Data Bulletin

0100DB0501R3/06
04/2006
Cedar Rapids, Iowa, USA

Short Circuit Selective Coordination for Low Voltage Circuit


Breakers
Retain for future use.

INTRODUCTION

The purpose of this data bulletin is to present short circuit selective


coordination data for various combinations of Square D low voltage circuit
breakers.
The scope of this data bulletin encompasses only breaker-to-breaker
short circuit selective coordination. Coordination between circuit breakers in
the overload region of their time-current curves, coordination with fuses and
the protection of motors, transformers and other devices, as well as
coordinated ground fault protection, is not dicussed. Conventional selective
coordination studies using time-current curves are still required to address
these issues. See the REFERENCE section, on page 5, for other data
bulletins on this subject.
This data bulletin is a companion to Enhancing Short Circuit Selective
Coordination with Low Voltage Circuit Breakers, document number
0100DB0403.

Appendix Guide
Appendix A: Levels of Short Circuit Selective Coordination
for UL 489 Standard Circuit Breakers

Page 6

Appendix B: Levels of Short Circuit Selective Coordination


for UL 489 LA/LH Mission Critical Circuit
Breakers

Page 38

Appendix C: Levels of Short Circuit Selective Coordination


for ANSI Low-voltage Power Circuit Breakers

Page 41

Appendix D: A glossary of terms used in this data bulletin.

Page 49

SELECTIVE COORDINATION
DATA

System designers are accustomed to determining the level of short circuit


selective coordination between combinations of low voltage circuit breakers
using trip curves. But using trip curves alone sometimes leads to the
determination of a selective coordination level that is lower than can actually
be achieved.

How Trip Curves Are Developed

Circuit breaker trip curves are typically developed by conducting interruption


tests at various levels of overload and short circuit current. The time
necessary for the circuit breaker to completely interrupt the current flow is
then measured. In the instantaneous region of the trip curve, it is often
assumed that the fault clearing time is constant, hence the curve is usually a
straight line in that region.

Current Limiting Circuit Breakers

Many modern circuit breakers are designed with blow-open contacts and /
or other features to quickly clear high fault currents, resulting in clearing
times that decrease as the current increases, unlike what the conservatively
drawn trip curves may indicate. Even circuit breakers not UL listed or
CSA certified as current limiting may exhibit current limiting characteristics.

Dynamic Characteristics of Circuit


Breakers

All circuit breakers, when they begin to open, serve to limit the prospective
flow of current, even if they are not listed or certified as current limiting. This
is an important factor to consider when two circuit breakers are connected in

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

0100DB0501R3/06
04/2006

series, especially if the downstream circuit breaker opens faster than the
upstream circuit breaker.

Impact on Selective Coordination

In the case of two circuit breakers connected in series, if the downstream


circuit breaker opens faster than the upstream circuit breaker, the
downstream circuit breaker may limit the flow of current below the point at
which the upstream circuit breaker will trip. The result may be a level of
selective coordination higher than might be determined by comparing the
trip curves of the two circuit breakers.

Actual Levels of Selective Coordination

The levels of selective coordination presented in this data bulletin were


determined based on the actual performance of Square D low voltage
circuit breakers. They were determined by comparing the current let-through
of the downstream breaker with the minimum instantaneous trip
characteristic of the upstream breaker, taking into account manufacturing
tolerances. Thus the maximum level of selective coordination was
determined for various pairings of upstream and downstream circuit
breakers.

SELECTIVE COORDINATION AND


SERIES RATINGS

It has been assumed by many that in all cases the upstream circuit breaker
will trip when two circuit breakers are connected in a series rated
combination. But this is not always the case.

Equipment Impedance

Sometimes the impedance of the equipment in which the circuit breakers


are installed, including the added impedance of the upstream circuit
breaker, is sufficient to limit the current to a point where the downstream
circuit breaker is able to interrupt the fault current by itself, without causing
the upstream circuit breaker to trip.

Downstream Circuit Breaker


Construction

Sometimes a circuit breaker manufacturer, for various reasons, may offer a


range of interrupting ratings for a given circuit breaker frame using a single
construction. For example, a circuit breaker frame might be available with
18 and 35 kA interrupting ratings, but both might actually be built with a
35 kA construction. In such an instance the 18 kA rated breaker might be
offered with a 35 kA series rating, which the circuit breaker would be
capable of interrupting on its own without the assistance of an upstream
breaker. Thus the pair might have a level of selective coordination higher
than anticipated.

ASSUMPTIONS

A few assumptions have been made in the compilation of this data.

Circuit Breaker Contact Position

It is assumed that all circuit breakers in the system, with the possible
exception of the branch breaker nearest to the fault, are in the closed (ON)
position when the fault occurs. Some circuit breakers, notably insulated
case and low voltage power circuit breakers, may incorporate a making
current release (MCR) trip function set slightly below the circuit breaker's
close and latch rating. The MCR trip level may be below that of the
adjustable instantaneous or instantaneous selective override trip functions.

Instantaneous Trip Setting

In order to maximize selective coordination, it is assumed that the


instantaneous trip setting on all upstream circuit breakers in the system, if
adjustable, will be set to the highest position. It is also assumed that if the
instantaneous trip function on upstream electronic trip circuit breakers can
be turned off, then it will be turned off.
Turning off the instantaneous trip function does not mean that the circuit
breaker loses its ability to protect against short circuits. Square D

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

electronic trip circuit breakers that have an OFF position on the


instantaneous switch are also equipped with a short time pick-up and delay
function, and may also be equipped with an instantaneous selective
override function if necessary for the proper functioning of the circuit
breaker.
The adjustment of trip settings does not affect any series rating that may be
employed as UL and CSA require series ratings tests to be conducted
with the instantaneous trip adjustment set to its highest position.

HOW TO USE THE TABLES

In order to use the data presented here, some basic information is needed.

System One-line Diagram

A one-line diagram of the system to be studied is absolutely necessary in


order to determine the level of system coordination.

System Voltage

While the system voltage, in and of itself, has no impact on selective


coordination, it does impact circuit breaker selection, which in turn impacts
coordination; thus the system voltage needs to be known.

Circuit Ampacity

The instantaneous trip characteristics of a circuit breaker may be a function


of the frame or current sensor rating rather than the current rating of the
circuit breaker. However, the current rating required to meet the ampacity of
the circuit drives the circuit breaker selection, thus it needs to be known.
(See NEC Articles 210, 215, 220, 225 and 230.)

Available Short Circuit Current

The available short circuit current at each point in the system should be
determined in order to select circuit breakers with the proper interrupting
rating and in turn to determine the level of selective coordination.

Determining Levels of Selective


Coordination

Based on this information, determine the level of selective coordination


between pairs of circuit breakers in the system by finding them in the tables
presented in APPENDIX A on page 6, APPENDIX B on page 38 and
APPENDIX C on page 41. The intersection of the upstream and
downstream circuit breakers in the tables lists the level of selective
coordination between that pair of circuit breakers.
Example

Let's consider a 480Y / 277 Vac system with 35 kA available short circuit
current. Assume that the system consists of an NF 250 A main lugs lighting
panelboard with single pole EG 35 kAIR rated circuit breakers fed from a
JGA36250 circuit breaker with a 35 kA interrupting rating located in an
I-Line power panelboard. Determine the level of selective coordination
between the upstream JGA circuit breaker and downstream EG circuit
breakers by following these steps.
1. Find the 480 Vac table listing EG downstream circuit breakers in
APPENDIX A, Table 6: on page 20.
2. Find the column for the EG downstream circuit breaker to be studied.
3. Go down the column until the row listing the 250 A JG upstream circuit
breaker is found.
4. Read the selective coordination level at the intersection of the column
and row, namely 2.4 kA. This means that the JG upstream circuit
breaker is selectively coordinated with downstream EG circuit breakers
up to 2,400 amps.

OPTIMIZING THE SELECTIVE


COORDINATION LEVEL

20052006 Schneider Electric All Rights Reserved

The selective coordination of a circuit breaker based low voltage system can
be optimized using the techniques presented in the Enhancing Short
Circuit Selective Coordination with Low Voltage Circuit Breakers data

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

0100DB0501R3/06
04/2006

bulletin and the data presented in APPENDIX A on page 6, and


APPENDIX C on page 41. The following is a brief summary of the
techniques more fully presented in the Enhancing Short Circuit Selective
Coordination with Low Voltage Circuit Breakers data bulletin.

Conduct A Short Circuit Study

Conducting a short circuit study may reveal that lower interrupting rated
downstream circuit breakers can be selected, possibly resulting in higher
withstand ratings.

Increase Frame Size

By increasing the frame size of the upstream circuit breaker, it may be


possible to increase the selective coordination at that level in the system.

Change Circuit Breaker Type

By changing the upstream circuit breaker from a molded case to an


insulated case circuit breaker, it may be possible to increase the selective
coordination at that level in the system.

Using the Tables

If the level of selective coordination between the two circuit breakers initially
selected is not sufficient for the application, the tables may be used to find
an alternate upstream circuit breaker selection that will yield a higher level
of selective coordination. This may involve a larger frame size or different
type of circuit breaker, as mentioned above. This may be done by going
down the tables to find possible upstream breakers that may deliver a
higher level of selective coordination.
Example

Using the same example previously stated under Determining Levels of


Selective Coordination, determine if a higher level of selective
coordination can be achieved by following these steps:
1. Move down the column for the EG downstream circuit breaker to be
studied, looking for upstream breakers that will yield a higher level of
selective coordination.
2. When the desired level of selective coordination is found, read across
the row to find the upstream breaker that will yield this level. In this case,
a PG circuit breaker will yield a level of selective coordination of 35,000
amps. This means that the upstream PG circuit breaker is fully selective
with downstream EG circuit breakers.

CONCLUSION

The actual level of selective coordination between pairs of Square D low


voltage circuit breakers needs to be considered when designing a
selectively coordinated low voltage electrical system. This may be done by
finding the pair of circuit breakers in the tables presented in this data bulletin
and reading the actual level of selective coordination.
If the level of selective coordination is not sufficient for the application, an
alternate upstream circuit breaker yielding a higher level of selective
coordination may be found by reading down the table. The alternate may be
an electronic trip circuit breaker whose instantaneous trip function can be
turned OFF, a larger frame size circuit breaker or a different type of circuit
breaker.
A short circuit study to determine the level of short circuit current available at
various points in the system may allow the selection of circuit breakers with
a lower interrupting rating and a higher instantaneous trip level.
The data bulletin Enhancing Short Circuit Selective Coordination with
Low Voltage Circuit Breakers, document number 0100DB0403, should be
consulted for a further explanation of optimizing techniques for enhancing
the level of short circuit selective coordination.

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Finally, do not neglect to properly adjust circuit breakers in the field as all
Square D low voltage circuit breakers are shipped from the factory with all
but the ampere-rating switch in the lowest position.

REFERENCE

20052006 Schneider Electric All Rights Reserved

Enhancing Short Circuit Selective Coordination with Low Voltage


Circuit Breakers
Document Number: 0100DB0403
Overcurrent Protection
Document Number: 0600DB0301
Reducing Fault Stress with Zone-selective Interlocking
Document Number: 0600DB0001

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

0100DB0501R3/06
04/2006

APPENDIX A
Levels of Short Circuit Selective
Coordination for UL 489 Standard
Circuit Breakers
Appendix A
Type

Volts

Downstream
Circuit Breaker
(type or frame size)

Table No.

Page No.
6

QO/B

100150 A

250 A

12

240

400 A

15

6001200 A

18

UL

100250 A

20

400 A

24

6001200 A

27

100250 A

29

400 A

10

33

6001200 A

11

36

480

600

Table 1:

The data in the following tables for UL 489 Listed molded and insulated
case circuit breakers also applies to CSA C22.2 #5-02 and ANCE NMX
J-266 Certified circuit breakers. All data is at 60 Hz. The data does not apply
to circuit breakers that are Certified to IEC 60947-2 only or at frequencies
other than 60 Hz.
Fully rated and series rated pairs of circuit breakers where there is a
reasonable expectation of selective coordination are shown. Pairings of the
same frame size or where the upstream circuit breaker might be a current
limiting circuit breaker are not shown as such pairings would not be
expected to selectively coordinate.
Gray shaded cells in the tables indicate series rated combinations. It should
be noted that series ratings vary by equipment type, thus published
information regarding the specific type of Square D equipment being
studied should be consulted for the actual series ratings available in that
equipment.
Based on laboratory testing, Square D certifies the following levels of
selective coordination based upon the construction of the specific circuit
breakers referenced as of the date of publication of this document.

UL 240 Vac QO/B Selective Coordination


Key:

Upstream
Circuit Breaker2
QO/B3

QO/B-VH3

QH/B3

25

HD4

10

10

10

10

22

22

22

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

FH

65

QO/BVHGFI/
EPD

65

0.9

0.9

1.3

1.3

NT-H
800/250 A

65

65

65

NW-N
800/250 A

65

65

65

1.3

QO/BAFI

QO/BVHAFI

1 Pole
120 V
15-20 A

1 Pole
120 V
15-20 A

10

10

22

10

22

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

125 HL4

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

10

QB

2.0

2.0

2.0

2.0

2.0

2.0

2.0

JD4

2.3

2.3

2.3

2.3

QD5, 4

2.0

JG4

2.4

2.4

CG

2.2

2.2

25

65

2.0
2.4

2.3

2.3

2.3

2.3

2.3

22

2.3

2.3

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.2

2.2

2.2

2.2

2.2

2.1

2.1

2.1

2.6

2.6

2.6

2.2

2.2

2.2

NT-H
800/250 A

65

65

65

PG

65

65

65

PK

65

65

65

2.1

2.1

2.1

65

65

65

QG5, 4

2.1

2.1

2.1

2.1

NW-N
800/250 A
JJ

2.6

2.6

2.6

2.6

100 PJ6
QJ7, 5, 4, 8
125 JL4

65

1.3

100 HJ

250 A

65

0.9

HG4
100/
150 A

QO/B-GFI/EPD

1 Pole
2 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole
1 Pole
2 Pole
1 Pole
120 V 120/240 V 240 V
240 V
120 V 120/240 V 240 V
120 V 120/240 V 240 V
120 V 120/240 V 120 V
15-70 A 15-125 A 15-100 A 15-100 A 15-30 A 15-150 A 15-150 A 15-30 A 15-30 A 15-150 A 15-30 A 15-60 A 15-30 A
kAIR1

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Type

Max.
Continuous
Current
Rating

Fully Rated

2.6
25

2.1
2.4

2.1
2.4

2.4

2.4

25

25

2.1

2.1

2.1

2.1

2.1

2.4

2.4

2.4

2.4

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 1:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 240 Vac QO/B Selective Coordination (continued)


Key:

Upstream
Circuit Breaker2
QO/B3

QO/B-VH3

QH/B3

42

10

10

10

10

22

LA9

QO/BVHGFI/
EPD

LA-MC

22

22

1810

DG

LH-MC
MG11

400 A
65

10

10

10

10

10

6510

10

10

10

10

10

65

65

65

3.2

3.2

65

3.2

3.2

65

5.6

5.6

10

10

22

QO/BVHAFI

1 Pole
120 V
15-20 A

1 Pole
120 V
15-20 A

10

22

10

10

*3.6

65

3.6

3.6

NT-H
1200 A

65

65

65

NW-N
2000 A

65

65

65

PG

65

65

65

PK

65

65

65

DG

65

4.8

4.8

MG11

65

65

QO/BAFI

3.2

LH

600 A

QO/B-GFI/EPD

1 Pole
2 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole
1 Pole
2 Pole
1 Pole
120 V 120/240 V 240 V
240 V
120 V 120/240 V 240 V
120 V 120/240 V 240 V
120 V 120/240 V 120 V
15-70 A 15-125 A 15-100 A 15-100 A 15-30 A 15-150 A 15-150 A 15-30 A 15-30 A 15-150 A 15-30 A 15-60 A 15-30 A
kAIR1

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Type

Max.
Continuous
Current
Rating

Fully Rated

65

5.4

5.4

NT-H
1200 A

5.4

65

65

65

NW-N
2000 A

65

65

65

PG

65

65

65

PK

65

65

65

RG

65

65

65

RK

65

65

65

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

QO plug-on breakers rated 15100 A only.

Series rating with 35-150 A QO/B-VH 3-pole circuit breakers only.

Series ratings limited to 70225 A only.

Series rating at 42 kA with 1530 A QO/B-VH 2- and 3-pole circuit breakers only.

Rated 208 Y / 120 Vac

Series rating with 35150 A QO/B-VH 2-pole circuit breakers only.

Series rating with 15125 A QO circuit breakers only.

10

See Appendix B for additional information about LA-MC and LH-MC levels of selective coordination with QO circuit breakers at 208 Y / 120 Vac.

20052006 Schneider Electric All Rights Reserved

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 2:

0100DB0501R3/06
04/2006

UL 240 Vac 100150 A Selective Coordination


Key:

Type

EDB

ECB

EGB

EJB

FA

HD

FH

HG

FJ

HJ

HL

FI

25

65

65

100

25

25

65

65

100

100

125

200

50

50

NT-L 800/250 A

125

NT-LF 800/250 A

125

NW-L 800/250 A

125

200

125

200

kAIR1
25

HD

50

NT-N 800/250 A

100/150 A

100

125

200

1.3
50

50

0.9

0.9

HG

1.3

1.3

NT-H 800/250 A

65

65

65

65

NW-N 800/250 A

65

65

65

65

HJ

1.3

FH
65

0.9

NT-L1 800/250 A

100

100

100

NW-H 800/250 A

100

100

100

HL

1.3

NW-LF 800/250 A
25
50

JD

2.3

QD

2.0

NT-N 800/250 A

50

JG

65

2.4
65

65

PG

65

65

PK

65

65

2.1

NW-N 800/250 A

65
2.6

125

2.0

2.0

65

2.1

2.6

2.6

50

50

2.4

2.4

65

65

65

65

65

65

2.1

65

NT-L1 800/250 A
100

2.3

2.4

2.1

JJ

2.3

50

NT-H 800/250 A

QG

250 A

2.6

65

65

2.6

2.6

100

NW-H 800/250 A

100

PJ

100

QJ3

2.1

JL

100
2.1
2.4

PL

50

2.1

2.1

2.4

2.4

2.4

2.4

125

125

125
9

NT-LF 800/250 A

NW-L 800/250 A

200
200

LA

3.2

3.2

5.6

5.6

5.6

50

50

50

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

65

5.6

3.6

3.6

NT-H 1200 A

65

NW-N 2000 A

65

PG

65

65

LA-MC
NT-N 1200 A

LH
LH-MC
65

100
100

2.4
125

DG
400 A

100
100

100

NW-LF 800/250 A
42

2.6
100

2.1
2.4

2.6
100

100

NT-L 800/250 A
200

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

MG

3.2

3.2

42
50

3.2

3.2

3.2

5.6

5.6

3.6

3.6

65

65

65

65

65

65

65

65

3.6

65

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 2:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 240 Vac 100150 A Selective Coordination (continued)


Key:

Type
kAIR1
65

100

125

EDB

ECB

EGB

EJB

FA

HD

FH

HG

FJ

HJ

HL

FI

25

65

65

100

25

25

65

65

100

100

125

200

65

65

65

65

3.6

3.6

PK
DJ

3.2

MJ

3.6

3.6

3.6

3.2

3.2

3.6

3.6

NT-L1 1200 A

100

100

100

NW-H 2000 A

100

100

100

100

100

PJ

400 A

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

100

100

100

PL

125

100
125

125

125

NT-L 1200 A
200

NT-LF 1200 A

NW-L 1600 A

200

NW-LF 1600 A
50

65

600 A
100

200

NT-N 1200 A

50

50

DG

4.8

4.8

MG

65

NT-H 1200 A

65

65

65

65

NW-N 2000 A

65

65

65

65

PG

65

65

PK

65

65

RG

65

65

RK

65

65

65

65

DJ

4.8

MJ

5.4

NT-L1 1200 A

100

NW-H 2000 A
PJ

50

4.8

4.8

5.4

5.4

65

65

65

65

65

65

65

65

5.4

5.4

4.8
5.4

100

100
100

100

RJ
125

5.4

50

100

100

4.8

100

5.4

100

100

100

100

100

100

100

100

100

100

PL

125

125

125

125

RL

125

125

125

125

125

100

NT-L 1200 A
200

NT-LF 1200 A

NW-L 1600 A

200

NW-LF 1600 A
50

65

800 A

100

125

200

NT-N 1200 A

50

50

50

50

7.2

65

MG

65

65

NT-H 1200 A

65

65

65

65

NW-N 2000 A

65

65

65

65

PG

65

65

PK

65

65

RG

65

65

RK

65

65

7.2

65

65

MJ

100

NT-L1 1200 A

100

7.2

7.2

NW-H 2000 A

100

PJ

100

RG

100

PL

20052006 Schneider Electric All Rights Reserved

65

65

65

65

65

65

65

65

7.2

7.2

100

7.2

100

100

100

100

100

100

100

100

100

100

125

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 2:

0100DB0501R3/06
04/2006

UL 240 Vac 100150 A Selective Coordination (continued)


Key:

Type
kAIR1
125

RL

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

EDB

ECB

EGB

EJB

FA

HD

FH

HG

FJ

HJ

HL

FI

25

65

65

100

25

25

65

65

100

100

125

200

125

125

125

125

125

NT-L 1200 A
800 A

200

NT-LF 1200 A

NW-L 1600 A

200

NW-LF 1600 A
50

65

200

NT-N 1200 A

50

50

NT-H 1200 A

65

65

NW-N 2000 A

65

65

65

65

65

65

65

65

65

65

65

65

PG
PK
RG
RK

1000 A

100

125

NT-L1 1200 A

100

100

NW-H 2000 A

100

100

PJ

RJ

100

PL

RL

125

125

100

100

100

100

100

125

125

125

125

NT-L 1200 A
200

NT-LF 1200 A

NW-L 1600 A

200

NW-LF 1600 A
50

65

200

NT-N 1200 A

50

50

NT-H 1200 A

65

65

NW-N 2000 A

65

65

PG

65

65

65

RG

65

65

65

65

65

RK

1200 A

100

NT-L1 1200 A

100

100

NW-H 2000 A

100

100

PJ

PK

125

100

100

100

100

100

100

RJ

100

100

PL

125

RL

125

125

125

125

125

NT-L 1200 A
200

NT-LF 1200 A

NW-L 1600 A

200

NW-LF 1600 A

200

NW-N 2000 A
65

RG

65

RK
1600 A

10

100

65

65

65

65

65

65

NW-H 2000 A
RJ

100

125

RL

125

200

NW-L 1600 A

100
125

125

100

100

100

100
125

125
125

200

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 2:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 240 Vac 100150 A Selective Coordination (continued)


Key:

1600 A

Type
kAIR1
200

EDB

ECB

EGB

EJB

FA

HD

FH

HG

FJ

HJ

HL

FI

25

65

65

100

25

25

65

65

100

100

125

200

125

200

65

65

NW-LF 1600 A
NW-N 2000 A

65

RG

65

RK
2000 A

100
125
200

65
2500
3000 A

4000
5000 A

100

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

65

65

65

65

NW-H 2000 A
RJ

100

RL

125

100
125

100

100

100

100

125

125

125

NW-L 2000 A

200

NW-LF 2000 A
RG

200
65

RK

65

65

65

65

NW-H 3000 A
RJ

100

125

RL

125

200

NW-L 3000 A

100

NW-H 6000 A

200

NW-L 6000 A

100
125

100

100

100

100

125

125

125
200

100

100
200

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

Rated 208 Y / 120 Vac.

See Appendix B for additional information about LA-MC and LH-MC levels of selective coordination with E frame circuit breakers.

20052006 Schneider Electric All Rights Reserved

11

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 3:

0100DB0501R3/06
04/2006

UL 240 Vac 250 A Selective Coordination


Key:

42
50

Type

LA

QB

QD

JD

QG

JG

PG

QJ

JJ

LE

LX

PJ

JL

PL

KI

10

25

25

65

65

65

100

100

100

100

100

125

125

200

3.6

3.6

50

50

36

3.6

3.6

3.6

3.6

LA-MC

5.6

5.6

NT-N 1200 A

50

50

DG

3.2

3.2

3.2

3.2

LH

3.2

3.2

LH-MC
65

5.6

3.6

3.6

NT-H 1200 A

65

65

36

65

65

NW-N 1200 A

65

65

36

65

65

PG

400 A

36

5.6

MG

3.6

65

3.6

65

PK

65

65

65

65

65

65

65

65

DJ
MJ
100

3.2
3.6

3.6

3.6

3.6

NT-L1 1200 A

100

NW-H 1200 A

100

100

100

100

36

100

100

PL

3.6

100

3.6

3.2

3.6

PJ
125

125

100
125

125

3.6

125

NT-L 1200 A
200

NT-LF 1200 A

NW-L 1200 A

200

NW-LF 1200 A
50

200

NT-N 1200 A

50

DG

50

36

5.4

NT-H 1200 A

65

65

36

65

65

NW-N 1200 A

65

65

36

65

65

PG

22

5.4

22

65

65

RK

65

65

65

65

65

65

65

65

65

65

51

65

65

65

65

51

65

65

5.4

DJ
MJ

125

5.4

4.8
5.4

RG

100

36

4.8
65

PK

600 A

50

5.4

MG

65

4.8
100

5.4

4.8

5.4

5.4

5.4

NT-L1 1200 A

100

NW-H 1200 A

100

100

100

100

100

100

100

100

100

PJ

100

100

100

RJ

100

100

100

PL

125

125

125

RL

125

125

125

43

125

NT-L 1200 A
200

NT-LF 1200 A

NW-L 1200 A

200

NW-LF 1200 A
800 A

12

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

50

NT-N 1200 A

65

MG

200

65

65

50

50

7.2

65

36

50

50

7.2

7.2

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 3:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 240 Vac 250 A Selective Coordination (continued)


Key:

65

Type

QB

QD

JD

QG

JG

PG

QJ

JJ

LE

LX

PJ

JL

PL

KI

10

25

25

65

65

65

100

100

100

100

100

125

125

200

NT-H 1200 A

65

65

36

65

65

NW-N 2000 A

65

65

36

65

65
65

PG

65

65

PK
RG

65

65

100

100

RK
MJ

800 A

100

125

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

65

65

65

65

65

65

65

65

65

51

65

65

65

51

65

100

7.2

7.2

65

65

7.2

7.2

NT-L1 1200 A

100

NW-H 2000 A

100

100

100

100

36

PJ

100

100

100

100

RJ

100

100

100

100

100

100

100

PL

125

125

125

125

RL

125

125

125

125

100

43

NT-L 1200 A
200

NT-LF 1200 A

NW-L 1600 A

200

NW-LF 1600 A
50

65

200

NT-N 1200 A

50

125

50

50

65

65

36

65

65

NW-N 2000 A

65

65

36

65

65
65

PG

65

65

PK
65

65

RK

100

36

NT-H 1200 A

RG

1000 A

50

65

65

65

65

65

65

65

65

65

51

65

65

65

65

51

65

65

NT-L1 1200 A

100

NW-H 2000 A

100

100

100

100

36

100

100

PJ

100

100

100

100

RJ

100

100

100

100

100

100

PL

125

125

125

125

RL

125

125

125

125

NT-L 1200 A
200

NT-LF 1200 A

NW-L 1600 A

200

NW-LF 1600 A
50

65

200

NT-N 1200 A

50

50

50

65

65

36

65

65

65

65

36

65

65
65

PG

65

65

PK
65

65

65

65

65

65

65

65

65

65

65

51

65

65

65

65

36

NT-L1 1200 A

125

50

NW-N 2000 A

RK

100

36

NT-H 1200 A

RG

1200 A

43

100

NW-H 1200 A

100

65

65

100

100

100

PJ

100

100

100

100

100

100

100

RJ

100

100

100

100

100

100

100

125

125

PL

20052006 Schneider Electric All Rights Reserved

125

100
125

13

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 3:

0100DB0501R3/06
04/2006

UL 240 Vac 250 A Selective Coordination (continued)


Key:

125

Type

RL

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

QB

QD

JD

QG

JG

PG

QJ

JJ

LE

LX

PJ

JL

PL

KI

10

25

25

65

65

65

100

100

100

100

100

125

125

200

125

43

125

125

125

NT-L 1200 A
1200 A

200

NT-LF 1200 A

NW-L 1600 A

200

NW-LF 1600 A

200

NT-N 1600 A
65

RG

65

RK
1600 A

100
125
200

100
125
200

65

2500 A

30006000 A

100

36

65

65

65

65

51

65

65

65

65

51

65

65

RJ

100

100

RL

125

125

100

100

100

100

36

100

100

100

100

100

125

125

43

NW-L 1600 A

200

NW-LF 1600 A

200

RG

51

RK
2000 A

65

NW-H 2000 A

NT-N 1200 A
65

65

65

65

36

65

65

65

65

51

65

65

65

65

51

65

65

NW-H 2000 A
RJ

100

100

RL

125

125

100

100

100

100

36

100

100

100

100

100

125

125

43

NW-L 1600 A

200

NW-LF1600 A
RG

200
51

RK

65

65

51

65

65

51

NW-H 3000 A
RJ

100

100

125

125

125

RL

200

NW L 3000 A

100

NW-H 3000 A

200

NW-L 6000 A

65

65

65

65

100

100

100

100

100

100

100

100

100

100

125

125

43
200

100

100

100

100

100
200

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

14

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 4:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 240 Vac 400 A Selective Coordination


Key:

Type
kAIR1
50

65

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

Q4

LA

LAMC

LH

LHMC

DG

DJ

PG

LC

LE

LX

PJ

PL

LI

LXI

42

42

42

65

65

65

100

65

100

100

100

100

125

200

200

50

50

50

43

125

125
9

NT-N 1200 A

50

50

DG

5.4

5.4

36

MG

5.4

5.4

5.4

5.4

5.4

NT-H 1200 A

65

65

65

36

65

65

NW-N 2000 A

65

65

65

36

65

65

PG

22

22

65

65

65

PK

22

22

65

65

65

RG

65

65

65

51

65

65

RK

65

65

65

51

65

65

DJ
MJ

600 A
100

125

200

5.4

5.4

5.4

5.4

NT-L1 1200 A

NW-H 2000 A

100

100

100

100

36

PJ

RJ

100

100

100

100

5.4

100

PL
RL
NT-L 1200 A

NT-LF 1200 A

NW-L 1600 A

200

200

22

22

NW-LF 1600 A
50

65

NT-N 1200 A

50

50

50

MG

7.2

7.2

7.2

7.2

7.2

NT-H 1200 A

65

65

65

36

65

65

NW-N 2000 A

65

65

65

36

65

65

PG

22

22

65

65

65

PK

22

22

65

65

65

RG

65

65

65

51

65

65

RK

65

65

65

51

MJ
800 A
100

125

200

36

7.2

7.2

NT-L1 1200 A

NW-H 2000 A

100

100

100

100

36

PJ

RJ

100

100

100

PL

125

125

NT-L 1200 A

NT-LF 1200 A

NW-L 1600 A

200

200

22

22

RL

43

NW-LF 1600 A
50
1000 A

65

NT-N 1200 A

50

50

50

36

50

50

NT-H 1200 A

65

65

65

36

65

65

NW-N 2000 A

65

65

65

36

65

65

PG

22

22

65

65

65

20052006 Schneider Electric All Rights Reserved

15

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 4:

0100DB0501R3/06
04/2006

UL 240 Vac 400 A Selective Coordination (continued)


Key:

Q4

LA

LAMC

LH

LHMC

DG

DJ

PG

LC

LE

LX

PJ

PL

LI

LXI

42

42

42

65

65

65

100

65

100

100

100

100

125

200

200

PK

22

22

65

65

65

RG

65

65

65

51

65

65

RK

65

65

65

51

65

65

43

125

125
9

Type
kAIR

65

100
1000 A
125

200

NT-L1 1200 A

NW-H 2000 A

100

100

100

36

PJ

RJ

100

100

PL
RL
NT-L 1200 A

NT-LF 1200 A

NW-L 1600 A

200

200

22

22

NW-LF 1600 A
50

65

1200 A

100

125

200

NT-N 1200 A

50

50

50

36

50

50

NT-H 1200 A

65

65

65

36

65

65

NW-N 2000 A

65

65

65

36

65

65

PG

22

22

65

65

65

PK

65

65

65

65

65

RG

65

65

65

51

65

65

RK

65

65

65

36

65

65

NT-H 1200 A

100

100

100

100

36

NW-H 2000 A

PJ

100

100

100

100

RJ

100

100

100

100

100

PL
RL

43

1600 A

100
125
200

16

125

125
9

NT-L 1200 A

NT-LF 1200 A

NW-L 1600 A

200

200

22

22

NW-LF 1600 A

65

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

NW-N 2000 A

65

65

65

36

65

65

RG

65

65

65

51

65

65

RK

65

65

65

51

65

65

NW-H 2000 A

100

100

100

100

36

RJ

100

100

100

100

100

RL

125

125

NW-L 1600 A

43

200

200

NW-LF 1600 A

22

22

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 4:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 240 Vac 400 A Selective Coordination (continued)


Key:

65

2000 A

100
125
200

2500 A

3000 A

Q4

LA

LAMC

LH

LHMC

DG

DJ

PG

LC

LE

LX

PJ

PL

LI

LXI

42

42

42

65

65

65

100

65

100

100

100

100

125

200

200

NW-N 2000 A

65

65

65

36

65

65

RG

65

65

65

51

65

65

RK

65

65

65

51

65

65

43

Type
kAIR

NW-H 2000 A

100

100

100

100

36

RJ

100

100

100

100

100

RL

125

125

NW-L 2000 A

200

200

NW-LF 2000 A

22

22

125

125

65

RG

65

65

65

200

RK

65

65

65

100

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

51

65
65

65

NW-H 3000 A

100

100

100

100

100

RJ

100

100

100

100

100

125

RL

200

NW-L 3000 A

4000 A

100

NW-H 6000 A

6000 A

200

NW-L 6000 A

51

65

43

100

100

100

100

100

200

200

200

200

200

200

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

20052006 Schneider Electric All Rights Reserved

17

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 5:

0100DB0501R3/06
04/2006

UL 240 Vac 6001200 A Selective Coordination


Key:

50

65

Type

DG

DJ

LC

LE

LX

LI

LXI

MG

MJ

PG

PK

PJ

PL

NT

NT

NT

NT

65

100

100

100

100

200

200

65

100

65

65

100

125

50

65

100

200

36

36

36

NT-N 1200 A

50

50

50

50

MG

7.2

7.2

7.2

7.2

NT-H 1200 A

65

65

65

65

36

36

36

NW-N 2000 A

65

65

65

65

36

36

36

PG

65

65

65

65

22

PK

65

65

65

65

22

RG

65

65

65

65

65

51

51

RK

65

65

65

65

65

51

51

7.2

7.2

7.2

MJ
800 A
100

125

7.2

50

65

1000 A

100

125

NW-H 2000 A

100

100

100

100

36

36

PJ

RJ

100

100

100

100

51

PL

RL

125

125

50

1200 A

65

100

18

36
9

100

43

NT-LF 1200 A

NW-L 1600 A

200

200

32

NW-LF 1600 A

22

22

22

NT-N 1200 A

50

50

50

50

36

36

36

NT-H 1200 A

65

65

65

65

36

36

36

36

36

NW-N 2000 A

65

65

65

65

36

PG

65

65

65

65

22

PK

65

65

65

65

22

RG

65

65

65

65

65

51

51

RK

65

65

65

65

65

51

51

36

NT-L1 1200 A

NW-H 2000 A

100

100

100

100

36

36

PJ

RJ

100

100

100

100

43

PL

RL

125

125

NT-L 1200 A
200

36

NT-L1 1200 A

NT-L 1200 A
200

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully
Rated

36

36

100

43

NT-LF 1200 A

NW-L 1600 A

200

200

32

NW-LF 1600 A

22

22

22

NT-N 1200 A

50

50

50

50

36

36

NT-L 1200 A

NW-N 2000 A

65

65

65

65

36

36

36

PG

65

65

65

65

22

PK

65

65

65

65

22

RG

65

65

65

65

65

51

51

RK

65

65

65

65

65

51

51

100

100

100

NT-L1 1200 A

100

36

36

36

36

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 5:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 240 Vac 6001200 A Selective Coordination (continued)


Key:

Type

DG

DJ

LC

LE

LX

LI

LXI

MG

MJ

PG

PK

PJ

PL

NT

NT

NT

NT

65

100

100

100

100

200

200

65

100

65

65

100

125

50

65

100

200

NW-H 2000 A
100

1200 A

125

200

65

1600 A

100
125
200

65

2000 A

100
125
200
65

25003000 A

40006000 A

100

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully
Rated

100

100

100

100

36

PJ

RJ

100

100

100

100

36

43

PL

RL

125

125

36

100

43

NT-L 1200 A

NT-LF 1200 A

NW-L 1600 A

200

200

32

NW-LF 1600 A

22

22

22

NW-N 1200 A

65

36

36

36

RG

65

65

51

51

36

NW-H 2000 A

100

100

100

100

36

36

RJ

100

100

100

100

43

100

36

RL

125

125

NW-L 1600 A

200

200

43
32

NW-LF 1600 A

22

22

22

NW-N 2000 A

65

36

36

36

RG

65

65

51

51

36

NW-H 2000 A

100

100

100

100

36

36

RJ

100

100

100

100

43

100

RL

125

125

NW-L 2000 A

200

200

NW-LF 2000 A

22

22

RG

65

43
200
22
65

51

51

NW-H 3000 A

100

100

100

100

100

100

RJ

100

100

100

100

43

100

125

RL

125

125

200

NW-L 3000 A

200

200

100

NW-H 6000 A

200

NW-L 6000 A

100

100

100

100
200

100

43
200
100

200

36

100

100
200

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

20052006 Schneider Electric All Rights Reserved

19

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 6:

0100DB0501R3/06
04/2006

UL 480 Vac 100250 A Selective Coordination


Key:

18

Type

ECB3 EDB3 EGB3 EJB3 FA FH FJ


14

FA

18

1.3

35

HG

1.3

50

NT-N/H
800/250 A
HJ

100/150 A

150
18
35

50

1.3

HL JD

JG

PG JJ

LE LX

PJ

65 200 18

35

65 100 18

35

35

65

65 100 100 200

50

50
1.3
65

NW-N 800/250 A

65

65

65

1.3

1.3

1.3

NT-L 800/250 A

100

NT-LF 800/250 A

100

NW-H 800/250 A

100

100

NW-L 800/250 A

150

NW-LF 800/250 A
JD
JG

2.3
2.4

2.3

2.4

2.4

35

22

35

NT-N/H 800/250
A

50

50

35
50

50

50

2.6

2.6 2.6 2.6

NT-L1 800/250 A

65

65

NW-N 800/250 A

65

65

65

2.6

2.6

2.7

2.7

65

65

2.7

2.7 2.7 2.7

50
2.6

2.6

2.6

9
2.7

2.7

2.7 2.7

NT-L 800/250 A

NT-LF 800/250 A

9
100

PL

30

NW-L 800/250 A

35

3.2

50
65

20

3.2 3.2

LA-MC

LH-MC

150

LA

DG

400 A

150

NW-LF 800/250 A

LH

KI

2.3

2.4

NW-H 800/250 A

150

65

PL

150
2.3

PG

JL

65

JL

50

65

1.3

1.3

PJ

100

25

HJ

1.3

JJ
65

18

HG

1.3

PK

250 A

65

HD

NT-L1 800/250 A

HL
100

35

FI

0.9

HD

65

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

3.2

3.2

3.2
30.0

30.0

3.2

3.2

3.2

3.2

3.2

3.2

35.0

35.0

MG

*
3.6

3.6

3.6

3.6

3.6

PG

35

35

35

35

35

NT-N/H 1200 A

50

50

50

PK

50

50

50

DJ

3.2

3.2

3.2

3.6 3.6
35
36

50

35

50

50

50

50

3.2

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 6:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 480 Vac 100250 A Selective Coordination (continued)


Key:

65

Type

ECB3 EDB3 EGB3 EJB3 FA FH FJ


14

18

35

25

FI

HD

HG

HJ HL JD

JG

PG JJ

LE LX

PJ

65 200 18

35

65 100 18

35

35

65

65 100 100 200

65

18

MJ

3.6

3.6 3.6 3.6

NT-L1 1200 A

65

65

NW-N 2000 A

65

65

65

65

65

65

36

PJ

65

65

3.6

NT-L 1200 A

400 A
100

35

50

600 A

65

100

NW-H 2000 A

36
9

800 A

100 36

9
150

NW-LF 1600 A

150

150

DG

4.8

MG

5.4

5.4

5.4

5.4

5.4

PG

35

35

35

35

35

RG

35

4.8

4.8

35

35

5.4 5.4

35

35

35

35

35

35
36

NT-N/H 1200 A

50

50

50

50

50

50

PK

50

50

50

50

50

50

DJ

4.8

4.8

4.8

4.8

MJ

5.4

5.4 5.4 5.4

5.4

5.4 5.4 5.4

NT-L1 1200 A

65

65

NW-N 2000 A

65

65

65

65

65

65

36

PJ

65

65

RJ

65

65

65

65

65

65

65

RK

65

65

65

65

65

65

65

NT-L 1200 A

NT-LF 1200 A

NW-H 2000 A

100
9

100 36

100

100 43

NW-L 1600 A

150

150

NW-LF 1600 A

150

150

MG

7.2

7.2

7.2

7.2

PG

35

35

35

35

35

35

7.2 7.2

35

35
35

50

50

50

PK

50

50

50

7.2

7.2 7.2 7.2

7.2 7.2

50

35
35

NT-H 1200 A

MJ

65

KI

150

RG
50

PL

NW-L 1600 A

RL

35

65

JL

3.6 3.6 3.6

NT-LF 1200 A

PL

150

65

PL
150

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

36

NT-L1 1200 A

NW-N 2000 A

65

65

65

65

36

PJ

RJ

65

65

65

65

65

RK

65

65

65

65

65

20052006 Schneider Electric All Rights Reserved

21

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 6:

0100DB0501R3/06
04/2006

UL 480 Vac 100250 A Selective Coordination (continued)


Key:

100

Type

ECB3 EDB3 EGB3 EJB3 FA FH FJ


14

18

35

65

18

25

FI

HD

HG

HJ

HL JD

JG

PG JJ

LE LX

PJ

65 200 18

35

65 100 18

35

35

65

65 100 100 200

35

50

65
1000 A

100

NW-H 2000 A

100
9

50

65

1200 A

100

9
100 43

150

150

150

150

PG

35

RG

35

35

35

35
35

35

35

35

35

35

NT-N/H 1200 A

50

50

50

50

PK

50

50

50

50

36

NT-L1 1200 A

NW-N 2000 A

65

65

65

65

36

PJ

RJ

65

65

65

65

65

RK

65

65

65

65

65

NT-L 1200 A

NT-LF 1200 A

NW-H 2000 A

100
9

100 36

100

100 43

NW-L 1600 A

150

150

NW-LF 1600 A

150

150

PG

35

RG

35

35

35

35
35

35

35

35

NT-N/H 1200 A

50

50

50

50

PK

50

50

50

50

36

NT-L1 1200 A

NW-N 2000 A

65

65

65

65

36

PJ

RJ

65

65

65

65

65

RK

65

65

65

65

65

NT-L 1200 A

NT-LF 1200 A

NW-H 2000 A

100

NW-H 3000 A

100 36

100
9

RL

22

NW-LF 1600 A

PL

150

NW-L 1600 A

RL

35

KI

100 36

100

PL

150

65

PL

NT-LF 1200 A

RL
150

65

JL

NT-L 1200 A

PL

800 A

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

9
100

100 100
9

9
100 43

NW-L 1600 A

150

NW-L 3000 A

150

150
150

NW-LF 2000 A

150

150

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 6:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 480 Vac 100250 A Selective Coordination (continued)


Key:

35

65

Type

ECB3 EDB3 EGB3 EJB3 FA FH FJ


14

18

35

100

150

35

65

2000 A

100

150

35
65
2500
3000 A

100

150
4000
6000 A

65

18

25

FI

HD

HG

HJ HL JD

JG

PG JJ

LE LX

PJ

65 200 18

35

65 100 18

35

35

65

65

65 100 100 200

35

35

35

35

RG

35

65

NW-N 2000 A

65

65

65

65

36

RJ

65

65

65

65

65

65

65

65

65

RK
1600 A

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

65

65

65

JL

PL

NW-H 2000 A

100

NW-H 3000 A

100

100 100

RL

100

100 43

KI

100 36

NW-L 1600 A

150

NW-L 3000 A

150

150

NW-LF 2000 A

150

150

RG

150

35

35

35

35

NW-N 2000 A

65

65

65

65

36

RJ

65

65

65

65

65

RK

65

65

65

65

65

NW-H 2000 A

100

100 36

NW-H 3000 A

100

100 100

NW-H 6000 A

100

100 100

RL

100

100 43

NW-L 2000 A

150

150

NW-L 3000 A

150

150

NW-L 6000 A

150

150

NW-LF 2000

150

150
35

35

RJ

RG

35
65

35

35
65

65

65

65

RK

65

65

65

65

65

NW-H 3000A

100

100 100

NW-H 6000A

100

100 100

RL

100

100 43

NW-L 3000A

150

NW-L 6000A

150

100

NW-H 6000 A

150

NW-L 6000 A

150
150
100

100 100

150

150

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

Rated 480 Y / 277 Vac.

See Appendix B for additional information about LA-MC and LH-MC levels of selective coordination with E frame circuit breakers at 480 Y / 277 Vac.

20052006 Schneider Electric All Rights Reserved

23

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 7:

0100DB0501R3/06
04/2006

UL 480 Vac 400 A Selective Coordination


Key:

35

50

Type

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

LA

LA-MC

LH

LH-MC

DG

DJ

PG

LC

LE

LX

PJ

PL

LI

LXI

30

30

35

35

35

65

35

65

65

65

65

100

200

200

5.4

NT-L 1200 A

NT-LF 1200 A

NW-H 2000 A

36

100

100

43

100

100

NW-L 1600 A

150

150

NW-LF 2000 A

22

22

DG

4.8

4.8

MG

5.4

5.4

5.4

5.4

PG

22

22

35

35

35

RG

35

35

35

35

35

35

NT-N/H 1200 A

50

50

50

50

PK

50

50

50

50

5.4

36

DJ
MJ

600 A

65

100

5.4

5.4

5.4

NT-L1 1200 A

NW-N 2000 A

65

65

65

65

36

PJ

RJ

65

65

65

65

43

RK

65

65

65

65

51

PL
RL
150

MG
35

50

65
800 A

100

7.2

7.2

7.2

PG

22

22

35

RG

35

35

35

7.2

35

7.2

35

35

35

35

NT-N 1200 A

50

50

50

50

PK

50

50

50

50

MJ

7.2

36

7.2

7.2

7.2

NT-L1 1200 A

NW-N 2000 A

65

65

65

65

36

PJ

RJ

65

65

65

65

43

RK

65

65

65

65

51

NT-L 1200 A

NT-LF 1200 A

NW-H 2000 A

36

100

100

43

100

100

NW-L 1600 A

150

150

NW-LF 2000 A

22

22

PL
RL
150

1000 A

24

35

PG

22

22

35

RG

35

35

35

35

22

22

51

51

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 7:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 480 Vac 400 A Selective Coordination (continued)


Key:

50

65

1000 A

100

Type

LA

LA-MC

LH

LH-MC

DG

DJ

PG

LC

LE

LX

PJ

PL

LI

LXI

30

30

35

35

35

65

35

65

65

65

65

100

200

200

36

NT-L 1200 A

NT-LF 1200 A

NW-H 2000 A

36

100

100

43

100

100

NW-L 1600 A

150

150

NW-LF 2000 A

22

22

NT-N/H 1200 A

50

50

50

50

PK

50

50

50

50

NT-L1 1200 A

NW-N 2000 A

65

65

65

65

36

PJ

RJ

65

65

65

65

43

RK

65

65

65

65

51

PL
RL
150

35

50

65

1200 A

100

PG

22

22

RG

35

35

35

35

35

35

35

NT-N/H 1200 A

50

50

50

PK

50

50

50

36

NT-L1 1200 A

NW-N 2000 A

65

65

65

36

PJ

RJ

65

65

65

43

RK

65

65

65

51

NT-L 1200 A

NT-LF 1200 A

NW-H 2000 A

36

100

100

NW-H 3000 A

100

100

100

PL

100

100

NW-L 1600 A

100

100

NW-L 3000 A

150

150

NW-LF 2000 A

22

22

100

RL

150

35

65

1600 A

100

150

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

RG

43

35

35

35

35

35

35

NW-N 2000 A

65

65

65

65

36

RJ

65

65

65

65

43

RK

65

65

65

65

51

NW-H 2000 A

36

100

NW-H 3000 A

100

100

100

RL

43

100

100

NW-L 1600 A

100

100

NW-L 3000 A

150

150

NW-LF 2000 A

22

22

20052006 Schneider Electric All Rights Reserved

25

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 7:

0100DB0501R3/06
04/2006

UL 480 Vac 400 A Selective Coordination (continued)


Key:

35

65

2000 A

100

150

35
65
2500
3000 A

100

150

Type

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully Rated

LA

LA-MC

LH

LH-MC

DG

DJ

PG

LC

LE

LX

PJ

PL

LI

LXI

30

30

35

35

35

65

35

65

65

65

65

100

200

200

35

35

35

35

35

NW-H 2000 A

36

100

100

NW-H 3000 A

100

100

100

NW-H 6000 A

100

100

100

RL

43

100

100

RG

35

NW-N 2000 A

65

65

65

65

36

RJ

65

65

65

65

43

RK

65

65

65

65

51

NW-L 2000 A

100

100

NW-L 3000 A

100

100

NW-L 6000 A

150

150

NW-LF 2000 A

22

22

100

RG

35

35

35

35

35

RJ

65

65

65

65

43

RK

65

65

65

65

51

NW-H 3000 A

100

100

NW-H 6000 A

100

100

100

RL

43

100

100

NW-L 3000 A

150

150

NW-L 6000 A

150

150

100

100

150

150

4000

100

NW-H 6000 A

6000 A

150

NW-L 6000 A

100

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

26

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 8:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 480 Vac 6001200 A Selective Coordination


Key:

Type
kAIR1

35

50

65
800 A

100

150

35

50

65
1000 A

100

150

35

50
1200 A

65

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Series Rated

DG

DJ

LC

LE

LX

LI

LXI

MG

MJ

PG

PJ

PL

RG

RJ

RL

35

65

65

65

65

200

200

35

65

35

65

100

35

65

100

MG

7.2

7.2

7.2

7.2

PG

35

35

35

35

RG

35

35

35

35

NT-N/H 1200 A

50

50

50

50

PK

50

50

50

50

MJ

7.2

7.2

7.2

7.2

NT-L1 1200 A

NW-N 2000 A

65

65

65

65

PJ

RJ

65

65

65

65

RK

65

65

65

65
9

NT-LF 1200 A

NW-H 2000 A

100

100

PL

RL

100

100

NW-L 1600 A

150

150

NW-LF 1600 A

150

150

PG

35

35

35

35

22

RG

35

35

35

35

35

NT

L1

NT
LF

50

65

100

100

36

36

36

36

35

NT-N/H 1200 A

50

50

50

50

36

PK

50

50

50

50

22

NT-L1 1200 A

NW-N 2000 A

65

65

65

65

36

36

PJ

RJ

65

65

65

65

43

43

RK

65

65

65

65

65

36

51

22

36

NT-L 1200 A

NT-LF 1200 A

NW-H 2000 A

36

100

100

PL

RL

100

100

NW-L 1600 A

150

150

150

150

43

PG

35

22

22

22

22

RG

35

51

51

51

51

51

NT-N/H 1200 A

50

50

50

50

36

PK

50

50

50

50

22

36

NT-L1 1200 A

NW-N 2000 A

65

65

65

65

36

36

PJ

RJ

65

65

65

65

43

43

RK

65

65

65

65

65

51

20052006 Schneider Electric All Rights Reserved

NT

36

NT-L 1200 A

NW-LF 1600 A

NT
N/H

36

27

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 8:

0100DB0501R3/06
04/2006

UL 480 Vac 6001200 A Selective Coordination (continued)


Key:

Type
kAIR1

100
1200 A

150

35

65

1600 A

100

150

35

65

2000 A
100

150

2000 A

150

35
65

25003000 A

DG

DJ

LC

LE

LX

LI

LXI

MG

MJ

PG

PJ

PL

RG

RJ

RL

35

65

65

65

65

200

200

35

65

35

65

100

35

65

100

NT

NT

NT

N/H

L1

NT
LF

50

65

100

100

NT-L 1200 A

NT-LF 1200 A

NW-H 2000 A

100

100

36

36

36

NW-H 3000 A

100

100

100

100

100

PL

RL

100

100

NW-L 1600 A

150

150

NW-L 3000A

150

150

NW-LF 1600 A

150

150

RG

35

43

35

35

35

NW-N 2000 A

65

65

65

65

35
36

35
36

RJ

65

65

65

65

43

43

RK

65

65

65

65

65

51

36

36

NW-H 2000 A

100

100

36

36

36

36

NW-H 3000 A

100

100

100

59

100

100

RL

100

100

43

NW-L 2000 A

150

150

NW-L 3000 A

150

150

NW-LF 1600 A

150

150

RG

35

35

35

NW-N 2000 A

35
65

65

65

65

35
36

35
36

RJ

65

65

65

65

43

43

RK

65

65

65

65

65

51

36

36

NW-H 2000 A

100

100

36

36

36

36

NW-H 3000 A

100

100

100

59

100

100

77

100

100

NW-H 6000 A

100

100

100

RL

100

100

43

NW-L 2000 A

150

150

NW-L 3000 A

150

150

NW-L 6000 A

150

150

NW-LF 2000 A

150

150

RG

35

35

35

RJ

35
65

65

65

65

35
43

35
43

RK

65

65

65

65

65

51

NW-H 3000 A

100

100

100

59

100

100

NW-H 6000 A

100

100

100

77

100

100

RL

100

100

43

NW-L 3000 A

150

150

NW-L 6000 A

150

150

100

NW-H 6000 A

100

100

150

NW-L 6000 A

150

150

100

150

40006000 A

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Series Rated

100

77

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

28

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 9:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 600 Vac 100250 A Selective Coordination


Key:

Type
kAIR1

14

18

100/150 A

EDB3 EGB3 EJB3 FA FH FJ3

HD HG

HJ

HL

FI

JD

JG

PG

JJ

PJ

LE

LX

JL

PL

KI

14kA

14

25

50

100

14

18

18

25

25

35

35

50

50

100

18

18

3.6

FA

0.9

HD

1.3

FH

18kA

25kA

1.3

1.3

25

HJ

1.3

1.3

1.3

35

NT-N 800/250 A
1.3

1.3

1.3

50

85
100
14
18

25
35
250 A

18

100

18

50

NW-N 800/250 A

50

NW-H 800/250 A

85

NW-L 800/250 A

100

NW-LF 800/250 A

100

JD

2.3

JG

2.4

PG
JJ

2.3
2.4

2.4 2.4

18

18

PJ

400 A
35
50
85
100

600 A

18

2.4

18

25

18
3

2.4

25

3
25

NT-N 800/250 A

35
2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

NT-H 800/250 A

50

NW-N 800/250 A

50
22

50

NW-H 800/250 A

85

NW-L 800/250 A

100

NW-LF 800/250 A

100

DG

3.2

3.2

3.2

3.2

MG

3.6

3.6

3.6

3.6

PG

18

DJ
25

18

35

PK
85

25

NT-H 800/250 A

JL
50

14

1.4

HG

HL

LH

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

3.2

18

18

18

18

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

MJ

3.6

3.6

3.6

3.6

3.6

PJ

25

25

25

25

35

35

NT-N 1200 A

35

NT-H 1200 A

50

50

50

50

PK

50

35
36

NW-H 2000 A

85

85

NW-L 1600 A

100

100

NW-LF 1600 A

100

DG

4.8

MG

5.4

PG

18

RG

18

20052006 Schneider Electric All Rights Reserved

18

100

4.8

4.8

4.8

5.4

5.4

5.4

5.4

5.4

18

18

18

18

18

18

18

18

18

18

18

29

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 9:

0100DB0501R3/06
04/2006

UL 600 Vac 100250 A Selective Coordination (continued)


Key:

Type
kAIR1

25

35

600 A

50

EDB3 EGB3 EJB3 FA FH FJ3

HD HG

HJ

HL

FI

JD

JG

PG

JJ

PJ

LE

LX

JL

PL

KI

14kA

14

25

50

100

14

18

18

25

25

35

35

50

50

100

5.4

18kA

25kA

14

18

25

18

DJ

4.8

4.8

4.8

4.8

MJ

5.4

25.0

5.4

5.4

5.4

PJ

25

25

25

25

35

35

NT-N 1200 A

35

NT-H 1200 A

50

50

36

NW-N 2000 A

50

50

36

50

50

PK

50

RL

50

43

65

85

NW-H 2000 A

85

85

NW-L 1600 A

100

100

18

NW-LF 1600 A

PG

25
35
800 A
50

65

100

18

RG

18

7.2

18

18

18

18

18

18

MJ
PJ

100

7.2

25

25

25

25

18
18
7.2
25

18

18

18

7.2

7.2

35

35

NT-N 1200 A

35

NT-H 1200 A

50

50

36

NW-N 2000 A

50

50

36

50

50

PK

50

RL

50

35

50

43

65

RK

65

85

NW-H 2000 A

85

85

NW-L 1600 A

100

100

100

18

25
35
1000 A
50

NW-LF 1600 A
PG

65

100
18

18

RG

18

PJ

25

RJ

18

100
18

18

18

18

25

25

25

25

25

25

25

18

18

18

18

25

25

35

35

NT-N 1200 A

35

NT-H 1200 A

50

50

36

NW-N 2000 A

50

50

36

50

50

PK

50

RL

30

50

RK

MG

1200 A

35

65

100

1000 A

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

50

35

50

43

65

RK

65

65

85

NW-H 2000 A

85

85

85

NW-H 3000 A

85

85

NW-L 2000 A

100

100

100

18

NW-L 3000 A

100

100

NW-LF 1600 A

100

100

PG
RG

18

18

18

18

18

18

18

18

18

18

18

18

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 9:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 600 Vac 100250 A Selective Coordination (continued)


Key:

Type
kAIR1

25
35

50

65
85

100

3000 A

FI

JD

JG

PG

JJ

PJ

LE

LX

JL

PL

KI

14kA

14

25

50

100

14

18

18

25

25

35

35

50

50

100

25

25

25

35

35

18kA

25kA

14

18

25

18

25

25

25

25

25

25
35

NT-H 1200 A

50

50

36

NW-N 2000 A

50

50

36

50

43

PK

50

65

50
50
65

65

NW-H 2000 A

85

85

NW-H 3000A

85

85

NW-L 2000 A

100

100

NW-L 3000 A

100

100

NW-LF 1600 A

100

100

18

18
25

18

18

25

25

18

18

25

25

NW-N 2000 A

50

50

RL

50

50

36

RK

51

65

NW-H 2000 A

65

85

NW-H 3000 A

85

85

NW-L 2000 A

85

100

NW-L 3000 A

100

100

NW-LF 1600 A

100

18

RG

25

RJ

50

35

RK

RG

18

18
25

100
18

18

25

25

25

18

18

25

25

NW-N 2000 A

50

50

36

RL

50

50

43

65

RK

51

65

85

NW-H 2000 A

65

85

85

NW-H 3000 A

85

85

NW-L 2000 A

85

100

NW-L 3000 A

100

100

NW-LF 2000 A

100

100

18

2500 A

HL

NT-N 1200 A

RJ

100

2000 A

HJ

RJ

25

85

2000 A

HD HG

PJ

18

50

1600 A

EDB3 EGB3 EJB3 FA FH FJ3

RL

1200 A

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

RG

18

100
18

25

25

18

25

25

RJ

50

RL

65

RK

51

85

NW-H 3000 A

65

65

100

NW-L 3000 A

100

100

85

NW-H 3000 A

85

85

100

NW-L 3000 A

100

100

50

25

18

25

20052006 Schneider Electric All Rights Reserved

25

18

43

43
51

31

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 9:

0100DB0501R3/06
04/2006

UL 600 Vac 100250 A Selective Coordination (continued)


Key:

40006000 A

Type
kAIR1

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

EDB3 EGB3 EJB3 FA FH FJ3

HD HG

HJ

HL

FI

JD

JG

PG

JJ

PJ

LE

LX

JL

PL

KI

14kA

14

25

50

100

14

18

18

25

25

35

35

50

50

100

18kA

25kA

14

18

25

18

85

NW-H 6000 A

85

85

100

NW-L 6000 A

100

100

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

Rated 600 Y / 347 Vac

32

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 10:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 600 Vac 400 A Selective Coordination


Key:

Type
kAIR1

PG

DG

LA

LH

DJ

PJ

LC

LE

LX

PL

LI

LXI

18

18

22

25

25

25

35

35

35

50

100

100

50

DG
18

25

600 A

35

50

4.8

MG

5.4

5.4

18

18

PG

18

18

18

18

18

18

18

18

5.4

RG

18

DJ

4.8

MJ

5.4

5.4

5.4

PJ

RJ

25

25

25

25

35

35

25

NT-N 1200 A

35

35

NT-H 1200 A

36

50

NW-N 2000 A

36

35

50

22

22

PK

22

RL

43

50

50

65

65

65

RK

85

NW-H 2000 A

85

85

NW-L 1600 A

100

100

22

22

50

100

65

18

PG
RG

35
800 A
50

65

65

18

7.2

7.2

7.2

7.2

18

18

18

18

18

18

18

18

7.2

7.2

MJ
25

65

NW-LF 1600 A
MG

7.2

7.2

PJ

RJ

25

25

7.2

25

NT-N 1200 A

25

25

25

35

35

35

36

NT-H 1200 A

36

50

NW-N 2000 A

36

50

50

22

22

PK
RL

43

50

50

65

65

65

RK

85

NW-H 2000 A

85

85

NW-L 1600 A

100

100

22

22

100

18

25
1000 A

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

35

50

65

65

65

NW-LF 1600 A
PG
RG

18

18

18

18

18

PJ

RJ

25

25

25

NT-N 1200 A

35

NT-H 1200 A

50

NW-N 2000 A

18

18

18

18

25

25

35

35

36
36

50

50

36

50

50

22

22

50

50

PK
RL

20052006 Schneider Electric All Rights Reserved

43

33

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 10:

0100DB0501R3/06
04/2006

UL 600 Vac 400 A Selective Coordination (continued)


Key:

Type
kAIR1
65
85

1000 A
100

18

25
35

1200 A

50

PG

DG

LA

LH

DJ

PJ

LC

LE

LX

PL

LI

LXI

18

18

22

25

25

25

35

35

35

50

100

100

65

65

65

RK
NW-H 2000 A

85

100

85

85

100

100

NW-L 3000 A

100

100

NW-LF 1600 A

22

22

PG
RG

18

18

18

18

18

PJ

RJ

25

25

25

NT-N 1200 A

35

18

18

18

18

25

25

35

35

1600 A

36

50

50

NW-N 2000 A

36

50

50

PK

2000 A

34

65

65

85

85

85

85
100

NW-L 3000 A

100

100

NW-LF 1600 A

22

22

18

18

18
25

25

25

18

18

25

25

NW-N 2000 A

36

50

50

RL

43

50

50

RK

65

65

65

NW-H 2000 A

65

65

85

85

NW-H 3000 A

85

85

NW-L 1600 A

100

100

NW-L 3000 A

100

100

NW-LF 1600 A

22

22

RJ

100

50

100

25

85

65

22

50

NW-L 1600 A

RG

65

65

22

NW-H 3000 A

18

50

65

NW-H 2000 A

RJ

100

43

RK

25

85

36

NT-H 1200 A

RG

65

65
85

NW-L 1600 A

18

50

65
85

NW-H 3000 A

RL
65

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

18

18

18
25

25

25

18

18

25

25

NW-N 2000 A

36

50

50

RL

43

50

50

RK
NW-H 2000 A

65

65

65

65

65

85

85

NW-H 3000 A

85

85

NW-L 2000 A

100

100

NW-L 3000 A

100

100

NW-LF 2000 A

22

22

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 10:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 600 Vac 400 A Selective Coordination (continued)


Key:

2500 A

3000 A
4000
6000 A

Type
kAIR1
18

RG

25

RJ

50

RL

65

RK

Series Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Fully Rated

PG

DG

LA

LH

DJ

PJ

LC

LE

LX

PL

LI

LXI

18

18

22

25

25

25

35

35

35

50

100

100

18

18

18

18

18

25

25

25

25

25

65

65

43
65

50

50

65

65

85

NW-H 3000 A

85

85

100

NW-L 3000 A

100

100

85

NW-H 3000 A

85

85

100

NW-L 3000 A

100

100

85

NW-H 6000 A

85

85

100

NW-L 6000 A

100

100

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

20052006 Schneider Electric All Rights Reserved

35

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 11:

0100DB0501R3/06
04/2006

UL 600 Vac 6001200 A Selective Coordination


Key:

18

Type

DG

DJ

LC

LE

LX

LI

LXI

MG

MJ

PG

PJ

PK

RG

RJ

RL

RK

18

25

35

35

35

100

100

18

25

18

25

50

18

25

50

65

MG

7.2

7.2

7.2

7.2

PG

18

18

18

18

18

RG

18

18

18

18

18

7.2

7.2

7.2

7.2

PJ

RJ

25

MJ
25

35
800 A
50

NT-N 1200 A

35

35

50

50

50

50

PK

22

22

RL

NW-H 2000 A

85

85

NW-L 1600 A

100

100

22

22

35

50

65

NW-LF 1600 A
18

18

18

18

18

RG

18

18

18

18

18

85

100

18

25
35

50

36

25

18

PJ

RJ

25

25

25

25

25

35

35

35

NT-N 1200 A

25
36

NT-H 1200 A

50

50

36

NW-N 2000 A

50

50

36

PK

22

22

50

50

43

65

65

65

NW-H 2000 A

85

85

NW-H 3000 A

85

85

NW-L 1600 A

100

100

NW-L 3000 A

100

100

NW-LF 1600 A

22

22

RK

65

65

65

PG

18

18

18

18

18

RG

18

18

18

18

18

36

36

36

36

18

PJ

RJ

25

25

25

25

25

35

35

35

NT-N 1200 A

50

36

PG

RL
65

1200 A

50
65

85

25

1000 A

50
65

RK

18

35

35

NW-N 2000 A

65

NT

NT-H 1200 A

65

NT

18

25

65

100

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully
Rated

9
25
36

NT-H 1200 A

50

50

36

NW-N 2000 A

50

50

36

PK

22

22

RL

50

50

43

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 11:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 600 Vac 6001200 A Selective Coordination (continued)


Key:

Type

DG

DJ

LC

LE

LX

LI

LXI

MG

MJ

PG

PJ

PK

RG

RJ

RL

RK

18

25

35

35

35

100

100

18

25

18

25

50

18

25

50

65

65

65

65

65

65

65

NW-H 2000 A

85

85

36

NW-H 3000 A

85

85

85

NW-L 1600 A

100

100

32

100

NW-L 3000 A

100

100

100

22

22

18

RG

25

RJ

65
85
1200 A

RK

NW-LF 1600 A

50

1600 A

65
85

100

2000 A

100

2500 A

3000 A
4000
6000 A

18

36
43

65

65

65

65

65

85

85

NW-H 3000 A

85

85

NW-L 1600 A

100

100

NW-L 3000 A

100

100

NW-LF 1600 A

22

22

18

18
9
50

36

RL

50

50

43

65

65

85

85

NW-H 3000 A

85

85

NW-L 2000 A

100

100

NW-L 3000 A

100

100

NW-LF 2000 A

22

22

18

RG

25

RJ

50

RL

65

RK

65

18
9

65

65

18

18

18

65

65

65

18

50

65

65

85

NW-H 3000 A

85

85

100

NW-L 3000 A

100

100

85

NW-H 3000 A

85

85

100

NW-L 3000 A

100

100

85

NW-H 6000 A

85

85

100

NW-L 6000 A

100

100

36

36

18
9

50

36

50

NW-H 2000 A

50

18
9

NW-N 2000 A

RK

35

50

NW-H 2000 A

NT

18

50

RK

NT

22
18

RL

RJ

85

18

50

25

65

18

50

RG

50

18

NW-N 2000 A

18

Series
Rated

Downstream Circuit Breaker - Type / kAIR


Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
kAIR1
Rating

Fully
Rated

9
43

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

20052006 Schneider Electric All Rights Reserved

37

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

0100DB0501R3/06
04/2006

APPENDIX B
Levels of Short Circuit Selective
Coordination for UL 489 LA/LH Mission
Critical Circuit Breakers

Table 12:

The following data for UL 489 Listed LA and LH Mission Critical circuit
breakers also applies to CSA C22.2 #5-02 Certified circuit breakers. All
data is at 60 Hz. The data does not apply to circuit breakers that are
Certified to ANCE NMX J-266, or IEC 60947-2 only, or at frequencies
other than 60 Hz.
Based on laboratory testing, Square D certifies the following levels of
selective coordination based upon the construction of the specific circuit
breakers referenced as of the date of publication of this document.

UL 208 Y / 120 Vac QO/B 1550 A Downstream Circuit Breakers


Key:

Upstream
Circuit Breaker

QO/B
15 A

20 A

30 A

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

200 A

182

182

162

182

182

102

72

225 A

kAIR1

42

Series Rated

Downstream Circuit Breaker - Type / Ampacity / Voltage Rating / Number of Poles / kAIR
Maximum Level of Selective Coordination Shown in kA

Type
Max.
Continuous
Current
Rating

Fully Rated

40 A

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

50 A

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

5.5

10 kAIR

LA-MC

18

18

18

18

18

16

11

102

18

6.52

82

10

10

7.5

10

10

7
9

182

182

182

182

182

182

182

182

142

10

10

10

10

10

400 A

182

182

182

182

182

182

182

182

182

10

10

10

10

10

10

200 A

6.52

5.5

250 A

225 A
250 A

18
65

LH-MC

16

18

18

10

10

182

182

182

182

182

162

112

182

82

10

10

7.5

10

10

142

10

10

10

10

10

182

182

10

10

10

10

10

10

18

182

400 A

18

18

18

182

18

182

182

18

182

18

18

182

18

182

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

The Panelboard in which the QO circuit breaker is located is fully rated 10 kA and series rated 18 kA.

Table 13:

UL 208 Y / 120 Vac QO/B 60100 A Downstream Circuit Breakers


Fully
Rated

Key:
Upstream
Circuit Breaker

Downstream Circuit Breaker - Type / Ampacity / Voltage Rating / Number of Poles / kAIR
Maximum Level of Selective Coordination Shown in kA
Type

QO/B
60 A

Max.
Continuous
Current Rating

70 A

80 A

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

200 A

52

62

52

52

62

225 A

kAIR

250 A

42

3 Pole
240 V

2 Pole
120/240 V

3 Pole
240 V

52

62

LA-MC

6.5

102

102

82

102

102

7.52

10

7.5

10

7.5

102

102

102

102

102

102

10

10

10

10

52

225 A

400 A

90100 A

2 Pole
120/240 V

200 A
65

3 Pole
240 V

10 kAIR

400 A

250 A

Series Rated

LH-MC

10

10

82

102

6.52

72

102

62

102

102

82

102

102

7.52

10

7.5

10

7.5

102

102

102

102

102

102

10

10

10

10

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

The Panelboard in which the QO circuit breaker is located is fully rated 10 kA and series rated 18 kA.

38

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 14:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

UL 208 Y / 120 Vac QO/B-VH 1550 A Downstream Circuit Breakers


Key:

Upstream
Circuit Breaker

Series Rated

Downstream Circuit Breaker - Type / Ampacity / Voltage Rating / Number of Poles / kAIR
Maximum Level of Selective Coordination Shown in kA

Type
Max.
Continuous
Current
Rating

Fully Rated

QO/B-VH
15 A

20 A

30 A

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

200 A

22

22

16

22

22

10

10

6.5

225 A

22

22

18

22

22

16

11

22

11

18

7.5

22

22

18

22

22

18

22

22

14

22

18

10

400 A

22

22

18

22

22

18

22

22

18

22

22

200 A

22

22

16

22

22

10

10

6.5

22

22

18

22

22

16

11

22

11

18

7.5

10

18

22

22

18

22

22

18

22

22

14

22

18

10

12

18

22

22

18

22

22

18

22

22

18

22

22

18

22

22

18

42

250 A

225 A

65

250 A

1 Pole
120 V

2 Pole
120/240 V

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

5.5

10

18

LA-MC

12

18

18

22

22

18

5.5

LH-MC

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Table 15:

UL 208 Y / 120 Vac QO/B-VH 60100 A Downstream Circuit Breakers


Fully
Rated

Key:
Upstream
Circuit Breaker

QO/B-VH
60 A

Max.
Continuous
Current Rating

Series Rated

Downstream Circuit Breaker - Type / Ampacity / Voltage Rating / Number of Poles / kAIR
Maximum Level of Selective Coordination Shown in kA

Type
70 A

80 A

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

200 A

225 A

13

6.5

10

250 A

42

3 Pole
240 V

2 Pole
120/240 V

90100 A

1 Pole
120 V
kAIR1

3 Pole
240 V

2 Pole
120/240 V

3 Pole
240 V

22 kAIR

LA-MC

10

13

10

11

7.5

11

7.5

10

7.5

400 A

22

22

18

22

22

18

22

18

22

18

200 A

225 A

13

6.5

10

10

13

10

11

7.5

11

7.5

10

7.5

22

22

18

22

22

18

22

18

22

18

250 A
400 A
1

3 Pole
240 V

22 kAIR

400 A
1

3 Pole
240 V

50 A

2 Pole
120/240 V

kAIR1

2 Pole
120/240 V

40 A

1 Pole
120 V

65

LH-MC

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

20052006 Schneider Electric All Rights Reserved

39

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 16:

0100DB0501R3/06
04/2006

UL 480 Y / 277 Vac ED Downstream Circuit Breakers


Key:

Upstream
Circuit Breaker
Max.
Continuous
Current
1
Rating kAIR

Fully Rated

Series Rated

Downstream Circuit Breaker - Type / Ampacity / kAIR


Maximum Level of Selective Coordination Shown in kA

Type

ED
15 A

20 A

30 A

40 A

50100A

18 kAIR

200 A

18

10

225 A

18

14

18

18

18

10

400 A

18

18

18

18

18

200 A

18

10

225 A

18

14

18

18

18

10

18

18

18

18

18

250 A

250 A

30

35

LA-MC

LH-MC

400 A
1

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Table 17:

UL 480 Y / 277 Vac EG Downstream Circuit Breakers


Key:

Upstream
Circuit Breaker
Max.
Continuous
Current
1
Rating kAIR

Fully Rated

Series Rated

Downstream Circuit Breaker - Type / Ampacity / kAIR


Maximum Level of Selective Coordination Shown in kA

Type

EG
15 A

20 A

30 A

40 A

50100A

35 kAIR

200 A

18

10

225 A

18

14

18

18

18

10

400 A

18

18

18

18

18

200 A

18

10

225 A

18

14

18

18

18

10

18

18

18

18

18

250 A

250 A
400 A
1

40

30

35

LA-MC

LH-MC

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

APPENDIX C
Levels of Short Circuit Selective
Coordination for ANSI Low Voltage
Power Circuit Breakers
Appendix C
Type

Volts

Downstream
Circuit Breaker
(frame size)

Table No.

Page No.

18

41

19

42

240
480

ANSI

800 A

600

20

43

240

21

44

22

45

480

1600 A

600

23

46

240

24

47

25

47

26

48

480

2000 A

600

Table 18:

ANSI 240 Vac 800 A Selective Coordination


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating
800 A

1600 A

Type

NT-N1

NW-N1

NW-H1

NW-H2

NW-H3

NW-L1

NW-L1F

42

42

65

85

100

200

200

200

200

NW-L1 2000 A

32

32

NW-L1F 2000 A

22

22

NW-L1 3200 A

200

200

200

200

NW-L1 3200 A

200

200

NW-L1 5000 A

200

200

kAIR1
42

NW-N1 1600 A

42

42

NW-N1 1600 A

42

65

NW-H1 3200 A

85

NW-H2 3200 A

100

200

65

85

2000 A

The data in the following tables for ANSI C37.13 and C37.50, UL 1066
Listed, low voltage power circuit breakers also applies to CSA
C22.2 #31-M89 Certified low voltage power circuit breakers. All data is at
60 Hz. The data does not apply to circuit breakers that are UL 489 Listed,
or Certified to IEC 60947-2 only, or at frequencies other than 60 Hz.
Fully rated pairs of circuit breakers where there is a reasonable expectation
of selective coordination are shown. Pairings of the same frame circuit
breakers are not shown, as such pairings would not be expected to
selectively coordinate.
Based on laboratory testing, Square D certifies the following levels of
selective coordination based upon the construction of the specific circuit
breakers referenced as of the date of publication of this document.

100

200

65
85

NW-H3 1600 A
NW-H3 3200 A

100

NW-L1 1600 A
NW-L1 3200 A
NW-H1 2000 A

65

NW-H1 3200 A

65

NW-H2 2000 A

85

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 2000 A

77

NW-H3 3200 A

77

NW-H3 5000 A

77

NW-L1 5000 A
65
85
3200 A

100

200

NW-H1 3200 A

65

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 3200 A

77

NW-H3 5000 A

77

20052006 Schneider Electric All Rights Reserved

41

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 18:

ANSI 240 Vac 800 A Selective Coordination (continued)


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

4000 A

5000 A

0100DB0501R3/06
04/2006

Type
kAIR1
85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

NT-N1

NW-N1

NW-H1

NW-H2

NW-H3

NW-L1

NW-L1F

42

42

65

85

100

200

200

200

200

200

200

85
77

85
77

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

Table 19:

ANSI 480 Vac 800 A Selective Coordination


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating
800 A

Type

NT-N1

NW-N1

NW-H1

NW-H2

NW-H3

NW-L1

NW-L1F

42

42

65

85

100

200

200

200

200

NW-L1 2000 A

32

32

NW-L1F 2000 A

22

22

NW-L1 3200 A

200

200

200

200

NW-L1 3200 A

200

200

NW-L1 5000 A

200

200

200

200

kAIR1
42

NW-N1 1600 A

42

NW-N1 1600 A

42

NW-H1 3200 A
1600 A

42

65

NW-H2 3200 A

85

NW-H3 3200 A

85

NW-L1 3200 A
65

85

2000 A

100

200

NW-H1 2000 A

65

NW-H1 3200 A

65

NW-H2 2000 A

85

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 2000 A

77

NW-H3 3200 A

77

NW-H3 5000 A

77

NW-L1 5000 A
65
85
3200 A

100

200

4000 A

42

NW-H1 3200 A

65

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 3200 A

77

NW-H3 5000 A

77

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85
77

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 19:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

ANSI 480 Vac 800 A Selective Coordination (continued)


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

5000 A

Type
kAIR1
85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

NT-N1

NW-N1

NW-H1

NW-H2

NW-H3

NW-L1

NW-L1F

42

42

65

85

100

200

200

200

200

85
77

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

Table 20:

ANSI 600 Vac 800 A Selective Coordination


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

1600 A

Type

NW-H1

NW-H2

NW-H3

NW-L1

NW-L1F

42

65

85

85

130

130

130

130

NW-L1 2000 A

35

35

NW-L1F 2000 A

24

24

NW-L1 3200 A

130

130

130

130

NW-L1 3200 A

130

130

NW-L1 5000 A

130

130

130

130

130

130

kAIR1
65

NW-H1 3200 A

85

NW-H2 3200 A

85

65

85

2000 A

NW-N1

85

130

65
85

NW-H3 3200 A

85

NW-L1 3200 A
NW-H1 2000 A

65

NW-H1 3200 A

65

NW-H2 2000 A

85

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 2000 A

85

NW-H3 3200 A

85

NW-H3 5000 A

85

NW-L1 5000 A
65
85
3200 A

85

130
85
4000 A

5000 A

NW-H1 3200 A

65

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 3200 A

85

NW-H3 5000 A

85

NW-H2 5000 A

85

NW-H3 5000 A

130

NW-L1 5000 A

85

NW-H2 5000 A

85

NW-H3 5000 A

130

NW-L1 5000 A

85
85

85
85

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

20052006 Schneider Electric All Rights Reserved

43

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 21:

ANSI 240 Vac 1600 A Selective Coordination


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Type

NW-N1

NW-H1

NW-H2

NW-H3

NW-L1

NW-L1F

42

65

85

100

200

200

NW-L1 2000 A

32

32

NW-L1F 2000 A

22

22

NW-L1 3200 A

200

200

200

200

NW-L1 3200 A

200

200

NW-L1 5000 A

200

200

200

200

200

200

kAIR1

65

85

2000 A

0100DB0501R3/06
04/2006

100

200

NW-H1 2000 A

65

NW-H1 3200 A

65

NW-H2 2000 A

85

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 2000 A

77

NW-H3 3200 A

77

NW-H3 5000 A

77

NW-L1 5000 A
65
85
3200 A

100

200

4000 A

5000 A

NW-H1 3200 A

65

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 3200 A

77

NW-H3 5000 A

77

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85
77

85
77

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

44

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 22:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

ANSI 480 Vac 1600 A Selective Coordination


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Type

NW-H1

NW-H2

NW-H3

NW-L1

NW-L1F

42

65

85

100

200

200

NW-L1 2000 A

32

32

NW-L1F 2000 A

22

22

NW-L1 3200 A

200

200

200

200

NW-L1 3200 A

200

200

NW-L1 5000 A

200

200

200

200

200

200

kAIR1

65

85

2000 A

NW-N1

100

200

NW-H1 2000 A

65

NW-H1 3200 A

65

NW-H2 2000 A

85

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 2000 A

77

NW-H3 3200 A

77

NW-H3 5000 A

77

NW-L1 5000 A
65
85
3200 A

100

200

4000 A

5000 A

NW-H1 3200 A

65

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 3200 A

77

NW-H3 5000 A

77

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85
77

85
77

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

20052006 Schneider Electric All Rights Reserved

45

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 23:

ANSI 600 Vac 1600 A Selective Coordination


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Type

NW-N1

NW-H1

NW-H2

NW-H3

NW-L1

NW-L1F

42

65

85

85

130

130

NW-L1 2000 A

32

32

NW-L1F 2000 A

22

22

NW-L1 3200 A

130

130

130

130

NW-L1 3200 A

130

130

NW-L1 5000 A

130

130

130

130

130

130

kAIR1

65

85

2000 A

0100DB0501R3/06
04/2006

85

130

NW-H1 2000 A

65

NW-H1 3200 A

65

NW-H2 2000 A

85

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 2000 A

85

NW-H3 3200 A

85

NW-H3 5000 A

85

NW-L1 5000 A
65
85
3200 A

85

130
85
4000 A

5000 A

NW-H1 3200 A

65

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 3200 A

85

NW-H3 5000 A

85

NW-H2 5000 A

85

NW-H3 5000 A

130

NW-L1 5000 A

85

NW-H2 5000 A

85

NW-H3 5000 A

130

NW-L1 5000 A

85
85

85
85

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

46

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Table 24:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

ANSI 240 Vac 2000 A Selective Coordination


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Type

85

100

200

4000 A

5000 A

NW-H2

NW-H3

NW-L1

NW-L1F

65

85

100

200

200

NW-L1 3200 A

200

200

NW-L1 5000 A

200

200

200

200

200

200

kAIR1
65

3200 A

NW-H1

NW-H1 3200 A

65

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 3200 A

77

NW-H3 5000 A

77

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85
77

85
77

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

Table 25:

ANSI 480 Vac 2000 A Selective Coordination


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Type

85

100

200

4000 A

5000 A

NW-H2

NW-H3

NW-L1

NW-L1F

65

85

100

200

200

NW-L1 3200 A

200

200

NW-L1 5000 A

200

200

200

200

200

200

kAIR1
65

3200 A

NW-H1

NW-H1 3200 A

65

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 3200 A

77

NW-H3 5000 A

77

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85

NW-H2 5000 A

100

NW-H3 5000 A

200

NW-L1 5000 A

85
77

85
77

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

20052006 Schneider Electric All Rights Reserved

47

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Table 26:

ANSI 600 Vac 2000 A Selective Coordination


Downstream Circuit Breaker - Type / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Maximum
Continuous
Current
Rating

Type

85

85

130
85
4000 A

5000 A

NW-H1

NW-H2

NW-H3

NW-L1

NW-L1F

65

85

85

130

130

NW-L1 3200 A

130

130

NW-L1 5000 A

130

130

130

130

130

130

kAIR1
65

3200 A

0100DB0501R3/06
04/2006

NW-H1 3200 A

65

NW-H2 3200 A

85

NW-H2 5000 A

85

NW-H3 3200 A

85

NW-H3 5000 A

85

NW-H2 5000 A

85

NW-H3 5000 A

130

NW-L1 5000 A

85

NW-H2 5000 A

85

NW-H3 5000 A

130

NW-L1 5000 A

85
85

85
85

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

48

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

APPENDIX D
Glossary

20052006 Schneider Electric All Rights Reserved

ampacityThe RMS current, in amperes, that a conductor or circuit


breaker can carry continuously under the conditions of use without
exceeding its temperature rating.
ampere ratingSee continuous current rating.
ANCE(National Association of Standardization and Certification for the
Electrical Sector) The standards and certification agency accredited by the
Mexican government.
ANSIAmerican National Standards Institute.
Canadian Standards Association(CSA) Canadian product safety
testing and certification organization.
circuit breakerA device designed to open and close a circuit by nonautomatic means and to open the circuit automatically on an overcurrent
without damage to itself when properly applied within its rating.
circuit breaker frame(1) The circuit breaker housing which contains the
current carrying components, the current sensing components, and the
tripping and operating mechanism. (2) That portion of an interchangeable
trip molded case circuit breaker remaining when the interchangeable trip
unit is removed.
close and latch ratingThe maximum level of current a circuit breaker can
be closed on and still have the mechanism latch in the fully closed position.
continuous current ratingThe designated RMS alternating or direct
current in amperes which a device or assembly will carry continuously in
free air without tripping or exceeding temperature limits.
CSASee Canadian Standards Association.
frame sizeThe largest ampere rating available in a group of circuit
breakers of similar physical configuration.
ground faultAn unintentional current path, through a grounded
conductor, enclosure, raceway or the earth, back to the source.
instantaneous selective overrideA fixed, non-adjustable, instantaneous
trip function set just below a circuit breakers withstand capability.
instantaneous tripA qualifying term indicating that no delay is purposely
introduced in the tripping action of the circuit breaker during short-circuit
conditions.
insulated case circuit breaker(ICCB) UL Standard 489 Listed non-fused
molded case circuit breakers which utilize a two-step stored energy closing
mechanism, electronic trip system and optional draw-out construction.
interrupting ratingThe highest current at rated voltage that the circuit
breaker is rated to interrupt in RMS symmetrical amperes. When the circuit
breaker can be used at more than one voltage, the interrupting rating will be
shown on the circuit breaker for each voltage level. The interrupting rating of
a circuit breaker must be equal to or greater than the available short-circuit
current at the point at which the circuit breaker is applied to the system.
kAIRAmpere Interrupting Rating in thousands of amperes. See
interrupting rating.
let-throughThe current which passes through an overcurrent protective
device during an interruption.
making current releaseA fixed, non-adjustable, instantaneous trip
function set just below a circuit breakers close and latch rating.
molded case circuit breaker(MCCB) A circuit breaker which is
assembled as an integral unit in a supportive and enclosed housing of

49

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

0100DB0501R3/06
04/2006

insulating material, generally 20 to 3000 A in size and used in systems up to


600 Vac and 500 Vdc.
NMX(Norma Mexicana X) Mexican safety standards. Note to Tech Pubs:
This is different than the definition in your glossary, which is incorrect.
selective coordinationLocalization of an overcurrent condition to restrict
an outage to the circuit or equipment affected, accomplished by the choice
of overcurrent protective devices and their ratings or settings. (NEC 100 Definitions)
trip curveA graphical representation of the response of a circuit breaker
to current over a period of time.
ULSee Underwriters Laboratories Inc.
Underwriters Laboratories Inc.(UL) An independent, not-for-profit
standards development, product safety testing and certification
organization.

50

20052006 Schneider Electric All Rights Reserved

0100DB0501R3/06
04/2006

20052006 Schneider Electric All Rights Reserved

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

51

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Schneider Electric USA


3700 6th Street S.W.
Cedar Rapids, Iowa 52404 USA
1-888-SquareD (1-888-778-2733)
www.us.SquareD.com

0100DB0501R3/06
04/2006