Sei sulla pagina 1di 3

Automation Technology>Automation and control systems>Industrial Automation Systems

SIMATIC >PLC>Modular Controller SIMATIC S7>S7-1200

6ES72314HF30-0XB0
6ES7231-4HF30-

S7-1200 ANALOG INPUT, 8AI

Technical / CAx data


Technical Data

CAx data

SIMATIC S7S7-1200, ANALOG INPUT, SM 1231, 8 AI, +/+/-10V, +/+/-5V, +/+/-2.5V, OR 00-20
MA 12 BIT + SIGN OR (13 BIT ADC)
Supply voltages
Rated value
24 V DC

Yes

Current consumption
Current consumption, typ.
from backplane bus 5 V DC, typ.

45 mA
90 mA

Power losses
Power loss, typ.

1.5 W

Connection method
required front connector

Yes

Analog inputs
Number of analog inputs
permissible input frequency for current input
(destruction limit), max.
permissible input current for voltage input
(destruction limit), max.
Cycle time (all channels) max.

8; Current or voltage differential inputs


35 V
40 mA
625 s

Input ranges
Voltage
Current
Thermocouple
Resistance thermometer
Resistance

Yes; 10 V, 5 V, 2.5 V
Yes; 0 to 20 mA
No
No
No

Input ranges (rated values), voltages


-10 V to +10 V
Input resistance (-10 V to +10 V)
-2.5 V to +2.5 V
Input resistance (-2.5 V to +2.5 V)
-5 V to +5 V
Input resistance (-5 V to +5 V)

Input ranges (rated values), currents


0 to 20 mA
Input resistance (0 to 20 mA)

Voltage input
permissible input voltage for voltage input
(destruction limit), max.

Yes
9M ohms
Yes
9M ohms
Yes
9M ohms
Yes
250 ohms
35 V

Current input
permissible input current for current input
(destruction limit), max.

40 mA

Temperature compensation
parameterizable

No

Analog outputs
Number of analog outputs

Analog value creation


Integrations and conversion time/ resolution per
channel
Resolution with overrange (bit including sign),
max.
Integration time, parameterizable
Interference voltage suppression for
interference frequency f1 in Hz

12 bit; + sign
Yes
40 dB, DC to 60 V for interference
frequency 50 / 60 Hz

Smoothing of measured values


parameterizable
Step: None
Step: Low
Step: Medium
Step: High

Yes
Yes
Yes
Yes
Yes

Errors/accuracies
Temperature error (relative to input area)

25C 0.1% to 55C 0.2% total


measurement range

Basic error limit (operational limit at 25 C)


Voltage, relative to input area
Current, relative to input area

+/- 0,1 %
+/- 0,1 %

Interference voltage suppression for f = n x (fl


+/+/- 1%), fl = interference frequency
common mode voltage, max.

12 V

Interrupts/diagnostics/status information
Alarms
Alarms
Diagnostic alarm

Yes
Yes

Diagnoses
Diagnostic functions
Monitoring the supply voltage to the
electronics
Wire break

Yes
Yes
No

Galvanic isolation
Galvanic isolation analog outputs
between the channels and the power supply of No
the electronics

Degree of protection
IP20

Yes

Standards, approvals, certificates


CE mark
C-TICK
FM approval

Yes
Yes
Yes

Mechanics
Plastic

Yes

Dimensions and weight


Dimensions
Width
Height
Depth

Weight

45 mm
100 mm
75 mm

Weight, approx.
Status

180 g
Jun 15, 2010

Siemens AG 2010 - Corporate Information - Privacy Policy - Terms of Use