As of ACS790 V9.00
OCI700.1
Service tool
Service case with software and service interface
The service tool consists of one service case with the ACS790 software included
on a CD ROM as well as the OCI700 service interface and 3 connecting cables
specific to the devices.
The software and service interface allow for commissioning and servicing KNX
and LPB/BSB devices.
Use
Commissioning and service of:
KNX devices
SyncoTM 200 devices
SyncoTM 700 control and room devices
SyncoTM living central apartment units
RXB../RXL.. room controllers
RDF../RDU../RDG.. room thermostats
VAV compact controllers GDB../GLB..
KNX central communications units OZW7..
LPB/BSB devices
Sigmagyr/Albatros control and room units
LPB/BSB central communication units OZW6../OCI6..
CE1N5655en
2013-11-04
Building Technologies
Functions
ACS790 software
The ACS790 software commissions and services KNX and LPB/BSB devices and
plants via the "ACS tool" program together with the OCI700 service interface.
User view (user level)
Administration
Parameter set
Commissioning
protocol
Trend
Online trend
Plant operation
Popcard
Plant diagram
Note
The CD ROM in the service case and the CD ROM "Engineering and service software
ACS790" are the same. (ACS790 is described in data sheet N5649).
The OCI700 service interface assumes signal conversion between the USB interface
connected to the PC/laptop and the service tool interface for the given device.
For additional details, refer to "Technical design" and "Technical data" below.
2/6
Siemens
Building Technologies
CE1N5655en
2013-11-04
Delivery
Product number
Service tool
OCI700.1
Documentation
Document title
Technical design
Basic design
The OCI700 service interface consists of one plastic housing with 2 LEDs and 3
interface sockets.
LED indication
The 2 LEDs, labeled "USB" and "BUS", indicate the operational state.
LED USB
LED lit
LED flashes
LED BUS
LED lit
LED flashes
Interfaces
Note
3/6
Siemens
Building Technologies
CE1N5655en
2013-11-04
Communication
connections
Select connection
General notes
Mounting
Power supply
Parameterization
ACS790 software
Note that not all ACS790 applications are supported on the OCI700 service interface.
For example, no alarm messages can be received with the ACS alarm program via
the OCI700 service interface.
4/6
Siemens
Building Technologies
CE1N5655en
2013-11-04
Requirements for
PC/laptop with ACS790
Minimum requirements
Processor
1 GHz
RAM
1 GB
Hard disk
2 GB for installation.
Additional space required for plant data
Monitor
Interfaces
Operating system
Drive
CD-ROM or DVD
Technical data
Power supply
KNX interface
Connection
Service cable length
Baud rate
Bus load number E
LPB/BSB interface
Standard
Connection
Service cable length
Baud rate
Bus load number E
Batibus-compatible
2-wire connection, non-interchangeable
3m
4800 baud
Dynamic/adaptive
USB interface
Standard
Service cable length
Device class
Baud rate
Connection cable
Plug on PC/Laptop
Plug on OCI700
USB V1.1
0.6 m (max. 5 m)
HID (human interface device)
Max. 12 Mbps (full speed)
Standards
conformity as per
EMC guideline
Immunity and emissions
Low-voltage directive
Electrical safety (HBES)
RCM mark conformity (emissions)
Degree of protection
USB type A
USB type B
2004/108/EC
EN 61000-6-2, EN 61000-6-3
EN 50491-5-3
2006/95/EC
EN 50491-3
AS/NZS 61000-6-3
IP20
5/6
Siemens
Building Technologies
CE1N5655en
2013-11-04
Permissible
environmental conditions
Transportation
Temperature
2570 C
Humidity
Storage
Temperature
Humidity
Weight
Operation
Temperature
Humidity
050 C
<85 % r.h. (non-condensing)
1.2 kg
Connections
The following pin assignments of the KNX and LPB/BSB plugs on the OCI700 service
interface apply to assembly of own connection cables:
1234567 8
Pin assignment
LPB/BSB, RJ12
1 2 3 4 5 6
5655Z03
5655Z02
Pin assignment
KNX, RJ45
1
2
3
4
5
6
7
8
CE+, Konnex
CE, Konnex
Unused
Unused
Voltage 16 V
Transmission line to RLU2..
Receiving line: RLU2.. or data line PPS or Ident'pin
Ground
1
2
3
4
5
6
Unused
Unused
DB, LPB/BSB
MB, LPB/BSB
Ident'pin
Unused
32,4
Dimensions
5655M01
69,9
125,5
Dimensions in mm
Subject to change