Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
BJEC
T-
TOPICDISASTER
RESISTANT
CONSTRUCTION
SUBTOPICRESISTANT
CONSTRUCTION
FIRE
TECHNICAL ELECTIVES
RASHMI BHAT.
FOURTH YEAR
B.ARCH(2012-13)
1 | Page
PAD.DR.D.Y.PATIL
COLLAGE OF
ARCHITECTURE
CONTENTS1.
2.
3.
4.
5.
INTRODUCTION
BASIC REQUIREMENTS OF FIRE RESISTIVE CONSTRUCTION
IMPORTANT CONSIDERATIONS IN FIRE PROTECTION
FIRE RESISTING MATERIALS AND ITS CHARACHTERISTICS
FIRE RESISTING PROPERTIES OF BUILDINGS
5.1 FIRE RESISTANCE
5.2 BENEFITS
5.3 FIRE RESISTANCE TESTING
5.4 FIRE RESISTIVE ASSEMBLIES
6. FIRE RESISTIVE BUILDING TECHNIQUES
6.1 REASONABLE RESISTANCE
6.2 BUILT-IN PREVENTION
6.3 PLANNED PASSIVITY
6.4 PASSIVE AUTOMATION
7. FIRE PROTECTION ELECTRICAL LIFE SAFETY CIRCUITS
8. FIRE PROTECTION USING CONSTRUCTION METHODS
9. STUDY OF FIRE RESISTIVE BUILDINGS( case study )
10. CONCLUSIONS
11. REFERENCES
1. INTRODUCTION:
The building where we spent our life should be strong enough to handle natural
disaster like flood, earthquake and fire etc. Fire-resistive construction is that construction
designed to prevent or slow the spread of fire using materials and assemblies tested for their
fire-resistive properties. The International Building Code (IBC) defines fire resistance as:
That property of materials or their assemblies that prevent or retard the passage of
excessive heat, hot gases or flames under conditions of use.
It is defined as the fire protection of the occupants of the building and adjacent
buildings, contents, and structure of the building, and adjacent buildings from the risks of
fire and spread of fire. Alternatively, the purpose of fire protection is to protect life, goods
and activities within a building and of adjacent buildings. This objective is achieved by using
fire-material in construction; by suitable planning of building internally and in relation to
adjacent buildings and providing suitable means of quick escape for the occupants. These
measures are essential to minimize the spread of the fire and thus limit the total damage to a
minimum.
Fire protection is basic requirement of a building. To make buildings completely fireproof is not a practical proposition, though may not be impossible. However, the chances of
catching a fire in building can be reduced through adequate planning of building units in
horizontal and vertical directions (i.e. adequate means of escape), properly designing the
structural elements such as walls, columns, beams, etc. and use of these materials have
obvious limitations, as the contents of many buildings are more easily set on fire than the
materials used in their construction. The designer, therefore, should resort to the methods of
achieving the recognized standards of fire safety specified in the Buildings Code for different
classes of occupancy.
goods, film stores etc, all required fire-proof structures. Buildings like cinema theaters,
schools, town halls, libraries, hotels, multistoried office buildings etc. should offer a better
degree of fire resistance.
In multistoried office buildings suitable equipment for detecting, extinguishing and
warning of fire should be installed in niches on all the floors for fire-fighting purposes. It
should be remembered that severity of a fire depends largely upon the amount, nature and
distribution of combustible materials in a buildings. The nature of hazards associated with
the fire is of following three types in order of importance:
i.
ii.
iii.
Even if the collapse of not occurred, the removal of the bearing wall on the second floor
eliminated its ability to act as a fire division wall and it is doubtful that the steel I beams
would have been fire protected
Cast Iron:
This material is rarely used in building construction. Cast iron breaks
into pieces when gets a normal temperature after getting heat during
the fire. Care should be taken while using cast iron in the building that
it should be covered either by brick work, cement concrete or any
other fire resistant material.
Steel:
It is good conductor of heat and it is heated quickly during fire. Steel
bars looses its tensile strength, yields stress if it is heated above 600
degree centigrade during fire. Steel bars completely melt at a
temperature of 1400 degree centigrade. During fire unprotected steel
columns, beams etc. become unsafe due to high temperature and
structure may fail. The paint on the surface of the steel items catches
fire easily, keeping in the above problem fire resistant paint should be
done on steel members.
Concrete:
Concrete is a bad conductor of heat and an effective material for fire
resistant construction. It offers higher resistance to fire than any
other material. The actual behavior of concrete in case of fire
depends on quality of cement and type of aggregate which form
concrete. In case of reinforced and pre-stressed structures, it also
depends on the position of steel in concrete.
There is no loss of strength in concrete when it is heated up to 250
degrees centigrade. The reduction of strength starts when the
temperature of fire increases beyond 250 degrees centigrade.
Normally re-enforced concrete structure can resist fire for about one
hour at the temperature of 1000 degrees centigrade without any
serious damage. Hence cement concrete is widely used in fire
resistant construction.
Glass:
It is a poor conductor of heat and expends little during heating.
Cracks are formed in glass when it is cooled after heating. Reenforced glass with steel wire is more resistant to fire than ordinary
glass. Re-enforced glass can resist sudden variation in temperature
without forming cracks. Wired glass even if it breaks, keeps fractured
glass in its original position.
Timber:
Any structure made from timbers rapidly destroys in case of fire.
Timber also enhances intensity of fire. As timber is bad conductor of
heat if heavy section is used it may attain a high degree of fire
resistance. To make timber more fire resistant, the surface of timber
is coated with chemicals such as ammonium phosphate and
soleplate, borax and boric acid. After doing treatment, the timber
becomes more resistant to heat. Sometimes fire resistant paint is also
applied on surface of the timber to protect it from heat.
5.1-Fire resistance:
In fire, concrete performs well both as an engineered structure, and
as a material in its own right.
Because of concretes inherent material properties, it can be used to
minimize fire risk for the lowest initial cost while requiring the least in
terms of ongoing maintenance. In most cases, concrete does not
require any additional fire-protection because of its built-in resistance
to fire. It is a non-combustible material (i.e. it does not burn), and has
a slow rate of heat transfer. Concrete ensures that structural integrity
remains, fire compartmentation is not compromised and shielding
from heat can be relied upon.
5.2 Benefits:
Concrete as a material
Concrete does not burn it cannot be set on fire unlike other
materials in a building and it does not emit any toxic fumes when
affected by fire.
Concrete is proven to have a high degree of fire resistance and, in the
majority of applications, can be described as virtually fireproof. This
excellent performance is due in the main to concretes constituent
materials (cement and aggregates) which, when chemically combined
within concrete, form a material that is essentially inert and,
importantly for fire safety design, has relatively poor thermal
conductivity. It is this slow rate of conductivity (heat transfer) that
enables concrete to act as an effective fire shield not only between
adjacent spaces, but also to protect itself from fire damage.
Concrete structures
Concrete structures perform well in fire. This is because of the
combination of the inherent properties of the concrete itself, along
with the appropriate design of the structural elements to give the
Critical circuits
With the advent of high-rise building, fire protection of electrical life safety
conductors became extremely important. These critical circuits in high-rise buildings,
hospitals, institutions and places of public assembly are required to be protected from fire.
They supply Power for two essential fire protection functions: facilitating safe egress for
occupants, and fire fighting. Circuits that facilitate safe egress for occupants include feeders
for pressurization fans for stair wells, smoke extraction fans, the fire alarm sy stem and
circuits supplying essential system s in hospitals. Circuits that are required to stay
operational for firefighting include emergency generator, fire pump, fire fighters' elevator
and again, of course, the fire alarm system.
CIRCUIT INTEGRITY CABLES:
Typical Applications of 2 -hour fire-rated Fire Alarm and Power cables that meet stringent
requirements for Life-Safety circuits.
Emergency Power Supply
Firefighter's Elevator
Fire Pumps
Fire Alarm
Voice Communication & Fire fighter's
Handsets
Emergency Power for Lighting
Pressurization Fans & Smoke Dampers
High-rise buildings
Hospitals and other institutions
Historic buildings
Tunnels and subway s
Airports, stadium s, hotels, banks, etc.
are difficult because of the thickness of the slab. If 4-in concrete is required to achiev e a 2
hour rating, the slab can be very large indeed, e.g. 4-in conduit with 4-in concrete on either
side implies a 1 2 -in slab! In addition, the lack of fire rating of junction and pull boxes com
promises the system .Moreover, this method, as with other construction methods, is not a
listed system for fire protection of electrical conductors.
Note: Encasing conduit in concrete is also very difficult after the fact when
retrofit work has to be done.
Gypsum board enclosures
CharacteristicsGypsum, a mineral, has outstanding fire-resistant properties. When exposed to high
Temperatures , chemically combined water in the gypsum is gradually released, providing
protection until all of its combined water is completely driven off. Its fire resistance plus the
fact that gypsum panels were far less expensive than MI fire-rated cable (the only other viable
non-concrete alternative for y ears) made gypsum board enclosures a
traditional and obvious choice for the fire protection of life safety electrical circuits.
Other advantages include:
Weight- a 2 -hour fire-rated gypsum wall weighs only nine pounds per sq ft;
And thinness- a 2 -hour fire-rated wall is only 3 - -in thick. They also install m ore quickly
and economically than "wet" shaft walls, such as masonry. Gypsum panel shaft walls are com
pelted early in the construction process and finished later, along with other interior
partitions. Moreover, gypsum panel system s have undergone extensive independent testing
as fire barriers-gypsum boards of different core formulation are fire-rated from one to four
hours. By adding layers of gypsum panels to each side of the studs, the fire resistance of
virtually any wall can be increased
In addition, when used for fire protection of electrical cables, gypsum panels are com
m only perceived as in expensive ; or even free' in the sense that gypsum board used
for fire-rated enclosures is usually absorbed within the overall gypsum board budget
line item rather than listed as a separate line under the electrical estimate.
2 -hour fire separation using vertical shaft way and horizontal run
Construction methods, left; and fire-rated cable, right.
2 -hour rated assembly horizontal metal duct enclosure (fire tested both sides).
While meeting test temperature requirements, this assembly is not tested
or listed for protecting conventional wiring for 2 hours.
some structures the seal between the end of the floor system
and the curtain walls is very irregular, providing another means
of vertical extension for heat and smoke. Even in cases where
the seal was good, the glass in these panels possesses very little
fire resistance, and normally peels away quite easily under fire
exposure, significantly increasing the vertical extension on the
exterior of the building.
Another method of reducing
weight, and thereby cost, was
the replacement of masonry
materials formerly used to
weight concrete poured over the top), the slab is at least four
inches thick. In post-tensioned concrete buildings, the floor
slabs will be no thicker than four inches, and normally will be flat
on the underside, no corrugations, no column capitals, no other
irregularities to the shape of the underside are usually visible.
These thin flat floor slabs are usually a dead giveaway that you
are looking at a post-tensioned slab.
In this building under construction notice
the thin floor slabs, the lack of beams or
column capitals, and the openings in the
end of the slabs.
What kind of
concrete
construction is
this? Answer =
Post-tensioned.
Notice also, the
higher
concentration of
conduits
where the floors
intersect the
columns, and the
amount of
formwork and
shoring in
place on the top
floor. This is
what must be
protected if
it is exposed to a
fire.
Notice the tendons sticking out of the conduits, this is another
dead-bang giveaway that this is going to be a post-tensioned
building.
Unprotected Structural Steel I Beams supporting a lightweight
metal building. This type of construction is quite common in
industrial and commercial areas of Long Beach and Signal Hill. The
term Unprotected Structural Steel should be an instant indicator of
a lack of fire resistance. Any building with steel structural elements
which are not protected by either permanent encasement (masonry
materials or concrete) or a sprayed-on in tumescent coating such as
Gunnite should be noted during walk-through inspections. This type
of unprotected construction will result in structural failure if the
structural steel elements are exposed to extreme heat (anything over
850 degrees according to some references, which is reached very
Dia
g
ram of
plenum
space
above
drop
ceiling.
Note that
the H. V.
A. C. system has ductwork
bringing air conditioned air into the living/working spaces, but
exhaust air from these areas enters the plenum through the
vent next to the light fixture, for return to the H. V. A. C. system.
This is what is called a common return air plenum, and it is open
throughout the entire floor area, above the drop ceiling. Should
a fire start in the living/working space of this floor, it would be
drawn into the return air plenum space and spread easily
throughout this hidden void space. This is one of the reasons
that as soon as you enter a floor from the stairwell, you should
pop a ceiling panel up and make sure the fire isnt already over
head before advancing any further onto the floor. Should you
not do this, you may find the fire has extended over your head
and behind you in this void space, cutting you off from your
means of escape. This is also one of the reasons that the first
arriving crews should gain control of the H. V. A. C.
system as soon as possible in a fire with such as
return air plenum space.
Most newly constructed commercial or office
buildings, particularly high-rises have interior, nonbearing walls made of galvanized sheet metal studs,
sheeted with drywall on both sides. These walls serve
as dividers between offices within an occupancy, or
between occupancies. Personnel should remember
this feature, as it could help them escape a building safely, if the
hallway they need to use to get back to the stairwell is now
blocked by fire. You may be able to simply break through these
lightweight walls until you can either get around the fire and
back into the hallway, or possibly even break all of the way
through into the stairwell itself.
Additionally, if a fire occurs in a highly secured office space, and
you are having difficulty in gaining access, you might be able to
enter the occupancy on either side of the involved one, and
as with all
large fires, the
incident
commander needs
to write off
any floor which is
significantly
involved, and
move to one
far enough above
the fire to be able to have enough crews in place to be able to
handle the volume of fire which may develop once it gets to
their location.
The First Interstate the Morning After by the time L. A. City Fire
Dept. got this fire under control, they had approximately three
hundred and fifty firefighters assigned to it. One of the lessons
learned the hard way on this incident was to make sure you
know where the fuel inlet for the in-house fire pumps is, and
what quantity and of type of fuel it takes. At one point during
the fire, the fire pump ran out of fuel and crews lost pressure.
The pumpers were providing back-up supply to the standpipes,
but there was a noticeable drop in pressure and hence
firefighting effectiveness until the fire pump could be re-fueled
and restarted. This has resulted in all of the fire pump inlets in
Long Beach being clearly identified with the type of fuel
needed. This is also why we have a policy of insuring that at
least one charged line goes to every Fire Dept. Connection in
any building that has a fire, and at least two charged lines go
into every F. D. C. that has one or more attack lines actually
working off of it, as you never know when something will go
wrong and we will be supplying the fire flows rather than the inhouse pumps.
10.CONCLUSION:-
Fire resistance is a key element of the building codes intent to provide safety
to life and property from fire. If youre a designer, specifier, product representative, or
contractor, you need to be aware of the requirements for fire resistance. Most jurisdictions
will insist that tested or listed assemblies be used and specifically identified in the contract
documents. Care must be taken in selecting and specifying materials and products used in
fire-resistance-rated assemblies. Skilled labor must be utilized when constructing fireresistance-rated assemblies, including the penetrations, which require more attention than
just applying red putty around the item. In the end, the assembly you design, specify,
provide, or install, may be the one thing that prevents a tragic event. The fire resistance of the
World Trade Center was heavily scrutinized at all levels, and although the event far exceeded
what anyone could have imagined, the outcome may eventually have a significant impact on
fire-resistive construction in all future construction, big or small.
11. REFERENCES