Table 23.173: Output Relay and Operating Specifications


Type of Relay

RM4TG

RM4TU

RM4TR

2 C/O

2 C/O

2 C/O

RM4TA
RM4TA3
2 C/O

2 C/O

Number of SPDT (C/O) Contacts


8 A resistive UL B300 a

DPDT
DPDT

DPDT

DPDT

RM4TA0
1C/O

Energized during fault free


operation. De-energized or
unable to energize on
detection of phase reversal
fault or failure of one or
more phases.

Energized during fault free


operation. De-energized
on detection of under
voltage or phase reversal
fault or failure of one or
more phases.

Energized during fault free


operation. De-energized
on detection of over
voltage, undervoltage or
phase reversal fault or
phase failure.

SPDT
Energized during fault free
operation. De-energized
on detection of phase
imbalance fault, phase
failure or phase reversal
fault.

Energized during fault free


operation. De-energized
on detection of an over
voltage or undervoltage
fault.

As % of the set value

3%

3%

3%

3%

Depending on the
permissible ambient
temperature

< 0.06% per C

< 0.06% per C

< 0.06% per C

< 0.06% per C

Within the supply


measuring range

< 0.5%

< 0.5%

< 0.5%

< 0.5%

As% of the full scale value:


10%

Output Relay State

Accuracy of the
Switching Threshold
Setting

Switching Threshold
Drift

Accuracy of the Time


Delay Setting
Time Delay Drift
Hysteresis

RM4UB

Fixed

Measuring Cycle

< 80 ms
a

10%
< 0.5%
< 0.07% per C
About 5% of the
de-energization threshold
< 80 ms

10%

10%

< 0.5%
< 0.07% per C
About 5% of the
de-energization threshold
< 80 ms

DPDT

10%

< 0.5%
< 0.07% per C
About 5% of the
de-energization threshold
< 80 ms

< 0.5%
< 0.07% per C
About 5% of the
de-energization threshold
< 80 ms

For additional contact ratings, refer to the catalog.

Table 23.174: Relays with Adjustable Thresholds (Single Phase Voltage Relay)
Adjustable
Time Delay

Rated Main Supply


Voltage b

Control Threshold

Width
in.

Width
mm

Output Relay

Catalog Number

$ Price

RM4UB34

362.00

RM4UB35

362.00

2 C/O

23

100200 V
50/60 Hz

Undervoltage
80120 V
Overvoltage
160220 V

180270 V
50/60 Hz

Undervoltage
160220 V
Overvoltage
220300 V

0.89

22.5
DPDT
2 C/O

0.110 seconds
0.89

22.5

RELAYS AND TIMERS

DPDT

RM4UB

Can be used on other supply voltages provided that the minimum operational voltages, maximum voltage between phases and compatibility are within
the control threshold ranges supplied in the table above.

Dimensions
Dual Dimensions:

RM4U, RM4T

Direct Mounting

Inches
Millimeters

3.15
80

23-36

0.89
22.5

3.52
89.5

I11

0.24
6

3.07
78

3.07
78

0.24
6

Rail Mounting

3.23
82

Discount
Schedule

0.16
4

2007 Schneider Electric


All Rights Reserved

Courtesy of Steven Engineering, Inc. 230 Ryan Way, South San Francisco, CA 94080-6370 General Inquiries: (800) 670-4183 www.stevenengineering.com

Phase Failure Relays

RM4T (Three Phase)

www.us.schneider-electric.com

Refer to Catalog 8430CT0001

FOR CURRENT INFORMATION

Table 23.175: Control Relays: Phase Reversal and Presence of Phases (Three Phase)
Time Delay

Rated Main Supply Voltage

Width, in.

None

220440 Vac
50/60 Hz

0.89

Width, mm Output Relay


2 C/O
22.5

Catalog Number

$ Price

RM4TG20

166.00

DPDT

Table 23.176: Control Relays: Phase Reversal and Presence of Phases + Undervoltage (Three Phase)
Time Delay

Rated Main Supply Voltage

Control Threshold

Width, in.

220240 V
50/60 Hz

Undervoltage
160220 V

0.89

RM4TG20

Width, mm Output Relay


2 C/O
22.5

Catalog Number

$ Price

RM4TU01

207.00

RM4TU02

207.00

DPDT
2 C/O

None
380-440 V
50/60 Hz

Undervoltage
300430 V

0.89

22.5
DPDT

Control Relays: Phase Reversal and Presence of Phases + Overvoltage and Undervoltage (Three Phase)
Table 23.177: Relays with Fixed Voltage Thresholds
Relays with Fixed Voltage Thresholds
Adjustable Time Delay

Rated Main Supply Voltage

Control Threshold

Width, in.

220 V
50/60 Hz

Undervoltage
198 V
Overvoltage
242 V

0.89

400 V
50/60 Hz

Undervoltage
360 V
Overvoltage
440 V

Width, mm Output Relay


2 C/O
22.5

Catalog Number

$ Price

RM4TR33

311.00

RM4TR34

311.00

Catalog Number

$ Price

RM4TR31

352.00

RM4TR32

352.00

DPDT
2 C/O

0.110 seconds
0.89

22.5
DPDT

RM4TR33

Table 23.178: Relays with Adjustable Voltage Thresholds


Relays with Adjustable Voltage Thresholds
Rated Main Supply Voltage

Control Threshold

Width, in.

200240 V
50/60 Hz

Undervoltage
160220 V
Overvoltage
220300 V

0.89

380440V
50/60 Hz

Undervoltage
300430 V
Overvoltage
420480 V

Width, mm Output Relay


2 C/O
22.5
DPDT
2 C/O

0.110 seconds
0.89

22.5
DPDT

Table 23.179: Control Relays: Phase Reversal and Presence of Phases + Imbalance (Three Phase)
Time Delay on
De-Energization

Rated Main Supply Voltage

Control Threshold

Width, in.

Width, mm Output Relay

Catalog Number

$ Price

RM4TA01

269.00

RM4TA02

269.00

RM4TA31

311.00

RM4TA32

311.00

1 C/O
200240 V
50/60 Hz

Imbalance
515%

0.89

22.5
SPDT
1 C/O

Fixed
0.5 seconds
380440 V
50/60 Hz

Imbalance
515%

0.89

22.5

200240 V
50/60 Hz

Imbalance
515%

0.89

22.5

23

SPDT
2 C/O

RELAYS AND TIMERS

Adjustable Time Delay

DPDT
2 C/O

Adjustable
0.110 seconds

RM4TA01
380440 V
50/60 Hz

Imbalance
515%

0.89

22.5
DPDT

Table 23.180: Approvals


File E164353
CCN NKCR

Approvals/Standards
Conforming to Standards
Temperature Ratings
Supply Voltage Range
Output Contact Ratings
a

2007 Schneider Electric


All Rights Reserved

File LR89150
Class 3211 07

IEC 60255-6 EN 60255-6


Storage
-40oF to 185oF (-40oC to 85oC)
Operational -4oF to 149oF (-20oC to 65oC)
See listings above.
8 A resistive UL B300 a

For additional contact ratings, refer to the catalog.

I11

Discount
Schedule

23-37

Courtesy of Steven Engineering, Inc. 230 Ryan Way, South San Francisco, CA 94080-6370 General Inquiries: (800) 670-4183 www.stevenengineering.com