Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Refrigeration
Automatic Purgers in
Refrigeration Systems
By Douglas T. Reindl, Ph.D., P.E., and James L. Denkmann
Member ASHRAE
Member ASHRAE
purger is an essential component for the proper and efficient operation of an industrial refrigeration system. A purger gathers, separates
and expels non-condensable gases from the system. Successfully
purging non-condensables from a refrigeration system leads to increased refrigeration capacity, improved system efficiency, and enhanced system safety.
In this article, we review the types of noncondensable gases (NCG) that can accumulate in systems, consequences of NCG,
purger operation, application considerations and factors that influence purger performance. Our emphasis is on vapor compression-based industrial refrigeration systems that use anhydrous ammonia as the
refrigerant because this choice covers the
majority of industrial systems in use today.
Background
Most industrial refrigeration systems
currently in use are based on the vapor
compression cycle. Vapor compression refrigeration systems function through a continuous closed cycle whereby a volatile
working fluid (refrigerant) undergoes a series of phase changes, which leads to the
ability for providing a useful refrigeration
effect. In the condenser, heat is rejected
from the system converting hot gaseous
refrigerant at high pressure to pure liquidphase refrigerant also at high pressure. The
high-pressure liquid is subsequently
throttled to lower pressures to be available
for absorbing heat into the system through
the evaporator as part of a refrigeration process. In the evaporator, low-pressure liquid refrigerant boils as a result of heat
added from a space or a process load. The
low-pressure vapor refrigerant generated
is then raised in pressure by the compressor and directed to the condenser to reject
heat from the system again. The effective30
ASHRAE Journal
w w w. a s h r a e j o u r n a l . o r g
August 2001
Refrigeration
trapped air must be removed by purging.
Secondary types of NCG include hydrogen and nitrogen.
Hydrogen and nitrogen gases accumulate as a result of the
refrigerant (NH3) dissociating (breaking-down) over time. The
two most important factors that influence the breakdown of
ammonia into its constituent parts are temperature and pressure. At higher temperatures, ammonia is more prone to irreversibly breaking down into nitrogen and hydrogen. Older systems (>25 years) and those with reciprocating compressors
appear to experience an accelerated rate of breakdown. However, the gross quantity of NCG generated by this mechanism is
relatively small. Even small dissociation rates lead to the accumulation of large quantities of hydrogen and nitrogen over time
if they are not removed from the system on a regular basis.
Tertiary sources of NCG arise from the breakdown of lubricating oils. Most industrial refrigeration systems use mineralbased lubricating oils. As a result, the oil will breakdown and
liberate a complex series of hydrocarbon gases. Some of the
gases will have lower molecular weights when compared with
ammonia (e.g., CH4) while others will be heavier (e.g., C8H18).
Table 1 lists each of the gases potentially present in a noncondensable gas mixture, along with their molecular weights
and densities at a design condensing pressure for many ammonia refrigeration systems (196 psia [1349 kPa]). Refrigerant R-22
is also shown for reference.
Consequences of Non-Condensable Gases
The total heat rejection requirement for a vapor compression
system is the sum of the gross refrigeration effect plus the
aggregate work input to the system by the compressors. Industrial refrigeration systems commonly use evaporative condensers as the means of rejecting heat from the system to the out-
Gas
Hydrogen
Ammonia
Nitrogen
Air
Oil Decomposition
R-22
Mol. Weight
2
17
28
29
1544
86
Table 1: Gas properties including common NCG and industrial refrigerants for reference.
Disadvantages
Capital cost: for the purger
unit, purger piping, solenoid
valves, and controls
Maintenance costs: for the
purger unit, accompanying
solenoid valves, and
transducers required for
purger control
ASHRAE Journal
31
ASHRAE Journal
due to the presence of NCG, the temperature of the condensing refrigerant (and its
pressure) must increase to reject the necessary heat from the system. The consequences of increased condensing (or head)
pressure are undesirable and include:
Decreased system refrigeration capacity;
Increased system electrical demand
and energy consumption (attributed to
compressors and condenser fans);
Decreased system efficiency;
Increased compressor discharge superheat (accelerating oil breakdown and
refrigerant dissociation);
Increased head pressure leading to
increased compressor wear and tear and
greater likelihood of system shutdowns
due to high head pressure; and
Increased condenser scaling, which
leads to increased maintenance costs and
decreased condenser life.
How A Purger Works
Functionally, there are two types of
purgersautomatic and manual. The automatic purger is a mechanical device integrated into a system that gathers, separates, and removes NCG from multiple
points in the refrigeration system without operator assistance. A manual purger
can be as simple as an angle valve that
requires a mechanic or technician to manually open the valve and dispel any vapor
(which will include mixture of ammonia
and NCG) into a water bucket.
A diagram of how most automatic purgers function is shown in Figure 1. A single
condenser purge solenoid valve has been
shown for simplicity although all systems
will have a multiplicity of purge points. A
mixture of NCG and ammonia vapor should
be drawn into a purge connection during
the time its respective solenoid valve is
open. This gas mixture flows down the foul
gas line to the purger unit piping connection. It is important that all gas purge lines
are free of any places where vapor can condense and collect, blocking further NCG
removal. Liquid traps cannot be tolerated
in this piping, particularly as it pertains to
some purger models. All purge piping
should be pitched down to the purger as
recommended by purger manufacturers.
The foul gas line is connected to a drain
trap at the purger. The function of the drain
trap is to separate and expel any liquid
32
ASHRAE Journal
w w w. a s h r a e j o u r n a l . o r g
August 2001
ASHRAE Journal
33
ASHRAE Journal
small concentration of NCG on the low-pressure side of a system will be relatively benign since it does not interfere with the phase
change process in the evaporators and has
no effect upon gas/liquid separation in accumulators and knockout vessels. Compressors
quickly move any NCG from the low-pressure
side to the high-pressure side of the system
where it can be removed by the purger.
Purging From High-Pressure Vessels
Thermosiphon receivers are not customarily provided with purge connections. One reason is that any NCG that enters this vessel is
pushed out the oil cooler gas return line and
back up to the condensers. Since this vessel
is not designed with heat transfer in mind, a
slight accumulation of NCG can be tolerated.
Figure 4: Diagram of multiple evaporative condensers showing the effect of
But this same rule could also apply to a highunequal pressures between heat exchangers and pressure differences between
pressure receiver (HPR) as well. If one cubic
condensers and thermosiphon receiver.
foot (28 L) of liquid enters this vessel, it will
displace an equal volume of NCG. This will be pushed up the hang-up. In some cases,
gas return line (commonly referred to as an equalizer line) and the liquid hang-up in the
into the evaporative condenser gas inlets. If the gas return line evaporative condenser is
is too small (which the authors have found to be quite com- so severe that the purge
mon), the pressure in the HPR increases. Even slight pressure solenoid opens only to
differences between the HPR and condenser drain outlets can see liquid refrigerant.
pose difficulties with proper condenser drainage.
Foul gas piping that
Many HPRs are installed outdoors, and with few exceptions creates liquid traps leads
are located on-grade. Most HPR foul gas line installations form to difficulty in establishliquid traps whenever the outside air ambient dry-bulb tem- ing an unimpeded flow of
perature is below the refrigerant saturation temperature. At- foul gas to the purger.
tempting to remove NCG from an HPR can be problematic if this
The purger is located
Figure 5: Evaporative condenser
situation is not recognized.
above one or more conwith extra deep condenser drain
denser purge points.
traps.
Factors Influencing Purger Performance
The purger is malSeveral factors influence the ability of a purger to collect functioning, usually due to dirt.
NCG from the system:
While purgers normally are equipped with liquid drain traps,
More than one purge solenoid valve is open simultaneously. the liquid-handling capacity of these traps is quite small. If a
This should never occur.
purge point gathers liquid refrigerant instead of vapor, all of this
Pressure imbalances exist between adjacent evaporative liquid cannot be completely passed by the liquid drainer; excescondenser heat exchangers, creating opportunities for liquid sive quantities then back up into the purgers vapor condenser.
If the vapor condenser fills with liquid, it becomes subcooled as
it passes through to the air separation chamber. A control senses
the higher liquid level in the air separation chamber and expels it
to the flooded evaporator. If the evaporator is already full of
liquid, then liquid will exit the purger via the suction line. This is
why purgers must be connected to a protected (wet) suction
line and not piped directly to the compressor suction.
Advertisement for the print edition
A fundamental requirement for purging NGC from a system is
formerly in this space.
to get NCG into the purger. Although this sounds trivial, complexities in system operation often prevent the purger from processing foul gas. One of the most overlooked conditions preventing a purger from receiving foul gas is liquid hang-up in
evaporative condensers.
It is not uncommon for a large evaporative condenser in an
ammonia refrigeration system to hold up >700 lb (318 kg) of liquid
34
ASHRAE Journal
w w w. a s h r a e j o u r n a l . o r g
August 2001
Refrigeration
with only a 0.25 psi (1.7 kPa) pressure difference between adjacent
circuits in the condensers. A pressure difference on the order of
0.25 psi (1.7 kPa) is normally sufficient to flood the liquid drain
header box and bottom two passes of most evaporative condenser
heat exchangers as shown in Figure 1. Under this situation, the
purge point becomes flooded with subcooled liquid. When the
purge solenoid opens to draw foul gasit draws in liquid refrigerant. If this continues over days or weeks, non-condensables will
continue to accumulate in the system and the condenser will slowly
lose heat-transfer effectiveness. In some severe cases, entire
evaporative condensers have been rendered nearly useless by
the end of a season (usually during winter). It now appears that
this may be more commonplace than originally thought.
Figure 3 shows a 12-pass evaporative condenser heat exchanger. The single condenser heat exchanger shown in this
figure is comprised of one inlet connection (the header at the
top of the tube bundle) and one outlet connection (the header
at the bottom of tube bundle) with many parallel tubes interconnecting the upper and lower header boxes. Individual tube
lengths vary between condenser sizes, ranging from approximately 70 lineal feet (21 m) (six-pass models) up to >200 lineal
feet (61 m) (12 pass models). Evaporative condenser heat exchangers are typically fabricated from nominal 1 in. (25 mm) hotdipped galvanized steel tubing. Evaporative condensers having dual inlet and outlet connections are equipped with two
heat exchangers. In this configuration, ammonia is prevented
from flowing from one heat exchanger directly into its neighbor. However, any slight pressure difference between evaporative condensers will force refrigerant liquid and/or vapor from
one condenser into another via the outlet drain piping whenever P-traps are shallow. This is mainly true of ammonia, and to
a lesser extent, the halocarbon refrigerants.
Condenser Drain Traps: How Deep Should They Be?
Figure 4 presents a typically accepted arrangement for draining multiple evaporative condensers. This figure assumes that
all drain connections are on a common elevation, but the heat
exchangers are of different sizes and the fans on condenser C3 have stopped. The condensers are shown draining to a common vessel. A thermosiphon receiver (TSR) is shown, although
an HPR also is common when thermosiphon oil coolers are not
used. In some cases, the HPR and TSR are combined into a
single vessel. The pressures at each node are numbered P1, P2,
etc. This figure also assumes that the oil cooler gas return line
imposes an excessive pressure drop.
From this figure it is evident that purging NCG has been
impaired in active condensers C-1 and C-2. Why does this occur? Three reasons explaining the phenomena are shown in
Figure 4:
The pressure within the thermosiphon receiver is greater
than the pressure at any of the condenser drain outlet connections, P1 > P5, P6, P7. This occurs as a result of an excessive
in the oil cooler gas return line.
Active condensers C1 and C2 are built from different
tubing lengths, therefore each imposes a different pressure drop,
(P2P5) (P3P6) 0.
The pressure at the bottom of condenser C3 is nearly equal
August 2001
ASHRAE Journal
35