DATA SHEET FOR HV VARIABLES SPEED DRIVES

DATA FURNISHED BY OWNER


Sl.
no
1.

FEATURES

Description

BASIC REQUIREMENTS
i.

Required rated output capacity

* (As per motor ratings / Pump


Load)

ii.

Torque requirement

As per pump requirement

iii.

Load/driven equipment details

Horizontal Centrifugal pumps

iv.

Load torque details

Centrifugal pumps

v.

Drive system

One drive for each pump

vi.

Reacceleration of motor

As per Operational requirements of


Pump specifications

2.

SITE CONDITIONS

a)

Location

As per SOR

b)

Design Ambient temperature

5- 500C

c)

Altitude

Less than 1000m above mean sea


level

d)

Humidity (max)

95%(relative)

e)

Location

Indoor

f)

Installation area for VFD

Indoor

g)

Installation area for motor & :


LCP

INPUT
POWER
SUPPLY
SYSTEM CONDITIONS

a)

No. of phases

Three

b)

AC input voltage

6.6KV

c)

Voltage fluctuation

10%

d)

Rated frequency

50 Hz

e)

Frequency fluctuation

3%

f)

System fault level

25 KA (1 sec.)

SYSTEM REQUIREMENTS

a)

Speed range required

As per Pump requirement

b)

Speed reference signal


:
Operation in case of loss of :
reference signal

4-20mA

Acceleration time

As per clause 6.1.5

c)

d)

Hazardous zone-2, gas groupIIA/IIB,


Temperature
class-T3,
Tropical, dusty, corrosive.

Last speed reference/ a set speed


lower than previous reference /
either of above as per manufactures
standard.

Sl.
no

FEATURES

Description

e)

Deceleration time

As per clause 6.1.5

f)

Communication facility between :


Owners control system and
drive

Required

g)

Harmonic study

Required

h)

Braking

i)

Converter transformer

Flux
braking/
DC
injection
braking/ either of the above
Dry type

j)

Output voltage of VFD system

6.6KV, three phase (without using


any output transformer)

k)

Type of converter/rectifier

Minimum 18 Pulse

l)

Harmonic filters on supply bus

Vendor shall ensure that converter


design is in such a way that both
harmonics V&I harmonics are
within limits as specified in IEEE519

m)

Power
factor
improvement :
feature as part of harmonic
filters

Vendor shall ensure that converter


design is in such a way, so that
minimum PF at input of each VFD
is 0.99 lag for the varying load of
10% to 110%

CONTROL LOCATION

a)

Local/Remote operation

b)

Local/Remote
location

c)

Speed raise/Lower signal

d)

Distance of VFD panel from :


Motor

COMMUNICATION

selector

Required

switch :

At VFD panel

At VFD panel
350m (maximum)

On communication network
(compatible RS 485 port) the
following
details
shall
be
available
a)

Protection features

Yes

b)

Indication

Yes

c)

Metering

Yes

d)

Annunciation

Yes

e)

Diagnostic

Yes

TECHNICAL DATA TO BE FURNISHED BY MANUFACTURER


(To be submitted separately for each location)
1.

Make

: Siemens / ABB / Rockwell / Yaskawa /


Hitachi

2.

Model No.

: *

3.

Rating of drive panel


a) Output in amperes
b) Rating

expressed

: * (to be provided)
at : *

(torque)
c) Rating

declared

at : 50 Deg C

(temp.)
d) Switching

frequency

at : * Hz

declared rating
4.

Applicable code / standards

: CSA,UL,IEC,NEMA,ANSI,IEEE,CE/equivalent

5.

Drive type

: CSI/VSI

6.

Speed range

: 10% to 110% of rated motor speed

7.

Speed reference signal type

: 4-20mA

8.

Input power supply ratings

: 3 Phase 6.6Kv

9.

Voltage

: 6600 V + 10%

10.

Frequency

: 50 Hz + 3%

11.

Output voltage at 10% : 6600 v


input voltage full speed, full
load
Overload
capability
of

12.

converter
a) 115% In( for variable : *
torque) for
13.

Overall efficiency of drive


(excl. motor) at
a) 100% load

: *

b) 75% load

: *

c) 50% load
14.

15.

16.

17.

18.
19.

: *

Overall power factor of drive :


(excl. motor) at
a) 100% load
: *
b) 75% load

: *

c) 50% load

: *

AC Output

a) Rated frequency range

: *

b) Accuracy of frequency

: *

Dynamic response

a) Speed fluctuation band

: *

b) Speed recovery time after : *


100% torque step
Waveform distortion factor : *
(% harmonics) in output /
input waveform.
(Number of harmonics and magnitude of each harmonic generated shall be
furnished)
Output short ckt. Capability : *
and duration
Controls
At Drive level
(Please answer as provided /
not provided
a) System start
: *
b) System stop

: *

c) Speed raise

: *

d) Speed lower

: *

e) Drive frequency setting

: *

h) Remote bkr.trip

: *

i)Electronic Ramp function

: *

j)

Speed

and

current : *

controller

20.

k) Drive ready to start signal

: *

l) Ammeter

: On digital operator or separate digital type

m) Speed indicator

: On digital operator or separate digital type

a)Diodes

IGBT : *

/IGCT/SGCT configuration
Number and Ratings
b)Total No. of diodes / IGBT : *
/IGCT / SGCT
Number and Ratings
21.

Cooling system

i) Type

: Fan forced cooling

ii) Redundancy in cooling : *


units
22.

a)Type

of

feed-back

for : Open loop Vector

speed control

23.

24.

25.

26.
27.

b)Speed control accuracy

: *

List of controls provided at


the front of panel (As per
specification)
List of status measuring
devices provided at the front
of panel (as per specification
List of status indication and
annunciation provided (as
per specification)
Type of electronic card
mounting arrangement
DIMENSION

: Yes / No

a) Length

: *

b) Height

: *

c) Depth

: *

d) Weight of cubicle

: *

: Yes / No

: Yes / No

: *

(Dimensional details of all panels shall be furnished).


28.

Degree

of

protection

for : * (Minimum IP 4X)

enclosure
29.

Paint shade

: As per specification

30.

Heat output of Panel

: *

31.

Whether Air conditioning is : *


required for these panels
Control supply voltage and : 415 V, 3 phase, 4 Wire
Aux. Power requirement
Converter Transformer (If :

32.
33.

applicable)
a) Make

: *

b) Type of transformer

: Dry type

c) KVA Rating

: *

d) Voltage ratio

: *

e) Vector group

: *

f) Taps

: *

g) Insulation class

: F (Min) for dry type transformer.

f) Impedance

: *

g) Efficiency

: > 98%

h) Weight

: *

i)

Winding

RTDs

/ : Minimum 1 per phase

Thermistors
g)

Overall

dimension : *

(L&BXH)
h) Transformer accessories

: *

* data to be filled up & furnished with the offer


Note:
1. If synchronous and de-synchronous transfers are required it shall be in "bumpless
close transition" only. Open transition is not acceptable.
2. Motor to be protected from all the electrical faults by VFD when it is in VFD mode and
by "DOL Feeder" when it is in DOL mode.