Modular SPU

Operating and Maintenance Manual

According to VdS Schadenverhtung GmbH, Anerkennungs-Nr S 4050001, 07 April 2005

Document code / revision: DOC0001718 B


Publishing date: 06 Mar 2013

Published by
Marioff Corporation Oy
2013 all rights reserved
Virnatie 3
01300 Vantaa
Finland
Tel. +358 (0)10 6880 000
Fax +358 (0)10 6880 010
http://www.marioff.com
In case of discrepancy between the original English document and the translated
document, the English text prevails.
All rights reserved. Marioff Corporation Oy reserves the right to change or modify the
information given in this document, including technical details, without notice.
Reproduction of any part of this document without the express written permission of
Marioff Corporation Oy is prohibited.
HI-FOG and Marioff are registered trademarks of Marioff Corporation Oy. Marioff is part
of UTC Climate, Controls and Security Systems, a unit of United Technologies Corp.
(NYSE:UTX), which provides high technology products and services to the building and
aerospace industries worldwide. More information on Marioff group companies, agents/
distributors and references can be found at www.marioff.com.

CAUTION
HI-FOG systems comprise mechanical components that employ high pressure for water
pressurization. HI-FOG system installation embraces high-pressure testing of discharge
tubing. Care must be taken to ensure that all relevant safety procedures are followed
during installation to the satisfaction of the authority having jurisdiction and that only
competent personnel, appropriately trained and certified, are permitted to install, test,
commission and service the system. Marioff group companies and their respective
affiliates, officers, employees and representatives shall have no liability whatsoever for the
compliance by third parties to the present manual or to any applicable safety procedures.

ii

DOC0001718 B

Table of Contents

Table of Contents
1. Introduction .................................................................................7
1.1 Modular design .................................................................7
1.2 Functionality......................................................................8
1.3 Installation.........................................................................8
1.4 More information...............................................................8
2. Warnings and cautions ..............................................................10
3. General MSPU description.........................................................12
3.1 Master and slave pump units............................................12
3.2 Tank unit ...........................................................................13
3.3 Filter unit ...........................................................................14
3.4 Starter Cabinet..................................................................14
4. Mechanical connections ............................................................18
4.1 Fastening pump units .......................................................18
4.2 Preparing tubes ................................................................18
4.3 Tightening torque for cutting ring tube connections..........18
4.4 Connecting master and slave pump units.........................19
5. Electrical connections................................................................24
5.1 Junction box cable connections........................................24
5.2 Starter Cabinet cable connections....................................24
6. Operation modes ........................................................................26
7. Starting and stopping.................................................................28
7.1 Automatic start..................................................................28
7.2 Manual local start..............................................................28
7.3 Stop after automatic and manual local start .....................28
7.4 Emergency start (remote) .................................................29
7.5 Stop after emergency start ...............................................29
8. Resetting......................................................................................30
9. Maintenance ................................................................................31
9.1 Check all valve positions ..................................................31
9.2 Check stand-by pressure and pump operation.................32
9.3 Check electric supply, test lamps .....................................32
9.4 Visually inspect pump unit and its fittings .........................33
9.5 Check pump oil levels.......................................................33
9.6 Check drive chains and flexible coupling..........................34
9.7 Check air pressure regulator and empty water lock .........35
9.8 Test run the unit................................................................35
9.9 Test units max pressure and flow ....................................36
9.10 Check control cabinet batteries and charger ..................38
9.11 Check settings of pressure and flow switches
and transducers .....................................................................38
9.12 Test unit in accordance with service instructions............38
9.13 Change pump oil.............................................................39
10. Troubleshooting........................................................................40
10.1 General faults .................................................................40

Marioff Corporation Oy

DOC0001718 B

iii

Modular SPU Operating and Maintenance Manual

10.2 Alarms.............................................................................41
A. APPENDIX - Spare parts..............................................................45
B. APPENDIX - Checking water filter................................................47

iv

DOC0001718 B

Marioff Corporation Oy

1. Introduction
This manual describes how to operate and maintain the modular HI-FOG Sprinkler
Pump Unit (MSPU) that is part of a VdS-approved HI-FOG system. This manual aims to
describe the MSPU at a general level; note that the illustrations or details in this document
may not reflect exactly the MSPU version supplied if there are customer-specific
modifications.
Any changes made to the supplied and installed system or its equipment are allowed only
with the written consent from Marioff Corporation Oy.

NOTICE! Always refer to project documentation for details of your installation.

1.1 Modular design


The modular HI-FOG Sprinkler Pump Unit (MSPU) is designed to supply high pressure
water to a HI-FOG water mist distribution system used for fire protection. It is used with
single-fluid, single-pipe type HI-FOG sprinkler systems that use water, in the form of a
fine mist, as the fire suppressant.
The modular design allows flexibility in construction: a large variety of different versions
and pump unit sizes can be built by using the standard modules. The basic modules are
pump modules PU2 and PU3, control cabinet, filter, and optionally break tanks and
reservoirs.
The basic features of the MSPU are:
Automatic starts, manual start, and remote start
Gravity-based (non-electric) water feed to the pump unit
Break water tank is not normally needed, but can be supplied on request
Possibility to check the pump unit max pressure and flow on periodic testing
The optional features of the MSPU are:
Water tank (standard tank size 2000 liters/529 US gallons)
External feed water pump
External feed water pump starter in the Starter Cabinet
Two electric supplies and automatic switchover function

Marioff Corporation Oy

DOC0001718 B

Modular SPU Operating and Maintenance Manual

Voltage options
60 Hz frequency
Soft starters
Connecting cables special lengths

1.2 Functionality
The MSPU comprises of pump modules which, upon activation, are started sequentially,
thus reducing the electric power peak loads. In stand-by position, the system pressure is
maintained at 25 bar (or other system-specific set value) by means of a stand-by pump.
The MSPU can be started automatically, manually, or remotely. The automatic start is
activated by flow or by low pressure. The manual start is activated from the Starter
Cabinet. The remote start can be included to allow activation by a release panel or a thirdparty signal.
A fire causes the heat-sensitive bulbs on one or more sprinklers to break. Alternatively,
section valves are opened and water starts to flow from the released spray heads. Pressure
switches generate a signal to start the MSPU when the pressure decreases. Also, the flow
monitor detects the flow and starts the MSPU.

1.3 Installation
The MSPU installation is instructed and described in project-specific documentation.
Contact Marioff if you have questions or concerns about the installation or need to get onsite help from an installation team.

NOTICE! HI-FOG system uses high pressure water which can be dangerous if
the system is not properly installed.

Service area
Reserve free space around the unit installation: at least 750 mm on all unit sides, 400 mm
above the unit and 800 mm in front of the Starter Cabinet doors (or the width of the
doors). This area needs to be kept available for service and maintenance work.

1.4 More information


Refer to the project-specific documentation as well as to the documents listed below for
more information.

DOC0001718 B

Marioff Corporation Oy

Marioff diagrams and drawings:


Hydraulic diagrams and parts lists for the supplied unit
Electric diagrams and parts lists for the supplied unit
Dimensional drawing for the supplied unit

Marioff Technical Data Sheets and Manuals:


DOC0001714 MSPU Overview
DOC0001715 MSPU02
DOC0001716 MSPU03
DOC0001717 MSPU04
DOC0001719 MSPU05
DOC0001720 MSPU06
DOC0001721 MSPU07
DOC0001722 MSPU08
DOC0001724 and TE2011 Tank Unit
TE9004 and TE9018 Filter Unit
TE1002 SPU Gearbox Chain and Coupling Change
K0008018 Safety valve sets for SPU and MSPU
DOC0002101 Marioff Water specification
P32010 Installation and Pre-Commissioning Manual Land Projects

Third-party documents:
High pressure plunger pump operating instructions
Stand-by pump operating and maintenance instructions
Fire Detection System operating instructions

Marioff Corporation Oy

DOC0001718 B

Modular SPU Operating and Maintenance Manual

2. Warnings and cautions


Cautions give information about possible system hazards. Warnings give information
about possible hazards for the users of the MSPU system.
Ensure that all mechanical and electrical assemblies and parts of the MSPU system are
used with care and inspected regularly. Ensure that the personnel using the system are
instructed in the proper use and care
aware of the performance limitations, and
aware and observe all warnings and cautions described in this manual.

Cautions
Water used with the HI-FOG system must be the equivalent of a potable supply. In all
cases the input water must be fed through a < 100 m filter and the chloride concentration
MUST not exceed 50 ppm (= 50 mg/l). Under no circumstances add suppression additives
to the stored water supply.
Only appropriately trained personnel are permitted to work on, test, and service the
MSPU, the sprinkler system, and its associated equipment. When in doubt, contact
Marioff representative.
Check, test, and service the MSPU in accordance with the instructions in this manual.

NOTICE! Failure to check, test, and service the MSPU in accordance with the
instructions given in this manual can jeopardize the reliable operation of the
system.

Only use spare parts that are manufactured, supplied, or recommended by Marioff.
If the MSPU is switched off for any reason, take adequate fire precautions, according to
your safety procedures, to cover the period that the MSPU is out of operation.

Warnings
The HI-FOG MSPU produces high-pressure water when operating. To avoid injury to
personnel and/or damage to equipment always follow the safety procedures described in
this manual and required by the authorities.

10

DOC0001718 B

Marioff Corporation Oy

NOTICE! Hazardous voltage will cause death or serious injury.

Only qualified personnel are permitted to perform electrical work on the MSPU. Check
local safety regulations.
Electrical cabinets may have several power supplies and voltages. Each power supply
must be isolated before starting electrical work.

Marioff Corporation Oy

DOC0001718 B

11

Modular SPU Operating and Maintenance Manual

3. General MSPU description


This chapter describes the MSPU parts and their functionality.

3.1 Master and slave pump units


The pump unit consists of a master unit, or of a master unit and a slave unit. The master
unit consists of the following main parts (see Figure 1 on page 13):
pump modules
The number of pump modules depends on the system size.
Each pump module consists of one 3-phase electric motor, two plunger pumps, and two
unloaders.
a pneumatic stand-by pump
pressure and flow indications
test connection and bypass outlet
The slave unit consists of the following main parts (see Figure 1 on page 13):
pump modules
connections to master pump unit

12

DOC0001718 B

Marioff Corporation Oy

High pressure
water outlet
Junction box

Electric motor
Pump
Water inlet

Unloader

Test valve

Stabilisation
valve

Test outlet and


bypass outlet
Flow meter
Stand-by pump

Figure 1. MSPU05: MSPU03 master and MSPU02 slave (used as an example)

3.2 Tank unit


The MSPU pump unit takes inlet water either from a water main supply or from a
reservoir. All water which is not needed by the water mist system is lead back to the
reservoir or to a drain. The size of the reservoir must be in accordance with the relevant
Marioff type approvals and with local rules.
Marioff can supply also a dedicated tank unit for water reservoir; this tank unit is a
modular unit built from 2000 liter tank modules. One tank module can also be used as a
water break tank to where unused water is circulated when there is no reservoir available
or not enough drain capacity.
The tank unit consists of the following main parts (see Figure 2 on page 14):
plastic water tanks
The number of tanks depends on the system size. In large combinations one tank acts as a
master tank and other tanks are slave tanks.
filter
piping: water inlet, water outlet, flushing line
overflow line and unloader line
Marioff Corporation Oy

DOC0001718 B

13

Modular SPU Operating and Maintenance Manual

Overflow line
Unloader line

Plastic tank

Filter

Water inlet

Water outlet and


flushing line

Figure 2. Tank unit assembly for 10m3 system (used as an example)

Tanks can be delivered with water level indicators: either electric level switches or
mechanic float valves. Always check project-specific documentation on tank unit
mechanical and electrical details.
For more information, see Technical Data Sheet DOC0001724.

3.3 Filter unit


The filter unit is used to purify water to an acceptable level before it reaches the pump
unit. The filter size depends on the number of pump modules, but the specification of
appropriate filtration level remains the same in all module arrangements.
For more information, see Technical Data Sheets TE9004, TE9018, and DOC0002101.
For filter maintenance, see Appendix B - Checking water filter.

3.4 Starter Cabinet


The Starter Cabinet is used to monitor, operate, and control the MSPU fire protection
system. It also indicates all operation and fault signals concerning the pump units and the
tank unit. The Starter Cabinet is installed near the pump unit.
Figure 3 and Figure 4 below show the MSPU05 Starter Cabinet as an example.
Arrangements vary per model, see the labels on lamps and switches.
For more information, see Technical Data Sheets of the installed pump unit.

14

DOC0001718 B

Marioff Corporation Oy

Figure 3. MSPU05 Starter Cabinet (used as an example)

The Starter Cabinet has the following manual operations and selections (numbers in
brackets correspond those in Figure 4 on page 17):
Manual start motor 15 (M1M5)
Pump Unit manual start (1)
Buzzer acknowledge (2)
Alarm reset (3)
Lamp test (4)
Voltage metering selection (5)
Pump Unit manual stop/system reset (6)
The Starter Cabinet has the following indications:
230VAC control voltage fault (7)
Battery charger fault (8)
Earth fault 24VDC (9)
Pressure switch PS-1/PS-2 fault (10)
Compressed air low pressure (11)
Out of water (12)
Sprinkler pump malfunction (13)
Inlet/outlet valve closed (14)
Circuit breaker released (15)
Pump Unit motor overload (16)
Control system on (17)

Marioff Corporation Oy

DOC0001718 B

15

Modular SPU Operating and Maintenance Manual

Pump Unit deactivated (18)


Motor M1.. M5 running
Main supply on (optional)
Emergency supply on (optional)
The Starter Cabinet has the following signals out for use by a third-party system:
Out of water
Sprinkler pump motor malfunction
Pump unit fault
24VDC control system on/off
Pump unit deactivated
Pump unit running
Stabilisation on
Pump unit flow
Line voltage fault
HI-FOG activated
Optional output signals (instead of Line voltage fault):
Main power supply fault
Emergency power supply fault

16

DOC0001718 B

Marioff Corporation Oy

15

12

17

18

13

M1

M2

M3

M4

3
M5

11

10

14

4
16

200

1800

1200

Figure 4. MSPU05 Starter Cabinet dimensions, operations, selections, and indications (used as an example)

Marioff Corporation Oy

DOC0001718 B

17

Modular SPU Operating and Maintenance Manual

4. Mechanical connections
This chapter describes how to connect the different MSPU parts. The master and slave
pump units are delivered as separate items that have to be connected when installing the
units. All needed parts are included in the delivery.
Note that the MSPU05 is used as an example in the instructions below. Always check the
details from project-specific documentation.

4.1 Fastening pump units


The pump units are bolted to the floor by using the fastening holes in the racks. The
distance between the pump unit racks is desinged to be 400 mm, but due to the modular
design can be modified. However, note the required service area (see chapter Installation
on page 8).

4.2 Preparing tubes


Bend and cut the tube to the desired shape and length, place the nuts, and pre-cut the
cutting ring connections. The tube preparation is described in detail in the document
P32010 Installation and Pre-Commissioning Manual Land Projects.

4.3 Tightening torque for cutting ring tube connections


Tighten the nuts with a wrench until resistance is felt, mark the position, and then
continue a turn over the mark. The tightening torque is described in detail in the
document P32010 Installation and Pre-Commissioning Manual Land Projects.

18

DOC0001718 B

Marioff Corporation Oy

4.4 Connecting master and slave pump units


Figure 5 below illustrates the six connection points.

3
2
1 high pressure line (38S ( 38x3) DIN2353
2 test outlet line (38S ( 38x3) DIN2353
3 water inlet pipe (DN80 DIN2642 FLANGE)

Figure 5. Connecting points of master and slave pump units (MSPU05 as an example)

Marioff Corporation Oy

DOC0001718 B

19

Modular SPU Operating and Maintenance Manual

To connect the high pressure line


See Figure 6 below.

Figure 6. Connecting the high pressure line between MSPU05 master pump unit MSPU03 (item A in the figure) and slave
pump unit MSPU02 (B)

Step 1. Prepare the high pressure line.


Follow the instructions in the document P32010 Installation and Pre-Commissioning
Manual Land Projects.

Step 2. Connect the high pressure line to the master pump and tighten the
connection.
Step 3. Connect the high pressure line to the slave pump and tighten the
connection.
Step 4. Attach and tighten the clamp on the slave pump connection of the high
pressure line.

20

DOC0001718 B

Marioff Corporation Oy

To connect the test outlet line


See Figure 7 below.

Figure 7. Connecting the test outlet line and water inlet line between MSPU05 master pump unit MSPU03 (A) and slave
pump unit MSPU02 (B)

Step 1. Prepare the test outlet line


Follow the instructions in the document P32010 Installation and Pre-Commissioning
Manual Land Projects.

Step 2. Connect the test outlet line to the master pump and tighten the
connection.
Step 3. Connect the test outlet line to the slave pump and tighten the
connection.

Marioff Corporation Oy

DOC0001718 B

21

Modular SPU Operating and Maintenance Manual

To connect the water inlet line


See Figure 8 below.

Step 1. Connect the water inlet line to the master pump.


Remember to place the seal between the flange connection.

A
B

Bolt

Flange

Seal

Nut

Figure 8. Connecting the water inlet between MSPU05 master pump unit MSPU03 (A) and slave pump unit MSPU02 (B)

Step 2. Tighten the flange connection.


Tighten the bolts evenly so that the flange fits in smoothly. If you tighten one bolt all the
way, the flange will not fit in smooth on all sides. Increase torque gradually, until the
correct torque is reached. See Figure 9 on page 23.

22

DOC0001718 B

Marioff Corporation Oy

1
3

Figure 9. Tightening order of the bolts in the flange connection

Step 3. Connect the water inlet line to the slave pump.


Remember to place the seal between the flange connection.

Step 4. Tighten the flange connection.


Tighten the bolts evenly so that the flange fits in smoothly. If you tighten one bolt all the
way, the flange will not fit in smooth on all sides. Increase torque gradually, until the
correct torque is reached. See Figure 9 above.

Marioff Corporation Oy

DOC0001718 B

23

Modular SPU Operating and Maintenance Manual

5. Electrical connections
This chapter describes the main electrical connections of the MSPU. For detailed
description of the electrical connections, see the Connection Diagram of the supplied unit.
The length of the standard cables is 10 m; special lenghts are available per request.
Note that all external cabling needs to be ordered separately.

5.1 Junction box cable connections


The cable connections of the Junction box include
pressure and flow switch signals,
the valve monitoring and control signals, and
the connection to the Starter Cabinet.
The Junction box connections are illustrated in Figure 10 on page 24.

Figure 10. Junction box cable connections (MSPU05, as an example)

5.2 Starter Cabinet cable connections


The Starter Cabinet has the following connections:

24

DOC0001718 B

Marioff Corporation Oy

Main supply
Motors
Air compressor
Junction box (pressure and flow switch signals, valve monitoring and control)
Water tank (low level switch)
Alarm panel signals, which are at least the following:
HI-FOG activated, line voltage fault, pump unit fault.
The cable entries for external cabling are illustrated in Figure 11 below.

2 3

1 Main supply connection


2 Motor cables, sensor and switch signals
3 Junction box cables, sensor and switch signals

Figure 11. Starter Cabinet external cabling entries

Marioff Corporation Oy

DOC0001718 B

25

Modular SPU Operating and Maintenance Manual

6. Operation modes
This chapter describes the various modes of the MSPU: stand-by, operating, off,
deactivated, and stabilisation.

Stand-by
Stand-by is the normal state of the system when it is on. In normal use the system MUST
always be in stand-by. The following conditions apply for the stand-by mode:
the MSPU is connected to the electric supply and the main power switch is on
working air is supplied to the stand-by pump and the pump is operational
the system pressure is within the set limits (25 bar, or system-specific)
the control system is operational
the piping and connections are sound and tight (for more information, see document
P32010 Installation and Pre-Commissioning Manual Land Projects)
After stabilisation the system automatically returns to the stand-by mode.

Operating
Operating is when the system is activated and high-pressure water is fed to the HI-FOG
system forming the HI-FOG mist discharge. The pump unit will maintain the required
pressure and flow in the system until a stop signal is given or before the pump runs out of
water.
When the MSPU is activated, the pump modules automatically start in sequence, with a
few seconds delay between each start, in order to reduce electric peak loads.
If the flow of water required is less than the output of the unit, the unloader valves open
and route extra water back to the tank unit or drain.
The low level switch in the break tank or a pressure switch in the feed water line will
prevent the unit from starting when there is not enough water, or will stop the motors
from running dry. When the redundancy source of water (if applicable) has been
connected and/or the water break tank has been refilled, the pumps restart automatically.

Off
Off mode is when the system is shut down for maintenance or repair.

26

DOC0001718 B

Marioff Corporation Oy

Deactivated
Deactivated state is when the pump unit has been either manually switched off from the
main switch or the inlet or outlet water valve has been closed.

Stabilisation
Stabilisation is needed for the system to return to stand-by mode again after a discharge.
Stabilisation is automatic; it is started when pressing the system reset button (pump unit
manual stop/system reset, item 6 in Figure 4 on page 17) and it takes from about 30
seconds up to a few minutes. During stabilisation the system pressure drops to the standby level (25 bars by default).

Marioff Corporation Oy

DOC0001718 B

27

Modular SPU Operating and Maintenance Manual

7. Starting and stopping


This chapter describes the starting and stopping functions of the MSPU. There are three
options for the system start: automatic start, emergency start, and manual local start.

NOTICE! Before initiating a local manual start, check that no fault alarms are on
and water is available. Running the system without water may damage the pumps.
Starting the pump with the manual switches in the Starter Cabinet overrides the
water low level interlocking in automatic and emergency start.

NOTICE! Stopping the pump unit is normally done by the fire officer or fire
protection responsible.

7.1 Automatic start


The MSPU starts automatically if the water pressure drops below a preset value (typically
17 bar) for more than preset time (typically 10 seconds) or if it detects a water flow for 10
seconds in the system.
When the MSPU is activated, the pump modules automatically start in sequence, with a
few seconds delay between each start, in order to reduce electric peak loads.

7.2 Manual local start


To manually start the MSPU, press the Pump unit manual start button in the Starter
Cabinet.

7.3 Stop after automatic and manual local start


Before stopping the discharge, make sure that
there is no fire, and
any released sprinklers or spray heads are isolated and that the section valves are closed
so that there is no flow in the HI-FOG system.

28

DOC0001718 B

Marioff Corporation Oy

To stop the MSPU after automatic and manual local start


Step 1. Stop the flow in the system.
Close the section valve in the discharged area.

Step 2. Check in the pressure gauge that the system pressure is at 130 140
bar.
Step 3. Press Pump Unit manual stop/system reset button on the Starter
Cabinet.
All motors are turned off and the stabilisation valve opens. The Pump Unit manual stop/
system reset signal light is on during stabilisation.

Step 4. Wait for the stabilisation to complete.


When the stabilisation is complete, the Pump Unit manual stop/system reset signal
light goes off.
The stopping sequence above can also be applied to situations when an unintentional
system discharge has occured.

NOTICE! Standard systems do not reset unless the system pressure has reached
130 bar. The pump unit must be run until the pressure has risen above130 bar
before resetting the system.

7.4 Emergency start (remote)


To start the MSPU remotely, press the EMERGENCY START button on the remote
location. Note that in standard MSPU systems the button will stay down after it has been
pressed.

7.5 Stop after emergency start


To stop the MSPU, press the same EMERGENCY START button on the remote location
again.
To reset the MSPU, press the Pump Unit manual stop/system reset button on the Starter
Cabinet.

Marioff Corporation Oy

DOC0001718 B

29

Modular SPU Operating and Maintenance Manual

8. Resetting
A reset after MSPU start and stop is always needed for the system to return to the stand-by
mode. Resetting MSPU is an automatic operation sequence and is started by pressing the
Pump Unit manual stop/system reset button in the Starter Cabinet. This is described in
chapter Stop after automatic and manual local start on page 28.
Before the whole system can be reset, all flow in the system must be stopped; if a sprinkler
has released, the section valve must be closed.
In system reset, first the stabilisation valve opens and the pressure in the system drops
down to a preset value (typically 22 bar). Then the stabilisation valve closes and the standby pump raises the stand-by pressure to the required 25 bar (or other system-specific set
value).
Stabilisation takes from about 30 seconds up to a few minutes, during which time an
automatic restart is prevented. During stabilisation the emergency start and manual local
start is possible.
The Pump Unit manual stop/system reset signal light is on when the system pressure
drops from 130 bar to 22 bar. When the signal light goes off, system has returned to standby mode.
Reset possible alarms by pressing the Alarm reset button in the Starter Cabinet.

NOTICE! Standard systems do not reset unless the system pressure has reached
130 bar. The pump unit must be run until the pressure has risen above130 bar
before resetting the system.

30

DOC0001718 B

Marioff Corporation Oy

9. Maintenance
This chapter describes the minimum requirements for maintenance routines of the
MSPU. Always check project-specific documentation for MSPU and system level
maintenance routines and their frequencies.
The table below displays the frequency of maintenance routines and the chapters after the
table describe the actual tasks. In addition to the information in Table 1, note the
following:
Other maintenance frequencies may be specified in local laws and regulations or in
customer-specific system specifications.
Refer to the respective third-party manufacturers instructions (as delivered with the
system) for more information.
Table 1: Maintenance routines for MSPU
Every 5
years

Chapter

Action

Weekly

Monthly

Annually

9.1

Check all valve positions

9.2

Check stand-by pressure and pump

9.3

Check electric supply, test lamps

9.4

Visually inspect unit and its fittings

9.5

Check pump oil levels

9.6

Check drive chains and flexible coupling

9.7

Check air pressure regulator and empty water


lock

9.8

Test run the unit

9.9

Test unit flow capacity

9.10

Check pump unit batteries and charger

9.11

Check settings of pressure and flow switches


and the transducers

9.12

Test unit in accordance with service instructions

9.13

Change pump oil (every 2 years or 200 hours)

*other frequencies may be specified in local laws and regulations or in the system-specific
instructions

9.1 Check all valve positions


In stand-by and operating modes the valves must be in the following positions. Numbers
in brackets correspond those in MSPU05 valve locations on page 32.

Marioff Corporation Oy

DOC0001718 B

31

Modular SPU Operating and Maintenance Manual

Open valves
outlet valve to the sprinkler system (1)
water inlet valve (2)
air inlet valve to the stand-by pump (3)

Closed valves
test valve (4)

1
3

2
4

Figure 12. MSPU05 valve locations

9.2 Check stand-by pressure and pump operation


Check that the stand-by pressure in the system is set to the correct level (25 bar by default,
if not otherwise stated).
Check that the stand-by pump does not start running too often; for example once a day is
too often. For more information, see chapter Stand-by pump striking frequently on
page 41. A faulty stand-by pump must be replaced with a new one.
For maintenance and overhaul refer to the third-party manufacturers operating and
maintenance instructions.

9.3 Check electric supply, test lamps


Check the Line voltage meter. When there are two electric feeds (optional feature), a light
indicates which feed is in use and thus shown in the Line voltage meter.

32

DOC0001718 B

Marioff Corporation Oy

Press the Lamp test button in the Starter Cabinet. All signal lights in the Starter Cabinet
should be lit (and the buzzer should ring). Change any faulty light bulbs.

9.4 Visually inspect pump unit and its fittings


Check that there is no water or air leaking from the system.
Check that all fittings are tight. Report all abnormal wear and tear, and damage.

9.5 Check pump oil levels


The optimal oil level is at the mid-level of the sight glass. If it is below this level, add more
oil. See Figure 13 below.

Figure 13. Check the oil level of the pumps

The oil color should be clear golden brown. If the oil is dirty, cloudy, or grey when the unit
is in the stand-by mode, change the oil. See the third-party manufacturers pump
operating instructions.

NOTICE! The oil appears cloudy when the unit is in the operation mode.

Marioff Corporation Oy

DOC0001718 B

33

Modular SPU Operating and Maintenance Manual

9.6 Check drive chains and flexible coupling

NOTICE! Switch the unit off before checking the drive chains and coupling.
Turn the main switch off and secure it before removing the cover.

The drive chains are self-lubricated, which means that they do not need to be greased. To
indicate this, there is a notification sticker attached to the gearbox with the following text:
Notice! Do not use grease. This roller chain is self-lubricated.

However, if the drive chains are not maintenance-free (in older pump units) and there is
no notification sticker, the drive chains must be well greased. If the chain is dry or rusty,
grease the chain by using Shell Kuggfett or an equivalent molybdenum-graphite based
grease with heat resistance up to +200C and good adhesion capability.
Check the condition of the flexible couplings. A slight amount of wear is normal - if any
signs of excessive wearing are shown, change the coupling. See Figure 14.

Figure 14. Check the drive chains and the flexible coupling

34

DOC0001718 B

Marioff Corporation Oy

Changing the chain and coupling


See Technical data sheet TE1002.

9.7 Check air pressure regulator and empty water lock


Check for leakages.
Make sure that the stand-by pressure is maintained at 25 bar (or other system-specific set
value).

9.8 Test run the unit


NOTICE! Before initiating a local manual start, make sure that there is water and
that no fault alarms are on. Running the system without water may damage the
pumps. Starting the pump with the manual switches in the Starter Cabinet
overrides the water low level interlocking in automatic and emergency start.
NOTICE! Make sure that the unit starts to supply water at full working pressure
after a short delay. Make sure that all motors and pumps are running.

To test run the unit


Step 1. Close the water outlet valve.
Step 2. Start the pump unit locally, remotely, or automatically.
Vary the way of starting to ensure that all starting modes work.

Step 3. When testing the automatic start locally, note the following.
The low pressure start is tested by closing the air supply to the stand-by pump and fully
opening the test valve.
The flow switch start is tested by slowly opening the test valve so the pressure does not
drop below 17 bar (or the set default value). See Figure 15.

Marioff Corporation Oy

DOC0001718 B

35

Modular SPU Operating and Maintenance Manual

Figure 15. MSPU05 test valve (1) and air inlet valve (2) locations

Step 4. Close the test valve if it has been opened for testing.
Step 5. Stop the unit by pressing the Pump Unit manual stop/system reset
button on the Starter Cabinet.
Step 6. Open the water outlet valve if has been closed for testing.
Step 7. Check that the pressure in the system returns to the 25 bar stand-by
pressure.
If the water outlet valve is closed, the stabilisation takes only seconds.

Step 8. Check that the whole system is reset and in stand-by mode.

9.9 Test units max pressure and flow


The pump units maximum output pressure and maximum flow must be periodically
tested (monthly). The pressure can be read from the pump units pressure gauge. The flow
can be read from the pump units integral flow meter that is installed to the test outlet.

36

DOC0001718 B

Marioff Corporation Oy

To test the units max pressure and flow

NOTICE! The maximum flow is tested per one motor at a time.

Step 1. Close the test valve by lifting the lever to upright position.

Test valve lever up, valve closed

Step 2. Start motor 1 manually by turning the motors switch to position 1.

Step 3. Check from the pressure gauge that the pressure is at 140 bar.

Pressure gauge

Step 4. Open the test valve by lowering the test valve lever.

Marioff Corporation Oy

DOC0001718 B

37

Modular SPU Operating and Maintenance Manual

Test valve lever down, valve open

Step 5. Read the maximum flow value from the flow meter.
The nominal flow output is 97,4 liters per one minute per one motor.

Step 6. Stop motor 1 by turning the motors switch to position A.

Step 7. Repeat steps 1-6 to other motors.

9.10 Check control cabinet batteries and charger


Check that the charger output voltage is 27.3 27.7 V at the battery.
Check the battery capacity with a suitable charge condition meter.
The batteries must be replaced every five (5) years, or more often if the battery is faulty, or
the unit is subjected to vibration, large temperature variations, or other severe
environmental conditions. Note that especially high ambient temperature reduces the
battery life time.

9.11 Check settings of pressure and flow switches and transducers


Check the setting values of pressure switches, transducers, and flow switch. If the
switching points have changed regarding the set point, adjust the point to original.

9.12 Test unit in accordance with service instructions


It is recommended that testing is carried out by a Marioff authorised service engineer.
Contact Marioff for more information.

38

DOC0001718 B

Marioff Corporation Oy

9.13 Change pump oil


With new systems the initial oil must be changed after the first 50 running hours (or 2
years), whichever comes first. After the initial oil change, the pump oil must be changed
every two (2) years or after 200 running hours, whichever comes first. See Figure 16 on
page 39. See also third-party manufacturers pump operating instructions.

Figure 16. Change pump oil: the locations of the oil fill and oil drain plugs

Use an ISO VG 220 or SAE 90 class gear oil. Oil quantity is 0,9 litres per pump. See the list
below for pump oil recommendations:
ARAL: Getriebel EP 85W-90, Degol BG 220
BP: Energear 90, Energol GR-XP 220
CASTROL: EP 90, ALPHA SP 220, ALPHA MW 220
ESSO: GEAR OIL GX 85W-90, GEAR OIL GP-D 85W-90
SPARTAN EP 220
Mobilube GX 85W-90-A
Mobilgear 630
Shell SPIRAX GX SAE 80W-90
NESTE GEAR EP 80W-90

Marioff Corporation Oy

DOC0001718 B

39

Modular SPU Operating and Maintenance Manual

10. Troubleshooting
This chapter lists the possible fault situations and their remedies. If the problem you are
facing is not listed here, contact Marioff immediately.
Always when contacting Marioff in troubleshooting situations, have the following
information available:
the project number of the installed system
the serial number of the pump unit
detailed description of the fault situation (what was done before the fault situation
occured and what happened during the fault situation)

10.1 General faults


This chapter lists the possible general MSPU faults.

10.1.1 Unit will not start


Possible reason: No electric supply.
Solution: Check if the main fuses in the main switchboard have blown. Check if the
Starter Cabinet main switch is open or the main circuit breaker has released.
Possible reason: No control voltage.
Solution: Connect supply. Check control voltage fuse of auxiliary voltage transformer.
Possible reason: No water.
Solution: Ensure feed water availability.
Possible reason: Stabilisation phase is on (Pump Unit manual stop/system reset light on
the Starter Cabinet is on).
Solution: Wait for completion of stabilisation phase and/or press the Pump unit manual
start button on the Starter Cabinet to start the unit.

10.1.2 Unit will not stop


Possible reason: Pressure has not exceeded 130 bar in the system and the emergency
start is still activated.
Solution: Run the unit until the pressure reaches 130 140 bar and/or deactivate
emergency start.

10.1.3 Unit starts unintentionally


Possible reason: Pressure switch is faulty or incorrectly adjusted.

40

DOC0001718 B

Marioff Corporation Oy

Solution: Adjust or replace pressure switch. Contact Marioff.


Possible reason: Flow switch is faulty or incorrectly adjusted.
Solution: Adjust or replace flow switch. Contact Marioff.
Possible reason: False start signal.
Solution: Check system wiring and signals.
Possible reason: System pressure drops due to system leakage or stand-by pump
problem.
Solution: Ensure system is tight. Check air supply to stand-by pump. Check stand-by
pump, replace if faulty.

10.1.4 Stabilisation phase not completed


The stabilisation will not start before the system pressure has reached 130 bar. The pump
unit must be run until the pressure has risen abo 130 bar before resetting the system is
possible.
Possible reason: Pressure switch is faulty or incorrectly adjusted.
Solution: Adjust or replace pressure switch. Contact Marioff.
Possible reason: Stabilisation valve is faulty.
Solution: Replace valve.

10.1.5 Stand-by pump striking frequently


Possible reason: Small leakage in the system.
Solution: Ensure system is tight.
Possible reason: Stand-by pump is faulty.
Solution: Replace stand-by pump.

10.2 Alarms
This chapter lists the MSPU system alarms.

10.2.1 Battery charger fault


Possible reason: No power supply to the charger unit. The fuse F13 is released and
causes the Circuit breaker released alarm.
Solution: Reconnect supply.
Possible reason: Charger is faulty.
Solution: Replace charger.

Marioff Corporation Oy

DOC0001718 B

41

Modular SPU Operating and Maintenance Manual

10.2.2 230VAC control voltage fault


Possible reason: No voltage in transformer T 0.3.
Solution: Check power supply and fuse F0.3.
Possible reason: Transformer is faulty.
Solution: Replace transformer.

10.2.3 Earth fault (24VDC)


Possible reason: + or - of the 24VDC control voltage in contact with earth (ground).
Solution: Find the contact point (for example, by opening fuses and disconnecting
panels) that causes the earth fault and rectify.

10.2.4 Circuit breaker released


Possible reason: Overload or short circuit.
Solution: If problem rectified or reason not found: switch on open/close.
If problem persists, contact Marioff.

10.2.5 Out of water


Possible reason: Water in water tank below low level or feed water pressure low in unit
without tank.
Solution: Make sure there is a feed water supply to water tank. Check that the water inlet
valve is open.
Possible reason: Tank low level switch faulty or stuck; cable fault.
Solution: Rectify or replace.

10.2.6 Pressure switch PS1/PS2 fault


Possible reason: Cable fault. Cable monitoring relay fault.
Solution: Check and replace cable if faulty. Check and replace monitor if faulty.

10.2.7 Compressed air low pressure fault


Possible reason: Compressor fault.
Solution: Check compressor; replace if faulty.
Check compressed air supply. If supply in order, check pressure switch and cables.

42

DOC0001718 B

Marioff Corporation Oy

10.2.8 Sprinkler pump malfunction


Possible reason: If one or more motors do not start, either the motor or the pump is not
functioning.
Solution: Check motor circuit breaker and control circuit breaker.

10.2.9 Inlet/outlet valve closed


Possible reason: The valve is not fully open, thus it sets an alarm.
Solution: Check that both valves are fully open.

10.2.10 Pump unit motor overload


Possible reason: A motor is overloaded.
Solution: Reset Thermal overload relay.
If problem persists, contact Marioff.

10.2.11 Pump unit fault


This fault is a signal to a third-party system. It is a common alarm set in result of any of
the alarms above.
Possible reason: Common MSPU alarm given.
Solution: Check the alarm in the Starter Cabinet and follow the appropriate instructions.

10.2.12 Pump unit deactivated


Possible reason: The main switch has been set to off or inlet/outlet valve has been closed.
Solution: Check that the main switch is set to on and that the inlet/outlet valves are open.

10.2.13 Line voltage fault


This fault is a signal to a third-party system.
Possible reason: Main supply voltage fault.
Solution: Check the system for low voltage, excess voltage, or asymmetric phases. Check
phase monitor relay K0.5.

10.2.14 Line voltage fault (with two electric feeds OPTIONAL)


This fault is a signal to a third-party system. It is a common alarm set in result of either
the Main power supply fault or Emergency power supply fault.
Possible reason: Main or emergency supply voltage fault.

Marioff Corporation Oy

DOC0001718 B

43

Modular SPU Operating and Maintenance Manual

Solution: Check the system for low voltage, excess voltage, or asymmetric phases. Check
phase monitor relay K0.5.

10.2.15 Other faults


Possible reason: Reason not found.
Solution: Contact Marioff.
Note that some faults are automatically remedied and the fault information is lost. In
some cases the faults are sent to a third-party system before the automatic remedy takes
place and possibly the fault alarm is visible in the third-party system but not in the MSPU
anymore. In those events the third-party system needs to be checked according to the
manufacturers instructions.

44

DOC0001718 B

Marioff Corporation Oy

A. Appendix - Spare parts


See table below for the available MSPU spare parts.
Parts not listed here are available upon request. Contact Marioff for more information.

Description

Type Code

Stock Code

Pump

NP25/41-140 left

E02050

Pump

NP25/50-140 left

E02055

Seal set for pump models NP25/50 and


NP25/41

G40130.1

Pump valve kit for pump models NP25/


50 and NP25/41

Manuf. ref. 14.0397

G40135

Pump oil

EP SAE80W-90

L53005

Unloader

UL262/2

D51023

Repair kit for unloader UL262/2

Manuf. ref. 14.0554

G40011

Electric motor

See nameplate

Voltage, frequency, power

Drive chain (self-lubricated)

10 B-2 L42 5/8

E04097.1

Drive clutch (green)

42/64 SH Clutch

E04019

Drive chain spare part set*

V31161 (for motor type 160L)


V31181 (for motor type 180L)

Pump support sleeve**

M12080

Pressure switch (stabilisation)

PN3001 0-250 bar

M23064.A

Pressure switch (start signal)

PK40

M23014

Pressure switch

PEV-1/4-B-OD

M23005

Flow monitor

SID10ADBFPKG/ US-100-IPF

M21012.1

Flow monitor

HP756B-030

M02000

Pressure gauge

213.53.63.250B/P ALA

M01022

Stand-by pump Trojan

Trojan type-J, 11:1

E40040

Seal set for Trojan stand-by pump

10108KP TROJAN-J AIR SIDE

G40090

10138KH/11 TROJAN-J WET

G40095

SVM 12-ANN-S12/12-10-0

D01535

Stabilisation valve NS-12


Repair kit for stabilisation valve NS-12***

V11070.A

Seal set for stabilisation valve NS-12***

V10101.A

Air regulator unit

FRC-1/4

E41015

Safety valve

VS200/180-60.5115.18

D-0002599

Marioff Corporation Oy

DOC0001718 B

45

Safety valve set****

V-0002692 (for MSPU01-02)


V-0002697 (for MSPU03)

Electric spare parts (such as contactors,


circuit breakers, relays etc.)*****

* Drive chain spare part sets include clutch flex element, clutch, roller chain, sprocket
wheel and other needed parts.
**You need 4 pieces of pump support sleeves to pull the pump out when replacing the
drive chain. Pump support sleeves are not included in drive chain spare part sets V31161
and V31181.
***See Marioff Spare part and maintenance drawing DMOVSE000862.
****See Marioff Technical data sheet K0008018.
*****Electrical components may vary considerably depending on the project. See projectspecific part list for electric spare parts.

46

DOC0001718 B

Marioff Corporation Oy

B. Appendix - Checking water filter


Follow the instructions below to check the water filter. Check the filter annually and
replace if it is dirty, rusty or damaged. Always replace the filter after a fire accident.

Bleeding screw
Water outlet
Filter cover

Filter cartridge

Water inlet

Drain plugs

Figure 17. Pump unit filter parts and bottom view

To check the water filter


Step 1. Close the water inlet valve.
Step 2. Carefully open the drain plugs in the filter bottom, relieve possible
excess pressure and allow water to drain out. See Figure 18.
Use a 19 mm socket.

Figure 18. Open the drain plugs

Marioff Corporation Oy

DOC0001718 B

47

Step 3. Open the filter cover by unscrewing the screws holding the lid in place.
Step 4. Pull out the filter cartridge and check it visually.
Change the cartridge if contaminated.

Step 5. Check the bypass valve.


The filter is equipped with a bypass valve, which allows the feed water flow even if the
flow through the filter cartridge would be prevented.
The bypass valve must be closed. If the valve is closed, the upper extension spring is
around the guide sleeve (see Figure 19.). If this is not the case (the bypass valve is
open), the valve must be reset. For instructions, see To reset the bypass valve on
page 49. Then continue to Step 6.

Figure 19. Water filters bypass valve in the cover

Step 6. Reinstall or replace the filter cartridge.


Step 7. Close the filter drain plugs.
Step 8. Close the filter cover and tighten it with the screws holding the lid in
place.
Step 9. When filling the unit via the filter, loose the air bleeding screw located
on top of the filter (see Figure 20.) to bleed air from the filter.
Use 8 mm Allen key.

48

DOC0001718 B

Marioff Corporation Oy

Figure 20. Open the air bleeding screw

Step 10. Carefully open the water inlet valve until water comes out from the
water filter bleeding screw.
Step 11. After filling the unit, tighten the air bleeding screw.

To reset the bypass valve

Figure 21. Resetting the bypass valve

Marioff Corporation Oy

DOC0001718 B

49

Step 1. Remove the locking wire from bypass screws (see Figure 22.).

Figure 22. Remove the locking wire

Step 2. Loosen the bypass screws (see Figure 23.).


NOTE: When loosening the bypass screws, the screw may pop up because of the spring
load when it has been screwed open. Hold a cloth in front of the screw to avoid hurting
yourself when opening the screw..

Figure 23. Open the bypass screws

Step 3. Remove the upper extension spring (see Figure 24.).


Step 4. Tighten the bypass screws (see Figure 24.).

Figure 24. Remove the upper extension spring and tighten the bypass screw

50

DOC0001718 B

Marioff Corporation Oy

Step 5. Install the locking wire (see Figure 25.).


Step 6. Reinstall the upper extension spring around the upper guide sleeve
(see Figure 25.).

Figure 25. Install the locking wire and upper extension spring

Marioff Corporation Oy

DOC0001718 B

51

52

DOC0001718 B

Marioff Corporation Oy

Protecting people, property and business from fire

Information on Marioff group companies, agents/distributors and


references can be found at www.marioff.com.

Head Office
Marioff Corporation Oy

Marioff Corporation Oy reserves the right to change or modify the


information given in this document, including technical details, without
notice. HI-FOG and Marioff are registered trademarks of Marioff Corporation Oy. Marioff is a part of UTC Climate,
Controls and Security Systems, a unit of United Technologies Corp. (NYSE:UTX).