Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Commissioning Manual
Version 3.0c
12/2014
Retain for future use.
Version 3.0c
12/2014
Technical Support
Questions and requests related to any part of this documentation can be directed to one of the following support
centers.
Technical Support: Americas, Europe, Middle East, Asia
Available Monday to Friday 8:00am 6:30pm Eastern Time
Toll free within North America
Direct Worldwide
Email
1-888-226-6876
+1-613-591-1943
supportTRSS@schneider-electric.com
Safety Information
Read these instructions carefully and look at the equipment to become familiar with the device before
trying to install, operate, service or maintain it. The following special messages may appear throughout
this bulletin or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
The addition of either symbol to a Danger or Warning safety label indicates that an electrical hazard exists which
will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages
that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not
avoided, can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not
avoided, can result in minor or moderate injury.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No
responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction, installation, and operation of
electrical equipment and has received safety training to recognize and avoid the hazards involved.
2
Version 3.0c
12/2014
WARNING
UNGUARDED MACHINERY HAZARD
Do not use this software and related automation equipment on
equipment which does not have point-of-operation protection.
Do not reach into machinery during operation.
Failure to follow these instructions can result in death or serious
injury.
Only the user can be aware of all the conditions and factors present during setup, operation, and maintenance of
the machine; therefore, only the user can determine the automation equipment and the related safeties and
interlocks which can be properly used. When selecting automation and control equipment and related software for
a particular application, the user should refer to the applicable local and national standards and regulations. The
National Safety Councils Accident Prevention Manual (nationally recognized in the United States of America) also
provides much useful information.
In some applications, additional operator protection such as point-of-operation guarding must be provided. This is
necessary if the operators hands and other parts of the body are free to enter the pinch points or other hazardous
areas and serious injury can occur. Software products alone cannot protect an operator from injury. For this reason
the software cannot be substituted for or take the place of point-of-operation protection.
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation protection have
been installed and are operational before placing the equipment into service. All interlocks and safeties related to
point-of-operation protection must be coordinated with the related automation equipment and software
programming.
Coordination of safeties and mechanical/electrical interlocks for point-of-operation protection is outside the scope
of this documentation.
CAUTION
EQUIPMENT OPERATION HAZARD
Before energizing equipment:
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other
temporary holding means used for shipment from all component
devices.
Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in minor or moderate
injury.
Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for
future references.
Software testing must be done in both simulated and real environments.
Version 3.0c
12/2014
Verify that the completed system is free from all short circuits and grounds, except those grounds installed
according to local regulations (according to the National Electrical Code in the U.S.A., for instance). If highpotential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental
equipment damage.
Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of
components, there are hazards that can be encountered if such equipment is improperly operated.
It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation.
Always use the manufacturers instructions as a guide for functional adjustments. Personnel who have access
to these adjustments should be familiar with the equipment manufacturers instructions and the machinery used
with the electrical equipment.
Only those operational adjustments actually required by the operator should be accessible to the operator.
Access to other controls should be restricted to prevent unauthorized changes in operating characteristics.
Version 3.0c
12/2014
Table of Contents
Table of Contents
1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1
1.2
2.2
2.3
2.4
2.5
3.8
3.9
3.10
3.11
21
Configuring the Computer for Communication with the Realift Rod Pump . . . . . . . . . . . . . . . . . . . . . . . . . 22
Establishing the Connection Between the Realift Rod Pump and the Computer . . . . . . . . . . . . . . . . . . . . 24
Changing the IP Address on the Realift Rod Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Resolving Conflicts in Location and Pump ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Establishing Communication Speed and Card Interval Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
RPC Version and RPC HMI Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Verifying Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.7.1
Pinging the Realift Rod Pump. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.7.2
Verifying Detailed Communication Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Setting Time of New Day on the Realift Rod Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Viewing Counters and Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Administering Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.10.1
Saving a Parameter Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.10.2
Opening a Parameter Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.10.3
Deleting a Parameter Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.10.4
Viewing Parameter Set Names. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.10.5
Resetting the Realift Rod Pump to Factory Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Configuring Energy Saving Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.2
11
Starting the Commissioning Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1.1
Using ViewX to Start the Commissioning Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1.2
Starting the Commissioning Software Using WebX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Creating and Deleting Pump Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Creating and Deleting Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Accessing Pump Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Navigating the User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5.1
Configuration Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.5.2
Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Commissioning Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1
........................................................................ 5
39
Defining the Drive Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.1.1
Configuring the Interface for an Altivar 71 Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.1.2
Configuring the Interface for a Generic Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.1.3
Configuring the Interface for a Starter or Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
External Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.5
5.6
43
Setting the Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Setting On & Off Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Setting Pump Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Setting Fill Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.4.1
Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.4.2
Surface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.4.3
Downhole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Setting Startup Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Setting Control Triggers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
53
Using API Dimensions in Surface or Downhole Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Setting a Measured Stroke Length (Torque) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Setting the Proximity Angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Setting the Proximity Angle (Mark II Pump Jack) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Setting the Proximity Debounce Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Setting the Load Cell Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Entering Downhole Calculation Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Entering Wellhead Information Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Entering Rod Taper Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Version 3.0c
12/2014
67
Setting Per Stroke Alarm Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Setting Real-Time Alarm Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Viewing Sensor Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Resetting Detection for Well and Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
73
Setting the Fill Control Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
8.1.1
Setting the Surface Fill Control Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
8.1.2
Setting the Downhole Fill Control Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
10
11
12.5
105
Using the History Card Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Viewing Periodic Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Viewing Stored Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Transferring Stored Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Changing Card Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Changing Card Storage Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Commissioning Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1
A.2
A.3
97
Viewing Trends and Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Modifying the Plot Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Transferring Stored Trends and Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
91
Summary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Well Activity Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Surface and Downhole Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Card Display and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
12.4.1
Defining Filtering Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Configuring External Sensors and Water Cut Percentage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Reading Downhole Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Sample Downhole Card Shapes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
13
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Checking Speed Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Forcing a Pump Off State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Testing Well Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
12
81
113
Drive Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Well Data Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Pump Control Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Copyright 2014 Schneider Electric Canada Inc.
Version 3.0c
12/2014
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.1
B.2
B.3
B.4
B.5
B.6
B.7
B.8
115
Creating a New Rod Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Dynagraph Plots Are Not Displayed But a Grid Appears . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Dynagraph Plots Are Blank But No Grid Appears . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
ClearSCADA Database Corrupt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Drive Runs in Hand or Manual Mode Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Realift Rod Pump Speed Oscillates or Realift Rod Pump Does Speed Hunting . . . . . . . . . . . . . . . . . . . 118
Difference Between Fill Control Level and Fill Target . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Operation in Downhole Mode and Pump Fill Indicates 0% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Periodic Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Stored Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
127
135
Reinstalling the SCADAPack 535 E Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Reinstalling the Application Package File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Version 3.0c
12/2014
Version 3.0c
12/2014
Introduction
Realift Rod Pump is an advanced rod pump controller for automating a rod pump.
This manual describes the procedure for commissioning the Schneider Electric Realift Rod Pump system.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Read and understand this manual before operating the Realift Rod
Pump system.
Any changes made to parameter settings must be performed by
qualified personnel.
Failure to follow these instructions can result in death or serious
injury.
1.1
The Realift Rod Pump HMI software installation procedure is complete (see Realift Rod Pump Software
Installation Manual).
The Realift Rod Pump hardware installation procedure is complete (see Realift Rod Pump Hardware Installation
Manual).
The Hand Off Auto (HOA) switch on the enclosure is set to Off.
The drive or motor starter contactor is configured and ready for power to be applied.
The commissioning procedure for Downhole Realift Rod Pumps is described in this section.
1.2
Commissioning Overview
The Realift Rod Pump is commissioned using the Realift Rod Pump HMI software. The software is built on the
Schneider Electric ClearSCADA platform. ClearSCADA is installed automatically as part of the Realift Rod Pump
HMI installation and places a ClearSCADA Server icon, a ClearSCADA Service Manager icon, and a ViewX icon
on the desktop.
This manual contains the following information:
Setting up WebX or ViewX to use the Realift Rod Pump HMI software is described in Getting Started on
page 11.
Defining initial time and network parameters is described in Configuring Time and Network Parameters on
page 21.
Configuring the drive you are using with the Realift Rod Pump is described in Configuring the Drive on page 39.
Verifying Realift Rod Pump control during operation is described in Verifying Realift Rod Pump Control During
Operation on page 83.
Testing the Realift Rod Pump system operation is described Testing Realift Rod Pump System Operation on
page 81.
Configuring how the data from the well is reported is described in Configuring Well Data on page 53.
Configuring how faults are detected and reported is described in Configuring Well Fault Detection on page 67.
Configuring the pump jack for standard operation is described in Configuring the Pump Jack for Standard
Operation on page 73.
10
Version 3.0c
12/2014
Optimizing Realift Rod Pump operation is described in Optimizing Realift Rod Pump Operation on page 87.
In Appendix B - Troubleshooting on page 115, you can find troubleshooting information for common
commissioning-related situations.
Viewing the system status is described in Viewing System Status on page 91.
Viewing history trends and events is described in Viewing History Trends and Events on page 97.
Managing history cards is described in Managing History Cards on page 105.
In Appendix A - Commissioning Checklist on page 113, you can find a commissioning checklist of the items you
should cover when configuring an Realift Rod Pump.
Version 3.0c
12/2014
Getting Started
The first steps in using the Realift Rod Pump HMI software to commission a Realift Rod Pump are explained in this
chapter.
2.1
2.1.1
) next to the Home Page text box. The Select Home Page dialog box appears.
6. In the Select Home Page dialog box, expand the Digital Oil Field.
7. Select Login and click OK to close the Select Home Page dialog box.
8. In the Options dialog box, click the Edit button next to Features. The Features dialog box appears.
9. In the Features dialog box, select the Display Home Page On Logon check box.
10. Click OK to close the Features dialog box.
11. Click OK to close the Options dialog box.
12. Close ViewX.
To start the commissioning software using ViewX:
1. Start ViewX by double-clicking the ViewX icon on the Windows desktop. If there is no ViewX icon on the
desktop, you can start ViewX using the Start button:
Select Start > All Programs > Schneider Electric ClearSCADA > ViewX.
2. The Realift Rod Pump HMI Main Menu, shown in Figure 2.3, appears.
3. Click the Login button near the top of the screen and enter the following user name and password:
Username: admin1
Password: welcome
The dialog box in Figure 2.1 appears.
11
Version 3.0c
12/2014
4. Read the warning and click Yes to continue. A second confirmation dialog appears.
5. Click Yes to continue.
6. The Current User field changes from Guest to admin1.
2.1.2
12
Version 3.0c
12/2014
2. Click the Login button near the top of the screen and enter the following username and password:
Username: admin1
Password: welcome
The Current User field changes from Guest to admin1.
Figure 2.3: Realift Rod Pump Main Menu
2.2
13
Version 3.0c
12/2014
3. In the Enter Pump Information dialog box, enter brief a description of the pump's Location (for example,
TestLocation2) and a Pump ID (for example, TestPump2). The Location and Pump ID text boxes cannot be
empty, are limited to a maximum of 14 characters, and can contain only letters, numbers, underscores, and
hyphens. If the Location or Pump ID entries are invalid, the Realift Rod Pump HMI software displays a
message.
4. Click OK. You are prompted to re-enter your password.
5. Enter your password and click OK. The Realift Rod Pump HMI software creates the new pump profile. While it
is creating the new pump profile, a message is displayed requesting you to wait until it has finished creating the
pump profile.
6. The Location and PumpID appear under Pump List in the Main Menu. Each pump entered into the Realift Rod
Pump HMI database on the same computer is listed under Pump List and can be accessed here for later
modification, as shown in Figure 2.5.
Figure 2.5: Pump List: Location and Pump ID
2.3
WARNING
UNEXPECTED EQUIPMENT OPERATION
Access to configuration settings should be restricted to reduce the possibility of
unauthorized device reconfiguration.
Failure to follow these instructions may result in death or serious injury.
14
Version 3.0c
12/2014
The User Account Information page appears, including a list of current system users, if any, and their privilege
level, as shown in Figure 2.7.
Figure 2.7: User Account Information Window
When the Realift Rod Pump HMI software is first installed, there are three default users. Their names indicate
their user privilege level. For more information on which parameters are available for each privilege level, see
User Privilege Levels on page 127.
admin1: The admin1 user has complete Realift Rod Pump control, including the ability to edit Realift Rod
Pump values, add and delete pumps, and add and delete users. The default password is welcome.
config1: The config1 user can navigate the Realift Rod Pump system and edit the values, but cannot add or
delete pumps or users. The default password is welcome.
view1: The view1 user can only navigate the system and view data, but cannot edit values or add pumps
and users. The default password is welcome.
For security reasons, it is recommended that you create new users with Admin, Config, and View rights and
that you delete these default users.
15
Version 3.0c
12/2014
CAUTION
RISK OF SYSTEM INTRUSION
There is a risk of an unauthorized user gaining access to the system and changing
parameters.
Create new users with secure passwords and delete the default users.
Failure to follow these instructions may result in death or serious injury.
2. On the User Account Information page, click Create User. The Create New User dialog box appears, as shown
in Figure 2.8.
Figure 2.8: Create New User Dialog Box
3. In the Create New Users dialog box, select the user privilege level from the Choose User Privilege Level list:
Admin: An Admin user has complete Realift Rod Pump control, including the ability to edit Realift Rod Pump
values, add and delete pumps, and add and delete users.
Config: A Config user can navigate the Realift Rod Pump system and edit the values, but cannot add or
delete pumps or users.
View: A View user can only navigate the system and view data, but cannot edit values or add pumps and
users.
4. Enter a New User Name. The user name is limited to a maximum of 20 characters and can contain only letters,
numbers, underscores, and hyphens.
5. Enter and confirm a password. The password is limited to a maximum of 20 characters and can contain only
letters, numbers, underscores, and hyphens.
6. Click OK. The new User Name with that users privilege level is added to the list of user accounts.
7. Click Exit to return to the main screen.
If this is a networked system, you can only add new users locally at the server.
To increase security, once you have created a new Admin user, you should log in with that account and delete the
default Admin user (admin1) in order to ensure that no one else can use it. You can delete users in the User
Account Information page by clicking a User Name in the Name/Type list to select it and then clicking Delete User
to remove that user from the system.
2.4
16
Version 3.0c
12/2014
3. Confirm that the correct Location and PumpID appear in the upper left-hand corner of the page, as shown in
Figure 2.10.
Figure 2.10: Location and Pump ID
2.5
17
Version 3.0c
12/2014
Pages
Pages, similar in concept to an operating systems windows, organize Realift Rod Pump HMI controls and data
into nine major functional areas, shown in Figure 2.12 on page 19.
The functions available on each Realift Rod Pump HMI page are discussed in detail in this section.
Panes
Pages are subdivided into panes, which group together similar controls and data fields.
Several functional panes are displayed in Figure 2.11:
Summary
Well Activity Summary
Surface & Downhole Data
Card Display & Settings
The pane found on each of the nine major functional area pages is the Navigation Pane, illustrated in Figure 2.12.
18
Version 3.0c
12/2014
2.5.1
Configuration Fields
In the Realift Rod Pump HMI software, any value that appears in a gray field is a read-only value that cannot be
changed by the user. Gray fields indicate current values, though some are configurable values that are not editable
due to some other settings.
A value in a white field can be changed by clicking the field.
Both types of fields are illustrated in Figure 2.13.
Figure 2.13: Gray and White Fields in a Typical Pane
19
Version 3.0c
12/2014
Green indicates that the Realift Rod Pump is operating as expected, as illustrated in Figure 2.14. In this
example, Run Pump is Enabled in the Realift Rod Pump HMI software, RPC Status is Auto (the HOA switch on
the enclosure is set to Auto), and Drive Status is forward the Realift Rod Pump is running.
Yellow indicates that a system parameter needs to be defined or needs attention, as illustrated in Figure 2.15.
In this example, although the Realift Rod Pump is Enabled in the Realift Rod Pump software, the RPC Status
(the HOA switch on the enclosure) is set to Off; turning the switch to Auto makes it possible for the Realift Rod
Pump to run and changes Drive Status to Forward.
Red indicates that a system parameter requires attention because the Realift Rod Pump has stopped the pump
because of, for example, a well fault, or it indicates a communication problem between network and the Realift
Rod Pump (see Figure 2.16).
See Troubleshooting on page 115 for detailed information on diagnosing communications interruptions.
2.5.2
Buttons
Other controls in this pane (for example, Set Curve Visibility and Set Filtering Options) are buttons. You click a
button to initiate an action.
20
Version 3.0c
12/2014
Direct connection to a Realift Rod Pump system at the well site, using a computer with either a wired or wireless
connection to the system
The Realift Rod Pump uses a static IP address. When you connect to the Realift Rod Pump over a network, a router
or a DHCP server assigns an IP address to your computer, allowing the computer and Realift Rod Pump to
communicate. The Communication State field in the Connection and Name pane displays Connected.
However, when you connect directly to the Realift Rod Pump at the well site, the IP addresses on the Realift Rod
Pump system and on the computer are unlikely to belong to the same network. So, before you can commission the
Realift Rod Pump system, you will have to configure both the computer and the Realift Rod Pump. You configure the
connection with the Realift Rod Pump using the Time and Network Configuration page.
If your SCADAPack 535 E does not have a valid license, a banner is displayed over the Communications pane of
the Time and Network Configuration page informing you of this fact (see Figure 3.1). If this is the case, contact your
local Schneider Electric representative.
Figure 3.1: Missing SCADAPack 535 E License
To configure the computer and the Realift Rod Pump for a direct connection:
1. Configure an IP address on the computer to work with the IP address on the Realift Rod Pump (see Configuring
the Computer for Communication with the Realift Rod Pump on page 22).
2. Connect the computer to the Realift Rod Pump (Establishing the Connection Between the Realift Rod Pump
and the Computer on page 24).
3. Configure a new IP address on the Realift Rod Pump that works with your network (Changing the IP Address on
the Realift Rod Pump on page 24).
You may also need to resolve conflicts in Location and Pump ID between those displayed in the Communication
pane and those of the Realift Rod Pump to which you are now connected.
21
Version 3.0c
12/2014
3.1
Configuring the Computer for Communication with the Realift Rod Pump
When you first connect a computer to a Realift Rod Pump, the Realift Rod Pump uses the SCADAPack 535 Es
factory address (192.168.0.101).
The first step in connecting the computer and the Realift Rod Pump is configuring an IP address and subnet mask
on the computer that work with the Realift Rod Pumps default IP address.
To configure an IP address and subnet mask on the computer with Windows 7:
1. Click the Start button and select Control Panel from the Start menu.
2. On the Control Panel, click Network and Internet. The Network and Internet window appears.
3. In the Network and Internet window, click Network and Sharing Center. The Network and Sharing Center
window appears.
4. In the menu on the left, click Change adapter settings. The Network Connections are displayed.
5. Double-click the Local Area Connection icon in the Network Connections window. The Local Area Connection
Status dialog box appears, as shown in Figure 3.3.
22
Version 3.0c
12/2014
6. In the Local Area Connection Status dialog box, click Properties. The Local Area Connection Properties dialog
box appears.
7. In the Local Area Connection Properties dialog box, scroll through the connection list and select the Internet
Protocol Version 4 (TCP/IPv4) check box.
8. Click Properties. The Internet Protocol (TCP/IP) Properties dialog box appears, as shown in Figure 3.4.
Figure 3.4: Internet Protocol (TCP/IP) Properties
23
Version 3.0c
12/2014
9. Select Use the following IP address and enter a new IP address for your computer:
a. Set the first three numbers of the IP address to match the drives address, but set the fourth number to
something different from the Realift Rod Pump IP address (for example, if the drive's IP address is
192.168.0.101, set the computer's IP address to 192.168.0.X, (where X is any number from 1 to 254 other
than 101).
b. Set the subnet mask. Typical values are 255.255.255.0 or 255.255.0.0.
A Default Gateway is not needed.
c. Click OK to save changes and exit from the Control Panel.
3.2
Establishing the Connection Between the Realift Rod Pump and the Computer
This section describes the process for connecting to the Realift Rod Pump using the Realift Rod Pumps factory IP
address (192.168.0.101). After you establish communication with the Realift Rod Pump, you can change the Realift
Rod Pumps IP address to an address that conforms to an appropriate range for your network (see Changing the IP
Address on the Realift Rod Pump on page 24).
To connect the computer to the Realift Rod Pump (when the Realift Rod Pump is using its default IP address):
1. In the Navigation pane, click Time & Network Configuration. The Time & Network Configuration page appears,
as shown in Figure 3.2.
2. In the Target IP Address field of the Communication pane, illustrated in Figure 3.5, enter the IP address of the
Realift Rod Pump. To change the Realift Rod Pump IP address, see Resolving Conflicts in Location and Pump
ID on page 25.
Figure 3.5: Communication Pane
3. If you still cannot connect to the Realift Rod Pump, contact your local Schneider Electric representative.
3.3
24
Version 3.0c
12/2014
The following suggestions will help you determine the new IP address:
If the Realift Rod Pump is connected to an already existing network, it may helpful to choose an IP address
within an appropriate range for that network.
If the Realift Rod Pump is to be connected behind a router to a stationary server, you should configure the
router so that it does not dynamically assign any device to the same IP address as the address given to the
Realift Rod Pump. This can be done by constraining the range of addresses the router uses for DHCP.
2. Under Value Applied at the Next Power Cycle, set the IP address. One possibility is 10.10.253.30.
3. Set subnet mask. One possibility is 255.255.255.0.
4. Connect to the Realift Rod Pump using the new IP address.
In the Communication pane, the Communication State field, now shaded in yellow, reads Connection Lost. The
Target IP Address field still shows the original IP address.
5. In the Target IP Address field, enter the IP Address and Subnet Mask created for the Realift Rod Pump in steps
2 and 3.
6. In the Communication pane, confirm that the Communication State field, now shaded in gray, reads Connected.
You are again connected to the Realift Rod Pump, now with a new IP address.
3.4
25
Version 3.0c
12/2014
26
Version 3.0c
12/2014
3. Click Exit to close the Rod Pump Controller Logistics Information Conflict dialog box.
3.5
Connection Speeds
Setting
Connection
Speed
High
1 Mbps
Medium
512 kbps
Low
27
Version 3.0c
12/2014
Realift Rod Pump is completely commissioned, it is recommended that you set card intervals to a value greater
than a few minutes, up to an entire day between cards, to limit network activity.
3.6
3.7
Verifying Communications
If the Realift Rod Pump cannot communicate properly with Realift Rod Pump HMI software due to a configuration
mismatch, the Communication State field in the Communication pane (Time & Network Configuration page)
displays Disconnected, as shown in Figure 3.11. You should verify communications before you proceed.
If Communication State displays Connection Lost, there can be a number of possible causes, including: the drive
might not be powered up or physically connected to the computer, the connection may be poor, or IP addresses or
subnet masks may not match.
Figure 3.11: Disconnected Communication State
3.7.1
28
Version 3.0c
12/2014
If you cannot successfully ping the target Realift Rod Pump system, as shown in Figure 3.13, your computer and
the target Realift Rod Pump system may not be in the same domain. See Configuring the Computer for
Communication with the Realift Rod Pump on page 22.
If you still cannot communicate with your Realift Rod Pump, you can use the SCADAPack E Configurator to
determine the devices IP address information after connecting by USB. For more information, see the
SCADAPack E Configurator User Manual.
Figure 3.13: Unsuccessful Ping
3.7.2
29
Version 3.0c
12/2014
The Detailed Settings dialog box can be opened from two locations:
By clicking the Detailed Settings button in the Communication pane (see Configuring the Computer for
Communication with the Realift Rod Pump on page 22).
By selecting Custom in the Communication Speed dialog box and then clicking OK (see Establishing
Communication Speed and Card Interval Settings on page 27).
If the Communication Timeout Count is increasing or if you continue to lose the connection with the Realift Rod
Pump, you can try these solutions:
If the Current Value (Realift Rod Pump system reading) for Data Collection Time is greater than the Set Value,
you can increase the Set Value.
If the Current Value (Realift Rod Pump system reading) for Data Reply Time is greater than the Set Value, you
can increase the Set Value.
Values in Set Value fields should be at least slightly higher than readings in Current Value fields. Table 3.2
contains a list of the preset values for High, Medium, and Low communication setting.
Table 3.2:
Defaults
30
High
Medium
Low
0.5 sec
2 sec
10 sec
2 sec
8 sec
45 sec
25 sec
80 sec
400 sec
Version 3.0c
12/2014
3.8
The Clocks pane also offers two date and time readings:
Server Date & Time: Current date and time on the computer being used to commission the Realift Rod Pump.
Realift Rod Pump Date & Time: Current date and time on the Realift Rod Pump.
The servers time and date is set through Windows. You can set the Realift Rod Pumps time and date using the
Realift Rod Pump HMI software. The rod pump cannot be enabled when you set the Realift Rod Pumps time and
date.
To set the Realift Rod Pumps time and date:
1. In the Summary pane on the Status page, ensure that the Status of the rod pump is Disabled. If the rod pump is
running, click the box to the right of the Status and wait until the Status changes to Disabled.
2. In the Clocks pane on the Time & Network page, click the Set button to the right of the RPC Date & Time box.
The Realift Rod Pump HMI software sets the Realift Rod Pump time to the server date and time.
3.9
31
Version 3.0c
12/2014
Because they are readings from the Realift Rod Pump, these parameters cannot be edited. However, the following
can be reset:
3.10
3.10.1
32
Drive Configuration: all parameters unless the parameter set is from an embedded Realift Rod Pump in which
case the drive configuration and control wiring parameters will need to be configured manually.
Version 3.0c
12/2014
2. In the Parameter Set Admin pane, click Save. The Save Parameter Set page appears, as shown in Figure 3.18.
Figure 3.18: Save Parameter Set Window
33
3.10.2
Version 3.0c
12/2014
Drive Configuration: The Min Speed and Max Speed are reset to 0, the Drive Interface Type is reset to
Altivar 71 Modbus, and the Drive Address is reset to 2.
3. Select the name of the parameter set from the list and click Open. A Confirm Action dialog box appears
requesting that you confirm that you want to open the selected parameter set and informing you that the current
Realift Rod Pump values will be overwritten by the values from the selected parameter set.
To guard against unintended Realift Rod Pump operation, opening a parameter set automatically sets Run
Enable to Disabled.
34
Version 3.0c
12/2014
WARNING
UNEXPECTED EQUIPMENT OPERATION
The Open Parameter command replaces the parameters on the controller. This can
affect your process. Ensure the process is in a safe state before executing the
command. Verify your configuration after executing this command.
Failure to follow these instructions can result in death or serious injury.
4. Click Yes to open the selected parameter set and overwrite the current Realift Rod Pump values.
You can manually change individual settings that differ from the saved parameter set.
3.10.3
3. Select the name of the parameter set from the list and click Delete. A Confirm Action dialog box appears
requesting that you confirm that you want to delete the selected parameter set and informing that this action
cannot be undone.
4. Click Yes to delete the selected parameter set.
35
3.10.4
Version 3.0c
12/2014
3.10.5
36
Version 3.0c
12/2014
WARNING
UNEXPECTED EQUIPMENT OPERATION
The Reset RPC to Factory Settings command replaces the current parameters with
the factory defaults. This can affect your process. Ensure the process is in a safe
state before executing the command. Verify your configuration after executing this
command.
Failure to follow these instructions can result in death or serious injury.
3. Click Yes to reset Realift Rod Pump to factory settings.
Resetting the Realift Rod Pump to factory settings does not change the card storage location. To change the card
storage location, refer to Changing Card Storage Location on page 112.
To restore your drive to factory settings, refer to the documentation provided by the manufacturer of your drive.
3.11
2. For each day in the Energy Save pane, enter a Begin Time in 24-hour format to mark the beginning of the
period during which the pump jack does not operate.
3. For each day, enter an End Time in 24-hour format to mark the end of the period during which the pump jack
does not operate.
The Realift Rod Pump stops the pump jack at Begin Time, and restarts at End Time, resuming normal pump
jack operation. The total time between Begin Time and End Time for a single day cannot exceed 24 hours.
37
38
Version 3.0c
12/2014
Version 3.0c
12/2014
WARNING
UNEXPECTED EQUIPMENT OPERATION
Read and understand this manual and the drives manual before
operating the Realift Rod Pump system.
Any changes made to parameter settings must be performed by
qualified personnel.
Failure to follow these instructions can result in death or serious
injury.
To configure the parameters of the drive:
1. On the Status page, stop the pump by clicking the Run Pump button and waiting until Run Pump is Disabled
and RPC Status is Disabled.
2. Click Drive Configuration in the Navigation pane. The Drive Configuration page appears (see Figure 4.1). The
actual appearance of the Drive Configuration page depends on the type of drive selected. The Drive
Configuration page is also used to configure external control wiring, if any, to the Realift Rod Pump.
Figure 4.1: Drive Configuration Page
39
4.1
Version 3.0c
12/2014
4.1.1
4.1.2
40
Version 3.0c
12/2014
3. In the Drive Interface pane, click the Min Speed field and enter a value for the minimum drive speed at 0 or
4 mA in the Drive Speed dialog box that appears (see Figure 4.2).
Figure 4.2: Drive Speed Dialog Box
4. Click OK.
5. Click the Max Speed field and enter a value for the maximum drive speed at 20 mA in the Drive Speed dialog
box that appears.
6. Click OK.
4.1.3
4.2
Bypass Contactor (DI-12): You can click the Bypass Contactor (DI-12) field and select No Bypass Connector,
Active Low, or Active High. When the Bypass Contactor (DI-12) is active (either Active High or Active Low), it
will stop the Realift Rod Pump while it is running, or prevent the Realift Rod Pump from running if it is not
running, and be reported as a status in the HMI software. The Bypass Contactor is intended to indicate to the
Realift Rod Pump that the drive is disconnected from the pump motor.
External Fault Trigger (DI-15): You can click the External Fault Trigger (DI-15) field and select either Active Low
or Active High. The external fault trigger can be any external device, sensor, or series of devices connected to
DI-15. When the external fault trigger (DI-15) is active (either Active High or Active Low), it will stop the Realift
Rod Pump while it is running, or prevent the Realift Rod Pump from running if it is not running, and be reported
as a status in the HMI software.
41
42
Version 3.0c
12/2014
Version 3.0c
12/2014
43
5.1
Version 3.0c
12/2014
Click Pump Control Configuration in the Navigation pane. The General Control pane is displayed in the Pump
Control Configuration page, as shown in Figure 5.1. The parameters are explained in the following sections.
Click Selected Control Mode and select one of the following modes:
Timed: The Realift Rod Pump operates as a timer, running for Pump On Time and stopping for Pump Off
Time, both of which are fixed, user-entered values.
Torque: The Realift Rod Pump system repeats cycles of running until the Torque Fill falls below the Torque
Fill Minimum for the Pump Off Count Limit, remaining off for Pump Off Time. While running, speed is
increased if the Torque Fill is above the Torque Fill Target and decreased if below the target. This control
mode is only supported by systems using the Altivar 71 drive.
Surface: The Realift Rod Pump system repeats cycles of running until the Surface Fill falls below the
Surface Fill Minimum for the Pump Off Count Limit, remaining off for Pump Off Time. While running, speed
is increased if the Surface Fill is above the Surface Fill Target and decreased if below.
Downhole: The Realift Rod Pump system repeats cycles of running until the Downhole Fill falls below the
Downhole Fill Minimum for the Pump Off Count Limit, remaining off for Pump Off Time. While running,
speed is increased if the Downhole Fill is above the Downhole Fill Target and decreased if below.
44
Version 3.0c
12/2014
5.2
Click Pump Control Configuration in the Navigation pane. The On & Off Time Settings pane is displayed in the
Pump Control Configuration page, as shown in Figure 5.1. The parameters are explained in the following
sections.
45
Version 3.0c
12/2014
5.3
46
Version 3.0c
12/2014
The speed settings are not used if you have selected starter or contactor on the Drive Configuration page.
Figure 5.4: Speed Settings Pane
Startup Speed
The Startup Speed is the system speed when starting in Auto Mode. The system maintains this speed until the
pump completes a selected number of strokes (Pre-Control Strokes), at which point the Realift Rod Pump adjusts
speed to the range defined by Minimum Speed and Maximum Speed. In Timed mode, the system runs at Startup
Speed until it reaches On Time, after which, it stops. The Startup Speed is defined by default in Hertz (Hz), but it
can be changed by clicking the Units for Speed Settings box.
The suggested value is at or above the mid-point of the range between Minimum Speed and Maximum Speed. If
Startup Speed is set to 0, RPC Status displays No-Run.
Maximum Speed
The Maximum Speed is the fastest drive speed when the pump is in Auto Mode and is adjusting the speed based
on the pump fill. It limits the upper end of pump jack speed so that it does not operate faster than the pump jacks
capabilities. The Startup Speed is defined by default in Hertz (Hz), but it can be changed by clicking the Units for
Speed Settings box.
If you are using a generic drive, do not confuse the Maximum Speed setting with Max Speed (Defining the Drive
Interface on page 40), the maximum speed at which the Realift Rod Pump operates under any conditions. Max
Speed takes precedence (defined on the Configuration Page), even if Maximum Speed is set higher.
If you are using an Altivar 71, the Altivar 71 uses the Maximum Speed (defined directly on the Altivar 71 by
selecting 1. Drive Menu > 1.1 Simply Start > High Speed) as the Max Speed when operating in hand mode.
The value varies depending on well conditions, but should not exceed the Max Speed defined on the Drive
Configuration Page (Defining the Drive Interface on page 40).
Minimum Speed
Minimum Speed is the slowest drive speed when the Realift Rod Pump is operating in Auto Mode and adjusting
speed based on the pump fill. The Startup Speed is defined by default in Hertz (Hz), but it can be changed by
clicking the Units for Speed Settings box.
The Minimum Speed varies, but should be set to a point equal to or below Startup Speed.
Units for Speed Settings
Units for Speed Settings determines whether speed is displayed as Hz or SPM (Strokes per Minute).
SPM:Hz Ratio
The SPM:Hz Ratio is a calculated ratio of drive output frequency in Hz compared to the pump jack speed in
Strokes per Minute (SPM). It is strongly recommended that you calculate the SPM:Hz ratio prior to using auto
mode so that the values calculated by Realift Rod Pump correspond to actual measurements. The ratio is
calculated in step 2 of the procedure described in Setting the Fill Control Levels on page 75.
47
5.4
Version 3.0c
12/2014
5.4.1
Torque
If operating in Torque mode, you only need to set the Fill Minimum and Fill Target parameters for Torque. Torque
mode is only supported by systems using the Altivar 71 drive.
Fill Minimum
Fill Minimum provides a point where the Realift Rod Pump system detects a Pump Off state. If the pump fill is less
than the Fill Minimum for the Pump Off Count Limit number of strokes, then the Realift Rod Pump stops the pump
jack and remains idle for Pump Off Time.
The lower the Fill Minimum, the less likely it is that the Realift Rod Pump enters a Pump Off state.
It is recommended that you enter a Fill Minimum from 15% to 30% below the value set at commissioning.
Fill Target
The Fill Target represents the ideal fill level for the rod pump. If the calculated fill status of the rod pump exceeds
the fill target, the frequency of rod pump will increase (up to the defined maximum speed, see Maximum Speed on
page 47). If the calculated fill status is lower than the fill target, the frequency of rod pump will decrease (down to
the defined minimum speed, see Minimum Speed on page 47) until it the pump fill again matches the fill target.
The Fill Target value is determined through observation after configuration is complete and the Realift Rod Pump is
started for initial monitoring. See Configuring the Pump Jack for Standard Operation on page 73.
Fill Status
The Fill Status fields provide ongoing readings of the current Fill Status reported by the Realift Rod Pump.
5.4.2
Surface
If operating in Surface mode, you need to set both Surface and Timed modes. The drive reverts to Timed mode if
the load cell signal is lost.
48
Version 3.0c
12/2014
Fill Minimum
Fill Minimum provides a point where the Realift Rod Pump system detects a Pump Off state. If the pump fill is less
than the Fill Minimum for the Pump Off Count Limit number of strokes, then the Realift Rod Pump stops the pump
jack and remains idle for Pump Off Time.
The lower the Fill Minimum, the less likely it is that the Realift Rod Pump enters a Pump Off state.
It is recommended that you enter a Fill Minimum from 15% to 30% below the value set at commissioning.
Fill Target
The Fill Target represents the ideal fill level for the rod pump. If the calculated fill status of the rod pump exceeds
the fill target, the frequency of rod pump will increase (up to the defined maximum speed, see Maximum Speed on
page 47). If the calculated fill status is lower than the fill target, the frequency of rod pump will decrease (down to
the defined minimum speed, see Minimum Speed on page 47) until it the pump fill again matches the fill target.
Fill Target values are determined through observation after commissioning is complete and the Realift Rod Pump is
started for initial monitoring. See Configuring the Pump Jack for Standard Operation on page 73.
Fill Status
The Fill Status fields provide ongoing readings of the current Fill Status reported by the Realift Rod Pump.
5.4.3
Downhole
If operating in Downhole mode, you need to set both Downhole and Timed modes. The drive reverts to Timed
mode if the load cell signal is lost.
49
5.5
Version 3.0c
12/2014
50
Version 3.0c
12/2014
5.6
Pre-Control Strokes
It is usually desirable to allow the pump jack to run for a number of strokes immediately following restart. This
allows the system to reach normal operating state and ignore any initial system instability before the Realift Rod
Pump makes speed adjustments to the pump. The Pre-Control Strokes is defined in strokes.
Suggested strokes vary with time required for any start-up transients to disappear, but a typical value is 20 strokes.
Speed Change Strokes
The number of strokes run between speed changes. The Realift Rod Pump can adjust speed with every stroke;
however, you may prefer that speed be adjusted once every 5 or 10 strokes. The Speed Change Strokes is defined
in strokes.
Speed is adjusted by the amount of the speed range (the difference between Maximum Speed and Minimum
Speed) proportional to how much Fill Status differs from Fill Target. If Fill Status suddenly drops to a value much
lower than Fill Target (for example, from 83% to 55% while Fill Target is 85%) and if speed is set to adjust with
every stroke, the Realift Rod Pump immediately reduces speed by a large amount to minimize fluid pound and
equipment wear.
The suggested setting is one stroke.
Pump Off Count Limit
When pump detects a persistent pump fill at less than the Fill Minimum (as in a Pump Off situation), you should set
the number of strokes the pump continues to run before it finally switches to Pump Off. This allows the pump to run
through temporary gas pockets or other anomalies affecting pump fill but not serious enough to warrant pumping
off. The Pump Off Count Limit is defined in strokes.
The suggested setting is three strokes.
51
52
Version 3.0c
12/2014
Version 3.0c
12/2014
6.1
53
Version 3.0c
12/2014
API dimensions are a series of six measurements on a typical pump jack, used to calculate Stroke Length based
on the geometry of the pump jack unit:
Rn Distance from the center of the crankshaft to the center of the Pitman Arm wrist pin in inches, where n =
the corresponding pin position
K Distance from the center of the crankshaft to the center of the saddle bearing, in inches
C Distance from the center of the saddle bearing to the center of the equalizer bearing, in inches
P Effective length of the Pitman, in inches
A Distance from the center of the saddle bearing to the center line of the polished rod, in inches
I Horizontal distance between the center line of the saddle bearing and the center line of the crankshaft, in
inches.
K=
[(H-G) + I ]
During the installation of the Realift Rod Pump HMI software, a spreadsheet was installed with the API dimensions
of the most common rod pumps. You can find it in the Schneider Electric Realift Rod Pump installation directory.
54
Version 3.0c
12/2014
C
A
P
K
H
If H, I, and G
are known, K
can be calculated
G
R1, R2, or Rn
I
Figure 6.5: Air-Balanced Pump Jack
C
A
R1, R2, or Rn
If H, I, and G
are known, K
can be calculated
55
Version 3.0c
12/2014
C
A
R1, R2, or Rn
If H, I, and G
are known, K
can be calculated
6.2
Stroke Length
Determine the stroke length using the Stroke Length diagram, Figure 6.8.
56
Version 3.0c
12/2014
Polished
Rod
Bottom of Stroke
Stroke
Length
Top of Stroke
6.3
The Realift Rod Pump uses the Proximity Angle to determine the location of the center axis of the Pitman Arm wrist
pin relative to the position at which the crank arm first triggers the proximity sensor. The Proximity Angle is
measured from bottom dead center (BDC) in a counter-clockwise direction when viewing the pump jack from its
side with the polished rod on the right, as shown in Figure 6.4. Figure 6.10, Proximity Angle, Conventional Pump
Jack, shows this in more detail.
57
Version 3.0c
12/2014
Pitman Arm
Gear Box
Crank Axis
Proximity Sensor
Wrist Pin
Pump Jack Base
Crank Arm
Proxmity Angle
BDC (0 )
Rotation (CCW)
The Proximity Angle should be between 0 and 90 (absolute value) when the proximity sensor is mounted below
the level of the crank axis, as in Figure 6.10. In certain instances it may be necessary to mount the proximity
sensor above the crank axis; if this is the case, the absolute value will be between 90 and 180.
The direction of rotation dictates whether the Proximity Angle is positive or negative. In Figure 6.10, the crank arm
is rotating counter-clockwise and triggers the proximity sensor after it passes BDC. The Proximity Angle in this
instance is positive (+). Alternately, if the crank arm is rotating clockwise, triggering the proximity sensor before
passing BDC, the Proximity Angle is negative (-).
Set the Proximity Angle by determining the point at which the crank arm first triggers the proximity sensor during a
stroke. It is recommended that someone else operate the pump jack hand brake when performing the following
procedure:
1. Using the potentiometer on the Realift Rod Pump enclosure, set pump jack speed at or just above its minimum
value.
2. Using the HOA switch (see Testing Realift Rod Pump System Operation on page 81) place the Realift Rod
Pump in Hand mode and slowly rotate the crank arm.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Read and understand this manual before operating the Realift Rod
Pump system.
Ensure that the pump jack is stopped with handbrake engaged before
approaching it to make observations, take measurements, or adjust the
equipment.
Failure to follow these instructions can result in minor or moderate
injury.
3. Switch HOA to Off as the helper quickly applies the pump jack brake, stopping the crank arm just as it triggers
the proximity sensor.
58
Version 3.0c
12/2014
4. After the pump jack is stopped with the hand brake engaged, confirm that the LED indicator on the base of the
proximity sensor is lighted, as shown in Figure 6.11.
Figure 6.11: Location of LED Indicators on Base of Proximity Sensor
With the crank arm held in place by the hand brake, the Proximity Angle can now be determined (see Figure 6.12).
If you have access to a hand-held protractor with plumb-bob or similar tool (there are also a number of smart
phone applications that do this), use this tool to measure the angle from vertical (BDC, or 0) to the center axis
of the wrist pin to obtain the Proximity Angle in degrees ().
If no such tool is available, calculate the Proximity Angle by measuring the distance Y from the crank axis to a
point of your choosing along the vertical axis, then measuring at a right angle from that point to the center axis
of the wrist pin to obtain X (if the proximity sensor is mounted above the Crank Axis, the procedure is still the
same).
59
Version 3.0c
12/2014
Figure 6.12: Measuring the Proximity Angle (Proximity Sensor Activated after Straight-down Position
Crank Axis
Proxmity Angle
Proximity Sensor
Wrist Pin
BDC (0 )
Rotation (CCW)
Calculate XY and look up the corresponding angle value in Table 6.3. Use the left hand column of the table if the
Proximity Sensor is mounted below the Crank Axis, and the right hand column if it is above the Crank Axis. Check
whether the crank arm triggers the proximity sensor before or after it passes BDC and enter the correct sign (+ or -)
as per the table.
Table 6.3:
Angle in
Degrees
60
Angle in
Degrees
X/Y Above
Crank Axis
0.00
90
(Y=0)
0.09
92.5
22.90
10
0.18
95
11.43
15
0.27
100
5.67
20
0.36
105
3.73
25
0.47
110
2.75
30
0.58
115
2.14
35
0.70
120
1.73
40
0.84
125
1.43
45
1.00
130
1.19
50
1.19
135
1.00
55
1.43
140
0.84
60
1.73
145
0.70
65
2.14
150
0.58
70
2.75
155
0.47
75
3.73
160
0.38
80
5.67
165
0.27
85
11.43
170
0.18
87.5
22.90
175
0.09
90
(Y=0)
180
0.00
Version 3.0c
12/2014
If the proximity sensor is triggered before the wrist pin reaches bottom dead center, the proximity angle is negative
(-). the proximity sensor is triggered after the wrist pin reaches bottom dead center, the proximity angle is positive
(+).
6.4
Proxmity Angle
(- 165 )
Wrist Pin
Crank Axis
Proximity Sensor
Rotation (CCW)
BDC (0 )
6.5
61
Version 3.0c
12/2014
Crank Arm
Cross Section
Proximity Sensor
Rotation
In such instances, set the Proximity Debounce Time to an interval long enough so that any subsequent triggering
of the proximity sensor is ignored until the rotation is complete. The default Debounce Time is 3000 ms (3 sec.), but
this value can be adjusted.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Read and understand this manual before operating the Realift Rod
Pump system.
Ensure that the pump jack is stopped with handbrake engaged before
approaching it to make observations, take measurements, or adjust the
equipment.
Failure to follow these instructions can result in death or serious
injury.
To adjust the debounce time:
1. Release the hand brake and using the HOA switch, set the pump jack back into motion.
62
Version 3.0c
12/2014
6.6
6.7
Damping Factor
The Damping Factor is the downhole calculation parameter that affects the shape of the Downhole Card. A typical
value is 0.080, although the Damping Factor can be adjusted to correct the shape of the Downhole Card.
The suggested value is 0.080.
Rod String Speed of Sound
The Rod String Speed of Sound is the velocity of sound traveling in the rod material. For steel, this value is
approximately 16300 ft/sec; for fiberglass, approximately 14900 ft/sec. The Rod String Speed of Sound is defined
in feet per second (ft/sec).
Tubing Fluid Gradient
The Tubing Fluid Gradient exerts pressure by a vertical foot of fluid in the well tubing. A typical value, which
depends on rod and tubing diameters and fluid characteristics, falls within 0.400 to 0.420 psi/ft. The Tubing Fluid
Gradients is defined in pounds per square inch per foot (psi/ft).
The recommended value is 0.4, unless more is known about system geometry and fluid characteristics.
Casing Fluid Gradient
The Casing Fluid Gradient exerts pressure by a vertical foot of fluid in the well casing, excluding tubing. A typical
value is from 0.400 to 0.430 psi/ft, although this depends on casing and tubing diameters and fluid characteristics.
The Casing Fluid Gradient is defined in pounds per square inch per foot (psi/ft).
The recommended value is 0.4 psi/ft, unless more is known about system geometry and fluid characteristics.
Copyright 2014 Schneider Electric Canada Inc.
63
Version 3.0c
12/2014
Pump Diameter
The Pump Diameter is the inside diameter of the pumping chamber in the pump at the bottom of the well. The
Realift Rod Pump calculates the Pump Area from the Pump Diameter to estimate production. The Pump Diameter
is defined in inches (in).
Enter the diameter of the pump currently installed in the well.
Pump Efficiency Factor
The Pump Efficiency Factor is multiplied by the theoretical production to result in the Realift Rod Pump production
values. The Pump Efficiency Factor is defined as a percentage (%). When you modify the Pump Efficiency Factor,
the Realift Rod Pump production values do not update immediately but take time to update.
It is suggested to set the value to 80%, until enough time elapses that Realift Rod Pump estimated production can
be compared to actual production and the Pump Efficiency Factor adjusted accordingly.
Include Buoyancy in Calculation
Include Buoyancy in Calculation determines whether the Realift Rod Pump includes the effects of buoyancy in
computing the Downhole Card. Select Yes or No.
Set to No, unless you include buoyancy in the load results on the Downhole Card.
6.8
64
Version 3.0c
12/2014
6.9
Number of Tapers
The Number of Tapers is the number of rod string sections currently installed in the well, with a value ranging from
one to six.
(Taper) Length
The Taper Length is the length of the rod string sections in the well. The (Taper) Length is defined in feet (ft).
(Taper) Diameter
The Taper Diameter is the diameter of the rod string sections in the well, excluding joints. The (Taper) Diameter is
defined in inches (in).
(Taper) Weight
The Taper Weight is the weight per foot of the rod tapers in the well. The (Taper) Weight is defined in pounds per
foot (lbs/ft).
See Table 6.4 for fiberglass and steel weights for typical rod sizes.
Table 6.4:
Weight Table
3/4
0.47
1.634
7/8
0.64
2.224
0.79
2.904
1.2
1.22
4.07
1.25
1.34
4.55
1.5
1.91
1.625
2.09
65
Version 3.0c
12/2014
(Taper) Modulus
The Modulus is the elasticity of the material of the rod string sections in the well. The Modulus for steel is
30.5 Mpsi. For fiberglass, it is 7.2 Mpsi. The (Taper) Modulus is defined in millions of psi (Mpsi).
66
Version 3.0c
12/2014
WARNING
UNEXPECTED EQUIPMENT OPERATION
Read and understand this manual before operating the Realift Rod
Pump system.
Any changes made to parameter settings must be performed by
qualified personnel.
Failure to follow these instructions can result in death or serious
injury.
Figure 7.1: Well Fault Detection Page
The system reports a Well Alarm or Well Fault when a data value consistently falls outside of a defined range for a
specified period of time or number of strokes. Well faults and alarms apply in both hand and auto mode.
Changing the Realift Rod Pump from Auto to Hand mode while it is running resets the current values of the well
alarm detection count to zero, but not the current values of the well fault detection count. Changing the Realift Rod
Pump from Auto to Hand mode while it is in a pump-off state, for example, due to an alarm or a fault state, clears
any existing alarms or faults and causes the pump to restart.
67
Version 3.0c
12/2014
Well Alarm and Well Fault detection parameters are described in Table 7.5:
Table 7.5:
Parameter
Enable
Startup Ignore
Threshold Value
Well Alarm
Detection Count,
Limit Value
Well Fault
Detection Count,
Limit Value
If Pump Off Time is zero it will not shut down due to pump off, unless a per stroke or real-time alarm occurs and, in
that case, then a pump off time of 1 minute will occur following the alarm. If a fault occurs, the pump stops.
When a Well Alarm is triggered, the parameter name is highlighted in yellow. When a Well Fault is triggered, the
parameter name is highlighted in red. In addition, the Well Fault Configuration icon in the Navigation pane is
highlighted and a message appears in the Alarm List on the Main menu page, shown in Figure 2.3 on page 13.
If the undesired condition persists such that Well Alarm Detection Count Current Value reaches Well Alarm
Detection Count Limit Value, a Well Alarm is recorded under the Well Fault Detection Count Current Value and the
Realift Rod Pump enters a Pump Off state. A corresponding alarm message appears on the Realift Rod Pump HMI
Main Menu in the Alarm List window.
If a bypass or external fault is detected during a Pump Off, the pump off time is set to zero and, once the bypass or
external fault condition is removed, the Realift Rod Pump will restart.
7.1
68
Version 3.0c
12/2014
Every Per Stroke alarm operates in the same way: conditions are evaluated by the Realift Rod Pump with each
complete stroke; detection for each parameter does not begin until Startup Ignore is complete.
If the Current Value exceeds the Threshold Value, the Well Alarm Detection Count begins to count strokes. If
the Current Value remains above the Threshold Value for the number of strokes indicated by the Well Alarm
Detection Count Limit Value, a Well Alarm is reported and the Realift Rod Pump stops the pump jack for one
Pump Off period.
If, upon restarting, the Well Alarm condition has not cleared, another Well Alarm is reported and the Realift Rod
Pump stops the pump jack again for one Pump Off period.
If the number of reported Well Alarms equals the number indicated in the Well Fault Detection Count Limit
Value, the Realift Rod Pump stops the pump jack again and reports a Well Fault. The pump jack does not
restart until the Well Fault is manually cleared.
For example, if the Threshold Value for High Belt Slip is set at 8% and the Well Fault Detection Count has a
Limit Value of four strokes:
If, on the first stroke, the Current Value is 5%, zero is entered for the Current Value under the Well Alarm
Detection Count.
If, on the second stroke, the Current Value is 10%, one stroke is entered for the Current Value under the
Well Alarm Detection Count.
If, on the third stroke, the Current Value is 10%, a second stroke is entered for the Current Value under the
Well Alarm Detection Count.
If, on the fourth stroke, the Current Value is 9%, a third stroke is entered for the Current Value under the
Well Alarm Detection Count.
If, on the fifth stroke, the Current Value is 4%, one stroke is removed from the Current Value under the Well
Alarm Detection Count and the stroke count returns to two.
If, on the sixth stroke, the Current Value is 10%, a third stroke is entered for the Current Value under the
Well Alarm Detection Count.
If, on the seventh stroke the Current Value is 9%, a fourth stroke is entered for the Current Value under the
Well Alarm Detection Count. The limit value of four triggers a Well Alarm and a Pump Off period.
There are four parameters for Per Stroke alarms, each of which can be enabled or disabled. When commissioning the
Realift Rod Pump, clear the Well Alarm and Well Fault detector check boxes. See Table 7.6 for suggested initial
values.
69
Table 7.6:
Version 3.0c
12/2014
Parameter
7.2
High Imbalance
3
3
If the Current Value exceeds the Threshold Value, the Well Alarm Detection Count begins to record the
duration. If the Current Value persists above the Threshold Value for the time indicated by the Well Alarm
Detection Count Limit Value, a Well Alarm is reported and the Realift Rod Pump stops the pump jack for one
Pump Off period.
If, on restart, the Well Alarm condition has not cleared, another Well Alarm is reported and the Realift Rod
Pump stops the pump jack again for one Pump Off period.
If the number of reported well alarms exceeds the number indicated in the Well Fault Detection Count Limit
Value, the Realift Rod Pump stops the pump jack again and reports a Well Fault. The pump jack does not
restart until the Well Fault is manually cleared.
For example, if the Threshold Value for High Torque is set at 300% and the Well Alarm Detection Count has a
Limit Value of five seconds:
If, on the first second, the Current Value is 250%, zero is entered for Current Value under Well Alarm
Detection Count.
If, on the second second, the Current Value is 310%, 1 second is entered for the Current Value under Well
Alarm Detection Count.
If, on the third second, the Current Value is 330%, an additional 1 second is entered for Well Alarm
Detection Count.
If, on the fourth second, the Current Value is 309%, another 1 second is entered.
If, on the fifth second, the Current Value is 250%, 1 second is removed from the count; the count returns to
2 seconds.
The count continues until the Limit Value of five seconds is reached, triggering a Well Alarm and a Pump Off
period.
The Well Alarm Detection Count for each real-time parameter is reset to 0 if one of the following conditions is met:
The Well Alarm Detection Count for a parameter is reset to 0 after the Well Fault Detection Count increments
and the pump has restarted (for example, after the pump off time has elapsed).
The Well Alarm Detection Count for a parameter is reset to 0 if the external Fault Reset has been triggered or
if the Reset Detection for Well and Drive button has been clicked.
The Well Alarm Detection Count for a parameter is reset to 0 if the parameter, which was disabled, is enabled.
The Well Fault Detection Count for each real-time parameter is reset to 0 if one of the following conditions is met:
The Well Fault Detection Count for a parameter is reset to 0 if the external Fault Reset has been triggered or
if the Reset Detection for Well and Drive button has been clicked.
The Well Fault Detection Count for a parameter is reset to 0 if the parameter is disabled.
There are a total of six possible parameters for the Real-Time alarm (High Torque, Low Torque, and High Motor
Power only apply to the Altivar 71), each of which can be enabled or disabled. You can set each of the Well Alarm
70
Version 3.0c
12/2014
Detection Count Limits to a value from 0 to 819 seconds. If the alarm detection count exceeds the maximum
allowable limit (819 seconds), the Well Alarm Detection Count Limit stops incrementing.
When commissioning the Realift Rod Pump, disable Well Alarm and Well Fault detectors. See Table 7.7 for
suggested initial values.
Table 7.7:
Parameter
Well Fault
Startup Ignore Well Alarm Detection
Detection
(Seconds)
Count Limit (Seconds)
Count Limit
High Torque1
30
Low Torque1
30
30
30
30
30
7.3
If the load cell signal is lost, the Realift Rod Pump reverts to Torque Mode, if the drive type is an Altivar 71,
otherwise the Realift Rod Pump reverts to Timed mode.
If the proximity sensor signal is lost, the Realift Rod Pump reverts to Timed Mode, beginning with a Pump Off
period and the Missed Prox Count increments. When the Missed Prox Count has incremented to 5, an alarm is
generated. Clicking the Reset button resets the Missed Prox Count to 0.
Clicking Load Cell or Proximity Sensor in the Sensor pane displays a graphic with load cell and proximity
sensor data (see Figure 7.4). You can select the values to be displayed by selecting or clearing the check
boxes at the bottom of the dialog box.
See also Off Time (Timed Mode) and On Time (Timed Mode), page 46.
Figure 7.3: Sensor Pane
71
Version 3.0c
12/2014
When a lost sensor begins to function again, the Realift Rod Pump automatically resumes operation in its
previously selected control mode.
Figure 7.4: Load Cell and Proximity Sensor Data
7.4
Additionally, when you click the Reset Detection for Well and Drive button on the Well Fault Detection page, a
digital input on the SCADAPack 535 E (DI-14) is set to True for one second. This digital input can be used to reset
faults on a drive. Consult your drive manufacturers documentation for more information.
If an Altivar 71 is used, when you click the Reset Detection for Well and Drive button on the Well Fault Detection
page, a reset faults command is issued to the drive. This command will clear some faults on the Altivar 71,
provided that the fault condition has been removed. Consult your drive manufacturer's documentation for details.
Messages in the Alarm List on the main menu (see Figure 2.3) can be cleared after Well Fault Detection counters
have been reset by highlighting that message and clicking the Acknowledge Selected Alarm button.
72
Version 3.0c
12/2014
The HOA switch is Off and the speed potentiometer is set to a speed at or just above the equipments minimum
speed.
In the Time & Network Configuration pages Communication pane, the Communication State field reads
Connected (Configuring the Computer for Communication with the Realift Rod Pump on page 22).
In the Status pages Card Display & Settings pane, the Card Interval is set to a maximum of 10 seconds (Card
Display and Settings on page 94).
After confirming baseline settings for the pump jack and Realift Rod Pump HMI software, use the following
procedure to configure the Realift Rod Pump:
1. Set the speed potentiometer to a point at or just above minimum speed.
2. In the Main Status page, confirm that the Run Pump command is set as shown in Figure 8.1:
Run Pump: Enabled
RPC Status: Hand
Drive Status: Forward
Figure 8.1: Summary Pane: Enabled, Hand, Forward
73
Version 3.0c
12/2014
If viewing a Surface card, the plot may be similar to the Surface plot shown in Figure 8.3.
Figure 8.3: Example Surface Plot
If viewing a Downhole card, the plot may resemble the Downhole plot shown in Figure 8.4. Ideal Downhole cards
have a roughly rectangular shape.
74
Version 3.0c
12/2014
7. After several dynamometer plots have been generated with consistent results, set the Control Load
parameters:
For Surface Fill Control Level, see Setting the Surface Fill Control Level on page 75.
For Downhole Fill Control Level, see Setting the Downhole Fill Control Level on page 76.
No Control Load parameter is required to operate in Torque mode.
8.1
Effective Stroke is the portion of the downstroke where fluid is flowing through the open traveling valve.
Total Stroke is the total length of the downstroke.
Ideally, the Fill Status ratio is 1:1. However, as the fluid level changes, so too does Effective Stroke.
For both surface and downhole cards, Effective Stroke is determined by finding the position, on the downstroke,
where load first decreases below a determined level. The determined level is called Control Load.
8.1.1
75
Version 3.0c
12/2014
Load
Lmax
Upstroke
Control
Load
Downstroke
L min
Total Stroke
Position
Effective Stroke
A
In Figure 8.5:
The Surface Total Stroke is the distance on the plot from A (lowest position of the stroke) to D (highest position
of the stroke).
The Surface Effective Stroke is calculated where the curve first falls below SFCL when the curve travels from A
to C.
In the Surface & Downhole Data pane on the Status page, Figure 8.6, enter the SFCL.
Figure 8.6: Surface & Downhole Data Pane
8.1.2
L max L min
CL = DFCL -----------------------------------100 + L min
Where:
CL is Control Load
DFCL is the chosen Downhole Fill Control Level
Lmax is the Downhole Card Maximum Load
Lmin is the Downhole Card Minimum Load
76
Version 3.0c
12/2014
Set DFCL such that, for most cards, Control Level intersects the downstroke where the slope of load versus
position is close to vertical. In general, DFCL is at or below 35% to achieve a representative Downhole Effective
Stroke and, therefore, Downhole Fill Status.
Displacement:
Load
Lmax
Upstroke
Control
Load
Downstroke
L min
Total Stroke
A
Effective Stroke
Position
In Figure 8.7:
The Downhole Total Stroke is the distance on the plot between A (lowest position of the stroke) and C (highest
position of the stroke).
The Downhole Effective Stroke is the distance between A and B (position where the slope of load versus
position is nearly vertical).
In the Surface & Downhole Data pane on the Status page, shown in Figure 8.6, enter the DFCL.
In general, a good Downhole Fill Control Level is about 35%. After observing operation, it may be advantageous to
adjust this value (likely to a value less than 35%) to achieve a more accurate measurement of Downhole Effective
Stroke.
1. On the Pump Control Configuration page, confirm Fill Minimum and Fill Target in the Fill Control Settings pane,
shown in Figure 8.8.
Figure 8.8: Fill Control Settings Pane
The Realift Rod Pump system adjusts speed once every Speed Change Strokes to maintain Fill Status equal to
Fill Target:
If Fill Status is greater than Fill Target, speed is increased.
If Fill Status is less than Fill Target, speed is decreased.
If speed decreases to Minimum Speed and Fill Status continues to decrease from Fill Target, speed is held
at Minimum Speed.
If Fill Status is less than Fill Minimum for a count of Pump Off Count Limit, the Realift Rod Pump system
enters a Pump Off state.
77
Version 3.0c
12/2014
If Fill Minimum is set to 0%, the Realift Rod Pump does not enter a Pump Off state. Adjust settings as
necessary to obtain optimal production rate.
If Fill Minimum is greater than 100%, the Realift Rod Pump will enter a Pump Off state (see Forcing a Pump
Off State on page 83).
For a more detailed explanation of the Fill Control Settings, refer to Forcing a Pump Off State on page 83.
2. Calibrate the SPM:Hz Ratio to convert motor speed (Hz) into pump rate (strokes per minute or SPM).
The Realift Rod Pump monitors the next six strokes, comparing the speed of the motor (Hz) with each stroke
identified by the proximity sensor. The software indicates when calibration is complete.
After calibration, Pump Rate in either Hz or SPM is displayed in the Summary pane of the Status page, shown
in Figure 8.1 on page 73. Clicking in that field changes the units from Hz to SPM and back again.
3. Navigate to the Well Fault Detection page (see Configuring Well Fault Detection on page 67) and confirm that
the Current Value fields are populated and within expected ranges. Adjust any Threshold or Limit Values as
necessary to trigger the Well Alarm or Well Fault detectors at the desired levels, shown in Figure 8.10.
78
Version 3.0c
12/2014
4. Confirm that the Realift Rod Pump is reading the well data properly. If the feedback is satisfactory, return the
HOA switch to Off.
5. Navigate back to the Status page. With the HOA switch on the drive enclosure set to Off, confirm the following
settings in the Summary pane, shown in Figure 8.11:
Run Pump: Enabled
RPC Status: Off
Drive Status: Not Ready
Figure 8.11: Summary Pane
The Realift Rod Pump does not operate unless the Run Pump command is Enabled and the HOA switch is
in either the Hand or Auto position.
If Run Pump reads Enabled, but the RPC Status reads Off, this indicates that the HOA switch is in the Off
position.
Similarly, if RPC Status reads No-Run, this may indicate that some other input wired in series with the run
command, such as a vibration or tank level sensor, is telling the Realift Rod Pump that it cannot start at this
time. The No-Run message also appears if a required parameter such as the Start Up Speed is set to zero.
The Realift Rod Pump starts normally after the situation triggering the No-Run message is resolved.
Disable the Run Pump command by clicking the Run Pump field in the Summary pane. RPC Status should
change to Disabled.
6. On the Pump Control Configuration page, set Control Mode to the desired setting: Timed, Torque (for Altivar 71
only), Surface, or Downhole (see Setting the Control Mode on page 44).
In Timed Mode, the Realift Rod Pump does not actively control pump speed and fill rate; it only runs the unit at
constant speed for specified on and off times. Timed mode requires that the Off Time and On Time values for
Timed Mode be set (see Setting On & Off Times on page 45).
7. On the Pump Control Configuration page, verify and configure Bypass Contactor and External Fault Trigger.
8. If using Torque (for Altivar 71 only), Surface, or Downhole Mode, set Auto Off Time Adjust to On. In addition,
confirm that the Off Time (non-Timed), Auto Adjust Max Off Time, and Auto Adjust Min Off Time parameters are
set at the required values (see Setting On & Off Times on page 45).
9. Navigate to the Well Fault Detection page and enable any of the Per Stroke or Real-Time Well Fault detectors
desired by clicking on the Enable box in each control pane.
79
Version 3.0c
12/2014
10. Set the HOA switch on the drive enclosure to Auto. The pump jack should not operate yet as the Run Pump
field was set to Disabled in Step 5.
11. Return to the Status page and enable the Realift Rod Pump by clicking the Run Pump field and setting it to
Enabled. The pump jack should now begin to operate and RPC Status values, which may vary depending on
your Realift Rod Pump HMI software settings, begin to appear.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Read and understand this manual and the drives manual before
operating the Realift Rod Pump system.
Any changes made to parameter settings must be performed by
qualified personnel.
Verify that it is safe to enable the rod pump before doing so.
Failure to follow these instructions can result in death or serious
injury.
If a Start Warning Indicator (SWI) is installed, the SWI activates for the amount of time set in the Startup
Timers pane in the Pump Control Configuration page (Refer to Set Startup Times on page 99). RPC Status
displays Start Warning. Pump jack motion begins when SWI time completes.
If Start Reverse Time is set, the pump jack turns in reverse at the speed set in the Startup Speed field in the
Speed Settings pane for the amount of time specified, then stops and begins to move forward, again at
Startup Speed (see Setting Pump Speeds on page 46). RPC Status displays Start Reverse and Drive
Status displays Reverse.
The pump jack runs for the number of strokes set in the Pre-Control Strokes field before it adjusts speed or
initiates Pump Off. Allow the pump jack to complete the Pre-Control Strokes before attempting to collect well
data (see Setting Control Triggers on page 51).
If any Well Fault Detectors are enabled, detection does not begin until the Startup Ignore period has
elapsed (see Configuring Well Fault Detection on page 67).
12. Navigate to the Well Fault Detection page and enable any of the Per Stroke or Real-Time Well Fault detectors
desired by clicking on the Enable box in each control pane (see Setting Per Stroke Alarm Parameters on
page 68 and Setting Real-Time Alarm Parameters on page 70).
13. Set the HOA switch on the drive enclosure to Auto. The pump jack should not operate yet because the Run
Pump field is set to Disabled (Step 5 on page 79).
14. Return to the Status page and enable the Realift Rod Pump by clicking the Run Pump field and setting it to
Enabled. The pump jack should now begin to operate, with RPC Status readings varying, depending on your
Realift Rod Pump HMI software settings.
80
Version 3.0c
12/2014
Click Well Data Configuration in the Navigation pane. The Well Data Configuration page appears, as shown in
Figure 9.1.
The next steps are performed on the Realift Rod Pump enclosure:
1. With the HOA control set to Off, set the speed at or just above the minimum speed the equipment allows.
2. Switch the HOA control to Hand mode to start the Realift Rod Pump.
81
Version 3.0c
12/2014
3. Gradually increase speed, using the potentiometer, until the pump jack begins to move. After the pump jack is
in motion, monitor operation and make sure that you:
Do not run the pump jack at excessive speed; verify the information on the nameplate.
Stop immediately if any deviation from expected pump jack operation occurs and investigate why operation
is not as expected.
82
Version 3.0c
12/2014
10
10.1
If the Fill Status exceeds the Fill Target, the Realift Rod Pump speeds up incrementally to return the Fill Status
to the target level. The speed change increment is proportional to the difference between the Fill Status and the
Fill Target. The Realift Rod Pump continues to increase speed until either the Fill Target is attained or until the
motor reaches the Maximum Speed value (see Setting Pump Speeds on page 46).
If the Fill Status drops below the Fill Target, the Realift Rod Pump slows the pump jack to return the Fill Status
to the target level or until the Minimum Speed value is reached.
Test the Speed Control by adjusting the Fill Target up or down slightly, observing the Realift Rod Pump as it
changes speed to accommodate the new settings. After confirming satisfactory Realift Rod Pump behavior, return
the Fill Target value to the desired operating level.
10.2
83
Version 3.0c
12/2014
4. Set the Fill Target and the Fill Minimum to 25% and allow the Realift Rod Pump speed to increase until it
reaches Maximum Speed.
5. Set the Fill Minimum back to 101% to force a Pump Off.
6. Upon restart, check to see that the Off Time (non-Timed) value is reduced by one minute.
7. Return the Fill Minimum and Fill Target back to their desired operating levels after satisfactory behavior is
confirmed.
10.3
After the Startup Ignore counts on the Well Fault Detection page are met, the Realift Rod Pump begins to
monitor selected Well Alarm conditions.
For any monitored parameter, if the Current Value moves above or below the Threshold Value in an undesirable
direction, the Well Alarm Detection Count begins. For example, if the Threshold Value for High Torque is set at
200%, and the Current Value exceeds 200%, the corresponding Well Alarm Detection Count increases.
After the system restarts, the Well Alarm monitoring sequence begins again. If the undesired state persists,
another Well Alarm is recorded and another Pump Off state begins. In the High Torque example above, the
Well Fault Detection Count Limit Value is set for three, which means the Realift Rod Pump repeats this process
three times.
If the number of recorded Well Alarms reaches the Well Fault Detection Limit Value, a Well Fault is reported.
The Realift Rod Pump stops the pump jack until the user manually clears the Well Fault condition.
Observe Realift Rod Pump operation as the Well Alarm Detection Counter reaches its Limit Value and the
Realift Rod Pump enters a Pump Off state. Wait for the Realift Rod Pump to restart and allow the sequence
to repeat.
g. When the number of Well Alarms reaches the Well Fault Detection Count Limit Value, observe that the
Realift Rod Pump enters a Well Fault state and that the pump jack shuts down.
h. Clear the Well Fault Message. This allows the Realift Rod Pump to restart when you click Reset Detection
for Well and Drive on the Well Fault Detection page.
84
Version 3.0c
12/2014
i.
Disable detection by un-checking the Enable box for the chosen parameter. Test other parameters as
desired. When the desired parameters have been tested, disable every detector except those that are to be
monitored in routine operation.
2. To clear a message saved in the Alarm List on the Main Menu page after Well Fault Detection counters have
been reset, highlight the message and click the Acknowledge Selected Alarm button.
3. Return the Auto Off Time Adjust parameter to the desired value for routine operation.
85
86
Version 3.0c
12/2014
Version 3.0c
12/2014
11
11.1
L max
L min
87
Version 3.0c
12/2014
L max
L min
Ideally, the Realift Rod Pump should have good fluid flow with valves working properly. This would generate a card
such as the one shown in Figure 11.2. The ideal card shown in Figure 11.2 demonstrates the instantaneous
increase in load from Lmin to Lmax as the pump plunger begins its upward stroke, the load remaining constant as it
completes its travel to the top. As soon as the pump plunger starts back down, the load instantly falls back to Lmin
where it remains constant as the pump travels to its bottom position again.
The load falling instantly to Lmin and remaining constant for the entire downstroke (Ptop to Pbottom) indicates that
the traveling valve on the pump has opened properly, transferring the fluid from pump to tubing. When the pump
plunger reaches bottom, the barrel is empty and the reciprocating motion of the pump jack begins to lift the entire
column of fluid up to the top again, causing more fluid to be pulled in from the reservoir through the standing valve.
However, when a condition such as low fluid level or trapped gas stops the traveling valve from opening properly
as the plunger starts downward, transfer of the contents of the pump to the tubing does not begin at the top of the
stroke. The fluid in the tubing merely descends with the traveling valve, maintaining load at Lmax, until fluid is
encountered or the gas compresses enough to open the traveling valve. Only when the plunger re-immerses in the
fluid can the traveling valve open and transfer of fluid through the traveling valve occur.
88
Version 3.0c
12/2014
L max
L min
The Realift Rod Pump detects the condition where the traveling valve does not open at the top of the stroke and
reduces pump speed to reduce mechanical stress on the system and to allow more time for the pump to fill. If
speed reduction does not work and fill remains low, the Realift Rod Pump enters a Pump Off State and waits for a
predetermined interval, called Pump Off Time, before restarting (see Setting Fill Controls on page 48).
The shapes of individual downhole cards not only provide valuable clues to diagnose changes in fill level over time, but
also aid in the evaluation of hardware conditions. Knowing if the reservoir is low, valves are leaking, tubing is
unanchored, or if other factors are at play allows the operator to better manage production levels and anticipate whether
maintenance is required.
Figure 11.4 illustrates the most common downhole card shapes and the well conditions associated with them.
Shapes vary among different pump jacks; these examples are for information only and do not represent absolute
well conditions or recommended courses of action.
89
11.2
Version 3.0c
12/2014
Full Pump
Worn Plunger or
Traveling Valve
Tubing Movement
90
Fluid Pound
Gas Interference
Worn
Standing Valve
Fluid Friction
Pump Hitting
Up or Down
Drag Friction
Bent Barrel or
Sticking Pump
Version 3.0c
12/2014
12
The run status of the pump, Realift Rod Pump Status, and Drive Status
A summary of various Realift Rod Pump parameters, including the active control mode, the fill status, frequency
command, pump rate, and fluid load
Surface and downhole data, including total and effective strokes.
The Status page also enables you to configure sensor weight, filtering, and external sensors.
Figure 12.1: Status Page
91
12.1
Version 3.0c
12/2014
Summary Data
The Summary pane which can be seen in Figure 12.1 displays an overview of the following parameters of the
Realift Rod Pump:
Run Pump: The Run Pump displays whether the Realift Rod Pump is Enabled or Disabled. Clicking Run Pump
enables or disables the Realift Rod Pump.
RPC Status: The RPC Status is the current state of Realift Rod Pump system operation. RPC Status values are
listed and defined in Table 12.8:
Table 12.8: RPC Status
Status
Off
Hand
Realift Rod Pump is running continuously, its speed determined by the speed pot.
Start Delay
Realift Rod Pump is in the Power Cycle Start Delay phase of the Auto startup
sequence
Start Warning
Realift Rod Pump is in the Start Warning Time phase of the Auto startup sequence.
Start Reverse
Realift Rod Pump is in the Start Reverse Time phase of the Auto startup sequence.
Auto
Pump Off
Well Flt
Alarm
Realift Rod Pump is not running and is in Pump Off state due to detection of a Well
Alarm.
No-Run
Realift Rod Pump is in Auto mode but not running (waiting for Run Command input
(DI-11), to go high), or Startup Speed is zero.
Energy
Realift Rod Pump is not running because the time of day is during the Energy Save
period.
Calibration
Disabled
Stop Key
External Fault
Drive Bypassed
Realift Rod Pump is in Drive Bypassed state. The drive is disconnected from the
motor and, if running, performs a freewheel stop. While the RPC Status is in the
Drive Bypassed state, the drive will not restart.
Drive Fault
If the drive is an Altivar 71, clicking the drive status field displays further information.
more detailed information is available. For other drive types, DI-3 has been set to
true.
92
Action
Although the HOA switch in the Off position is by far the most common cause of the Off status, there are
other possibilities, including:
External sensor has opened Run Command input (DI-11) while HOA is in Hand position
Remote Disable (DI-2)
(see the Realift Rod Pump Hardware Installation Manual for information on DI-11.)
Drive Status: The Drive Status is the current state of drive. The Drive Status can be Forward, Reverse, or Not
Ready.
Active Control Mode: The Active Control Mode is the control mode in use. The Active Control Mode can be
different from the Control Mode set on the Pump Control Configuration page. If a sensor detects a Well Fault,
the Realift Rod Pump will change the control mode and the Active Control Mode will display the actual control
mode.
Run Time Current Run: The Run Time Current Run is the length of time the Realift Rod Pump has been running
since its last Pump Off.
Stroke Count Current Run: The Stroke Count Current Run is the number of strokes since the last Pump Off.
Fluid Height in Casing: The height of the fluid within the well casing.
Fill Status: The Fill Status is the pump fill in percentage for the active control mode.
Pump Rate: The Pump Rate is the Realift Rod Pump speed calculated over the time duration between the last
two times the crank arm passed the proximity sensor. [Units: Strokes per Minute (SPM), minimum: 0.0,
maximum: 100.0]
Version 3.0c
12/2014
12.2
Pump Intake Pressure: The Pump Intake Pressure is the pressure in the casing at the depth specified as the
pump intake.
Imbalance: The Imbalance is a calculated value indicating the balance between the counter weight and the rod
string weight, based on the difference between maximum upstroke torque and maximum downstroke torque. A
negative value indicates that the counterbalance weight is greater than the rod string weight. [Units: percent
(%), minimum: -1000.0, maximum: +1000.0]
Frequency Command: The Frequency Command indicates the set frequency of the drive. If the Drive Status is
Reverse, the Frequency Command is displayed as a negative.
Actual Frequency: The Actual Frequency is the frequency of the drive as reported by the Altivar 71 drive. If the
Drive Status is Reverse, the Actual Frequency is displayed as a negative. For generic drives, the Frequency
Command and Actual Frequency values are the same because the system does not use a frequency feedback
with generic drive types.
Belt Slip: The Belt Slip is the difference between the rod pump system speed measured by the drive (motor
speed) and the pump speed as determined by the proximity sensor (crank arm speed). [Units: percent (%),
minimum: -1000.0, maximum: +1000.0]
12.3
For detailed information on the Fill Control Level settings, see Configuring the Pump Jack for Standard Operation
on page 73.
93
12.4
Version 3.0c
12/2014
Card Interval sets the frequency at which card data is collected by Realift Rod Pump HMI software. When
configuring the Realift Rod Pump for the first time, this value is set in Establishing Communication Speed and Card
Interval Settings on page 27. Changing the Card Interval is explained in Changing Card Interval on page 110.
The Card Display and Settings pane also enables you to set the curves that will be displayed in the card. For more
information, see Setting Curve Visibility on page 106.
12.4.1
94
Version 3.0c
12/2014
2. Define the Load Cell Filter Weight as a percentage. The Load Cell Filter Weight filters data directly from the
load cell. If the load cell data is noisy, increase the value of the filter until the noise is sufficiently rejected.
3. Define the Pump Fill Filter Weight as a percentage. If this filter is used, each new pump fill calculation is
averaged with the previous pump fill calculations to reduce the speed oscillations or hunting that result from
an oscillating pump fill.
4. Click OK.
95
12.5
Version 3.0c
12/2014
Input: The Input corresponds to the analog input on the SCADAPack 535 E that the external sensor is
connected to.
Name and Units: You can enter a descriptive name and the units of the value the sensor is measuring.
Manual Calibration: You can enter values under Manual Calibration to convert the measured value into the
value you want displayed. For example, if the measured temperature is in Fahrenheit, you can convert it to
Celsius by entering -32 in Offset and 0.5556 in Mult.
You can also define filters for external sensors and the proximity sensor in the External Sensors dialog box.
When you select the Enable External Sensors Filtering check box, Realift Rod Pump enables an infinite impulse
response exponential filter on the external sensor inputs. The current value is compared to the previous value by
taking 70% of the previous value and adding it to 30% of the current value. The measured sensor results are
smoothed out and the values displayed show a more natural progression.
When you select the Enable Prox Sensors Filtering check box, Realift Rod Pump enables a filter designed to
reduce spurious strokes. When selected, the Proximity Sensor must be true for at least two Realift Rod Pump
program scans for it to count a stroke.
In the Production pane, the gross and net production rates are displayed. The Net Oil rates are calculated using the
Water Cut that you can enter by clicking the Water Cut field. When you modify the value in the Water Cut field, the
Net Oil values update immediately.
96
Version 3.0c
12/2014
13
By default, the History Trends and Events page displays the Pump Fill and Pump Off trends. You can also view the
plots of any of the parameter sets in the Data Selection pane.
There are three sources of data to choose from:
13.1
Real-Time Trends
Stored Trends
Stored Events.
97
Version 3.0c
12/2014
2. Under the Trace column, select the check box corresponding to each parameter you want displayed on the plot
or clear the check box if you do not want the parameter displayed.
3. When you have finished, close the window by clicking the Close button in the upper right-hand corner of the
window.
Real-Time Parameters Available for Trending
The parameters available in each Real-time plot page are shown in Table 13.9:
Table 13.9: Real-Time Trending Parameters (History Trends and Events Window: Data
Selection)
Real-Time Plot
Parameters
Fluid Load (lbs)
Fluid Height in Casing (ft)
Downhole Card Force Max (lbs)
Downhole Diagnostics
98
Version 3.0c
12/2014
Table 13.9: Real-Time Trending Parameters (History Trends and Events Window: Data
Selection) (continued)
Real-Time Plot
Parameters
Surface Card Max Load (lbs)
Surface Diagnostics
The Control Enabled parameter indicates when the Realift Rod Pump is controlling the pump
(i.e., when the pre-control strokes have ended).
The production today is calculated using the gross production and not the net production. In
other words, water cut is not taken into consideration when calculating the production today.
99
Version 3.0c
12/2014
Determine which parameters to view by clicking the check box next to the desired item at the bottom of the page,
shown in Figure 13.4.
Figure 13.4: Pump Fill and Pump Off Plot Window (Showing Only Fill Status)
Multiple parameters can be displayed simultaneously, providing a better picture of operational cause and effect
over time, as shown in Figure 13.5.
Figure 13.5: Gross Downhole Production and Power (Combination of Fill Status and Production)
100
Version 3.0c
12/2014
Parameters
Pump Rate
Run Time
The production estimate is calculated using the gross production and not the net production. In
other words, water cut is not taken into consideration when calculating the production estimate.
If you transfer events as explained in Transferring Stored Trends and Events on page 102, after having reset the
RPC, after having clicked the Reset RPC Values button in the Events and Start/Stop Log window, the events in the
database will be cleared.
101
13.2
Version 3.0c
12/2014
Using the context menu, you can zoom in and out, display titles and other content, pan left or right, and more.
By clicking just below the plot and using the mouse's scroll wheel, you can zoom in and out without using the plot
menu.
If you select Pan from the context menu, you can quickly zoom in and isolate any part of the plot for closer
inspection by placing the cursor over the plot and using the mouses scroll wheel.
13.3
102
Version 3.0c
12/2014
2. Click the Transfer Stored Trends and Events button to start the transfer of information from the Realift Rod
Pump. A transfer indicator lights and the progress bar fills until transfer is complete:
Figure 13.9: Transfer Control and Status Pane Indicators
3. Allow time for the transfer to complete. Stored trends can then be viewed in the same manner as real-time
trends (see Viewing Trends and Events on page 97). The stored data plot pages are identified by the words
Historic Data at the top of each plot, shown in Figure 13.10.
Figure 13.10:Typical Historic Data Plot
103
104
Version 3.0c
12/2014
Version 3.0c
12/2014
14
14.1
Clicking the Set Curve Visibility enables you to chose the curve that is
emphasized in the displayed card. For more information, see Setting Curve
Visibility on page 106.
Clicking the Refresh button refreshes the display.
Clicking the Up button takes you to the directory level up from the current view.
105
Version 3.0c
12/2014
Clicking the Home button takes you to the main directory holding the Stored
Cards and Periodic Cards.
Clicking the Active button opens the folder containing the most recent Periodic
Cards.
Setting Curve Visibility
You can select the curve that is emphasized in a displayed card. You can select the curve that is emphasized
before you display a card, or you can change the emphasized curve on a card that youve already opened.
To select the curve emphasized:
1. Click the Set Curve Visibility button at the top of the History Card Browser pane. The Curve Visibility Options
dialog box appears, as shown in Figure 14.3.
Figure 14.3: The Curve Visibility Options
2. From the Emphasized Curve list, select the curve that you want emphasized in the display. The scaling of the
card will adjust to best display the emphasized curve.
3. Under Additional visible curves, select the check box corresponding to the curve you want displayed and clear
the check box corresponding to the curve you do not want displayed.
4. Click OK to close the dialogue box and save your changes. The changes are applied to the displayed history
card (if any) and on future displayed cards until you change the curve visibility options again.
14.2
106
Version 3.0c
12/2014
Scroll down the folder list to see the folders currently in memory. Clicking on a folder displays its individual cards,
each identified by its time stamp, as shown in Figure 14.5.
Figure 14.5: Periodic Folder Contents
Clicking on the file name of the desired card displays the card data, as shown in Figure 14.6. If the data in the
selected card has been corrupted, the History Card Browser will not display the card. It will display instead the last
card with valid data.
107
Version 3.0c
12/2014
14.3
Cards stored locally on the Realift Rod Pump while the Realift Rod Pump HMI was disconnected
Last Pump Off state or Well Fault, including well conditions immediately prior to an event.
If the data in the selected card has been corrupted, the History Card Browser will not display the card. It will display
instead the last card with valid data. The card data is stored in a CSV file which could be viewed or modified by an
outside program.
108
Card Description
Stored 06 - 5th Card Before Last Stop - Location Pump ID-year-month-datehour minute_seconds.csv
Stored 07 - 4th Card Before Last Stop -Location Pump ID-year-month-datehour minute_seconds.csv
Version 3.0c
12/2014
Stored 08 - 3rd Card Before Last Stop - Location Pump ID-year-month-datehour minute_seconds.csv
Stored 09 - 2nd Card Before Last Stop - Location Pump ID-year-month-datehour minute_seconds.csv
Stored 10 - Last Card Before Last Stop - Location Pump ID-year-month-datehour minute_seconds.csv
Stored 11 - 5th Card Before 2nd Last Stop -Location Pump ID-year-monthdate-hour minute_seconds.csv
Stored 12 - 4th Card Before 2nd Last Stop - Location Pump ID-year-monthdate-hour minute_seconds.csv
Stored 13 - 3rd Card Before 2nd Last Stop - Location Pump ID-year-monthdate-hour minute_seconds.csv
Stored 14 - 2nd Card Before 2nd Last Stop - Location Pump ID-year-monthdate-hour minute_seconds.csv
Stored 15 - Last Card Before 2nd Last Stop - Location Pump ID-year-monthdate-hour minute_seconds.csv
Stored by the operator using the Save Current Card button on the Status page.
As with Stored Trends and Events, you should refresh Stored Cards before viewing the most recent set.
The 18 cards stored cards are created immediately by Realift Rod Pump but no data is stored in them until the event
occurs. For example, the Card Saved by Operator is created but remains blank until you click Save Current Card on
the Status page, then the card currently displayed on the Status page is stored in the Card Saved by Operator. When
you transfer cards from the Realift Rod Pump using the Transfer Control and Status pane (see Transferring Stored
Cards on page 110), Realift Rod Pump transfers all 18 cards, even if some of them are blank. When you transfer
the stored cards, the most recent complete sets of 18 cards in folders identified by the timestamp (date and time) of
the transfer, as shown in Figure 14.7 are displayed.
Figure 14.7: Stored Card Folders
109
Version 3.0c
12/2014
14.4
Click Transfer Stored Trends and Events in the Transfer Control and Status pane. The Transfer Control and
Status pane is found on both the History Cards page and the History Trends and Events page. A transfer
indicator lights and the progress bar fills until transfer is complete (see Figure 14.10).
Stored trends can then be viewed in the same manner as real-time trends (see Viewing Stored Cards on
page 108).
14.5
110
Version 3.0c
12/2014
2. Enter the Card Interval Hours, Card Interval Minutes, and Card Interval Seconds to define the time the Realift
Rod Pump collects each card.
3. Click OK to close the Card Interval dialog box and save your changes.
You can also define the card interval in the Communication pane on the Time & Network Configuration page (see
Establishing Communication Speed and Card Interval Settings on page 27).
111
14.6
Version 3.0c
12/2014
112
Version 3.0c
12/2014
Commissioning Checklist
A.1
Drive Configuration
Table A.1:
A.2
Preparation
Did you connect the laptop and establish a connection? (see the Realift Rod Pump Software
Installation Manual)
Did you resolve any Location and Pump ID conflicts? (page 25)
Did you Auto-Set HMI Settings Required for the Realift Rod Pump? (page 53)
Did you enter the Stroke Length or appropriate API data? (page 53)
Table A.3:
ft/sec
psi/ft
psi/ft
in
Have you entered the complete rod taper information? (page 65)
Table A.4:
klbs
Did you start the Realift Rod Pump in hand mode and verify cards appear? (page 63)
The proximity angle can be calculated with a smart phone tilt sensor.
Table A.5:
113
A.3
Version 3.0c
12/2014
General Control
If Auto Off Time Adjust is on, is Auto Adjust Max Off Time set? (page 45)
If Auto Off Time Adjust is on, is Auto Adjust Min Off Time set? (page 46)
Table A.7:
Configure Timed Mode settingsa sensor alarm can cause the system to revert to timed mode, regardless of
selected control mode.
Table A.8:
Speed Settings
Did you enter Maximum, Minimum, and Startup speeds? (page 46)
Did you place the HOA switch in the Auto position? (see the Realift Rod Pump Hardware
Installation Manual)
Did you set Downhole Fill Control Level (DFCL)?1 (page 76)
Table A.9:
DFCL can usually only be properly set after the well is pumped off. Excessive fluid pound can occur if the Realift
Rod Pump does not observe the pump off as a result of this parameter not being properly set after a pumped-off
card is observed.
114
Did you verify Realift Rod Pump Control during operation? (page 83)
If configuring a stand-alone server, did you reduce Card Interval? (page 110)
Version 3.0c
12/2014
Troubleshooting
The information in this appendix is designed to help you with common situations.
B.1
).
admin1
Password:
welcome
4. Expand the database tree by clicking the symbol to the right of MAIN.
5. Expand the folder "RPC -"
6. Inside this folder, delete any instances that do not have names of the format RPCXXXX.
Figure B.1: Database Tree in ViewX
115
B.2
Version 3.0c
12/2014
If the system shows a grid pattern but is blank, verify that the proximity sensor is installed.
On the Well Fault Detection page, verify no sensor faults have occurred.
B.3
116
Version 3.0c
12/2014
Background:
The Dynagraph plot is generated by the following program:
C:\Program Files\Schneider Electric\DynagraphTool\Graphtool.exe
This program runs as a service and converts data to PNG images that are displayed as remote images in
ClearSCADA.
They are served on port 8080 by the following program:
C:\Program Files\Schneider Electric\DynagraphTool\mongoose-3-0.exe
The following program starts the graph tool and mongoose-3-0 and restarts them if necessary:
C:\Program Files\Schneider Electric\DynagraphTool\GraphRunningCheck.exe
These three programs run as services.
Solution:
1. Verify that these services are running:
a. Click Start.
b. Type Services and press Enter. The Services dialog box appears.
c. Click the top of the "Name" column so that the services are listed in alphabetical order.
d. Look for each of these services and verify that they are running.
e. If they exist and have been stopped, start them and set them to start automatically
2. If they are not on the list of services.
a. Use "My Computer" and navigate to the following directory:
C:\Program Files\Schneider Electric\DynagraphTool\
b. Verify that each of the 3 service executable files described above actually exists and has not been deleted
by anti-virus software. If they have been, restore them from another Realift Rod Pump-HMI installation.
3. If the executable files for these services do exist but the services are not on the services list in the Services
dialog box:
a. Navigate to:
C:\Program Files\Schneider Electric\DynagraphTool\
b. Right-click the "The Services -- Setup GraphRunningCheck and Mongoose service.exe" file and select "Run
as Administrator" from the context menu.
c. Right-click the "The Services - Start.exe" file and select "Run as Administrator" from the context menu.
4. Verify that the services are now running. If they are, when you go back to the software, the cards may still be
blank.
To restore the cards when the services have been restarted:
a. From the Realift Rod Pump HMI Software Main Menu, navigate to a pump by clicking on the pump and then
clicking Navigate to Pump button.
b. In the Card Display & Settings dialog box, at the lower right corner of the Status page, click Set Curve
Visibility.
117
Version 3.0c
12/2014
c. Select or clear the check box corresponding to one of the curves. This will change the curve visibility and
cause the graph to refresh.
5. If the services are running but the card is still blank, port 8080 may be blocked or another service could already
be installed that listens on port 8080.
a. Try disabling any anti-virus software, especially McAfee.
b. Try disabling any other web-servers that exists on port 8080 (ClearSCADA WebX listens on port 80 not port
8080).
6. If you still cannot get the cards to appear, try either installing the software onto a different computer or installing
onto a virtual machine.
B.4
B.5
B.6
Verify that Startup Speed (Keypad Start Speed) is set to an appropriate value. See Setting Pump Speeds on
page 46.
Verify that Maximum Speed (Keypad Max Speed) is set to an appropriate value. See Setting Pump Speeds on
page 46.
Realift Rod Pump Speed Oscillates or Realift Rod Pump Does Speed Hunting
Background:
The Realift Rod Pump speed is oscillating or the Realift Rod Pump is doing speed hunting.
118
Version 3.0c
12/2014
Solution:
You can increase the pump fill filter weight. The Pump Fill Filter Weight filters Pump fill so that it can not update as
quickly. Each new pump fill calculation is averaged with the previous pump fill calculations to reduce the speed
oscillations or hunting that result from an oscillating pump fill.
To increase the pump fill filter weight:
1. Go to the Status page.
2. In the lower right corner of the Status page, click the Set Filtering Options button in the Card Display & Settings
pane.
3. Define the Pump Fill Filter Weight as a percentage.
For more information, see Card Display and Settings on page 94.
B.7
B.8
The Fill Control Level determines how the Realift Rod Pump calculates pump fill. When the well is less than
100% full, the rods begin to hammer. This is visible in the downhole card when the lower right corner of the
downhole card disappears. The Fill Control Level is the position above the bottom of the card where the Realift
Rod Pump looks to calculate pump fill. The default is 35% and it should be set to this value. This means that the
Realift Rod Pump will look 1/3rd of the way up from the bottom of the downhole card to measure pump fill.
Pump fill is the width of the card 1/3rd of the way from the bottom.
The Fill Target is different from this. If the Actual Fill is more than the Fill Target, the Realift Rod Pump will
speed up in an attempt to pump out oil so that actual fill matches the fill target. If the actual fill is less than the fill
target the Realift Rod Pump will slow down so that the pump will fill back up. The Realift Rod Pump will slow
down to minimum speed if necessary in order to match the fill target. If fill reaches the fill minimum, the Realift
Rod Pump will stop for pump off time.
119
120
Version 3.0c
12/2014
Version 3.0c
12/2014
C.1
Periodic Cards
The data stored on periodic cards is divided into the following sections:
General
Status
Time and Network Configuration
Pump Control Configuration
Well Data Configuration
Well Fault Detection
ATV Drive.
General
Location
Pump ID
Card Type
Server Clock (Time Downloaded from RPC)
RPC Clock (Card Time Stamp)
Status
RPC Status
Fill Status - Downhole (%)
Reference Frequency (Hz)
Output Frequency (Hz)
Card Frequency (Hz)
Card Pump Rate (SPM)
Pump Rate (SPM)
Fluid Height in Casing (ft)
Pump Intake Pressure (psi)
Fluid Load (lbs)
Belt Slip (%)
Imbalance (%)
Run Time Today (%)
Production Today (bbl)1
Fill Control Level - Surface (lbs)
Fill Control Level - Downhole (%)
Surface Total Stroke (in)
Downhole Total Stroke (in)
Surface Effective Stroke (in)
Downhole Effective Stroke (in)
Polished Rod Power (HHP)
Pump Power (HHP)
The production today is calculated using the gross production and not the net production. In other words, water cut is not taken into consideration
when calculating the production today.
121
Version 3.0c
12/2014
122
Version 3.0c
12/2014
High Belt Slip - Well Alarm Detection Limit Current Value (str)
High Belt Slip - Well Alarm Detection Count Current Value (str)
High Belt Slip - Well Fault Detection Limit Current Value
High Belt Slip - Well Fault Detection Count Current Value
Imbalance (%)
123
Version 3.0c
12/2014
Low Max Card Load - Well Alarm Detection Limit Current Value (str)
Low Max Card Load - Well Alarm Detection Count Current Value (str)
Low Max Card Load - Well Fault Detection Limit Current Value
Low Max Card Load - Well Fault Detection Count Current Value
Low Fluid Load - Well Alarm Detection Limit Current Value (str)
Low Fluid Load - Well Alarm Detection Count Current Value (str)
Low Fluid Load - Well Fault Detection Limit Current Value
Low Fluid Load - Well Fault Detection Count Current Value
Torque (%)
Torque (%)
Low Torque - Well Alarm Detection Limit Current Value (sec)
Low Torque - Well Alarm Detection Count Current Value (sec)
Low Torque - Well Fault Detection Limit Current Value
Low Torque - Well Fault Detection Count Current Value
Low Output Frequency - Well Alarm Detection Limit Current Value (sec)
Low Output Frequency - Well Alarm Detection Count Current Value (sec)
124
Version 3.0c
12/2014
High Motor Power - Well Alarm Detection Limit Current Value (sec)
High Motor Power - Well Alarm Detection Count Current Value (sec)
High Motor Power - Well Fault Detection Limit Current Value
High Motor Power - Well Fault Detection Count Current Value
High Load Cell - Well Alarm Detection Limit Current Value (sec)
High Load Cell - Well Alarm Detection Count Current Value (sec)
High Load Cell - Well Fault Detection Limit Current Value
High Load Cell - Well Fault Detection Count Current Value
Low Load Cell - Detection Enabled
Low Load Cell - Startup Ignore (sec)
Low Load Cell - Well Threshold Value (lbs)
Target IP Address
RPC Version
RPC Version Type
RPC HMI Version
Parameter Set Most Recently Accessed
Rod Stroke Count (str)
Pump Stroke Count (str)
Stroke Count Current Run (str)
Run-Time Since Reset (hours)
Run Time Current Run (hh:mm:ss)
Run Time Total (hours)
Energy Save Begin Time - Sunday
125
Version 3.0c
12/2014
ATV Drive
C.2
Stored Cards
The data stored on stored cards is divided into the following sections:
General
Status
Time and Network Configuration.
General
Location
Pump ID
Card Type
RPC Clock (Card Time Stamp)
Status
126
Version 3.0c
12/2014
Table 1:
Config
View
Refresh List
Active
Active
Active
Active
Active
Active
Logout
Active
Active
Active
Active
Disabled
Disabled
Active
Disabled
Disabled
Active
Disabled
Disabled
Manage Users
Active
Disabled
Disabled
Active
Active
Active
Create User
Active
Disabled
Disabled
Delete User
Active
Disabled
Disabled
Exit
Active
Active
Active
Run Pump
Active
Active
Disabled
RPC Status
Read-Only
Read-Only
Read-Only
Drive Status
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Fill Status
Read-Only
Read-Only
Read-Only
Frequency Command
Read-Only
Read-Only
Read-Only
Actual Frequency
Read-Only
Read-Only
Read-Only
Pump Rate
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Fluid Load
Read-Only
Read-Only
Read-Only
Belt Slip
Read-Only
Read-Only
Read-Only
Imbalance
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Production Today
Read-Only
Read-Only
Read-Only
Production Yesterday
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Login Page
Manage Users
Status Page
127
Table 1:
Version 3.0c
12/2014
Config
View
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Card Interval
Active
Active
Disabled
Card Age
Read-Only
Read-Only
Read-Only
Active
Active
Active
Active
Active
Active
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Active
Active
Active
Active
Active
Active
Active
Downhole Diagnostics
Active
Active
Active
Surface Diagnostics
Active
Active
Active
Torque Diagnostics
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Pump Rate
Active
Active
Active
Load Samples
Active
Active
Active
Run Time
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Production Estimate
Active
Active
Active
Active
Active
Active
Active
Active
Disabled
Active
Active
Disabled
Exit
Active
Active
Active
Active
Active
Disabled
Active
Active
Active
Refresh
Active
Active
Active
Up One Level
Active
Active
Active
Home
Active
Active
Active
Active Folder
Active
Active
Active
Active
Active
Active
Card Interval
Active
Active
Disabled
Read-only
Read-only
Read-only
Active
Active
Active
Trend Page
History Page
128
Version 3.0c
12/2014
Table 1:
Config
View
Root Directory
Active
Disabled
Disabled
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Active
Active
Read-Only
Exit
Active
Active
Active
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
GDT Password
Hidden
Hidden
Hidden
Produced Resource
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Startup Speed
Active
Active
Disabled
Max Speed
Active
Active
Disabled
Min Speed
Active
Active
Disabled
Active
Active
Active
SPM : Hz Ratio
Active
Active
Read-Only
Active
Active
Disabled
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Pre-Control Strokes
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Stroke Length
Active
Active
Disabled
Read-Only
Read-Only
Disabled
Active
Active
Active
Active
Active
Disabled
Direction of Rotation
Active
Active
Disabled
SPM : Hz Ratio
Active
Active
Disabled
129
Table 1:
Version 3.0c
12/2014
Config
View
Calibrate
Active
Active
Disabled
Proximity Angle
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Prox Status
Read-Only
Read-Only
Read-Only
Load Status
Read-Only
Read-Only
Read-Only
Damping Factor
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Pump Diameter
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Number of Tapers
Active
Active
Disabled
Taper 1 Length
Active
Active
Disabled
Taper 1 Diameter
Active
Active
Disabled
Taper 1 Weight
Active
Active
Disabled
Taper 1 Modulus
Active
Active
Disabled
Taper 2 Length
Active
Active
Disabled
Taper 2 Diameter
Active
Active
Disabled
Taper 2 Weight
Active
Active
Disabled
Taper 2 Modulus
Active
Active
Disabled
Taper 3 Length
Active
Active
Disabled
Taper 3 Diameter
Active
Active
Disabled
Taper 3 Weight
Active
Active
Disabled
Taper 3 Modulus
Active
Active
Disabled
Taper 4 Length
Active
Active
Disabled
Taper 4 Diameter
Active
Active
Disabled
Taper 4 Weight
Active
Active
Disabled
Taper 4 Modulus
Active
Active
Disabled
Taper 5 Length
Active
Active
Disabled
Taper 5 Diameter
Active
Active
Disabled
Taper 5 Weight
Active
Active
Disabled
Taper 5 Modulus
Active
Active
Disabled
Taper 6 Length
Active
Active
Disabled
Taper 6 Diameter
Active
Active
Disabled
Taper 6 Weight
Active
Active
Disabled
Taper 6 Modulus
Active
Active
Disabled
Stroke Length
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Direction of Rotation
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
API Dimensions
130
Version 3.0c
12/2014
Table 1:
Config
View
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Active
High Imbalance
Active
Active
Active
Active
Active
Active
Active
Active
Active
High Torque
Active
Active
Active
Low Torque
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Disabled
High Imbalance
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
High Torque
Active
Active
Disabled
Low Torque
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
High Imbalance
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
High Torque
Active
Active
Disabled
Low Torque
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
High Imbalance
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
High Torque
Active
Active
Disabled
Low Torque
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Startup-Ignore
Threshold-Value
131
Table 1:
Version 3.0c
12/2014
Config
View
Active
Active
Disabled
High Imbalance
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
High Torque
Active
Active
Disabled
Low Torque
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
High Imbalance
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
High Torque
Active
Active
Disabled
Low Torque
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
High Imbalance
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
High Torque
Read-Only
Read-Only
Read-Only
Low Torque
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
High Imbalance
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
High Torque
Read-Only
Read-Only
Read-Only
Low Torque
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
High Imbalance
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Alarm-Limit
Fault-Limit
132
Version 3.0c
12/2014
Table 1:
Config
View
High Torque
Read-Only
Read-Only
Read-Only
Low Torque
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Active
Active
Active
Active
Active
Active
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Location
Active
Active
Disabled
Active
Active
Disabled
Communication State
Read-Only
Read-Only
Read-Only
Target IP Address
Active
Active
Disabled
RPC Version
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Communication Settings
Active
Active
Disabled
Detailed Settings
Active
Active
Active
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Set Time
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Active
Active
Active
Read-Only
Read-Only
Read-Only
Active
Active
Active
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Active
Active
Active
Active
Active
Active
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
133
Table 1:
Version 3.0c
12/2014
Config
View
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Active
Active
Disabled
Communications State
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Communication Settings
Active
Active
Disabled
Reestablishment Interval
Active
Active
Disabled
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Read-Only
Read-Only
Read-Only
Active
Active
Disabled
Active
Active
Disabled
Min Speed
Active
Active
Disabled
Max Speed
Active
Active
Disabled
Active
Active
Disabled
Drive Address
Active
Active
Disabled
Active
Active
Disabled
Bypass Contactor
Active
Active
Disabled
Active
Active
Disabled
Drive Configuration
134
Version 3.0c
12/2014
E.1
135
Version 3.0c
12/2014
3. Select Start > All Programs > Schneider Electric SCADAPack E > SCADAPack E Configurator. The
SCADAPack E Configurator opens (see Figure E.2).
136
Version 3.0c
12/2014
4. When SCADAPack E Configurator opens, select Open an existing RTU configuration file and click Finish. The
Open dialog box appears.
5. In the Open dialog box, navigate to the following folder on your computer:
On 32-bit Windows (x86): C:\Program Files\Schneider Electric\Realift Rod Pump\ConfigurationFiles
On 64-bit Windows (x64): C:\Program Files (x86)\Schneider Electric\Realift Rod Pump\ConfigurationFiles.
6. In the ConfigurationFiles folder, select CONFIGFILE.rtu and click Open.
7. In the tree control displayed on the left-hand side of the SCADAPack E Configurator main window, expand the
General folder and select Controller Status.
8. Click the Refresh button (
) in the toolbar.
9. On the Controller Status property page, verify that you have communication with the SCADAPack 535 E.
10. Select File > Write RTU Configuration. A message appears asking you to confirm that you want to write the
configuration to the RTU.
Figure E.3: Confirm Writing the Configuration to the RTU
11. Click Yes. A message is displayed, indicating the progress of writing the configuration to the SCADAPack
535 E.
137
Version 3.0c
12/2014
When SCADAPack E Configurator has completed writing the configuration to the SCADAPack 535 E, you are
asked to restart it (see Figure E.5).
Figure E.5: Restarting the RTU
13. Click OK. The SCADAPack 535 E is restarted. Once the SCADAPack 535 E has restarted.
The next step is reinstalling the application package file.
138
Version 3.0c
12/2014
E.2
2. Select Communication > Communication Settings. The DNP3 TCP Configuration dialog box appears.
3. In the DNP3 TCP Configuration dialog box, verify that IP address is set to 192.168.0.101, the factory default IP
address for the Realift Rod Pump.
4. In the toolbar, click the Refresh button (
).
5. On the Controller Status property page, verify that you have communication with the SCADAPack 535 E.
6. Select IEC 61131-3 > Write Application. The Write IEC 61131-3 Application to the RTU dialog box appears (see
Figure E.8).
Figure E.8: The Write IEC 61131-3 Application to the RTU Dialog Box
139
Version 3.0c
12/2014
7. In the Write IEC 61131-3 Application to the RTU dialog box, navigate to the following folder on your computer:
On 32-bit Windows (x86): C:\Program Files\Schneider Electric\Realift Rod Pump\ConfigurationFiles
On 64-bit Windows (x64): C:\Program Files (x86)\Schneider Electric\Realift Rod Pump\ConfigurationFiles.
8. In the ConfigurationFiles folder, select SCADAPack535E.I5P and click Open. A message is displayed,
indicating the progress of writing the application package file to the SCADAPack 535 E. When the SCADAPack
E Configurator has completed writing the configuration, a dialog box is displayed, indicating that the application
package file was successfully loaded onto the SCADAPack 535 E.
9. Click OK.
10. In the tree control displayed on the left-hand side of the SCADAPack E Configurator main window, expand the
Logic folder and select IEC 61131-3.
11. In the toolbar, click the Refresh button (
).
12. On the IEC 61131-3 property page, verify that both resources on the SCADAPack 535 E are running (see
Figure E.9).
Figure E.9: IEC 61131-3 Target
140
Version 3.0c
12/2014
141
142
Version 3.0c
12/2014