Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
BMS
Gateway
pr
int
ou
t
lin
ar
al
ar
al
2
rx
tx
se
re
Serial module
chiller
compact
4899
Service Manual
BMS option for Daikin water chillers
Gateway Address card
EKBMSMBA
EKBMSBNA
EKAC10A/30A/60A/120A
ESIE9903
Table of Contents
1
1
Introduction
1.1 About This Manual ........................................................................................................ v
1.2 Building Management System (BMS) .......................................................................... vi
Part 1
System Outline
1
System Outline
1.1 What Is in This Chapter?........................................................................................... 1-3
1.2 Communication Outline............................................................................................. 1-4
1.3 Product Range .......................................................................................................... 1-6
1.4 Protocol and Data Transfer ....................................................................................... 1-7
1.5 Outline of the Gateway.............................................................................................. 1-8
1.6 Outline of the Address Card in kit EKAC10A .......................................................... 1-10
1.7 Outline of the Address Cards in the EKAC30A/60A/120A kits................................ 1-11
4
5
Table of Contents
ESIE9903
Part 2
Installation
1
3
4
Configuration
2.1 What Is in This Chapter? .........................................................................................2-13
2.2 Gateway Hardware Configuration............................................................................2-14
2.3 Gateway Software Configuration (MSDOS program) ............................................2-17
2.4 How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller .2-19
2.5 Settings: Direct and User Parameters in the Small Daikin Controller ......................2-20
2.6 How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller .2-22
2.7 e User Settings Menu in the Large Daikin Controller ............................................2-23
ii
Table of Contents
ESIE9903
Part 3
Functional Description
1
General
1.1 What Is in This Chapter?........................................................................................... 3-3
1.2 Generalities on the Protocols .................................................................................... 3-4
1.3 References to ASHRAE Manual of the BACnet Protocol.......................................... 3-5
4
3
Database
3.1 What Is in This Chapter?......................................................................................... 3-11
3.2 Database creation ................................................................................................... 3-12
3.3 The Address Card EKAC10A Database ................................................................. 3-16
3.4 The Address Card EKAC30A Database ................................................................. 3-18
3.5 The Address Card EKAC60A Database ................................................................. 3-21
3.6 The Address Card EKAC120A Database ............................................................... 3-24
Table of Contents
iii
ESIE9903
Part 4
Troubleshooting
1
Troubleshooting
1.1 What Is in This Chapter? ...........................................................................................4-3
1.2 Fault Indications.........................................................................................................4-4
1.3 Troubleshooting .........................................................................................................4-6
3
4
Appendix A
Drawings
Index
iv
Table of Contents
ESIE9903
Introduction
Introduction
1.1
Introduction
The purpose of the Daikin Gateway and address cards is to connect the Daikin water chillers to a larger
Building Management System (BMS).
There are two different Gateways:
The other card is used in the EKAC30A, EKAC60A and EKAC120A kits.
3
4
Before starting up the system for the first time, ensure it has been properly installed.
You will find the following tools at the back of the manual:
Usage of the
manual
The present manual gives you all the information you need to do the set up and the troubleshooting
related to the BMS option for Daikin water chillers. It is intended for and should only be used by
qualified engineers. It is not intended to replace technical know-how acquired through training and
experience.
Using icons
Icons are used to attract the attention of the reader to specific information. The meaning of each icon
is described in the table below:
Icon
Type of
information
Note
Description
A note provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
Caution
Warning
Reference
Introduction
1.2
ESIE9903
Introduction
As buildings, plants or other sites become too large to control manually, the need for automatic
distance control becomes more important. Building Management Systems (BMS) were developed to
have a centralized overview of complete sites.
In general, control of lights, elevators, water supply, air conditioning, power consumption, etc. can be
controlled by one control system.
Communication
To implement correct communication between the connected subsystems and the control system, the
same communication protocol must be used.
The Daikin BMS option makes it possible to connect the Daikin chillers to a larger control system. The
tools necessary for this communication are the Gateway and the address cards.
After installing address cards and Gateway, the BMS must be programmed to be able to control and
monitor the chillers through the Gateway. To enable this configuration, individual parameters and
relative addresses of the chillers are described in this manual.
Illustration
BMS
...
5
Gateway
pr
Serial module
chiller
compact
Daikin chiller
Daikin chiller
Daikin chiller
vi
int
ou
t
lin
alar
1
alar
2
rx
tx
re
se
Gateway
ESIE9903
1
Part 1
System Outline
Introduction
The purpose of this part is to describe the communication network outline and the outline of the
individual parts.
Overview
See ...
1 System Outline
page 1-3
3
4
5
11
ESIE9903
11
3
4
5
12
ESIE9903
System Outline
Part 1
1
1
System Outline
1.1
Introduction
Overview
The purpose of this chapter is to display a communication network example, to display the Gateway
and address card outline and to display the applicable Daikin chillers software versions.
See ...
page 1-4
page 1-6
page 1-7
page 1-8
page 1-10
page 1-11
13
System Outline
11
1.2
ESIE9903
Communication Outline
Introduction
The communication between Gateway and address cards is possible in Carel protocol. The
communication between Gateway and BMS is possible in Modbus-Jbus or BACnet protocol.
The chillers, address cards and the Gateway are Daikin parts. The other equipment must be field
supplied.
Communication
outline example
water supply
lights
elevators
...
Modbus-Jbus or
BACnet protocol
Gateway
Gateway
t
ou
nt
e
pri
lin
2
1
rm
rm
ala
ala
rx
tx
t
se
re
Serial module
chiller
compact
EUWY10HCW1 or
EUWA12HDZW1 or ...
Address card
EKAC10A
Address card
EKAC30A/60A
Configuration
PC
Carel protocol
EUWA35HDZW1 or
EUW*100KXY1 or
EUWAT50KAY1 or ...
EUWA200KX or
EUW(*)120KX or ...
14
Address card
EKAC120A
ESIE9903
Parts and
description
System Outline
The table below gives a description of the different parts of the communication outline:
Part
Description
BMS
Gateway
The Gateway is necessary as an interface between the chillers and the BMS.
It translates the Carel protocol, which is used by the address cards to the
Modbus-Jbus or BACnet protocol, used by the BMS. Refer to Outline of the
Gateway on page 1-8.
Address Card
EKAC10A
Address card
EKAC30A/60A
Address Card
EKAC120A
The EKAC120A are two small electronic boards that must be attached to the
two electronic boards of the chiller. It enables the chiller to communicate with
the Gateway. Refer to Outline of the Address Cards in the
EKAC30A/60A/120A kits on page 1-11.
Configuration PC
3
4
5
15
System Outline
11
1.3
ESIE9903
Product Range
Introduction
From this series onwards, all Daikin chillers can be connected to a supervisory BMS.
To make it possible to connect 512HP chillers to a BMS system, a complete redesign of the switchbox
and the controller had to be done. This means that not on all chillers 512HP BMS is applicable.
The only changes for the larger chillers were made in the software. During the first year of production,
the chillers were not equipped with BMS-applied software. To ensure that the chiller is usable for the
BMS the software version must be checked first.
To change the EPROM for the correct software, refer to "Procedure for the Changing of the PCB" in
the relevant Daikin chiller service manual.
Address cards
The table below displays the product range of the address cards:
Address card kit
name
Applicable chillers
Software version
Number of
addresses
per chiller
EKAC10A
EUWA5-12H(C/D)(Z)
EPDAIECHOA
V2.012 or later
EPDAIECHLA
V2.012 or later
EUWY5-10H(C/D)
EKAC30A
EUWA15-30(35)HD(Z)
EUWY15-30HD
EKAC60A
EUWA*40-60KA
EUWA*40-60KAX
EKAC120A
EUW*40-100KX
EPDAIECHWA
V2.012 or later
EUWA*80-120KA
EPDAIECHPA
V2.012 or later
EUWA*80-120KAX
EUWA*160-200KX
EUW*120-200KX
Gateway
16
EPDAIECHZA
V2.012 or later
Supported protocol
Communication is possible
with maximum ... addresses.
EKBMSMBA
Modbus-Jbus
16
EKBMSBNA
BACnet
ESIE9903
1.4
System Outline
Introduction
BACnet and
Modbus-Jbus
differences
Address of the
Gateway
The communication between the Daikin chillers and the supervisory BMS is achieved in two steps with
a different communication protocol:
There are two major differences between the BACnet system and the Modbus-Jbus system:
BACnet system
Modbus-Jbus system
The Gateway can be identified by the supervisor through the assignment of a univocal address within
the Modbus-Jbus and the BACnet network. The address of the Gateway is programmable during the
configuration.
3
4
Master-slave
The management of the communication occurs in accordance with a master-slave structure in polling,
where the Gateway is the master and the address cards are the slaves.
The variable
database of each
address card
The chillers variable databases are used as the point of reference for the supplier of the supervisory
BMS to assign a suitable meaning to the variables.
The variables can be read and/or written by the supervisory BMS according to the connected chiller
and/or the application program being used.
The supervisory BMS cant assign a value to a variable in real mode. The command would be
ineffective.
The variables requested from the supervisory BMS, but not available in the chiller with installed
address card, are sent from the Gateway to the supervisory BMS with the value 0. The supervisory
BMS will have to manage them properly.
Refer to Database on page 3-11.
17
System Outline
11
1.5
ESIE9903
Introduction
The Gateway is the interface between the chillers address cards communicating in Carel protocol and
a supervisory BMS communicating in Modbus-Jbus or BACnet protocol.
The Gateway should be installed indoors, next to the BMS.
Gateway kit
Illustration
one Gateway
one PC diskette with an MS-DOS-formatted program for the initial configuration of the Gateway
The illustrations below display a general overview of the Gateway and its dimensions.
DIMENSIONS
re
se
t
2
18
tx
y
ewa
Gat
pr
in
to
ut
lin
e
20
ay
rx
52
226
1
al
ar
m
Gatew
al
ar
m
130
20
105.4
FRONT VIEW
166
7
REAR VIEW
Gateway
18
1
2
m
m
ar
ar
al
al
rx
tx
t
se
re
modem
config.
rs422/485
Carel Net.
cod.
t
ou
e
int
pr
lin
relay
fuse
Function
print out
No function
reset
ESIE9903
System Outline
Colour
line
yellow
alarm 1
red
alarm 2
red
rx
green
Communication is OK (flashing)
tx
green
Communication is OK (flashing)
Connections
Technical data
Connector name
Type
Connect to ...
modem
9-pin
male
RS-422/485
9-pin
female
config.
9-pin
male
Configuration PC or terminal
Carel Net.
9-pin
female
fuse
page 2-16
Refer to ...
240 VAC factory standard power supply (can be changed into 24 VAC or 120 VAC (1))
19
System Outline
11
1.6
ESIE9903
Introduction
The address card EKAC10A will enable the chillers EUWA5-12H(C/D)(Z) and EUWY5-10H(C/D) to
communicate with the Gateway.
Illustration
The illustration below shows the dimensions of the address card EKAC10A.
Serial module
88
compact
70
44
chiller
Connections on the
address card
64
The address card, installed on the chillers DIN rail (1), has to be connected to:
110
ESIE9903
1.7
System Outline
Introduction
The address card in the EKAC30A/60A/120A kits will enable the Daikin chillers to communicate with
the Gateway.
The table below gives the address card kits and the applicable chillers:
The address card kit ...
consist of ...
Applicable chillers
EKAC30A
EUWA15-30HD(Z)
EUWY15-30HD
EKAC60A
EKAC120A
Illustration
EUWA*40-60KA
EUWA*40-60KAX
EUW*40-100KX
EUWA*80-120KA
EUWA*80-120KAX
EUWA*160-200KX
EUW*120-200KX
The illustration below shows the dimensions of the address cards EKAC30A/60A/120A.
RX-/TX-
RX+/TX+
GROUND
M1
43
JS2
Connections into
the serial line
70
To connect the address card into the serial line the following connections have to be made:
from the field rail to the Gateway or another address card in the serial line (2).
(1) Refer to Connecting the Address Card EKAC30A/60A/120A to the Field Rail on page 2-9.
(2) Refer to Connecting an Address Card in the Serial Line on page 2-4.
111
System Outline
ESIE9903
11
3
4
5
112
ESIE9903
4
Part 2
Installation
Introduction
The purpose of this part is to tell you how to install, connect and configurate the system. The chillers
set up may differ slightly depending on the model.
2
3
Refer to the relevant Daikin chiller service manual if the screens described in this manual differ too
much from the screens on the chillers controller.
Overview
See ...
page 2-3
2 Configuration
page 2-13
Part 2 Installation
21
ESIE9903
1
2
3
4
5
22
Part 2 Installation
ESIE9903
Part 2
1
1
2
1.1
Introduction
The purpose of this chapter is to tell you how to set up the system. The troubleshooting chapter refers
to this chapter to check correct installation and wiring.
Precautions
Observe the following precautions:
Do not touch the electronic components with your fingers when manipulating internal jumpers.
Thus, you will prevent stray currents, which could irreparably damage the components.
Earth the Gateway casing to the stud identified by the appropriate yellow label.
Connect all wires correctly because erroneous connection could damage the entire system.
Ensure that the Gateway is switched off prior to inserting the cables into the connectors.
Strictly follow the instructions on the use of the relevant program during the configuration phase.
Keep the communication cables to link the chillers away from power cables to avoid interference.
Before installing
the Gateway
Before installing the Gateway ensure you have installed the address cards correctly. Follow the
instructions in the installation manuals of the address cards or use the pages listed in the table below.
Overview
Part 2 Installation
Topic
See ...
page 2-4
page 2-5
page 2-6
page 2-7
page 2-8
page 2-9
page 2-10
page 2-11
23
4
5
1.2
ESIE9903
Introduction
An address card (EKAC10A) or the field rail of an address card (EKAC30A/60A/120A) can be
connected to:
the Gateway
The serial line must be terminated with the resistor (120 1/4 W) between the TX/RX+ and
TX/RX- terminals of the address card situated at the end of the network.
Example
The illustration below shows you a possible serial line connection to the Gateway.
3
RX-/TX-
GROUND
RX+/TX+
EKAC10A
Gateway
to serial line
GND TX+RX+ TX-RX1 2 3
Serial module
chiller
compact
modem
config.
rs422/485
Carel Net.
relay
fuse
45
EKAC30A
screw connector
197198199
9-pole male
field rail connection
5
Connecting an
address card in the
serial line
The table below shows where address cards must be connected in the serial line:
If the chiller is
If you have to connect two address cards or field rails, use AWG20 or AWG22 shielded couple type
cables.
Connections
24
EKAC10A
EKAC30A/60A/120A
9-pole male
screw connectors
field rail
1. GND
1. GND
197. GND
4. TX+
2. RX+
198. RX+
5. TX-
3. RX-
199. RX-
Part 2 Installation
ESIE9903
1.3
Introduction
Before the address card EKAC10A can be connected in the serial line, the EKAC10A module must be
installed on the chillers DIN-rail.
Installing the
address card
The illustration below shows you how to install the address card EKAC10A.
module
Serial
chiller
ct
compa
Installation
procedure
Removing the
address card
Part 2 Installation
Follow the steps in the table below to install the address card:
Step
Action
Place the address card on the upper side of the omega rail.
Push the bottom side of the address card until you hear it click into place.
The address card is now locked onto the omega rail.
4
5
Follow the steps in the table below should you wish to remove the address card:
Step
Action
Release the grey clip at the bottom of the address card using a screwdriver.
25
1
2
1.4
ESIE9903
Introduction
Installation
procedure
Follow the steps in the table below to connect the address card to the controller:
Step
Action
Illustration
4
5
26
Part 2 Installation
ESIE9903
1.5
Introduction
The address card EKAC10A must be connected to the chillers transfo for power supply.
Illustration
The illustration below shows you how to connect the address card to the transfo.
2
12 11
G G0
power supply
Serial module
chiller
compact
50 51
fuse
50 51
Installation
procedure
Part 2 Installation
Follow the steps in the table below to connect the address card to the transfo:
Step
Action
Connect screw connection 11 G0 on the address card to terminal 50 on the main rail. Use
the supplied unfused connection wire.
Connect screw connection 12 G on the address card to terminal 51 on the main rail. Use
the supplied fused connection wire.
27
1
2
1.6
ESIE9903
Introduction
Before the address card can be connected in the serial line, first it must be installed on the PCB(s).
Installing the
address card
The illustration below shows you how to install the address card EKAC30A/60A/120A.
Installation
procedure for
EKAC30A/60A
Follow the steps in the table below to install the address card:
3
4
5
Installation
procedure for
EKAC120A
Connections
between PCB A and
PCB B (EKAC120A)
28
Step
Action
Handle the address card by its edges as indicated in the illustration above.
Carefully place the address card with the socket into the 7-pin PCB header.
Units with two circuits have two PCBs. You have to install an address card on each PCB.
Follow the steps in the table below to install the address card:
Step
Action
Handle the address card by its edges as indicated in the illustration above.
Carefully place the address card with the socket into the 7-pin PCB header (PCB A).
Connect the address card of PCB A to the address card of PCB B as listed below. Always
use the same screw connectors.
PCB A and PCB B of the chillers with 2 circuits must be connected as listed below:
PCB A
wire colour
PCB B
GROUND
red
GROUND
RX+/TX+
white
RX+/TX+
RX-/TX-
brown
RX-/TX-
Part 2 Installation
ESIE9903
1.7
EKAC30A/60A to
the field rail
The figure below shows you how to connect the address card EKAC30A/60A to the field rail.
RX-/TX-
RX+/TX+
The address card EKAC30A/60A/120A has to be connected to the field rail and this field rail has to be
connected in the serial line.
GROUND
Introduction
3
4
197198199
The figure below shows you how to connect the address card EKAC120A of PCB B to the field rail.
RX-/TX-
PCB B
RX+/TX+
PCB A
GROUND
EKAC120A of
PCB B to the field
rail
197198199
Connections of the
EKAC30A/60A/120A
Part 2 Installation
wire colour
GROUND
grey
197
RX+/TX+
white
198
RX-/TX-
brown
199
29
1
2
1.8
ESIE9903
Introduction
To configurate the Gateway, you must first make a connection between the Gateway and the
configuration computer. Disconnect the link to the PC after configuration.
Illustration
The illustration below shows you how to connect the Gateway to the configuration computer.
25-pin
73
Configuration PC
Gateway
2
female
9-pin
female
52
modem
config.
rs422/485
Carel Net.
relay
fuse
35
Different cables
The configuration computer connection to the Gateway is made via the 9-pin male connector at the
back of the Gateway labelled config.. Two different cables can achieve connection:
a cable with one 9-pin female connector (to the Gateway) and one 25-pin female connector (to the
computer).
A program on a disk delivered with the kit can start the initial configuration once the cable connects
the Gateway to the computer.
Refer to Gateway Software Configuration (MSDOS program) on page 2-17.
210
2. TX
2. RX
3. RX
3. TX
7. GND
5. GND
3. TX
2. RX
2. RX
3. TX
5. GND
5. GND
Part 2 Installation
ESIE9903
1.9
Introduction
Illustration RS-232
There are two possibilities for connecting the BMS to the Gateway:
using the RS-232 standard (for BMS using BACnet or Modbus-Jbus protocol)
using the RS-485 standard (only for BMS using Modbus-Jbus protocol).
9-pin
female
52
2
Gateway
modem
config.
rs422/485
Carel Net.
relay
fuse
35
RS-232 connection
(Modbus-Jbus and
BACnet)
The RS-232 connection to the supervisory BMS in Modbus-Jbus and BACnet is standard. The
Gateway using the BACnet protocol has no other options to make a connection with the BMS.
Make the RS-232 connection at the Gateway side to the 9-pin male connector labelled modem.
A 25-pin female
connector
Part 2 Installation
2. TX
2. RX
3. RX
3. TX
7. GND
5. GND
2. RX
3. TX
3. TX
2. RX
5. GND
5. GND
211
Illustration RS-485
ESIE9903
2
3
Gateway
RS-485 connection
(only for
Modbus-Jbus)
45
modem
config.
rs422/485
Carel Net.
relay
fuse
9-pin
male
For connection between Gateway and BMS using the Modbus-Jbus protocol the possible connections
are listed below:
Supervisory BMS
1. GND
4. TX+/RX+
5. TX-/RX-
212
Part 2 Installation
ESIE9903
Configuration
Configuration
2.1
Introduction
The purpose of this chapter is to tell you how to configure the Gateway and how to address the chillers
with the controller.
Overview
2
3
Topic
See ...
page 2-14
page 2-17
2.4 How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller
page 2-19
2.5 Settings: Direct and User Parameters in the Small Daikin Controller
page 2-20
2.6 How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller
page 2-22
page 2-23
4
5
Part 2 Installation
213
Configuration
2.2
Introduction
ESIE9903
to determine which connections towards the BMS and to the address cards there are used
To enable the connections that you want the Gateway to use, you have to set the jumpers A, B, C and
D on the Gateway PCB according to the table below:
place
jumper
in position
12
Modbus-Jbus or
BACnet
RS-422/485 serial
port towards the
BMS
23
Modbus-Jbus or
BACnet
12
Modbus-Jbus
communication from
the Gateway to the
chillers network in
RS-485 mode
12
Modbus-Jbus or
BACnet
To enable ...
3
4
5
Remark
Other jumper positions will lead to error codes and communication malfunction.
Locating the
jumpers
The illustration below shows the Gateway PCB with the 4 jumpers.
1
2
3
jumper A
jumper B
1
2
3
jumper C
NO
jumper D
214
B 23
NC
Part 2 Installation
ESIE9903
Possible power
supply
Configuration
24 VAC
120 VAC
240 VAC.
Changing the
power supply
The illustration below shows the power supply on the PCB of the Gateway.
3
transformer
240V~
power
supply
unit
120V~
fuse
24V~
Changing to 24 or
120 VAC
5
Follow the instruction given below to change the 240 VAC to 24 or 120 VAC:
Step
Action
Disconnect the cable end coming from the power supply and located at the position
marked with 240 V~.
Part 2 Installation
24 V~ and place it over the free connection (240 V~) when you want to change to
24 VAC power supply.
120 V~ and place it over the free connection (240 V~) when you want to change to
120 VAC power supply.
Connect the cable end, which youve disconnected in step 3, with the connection marked
with:
215
Configuration
ESIE9903
Step
Action
240 VAC and 120 VAC use the same fuse (on the Gateway PCB):
type T time-delay
sizes 5 x 20.
When you change the power supply to 24 VAC then replace the fuse with a fuse with the
following specifications:
3
7
type T time-delay
sizes 5 x 20.
Tighten the nuts of the cover and ensure the chassis is grounded again.
4
5
216
Part 2 Installation
ESIE9903
2.3
Configuration
Introduction
The Gateway must be configured before it can be used to transfer variables. Therefore a PC has to
be connected to the Gateway (1). The PC (field supplied) must have the following system
requirements:
(1) Refer to Connecting the Gateway to the Configuration Computer on page 2-10.
Installation
procedure
To configure the Gateway from the PC follow the steps in the table below:
Step
Action
When the configuration is successful the following message appears ***GATEWAY PROGRAMMED*** on the display.
Gateway
t
ou
e
int
pr
lin
Parameter writing
1
2
m
m
ar
ar
al
al
rx
tx
t
se
re
Parameter list means the sequence of parameter selection with the following syntax:
parameter list = <com> <net_address> <n_of_slaves> <Carel_baud> <Gateway_baud> <stop>
<parity>
Parameter reading
The PC screen displays the present Gateway configuration in which the parameters depend on the
software version.
Part 2 Installation
217
Configuration
Parameter
selections
ESIE9903
2
3
4
parameter
Description
Possible selection
com
/COM1- /COM2
net_address
1-16
n_of_slaves
carel _baud
19200
gateway_baud
stop
1- 2
parity
If you only digitize wrbaccnf (for BACnet) or writemb0 (for Modbus-Jbus) without parameters or if
certain parameters are not defined, the DOS program will display the correct syntax to be used.
Parameter values must be separated from the next by means of a blank space.
These parameters are chosen in consultation with the supervisory BMS supplier.
Error messages
Refer to Troubleshooting on page 4-1 should one of the following error messages appear on-screen:
Example
The example below is a possible configuration command for the site on page 3-14:
a:\writemb0/COM1 1 4 19200 9600 1 NONE
218
Part 2 Installation
ESIE9903
2.4
Configuration
How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller
Addressing
procedure
To address the chillers using the address card EKAC10A, proceed as follows:
START
Press s.
Do you want to
adjust the value?
NO
YES
Adjust the value using the u and d buttons.
STOP
After 5 seconds the display starts flashing when no buttons are pressed.
You can exit at every step by leaving the buttons untouched for 1 minute. The modifications will
not be saved.
Refer to Settings: Direct and User Parameters in the Small Daikin Controller on page 2-20 for an
overview of the parameters.
Part 2 Installation
219
Configuration
2.5
ESIE9903
Introduction
The grey-filled boxes relate to the chillers addressing procedure with address card EKAC10A.
Refer to How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller on
page 2-19.
direct parameters are used for the every day usage of the unit (for example to set the cooling and
heating temperature point and to read operational information)
4
5
Parameter overview
220
to have access to
A password is
not required.
In the table below you will find the description, the type, the code and the values of all of the
parameters:
Description
Type
Code
Default
Value
Limit values
Step
value
measurement unit (C or F)
user
0 C
0 or 1
direct
r1
12.0 C
7.0 C to 25.0 C
0.1 C
direct
r2
3.0 C
0.1 C to 11.0 C
0.1 C
direct
r3
40.0 C
25.0 C to 55.0 C
0.1 C
direct
r4
3.0 C
0.1 C to 11.0 C
0.1 C
direct
r6
read only
0.1 C
coil temperature
direct
r8
read only
0.1 C
not used
c4
10
not used
c5
00
not used
c6
user
c7
20 s
0 to 150 s
1s
user
c8
20 min
0 to 150 min
1 min
direct
c9
read only
1 hour
Part 2 Installation
ESIE9903
Configuration
Description
Type
Code
Default
Value
Limit values
Step
value
not used
ca
user
cb
0 hours
(disabled)
0 to 10 000 hours
100 hours
direct
cv
read only
1 hour
user
p4
1 min
0 min: buzzer
disabled
1-14 min:
buzzer
activation
period
15 min: buzzer
activated until
m button is
pressed
1
2
1 min
remote cool/heat
user
h6
0 or 1
remote start/stop
user
h7
0 or 1
user
h9
0 or 2: locked and
1 or 3: unlocked
user
ha
1 to 16
not used
hb
4
5
(1) Never lock the keyboard. Unlocking is not possible with the same password. Refer to "Unlocking
the Keyboard" in the service manual for small Daikin chillers ESIE9806.
The following advanced functions are unavailable when you lock the keyboard:
Modifying direct and user parameters (parameters can be displayed but not modified).
Refer to the service manual for small Daikin chillers ESIE9806 for more information how to change
the parameters.
Part 2 Installation
221
Configuration
2.6
ESIE9903
How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller
Addressing
procedure
To address the chillers using the address card EKAC30A/60A/120A, proceed as follows:
START (1)
Press the USER SETTINGS menu-button e.
Do you
want to save the
modifications?
NO
YES
Press j until the cursor stands in the left upper corner.
Select screen 5 (see page 2-24) and 6 (see page 2-25) using the h button.
Adjust the parameters in screen 5 (see page 2-24) and 6 (see page 2-25).
222
Part 2 Installation
ESIE9903
2.7
Configuration
Introduction
The grey-filled boxes relate to the chillers addressing procedure with address card
EKAC30A/60A/120A (1).
You need the password to enter this menu. The units leave the factory with password 1914. You can
also create your own password (2).
(1) Refer to How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller on
page 2-22.
Menu description
Screen 1
Screen 2
Part 2 Installation
This menu allows a full customizing of the units and displays the following nine screens:
Screen No.
Display
Description
ENTER PASSWORD
REMOTE CONTROL
CONTROL SETTINGS
THERM. SETTINGS
BMS SETTINGS
BMS BOARD
SETTINGS
LEAD-LAG SETTINGS
PUMP CONTROL
SETPOINT PASSWORD
4
5
You need to enter the correct password before you can consult the screens in this menu:
Line No.
Display
Description
ENTER PASSWORD
screen title
PASSWORD: 0000
1914
Line No.
Display
Description
REMOTE CONTROL
screen title
REMOTE ON/OFF
Y/N
223
Configuration
Screen 3
ESIE9903
Display
Description
Possible settings
CONTROL SETTINGS
screen title
MODE
CIR1 /C1R2
0/25/40/70/100 %
F1/F2
2
3
Screen 4
OFF/LOW/MED/HIGH
Upper
limit
Step
Default
0.4
2.0
0.1
1.5
STEPDIFFERENCE ( C)
0.2
0.8
0.1
0.5
LOADUP (30 s)
15
300
180
LOADDOWN
15
300
20
Line No.
Display
Description
THERM. SETTINGS
screen title
STPLENGTH ( C)
5
Screen 5
This screen allows you to activate the PC control mode and to modify the BMS settings:
Possible
settings
Line No.
Display
Description
BMS SETTINGS
screen title
ADDRESS PCB A
ADDRESS PCB B
00-31
PROTOCOL
CAREL
This screen will only be displayed if you mentioned that the optional BMS card is installed. You can do
this in screen 2.
224
Part 2 Installation
ESIE9903
Screen 6
Configuration
Display
Description
BMS BOARD
SETTINGS
screen title
SERIAL BOARD
Possible settings
RS485 (default)
RS422
3
BAUD RATE
2400
1200
This screen will only be displayed if you mentioned that the optional BMS card is installed. You can do
this in screen 2.
Screen 7
Screen 8
Part 2 Installation
Line No.
Display
Description
LEAD-LAG SETTING
screen title
LEAD-LAG MODE
AUTO
C1>C2
C2>C1
LEAD-LAG HOURS
100-1000 H
EQUAL START-UP
Y/N
This screen allows you to force the pump via the chillers controller and to adjust the pump lead and
lag time:
Possible
settings
Line No.
Display
Description
PUMP CONTROL
screen title
0-180 S
0-180 S
225
Configuration
Screen 9
ESIE9903
This screen allows you to assign password protection to the set point menu:
Line No.
Display
Description
SETPOINT PASSWORD
screen title
PASSWORD NEEDED TO
CHANGE SETPOINTS
Possible
settings
Y/N
3
4
5
226
Part 2 Installation
ESIE9903
4
Part 3
Functional Description
Introduction
The purpose of this part is to give some general and some more specific information about the used
protocols, the implemented commands and the databases.
Overview
See ...
1 General
page 3-3
page 3-7
3 Database
page 3-11
33
4
5
31
ESIE9903
33
4
5
32
ESIE9903
General
Part 3
1
1
General
1.1
Introduction
Overview
The purpose of this chapter is to give some general information and some references on the used
protocols.
33
See ...
page 3-4
page 3-5
4
5
33
General
1.2
ESIE9903
BACnet
conformities
Modbus-Jbus
conformities
33
The Modicon Modbus protocol implemented in the Gateway complies with the content of the
document:
Reference Guide
The implemented Modbus-Jbus protocol is of the RTU type based on times. The configuration is of the
multi-drop in RS-485 or point-to-point RS-232. The address sent into the Modbus packet addresses
the Gateway.
BACnet
communication
parameters
Modbus-Jbus
communication
parameters
34
The communication parameters between the supervisory system using the BACnet protocol and the
Gateway, selectable by the user, are listed below:
Parameter
Selectable value
baud rate
8 (fixed)
parity
12
The communication parameters between the supervisory system using the Modbus-Jbus protocol and
Gateway, selectable by the user, are listed below:
Parameter
Selectable value
baud rate
8 (fixed)
parity
12
ESIE9903
1.3
General
ASHRAE manual
All pages mentioned below refer to the ASHRAE manual of the BACnet.
Characteristics
Characteristics of
the Gateway
Errors and
messages
Examples
Chapter
Page
page 8-13
page 14-24
page 50-73
page 103-134
33
The Gateway Conformity Class, Object and Service characteristics are listed in the table below:
Chapter
Page
Error codes
page 313-317
page 322-334
page 334-347
4
5
Page
Error codes
page 313-317
page 322-334
page 334-347
Page
page 467
page 475
35
General
ESIE9903
33
4
5
36
ESIE9903
Part 3
1
2
2.1
Introduction
Overview
The purpose of this chapter is to provide further information concerning the implemented commands
in the Gateway.
33
See ...
2.2 Protocol
page 3-8
page 3-9
4
5
37
2.2
ESIE9903
Protocol
BACnet
Implemented BACnet protocol commands correspond to the Conformity Classes 1 and 2, namely
ReadProperty and WriteProperty. With these functions, it is possible to read and write a single value
at a time.
Modbus-Jbus
The software commands of the Modbus-Jbus protocol, ensure the compatibility between Modbus and
Jbus.
The data representation of the Modbus-Jbus protocol:
digital data
analogue data.
33
Digital data
Modbus-Jbus
All the digital variables are assigned to bit of consecutive registers, each one having:
4
5
Analogue data
Modbus-Jbus
An analogue value is represented by a 16-bit register in binary notation in complement on two with:
38
ESIE9903
2.3
Implemented Commands
In the Gateway
program
Meaning
Notes
15
16
33
4
Due to the variety of chillers with installed address cards no distinction is made between input
variables (read only) and output variables (read/write) so that the knowledge of the database and
its management depends on the part present on the supervisory system.
Due to the generality of the system, the Gateway answers in the same way to various Modbus
commands.
39
ESIE9903
33
4
5
310
ESIE9903
Database
Part 3
1
3
Database
3.1
Introduction
The purpose of this chapter is to give further information about on database creation.
Overview
33
Topic
See ...
page 3-12
page 3-16
page 3-18
page 3-21
page 3-24
4
5
311
Database
3.2
ESIE9903
Database creation
Introduction
The supervisory BMS and the address cards communicate through a fixed set of variables, also called
address numbers.
These variables are transferred from:
33
4
each address card database to the Gateway, where they are put in the Gateway database
The variables from each address card database can be digital, analogue or integer. The maximum
number of transferable variables from an address card to the Gateway is given below:
Variable type
Maximum number
digital
200
analogue
128
integer
128
The BACnet and Modbus-Jbus protocols do not distinguish between analogue and integer variables.
Therefore variables leaving the Gateway to the BMS can only be digital or analogue.
The analogue and integer variables of the address card database are in the Gateway database put
together in the analogue variables. The old analogue variables are numbered from 1 to 128 and the
old integer variables from 129 to 256.
The maximum number of transferable variables from the Gateway to the supervisory BMS is given
below:
Variable type
Maximum number
Corresponding BACnet
object
digital
200
binary value
analogue
256
analogue value
If requested by the supervisory BMS, the Gateway sends out the variables that are not present on the
machine with the value 0.
This way, extra inline traffic is created, but the generality of the application is saved. The database is
dimensioned for the address card with the largest number of variables.
Example EKAC10A
database
The table below shows an example of a digital, an analogue and an integer variable for the address
card EKAC10A:
Parameter
Variable
type
Address
number
Read/
write
digital
47
analogue
integer
312
Comment
Direct/
user
Name
Description
r/w
H7
13
r/w
r4
Heating difference
38
r/w
H9
1=enable
0=disable
0=keyboard disabled
1=keyboard enabled
ESIE9903
Gateway database
creation
Database
The digital variables are transferred with their addresses to the Gateway (Modbus-Jbus or BACnet)
database. In the Modbus-Jbus database they are read using the commands 1 or 2 (1).
The analogue variables are transferred with their addresses to the Gateway (Modbus-Jbus or
BACnet database). In the Modbus-Jbus database they are read using the commands 3 or 4 (1).
The integer variables are transferred with their addresses on top of the analogue variables to the
Gateway (Modbus-Jbus or the BACnet) database. In the Modbus-Jbus database they are read
using the commands 3 or 4 (1).
Gateway database
diagram
The creation of a Gateway database from address card databases (slave n databases) is given below.
33
Gateway database
Digital variables
1
200
1
128
1
128
1
Digital variables
200
Analog variables
400
...
(n-1)*200
Integer variables
Analogue variables
1
256
512
...
(n-1)*256
(n-1)*256+128
Modbus supervisor
In the Modbus supervisor, the operator must reserve 25 bytes for the digitals (200 digital variables)
and 512 bytes for the analogues (128 analogue variables and 128 integer variables) for a total of 456
variables for each address card.
313
Database
Address list
creation illustration
ESIE9903
The illustration below shows the Daikin chillers and the BMS.
BMS
Gateway
pr
t
ou
int
e
lin
1
2
m
m
ar
ar
al
al
rx
tx
t
se
re
Serial module
chiller
compact
33
Address 1
EUWY10HCW1
4
Address 2
EUWAT50KAY1
PCB A: Address 3
EUWT200KXY1
Gateway database
creation: digital
variables
PCB B: Address 4
The Gateway database creation for the digital variables in the illustration above is herewith given:
Unit
Address towards
the Gateway
EUWY10HCW1
001 200
EUWAT50KAY1
201 400
PCB A
401 600
PCB B
601 800
EUWT200KXY1
314
ESIE9903
Gateway database
creation: analogue
variables
Database
The Gateway database creation for the analogue variables in the illustration above is herewith given:
Unit
Address towards
the BMS
Assigned address in
the Gateway database
(analogue variables)
EUWY10HCW1
001 128
Analogue
129 256
Integer
257 384
Analogue
385 512
Integer
513 640
Analogue
641 768
Integer
769 896
Analogue
897 1025
Integer
EUWAT50KAY1
EUWT200KXY1
PCB A
PCB B
33
4
5
315
Database
3.3
Introduction
The BMS or supervisory system and the address card communicate through a fixed set of variables,
also called address numbers. Information about the digital, integer and analogue variables that the
BMS or supervisory system can read from, or write to, the chillers address card is given in this section.
Digital variables
Address
33
4
5
ESIE9903
Read
/write
Parameter
Direct/ user
Name
1
2
5
r/w
r/w
r
H1
6
8
9
r
r
r
L1
FL
E3
10
11
12
13
14
15
17
18
19
21
22
25
26
28
29
30
31
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
E2
E1
n1
EP
EE
EL
d1
r1
A1
EO
EU
32
33
40
47
r
r
r/w
r/w
316
U
U
/d
H7
Comment
Description
Cooling or Heating
On or off
Alarm: high pressure or discharge protector or
overcurrent
Alarm: evaporating temperature thermostat
Alarm: flow switch
Alarm
Alarm
Alarm
Warning: compressor requires maintenance
Alarm: EEPROM defective
Alarm: EEPROM defective
Alarm: power supply has unusual noise
Defrost cycle
Warning: defrost cycle not completed
Alarm: anti-freeze
Alarm: supply voltage is high
Alarm: supply voltage is low
Output of pump
Output of compressor
Output of reversing valve
Output of alarm
Output of fan
Input of high pressure or discharge protector or
overcurrent alarm
Input of evaporating temperature thermostat alarm
Input of remote on/off
Measurement unit of temperature
Enable/disable remote on/off digital input
EUWA510HB(Z)
EUWY510HB*
1=cooling 0=Heating
1=on 0=off
1= alarm 0=no alarm
1= alarm 0=no alarm
1= alarm 0=no alarm
Ambient
Coil
temperature
temperature
ESIE9903
Database
Integer variables
Address
Read
/write
Name
Comment
Description
12
r/w
c7
13
r/w
c8
14
15
16
32
38
r
r/w
r
r/w
r/w
D
U
D
U
U
c9
cb
cC
P4
H9
39
HA
Serial address
Analogue variables
Address Read
/write
1
2
3
10
11
12
13
r
r
r
r/w
r/w
r/w
r/w
0= keyboard disabled
1= keyboard enabled
33
Direct/ user
D
D
D
D
Name
r1
r2
r3
r4
Description
Analogue input 1
Analogue input 2
Analogue input 3
Cooling setpoint
Cooling difference
Heating setpoint
Heating difference
Comments
EUWA5-10HB(Z)
EUWY5-10HB
Ambient temperature
Coil temperature
317
Database
3.4
ESIE9903
Introduction
The BMS or supervisory system and the address card communicate through a fixed set of variables,
also called address numbers. Information about the digital, integer and analogue variables that the
BMS or supervisory system can read from, or write to, the chillers address card is given in this section.
1. If there is referred to a circuit the following syntax is used:
X/Y: circuit X of EUWA/Y 15-20HB(Z): these chillers have a maximum of 2 circuits
circuit Y of EUWA/Y25-30HB(Z): these chillers have a maximum of 3 circuits
2. For all possible values of user settings, refer to the chillers operation manual.
33
4
5
318
ESIE9903
Database
Digital variables
Address
Read
/write
Description
1
2
3
4
r
r
r
r
Digital input 1
Digital input 2
Digital input 3
Digital input 4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
w
Digital input 5
Digital input 6
Digital input 7
Digital input 8
Digital input 9
Digital input 10
Digital input 11
Digital output 1
Digital output 2
Digital output 3
Digital output 4
Digital output 5
Digital output 6
Digital output 7
Digital output 8
Digital output 9
Digital output 10
Digital output 11
Digital output 12
Digital output 13
Cooling/heating mode
Unit status
Freeze up circuit 1/1 active
Freeze up circuit -/2 active
Freeze up circuit 2/3 active
Circuit 1/1 safety active
Circuit -/2 safety active
Circuit 2/3 safety active
Manual mode active
Load up timer active
Load down timer active
Start timer active
Flow start timer
Flow stop timer
Guard timer compressor 1/1 active
Guard timer compressor -/2 active
Guard timer compressor 2/3 active
Anti-recycling time compressor 1/1 active
Anti-recycling time compressor -/2 active
Anti-recycling time compressor 2/3 active
Defrost busy compressor 1/1
Defrost busy compressor -/2
Defrost busy compressor 2/3
Compressor 1/1 off for defrost of other circuit
Compressor -/2 off for defrost of other circuit
Compressor 2/3 off for defrost of other circuit
On-off command
55
Comments
EUWA15-30HB(Z)
Safety circuit 1/1
Safety circuit -/2
Safety circuit 2/3
-
EUWY15-30HB
Remote cooling/heating
selection
Flow switch
Defrost circuit 1/1
Defrost circuit -/2
Defrost circuit 2/3
Dual setpoint
Remote on/off
Reverse phase protector
Compressor 1/1
Compressor -/2
Compressor 2/3
LP bypass circuit 1/1
LP bypass circuit -/2
Pump
General Alarm
System on
Fanspeed 1 (ry1)
Fanspeed 2 (ry2)
Fanspeed 3 (ry3)
Lp bypass circuit 2/3
Evaporator heater
Reversing valve
0=heating 1=cooling
1=on 0=off
1=yes 0=no
1=yes 0=no
1=yes 0=no
1=yes 0=no
1=yes 0=no
1=yes 0=no
1=yes 0=no
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=yes 0=no
1=yes 0=no
1=yes 0=no
1=yes 0=no
1=yes 0=no
1=yes 0=no
If 1 is written, then toggle status of the unit.
After this action the controller resets this parameter
If 1 is written, then toggle
status of the unit. After this
action the controller resets this
parameter
319
33
4
5
Database
Integer variables
Address
33
4
5
ESIE9903
Read/
write
Description
1
2
3
4
5
r
r
r
r
r
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
27
r
r
r
r
r
r
r
r
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r
28
29
30
31
r
r
Refrigeration type
Manufacturer number 1
Manufacturer number 2
Manufacturer number 3
Manufacturer number 4
Manufacturer number 5
Manufacturer number 6
Manufacturer number 7
Total steps number
Manual setting of compressor 1/1
Manual setting of compressor -/2
Manual setting of compressor 2/3
Manual setting of fans
Load up time
Load down time
Running mode
Water/air-cooled unit
Analogue variables
Address
Read
/write
1
2
3
4
5
6
7
8
9
10
11
12
r
r
r
r
r
r
r/w
r/w
r/w
r/w
r/w
r/w
320
Comment
EUWA15-30HB(Z)
EUWY15-30HB
Comment
EUWA15-30HB(Z)
Analogue input
Analogue input
Analogue input
Analogue input
Analogue input
Minimum outlet water
Step length
Step difference
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
EUWY15-30HB
ESIE9903
3.5
Database
Introduction
The BMS or supervisory system and the address card communicate through a fixed set of variables,
also called address numbers. Information about the digital, integer and analogue variables that the
BMS or supervisory system can read from, or write to, the chillers address card.
1. If there is referred to a circuit the following syntax is used:
X/Y: circuit X of EUWA/Y 15-20HB(Z)*: these chillers have a maximum of 2 circuits
circuit Y of EUWA/Y25-30HB(Z)*: these chillers have a maximum of 3 circuits
2. For all possible values of user settings, refer to the chillers operation manual.
Digital variables
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
36
37
38
39
Read/
write
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
w
r
r
r
r
33
Comments
EUWA*40-60KA(X)
EUW*40-100KX
1=On 0=Off
1=Yes 0=No
1=Yes 0=No
Low pressure switch
High pressure switch
Reverse phase protector
Overcurrent
Discharge thermal protector
Compressor thermal protector
Flow switch
Bypass
Dual setpoint
Digital input remote on/off
Emergency
Star
Delta
Compressor status
Pump
Alarm status
12%
25%
40%
Fan 1
Fan 2
Fan 3
Evaporator heater
70%
1=yes 0=no
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
If 1 is written, then toggle status unit. After this action the controller resets this parameter
0=not active 1=active
Enable/disable limitation
0=no 1=yes
0=no 1=yes
321
4
5
Database
Integer variables
Address
33
4
5
ESIE9903
Read/
write
Description
1
2
3
4
5
r
r
r
r
r
Unit type
8
9
10
11
12
13
14
15
16
17
18
r
r
r
r
r
r
r
r
r
r
r/w
Refrigeration type
Manufacturer number 1
Manufacturer number 2
Manufacturer number 3
Manufacturer number 4
Manufacturer number 5
Manufacturer number 6
Manufacturer number 7
Actual thermostat step
Maximum number of thermostat step
Manual setting of compressor
19
r/w
20
21
22
23
24
r/w
r/w
r/w
r/w
r/w
27
Water/air-cooled unit
28
29
30
31
r
r
322
Comments
EUWA*40-60KA(X)
User settings
(00000)
(00000)
0=off,1=low,2=med,3=high
0= ON 12 star
1= ON 12% delta
2= ON 25% delta
3= ON 40% delta
4= ON 70% delta
5= ON 100% delta
0= OFF Can startup
1= OFF Timers busy
2= OFF Disabled (contact)
3= OFF safety active
4= OFF bypass mode
0=EUWA*40J* 1=EUWA*50J*
2=EUWA*60J* 3=EUWA*40K*
4=EUWA*50K* 5=EUWA*60K*
0=R134a 1=R22
First digit
Second digit
Third digit
Fourth digit
Fifth digit
Sixth digit
Seventh digit
0,1,2,3,4
3,4
User settings manual mode:
If 25% is installed:
0=0%, 1=25%,2=40%,
3=70%,4=100%
User settings manual mode
0=off,1=low,2=med,3=high
User setting (thermostat)
User setting (thermostat)
User setting (thermostat)
User setting (thermostat)
0=inlet, 1=outlet, 2=manual
EUW*40-100KX
0=air-cooled unit
1=water-cooled unit
0=cooling only
1=heat pump
0= EUWA/Y15-30HB
1= EUWA*40-60KA(X)
2= EUWA*80-120KA(X)
3= EUW*40-100KX
4= EUW*120-200KX
5= EUWA*160-200KX
1=V1
(V1.012)
Example 12
(V1.012)
ESIE9903
Database
Analogue variables
Address
Read
/write
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
r
r
r
r
r
r
r
r
r
r
r
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
Analogue input 2
Analogue input 3
Analogue input 1
Analogue input 7
Analogue input 8
Converted analog input 7
Converted analog input 8
Analogue input 6
Analogue input 5
Actual setpoint
Minimum outlet water
Inlet setpoint 1 cooling
Inlet setpoint 2 cooling
Outlet setpoint 1 cooling
Outlet setpoint 2 cooling
Step length in inlet control
Step difference in inlet control
Step length in outlet control
Step difference in outlet control
Inlet setpoint 1 heating
Inlet setpoint 2 heating
Comments
EUWA*40-60KA(X)
EUW*40-100KX
Inlet evaporator temperature
Outlet evaporator temperature
Ambient temperature
Inlet condenser temperature
Low pressure
High pressure
High pressure converted in temperature
Low pressure converted in temperature
Voltage (only if V-A option is installed else value 99.0)
Current (only if V-A option is installed else value 99.0)
User setting (In/outlet setpoint 1 or 2)
Factory setting
User setting
User setting
User setting
User setting
User setting
User setting
User setting
User setting
User setting
User setting
33
4
5
323
Database
3.6
ESIE9903
Introduction
The BMS or supervisory system and the address card communicate through a fixed set of variables,
also called address numbers. Information about the digital, integer and analogue variables that the
BMS or supervisory system can read from, or write to, the chillers address card is given in this section.
These chillers have two PCBs: PCB A & B.
PCB A: General parameters and circuit 1 parameters
PCB B: Circuit 2 parameters
If a parameter is marked with X in column of PBC A or B, then the parameter is present on the marked
PCB.
33
4
5
324
ESIE9903
Database
Digital variables
Address
Read/ A
write
1
2
3
4
5
6
7
8
9
10
r
r
r
r
r
r
r
r
r
r
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
w
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
36
37
r
r
38
39
r
r
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Description
Comments
EUWA*80-120*KA(X)
EUWA*160-200KX
1=on 0=off
1=yes 0=no
1=yes 0=no
Low pressure switch
High pressure switch
Reverse phase protector
Overcurrent
Discharge thermal protector
Compressor thermal protector
PCB A:
PCB B:
PCB A:
PCB B:
Flow switch Enable/
Flow
Disable C1 switch
Digital input 8
PCB A:
PCB B:
PCB A:
PCBB:
Bypass
Enable/
Bypass
disable C2
Digital input 9
Dual setpoint
Digital input 10
Digital input remote on/off
Digital input 11
Emergency
Digital output 1
Star
Digital output 2
Delta
Digital output 3
Compressor status
Digital output 4
Pump
Digital output 5
Alarm status
Digital output 6
12%
Digital output 7
25%
Digital output 8
40%
Digital output 9
Fan 1
Fan 1
Digital output 10
Fan 2
Fan 2
Digital output 11
Fan 3
Fan 3
Digital output 12
Evaporator heater
Evaporator heater
Digital output 13
70%
Circuit safety active
1=yes 0=no
Guard timer active
1=not zero 0=zero
Start up timer active
1=not zero 0=zero
Anti-recycling timer active
1=not zero 0=zero
Load up timer active
1=not zero 0=zero
Load down timer active
1=not zero 0=zero
On/off command
If 1 is written, then toggle status of the unit.
After this action the controller resets this parameter
High pressure setback active 0=not active 1=active
Digital input 12
Enable/disable capacity
limitation
25% installed
0=no 1=yes
V-a meter installed
0=no 1=yes
Unit status
Enable remote on/off
Unit safety active
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Digital input 7
EUW*120-200KX
PCB A:
PCB B:
Flow switch PCB A:
Bypass
33
PCB B:
-
4
5
Enable/disable capacity
limitation
325
Database
Integer variables
Address
33
ESIE9903
Read/ A
write
1
2
r
r
X
X
4
5
r
r
X
X
X
X
8
9
10
11
12
13
14
15
16
17
r
r
r
r
r
r
r
r
r
r
X
X
X
X
X
X
X
X
X
X
18
r/w
4
5
19
r/w
20
21
r/w
r/w
X
X
22
23
24
27
r/w
r/w
r/w
r
X
X
X
X
28
29
30
31
r
r
X
X
326
Description
Enable write BMS
Running hours compressor
(higher part)
Running hours compressor
(lower part)
Actual fanstep
Status of compressor (if on) for
readout in mask
Comments
EUWA*80-120*KA(X)*
User settings
(00000)
EUWA*160-200KX*
EUW*120-200KX*
(00000)
0=off,1=low,2=med,3=high
0= ON 12 star
1= ON 12% delta
2= ON 25% delta
3= ON 40% delta
4= ON 70% delta
5= ON 100% delta
X Status of compressor (if off) for 0= OFF Can startup
readout in mask
1= OFF Timers busy
2= OFF Disabled (contact)
3= OFF safety active
4= OFF bypass mode
Unit type
0=EUWA*80J
1=EUWA*100J
2=EUWA*120J
3=EUWA*80K
4=EUWA*100K
5=EUWA*120K
Refrigeration type
1=R22 0=R134a
Manufacturer number 1
First digit
Manufacturer number 2
Second digit
Manufacturer number 3
Third digit
Manufacturer number 4
Fourth digit
Manufacturer number 5
Fifth digit
Manufacturer number 6
Sixth digit
Manufacturer number 7
Seventh digit
Actual thermostat step
0,1,2,3,4,5,6,7,8
Maximum number of
7,8
thermostat step
X Manual setting of compressor
User settings manual mode
If 25% is installed
0=0%, 1=25%,2=40%,
3=70%,4=100%
X Manual setting of fans
User settings manual mode
0=off,1=low,2=med,3=high
Load up time in outlet control
User setting (thermostat)
Load down time in outlet
User setting (thermostat)
control
Load up time in inlet control
User setting (thermostat)
Load down time in inlet control User setting (thermostat)
Running mode
0=inlet 1=outlet 2=manual
Water/air cooled unit
0=aircooled unit
1=watercooled unit
Cooling only/heat pump
0=cooling only
1= heat pump
Unique eprom parameter
0= EUWA/Y15-30HB(Z)
1= EUWA*40-60KA(X)
2= EUWA*80-120KA(X)
3= EUW*40-100KX
4= EUW*120-200KX
5= EUWA*160-200KX
Eprom version (higher part)
1=V1
(V1.012)
Eprom version (lower part)
Example 12
(V1.012)
ESIE9903
Database
Analogue variables
Address
Read/ A
write
1
2
r
r
X
X
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
r
r
r
r
r
r
r
r
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Comments
EUWA*80EUWA*160-200KX
EUW*120-200KX
120*KA(X)
Analogue input 2
Inlet evaporator temperature
Analogue input 3
PCB A
PCB B Outlet evaporator temp of Outlet evaporator temp of
Outlet
circuit
circuit
evaporator
temp.
Analogue input 1
PCB A
PCB B PCB A
PCB B
PCB A
PCB B
Ambient
Ambient
Mixed outlet
Inlet
Mixed outlet
temp.
temp.
evaporator
condenser evaporator
temp.
temp.
temp.
Analogue input 7
High pressure
Analogue input 8
Low pressure
Converted analogue input 7
High pressure converted in temperature
Converted analogue input 8
Low pressure converted in temperature
Analogue input 6
Voltage (only if V-A option is installed, els value 99.0)
Analogue input 5
Current (only if V-A option is installed, else value 99.0)
Actual setpoint
User setting (In/outlet setpoint 1 or 2)
Minimum outlet water
Factory setting
Inlet setpoint 1 cooling
User setting
Inlet setpoint 2 cooling
User setting
Outlet setpoint 1 cooling
User setting
Outlet setpoint 2 cooling
User setting
Step length in inlet control
User setting
Step difference in inlet control User setting
Stepl ength in outlet control
User setting
Step difference in outlet control User setting
Inlet setpoint 1 heating
User setting
Inlet setpoint 2 heating
User setting
Description
327
33
4
5
Database
ESIE9903
33
4
5
328
ESIE9903
Part 4
Troubleshooting
Introduction
The purpose of this part is to help you to find the malfunction causes of the system.
Overview
See ...
1 Troubleshooting
page 4-3
4
5
Part 4 Troubleshooting
41
ESIE9903
42
Part 4 Troubleshooting
ESIE9903
Troubleshooting
Part 4
1
Troubleshooting
1.1
Introduction
The purpose of this chapter is to help you to identify malfunctions or problems. Before checking the
Daikin BMS option, first check whether the chiller itself is working properly.
The BMS-option enables communication between the Daikin chillers and the BMS. Should a
malfunction in the BMS option occur, it is most likely a communication problem.
Overview
See ...
page 4-4
1.3 Troubleshooting
page 4-6
4
5
43
Troubleshooting
1.2
ESIE9903
Fault Indications
Introduction
The LED indicators that will help you to solve the malfunction are located on the Gateway front panel
and on the chillers PCB(s).
The illustration below shows the LED indicators on the Gateway front panel.
Gateway
t
ou
e
int
pr
lin
Normal Gateway
indicators
4
5
Gateway
malfunction
indicators
2
1
m
m
ar
ar
al
al
rx
tx
t
se
re
line
yellow
on
alarm 1
off
alarm 2
off
rx
green
flashing
tx
green
flashing
is ...,
then ...
line
off
alarm 1
red
on
alarm 2
red
on
44
ESIE9903
Troubleshooting
main PCB
orange
on
red
off
orange
flashing
green
on
(1) This is only for units with two circuits or sites with a DICN.
Chiller malfunction
indicators
Refer to the relevant Daikin water chiller service manual.
4
5
45
Troubleshooting
1.3
ESIE9903
Troubleshooting
Introduction
This section tells you where or what to check when there is a LED fault indication on the Gateway front
panel.
Refer to the relevant Daikin water chiller service manual for more information about the chillers PCB
LED fault indications.
3
4
Gateway LED
"alarm 1" is on
5
Gateway LED
"alarm 2" is on
46
The table below displays the possible causes and the items that must be checked:
Possible causes
Check ...
No power
Fuse blown
The table below displays the possible causes and the items that must be checked:
Possible causes
Action
No Gateway software
configuration
Refer to ...
The table below displays the possible causes and the items that must be checked:
Possible causes
Check ...
Refer to ...
Gateway Software
Configuration (MS
DOS program) on
page 2-17.
Software version
on page 1-6.
ESIE9903
Troubleshooting
Possible causes
Check ...
Wrong connected or
loose 9-pin male connector from the Gateway to
the chillers
Refer to ...
Installing and Connecting the System on
page 2-3.
4
5
47
Troubleshooting
ESIE9903
3
4
5
48
ESIE9903
Appendix A
Drawings
Introduction
In order to quickly find the drawings inserted in this manual, appendix A offers a list with all the
drawings.
Overview
The table below shows the page and description of all the drawings:
Description
See ...
page vi
page 1-4
page 1-8
page 1-10
page 1-11
page 2-4
page 2-5
page 2-6
page 2-7
page 2-8
page 2-9
page 2-9
page 2-10
page 2-11
page 2-12
page 2-14
page 2-15
page 2-17
page 3-13
page 3-14
page 4-4
A1
ESIE9903
A2
ESIE9903
Index
1
A
address cards
data transfer to the Gateway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
EKAC10A connecting to the controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
EKAC10A connecting to the transfo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
EKAC10A database variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-16
EKAC10A dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
EKAC10A installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5
EKAC10A kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
EKAC120A database variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24
EKAC30A database variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-18
EKAC30A/60A/120A connecting to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
EKAC30A/60A/120A dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
EKAC30A/60A/120A installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
EKAC30A/60A/120A kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
EKAC60A database variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-21
product range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-6
serial line example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
alarms
Gateway LED alarm 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-6
Gateway LED alarm 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-6
analogue
database creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
EKAC10A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-17
EKAC120A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-27
EKAC30A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-20
EKAC60A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-23
Modbus-Jbus representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-8
ASHRAE
references of the BACnet protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-5
3
4
5
B
BACnet
ASHRAE references . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-5
communication parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
BMS
centralized building control example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k vi
connecting to the Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-11
enabling communication with the Gateway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
parameter settings with the large controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-22
parameter settings with the small controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-19
C
communication
outline example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-4
configuration
Gateway hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
Gateway software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
Index
ESIE9903
1
connecting
address card in the serial line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
EKAC10A to the controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
EKAC10A to the transfo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
EKAC30A/60A/120A to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
Gateway to the BMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-11
Gateway to the configuration PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-10
D
databases
creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
EKAC10A variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-16
EKAC120A variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24
EKAC30A variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-18
EKAC60A variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-21
digital
database creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
EKAC10A variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-16
EKAC120A variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-25
EKAC30A variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-19
EKAC60A variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-21
Modbus-Jbus representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-8
dimensions
EKAC10A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
EKAC30A/60A/120A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
3
4
5
E
EKAC10A
connecting to the controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
connecting to the transfo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
database variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-16
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5
kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
EKAC120A
connecting to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
database variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-24
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
EKAC30A
connecting to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
database variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-18
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
EKAC60A
connecting to the field rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
database variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-21
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
ii
Index
ESIE9903
1
G
Gateway
buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
configuration PC installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
connecting to the BMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-11
connecting to the configuration computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-10
connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-9
data transfer to the BMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
database creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-13
enabling communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
hardware configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
implemented commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-9
kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-8
LED indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-9, 4-4
parameter descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-18
power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-15
precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-3
product range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-6
serial line example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-9
3
4
I
integer
database creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EKAC10A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EKAC120A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EKAC30A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EKAC60A variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
k
k
k
k
k
3-12
3-17
3-26
3-20
3-22
J
jumpers
enabling address cards-Gateway-BMS communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
locating on the Gateway PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-14
L
LED indicators
chillers PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-4
M
master-slave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-7
Modbus-Jbus
communication parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
conformities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
data representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-8
MS-DOS
Gateway software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
O
outline
communication example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-4
EKAC10A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-10
EKAC30A/60A/120A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-11
Index
iii
ESIE9903
1
P
parameters
BACnet communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
BMS settings with the large controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-22
BMS settings with the small controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-19
direct and user settings in the small controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20
Modbus-Jbus communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
user settings in the large controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-23
PC
connecting to the Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-10
Gateway configuration requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
precautions
Gateway installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-3
protocol
ASHRAE references . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-5
BACnet and Modbus-Jbus differences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-7
generalities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-7, 3-4
Modbus-Jbus data representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-8
3
4
R
RS-232
enabling Gateway serial port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gateway-BMS connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RS-485
enabling Gateway serial port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gateway-BMS connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
k 2-14
k 2-11
k 2-14
k 2-12
S
serial line
communication outline example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-4
connections example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
software
configuration Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
EPROM versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-6
T
troubleshooting
chillers PCB LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
Gateway LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-4
iv
Index
SERVICE MANUAL
Daikin Europe NV is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services
related to the product.
Zandvoordestraat 300
B-8400 Oostende
Belgium