Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Table of Contents
Actuators:
Introduction
I – Electrical Actuators
3 - Solenoid
• Definition of Solenoid .
• Technical considerations .
• Types of solenoids .
• Example on Application of Solenoids .
II – Hydraulic Actuators
• Components of Hydraulic system .
• Types of valves used .
• Types of cylinders used .
• Advantages & Disadvantages of Hydraulic actuators .
III – Pneumatic Actuators
• Some basic characteristics of pneumatic systems .
• Some symbols for pneumatic systems .
• Advantages and Disadvantages of pneumatic actuators .
2
Sensors:
Introduction
I – Proximity Sensors
II - Strain Gauge
• Introduction .
• Definition of Strain .
• Strain Gauge Measurement .
• Calibration .
III -Thermocouple
Introduction .
• Definition of thermocouple .
Thermoelectric characteristics .
Thermocouple Calibration Procedures .
Applications .
• Appendix 1 .
3
Actuators
Introduction
Actuators are a type of tool which is used to put something into
automatic action. It is used on a wide variety of sources, from humans
putting something into action to computers starting up a program.
Whichever type of actuator you are in need of, there are several
.different tools that can help you achieve putting something into motion
There are several reasons why actuators may be used in an office work
area. Most of these will be used as the thing that positions or moves a
certain object. For example, many will be used to move or position
4
valve doors in certain systems. They may also be used to maneuver
certain mechanical devices that are used in a work area. By using
actuators, it is easier for one to work in their area, as well as easier to
maneuver something around in the certain area. The main way in which
actuators are divided for best use is through their shape and style.
Through the several different types of styles available, one is able to
determine which type of actuator will be best for their task . In this
.Report we will focus on hydraulic , pneumatic &electric actuators
:Definition of actuator
Types of Actuators
Here we will focus only on :
• Electric Actuators
• Hydraulic Actuators
• Pneumatic Actuators
5
I – Electric Actuators
Electrically actuated systems are very widely used in control systems
because they are easy to interface with the control systems which are
also electric and because electricity is easily available unlike fluid
power which require pumps and compressors .
• Electricity
is easily routed to the actuators ; cables are simpler than
pipe work .
• Electrical
equipment is more of a fire hazard than other systems
unless made intrinsically safe in which case it becomes expensive .
• Electric
actuators are all basically rotary motion and complicated
mechanisms are needed to convert rotation into other forms of
motion .
Movement
• Multi-turn actuators
• Part-turn actuators
• Linear actuators
Design
6
• Motor (1)
• Limit and torque sensors (2)
• Gearing (3)
• Valve attachment (4)
• Manual operation (5)
• Actuator controls (6)
• Electrical connection (7)
• Field bus connection (8)
Functions
Duty types
• Open-close duty
• Positioning duty
• Modulating duty
Service conditions
• Enclosure protection
• Ambient temperatures
• Explosion protection
7
• Motors
• Solenoid
Linear Actuators
8
Electric linear actuators provide linear motion via a motor-driven ball
screw, lead screw, or acme screw assembly. The load is attached to the
end of the screw and is unsupported. Acme screws are lead screws with
matching threads on both the screw and nut. Ball screws are lead screw
and ball nut combinations that enable the balls in the nut to circulate
when the actuator is in motion. Electric linear actuators with belt drives,
geared drives, and direct drives are also available. Belt drives connect
the motor to the actuator with a belt. Geared drives connect the motor
to the actuator with a set of gears. With direct drives, the motor is
connected directly to the electric linear actuator. In terms of
performance, important specifications include stroke, rated force or
load, system backlash, and rated speed. Stroke is the maximum
distance that the shaft travels from a fully extended position to a fully
retracted position. Backlash is the position error due to directional
change. The maximum rated speed is typically a low or no load
amount.
Compression Load
A load that leads toward compressing the positioner.
Continuous Motor Torque
The torque created by the motor at rated constant current.
Cycle
A complete positioner extension and retraction returned to the
beginning point.
Duty Cycle
The amount of time a positioner can run and how much time it
needs to cool. It is on time to cooling time, meaning a duty cycle of
25% is a cycle in which a positioner operates continually for ten
seconds must rest for thirty seconds.
11
The speed at which the positioner extends or retracts. Extension
rate differs with the load on DC positioners but differs very little on AC
positioners or step-motor positioners.
Force Rating
The linear force created by the actuator at constant motor torque.
Hardwired Signals
Electrical signals traveling between two control devices that are
connected with dedicated conductors.
Holding Brake
A brake that works against back driving to hold the positioner in
place under compression loads or tension.
Hysteresis
The opposing force accumulated in an elastic material or
mechanism after the outside forces acting on it have been changed
(e.g. the mechanical wind-up in the lead-screw assembly).
Jog
Moving or positioning a load in incremental steps.
Lead
The distance the leadscrew nut travels for every rotation of the
leadscrew.
Limit Switch
A switch that limits the travel or motion in a specific direction.
Linear Movement
Movement in a straight line.
Linear Position Accuracy
The error between the intended shift and real position attained by
a linear positioning component or stage system. The linear accuracy of
components and stage systems, which includes motor accuracy,
leadscrew accuracy, stage accuracy (pitch and yaw) and thermal
expansion, varies with complexity and number of components.
Linear Rate
Rate of movement of a linear component.
Load
The amount of force axially put on the positioner.
Max Velocity
The linear velocity the actuator will attain at a given motor rpm.
Maximum Static Load
The mechanical load limit of the actuator if recirculated oil or other
cooling method is used to allow higher than rated torque from the
motor.
Microstepping
The technique of electronically subdividing every complete step of
a stepping motor.
Multiplex System
12
A system that utilizes two lead-screws in order to actuate several
three-piece pump modules, the combination of which drives the pistons
in a linear motion to create displacement. Each system uses a
pneumatic rotary actuator to drive its main function.
Optical Encoder
A linear or rotary element that has alternating opaque and clear
spaces. Detectors calculate the light and dark changes, and the position
is determined by counting the amount of changes.
Resolution
The lowest exact positioning movement attainable from a system.
Stroke Length
The complete movement of the positioning table from complete
retraction to full extension.
Thrust
The complete force necessary to move a load, taking into account
friction, acceleration and gravity.
Unidirectional Repeatability
The capability of a system to return to an intended position, nearing
that position from a plus and minus direction.
Motors
• A.C. motors.
• D.C. motors.
• Stepper motors.
1. A.C. motors
13
A.C. motors are mainly used for producing large power outputs at a
fixed speed. Typically these are 1420 or 2900 rev/min. Such motors are
controlled by switching them on and off.
Lead screws are used to convert rotation into linear motion as shown.
Rotation screws the carriage back and forth along the lead screw.
2. D.C. motors
14
Direct current motors are more widely used in control applications and
they are usually referred to as SERVO MOTORS. These are covered in
detail later in the tutorial. The development of more powerful magnets
is improving the power to weight ratio but they are still not as good as
hydraulic motors in this respect. Servo motors usually have a
transducer connected to them in order to measure the speed or angle
of rotation. The diagram shows a typical arrangement
3. Stepper motors
Basically a stepper motor rotates a precise angle according to the
number of pulses of electricity sent to it. Because there is confidence
that the shaft rotates to the position requested, no transducer is
needed to measure and check the position and so they are common on
open loop systems.
There are 3 types of stepper motor in common use and these are:
15
1. The PERMANENT MAGNET TYPE.
2. The VARIABLE RELUCTANCE TYPE.
3. The HYBRID TYPE.
If the polarity of both pairs of poles are reversed the pattern will change
to S - N - S - N and the rotor will flip 45o to a new position of balance.
In order to obtain more steps, more pairs of poles are used but there
are only two windings. Reversing the polarity of both windings moves
the rotor on one step. Stepping is produced by simply reversing the
polarity.
16
When a current is applied to the stator windings, the rotor aligns itself
in the position of least magnetic reluctance. This position depends upon
the number of phases energized.
The rotor retains very little magnetism so there is no holding torque
when the current is removed. The number of steps is given by N = SR/
(S-R) where S is the number of stator slots and R the number of rotor
slots.
Hybrid motors are a combination of the last two types. Each pole is
divided into slots as shown. The rotor has two sets of slots, one behind
the other with one set offset to the other by 1/2 slot pitch. The rotor is
magnetized longitudinally. This produces a high resolution.
For a given motor the area, lengths and radius are constant so the
equation reduces to
T = k1 φ Ia ................ (1)
18
For a given motor in which the area and length may be considered
constant, the equation becomes
E = K2φ N ......................... (2)
All DC motors are based on these principles. The flux may be produced
by permanent magnetic poles or by separate coils called the FIELD
WINDINGS. The rotor in the diagram would be called the ARMATURE. It
is possible to have brushless motors and for the stator to be the
armature. A typical design is the use of two pairs of poles and many
loops on the rotor which are energized through the commutator.
19
Ea = 2πNT/Ia ........
(2a)
Or T = IaEa /2πN ........
(2b)
Ea = Va –
IaRa ................... (3)
Substitute for Ea N = (Va
- IaRa)/2πk1φ .......................... (4)
It follows that the torque and speed may be controlled by varying the
field current. This has an advantage that a relatively large power may
be controlled by a small field current and the power amplifier needed in
the control circuit is relatively small. The diagram shows the
relationship between torque and speed for constant field current.
Va - TRa /kt = N Ke
T = ( Va - Nke )kt/Ra
T = C1Va - C2N ........................... (7)
Or
Va = C3T + C4N ...........................
(8)
These are the equations commonly used to explain the steady state
characteristic of a DC motor with armature control.
So far you have studied motors with separate field and armature
windings and looked at the characteristics of these motors.
We will now study the characteristics of various motor configurations of
the type mainly used on large D.C. Machines. In the previous work it
was shown that
V = Ea + Ia Ra E = k1φ2πN = kNφ T = K1 φ Ia
21
Ea is the back e.m.f on the armature, φ is the flux per pole, T is the
torque and N the speed (rev/s).
Ea = V - IaRa
T = k1φ Ia so Ia = T/φk1
Ea = V - TRa/φk1 = k Nφ but φ is constant so everything is a constant
except T and N so for constant
electrical power this reduces to
T = C1 - C2 N
The compound motor is a cross between the other two with both a
parallel and series field winding. For constant
electric power, the Torque - speed characteristic
is between that of the other two.
FIELD CONTROL
ARMATURE CONTROL
The other important constants quoted for such motors are the Torque
constant kt and the e.m.f. constant ke. Torque is normally quoted in N
cm which is not a recommended SI unit and the shaft speeds are
quoted in 1000 rev/min.
24
DATA TABLES FOR MOTORS
When the motor is started, the speed is zero so there is no back e.m.f.
It follows that
V = Ia Ra
The starting current without protection would be V/Ra and this would
be very large. In addition to this, there will be a load with inertia
connected to the motor and a large current is needed to provide the
torque.
SERIES MOTOR
SHUNT MOTOR
COMPOUND MOTOR
Ti = I d2θ/dt2
T = TL + Tf + Kd dθ/dt + I d2θ/dt2
27
This will be explained in another tutorial. If the motor uses field control,
the electrical time constant is based on the field winding inductance
and resistance.
28
Solenoids
Definition of Solenoid
A solenoid is an electromechanical device that converts electrical
energy into linear or rotary mechanical motion.
29
Rotary solenoids operate on the same principle as linear solenoids
except that the axial movement of the armature is converted into
rotary movement by various mechanical devices. One of these is the
use of internal lands or ball bearings and slots or races that convert a
pull-in stroke to rotary or twisting motion.
30
Solenoids are the most common actuator components. The basic
principle of operation is there is a moving ferrous core (a piston) that
will move inside wire coil as shown in Figure 5.1. Normally the piston is
held outside the coil by a spring. When a voltage is applied to the coil
and current flows, the coil builds up a magnetic field that attracts the
piston and pulls it into the center of the coil. The piston can be used to
supply a linear force. Well known applications of these include
pneumatic values and car door openers.
Technical Considerations
Important factors to consider when selecting solenoids are their rated
torque/force, duty cycles, estimated working lives, performance curves,
ambient temperature range, and temperature rise. The solenoid must
have a magnetic return path capable of transmitting the maximum
amount of magnetic flux density with minimum energy input. Magnetic
flux lines are transmitted to the plunger or armature through the
bobbin and air gap back through the iron or steel shell. A ferrous metal
path is more efficient than air, but the air gap is needed to permit
plunger or armature movement. The force or torque of a solenoid is
inversely proportional to the square of the distance between pole
faces. By optimizing the ferrous path area, the shape of the plunger or
armature, and the magnetic circuit material, the output torque/force
can be increased . The torque/force characteristic is an important
solenoid specification. In most applications the force can be a minimum
at the start of the plunger or armature stroke but must increase at a
rapid rate to reach the maximum value before the plunger or armature
reaches the backstop. The magnetizing force of the solenoid is
proportional to the number of copper wire turns in its coil, the
magnitude of the current, and the presence of the magnetic circuit. The
pull force required by the load must not be greater than the force
developed by the solenoid during any portion of its required stroke, or
the plunger or armature will not pull in completely. As a result, the load
31
will not be moved the required distance. Heat buildup in a solenoid is a
function of power and the length of time the power is applied. The
permissible temperature rise limits the
magnitude of the input power. If constant voltage is applied, heat
buildup can degrade the efficiency of the coil by effectively reducing its
number of ampere turns. This, in turn, reduces flux density and
torque/force output. If the temperature of the coil is permitted to rise
above the temperature rating of its insulation, performance will suffer
and the solenoid could fail prematurely. Ambient temperature in excess
of the specified limits will limit the
and conduction. Heat can be dissipated by cooling the solenoid with
forced air from a fan or blower, mounting the solenoid on a heat sink, or
circulating a liquid coolant through a heat sink. Alternatively, a larger
solenoid than the one actually needed could be used .The heating of
the solenoid is affected by the duty cycle, which is specified from 10 to
100%, and is directly proportional to solenoid on time. The highest
starting and ending torque are obtained with the lowest duty cycle and
on time. Duty cycle is defined as the ratio of on time to the sum of on
time and off time. For example, if a solenoid is energized for 30 s and
then turned off for 90 s, its duty cycle is 30⁄120 = 1⁄4, or 25%.
: Types of solenoids
Open-Frame Solenoids
Box-Frame Solenoids
Box-frame solenoids have steel frames that enclose their coils on two
sides, improving their mechanical strength. The coils are wound on
phenolic bobbins, and the plungers are typically made from solid bar
stock .The frames of some box-type solenoids are made from stacks of
thin insulated sheets of steel to control eddy currents as well as keep
stray circulating currents confined in solenoids powered by AC. Box-
frame solenoids are specified for higher-end applications such as tape
decks, industrial controls, tape recorders, and business machines
because they offer mechanical and electrical performance that is
superior to those of C frame solenoids. Standard catalog commercial
box-frame solenoids can be powered by AC or DC current, and can have
strokes that exceed 0.5 in. (13 mm).
Tubular Solenoids
The coils of tubular solenoids have coils that are completely enclosed in
cylindrical metal cases that provide improved magnetic circuit return
and better protection against accidental damage or liquid spillage.
These DC solenoids offer the highest volumetric efficiency of any
commercial solenoids, and they are specified for industrial and
military/aerospace equipment where the space permitted for their
installation is restricted. These solenoids are specified for printers,
computer disk-and tape drives, and military weapons systems; both
33
pull-in and push-out styles are available. Some commercial tubular
linear solenoids in this class have strokes up to 1.5 in. (38 mm), and
some can provide 30 lbf (14 kgf) from a unit less than 2.25 in (57 mm)
long. Linear solenoids find applications in vending machines, photocopy
machines, door locks, pumps, coin-changing mechanisms, and film
processors.
Rotary Solenoids
Rotation continues until the balls have traveled to the deep ends of the
races, completing the conversion of linear to rotary motion.
34
This type of rotary solenoid has a steel case that surrounds and
protects the coil, and the coil is wound so that the maximum amount of
copper wire is located in the allowed space. The steel housing provides
the high permeability path and low residual flux needed for the efficient
conversion of electrical energy to mechanical motion. Rotary solenoids
can provide well over 100 lb-in. (115 kgf-cm) of torque from a unit less
than 2.25 in. (57 mm) long.
The flow of fluids and air can be controlled with solenoid controlled
valves. An example of a solenoid controlled valve is shown below . The
solenoid is mounted on the side. When actuated it will drive the central
spool left. The top of the valve body has two ports that will be
connected to a device such as a hydraulic cylinder. The bottom of the
valve body has a single pressure line in the center with two exhausts to
the side. In the top drawing the power flows in through the center to
the right hand cylinder port. The left hand cylinder port is allowed to
exit through an exhaust port. In the bottom drawing the solenoid is in a
new position and the pressure is now applied to the left hand port on
the top, and the right hand port can exhaust. The symbols to the left of
the figure show the schematic equivalent of the actual valve positions.
35
Valves are also available that allow the valves to be blocked when
unused.
II – Hydraulic Actuators
Hydraulic systems are used in applications requiring a large amount of
force and slow speeds. When used for continuous actuation they are
mainly used with position feedback .They also suffer from maintenance
problems (e.g. leakage of the hydraulic fluid, dirt/contamination of
fluid.) Hydraulic actuators may be linear, or rotary.
36
Hydraulic systems normally contain the following components :
1. Hydraulic Fluid .
2. An Oil Reservoir .
3. A Pump to Move Oil, and Apply Pressure .
4. Pressure Lines .
5. Control Valves - to regulate fluid flow .
6. Piston and Cylinder - to actuate external mechanisms .
2-way normally closed - these have one inlet, and one outlet. When
unenergized, the valve is closed. When energized, the valve will open,
allowing flow. These are used to permit flows.
2-way normally open - these have one inlet, and one outlet. When
unenergized, the valve is open, allowing flow. When energized, the
valve will close. These are used to stop flows. When system power is
off, flow will be allowed.
3-way normally closed - these have inlet, outlet, and exhaust ports.
When unenergized , the outlet port is connected to the exhaust port.
When energized, the inlet is connected to the outlet port. These are
used for single acting cylinders.
3-way normally open - these have inlet, outlet and exhaust ports. When
unenergized , the inlet is connected to the outlet. Energizing the valve
connects the outlet to the exhaust. These are used for single acting
cylinders .
3-way universal - these have three ports. One of the ports acts as an
inlet or outlet, and is connected to one of the other two, when
energized/unenergized. These can be used to divert flows, or select
alternating sources .
37
4-way - These valves have four ports, two inlets and two outlets.
Energizing the valve causes connection between the inlets and outlets
to be reversed. These are used for double acting cylinders.
Some of the ISO symbols for valves are shown below . When using the
symbols in drawings the connections are shown for the unenergized
state. The arrows show the flow paths in different positions. The small
triangles indicate an exhaust port.
Single acting cylinders apply force when extending and typically use a
spring to retract the cylinder. Double acting cylinders apply force in
both direction.
39
Schematic Symbols for Cylinders
40
- additional equipment is required for a pressurized air supply- linear
and rotatory actuators are available.
- dampers can be used to cushion impact at ends of cylinder travel.
When designing pneumatic systems care must be taken to verify the
operating location. In particular the elevation above sea level will result
in a dramatically different air pressure.
Some symbols for pneumatic systems :
41
• The flow control valve is used to restrict the flow, typically to slow
motions.
• The shuttle valve allows flow in one direction, but blocks it in the
other.
• The receiver tank allows pressurized air to be accumulated.
• The dryer and filter help remove dust and moisture from the air,
prolonging the life of the valves and cylinders.
42
Sensors
43
Introduction
Sensors convert physical phenomena to measurable signals , typically
voltages or currents .
•Acceleration .
•Tempreature.
•Light intensity .
•Sound .
Types of Sensors :
In this report we will focus only on the types mentioned below :
• Proximity Sensors
• Strain Gauge
•Thermocouple
44
Proximity Sensor
Definition of Proximity Sensor
It is a device to detect object with no contact, making use of changes in
a magnetic/ electric field.
Detection Mechanism
A proximity sensor create a net of electro/magnetic field and detects an
object which enters the field , just as a spider form its web and catches
its prey. The net is created by the magnetic lines originated from the
oscillation circuit. When a metallic object comes into the field, the
magnetic lines get disordered, which is transmitted to the oscillating
circuit .The oscillating circuit will detect the object approaching and
output the decision.
Working range
45
Classification
• Detection mode and principles
46
• Shape
47
Features of Proximity Sensor
Major Characteristics
(1) Effect according to materials of object
48
(2) Size of object and detection distance (Model E2E-XIR5E1)
Surface effect
Electric current flows equally in a conductor
when frequency is low (DC), but flows densely
on the surface and sparsely inside with high
frequency. The higher the magnetic transparent
ratio is, the higher this tendency is.
49
Whirling current flows deep inside of an object due to low transparent
ratio. Small anti-magnetic bundle occurs from the surface and inside as
well.
Therefore a proximity sensor can only detect an object within a short
distance.
- Steel
Whirling current flows densely on
the very surface due to high
transparent ratio. Therefore, large
anti-magnetic bundle the occurs
on surface. As a result a proximity
from the detect distance.
50
51
STRAIN GAUGE
INTRODUCTION
The strain gauge has been in use for many years and is the
fundamental sensing element for many types of sensors, including
pressure sensors, load cells, torque sensors, position sensors, etc.The
majority of strain gauges are foil types, available in a wide choice
of shapes and sizes to suit a variety of applications. They consist of a
pattern of resistive foil which is mounted on a backing material. They
operate on the principle that as the foil is subjected to stress, the
resistance of the foil changes in a defined way.
Strain gauges are sensing devices used in a variety of physical test and
measurement applications. They change resistance at their output
terminals when stretched or compressed. Because of this characteristic,
the gauges are typically bonded to the surface of a solid material and
measure its minute dimensional changes when put in compression or
tension. Strain gauges and strain gauge principles are often used in
devices for measuring acceleration, pressure, tension, and force. Strain
is a dimensionless unit,defined as a change in length per unit length.
Strain gauges have a characteristic gauge factor, defined as the
fractional change in resistance divided by the strain.Common gauge
resistance values typically range from 120 to 350(, but some devices
are as low as 30O or as high as 3 k).
Definition Of Strain
Strain is the amount of deformation of a body due to an applied force.
More specifically, strain (e) is defined as the fractional change in length,
as shown in Figure 1 below.
52
Figure 1. Definition of Strain
The metallic strain gauge consists of a very fine wire or, more
commonly, metallic foil arranged in a grid pattern. The grid pattern
maximizes the amount of metallic wire or foil subject to strain in the
parallel direction (Figure 2). The cross sectional area of the grid is
minimized to reduce the effect of shear strain and Poisson Strain. The
grid is bonded to a thin backing, called the carrier, which is attached
directly to the test specimen. Therefore, the strain experienced by the
test specimen is transferred directly to the strain gauge, which
responds with a linear change in electrical resistance. Strain gauges are
available commercially with nominal resistance values from 30 to 3000
Ω, with 120, 350, and 1000 Ω being the most common values.
53
Figure 2. Bonded Metallic Strain Gauge
It is very important that the strain gauge be properly mounted onto the
test specimen so that the strain is accurately transferred from the test
specimen, through the adhesive and strain gauge backing, to the foil
itself.
A fundamental parameter of the strain gauge is its sensitivity to strain,
expressed quantitatively as the gauge factor (GF). Gauge factor is
defined as the ratio of fractional change in electrical resistance to the
fractional change in length (strain):
54
Figure 3. Wheatstone Bridge
From this equation, it is apparent that when R1/R2 = R4/R3, the voltage
output VO will be zero. Under these conditions, the bridge is said to be
balanced. Any change in resistance in any arm of the bridge will result
in a nonzero output voltage.
55
Figure 4. Quarter-Bridge Circuit
Ideally, we would like the resistance of the strain gauge to change only
in response to applied strain. However, strain gauge material, as well as
the specimen material to which the gauge is applied, will also respond
to changes in temperature. Strain gauge manufacturers attempt to
minimize sensitivity to temperature by processing the gauge material
to compensate for the thermal expansion of the specimen material for
which the gauge is intended. While compensated gauges reduce the
thermal sensitivity, they do not totally remove it.
By using two strain gauges in the bridge, the effect of temperature can
be further minimized. For example, Figure 5 illustrates a strain gauge
configuration where one gauge is active (RG + DR), and a second gauge
is placed transverse to the applied strain. Therefore, the strain has little
effect on the second gauge, called the dummy gauge. However, any
changes in temperature will affect both gauges in the same way.
Because the temperature changes are identical in the two gauges, the
ratio of their resistance does not change, the voltage VO does not
change, and the effects of the temperature change are minimized.
56
Figure 6, yields an output voltage that is linear and approximately
doubles the output of the quarter-bridge circuit.
Finally, you can further increase the sensitivity of the circuit by making
all four of the arms of the bridge active strain gauges in a full-bridge
configuration. The full-bridge circuit is shown in Figure 7.
The equations given here for the Wheatstone bridge circuits assume an
initially balanced bridge that generates zero output when no strain is
applied. In practice however, resistance tolerances and strain induced
by gauge application will generate some initial offset voltage. This
initial offset voltage is typically handled in two ways. First, you can use
a special offset-nulling, or balancing, circuit to adjust the resistance in
the bridge to rebalance the bridge to zero output. Alternatively, you can
measure the initial unstrained output of the circuit and compensate in
software.
The equations given above for quarter, half, and full-bridge strain
gauge configurations assume that the lead wire resistance is negligible.
While ignoring the lead resistances may be beneficial to understanding
the basics of strain gauge measurements, doing so in practice can be a
major source of error. For example, consider the 2-wire connection of a
57
strain gauge shown in Figure 8a. Suppose each lead wire connected to
the strain gauge is 15 m long with lead resistance RL equal to 1 W.
Therefore, the lead resistance adds 2 W of resistance to that arm of the
bridge. Besides adding an offset error, the lead resistance also
desensitizes the output of the bridge.
You can compensate for this error by measuring the lead resistance RL
and accounting for it in the strain calculations. However, a more difficult
problem arises from changes in the lead resistance due to temperature
fluctuations. Given typical temperature coefficients for copper wire, a
slight change in temperature can generate a measurement error of
several me.
Using a 3-wire connection can eliminate the effects of variable lead wire
resistance because the lead resistances affect adjacent legs of the
bridge. As seen in Figure 8b, changes in lead wire resistance, R2, do not
change the ratio of the bridge legs R3 and RG. Therefore, any changes in
resistance due to temperature cancel each other.
Heating
Resistive heating in strain gauges also should be considered because
the gauges respond to temperature as well as stress. In most standard
circuits, the heat that each gauge dissipates is less than 100 mW, so it's
not usually a problem. This is especially
true when the strain gauge is bonded to a material that conducts heat
quickly, such as metal. However, because most wood, plastic, or glass
materials do not conduct heat away as rapidly, use the lowest
58
excitation voltage possible without introducing noise problems. Also,
heat can become a problem when the strain gauges are uncommonly
small, or numerous gauges occupy a limited space.
Calibration
The signal-conditioning module also typically provides a shunt
calibration feature. See Figure 7. It lets users switch their own shunt
resistors into either one of the two lower legs of the bridge under
software control. For example, a shunt resistor can be calculated to
simulate a full load. Applying a shunt resistor is a convenient way to
simulate an unbalance without having to apply a physical load. For any
balanced bridge, a specific resistor can be connected in parallel with
one of the four bridge elements to obtain a predictable unbalance and
output voltage.
59
Thermocouple
INTRODUCTION
In his discovery, Seebeck also concluded that any two metals can be
used. However, the magnitude and direction of the generated current
are functions of the magnitude of the temperature difference between
the junctions and the thermal properties of the metals used in the
circuit. Therefore, not every combination of metals is acceptable for
thermocouple usage.
Definition Of Thermocouple
Thermocouples are pairs of dissimilar metal wires joined at least at one
end, which generate a net thermoelectric voltage between the the open
pair according to the size of the temperature difference between the
ends, the relative Seebeck coefficient of the wire pair and the
.uniformity of the wire-pair relative Seebeck coefficient
60
THERMOELECTRIC CHARACTERISTICS
A thermocouple should have thermoelectric characteristics such that
the electromotive force (emf) produced per degree of temperature
change is sufficient to be detected by standard measuring instruments.
The device must also be capable of withstanding temperature extremes
for prolonged periods, rapid temperature changes, and corrosive
atmospheres while exhibiting reproducibility and a high degree of
accuracy.
Temperat
Temperatu ANSI
ure range Toleranc Toleranc IEC BS
re range Colou
Type °c e class 1 e class 2Colour Colour
°c (short r
(continuo (°c) (°c) code code
term) code
us)
-40 to -40 to
+375 ± +333 ±
1.5 °c, 2.5 °c,
-180 to
K 0 to +1100 375 to 333 to
+1300
1000 ± 1200 ±
0.004*[t]° 0.0075*[t
c ]°c
-40 to -40 to
+375 ± +333 ±
1.5 °c, 2.5 °c,
-180 to
J 0 to +700 375 to 333 to
+800
750 ± 750 ±
0.004*[t]° 0.0075*[t
c ]°c
-40 to -40 to
+375 ± +333 ±
1.5 °c, 2.5°c,
-270 to
N 0 to +1100 375 to 333 to
+1300
1000 ± 1200 ±
0.004*[t]° 0.0075*[t
c ]°c
61
0 to
+1100 ±
0 to +600
1.0°c,
± 1.5 °c,
1100 to Not
-50 to 600 to
R 0 to +1600 1600 ± define
+1700 1600 ±
(1+0.003 d.
0.0025*[t
(t-
]°c
1100))*[t]
°c
0 to
+1100 ±
0 to +600
1.0 °c,
± 1.5°c,
1100 to Not
-50 to 600 to
S 0 to 1600 1600 ± define
+1750 1600 ±
(1+0.003 d.
0.0025*[t
(t-
]°c
1100))*[t]
°c
No No
600 to
standa standa Not
+200 to Not 1700 ±
B 0 to +1820 rd use rd use define
+1700 Available 0.0025*[t
copper copper d.
]°c
wire wire
-40 to
-40 to
+125 ±
+133 ±
0.5°c,
-185 to -250 to 1.0°c,133
T 125 to
+300 +400 to 350 ±
350 ±
0.0075*[t
0.004*[t]°
]°c
c
-40 to + -40 to
375 ± +333 ±
1.5°c, 2.5°c,
E 0 to +800 -40 to +900 375 to 333 to
800 ± 900 ±
0.004*[t]° 0.0075*[t
c ]°c
For further information on thermocouple types & other colour codes see
Appendix 1.
LOCATION
63
When a thermocouple is located too close to the workload, there is a
substantial delay in sensing the proper control point and the result is
overshooting the temperature. In most cases, it is better to be too close
to the heaters than the workload as once a temperature point is
passed, it becomes difficult to cool the workload unless a forced cooling
system is used. Two thermocouples connected in parallel could be
used, one located near the heaters and the other near the workload.
Both will balance these two factors and provide closer control.
64
COMPENSATION
65
In the other method, the cold junction is situated in a precisely
controlled temperature above ambient, as shown below. In this case,
ambient compensation is not necessary. The mechanical zero
adjustment is set at the cold junction temperature being maintained.
The normal temperature being maintained is 150 to 200 degrees F at
the cold junction.
66
Each millivolt measuring instrument is calibrated for both the type of
thermocouple being used and the length and gauge of the lead wire.
The thermocouple lead wire is in effect in series with the thermocouple
wire and the meter movement. Using wrong thermocouple lead wire
can be avoided by simply following the color-coding used by all
manufacturers (Table, below). A solid state controller can be used with
up to 100 ohms of external resistance without having to be
recalibrated.
Calibration symbols and color codes for thermocouple and extension wire
Thermocou White Re
J -- Iron + Constantan - Brown
ple (Magnetic) d
Re
Extension JX -- Iron + White Constantan - Black
d
Thermocou T -- Re
+ Blue Constantan - Brown
ple Copper d
TX -- Re
Extension + Blue Constantan - Blue
Copper d
Thermocou E -- Re
+ Tan Constantan - Brown
ple Chromel d
EX -- Re
Extension + Tan Constantan - Brown
Chromel d
Thermocou K -- Alumel Re
+ Yellow - Yellow
ple chromel (Magnetic) d
Thermocou S -- PT
+ -- Platinum - -- --
ple 10% RH
Thermocou R -- PT
+ -- Platinum - -- --
ple 13% RH
SX -- Re
Extension + Black Alloy 11 - Green
Copper d
200 deg 400 deg 800 deg 1600 deg 2500 deg
68
F F F F F
Chromel-
1.13 1.33 1.7 2.5 ----
Constantan
Plat. 10% RH -
1.13 1.34 1.83 2.67 3.50
Platinum
Plat. 13% RH -
1.13 1.33 1.80 2.60 3.40
Platinum
69
0-2400 deg F PLT/PLT + 10% RH (14.32% at 20
Ohms)
THERMOCOUPLE CONNECTION
70
in, an unattended process will not overheat because of the loss of
control.
REFERENCE JUNCTIONS
72
A thermocouple's output is based on the difference in temperature
between the measuring junction (hot junction) and the reference
junction (cold junction). See Figure A.
ICE BATH
One of the most common reference junctions is the ice bath. The ice
bath is made up of a mixture of melting shaved ice and water. The ice
bath is a convenient and inexpensive way to achieve an ice point, it can
be reproduced with ease and with exceptional accuracy. Junctions
formed between the thermocouple materials and instrument leads can
be simply immersed into the slush mixture, or alternatively glass "U"
tubes containing a quantity of mercury approximately 3/4" to 1" depth
can be placed into the slush mixture. Quick electrical connection can
then be made between thermocouple and instrument leads through the
mercury. (Figure B).
Note: An improperly used ice bath can result in serious errors. The
largest error which is likely to occur arises due to melting of the ice at
the bottom of the bath until the reference junctions are below the ice
level and surrounded by water alone. This water may be as much as 7
degrees F above the ice point.
ELECTRONIC COMPENSATION
73
This method employs a compensation circuit containing a source of
current and a combination of fixed resistors and a temperature
sensitive resistor (TSR). This device can be designed to produce similar
EMF to that of the thermocouple being calibrated. The Electronic
Compensator will make EMF compensations to the thermocouple circuit
based in the difference in EMF from 32 to ambient temperature.
MEASURING INSTRUMENTS
REFERENCE THERMOMETERS
LIQUID-IN-GLASS THERMOMETERS
74
achieved, an individual thermometer must cover a very narrow
temperature range so that the graduation intervals can be as large as
possible. A further disadvantage of the liquid-in-glass thermometer is
that because of their fine graduations reading errors are a distinct
possibility. Taylor Instruments offers Superior Grade Certified
Secondary Reference Thermometers individually or in matched Celsius
or Fahrenheit sets, which Branom stocks.
JUNCTION LOCATION
MEASUREMENT
Once the reading is taken, raise the test temperature to the next higher
temperature, first removing the test assembly from the temperature
source, or advance the test assembly to the next temperature source.
Allow the temperature source and the test assembly to stabilize as
before, and take a second set of readings at the new temperature.
76
In all cases take the reading in sequence from the lowest to the highest
temperature. A base metal reference standard shall be used for one
series of temperature changes only.
77
CALIBRATION PROCEDURE
FLUIDIZED BEDS
Stirred liquid baths operate on the same principal as fluidized beds and
are an excellent means of establishing closely controlled temperatures.
Although stirred liquid baths using molten salts or liquid tin are
available with a temperature range as high as 932 degrees F., the most
78
common application is in the range of ambient to 500 degrees F.
utilizing silicone oil as the bath material.
Figure A:
79
Figure B:
Figure C:
Figure D:
80
Applications
Thermocouples are most suitable for measuring over a large
temperature range, up to 1800 K. They are less suitable for applications
where smaller temperature differences need to be measured with high
accuracy, for example the range 0–100 °C with 0.1 °C accuracy. For
such applications, thermistors and RTDs are more suitable.
Steel Industry
Many gas-fed heating appliances like ovens and water heaters make
use of a pilot light to ignite the main gas burner as required. If the pilot
light becomes extinguished for any reason, there is the potential for un-
combusted gas to be released into the surrounding area,
thereby creating both risk of fire and a health hazard. To prevent such a
danger, some appliances use a thermocouple as a fail-safe control to
sense when the pilot light is burning. The tip of the thermocouple is
placed in the pilot flame. The resultant voltage, typically around 20 mV,
operates the gas supply valve responsible for feeding the pilot. So long
as the pilot flame remains lit, the thermocouple remains hot and holds
the pilot gas valve open. If the pilot light goes out, the temperature will
fall along with a corresponding drop in voltage across the thermocouple
leads, removing power from the valve. The valve closes, shutting off
the gas and halting this unsafe condition.
Appendix 1
Thermocouple Types
The selection of the optimum thermocouple type (metals used in their
construction) is based on application temperature, atmosphere,
83
required length of service, accuracy and cost. When a replacement
thermocouple is required, it is of the utmost importance that the type of
thermocouple type used in the replacement matches that of the
measuring instrument. Different thermocouple types have very
different voltage output curves. It is also required that thermocouple or
thermocouple extension wire, of the proper type, be used all the way
from the sensing element to the measuring element. Large errors can
develop if this practice is not followed.
The thermocouple types are listed below with the positive electrode
first, followed by the negative electrode.
84
B, R, and S
85
M
Type M thermocouples use a nickel alloy for each wire. The positive
wire contains 18% molybdenum while the negative wire contains 0.8%
cobalt[1]. These thermocouples are used in the vacuum furnaces for the
same reasons as with type C. Upper temperature is limited to 1400 °C.
Though it is a less common type of thermocouple, look-up tables to
correlate temperature to EMF (milli-volt output) are available.
French NFE:
German DIN:
86
87