Sei sulla pagina 1di 64

CP RC

User Manual

CP RC User Manual

Manual Version: CPRC.AE.1


OMICRON electronics GmbH 2011. All rights reserved.
This manual is a publication of OMICRON electronics GmbH.
All rights including translation reserved. Reproduction of any kind, for example, photocopying,
microfilming, optical character recognition and/or storage in electronic data processing systems,
requires the explicit consent of OMICRON electronics GmbH. Reprinting, wholly or in part, is not
permitted.
The product information, specifications, and technical data embodied in this manual represent the
technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this manual is useful, accurate and
entirely reliable. However, OMICRON electronics GmbH does not assume responsibility for any
inaccuracies which may be present.
The user is responsible for every application that makes use of an OMICRON product.
OMICRON electronics GmbH translates this manual from the source language English into a number
of other languages. Any translation of this manual is done for local requirements, and in the event of a
dispute between the English and a non-English version, the English version of this manual shall govern.

Contents

Contents
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Safety Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Conventions and Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Safety Rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Operating the Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Orderly Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
1.1
1.2
1.3
1.4

Designated Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
CP TR8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
CP CR4 and CP CR6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CP RC Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2.1
2.2
2.3

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Compensation Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Measurement Setups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.3.1
2.3.2
2.3.3
2.3.4
2.3.5
2.3.6
2.3.7

2.4

Setup Version A: 8 mH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Version B: 4.44 mH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Version C: 3.43 mH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Version D: 2.67 mH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Version E: 1.85 mH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Setup Version F: 1.60 mH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Setup Version G: 1.26 mH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

18
20
22
24
26
28
30

Test Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.4.1 Test Settings for HV Resonance Test System . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
3.1
3.2
3.3

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Measurement of the Leakage Reactance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.3.1 Theoretical Background to Calibration of Voltage Measurement . . . . . . . . . . . . 42

3.4

Finding the Setup for the High-Voltage Test . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

CP RC User Manual

3.4.1 Preparation of the Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44


3.4.2 Determination of the Capacitance of the Test Setup. . . . . . . . . . . . . . . . . . . . . . 44
3.4.3 Select the Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

3.5

Performing the HV Test Without Second VT . . . . . . . . . . . . . . . . . . . . . . . . . . . 48


3.5.1 Test Settings for the High-Voltage Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3.5.2 Determine the Resonance Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3.5.3 Conducting the Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

3.6

Performing the HV Test With Second VT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53


3.6.1 Test Settings for the High-Voltage Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.6.2 Determine the Resonance Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3.6.3 Conducting the Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
4.1
4.2
4.3
4.4
4.5

Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Mechanical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Environmental Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
CE Conformity and Safety Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Contact Information / Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . 61


Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Using This Manual

Using This Manual


This User Manual provides information on how to use the CP RC Test Set
safely, properly and efficiently. The CP RC User Manual contains important
safety instructions for working with the CP TR8 and CP CR4/CP CR6, and gets
you familiar with operating the CP RC Test Set. Following the instructions in this
User Manual will help you to prevent danger, repair costs and possible down
time due to incorrect operation.
The CP RC User Manual always has to be available at the site where the CP RC
Test Set is used. It must be read and observed by all users of the CP RC Test
Set.
Reading the CP RC User Manual alone does not release you from the duty of
complying with all national and international safety regulations relevant to
working with the CPC 100, and CP RC. The regulation EN 50191 "Erection and
Operation of Electrical Test Equipment" as well as all the applicable regulations
for accident prevention in the country and at the site of operation has to be
fulfilled.

Safety Standards
Working on high-voltage power equipment can be extremely dangerous.
Measuring using the CP RC must be carried out only by qualified, skilled, and
authorized personnel. Before starting work, clearly establish the responsibilities.
Personnel receiving training, instructions, directions, or education on the CP RC
must be under constant supervision of an experienced operator while working
on the high-voltage power equipment.
Measuring with the CP RC must comply with the relevant national and
international safety standards:

EN 50191 (VDE 0104) "Erection and Operation of Electrical Test Equipment"

EN 50110-1 (VDE 0105 Part 100) "Operation of Electrical Installations"

IEEE 510 "IEEE Recommended Practices for Safety in High-Voltage and


High-Power Testing"

Moreover, observe all applicable regulations for accident prevention in the


country and at the site of operation.

CP RC User Manual

Conventions and Symbols Used


In this manual, the following symbols indicate paragraphs with special safetyrelevant meaning:
Symbol

Description
Caution: Equipment damage or loss of data possible

Warning: Personal injury or death of the operating staff or


severe damage to objects possible

Related Documents
The following documents complete the information covered in the CP RC User
Manual:

Title

Description

CPC 100 User Manual

Contains information on how to use


the CPC 100 test system and
relevant safety instructions.

CPC 100 Reference Manual

Contains detailed hardware and


software information on the CPC 100
including relevant safety instructions.

Safety Rules

Safety Rules
Before operating the CP RC, please carefully read the following safety
instructions. It is not recommended to use the CP RC without understanding the
information in this manual. The CP RC should only be operated by trained
personnel.
Maintenance and repair is only permitted by qualified experts either at
OMICRON electronics repair centers.

Operating the Measurement Setup


Application of high-voltage tests is only allowed for operators who are
particularly skilled and experienced in high-voltage testing! The operator is
responsible for the safety requirements during the whole test. Before performing
tests using high voltage, please read the following:
Do not perform any test without having carefully read the CPC 100 and CP RC
user manuals!

Make sure to position the test equipment on dry, solid ground!

Pay attention to the national and international standards for the safe
operation of high-voltage test equipment (EN 50191, IEEE 510).

Never touch any parts without a visible ground connection!

Opening the housings of the CP RC Test Set invalidates all warranty claims.

Properly ground the CP RC and the CPC 100 by connecting them to the
common equipotential ground. Use ground connection cables of at least
6 mm cross-section. Never operate the CP RC without solid grounding.

FOR YOUR OWN SAFETY


Always follow the five safety rules:
1. Insulate
2. Secure to prevent reconnecting
3. Check isolation
4. Ground and short-circuit
5. Cover or shield neighboring live parts

CP RC User Manual

Orderly Measures
The CP RC User Manual or alternatively the e-book in PDF format has always
to be available on site where the CP RC is being used. It must be read and
observed by all users of the CP RC.
The CP RC may be used only as described in 2 "Operation" on page 15. Any
other use is not in accordance with the regulations. The manufacturer and/or
distributor is not liable for damage resulting from improper usage. The user
alone assumes all responsibility and risk.
Following the instructions provided in this User Manual is also considered part
of being in accordance with the regulations.

Disclaimer
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.

Introduction

Introduction

1.1

Designated Use
The CP RC is designated for performing high-voltage tests on GIS. The testing
system consists of the CP TR8 providing galvanic separation, the CP CR4 and
CP CR6 to compensate the reactive power, and the power voltage transformer
(VT). The power VT is part of the GIS and not provided by OMICRON
electronics. It replaces the standard VT inside the GIS and is designed to
withstand the needed test current.
Caution: It has to be guaranteed that the windings of the voltage transformer
can withstand the needed test current.
The busbars, the breakers, the disconnectors, the CTs and VTs inside a GIS
represent capacitive load on the high-voltage side of the voltage transformer
which is transformed to the low-voltage side by the square of the turns ratio.
Without compensating this reactive power, the CPC 100 is not able to deliver the
needed total power. The CP RC and the capacitive load build a parallel
resonance circuit. To get the exact resonance point, the test frequency is tuned
to resonance.

CP RC User Manual

1.2

CP TR8
The CP TR8 provides galvanic separation of the booster output of the CPC 100
for resonance circuiting with the GIS. With a ratio of 1:1 and an inductivity of
8 mH, capacitive loads can be compensated.
Output A
1+2
(internally connected)

Output B
1+2
(internally connected)

Measurement
connection B
(internally connected
to Output B)

Measurement
connection A
(internally connected
to Output A)

BOOSTER INPUT

Figure 1-1

10

Functional components of the CP TR8

Equipotential ground
terminal

Introduction

1.3

CP CR4 and CP CR6


The CP CR4 and CP CR6 are designed to compensate the reactive power
which is needed at the low-voltage winding of the power VT. Both have a fix air
gap.
Connection A
1+2
(internally connected)

Measurement
connection A
(internally connected
to Connection A)

Connection B
1+2
(internally connected)

Measurement
connection B
(internally connected
to Connection B)

Equipotential ground
terminal

Figure 1-2

Functional components of the CP CR4 and CP CR6

11

CP RC User Manual

1.4

CP RC Accessories
The following accessories are delivered with the CP RC.

12

Accessories

Description

2x Y-Cable, red

Connection from the


CP TR8s Output A to
the CP CR4/CP CR6s
Connection A and the
transformers a terminal

2x Y-Cable, black

Connection from the


CP TR8s Output B to
the CP CR4/CP CR6s
Connection B and the
transformers n terminal

1x I-Cable, red/black

Connection between the


CP CR4s Connection A
and the CP CR6s
Connection B

3x Grounding cable

Connection from the


CP TR8s, CP CR4s,
and CP CR6s
equipotential ground
terminals to the
substation ground

1x Booster cable
6 m/3x 1.5 mm2

Power connection from


the CPC 100s EXT.
BOOSTER output to the
CP TR8s BOOSTER
INPUT

1x KSO104 Current
transformer 1000/1 A,
1 VA, Kl. 0.1 ext. 120%
(15 VA, Kl. 0.2)

Current transformer to
measure the current on
the secondary side of
the voltage transformer

Introduction

Accessories

Description

2x Connector adapter,
yellow, 4 mm

Connection for the


current transformer

2x Transport case

To transport the entire


equipment

13

CP RC User Manual

14

Operation

Operation
This chapter provides a general description of the measurement setup.
Furthermore, it gives an overview of the compensation ranges for different
connection versions of the CP TR8, CP CR6 and CP CR4, as well as an
instruction on how to set up. Moreover, the HV Resonance Test System test
card to perform the high-voltage measurement is described.
As already mentioned earlier in this manual, different connection versions are
possible and/or required, depending on the load. All possible connection
versions are described below.
Warning: Use only designated connection options to prevent a life risk!

2.1

General
Independent of the connection option used, the following measurement
connections have to be provided (see Figure 2-1 on page 16):

For current measurement on the power VTs input, connect the current
transformer delivered in the package.

Press the Emergency Stop button on the CPC 100 front panel. Continue with
connecting only if the green warning light is on.

Connect terminals k (S1) and l (S2) to the I AC input of the CPC 100.

For voltage measurement, connect the a and n terminals of the power VT


(low-voltage side) to the V1 AC input on the CPC 100. If this is not possible,
the Measurement connections A and B of the CP TR8 can be used instead.

15

CP RC User Manual

CP TR8 (8 mH)

P2 P1
s2

s1
VT

Figure 2-1

General measurement setup

In all connection options, all elements of the setup have to be grounded using
the equipotential ground connection. For this purpose, use the grounding
cables delivered in the package.

Connect the EXT. BOOSTER output of the CPC 100 to the BOOSTER
INPUT of the CP TR8 with the booster cable.

Warning: Do not connect a reactor in serial with the CP TR8 output.


Dangerous voltages can be generated!

16

Operation

Compensation Ranges
Table 2-1 shows the possible compensation ranges. The indicated capacitances
refer to the low-voltage side of the VT. In order to calculate the maximum
capacitance on the high-voltage side, the ratio of the VT has to be considered.
Example: Ratio of the VT = 110 kV:100 V, C (HV side) = 1 nF:
C (LV side) = 1 nF x (110,000/100)2 = 1210 F
Table 2-1

Table of compensation ranges


f [Hz]

90

100

110

120

L [mH]

C [F]

C [F]

C [F]

C [F]

Setup A

8.00

391

317

262

220

Setup B

4.44

704

570

471

396

Setup C

3.43

912

739

611

513

Setup D

2.67

1173

950

785

660

Setup E

1.85

1694

1372

1134

953

Setup F

1.60

1954

1583

1308

1099

Setup G

1.26

2476

2005

1657

1393

Compensated Capacity

Capacitace LV [F]

2.2

Frequency [Hz]

Figure 2-2

Diagram of compensation ranges

17

CP RC User Manual

2.3

Measurement Setups

2.3.1

Setup Version A: 8 mH
If only the CP TR8 is used for compensation, loads of up to 391 F can be
compensated (at 90 Hz). This setup is also used to determine the load capacity.
Make sure to measure the current and voltage of the power VT on the lowvoltage side as shown in Figure 2-1 "General measurement setup" on page 16.

To CPC 100
Booster
Output

CP TR8

To CPC 100
I AC/DC Input

Figure 2-3

18

VT

Connection diagram for a 8 mH-setup

Operation

CP TR8

Figure 2-4

Setup for 8 mH

For this setup, provide the following connection:

Connect the red Y-cable from the Outputs A1 and A2 of the CP TR8 to the
a terminal of the power VT.

Connect the black Y-cable from the Outputs B1 and B2 of the CP TR8 to the
n terminal of the power VT.

For current measurement on the power VTs input, connect the current
transformer delivered in the package as shown in Figure 2-1 on page 16.

Connect terminals k (S1) and l (S2) to the I AC input of the CPC 100.

19

CP RC User Manual

2.3.2

Setup Version B: 4.44 mH


In this setup option, an inductivity of 4.44 mH is achieved by serial connection of
both compensation reactors CP CR4 and CP CR6, and parallel connection of
the reactors to the CP TR8. Thus, it is possible to compensate load
capacitances of up to 704 F (at 90 Hz). Make sure to measure the current and
the voltage of the power VT on the low-voltage side as shown in
Figure 2-1 "General measurement setup" on page 16.

To CPC 100
Booster
Output

CP TR8

CP CR6
CP CR4

To CPC 100
I AC/DC Input

Figure 2-5

20

VT

Connection diagram for a 4.44 mH-setup

Operation

CP CR6

CP TR8

CP CR4

Figure 2-6

Setup for 4.44 mH

For this setup, provide the following connection:

Connect the red Y-cable from Output A1 of the CP TR8 to the Connection
A1 of the CP CR6.

Connect the black Y-cable from the Output B1 of the CP TR8 to the
Connection B1 of the CP CR4.

Connect the short connection cable (red and black plug) from Connection
B2 of the CP CR6 to the Connection A1 of the CP CR4.

Connect the open ends of the Y-cables to the a and n terminals of the power
VT.

For current measurement on the power VTs input, connect the current
transformer delivered in the package as shown in Figure 2-1 on page 16.

Connect terminals k (S1) and l (S2) to the I AC input of the CPC 100.

21

CP RC User Manual

2.3.3

Setup Version C: 3.43 mH


For compensating a load capacitance of 740 F, the CP CR6 is connected to the
CP TR8 in parallel. Thus, an inductivity of 3.43 mH is achieved. Make sure to
measure the current and voltage of the power VT on the low-voltage side as
shown in Figure 2-1 "General measurement setup" on page 16.

To CPC 100
Booster
Output

CP TR8

CP CR6

To CPC 100
I AC/DC Input

Figure 2-7

22

VT

Connection diagram for a 3.43 mH-setup

Operation

CP TR8

Figure 2-8

CP CR6

Setup for 3.43 mH

For this setup, provide the following connection:

Connect the red Y-cable from the Output A1 of the CP TR8 to the
Connection A1 of the CP CR6.

Connect the black Y-cable from the Output B1 of the CP TR8 to the
Connection B1 of the CP CR6.

Finally, connect the open ends of the Y-cables to the a and n terminals of the
power VT.

In order to reduce cable losses, the second pair of Y-cables can be used to
connect Connection A2 and Connection B2. In this case too, connect the
open ends of the Y-cables to the a and n terminals of the power VT.

For current measurement on the power VTs input, connect the current
transformer delivered in the package as shown in Figure 2-1 on page 16.

Connect terminals k (S1) and l (S2) to the I AC input of the CPC 100.

23

CP RC User Manual

2.3.4

Setup Version D: 2.67 mH


As in the setup version for 3.43 mH, a parallel connection between the CP TR8
and the compensation reactor is provided. However, in this setup the CP CR4 is
used instead of the CP CR6. Thus, an inductivity of 950 F is achieved at
100 Hz. Make sure to measure the current and voltage of the power VT on the
low-voltage side as shown in Figure 2-1 "General measurement setup" on
page 16.

To CPC 100
Booster
Output

CP TR8

CP CR4

To CPC 100
I AC/DC Input

Figure 2-9

24

VT

Connection diagram for a 2.67 mH-setup

Operation

CP TR8

Figure 2-10

CP CR4

Setup for 2.67 mH

For this setup, provide the following connection:

Connect the red Y-cable from the Output A1 of the CP TR8 to the
Connection A1 of the CP CR4.

Connect the black Y-cable from the Output B1 of the CP TR8 to the
Connection B1 of the CP CR4.

Finally, connect the open ends of the Y-cables to the a and n terminals of the
power VT.

For current measurement on the power VTs input, connect the current
transformer delivered in the package as shown in Figure 2-1 on page 16.

Connect terminals k (S1) and l (S2) to the I AC input of the CPC 100.

In order to reduce cable losses, the second pair of Y-cables can be used to
connect Connection A2 and Connection B2. In this case too, connect the open
ends of the Y-cables to the a and n terminals of the power VT.

25

CP RC User Manual

2.3.5

Setup Version E: 1.85 mH


In this setup version, a second compensation reactor is added to the parallel
connection from setup versions C (3.43 mH) and D (2.67 mH). Thus, a
maximum compensation of 1.4 mF can be achieved at 100 Hz. Make sure to
measure the current and voltage of the power VT on the low-voltage side as
shown in Figure 2-1 "General measurement setup" on page 16.

To CPC 100
CP TR8
Booster
Output

CP CR6

CP CR4

To CPC 100
I AC/DC Input

Figure 2-11

26

VT

Connection diagram for a 1.85 mH-setup

Operation

CP TR8

Figure 2-12

CP CR6

CP CR4

Setup for 1.85 mH

For the setup, provide the following connection:

Connect the first red Y-cable from the Output A1 of the CP TR8 to the
Connection A1 of the CP CR6.

Connect the second red Y-cable from the Connection A2 of the CP CR6 to
the Connection A1 of the CP CR4.

Connect both open ends of the red Y-cables to the a terminal of the power
VT.

Connect the first black Y-cable from the Output B2 of the CP TR8 to the
Connection B2 of the CP CR6.

Connect the second black Y-cable from the Connection B1 of the CP CR6
to the Connection B2 of the CP CR4.

Connect both open ends of the black Y-cables to the n terminal of the power
VT.

For current measurement on the power VTs input, connect the current
transformer delivered in the package as shown in Figure 2-1 on page 16.

Connect terminals k (S1) and l (S2) to the I AC input of the CPC 100.

27

CP RC User Manual

2.3.6

Optional Setup Version F: 1.60 mH


Similar to setup version E, a second compensation reactor is added to the
parallel connection. Thus, a maximum compensation of 1.6 mF can be achieved
at 100 Hz. Make sure to measure the current and voltage of the power VT on the
low-voltage side as shown in Figure 2-1 "General measurement setup" on
page 16.

To CPC 100
CP TR8
Booster
Output

CP CR4

CP CR4

To CPC 100
I AC/DC Input

Figure 2-13

28

VT

Connection diagram for a 1.60 mH-setup

Operation

CP TR8

Figure 2-14

CP CR4

CP CR4

Setup for 1.60 mH

For the setup, provide the following connection:

Connect the first red Y-cable from the Output A1 of the CP TR8 to the
Connection A1 of the first CP CR4.

Connect the second red Y-cable from the Connection A2 of the first CP CR4
to the Connection A1 of the second CP CR4.

Connect both open ends of the red Y-cables to the a terminal of the power
VT.

Connect the first black Y-cable from the Output B2 of the CP TR8 to the
Connection B2 of the first CP CR4.

Connect the second black Y-cable from the Connection B1 of the first
CP CR4 to the Connection B2 of the second CP CR4.

Connect both open ends of the black Y-cables to the n terminal of the power
VT.

For current measurement on the power VTs input, connect the current
transformer delivered in the package as shown in Figure 2-1 on page 16.

Connect terminals k (S1) and l (S2) to the I AC input of the CPC 100.

29

CP RC User Manual

2.3.7

Optional Setup Version G: 1.26 mH


In this setup version, a third compensation reactor is added to the parallel
connection from setup versions C (3.43 mH) and D (2.67 mH). For this setup, an
additional CP CR4 unit is required. Thus, a maximum compensation of 2.0 mF
can be achieved at 100 Hz. Make sure to measure the current and voltage of the
power VT on the low-voltage side as shown in Figure 2-1 "General
measurement setup" on page 16.

To CPC 100
CP TR8
Booster
Output

CP CR6
CP CR4
CP CR4

To CPC 100
I AC/DC Input

Figure 2-15

30

VT

Connection diagram for a 1.26 mH-setup

Operation

CP TR8

Figure 2-16

CP CR6

CP CR4

CP CR4

Setup for 1.26 mH

For the setup, provide the following connection:

Connect the first red Y-cable from the Output A1 of the CP TR8 to the
Connection A1 of the CP CR6.

Connect the second red Y-cable from the Connection A1 of the first CP CR4
to the Connection A1 of the second CP CR4.

Connect both open ends of the red Y-cables to the a terminal of the power
VT.

Connect the first black Y-cable from the Output B2 of the CP TR8 to the
Connection B2 of the CP CR6.

Connect the second black Y-cable from the Connection B2 of the first
CP CR4 to the Connection B2 of the second CP CR4.

31

CP RC User Manual

2.4

Connect both open ends of the black Y-cables to the n terminal of the power
VT.

For current measurement on the power VTs input, connect the current
transformer delivered in the package as shown in Figure 2-1 on page 16.

Connect terminals k (S1) and l (S2) to the I AC input of the CPC 100.

Test Card
The HV Resonance Test System test card is used for generic high-voltage
tests with resonance circuits in combination with the CP TR8 as well as CP CR4
and CP CR6.
To select a test card, press Insert Card in the Test Card View.
Use the context-dependent Up/Down menu keys to the right, or the handwheel,
to browse through the structure. On Others, press Enter.
Alternatively, press the accelerator key to open the Insert a new test card
dialog box.
For Others, the following test cards are available:

Figure 2-17

Inserting test cards

Highlight the HV Resonance Test System test card either by navigating with
the handwheel or by using the context-dependent Up/Down menu keys, and
then press Enter.

32

Operation

2.4.1

Test Settings for HV Resonance Test System


The output voltage is displayed very clearly on the main page of the test card.
The frequency has to be set manually or by pressing Search f0. The location
indicator shows the controlled input channel. The location indicator is placed
either above V out (External Booster) or above VT (V1 AC).
Test settings

Set output voltage

Set frequency value


Controlled input channel

Figure 2-18

HV Resonance Test System test card

33

CP RC User Manual

Navigate to the parameter fields and enter the values according to your test
requirements:
Ratio estim.:

Estimated VT ratio

Search f0...:

Automatic search of resonance frequency. Pressing this


key will open the following dialog:

Test cycle:

Define/set automatic test cycle

VT:

Voltage as defined in the settings page.

CT:

Current as defined in the settings page.

V out:

Output voltage at CPC 100 Ext. Booster output

I out:

Output current at CPC 100 Ext. Booster output

The shows the phase angle of I out relative to V out.

Time:

Time elapsed for this measurement

To set the test cycle:


Press to add state
Indicates the voltage slope between
the states

State definition
Total time of test cycle

Figure 2-19

34

Test cycle settings

Operation

Pressing the Settings menu key opens the settings page.

Figure 2-20

Settings page of the HV Resonance Test System test card

35

CP RC User Manual

36

CT ratio:

Nominal CT ratio according to CT nameplate

VT ratio nom.:

Nominal VT ratio according to VT nameplate

Estimate HV@f0=n/a:

Select if no measurement VT is available. Selecting


this check box will show a different circuit diagram
on the test card:

X sc@100Hz:

Short-circuit impedance of the power VT at 100 Hz

VT ratio w/ loss=:

Estimated power VT ratio with losses (refer also to


section 3.5.3 on page 51)

Operation

After determining the resonance frequency, the settings page will show
additional information (marked in red):

37

CP RC User Manual

38

Measurement

Measurement

3.1

Overview
The entire measurement procedure is outlined below:
Prepare test setup

Short-circuit all low-voltage terminals

Measure the leakage reactance of the power VT


(optional)

Provide the measurement setup and short-circuit the


high-voltage side of the VT

Find the setup for the HV test

Use Setup A

Determine the resonance frequency

Select setup

Perform the HV test

Without second VT

With second VT

Define test settings

Determine the resonance frequency

Determine the resonance frequency

Conduct the measurement

Conduct the measurement

Figure 3-1

Define test settings

Measurement overview

39

CP RC User Manual

3.2

Preparation

Short-circuit all low-voltage terminals.

All unused VTs of the GIS have to be short-circuited on the low-voltage


terminals.
Caution: Short-circuit the low-voltage terminals of the non-used phases! This
is important since coupling between the phases will result in voltage induction
in the non-tested phases. Thus, the test voltage from phase to phase cannot
be reached.

Figure 3-2

40

Short-circuiting the low-voltage terminals of the unused phases

Measurement

3.3

Measurement of the Leakage Reactance


This procedure is only required, if no direct measurement on the high-voltage
side is possible, for example, due to a second VT or voltage divider.

Provide the measurement setup as shown in Figure 3-3 "Example for


measuring the leakage reactance" and make sure to short-circuit the highvoltage side of the voltage transformer.

Figure 3-3

Example for measuring the leakage reactance

Insert a Quick test card and set the output range to 6A AC, the output
frequency to 100 Hz, and the output current to 5.00 A.

Set the 1st measurement channel to V1 AC, the 2nd measurement channel to
I AC, and the calculate value to R,X.

Press the I/O (test start/stop) push-button to start the test.

Press Keep Result and the I/O (test start/stop) push-button to stop the test.

41

CP RC User Manual

Figure 3-4

3.3.1

Measurement results

The leakage reactance of the VT at 100 Hz is displayed in the last column of


the results line (for example, Xsc = 306 m).

Theoretical Background to Calibration of Voltage


Measurement
The load on the primary (high-voltage) side of the voltage transformer is almost
capacitive.
Simplified electrical equivalent circuit of the voltage transformer under load:
U
Is
Us

Figure 3-5

Xsc

U'p

C'

Electrical equivalent circuit of the voltage transformer under


load

The voltage on the secondary (low-voltage) side and the primary (high-voltage)
side have the following correlation:

U s = U + U' p = I s jX sc + U' p

42

Measurement

where
Us

= input voltage (voltage of the low-voltage side of the VT)

Is

= input current

U'p

= voltage on the high-voltage side of the VT referred to the


secondary low-voltage side

= voltage drop due to capacitive load

Xsc

= leakage reactance of the VT

The output voltage U'p is larger than the input voltage Us. This is caused by the
losses of the leakage reactance.
U'p U
Us

Is
Figure 3-6

Influence of the capacitive load

If the voltage Us is used for determining the voltage Up on the high-voltage side,
U has to be considered. To calculate U, the current Is and the leakage
reactance Xsc have to be known.

43

CP RC User Manual

3.4

Finding the Setup for the High-Voltage Test

3.4.1

Preparation of the Measurement

Prepare the measurement by using Setup A (see section 2.3 on page 18):

CP TR8 (8 mH)

P2 P1
s2 s1
VT

Figure 3-7

Test circuit

This measurement setup is used to determine the total capacitance of the test
setup. Once the capacity is known, the correct measurement setup can be
selected to perform the high-voltage test.

3.4.2

Determination of the Capacitance of the Test Setup

Insert a new HV Resonance Test System test card and select Settings.

Set the CT ratio and VT ratio nom.:

Set a ratio of 1000:1 for the CT (transformer in accessories package)

Set the ratio for the VT according to the VT nameplate

Figure 3-8

44

Settings on the HV Resonance Test System test card

Measurement

Determine the Resonance Frequency (only CP TR8) :

Change to the main page by pressing the Main Page key.

Set the output voltage to a reasonably low voltage, for example, 10 kV.

Search the resonance frequency manually or by pressing the Search f0


button.

Press the I/O (test start/stop) push-button to start the test.

The determined frequency is used to select the test setup.

Figure 3-9

Resonance frequency

45

CP RC User Manual

3.4.3

Select the Setup


Select the total capacitance:
Use your determined frequency and choose the correct measurement setup
for the high-voltage test using the diagram below and Table 2-1 on page 17.

Capacitance LV. [F]

Frequency [Hz]

46

Figure 3-10

Resonance diagram

Table 3-1

Setups

Color

Setup

Description

Inductance

Blue

Setup A

CP TR8 (8 mH) alone

8.00 mH

Green

Setup B

CP TR8 (8 mH) II (CP CR6


(6 mH) + CP CR4 (4 mH))

4.44 mH

Red

Setup C

CP TR8 (8 mH) II CP CR6


(6 mH)

3.34 mH

Measurement

Table 3-1

Setups

Color

Setup

Description

Inductance

Pink

Setup D

CP TR8 (8 mH) II CP CR4


(4 mH)

2.67 mH

Orange

Setup E

CP TR8 (8 mH) II CP CR6


(6 mH) II CP CR4 (4 mH)

1.85 mH

Light Blue

Setup F

CP TR8 (8 mH) II CP CR4


(4 mH) II CP CR4 (4 mH)

1.60 mH

Purple

Setup G

CP TR8 (8 mH) II CP CR6


(6 mH) II CP CR4 (4 mH) II
CP CR4 (4 mH)

1.26 mH

Build the measurement circuit with the measurement setup selected (see
2.3 "Measurement Setups" on page 18).

47

CP RC User Manual

3.5

Performing the HV Test Without Second VT


If the power VT is used for the high-voltage measurement, it is required to adjust
the ratio as shown in section 3.3.1 "Theoretical Background to Calibration of
Voltage Measurement" on page 42.

3.5.1

Test Settings for the High-Voltage Test

Insert a new HV Resonance Test System test card and select Settings.

Set the CT ratio and VT ratio nom.:

Set a ratio of 1000:1 for the CT (transformer in accessories package)

Set the ratio for the VT according to the VT nameplate

Select Estimate HV@f0 and enter the short-circuit impedance of the power
VT at 100 Hz (X sc@100Hz).

Figure 3-11

48

Settings on the HV Resonance Test System test card

Measurement

3.5.2

Determine the Resonance Frequency

Change to the main page by pressing the Main Page key.

Set the output voltage to a reasonably low voltage, for example, 10 kV.

Search the resonance frequency by pressing the Search f0 button.

Press the I/O (test start/stop) push-button to start the test.

The determined frequency is used for the high-voltage test.

Figure 3-12

Determined resonance frequency

49

CP RC User Manual

With the resonance frequency and I0 and V0 at this frequency, the leakage
reactance is calculated and thus the voltage drop due to capacitive load.

Make sure that Estimate HV@f0=n/a was selected and the short-circuit
impedance at 100 Hz for the power VT (X sc@100Hz) was entered.

The settings page shows the resonance frequency f0, as well as I0 and V0
at resonance frequency (marked in red).

With these values the VT ratio w/ loss is determined.

Figure 3-13

50

Resonance frequency, I0 and V0

Measurement

3.5.3

Conducting the Measurement


Use the HV Resonance Test System test card as prepared in sections
3.5.1 "Test Settings for the High-Voltage Test" on page 48 and 3.5.2 "Determine
the Resonance Frequency" on page 49.
Warning: Do not leave the test setup unattended!

Warning: Observe the maximum operating hours as listed in


4.1 "Specifications" on page 57 and the maximum operating hours of the VT
according to nameplate data!

Performing the high-voltage test with automatic test cycle:

Select Test cycle if you would like to run the test in defined states. For this
purpose, use the test settings as described in 2.4.1 "Test Settings for HV
Resonance Test System" on page 33.

Figure 3-14

Test cycle settings

51

CP RC User Manual

Press Back to Top to open the main page.

Press the I/O (test start/stop) push-button to start the test.

The test stops automatically after completing the test cycle.

The results will be shown in the results table:

Figure 3-15

Measurement results with automatic test cycle

Performing the high-voltage test with manual test cycle:

Press the I/O (test start/stop) push-button to start the test.

Increase the output voltage of the CPC 100 to reach your test voltage.

Press Keep Result for each test voltage level.

Press the I/O (test start/stop) push-button to stop the test.

The results will be shown in the results table:

Figure 3-16

52

Measurement results with manual test cycle

Measurement

3.6

Performing the HV Test With Second VT


If a direct measurement on the high-voltage side is possible, for example, due
to a second VT or voltage divider, proceed as described below.

3.6.1

Test Settings for the High-Voltage Test

Insert a new HV Resonance Test System test card and select Settings.

Set the CT ratio and VT ratio nom.:

Set a ratio of 1000:1 for the CT (transformer in accessories package)

Set the ratio for the VT according to the second VT or voltage divider
nameplate

Connect the low-voltage clamps of the second VT or voltage divider to the


V1AC input of the CPC 100.

Figure 3-17

Settings page with second VT in circuit diagram

53

CP RC User Manual

3.6.2

Determine the Resonance Frequency

Change to the main page by pressing the Main Page key.

Set the output voltage to a reasonably low voltage, for example, 10 kV.

Search the resonance frequency by pressing the Search f0 button.

Press the I/O (test start/stop) push-button to start the test.

The determined frequency is used for the high-voltage test.

Figure 3-18

54

Determined resonance frequency

Measurement

3.6.3

Conducting the Measurement

Use the HV Resonance Test System test card as prepared in sections


3.5.1 "Test Settings for the High-Voltage Test" on page 48 and
3.5.2 "Determine the Resonance Frequency" on page 49.

Warning: Do not leave the test setup unattended!

Warning: Observe the maximum operating hours as listed in


4.1 "Specifications" on page 57 and the maximum operating hours of the VT
according to nameplate data!

Performing the high-voltage test with automatic test cycle:

Select Test cycle if you would like to run the test in defined states. For this
purpose, use the test settings as described in 2.4.1 "Test Settings for HV
Resonance Test System" on page 33.

Figure 3-19

Test cycle settings

55

CP RC User Manual

Press Back to Top to open the main page.

Press the I/O (test start/stop) push-button to start the test.

The test stops automatically after completing the test cycle.

The results will be shown in the results table:

Figure 3-20

Measurement results with automatic test cycle

Performing the high-voltage test with manual test cycle:

Press the I/O (test start/stop) push-button to start the test.

Increase the output voltage of the CPC 100 to reach your test voltage.

Press Keep Result for each test voltage level.

Press the I/O (test start/stop) push-button to stop the test.

The results will be shown in the results table:

Figure 3-21

56

Measurement results with manual test cycle

Technical Data

Technical Data
This section lists the CP TR8 & CP CR4/6 specifications, requirements, and
standard compliance.

4.1

Specifications
Table 4-1

CP TR8 & CP CR4/6 Specifications

Characteristic

Rating

Isolation transformer CP TR8 (8 mH)


Uout

220 V

Iout

60 A (10 min on, 120 min off)

Ssec

13.2 kVAr (10 min on, 120 min off)

90 - 120 Hz

Insulation class

Compensation Reactor CP CR6 (6 mH)


Uout

220 V

Iout

150 A (10 min on, 120 min off)

Ssec

33 kVAr (10 min on, 120 min off)

90 - 120 Hz

Insulation class

Compensation Reactor CP CR4 (4 mH)


Uout

220 V

Iout

150 A (10 min on, 120 min off)

Ssec

33 kVAr (10 min on, 120 min off)

90 - 120 Hz

57

CP RC User Manual

4.2

Mechanical Data
Table 4-2

4.3

Characteristic

Rating

Dimensions (w h d) - without handle

262 mm x 225.5 mm x 222 mm

Dimensions (w x h x d) - with handle

262 mm x 277.5 mm x 222 mm

Weight CP TR8

19 kg

Weight CP CR4 and CP CR6

20.5 kg

Environmental Conditions
Table 4-3

58

Mechanical Data of CP TR8 & CP CR4/CP CR6

Environmental Conditions

Characteristic

Rating

Operating temperature

10+55 C/14131 F

Transport & storage temperature

20+70 C/4158 F

Relative humidity

595%, non-condensing

Protection

IP20

Technical Data

4.4

CE Conformity and Safety Standards


Table 4-4

CE Conformity and Safety Standards

CE Conformity
The product adheres to the specifications of the guidelines of the Council of
the European Community for meeting the requirements of the member states
regarding the low-voltage Directive 2006/95/EC.
Certified Safety Standards

4.5

Europe

EN 61010-1 (partly)

International

IEC 61010-1(partly)

USA

UL 61010-1 (partly)

Suitable for usage according to

IEEE 510, EN 50191 (VDE 0104),


EN 50110-1 (VDE 0105 Part 100)

Cleaning
Warning: Prior to cleaning, always disconnect the CP TR8, CP CR4 and
CP CR6.
To clean the CP TR8, CP CR4 and CP CR6 use a cloth dampened with
isopropanol alcohol or water.

59

CP RC User Manual

60

Contact Information / Technical Support

Contact Information / Technical Support


Americas
OMICRON electronics Corp. USA
12 Greenway Plaza, Suite 1510
Houston, TX 77046, USA
Phone: +1 713 830-4660
1 800-OMICRON
Fax:
+1 713 830-4661
techsupport@omicronusa.com
www.omicronusa.com

Asia Pacific
OMICRON electronics Asia Ltd.
Suite 2006, 20/F, Tower 2
The Gateway, Harbour City
Kowloon, Hong Kong S.A.R.
Phone: +852 3767 5500
Fax:
+852 3767 5400
support@asia.omicron.at
www.omicron.at

Europe, Middle East, Africa


OMICRON electronics GmbH
Oberes Ried 1
A-6833 Klaus, Austria
Phone: +43 5523 507-333
Fax:
+43 5523 507-999
support@omicron.at
www.omicron.at
For addresses of OMICRON electronics offices with customer service centers,
regional sales offices or offices for training, consulting and commissioning
please visit our Web site.

61

CP RC User Manual

62

Index

Index
A

G
ground
grounding 7

accelerator key 32

handwheel 32
hotline 61
HV Resonance Test System 32

BOOSTER
INPUT 16
booster
external 16

C
cable
loss 23, 25
capacitive
load 9
connection
parallel 20, 24, 26, 28, 30
serial 16, 20
versions 15
contact information 61

E
earth
connection 7
EN 50110-1 59
EN 50191 5, 59
EN 61010-1 59
EN 50110-1 5
equipotential
ground 7
EXT. BOOSTER 16

F
frequency
test frequency 9

I
IEC 61010-1 59
IEEE 510 5, 59
inductivity 20
Insert a new test card 32
Insert Card 32
IP20 58

L
load
capacitive 9
loss
cable loss 23, 25

M
measurement
connections 15
overview 39
procedure 39

P
parallel
connection 20, 24, 26, 28, 30

R
resonance
circuit 9

63

CP RC User Manual

S
safety rules 7
serial
connection 16, 20
Settings page 35
setup
1.26 mH 30
1.60 mH 28
1.85 mH 26
2.67 mH 24
3.43 mH 22
4.44 mH 20
8 mH 18
support 61

T
technical support 61
terminal 7
Test Card View 32
test frequency 9
turns ratio 9

U
UL 61010-1 59
Up/Down menu keys 32

V
VDE 0104 5, 59
VDE 0105 Part 100 59
VDE 0105 Part 100 5

64