TANGRA

HEATING VENTILATION AIR-CONDITIONING

Heat recovery units

Save Energy
Reduce Your Expenses
Take Care of the Environment

Peoplewhostayindoorsmostofthetimeneedfreshair.Thisaffectstheirhealth,efficiencyandmuchmore.
Exhaustingairoftechnologicalsystems(hot,humidorharmful)hastobecompensated.
Theinstallationssupplyingfreshairarebigenergyconsumersforheatinginwinterandcoolinginsummer.Thecostofthis
energyforventilationiscommensuratewiththatforheatingbutstillnotadequatelyassessed.
Nowadays there systems which can reduce these expenses with 40% up to 80%. The correct choice is to be subjected to
accurateeconomicanalysesoftheinitialinvestmentaswellastheexpensesoftheirexploitation.
Thebasicfactorstobeconsideredare:
Dailyoperation(hourperday);
Ambientconditions;
Energycosts;
Initialinvestments;
Maintenanceexpenses.
Lifetimeoftheinstallation;
Q ,kWh

ENERGY CONSUMPTION PER YEAR, kWh

10000
9000
8000
AHU - A

7000
6000
5000

System without
recuperation

4000
3000

AHU - A

E=0%

2000
1000
0
-15

Q ,kWh

-10

-5

10
text ,

ENERGY CONSUMPTION PER YEAR, kWh

10000
9000
AHU - A

8000
7000

AHU - B

6000
5000

System with plate


heat exchanger

4000
3000

REC

AHU - B

E=45 55%

2000
1000
0
-15

Q ,kWh
10000

-10

-5

10
text ,

ENERGY CONSUMPTION PER YEAR, kWh

9000
AHU - A

8000
7000

AHU - C

6000
5000
4000

AHU - C

REC

REC

System with high


efficiency plate
heat exchanger

3000

E=60 70%

2000
1000
0
-15

Q ,kWh
10000

-10

-5

10
text ,

ENERGY CONSUMPTION PER YEAR, kWh

9000
AHU - A

8000
7000

AHU - D

6000
5000

System with rotary


heat exchanger

4000
3000

AHU - D

E=65 75%

2000
1000
0
-15

Q ,kWh
10000

-10

-5

10
text ,

ENERGY CONSUMPTION PER YEAR, kWh

9000
AHU - A

8000
7000

AHU - E

6000
5000
4000

AHU - E

REC

System with plate


heat exchanger and
heat pump

3000

E=75 85%

2000
1000
0
-15

-10

-5

10
text ,

The initial investments for an energy saving system is higher, but the operation expenses are
significantlylower

Amount,

Thedatashownarenotuniversal.These
parametersarevalidforthefollowing
conditions:

Bulgaria,Sofia;
Indoortemperature22oC;
Airvolume3000m3/h;
Dailyoperation10h.of24h.
Installationlifetime10years;
Energyprice0.1Euro/kWh;
8%annualexpensesformaintenance;
Growthoftheenergyprice12%peryear;
TheinitialexpensesforHVACsystemare
tentative;
SystemtypeDallowsmoistexchange;
SystemtypeEallowscoolingduringthe
summertime.

Anual expences with accumulation,

50 000

45 000

40 000

35 000

30 000

25 000

20 000

15 000

10 000

5 000

4
5
Years

10

theseareyourlostmoney

Thereisapreliminarytrendforgrowingofenergypriceforthelast10years.

US $/Barrel

Price trend of oil

100
90
80
70
60
50
40
30
20
10
0
2000

2001

2002

2003

2004

2005

2006

2007

2008

2009

2010

Thereisnodoubtaboutthefollowing:
Thepriceoftheenergywillnotgodown!
Thequalityofthemicroclimateissomethingwithwhichwecannotmakea
compromise!
Theprotectionoftheenvironmentisourobligationtothefuturegeneration!

Heatrecoveryunitsapplication
Ventilationandairconditioningsystemsupplyingfreshair:
Officeandresidentialbuildings;
Hotels,restaurants,coffeebars,nightclubs;
Sporthall,gym,swimmingpool;
Hospitals,schools,laboratories;
Cinema,theatersconcerthalls;
Foodindustrybakery;
Technologicalventilation,workshops.

TangraHeatrecoveryunits
StandardrangeEVBAL

MiddlerangelowpressureEVBCBM

MiddlerangehighpressureEVBCBP

HighefficiencyrangeEVBTOP/PLUS

RotaryheatexchangersrangeEVBROT

Tehnical characteristics - quick selection


Model

Max.
capacity,
[m3/h]

Fan
speed
[r.p.m]

Fan type

Motor
Max.
Voltage Efficiency Heating/cooling
power, current,
coil
[kW]
[A]
[V]
[%]

Q80/60,C
Heating
[kW]

Q7/12,C
Cooling
[kW]

Heating
Cooling
Weight
Inlet Temp.
Inlet Temp.
Outlet Temp.
Outlet Temp.
[t,C]
[t,C]
[t,C]
[t,C]
[kg]
After
After
After
After
Fresh air Exchanger Heating coil Fresh air Exchanger Cooling coil

HEAT RECOVERY UNITS - EVB AL


EVB PP-04-

500

CBM/2 - 133/190

2450

0.185

2 x 0,79

230

50

400/200 - 2R

5.1

1.7

38.3

19

40

EVB AL-06

700

CBM/2 - 146/180

2400

0.22

2 x 1,01

230

49

400/200 - 2R

1.8

34.5

20

60

EVB AL-10

1000

CBM/4 - 180/180

1350

0.15

2 x 1,5

230

48

400/400 - 2R

10.5

3.5

18.5

100

EVB AL-20

2200

CBM/4 - 240/240

1350

0.37

2 x 3,8

230

48

500/500 - 2R

18

5.5

35

20

140

EVB AL-30

3000

CBM/4 - 270/200

1300

0.37

2x5

230

47

600/600 - 2R

26.4

8.3

36

19.5

170

EVB AL-35

3500

CBM/4 - 270/270

1400

0.55

2 x 5,9

230

46

600/600 - 2R

29.5

9.2

34

20.1

210

32

20.3

400

20.5

480

30

20.8

550

34.1

16.9

300

17.2

400

32.4

16.8

550

33.1

20.8

220

20

280

34.2

20.5

350

37.3

19.9

200

19.5

250

36.4

20

280

36

16.1

550

17

750

17

1050

-10

4.5

40.5

33

27.5

HEAT RECOVERY UNITS [MIDDLE RANGE - LOW RPESURE] - EVB AL - CBM


EVB AL-40-CBM

4000

CBM - 320/320

900

2 x 1,1 2 x 7,0/4 230/400

52.5

800/800 - 2R

45

11.4

EVB AL-60-CBM

6000

CBM - 380/380T

940

2 x 2,2 2 x 10,4/6 230/400

52.5

800/800 - 2R

63.5

15.5

EVB AL-80-CBM

8000

CBM - 380/380T

940

2 x 2,2 2 x10,4/6 230/400

52.5

800/800 - 2R

67.7

16.7

-10

31.5

33

27

HEAT RECOVERY UNITS [MIDDLE RANGE - HIGH RPESURE] - EVB AL - CBP


EVB AL-41-CBP

4000

CBP - 10/10

14001700 2 x 1,5

2 x 2,8

380

50

800/500 - 2R/4R

34.5

13.7

EVB AL-61-CBP

6000

CBP - 12/12

10001400 2 x 3,0

2 x 6,8

380

52

800/800 - 2R/4R

57.5

23.5

EVB AL-81-CBP

8000

CBP - 15/15

8001200 2 x 4,0

2 x 8,9

380

52

1000/800 - 2R/4R

74

31

-10

33.3

33

27

HEAT RECOVERY UNITS WITH INCREASED EFFICIENCY - EVB TOP


EVB-20-TOP

2000

CBM/4 - 240/240

1350

0.37

2 x 3,8

230

69

500/300 - 2R

15

3.8

EVB-30-TOP

2700

CBM/4 - 270/200

1300

0.37

2x5

230

69

700/400 - 2R

22.5

EVB-35-TOP

3300

CBM/4 - 270/270

1400

0.55

2 x 5,9

230

70

700/400 - 2R

24.5

6.5

-10

36.1

33

25

HEAT RECOVERY UNITS WITH INCREASED EFFICIENCY - EVB PLUS


EVB-20 PLUS

2000

CBM/4 - 240/240

1350

0.37

2 x 3,8

230

68

500/500 - 2R

16.7

4.3

EVB-30 PLUS

2700

CBM/4 - 270/200

1300

0.37

2x5

230

68

600/600 - 2R

24.1

6.4

EVB-35PLUS

3300

CBM/4 - 270/270

1400

0.55

2 x 5,9

230

69

600/600 - 2R

26.8

-10

38.4

33

25

HEAT RECOVERY UNITS WITH ROTARY REGENERATIVE HEAT EXCHANGER - EVB ROT
EVB ROT 42

4000

CBP - 10/10

14001600 2x2,2

2x5

380

72

1000/500 - 2R/4R

38

17.5

EVB ROT 62

6000

CBP - 15/15

10001200

2x9

380

75

1000/600 - 2R/4R

52

24

EVB ROT 82

8000

BDB - 400

2 x 12

380

75

1200/600 - 2R/4R

67

32

2x4

16002000 2x5,5

-10

10.5

33

33

33

Weight - Weight of standart type Heat Recovery Units


We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

24.5

05 01.01

HEAT RECOVERY UNITS


EVB-AL
Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.
Operation temperatures from -20oC up to 50oC.
Designed to work with clean air in nonaggressive and non-sparkling environment.
CONSTRUCTION

Supporting construction, made by anodized aluminum profiles.


Thermo and sound insulated panels, powder coated RAL7035;
o Internal insulation Firex 10 mm, fire resistance class: 0-BS 476 Part 6; class 1 BS 476 Part7;
o Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0;
Cross flow aluminum plate heat exchanger with efficiency up to 55%;
Double inlet direct drive centrifugal fans 230V, 50Hz, IP 20 (higher protection by request);
Air filters class G4 EN 779:2002;
Rectangular or round duct connector;
Drain tray with connection;
Configuration allows easily modifying position of the filters, fans and duct connectors;
Service doors from the bottom and from the side;
By-pass with multiple leaf damper by request;
Heating/ cooling coil by request;
Hanging support or basic steps by request;
Roof panels for outdoor installation by request.

The construction allows horizontal () or vertical (V) installation.


www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 01.02
Heat recovery units

EVB-L
HEAT RECOVERY UNITS EVB AL

INSTALLATION
Horizontal installation H

Type size

Max.
capacity
3
m /h

H max

VB PP-04-H
VB AL-06-H
VB AL-10-H
VB AL-20-H
VB AL-30-H
VB AL-35-H

500
700
1000
2200
3000
3500

800
1000
1000
1060
1200
1200

280
350
420
480
580
680

800
1000
1300
1500
1600
1600

320
390
460
520
620
720

215
225
235
300
265
335

150
180
210
260
290
290

200
250
280
315
355
355

215
225
300
300
400
400

150
180
250
300
300
400

Dimensions, mm

Vertical installation - V

Max.
capacity
m3/h

B max

500

280

800

800

320

150

150

200

215

150

45

VB AL-06-V

700

350 1000 1000

390

180

225

250

225

180

50

VB AL-10-V
VB AL-20-V
VB AL-30V
VB AL-35-V

1000
2200
3000
3500

420
510
580
680

460
550
620
620

210
260
290
290

235
300
265
335

280
315
355
355

250
300
300
400

300
300
400
400

85
105
90
140

Type size
VB PP-04-V

Dimensions, mm

1000
1060
1200
1200

1300
1500
1600
1600

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 01.03
Heat recovery units

EVB-L

HEATRECOVERYUNITSEVBALH(BYPASSBS)

By-pass with internal multiple leaf damper;

Manual control - by request;

Belimo ON-OFF actuator standard execution

BY PASS BS
Dimensions, mm
Type size

H max

VB AL-06-BS

1050

450

1200

520

225

180

225

180

250

VB AL-10-BS

1050

520

1300

590

235

210

300

250

280

VB AL-20-BS

1060

650

1500

720

300

260

300

300

315

VB AL-30-BS

1200

750

1600

820

265

290

400

300

355

VB AL-35-BS

1300

850

1600

920

335

290

400

400

355

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 01.04
Heat recovery units

EVB-L

HEATRECOVERYUNITSEVBALH(HEAT+BYPASSHBS)

By-pass with internal multiple leaf damper;

Manual control - by request;

Belimo ON-OFF actuator standard execution

Two rows water coil Cu/Al;

Four rows water coil (cooling) - by request.

HEAT + BY PASS - HBS


Dimensions, mm

Type size

H max

VB AL-06-HBS

1050

450

1600

520

225

180

225

180

250

VB AL-10-HBS

1050

520

1600

590

235

210

300

250

280

VB AL-20-HBS

1200

650

1900

720

300

260

300

300

315

VB AL-30-HBS

1300

750

1900

820

265

290

400

300

355

VB AL-35-HBS

1300

850

1900

920

335

290

400

400

355

1
1
1

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 01.05
Heat recovery units

EVB-L

Typesize

Fan

Nominalpower,
W

Ratedcurrent
A

EVBPP04

CBM/2133/190

2x185

0.8

EVB AL - 06

Type size
BV AL- 06

Fan
BM/2-146/180

Nominal power
W

Rated current
A

2220

1,01

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 01.06
Heat recovery units

Type size

EVB-L

Fan

Nominal power
W

Rated current
A

BV AL-10

BM/4-180/180

2147

1,5

BV AL-10/3V

BM/4-180/180 V

2147

1,33

Type size

Fan

Nominal power
W

Rated current
A

BV AL- 20

BM/4-240/240

2370

4,2

BV AL- 20/3V

BM/4-240/240 3V

2370

3,8

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 01.07
Heat recovery units

EVB-L

Type size

Fan

Nominal power
W

Rated current
A

BV AL-30

BM/4-270/200

2370

4,0

BV AL-30/3V

BM/4-270/20 3V

2370

3,0

EVBAL 35
600

E=50%

500

H,Pa

400

E=48%

300

E=46%

200

E=46%
100

1
1 +600/6002R

0
0

500

1000

1500

2000

2500

3000

3500

V,m3/h

Type size
BV AL- 35

Fan
BM/4-270/270

Nominal power
W

Rated current
A

2550

6,2

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 01.08
Heat recovery units

EVB-L

STANDARD CONFIGURATIONS
Horizontal installation
A

Vertical installation
C

Units are produced in configuration A and C. Modification from A to B or from C to D has to be ordered
to the factory and also is possible at the building site.
ACCESSOARIES
External high efficiency filter F7, Pmax =80Pa;
Sound attenuators;
External electric heater;
Roof for outdoor installation;
Flexible duct connectors;
3-way valve for water coil;
Freeze protection;
Pressure switch;.
3-speed switch;
Hanging supports;
Basic steps;
Frame for outdoor installation.
ORDER DESIGNATION
EVB AL 30 3V HBS
Heating coil and by-pass
3-speed fan
Typesize
Heat recovery unit
www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 02.01

HEAT RECOVERY UNITS


MIDDLE RANGE LOW PRESURE
VB AL- M
Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.
Operation temperatures from -20oC up to 50oC.
Designed to work with clean air in nonaggressive and non-sparkling environment.
CONSTRUCTION

Supporting construction, made by anodized aluminum profiles.


Thermo and sound insulated panels, powder coated RAL7035;
o Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0;
Cross flow aluminum plate heat exchanger with efficiency up to 55%;
Double inlet direct drive centrifugal fans 380V, 50Hz;
Air filters class G4 EN 779:2002;
Rectangular duct connector;
Drain tray with connection;
Service doors from the bottom and from the side;
By-pass with multiple leaf damper by request;
Heating/ cooling coil by request;
Support frame or basic steps by request;
Roof panels for outdoor installation by request.

The construction allows horizontal () or vertical (V) installation.

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 02.02
Heat recovery units

EVB-L

INSTALLATION
OVERALL AND JOINED DIMENTIONS VB AL M

Horizontal installation - H

Vertical installation - V

Typesize
VB-AL- 40 CBM
VB-AL- 60 CBM
VB-AL- 80 CBM

Fan
CBM 320/320
CBM 380/380
CBM 380/380

Recuperative
exchanger

Dimensions, mm
H

RECAL-1200/9-070 700 2550 400


RECAL-1200/9-080 800 2650 475
RECAL-1200/9-110 1000 2650 475

340
400
400

600
700
700

500
600
700

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 02.03
Heat recovery units

EVB-L

OVERALL AND JOINED DIMENTIONS VB AL M HBS (HEAT+BY PASS HBS)

Horizontal installation - H

Vertical installation - V

Typesize
VBAL- 40 CBM HBS
VBAL- 60 CBM HBS
VBAL- 80 CBM HBS

Fan
CBM 320/320
CBM 380/380
CBM 380/380

Recuperative
exchanger

Dimensions, mm
H

RECAL-1200/9-070 1000 3000 400


RECAL-1200/9-080 1100 3100 475
RECAL-1200/9-110 1300 3100 475

340
400
400

600
700
700

500
600
700

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 02.04
Heat recovery units

EVB-L

AERODYNAMIC CHARACTERISTICS
EVB AL40
350
E=55%
300
E=54%

ExternalpressurePa

250

200
E=53%
150
E=52%
100

50

0
2500

3000

3500

4000

4500

5000

5500

6000

Airvolumem3/h

Type size

Nominal power
W
21100

Fan

BV AL- 40 CBM

BM-320/320

Rated current
A
7,2

EVB - Al - 60
450
E=56%

400

E=55%

External pressure Pa

350

E=54%

300
250

E=53%

200
E=52%
150
100
50
0
3500

4000

4500

5000

5500

6000

6500

7000

7500

8000

8500

9000

Air volume m3/h

Type size

Fan

BV AL- 60 CBM BM-380/380

Nominal power
W
22200

Rated current
A
13,8

----- external External pressure ; Pa


- - - external External pressure (with water heating coil 800/800 2R 80/60 0C)

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 02.05
Heat recovery units

EVB-L

EVB - Al - 80
400
350

E=55%

E=54%

External pressure Pa

300

E=53%

250
E=52%
200
150
E=51%
100
50
0
5000

5500

6000

6500

7000

7500

8000

8500

9000

9500

10000

10500

11000

Air volume m3/h

Type size

Fan

BV AL- 80 CBM BM-380/380

Nominal power
W
22200

Rated current
A
13,8

---- external External pressure ; Pa


- - - external External pressure (with water heating coil 800/800 2R 80/60 0C)

ORDER DESIGNATION
Heat recovery unit EVB AL - 40 - CBM ST/HBS H/V
EVB AL - 40 - CBM

HBS - H
Horizontal installation
HEAT+BY PASS HBS

ypesize
Heat recovery unit AL

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 03.01

HEAT RECOVERY UNITS


MIDDLE RANGE HIGH PRESSURE
VB AL- P
Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.
Operation temperatures from -20oC up to 50oC.
Designed to work with clean air in nonaggressive and non-sparkling environment.
CONSTRUCTION

Supporting construction, made by anodized aluminum profiles.


Thermo and sound insulated panels, powder coated RAL7035;
o Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0;
Cross flow aluminum plate heat exchanger with efficiency up to 55%;
Double inlet belt driven centrifugal fans 380V, 50Hz;
Air filters class G4 EN 779:2002;
Rectangular duct connector;
Drain tray with connection;
Service doors from the side;
By-pass with multiple leaf damper;
External box with heating/ cooling coil by request;
Support frame or basic steps by request;
Roof panels for outdoor installation by request.

05 03.02
Heat recovery units

EVB-L

INSTALLATION
OVERALL AND JOINED DIMENSIONS VB AL P

Standard Version for vertical mounting


Recuperative
exchanger

Typesize

Fan

VB AL- 41 CBP

CBP 10/10

Dimensions, mm
H

RECAL-600/5-040 1150

1350

1900

335

290

600

400

VB AL- 61 CBP

CBP 12/12 RECAL-1200/9-060 850

2000

2500

400

340

500

600

VB AL- 81 CBP

CBP 15/15 RECAL-1200/9-080 1050

2000

3000

470

400

600

600

Typesize

Fan

Heating/ cooling
coil

Dimensions, mm
B

H1

L1,m L1

VB AL- 41 CBP CBP 10/10

800/500 2R

1150 1350 1600 1900 1300 1500 335 290 600 400

VB AL- 61 CBP CBP 12/12

800/800 2R/ 4R

1050 2000 2400 2500 1400 1600 400 340 500 600

VB AL- 81 CBP CBP 15/15

1000/800 2R/ 4R 1250 2000 2700 3000 1600 1800 470 400 600 600

05 03.03
Heat recovery units

EVB-L

AERODYNAMIC CHARACTERISTICS free pressure

1. EVB AL- 41 CBP

Note:

the curve is valid for EVB-CBP with incorporated water heating coil COT 800/500 2R

2. EVB AL- 61 CBP

Note:

the curve is valid for EVB-CBP with incorporated water heating coil COT 800/800 2R

05 03.04
Heat recovery units

EVB-L

2. EVB AL- 81 CBP

Note:

the curve is valid for EVB-CBP with incorporated water heating coil COT 1000/800 2R

ORDER DESIGNATION
Heat recovery unit EVB AL - 41 - CBP
EVB AL - 41/1600 - CBP

ype size/ Rpm


Heat recovery unit AL

05 04.01

HEAT RECOVERY UNITS


HIGH EFFICIENCY RANGE
VB TOP/ PLUS
Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.
Operation temperatures from -20oC up to 50oC.
Designed to work with clean in nonaggressive and non-sparkling environment.
CONSTRUCTION

Supporting construction, made by anodized aluminum profiles.


Thermo and sound insulated panels, powder coated RAL7035;
o Internal insulation Firex 10 mm, fire resistance class: 0-BS 476 Part 6; class 1 BS 476 Part7;
o Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0;
Counter flow aluminum plate heat exchanger with efficiency up to 70%;
Double inlet direct drive centrifugal fans 230V, 50Hz, IP 20 (higher protection by request);
Air filters class G4 EN 779:2002;
Rectangular or round duct connector;
Drain tray with connection;
Fixed configuration:
o type TOP for vertical installation with connections on the top side only;
o type PLUS for horizontal installation. Panels with fans and inlet panels could be replaced on the
front or on the side
Service doors :
o type TOP on the front side;
o type PLUS on the bottom or on the side;
By-pass with multiple leaf damper by request;
Heating/ cooling coil by request;
Hanging support or basic steps by request;

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 05.02
Heat recovery units

ROT

OVERALL AND JOINED DIMENSIONS EVB P - (STANDARD VERSION)

Typesize
VB - 20-TOP
VB - 30-TOP
VB - 35-TOP

Max.
volume
m3/h

2500
3000
3500

Dimensions, mm

600 1500 2100


700 1500 2100
800 1500 2100

315
355
355

50

72

50
50

172
222

OVERALL AND JOINED DIMENSIONS EVB P - HBC (BY-PASS AND WATER COIL)

Typesize

Max.
volume,
m3/h

VB -20-TOP-HBC
VB -30-TOP-HBC
VB -35-TOP-HBC

2500
3000
3500

Dimensions, mm

680
880
980

1500
1500
1500

L
2100
2100
2100

D
315
355
355

Heating
capacity
B/H
kW
500/300-2R
15
700/400-2R 22,5
700/400-2R 24,5
Water coil

K
50
50
50

N
162
262
312

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 04.03
Heat recovery units

TOP/ PLUS

AERODYNAMIC CHARACTERISTICS external static pressure


Curves, marked with 13 are corresponding to the three speeds of the fans (3V);
For single speed fans use curve 1;
Dotted line is valid for unit with by-pass and water coil.

EVB 20TOP
400
350

E=69%
300

H,Pa

250

E=67%

200
150

E=65%
100

50

3
0

250

500

750

1000

1 +500/3002R

0
1250

1500

1750

2000

2250

2500

V,m3/h

Typesize
BV 20 - P
BV 20 - TOP/3V

Fan
BM/4-240/240
BM/4-240/240 3V

Motor power
W

Rated current
A

2370
2370

4,2
3,8

EVBAl 30TOP
500
450

E=69%

400

E=67%

350

H,Pa

300
250

E=65%

200
150
100

3
1

50

1 +700/4002R

0
0

500

1000

1500

2000

2500

3000

V,m3/h

Typesize
BV-30-TOP
BV-30-TOP/3V

Fan
BM/4-270/200
BM/4-270/200 3V

Motor power
W
2370
2370

Rated current
A
4,0
3,0

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 04.04
Heat recovery units

TOP/ PLUS

EVB 35TOP
500
450

E=72%

400

H,Pa

350

E=67%

300
250
200

E=65%

150
100
50
0
0

500

1000

1500

2000

2500

3000

3500

V,m3/h

Typesize
BV- 35-TOP

Fan

Motor power
W

Rated current
A

2550

6,2

BM/4-270/270

Note: The Efficiency is calculated with the following parameters: amb. = -10/ 90%
room. = 22/ 40%

NOISE LEVEL INPUT/ OUTPUT OF VB [ dB(A)]


Typesize
EVB 20-P
EVB - 30-P
EVB- 35-P

Hz
input
output
input
output
input
output

63

125

250

500

1000

2000

4000

8000

40
43
43
50
44
50

52
54
57
61
58
61

58
57
60
67
61
67

53
56
55
69
56
68

56
70
57
75
58
74

57
64
69
73
59
72

56
63
65
70
60
73

50
55
56
62
54
65

ORDER DESIGNATION
Heat recovery unit EVB 20 TOP- S/CB / 3V
EVB - 20 -TOP- HBC 3V
3-speed fan
By-pass and water coil
Model
Typesize
Heat recovery unit

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 04.05
Heat recovery units

TOP/ PLUS

OVERALL AND JOINED DIMENSIONS EVB PLUS - (STANDARD VERSION)

Typesize

Max.
volume,
m3/h

max

VB - 20-PLUS

2500

1200 600

640

2400

315

90

140,5

70

VB - 30-PLUS

3000

1300

700

740

2500

355

115

182,5

80

VB 35-PLUS

3500

1300

800

840

2500

355

115

147,5

80

Dimensions, mm

OVERALL AND JOINED DIMENSIONS EVB PLUS - HBC (BY-PASS AND WATER COIL)

Typesize

VB - 20-PLUS-HBC
VB - 30-PLUS-HBC
VB 35-PLUS-HBC

Max.
volume,
m3/h

2500
3000
3500

Dimensions, mm

1200 780
1300 880
1300 980

COT

Heating
capacity.

max

B/H

kW

640

2700

90

140,5

70

500/500-2R

16,7

740
840

2800
2800

315
355
355

115
115

182,5
147,5

80
80

600/600-2R
600/600-2R

24,1
26,8

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 04.06

Heat recovery units

TOP/ PLUS

AERODYNAMIC CHARACTERISTICS external static pressure


Curves, marked with 13 are corresponding to the three speeds of the fans (3V);
For single speed fans use curve 1;
Dotted line is valid for unit with by-pass and water coil.

EVB 20PLUS
400
350

E=69%
300

H,Pa

250

E=67%

200
150

E=65%
1

100
50

3
0

250

500

750

1000

1 +500/5002R

0
1250

1500

1750

2000

2250

2500

V,m3/h

Typesize

Fan

BV 20 - PLUS
BV 20 - PLUS/3V

Motor power
W

Rated current
A

2370
2370

4,2
3,8

BM/4-240/240
BM/4-240/240 3V

EVBAl 30PLUS
500
450

E=69%

400

E=67%

350

H,Pa

300
250

E=65%

200
150
100

3
1

50

1 +600/6002R

0
0

500

1000

1500

2000

2500

3000

V,m3/h

Typesize
BV-30-PLUS
BV-30-PLUS/3V

Fan
BM/4-270/200
BM/4-270/200 3V

Motor power
W
2370
2370

Rated current
A
4,0
3,0

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 04.07

Heat recovery units

TOP/ PLUS

EVB 35PLUS
500
450

E=72%

400

H,Pa

350

E=67%

300
250
200

E=65%

150

100
50

1 +600/6002R

0
0

500

1000

1500

2000

2500

3000

3500

V,m3/h

Typesize
BV- 35-PLUS

Fan

Motor power
W

Rated current
A

2550

6,2

BM/4-270/270

Note: The Efficiency is calculated with the following parameters: amb. = -10/ 90%
room. = 22/ 40%
NOISE LEVEL INPUT/ OUTPUT OF VB [ dB(A)]
Typesize
EVB 20-P
EVB - 30-P
EVB- 35-P

Hz
input
output
input
output
input
output

63

125

250

500

1000

2000

4000

8000

40
43
43
50
44
50

52
54
57
61
58
61

58
57
60
67
61
67

53
56
55
69
56
68

56
70
57
75
58
74

57
64
69
73
59
72

56
63
65
70
60
73

50
55
56
62
54
65

ORDER DESIGNATION
Heat recovery unit EVB 20 TOP- S/CB / 3V
EVB - 20 - PLUS - HBC / 3V
3-speed fan
Water coil and by-pass
Model
Typesize
Heat recovery unit

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 05.01

HEAT RECOVERY UNITS


WITH ROTARY REGENERATIVE HEAT EXCHANGER
EVB ROT
Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.
Operation temperatures from -20oC up to 50oC.
Designed to work with clean air in nonaggressive and non-sparkling environment.
CONSTRUCTION

Supporting construction, made by anodized aluminum profiles.


Thermo and sound insulated panels, powder coated RAL7035;
o Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0;
Rotary regenerative heat exchanger with efficiency up to 75%;
Double inlet belt driven centrifugal fans 380V, 50Hz;
Air filters class G4 EN 779:2002;
Rectangular duct connector;
Drain tray with connection;
Service doors from the side;
By-pass with multiple leaf damper by request;
Heating/ cooling coil by request;
Supporting frame by request;
Roof panels for outdoor installation by request.

www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

05 05.02
Heat recovery units

ROT

OVERALL AND JOINED DIMENSIONS

Typesize
42

62

82

V,
m3/h
3000
4000
5000
5000
6000
7000
7000
8000
9000

B,
mm

L,
mm

L,
mm

L,
mm

L,
mm

L,
mm

H,
mm

H,
mm

H,
mm

H,
mm

120
0

650

170
0

170
0

700

700

140
0

150
0

130
0

800

180
0

180
0

800

800

160
0

170
0

155
0

800

165
0

550

850

135
0

100
0

100
0

200
0

210
0

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product
development.

h,
mm
300
400
400
400
400
500
500
500
500

b,
mm
500
500
600
700
800
800
800
900
1000

05 05.03
Heat recovery units

ROT

TECHNICAL CHARACTERISTICS
The data given in tables are valid for the following parameters of the air:
inlet= -12, relative air humidity 80% (fresh air)

Winter mode:

outlet= 20, relative air humidity 30% (exhaust air)


Water temperature 80/60C
inlet= 33, relative air humidity - 35% (fresh air)

Summer mode:

outlet= 25, relative air humidity - 40% (exhaust air)


Water temperature 7/12C

Typesize

V
[m/h]

E
[%]

42-30

3000

72,3

42-40

4000

67,1

42-50

5000

62,8

62-50

5000

75,6

62-60

6000

68,6

62-70

7000

63,1

82-70

7000

75,3

82-80

8000

70,4

82-90

9000

66,3

Working
mode

outlet
after
ROT
[C]

Heating/
cooling water
coil

Q,
[kW]

outlet,

[ ]

winter

11.1

1000/500-2R

32

40

summer

27.1

1000/500-4R

15

15

winter

9.5

1000/500-2R

38

36

summer

27.6

1000/500-4R

17,5

16,1

winter

8.1

1000/500-2R

43

33

summer

27.9

1000/500-4R

20

17

winter

11

1000/600-2R

41

38

summer

27.2

1000/600-4R

18

15,5

winter

9.9

1000/600-2R

52

33

summer

27.4

1000/600-4R

24

17

winter

1000/600-2R

61

30

summer

27.7

1000/600-4R

28

18

winter

11.3

1200/600-2R

57

36

summer

27.1

1200/600-4R

27

16,0

winter

10.5

1200/600-2R

67

33

summer

27.3

1200/600-4R

32

17

winter

9.8

1200/600-2R

76

31

summer

27.5

1200/600-4R

37

18

Pext,
[Pa]

Fan

Rpm

Motor
power
[kW]

300

CBP 10/10

1420

1,1

300

CBP 10/10

1480

1,5

300

CBP 10/10

1620

2,2

330

CBP 15/11

1030

2.2

380

CBP15/11

1130

3,0

420

CBP 15/11

1200

4,0

400

BDB 400

1630

430

BDB 400

1780

540

BDB 400

1980

5.5

Note: In case of parameters, different from the mentioned above, please, contact the producer.

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product
development.

05 05.04
Heat recovery units

ROT

AERODYNAMIC CHARACTERISTICS PRESSURE DROP

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product
development.

05 05.05
Heat recovery units

ROT

SUPPORTING FRAME
This is the base over which are assembled the separate sections. Supporting frame is made of
galvanized profiles with openings for lift up and transportation, drainage and etc.
FRAME FOR OUTDOOR INSTALLATION
Designed for installation of the units over flat and low-pitched roofs without breach of the hydro
insulation.
The frame consists of profiles over which are assembled the separate sections of the heat
recovery unit. Profiles are clamped together with special clutches. This makes the frame easy
joinable and convenient for leveling and transportation.
OPTIONS FOR CONTROL AND AUTOMATION

Freeze protection;
Torn belt differential presostat;
Dirty filter differential presostat;
Electric motor (actuator) for multiple leaf dampers;
3-way valves for heating/ cooling water coils;
Air temperature remote tracking;
Power board for control and automation;
Rotary heat exchanger automatic control system.

ORDER DESIGNATION
EVB ROT 42 40
Air volume- (4000 /h)
Typesize / series /
Rotary regenerative heat exchanger
Heat recovery unit

www.tangra.bg
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product
development.

Ventilation

Heating

Air-conditioning

Head Office
174 "Europe" blvd.
1331, Sofia
Bulgaria
Phones: (+359 2) 9250599;
9250610
Fax: (+359 2) 9250557
www.tangra.bg