounting management & Call
charge & Traffic

Rev- 0

must be
mentioned

Full
Yes
Yes

System level

must be
mentioned
flash
memory
& CD ROM
& flappy
disk
mention
other media
Programma
ble
Yes

Card level

Yes

Port level

Yes
must be
mentioned

report
2.4

PABX software and database


backup

2.5

Fault declaration and warning :

Other levels
Real time alarm, event, status and
system states:
Representation

Yes

Saving

Yes

Management

Yes

2.7

Software offline working

Yes

Analog extensions

3.1

Line type

Twisted pair

3.2

Line loop resistance

2000

2.6

Tehran Regional Electric


Company (T.R.E.C)
Page 96 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Min. distance

Max. distance

3.3
3.4
3.5
3.6
3.7
3.8

3.9

Line insulation
Earth recall recognized by resistance
to ground
Line seizure (off-hook) recognition
time
Dialing
Line release (on hook) recognition
time
Resistance between the two line
terminals during
the break (loop open)
Voltage drop between the two line
terminals
during the make (loop close)

3.10

3.11

3.12

3.13

Stabilization time of the line current


for values
greater than 15 mA
Attenuation on dialing impulses
during
conversation

Rev- 0

6km
(0.4mm
diameter)
12km
(0.6mm
diameter)
50 K
30
100ms
DTMF and
Pulse
> 200 ms
> 100K

5.5V
for 18mA I
28 mA
15 ms

85 dB

Call signaling :
Maximum voltage output

75 Vrms

Frequency

25Hz

Normal charge

2REN

Twisted pair powering :


Idle current

100A

Tehran Regional Electric


Company (T.R.E.C)
Page 97 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Loop current with loop resistance


< 1 K
Current with loop in short circuit
3.14

Caller ID:
Subscriber line protocol over the
local for
display (and related) services
Method for CLI transmission

3.15

Terminal Equipment Alerting


Signal
Expandability (Up to 48 port)

Digital extensions

4.1

4.3

Line type
MULTI-CALL Key system for
telephone set
Local power for telephone set

4.4

Facilities of telephone set

4.2

4.5

4.6

Minimum distance for digital phone


0.6 mm
twisted pair

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

22mA
28mA
On hook
data
transmissio
n
Data
transmission
prior to
ringing
Ringing
Pulse
Yes

Twisted pair
Yes
No
must be
mentioned
600m

Power supply
Current consumption

50mA Max.

4.7

Expandability (Up to 48 port)

Yes

IP extensions

5.1

Technical characteristics of IP
phone:

5.1.1

LCD

With
backlit, min 20

Page 98 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

5.1.2

Function-Key

Rev- 0

character in
two lines
Min 12 keys
with LED
Ring tone ,
voices
and
disconnection
Yes (full
duplex)

5.1.3

Adjustable keys

5.1.4

Hands-free possibility

5.1.5

Interactive user

Min 2
dialog keys

5.1.6

Port

Dual ,
10/100 Mbps

ISDN

6.1

Protocol
The impedance to ground at both
the input & output:
For freq. from 0 Hz to 1 MHz
Maximum line length such that the
maximum
attenuation does not exceed 6 dB at
1 MHz
Characteristics of the transmitted
signal

6.2

6.3

6.4
6.4.1

Frequency

6.4.2

Line coding
Number of couplings for each
transmission direction :
Coaxial

6.4.3

PRI

> 1000

2048KHz
50ppm
HDB3

One

Tehran Regional Electric


Company (T.R.E.C)
Page 99 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

o Impedance
o Impulse nominal peak voltage
o Maximum voltage in impulse
absence
Balanced twisted pair
o Impedance

6.4.4

6.4.5

6.4.6

o Impulse nominal peak voltage


o Maximum voltage in impulse
absence
Nominal duration of impulse
Amplitude ratio between positive
and negative
impulses with reference to ground
Ratio of duration between positive
and negative
impulses at 50%

Rev- 0

75
2.37 V
237 mV
One
120
3.0V
300 mV
244 nsec

10.05

10.05

6.4.7

Rise-time

64 nsec
Max.

6.4.8

Overshoot

20% Max.

6.4.9

Output signal balancing, using


120 connection :
Up to 1MHz
From 1MHz to 30MHz

6.5

Characteristics of received signal

6.5.1

Impedance characteristic

6.5.2

Max. attenuation with variations


proportional to
square root of f

40 dB
Atten.20dB/
decade
75 or
120
6 dB

Tehran Regional Electric


Company (T.R.E.C)
Page 111 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

6.5.3

Return loss:
From 512KHz

6.6

Rev- 0

to 1024KHz

12dB

From 1024 KHz to 2048 KHz

18dB

From 2048 KHz to 3072 KHz

14dB

Jitter in reception
(Freq. = 2048 KHz 32 ppm; 1UI =
488 nsec):
0 to 12x10-6 Hz
12x10-6 to 20Hz
20 to 2400Hz
2400 to 18KHz
18KHz to 100KHz

6.7

20.5 UI
Atten.20dB/
decade
1.5UI
Atten.20dB/
decade
0.2UI

Jitter in transmission
(Freq. = 2048 KHz 32 ppm);
(Band-pass filter with cut off
frequencies f1, f2):
f1 = 20Hz , f2 = 100KHz

B1 = 1.6UI

f1 = 700Hz , f2 = 100KHz

B2 = 0.11 UI

E1 link

7.1

Protocols

7.2

R2 MF Transmitter and receiver


characteristics

7.3

Expandability (Up to 4 card)

7.4

R2 REGISTER

7.4.1

Group monitoring LED

PRI (other
protocols
must be
mentioned)
Comply
with CCITT
Q.454
YES
ITU-T
G.712

Tehran Regional Electric


Company (T.R.E.C)
Page 111 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

7.4.2

Availability

7.4.3

Settings for Vector alarm wire:


Applicable input standards
Applicable standard

7.4.4

Output contact type


Applicable negative voltage

Max. Current with residual voltage


< 3V
between contact and ground
Modem characteristics (data
channel of 2/4 wire):
Standard
Data rate

7.4.6

Every
individual
2Mb/s card
Ground /
Open
Ground
<200
& Open
>50K

Setting for compander exclusion:


Output standard

7.4.5

Rev- 0

Modulation type
Recognition threshold of carrier
detect for a
change from OFF to ON
Recognition threshold of carrier
detect for a
change from ON to OFF
RS232 V24(data channel of
multiplexer)

Ground /
Open
Open
collector
< 60V
(absolute
value)
30mA

ITU-T V.32
14400 bps
max.
FSK
(-43) ~ (45.5)
dBm
(-45.5) ~ (48)
dBm

Tehran Regional Electric


Company (T.R.E.C)
Page 112 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Standard

Async. Parameters
Clock

from DCE

Code

NRZ

Protocol

HDLC sync

Analog 6 wired E&M Trunks

8.1

signaling protocols:
Immediate dial trunks
Delay dial trunks
E&M continues signaling trunks
Wink start trunks

E&M pulse signaling trunks


8.2
8.3
8.3.1

Rev- 0

EIA
19200bps
Max.
8N2

Data rate

Expandability (Up to 700 port)


Analog tie-line interface with E&M
signaling
Output signaling (M wire):
Output standards
Output contact type
Applicable negative voltage

Max. Current between contact and


ground

Tehran Regional Electric


Company (T.R.E.C)

Yes
Yes
(Programmabl
e)
Yes
Yes
(Programmabl
e)
Yes
(Programmabl
e)
Yes

Ground /
open
Open
collector
< 60V
(absolute
value)
30mA

Page 113 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

(with residual voltage < 3V)


Pulse repetition rate
Break / make ratio

8.3.2

Break / make ratio tolerance


Output signaling (compander
exclusion wire):
Output standards
Output contact type
Applicable negative voltage

Max. Current between contact and


ground
(with residual voltage < 3V)
8.3.3

Programma
ble
Programma
ble
1ms

Ground /
open
Open
collector
< 60V
(absolute
value)
30mA

Input signaling (E wire):


Applicable incoming standards
o Ground

R < 200

o Open

Minimum duration of break /


make allowed
input signaling filter

R > 50 K
Programma
ble
Programma
ble
Programma
ble
Digital

Assured recognition of break

> 10ms

Assured non-recognition of break

< 6ms

Pulse repetition rate


Break / make ratio

8.3.4

Input signaling (vector alarm wire):


Applicable incoming standards

Tehran Regional Electric


Company (T.R.E.C)
Page 114 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

o Ground

R < 200

o Open

R > 50K

Analog CO. trunks

9.1

Type

9.2

Features:

9.3

Rev- 0

Twisted pair
(comply
with Iran
Telecommu
nication
Cornpany)

Tone / DP

Yes

Caller-ID

Yes

Pulse metering

Yes

Timer abilities
DTMF transmitter and receiver
characteristics

Yes

10

Wire-Less extension

10.1

Features

10.2

Data / voice

10.3

Signaling / commands toward


terminations

ITU-T Q23

All PABX
supported
features
64Kb/s
on B
channel
16Kb/s
on D
channel

10.4

Signaling / commands toward TDM


proc.

37440 Kb/s
on
asynchronous
serial
fullduplex

Tehran Regional Electric


Company (T.R.E.C)
Page 115 of 139

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

10.5

Max. distance

1000 m

10.6

Max. current consumption

100 mA

CONSOLE
TECHNICAL
NO

DESCRIPTION
REQUIRMENT

Console

1.1

Facilities:

1.2
1.3

TENANT

Yes

Hands free

Yes

Headset

Yes

Hold
Call transfer and intercom
between consoles
Station name, time and date
displaying
Out of service displaying
Sending emergency signal from
station
Dialling over trunk

Yes
Yes
Yes
Yes
Yes
Yes

SCHEDULE MDF & DDF (I)


MAIN & DIGITAL DISTRIBUTION FRAME (MDF & DDF)
TECHNICAL
NO

DESCRIPTION

REQUIRMENT

Page 116 of 139

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

NO

Rev- 0

DESCRIPTION

1
1.1
1.2
1.3

Tehran Regional Electric


Company (T.R.E.C)

TECHNICAL
MDF

Manufacturer (Name &


Country)
Manufacturer's Model
Designation
Mounting style

stand alone
rack mount

MDF CABINET

2.1

Material

2.2

Color code

2.3

Painting type

RAL 7032
as mentioned
in tender doc

2.4

IP code for cabinet must be mentioned

2.5

Weight must be mentioned

2.6

Dimensions (HxWxD) in must be mentioned


cm
Capacity of terminal must be mentioned
blocks
MDF TERMINAL BLOCK

2.7
3
3.1
3.2

3.3

Connection capacity per must be mentioned


block
Connection type :
Normally close

Yes

Normally open

Yes

Protection for
connections :
Over voltage

Yes

Over current

Yes

Accessories

must be mentioned

Page 117 of 139

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

NO

Rev- 0

DESCRIPTION

5
5.1

Tehran Regional Electric


Company (T.R.E.C)
Page 118 of 139

TECHNICAL
DDF

DDF(cabinet & terminal


connections) for any type
of 2Mbps trunk

Yes

SCHEDULE TPS (I)


TPS TECHNICAL SCHEDULES
ROW

PARAMETER

TECHNICAL
REQUIRMENT

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ROW

Tehran Regional Electric


Company (T.R.E.C)
Page 119 of 139

Rev- 0

PARAMETER

TECHNICAL
REQUIRMENT

MANUFACTURER

1-1

NAME AND COUNTRY

1-2

TYPE REFERENCE

2
2-1
3

VALID TEST REFERENCE FOR


ACCORDING TO IEC-60834 AND OTHER RELATIVE
STANDARDS
INTERFACE

3-1

INTERFACE TYPE BETWEEN TPS AND PLC

3-2

INTERFACE TYPE BETWEEN TPS AND OTHER


TELECOMMUNICATION SYSTEMS SUCH AS FIBER
OPTIC AND DIGITAL CHANNEL
COMMANDS

YES

ANALOG ,600,
300~2400Hz
OPTICAL INTERFACE /
G.703-64Kbps

4-1

NUMBER OF INDEPENDENT COMMANDS

4-2

NUMBER OF SIMULTANEOUS COMMANDS

4-3

COMMAND PRIORITY

YES

4-4

TYPE OF COMMAND TRANSMISSION:


CODED
NONCODED
TYPE OF TPS SCHEMS

YES
YES - FSK

5-1

INTER TRIPPING (DIRECT)

YES

5-2

PERMISSIVE TRIPPING (UNDER REACH)

YES

5-3

PERMISSIVE TRIPPING (OVER REACH)

YES

5-4

BLOCKING

YES

OPERATION TIME

6-1

DIRECT TRIPPING (msec)

6-2

PERMISSIVE TRIPPING (msec)

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ROW

Tehran Regional Electric


Company (T.R.E.C)
Page 111 of 139

Rev- 0

PARAMETER

TECHNICAL
REQUIRMENT

6-3

BLOCKING TRIPPING (msec)

6-4

MINIMUM INITALIZATION TIME FOR COMMAND


(mesc)
MAXIMUM ACCEPTABLE PROPAGATION TIME FOR
TELECOMMUNICATION LINK (mesc)
ADDITIONAL DELAY BY NOISE RANGE (mesc)

6-5
6-6
7

2
100
40

TRANSMITTER

7-1

Tx LEVEL RANGE FOR COMMAND / GUARD (dBm)

7-2

RETURN LOSS (dBm)

7-3

NUMBER OF SIGNALS FOR EACH COMMAND

7-4

HARMONIC DISTORTION

5%

7-5

LEVEL BOOSTING OF COMMANDS(dB)

10

20
1

RECEIVER

8-1

Rx LEVEL RANGE FOR COMMAND / GUARD (dBm)

8-2

RETURN LOSS (dB)

20

8-3

DYNAMIC RANGE (dB)

25

8-4

RECEIVER SELECTIVITY 300 Hz OUT OF GUARD'S


AND COMMAND'S RANGE (dBm0)
S/N RATIO (dB)

55

8-5
9

HIGH VOLTAGE INTERFACES

9-1

COMMAND AND START INPUT VOLTAGE RANGES


(Vdc)
NUMBER OF CONTACTS FOR EACH COMMAND

9-2
9-3
9-4

NUMBER OF ALARM CONTACT FOR EACH


COMMAND
COMMAND AND ALARM CONTACTS RATINGS (VA)

9-5

TYPE OF COMMAND CONTACTS

5
48 ~ 220
2
1
250

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ROW

Tehran Regional Electric


Company (T.R.E.C)
Page 111 of 139

Rev- 0

PARAMETER

TECHNICAL
REQUIRMENT

9-6

TYPE OF ALARM CONTACTS

9-7

DURATION TIME BEFORE OPERATING OF ALARM


RELAYS (msec)
ALARM CONDITIONS

10
10-1

TRANSMITTER FAILED

YES

10-2

PLC FAILED

YES

10-3

GUARD SIGNAL ABSENCE

YES

10-4

LOW S/N RATIO

YES

10-5

NO CARD LOCATED

YES

10-6

ANY DAMAGE OF BOARDS

YES

10-7

FAR-END TPS TURNED OFF

YES

10-8

YES

10-9

PRESENCE OF GUARD AND COMMON SIGNAL


SIMULTANEOUSLY
PRESENCE OF COMMAND SIGNAL CONTINUOUSLY

10-10

WATCH DOG ACTIVATION ALARM

YES

11

YES

SOFTWARE FACILITIES

11-1

TPS HARDWARE ASSIGNMENT

YES

11-2

TPS CONFIGURATION

YES

11-3

COMMAND ASSIGNMENT

YES

11-4

COMMAND AND ALARM ASSIGNMENT

YES

11-5

OPERATION TIME ASSIGNMENT FOR EACH


COMMAND INDEPENDENTLY
DURATION AND DELAY TIME ASSIGNMENT FOR
EACH COMMAND INDEPENDENTLY
RECORDE FOR COUNTERS , EVENTS AND FAULTS
WITH TIME TAG
REMOTE TPS CONFIGURATION AND MONITORING

YES

11-6
11-7
11-8

YES
YES
YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ROW

Tehran Regional Electric


Company (T.R.E.C)
Page 112 of 139

Rev- 0

PARAMETER

TECHNICAL
REQUIRMENT

12

BASIS OF TIME

12-1

INTERNAL TIME BASE

YES

12-2

EXTERNAL TIME BASE REAL TIME


CLOCK SUCH AS GPS INTERFACE
DEPENDABILITY AND SECURITY (FOR 10 exp -3)

YES

13-1

S / N RATIO (dB)

13-2

OPERATION TIME (msec)

15

13-3

TYPE AND BANDWIDTH OF NOISE

13

14

TEST FACILITIES

14-1

LOCAL TEST

YES

14-2

LOCAL LOOP TEST

YES

14-3

REMOTE LOOP TEST

YES

14-4

PERIODICALLY AUTO TEST

YES

15

POWER SUPPLY

15-1

NOMINAL SUPPLY VOLTAGE

15-2

SUPPLY TOLERANCE

15-3

POWER SUPPLY RIPPLE

5%<

15-4

POWER CONSUMPTION w

15

16
16-1

-48 VCD
-15%,+20%

ENVIRONMENTAL CONDITION
OPERATION

16-1-1

TEMPERATURE RANGE C

16-1-2

RELATIVE HUMIDITY %

40C 95% at

16-1-3

CLASS OF STANDARD FOR MECHANICAL

IEC 721 -3-3


CLASS 3 M 1

16-2

STORAGE

-5 ~+55C

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ROW

Tehran Regional Electric


Company (T.R.E.C)
Page 113 of 139

Rev- 0

PARAMETER

TECHNICAL

16-2-1

TEMPERATURE RANGE C

REQUIRMENT
-40 ~ +70C

16-2-2

RELATIVE HUMIDITY %

40C 95% at

16-2-3

CLASS OF STANDARD FOR MECHANICAL

17

DIAGNOSTIC

17-1

ONLINE MAINTENANCE AND DIAGNOSTIC

17-2

CHECKING FACILITIES :
POWER SUPPLY
OTHERS
ELECTROMAGNETIC AND INSULATION

18

IEC-721-3-1
CLASS 1 K 5
YES
YES
YES
YES

18-1

HF DISTURBANCE

18-2

FAST TRANSIENT BURST

2000 V / IEC-801-4

18-3

ELECTROMAGNETIC DISCHARGE

8000 V / IEC-801-2

19

2500 V / IEC-255-22-1

ALL OF THE PERIPHERAL EQUIPMENTS , TOOLS ,


HARDWARE , SOFTWARE AND TECHNICAL
DOCUMENTS INCLUDED WITH EACH TPS
TERMINAL

23- SCHEDULE LINE TRAP AND LMU (I)


LINE TRAP AND LMU TECHNICAL SCHEDULES

YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 114 of 139

Rev- 0

UNIT

TECHNICAL
REQUIRMENT

System Characteristics
1

Nominal service voltage

kV

63

Highest system voltage

kV

72.5

Rated frequency

Hz

50

Number of phases

3 phase

Type of neutral grounding

Effective

Surge impedance of power transmission lines

400

Line Trap Characteristics


7

Type

Outdoor, Air core, Dry,


single phase
As per IEC 60353
/19.3.1
As per IEC 60353
/10.1
1250

Basic Insulation Level.

kV peak

One minute power frequency withstand voltage

kV rms

10

Continuous current of line trap at IEC 353

11

Rated short circuits withstand current

kA rms

40

12

Rated asymmetrical short time current

kA peak

100

13

Rated duration of short circuit

Sec.

14

Inductance of main coil

m.H

0.5

15

Required blocking bandwidth for line trap

kHz

60- 400

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ITEM

DESCRIPTION

Tehran Regional Electric


Company (T.R.E.C)
Page 115 of 139

Rev- 0

UNIT

TECHNICAL
REQUIRMENT

16

Max. Tapping loss within the specified band width

db

2.6

17

Max. R.I.V. level measured at 1.15 * Um KV & 1 MHz

18

Type & Rated discharge current of protective device

kA

Zno / 10

19

Whether bird barrier is required?

20

Method of the line trap installation

21

Blocking Impedance of line trap within the specified


bandwidth

Yes
suspension

600

Line matching Unit


22

Type of coupling.

Phase- Ground

23

Degree of protection of line matching unit cabinet

IP55

24

Drain coil to connect output lead of CVT to ground

Yes

25

Whether disconnect and ground switch for


grounding the L.M.U is required?

Yes

24- PABX SCHEDULE DATA (I)


RATING AND CHARACTERISTICS OF DISTRIBUTED CONTROL SYSTEM

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

PABX
TECHNICAL
NO

DESCRIPTION
REQUIRMENT

GENERAL

1.1

Manufacturer (Name & Country)

1.2
1.3

Manufacturer's Model Designation


Designation technology

1.4

PABX basis

1.5

Call processing performance

Converged
technology
TDM-PCM
& IP & ISDN
Non-blocking

1.6

Hardware cards Hot-plugging

Yes

1.7

Redundancy

1.8

1.9

1.10
1.11

1.12

DC-DC converter

Yes

Other (must be mentioned)

Yes

System remoting
Relative to central switch

Yes

Unrelated to central switch

Yes

Busy Hour Call Attempts (BHCA)

250000

Stand alone extending up to 5000


port
PABX Operating System (OS) :

Yes

Basis

Open Source

Man Machine Interface (MMI)

Windows

Supported Carriers :
E1
Ethernet

optical
& electrical
IEEE 802.3

Tehran Regional Electric


Company (T.R.E.C)
Page 116 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

o Input VF level

6 wire and 2
wire
0 dBm

o Output VF level

0 dBm

Cable

Microwave
o Input VF level

Tehran Regional Electric


Company (T.R.E.C)

6 wire
-16dBm

QSIG

Yes

R2

Yes

CAS
1.13

IP trunking protocols

1.14

Time limitation for trunk access

1.15

Automatic attendant

Yes
must be
mentioned
Yes
(programmable)
Yes

1.16

Voice mail

Yes

1.17

Cabinet color code

RAL 7032

1.18

Cabinet painting type

as mentioned

1.19

IP code for cabinet

1.20

Dimensions (HxWxD) in cm

Management and accounting

2.1
2.2
2.3

2.4

Supervision and programming for


digital trunks
List Cost Routing (LCR)
Accounting management & Call
charge & Traffic

in tender doc
must be
mentioned
must be
mentioned

Full
Yes
Yes

report

must be
mentioned

PABX software and database


backup

flash memory
& CD ROM

Page 117 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

2.5

Rev- 0

Fault declaration and warning :

& flappy disk


mention other
media
Programmable

System level

Yes

Card level

Yes

Port level

Yes
must be
mentioned

Other levels
Real time alarm, event, status and
system states:
Representation

Yes

Saving

Yes

Management

Yes

2.7

Software offline working

Yes

Analog extensions

3.1

Line type

Twisted pair

3.2

Line loop resistance

2000

Min. distance

6km
(0.4mm
diameter)
12km
(0.6mm
diameter)
50 K

2.6

Max. distance

3.3
3.4
3.5
3.6
3.7

Line insulation
Earth recall recognized by resistance
to ground
Line seizure (off-hook) recognition
time
Dialing
Line release (on hook) recognition
time

Tehran Regional Electric


Company (T.R.E.C)

30
100ms
DTMF and Pulse
> 200 ms

Page 118 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

3.8

3.9

Resistance between the two line


terminals during
the break (loop open)
Voltage drop between the two line
terminals
during the make (loop close)

3.10

3.11

3.12

3.13

Stabilization time of the line current


for values
greater than 15 mA
Attenuation on dialing impulses
during
conversation

> 100K

5.5V
for 18mA I
28 mA
15 ms

85 dB

Call signaling :
Maximum voltage output

75 Vrms

Frequency

25Hz

Normal charge

2REN

Twisted pair powering :


Idle current
Loop current with loop resistance
< 1 K
Current with loop in short circuit

3.14

Rev- 0

Caller ID:
Subscriber line protocol over the
local for
display (and related) services
Method for CLI transmission

3.15

Terminal Equipment Alerting


Signal
Expandability (Up to 48 port)

Digital extensions

100A
22mA
28mA

On hook data
transmission
Data
transmission
prior to ringing
Ringing Pulse
Yes

Tehran Regional Electric


Company (T.R.E.C)
Page 119 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

4.1

4.3

Line type
MULTI-CALL Key system for
telephone set
Local power for telephone set

4.4

Facilities of telephone set

4.2

4.5

4.6

Minimum distance for digital phone


0.6 mm
twisted pair

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Twisted pair
Yes
No
must be
mentioned
600m

Power supply
Current consumption

50mA Max.

4.7

Expandability (Up to 48 port)

Yes

IP extensions

5.1

Technical characteristics of IP
phone:

5.1.1

LCD

5.1.2

Function-Key

With backlit,
min 20
character in two
lines
Min 12 keys
with LED
Ring tone ,
voices
and
disconnection
Yes (full duplex)

5.1.3

Adjustable keys

5.1.4

Hands-free possibility

5.1.5

Interactive user

Min 2 dialog
keys

5.1.6

Port

Dual , 10/100
Mbps

Page 121 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ISDN

6.1

Protocol
The impedance to ground at both
the input & output:
For freq. from 0 Hz to 1 MHz
Maximum line length such that the
maximum
attenuation does not exceed 6 dB at
1 MHz
Characteristics of the transmitted
signal

6.2

6.3

6.4
6.4.1

Frequency

6.4.2

Line coding
Number of couplings for each
transmission direction :
Coaxial

6.4.3

o Impedance
o Impulse nominal peak voltage
o Maximum voltage in impulse
absence
Balanced twisted pair
o Impedance

6.4.4

6.4.5

6.4.6

o Impulse nominal peak voltage


o Maximum voltage in impulse
absence
Nominal duration of impulse
Amplitude ratio between positive
and negative
impulses with reference to ground
Ratio of duration between positive
and negative

Rev- 0

PRI

> 1000

2048KHz
50ppm
HDB3

One
75
2.37 V
237 mV
One
120
3.0V
300 mV
244 nsec

10.05

10.05

Tehran Regional Electric


Company (T.R.E.C)
Page 121 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Rev- 0

impulses at 50%
6.4.7

Rise-time

64 nsec Max.

6.4.8

Overshoot

20% Max.

6.4.9

Output signal balancing, using


120 connection :
Up to 1MHz
From 1MHz to 30MHz

6.5

Characteristics of received signal

6.5.1
6.5.2

Impedance characteristic
Max. attenuation with variations
proportional to
square root of f

6.5.3

Return loss:
From 512KHz

6.6

75 or 120
6 dB

to 1024KHz

12dB

From 1024 KHz to 2048 KHz

18dB

From 2048 KHz to 3072 KHz

14dB

Jitter in reception
(Freq. = 2048 KHz 32 ppm; 1UI =
488 nsec):
0 to 12x10-6 Hz
12x10-6 to 20Hz
20 to 2400Hz
2400 to 18KHz
18KHz to 100KHz

6.7

40 dB
Atten.20dB/dec
ade

Jitter in transmission
(Freq. = 2048 KHz 32 ppm);
(Band-pass filter with cut off

20.5 UI
Atten.20dB/dec
ade
1.5UI
Atten.20dB/dec
ade
0.2UI

Tehran Regional Electric


Company (T.R.E.C)
Page 122 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

frequencies f1, f2):


f1 = 20Hz , f2 = 100KHz

B1 = 1.6UI

f1 = 700Hz , f2 = 100KHz

B2 = 0.11 UI

E1 link

7.1

Protocols

7.2

R2 MF Transmitter and receiver


characteristics

PRI (other
protocols
must be
mentioned)
Comply
with CCITT
Q.454
YES

7.3

Expandability (Up to 4 card)

7.4

R2 REGISTER

7.4.1

Group monitoring LED

ITU-T G.712

7.4.2

Availability

Every individual
2Mb/s card

7.4.3

Settings for Vector alarm wire:


Applicable input standards

Ground / Open

Applicable standard

Ground <200
& Open >50K

7.4.4

Setting for compander exclusion:


Output standard

Ground / Open

Output contact type

Open collector

Applicable negative voltage

< 60V
(absolute value)

7.4.5

Max. Current with residual voltage


< 3V
between contact and ground
Modem characteristics (data
channel of 2/4 wire):
Standard

30mA

ITU-T V.32

Page 123 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

7.4.6

14400 bps max.

Modulation type
Recognition threshold of carrier
detect for a
change from OFF to ON
Recognition threshold of carrier
detect for a
change from ON to OFF
RS232 V24(data channel of
multiplexer)
Standard

FSK

Data rate

19200bps Max.

Async. Parameters

8N2

Clock

from DCE

Code

NRZ

Protocol

HDLC sync

Analog 6 wired E&M Trunks

8.1

signaling protocols:
Immediate dial trunks
Delay dial trunks
E&M continues signaling trunks
Wink start trunks
E&M pulse signaling trunks

8.2
8.3
8.3.1

Rev- 0

Data rate

Expandability (Up to 700 port)


Analog tie-line interface with E&M
signaling
Output signaling (M wire):

Tehran Regional Electric


Company (T.R.E.C)

(-43) ~ (-45.5)
dBm
(-45.5) ~ (-48)
dBm

EIA

Yes
Yes
(Programmable)
Yes
Yes
(Programmable)
Yes
(Programmable)
Yes

Output standards

Ground / open

Output contact type

Open collector

Page 124 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Applicable negative voltage

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

< 60V
(absolute value)

Max. Current between contact and


ground
(with residual voltage < 3V)

8.3.2

30mA

Pulse repetition rate

Programmable

Break / make ratio

Programmable

Break / make ratio tolerance


Output signaling (compander
exclusion wire):
Output standards

1ms

Output contact type

Open collector

Applicable negative voltage

< 60V

Ground / open

(absolute value)
Max. Current between contact and
ground
(with residual voltage < 3V)
8.3.3

30mA

Input signaling (E wire):


Applicable incoming standards

8.3.4

o Ground

R < 200

o Open

R > 50 K

Pulse repetition rate

Programmable

Break / make ratio


Minimum duration of break /
make allowed
input signaling filter

Programmable

Assured recognition of break

> 10ms

Assured non-recognition of break

< 6ms

Programmable
Digital

Input signaling (vector alarm wire):


Applicable incoming standards
o Ground

R < 200

Page 125 of 139

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

o Open
9

Analog CO. trunks

9.1

Type

9.2

Features:

9.3

Rev- 0

R > 50K

Twisted pair
(comply with
Iran
Telecommunicat
ion
Cornpany)

Tone / DP

Yes

Caller-ID

Yes

Pulse metering

Yes

Timer abilities
DTMF transmitter and receiver
characteristics

Yes

10

Wire-Less extension

10.1

Features

10.2

Data / voice

Tehran Regional Electric


Company (T.R.E.C)

ITU-T Q23

All PABX
supported
features
64Kb/s
on B channel

10.3

Signaling / commands toward


terminations

16Kb/s
on D channel

10.4

Signaling / commands toward TDM


proc.

37440 Kb/s
on asynchronous
serial full-duplex

10.5

Max. distance

1000 m

Page 126 of 139

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

10.6

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

Max. current consumption

100 mA

CONSOLE
TECHNICAL
NO

DESCRIPTION
REQUIRMENT

Console

1.1

Facilities:

1.2
1.3

TENANT

Yes

Hands free

Yes

Headset

Yes

Hold
Call transfer and intercom
between consoles
Station name, time and date
displaying
Out of service displaying
Sending emergency signal from
station
Dialling over trunk

Yes
Yes
Yes
Yes
Yes
Yes

SCHEDULE MDF & DDF (I)


MAIN & DIGITAL DISTRIBUTION FRAME (MDF & DDF)
TECHNICAL
NO
1

DESCRIPTION

REQUIRMENT
MDF

Page 127 of 139

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

NO
1.1
1.2
1.3

Tehran Regional Electric


Company (T.R.E.C)

Rev- 0

DESCRIPTION

TECHNICAL

Manufacturer (Name &


Country)
Manufacturer's Model
Designation
Mounting style

stand alone
rack mount

MDF CABINET

2.1

Material

2.2

Color code

2.3

Painting type

RAL 7032
as mentioned
in tender doc

2.4

IP code for cabinet must be mentioned

2.5

Weight must be mentioned

2.6

Dimensions (HxWxD) in must be mentioned


cm
Capacity of terminal must be mentioned
blocks
MDF TERMINAL BLOCK

2.7
3
3.1
3.2

3.3

Connection capacity per must be mentioned


block
Connection type :
Normally close

Yes

Normally open

Yes

Protection for
connections :
Over voltage

Yes

Over current

Yes

Accessories

DDF

5.1

DDF(cabinet & terminal

must be mentioned

Page 128 of 139

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 129 of 139

Rev- 0

NO

DESCRIPTION

TECHNICAL

connections) for any type


of 2Mbps trunk

Yes

SCHEDULE TPS (I)


TPS TECHNICAL SCHEDULES
ROW

PARAMETER

TECHNICAL
REQUIRMENT

MANUFACTURER

1-1

NAME AND COUNTRY

1-2

TYPE REFERENCE

2
2-1
3

VALID TEST REFERENCE FOR


ACCORDING TO IEC-60834 AND OTHER RELATIVE
STANDARDS
INTERFACE

3-1

INTERFACE TYPE BETWEEN TPS AND PLC

3-2

INTERFACE TYPE BETWEEN TPS AND OTHER


TELECOMMUNICATION SYSTEMS SUCH AS FIBER
OPTIC AND DIGITAL CHANNEL
COMMANDS

YES

ANALOG ,600,
300~2400Hz
OPTICAL INTERFACE /
G.703-64Kbps

4-1

NUMBER OF INDEPENDENT COMMANDS

4-2

NUMBER OF SIMULTANEOUS COMMANDS

4-3

COMMAND PRIORITY

YES

4-4

TYPE OF COMMAND TRANSMISSION:


CODED
NONCODED
TYPE OF TPS SCHEMS

5
5-1

INTER TRIPPING (DIRECT)

YES
YES - FSK
YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ROW

Tehran Regional Electric


Company (T.R.E.C)
Page 131 of 139

Rev- 0

PARAMETER

TECHNICAL
REQUIRMENT
YES

5-2

PERMISSIVE TRIPPING (UNDER REACH)

5-3

PERMISSIVE TRIPPING (OVER REACH)

YES

5-4

BLOCKING

YES

OPERATION TIME

6-1

DIRECT TRIPPING (msec)

6-2

PERMISSIVE TRIPPING (msec)

6-3

BLOCKING TRIPPING (msec)

6-4

MINIMUM INITALIZATION TIME FOR COMMAND


(mesc)
MAXIMUM ACCEPTABLE PROPAGATION TIME FOR
TELECOMMUNICATION LINK (mesc)
ADDITIONAL DELAY BY NOISE RANGE (mesc)

6-5
6-6
7

2
100
40

TRANSMITTER

7-1

Tx LEVEL RANGE FOR COMMAND / GUARD (dBm)

7-2

RETURN LOSS (dBm)

7-3

NUMBER OF SIGNALS FOR EACH COMMAND

7-4

HARMONIC DISTORTION

5%

7-5

LEVEL BOOSTING OF COMMANDS(dB)

10

20
1

RECEIVER

8-1

Rx LEVEL RANGE FOR COMMAND / GUARD (dBm)

8-2

RETURN LOSS (dB)

20

8-3

DYNAMIC RANGE (dB)

25

8-4

RECEIVER SELECTIVITY 300 Hz OUT OF GUARD'S


AND COMMAND'S RANGE (dBm0)
S/N RATIO (dB)

55

8-5
9

HIGH VOLTAGE INTERFACES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ROW
9-1
9-2
9-3

Page 131 of 139

Rev- 0

PARAMETER
COMMAND AND START INPUT VOLTAGE RANGES
(Vdc)
NUMBER OF CONTACTS FOR EACH COMMAND

9-4

NUMBER OF ALARM CONTACT FOR EACH


COMMAND
COMMAND AND ALARM CONTACTS RATINGS (VA)

9-5

TYPE OF COMMAND CONTACTS

9-6

TYPE OF ALARM CONTACTS

9-7

DURATION TIME BEFORE OPERATING OF ALARM


RELAYS (msec)
ALARM CONDITIONS

10

Tehran Regional Electric


Company (T.R.E.C)

TECHNICAL
REQUIRMENT
48 ~ 220
2
1
250

10-1

TRANSMITTER FAILED

YES

10-2

PLC FAILED

YES

10-3

GUARD SIGNAL ABSENCE

YES

10-4

LOW S/N RATIO

YES

10-5

NO CARD LOCATED

YES

10-6

ANY DAMAGE OF BOARDS

YES

10-7

FAR-END TPS TURNED OFF

YES

10-8

YES

10-9

PRESENCE OF GUARD AND COMMON SIGNAL


SIMULTANEOUSLY
PRESENCE OF COMMAND SIGNAL CONTINUOUSLY

10-10

WATCH DOG ACTIVATION ALARM

YES

11

YES

SOFTWARE FACILITIES

11-1

TPS HARDWARE ASSIGNMENT

YES

11-2

TPS CONFIGURATION

YES

11-3

COMMAND ASSIGNMENT

YES

11-4

COMMAND AND ALARM ASSIGNMENT

YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ROW
11-5
11-6
11-7
11-8
12

Tehran Regional Electric


Company (T.R.E.C)
Page 132 of 139

Rev- 0

PARAMETER
OPERATION TIME ASSIGNMENT FOR EACH
COMMAND INDEPENDENTLY
DURATION AND DELAY TIME ASSIGNMENT FOR
EACH COMMAND INDEPENDENTLY
RECORDE FOR COUNTERS , EVENTS AND FAULTS
WITH TIME TAG
REMOTE TPS CONFIGURATION AND MONITORING

TECHNICAL
REQUIRMENT
YES
YES
YES
YES

BASIS OF TIME

12-1

INTERNAL TIME BASE

YES

12-2

EXTERNAL TIME BASE REAL TIME


CLOCK SUCH AS GPS INTERFACE
DEPENDABILITY AND SECURITY (FOR 10 exp -3)

YES

13-1

S / N RATIO (dB)

13-2

OPERATION TIME (msec)

15

13-3

TYPE AND BANDWIDTH OF NOISE

13

14

TEST FACILITIES

14-1

LOCAL TEST

YES

14-2

LOCAL LOOP TEST

YES

14-3

REMOTE LOOP TEST

YES

14-4

PERIODICALLY AUTO TEST

YES

15

POWER SUPPLY

15-1

NOMINAL SUPPLY VOLTAGE

15-2

SUPPLY TOLERANCE

15-3

POWER SUPPLY RIPPLE

5%<

15-4

POWER CONSUMPTION w

15

16
16-1

ENVIRONMENTAL CONDITION
OPERATION

-48 VCD
-15%,+20%

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

ROW

Tehran Regional Electric


Company (T.R.E.C)
Page 133 of 139

Rev- 0

PARAMETER

TECHNICAL
REQUIRMENT

16-1-1

TEMPERATURE RANGE C

16-1-2

RELATIVE HUMIDITY %

40C 95% at

16-1-3

CLASS OF STANDARD FOR MECHANICAL

IEC 721 -3-3


CLASS 3 M 1

16-2

STORAGE

16-2-1

TEMPERATURE RANGE C

16-2-2

RELATIVE HUMIDITY %

16-2-3

CLASS OF STANDARD FOR MECHANICAL

17

-40 ~ +70C
40C 95% at
IEC-721-3-1
CLASS 1 K 5

DIAGNOSTIC

17-1

ONLINE MAINTENANCE AND DIAGNOSTIC

17-2

CHECKING FACILITIES :
POWER SUPPLY
OTHERS
ELECTROMAGNETIC AND INSULATION

18

-5 ~+55C

YES
YES
YES
YES

18-1

HF DISTURBANCE

18-2

FAST TRANSIENT BURST

2000 V / IEC-801-4

18-3

ELECTROMAGNETIC DISCHARGE

8000 V / IEC-801-2

19

ALL OF THE PERIPHERAL EQUIPMENTS , TOOLS ,


HARDWARE , SOFTWARE AND TECHNICAL
DOCUMENTS INCLUDED WITH EACH TPS
TERMINAL

2500 V / IEC-255-22-1

YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 134 of 139

Rev- 0

25- TELEPHONE SCHEDULE DATA (I)


RATING AND CHARACTERISTICS OF LIGHTING AND TELEPHONE
ITE
M

DESCRIPTION

UNIT

TECHNICAL
REQUIREMENTS

1.

Telephone system

1.1

Type of control & communication cable in telephone


system

1.2

Degree of protection for terminal boxes

PVC or XLPE insulated with wire


or interlocking type armour &
overall fire retardant
thermoplastic jacket

1.2.1

Indoor

IP42

1.2.2

Outdoor

IP55

1.3

Type of telephone

Desk mounted / wall mounted

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Tehran Regional Electric


Company (T.R.E.C)
Page 135 of 139

Rev- 0

2.

Type of incoming circuit breaker in panel

MCCB

3.

Type of outgoing circuit breakers in panel

(MCCB or MCB)

4.

Rating of socket

4.1

Single phase

>16

4.2

Three phase

Acc. To calculation

5.

Minimum cross section of outdoor lighting cables

mm

6.

Minimum cross section of indoor lighting cables

mm

1.5

7.

Minimum cross section of socket cables

mm

2.5

8.

Type of equipments in battery room

explosion proof

26- SCHEDULE OPTICAL ACCESS MULTIPLEXER (I)


OPTICAL ACCESS MULTIPLEXER TECHNICAL SCHEDULES
ITEM

DESCRIPTION

UNIT

TECHNICAL
REQUIRMENT

1
2

Applicable Standards

ITU-T G,Q,V

Configurations
Terminal with Multiplexing & Submultiplexing

YES

ADM in Linear & Ring

YES

CXC in Mesh & Tree

YES

General functionalities

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

YES
YES
at STM-1, E1, n64 Kbps, 64
Kbps, Time slot and bit levels

Cross-connect capacity

252*VC-12

Drop/Insert

YES

VF operation

YES

Signaling
Transmission delay

Page 136 of 139

Rev- 0

Time multiplexing/demultiplexing of all voice


and data channels
Subrate data multiplexing based on ITU-T VSeries synch/async data
Cross-Connecting

Tehran Regional Electric


Company (T.R.E.C)

ITU-T G.704, G.706, G.732


E&M,CAS
<250

Redundancy
Line card redundancy

1+1

Power supply redundancy

1+1

Cross Connection redundancy

1+1

Redundancy of processor

1+1

Clock

1+1

Line Interface
E1

YES

STM-1 (up to 90 Km)

YES

Interfaces

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

E1

YES

2/4 wire E&M signaling

YES

2/4 wire FXO/FXS

YES

0.3-64 Kbps Sync./Async. V.24/V.28

YES

64 Kbps Sync./Async. V.35

YES

64 Kbps Co/Contra-directional, G.703

YES

N 64 Kbps Sync./Async.

YES

V.24/RS-232, V & X-Series Recs. (V.11/RS-422,


V.28, V.35, V.36, X.21,24
Ethernet/FEthernet (with L2 Switching
Capability)

YES
YES

Rack and Shelf

Power Supply

Page 137 of 139

Rev- 0

19" rack mounting

Tehran Regional Electric


Company (T.R.E.C)

Closed rack
VDC

-48

Operating temperature

XXX

Storage & transportation temperature

XXX

Humidity

XXX

Environmental Condition

Minimum ports per card


E1

12

2/4W E&M Signaling

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Namdaran Transmission

System Eng. Co

Technical Specification for Schedule Data

10

11

Tehran Regional Electric


Company (T.R.E.C)
Page 138 of 139

Rev- 0

2/4W FXO/FXS

0.3-64 Kbps (Sync./Async.) V.24/V.28

64 Kbps Co/Contra-directional G.703

Ethernet

Minimum ports per shelf


E1

21

2/4W E&M Signaling

30

2/4W FXO/FXS

30

0.3-64 Kbps (Sync./Async.) V.24/V.28

30

64 Kbps Co/Contra-directional G.703

30

Ethernet

16
Management System

Maximum number of supported NEs

XXX

Operation, Administration,
Maintenance and Provisioning (OAM&P)
Configuration Management

YES

Remote control, monitoring and configuration

YES

Remote commissioning

YES

configuration information storage in a nonvolatile memory


Alarm Management

YES

YES

YES

Namdaran Transmission

System Eng. Co

Procurement and Finance (P.F) of 312


Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)

Technical Specification for Schedule Data

Page 139 of 139

Rev- 0

Management Port

YES

Performance Management

12

Tehran Regional Electric


Company (T.R.E.C)

G.821

ES, SES,CRC Errors ,Remote Alarm Indications

YES

Graphical performance report

YES

Periodical PM info.

YES

LCT Hardware (Laptop Specification)


Type & CPU

Sony/DELL Core i7

HHD Capacity

GB

>500

RAM

GB

LCD size

inch