Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
MP75/CVL/015
TECHNICAL SPECIFICATION
TABLE OF CONTENTS
MP75/CVL/015
Rev. 0
Page 1 of 27
1.0
INTRODUCTION ......................................................................................................... 4
2.0
2.1
2.2
2.3
2.4
3.0
4.0
4.1
4.2
4.3
General ....................................................................................................................... 7
Pre-Assembly .............................................................................................................. 7
Calculations ................................................................................................................. 7
5.0
6.0
6.1
6.2
6.3
6.3.1.
6.3.2.
6.3.3.
6.4
6.4.1.
6.4.2.
6.4.3.
6.5
6.6
6.7
6.8
6.8.1.
6.8.2.
6.8.3.
7.0
7.1
7.2
8.0
8.1
8.2
8.2.1.
8.2.2.
8.2.3.
8.2.4.
8.2.5.
8.2.6.
8.2.7.
8.2.8.
8.3
8.3.1.
8.3.2.
8.3.3.
8.3.4.
8.3.5.
MP75/CVL/015
General ....................................................................................................................... 8
Dead Loads ................................................................................................................. 9
Live Loads ................................................................................................................... 9
Facilities and Buildings ................................................................................................ 9
Retaining Walls.......................................................................................................... 10
Slabs on Ground and Trafficable Culverts .................................................................. 10
Equipment loads ........................................................................................................ 10
General ..................................................................................................................... 10
Impact and Dynamic Loads........................................................................................ 11
Vibration Loads.......................................................................................................... 11
Wind Loads ............................................................................................................... 12
Earthquake Loads...................................................................................................... 12
Temperature Effects .................................................................................................. 12
Combined Loads ....................................................................................................... 13
Loading Combinations ............................................................................................... 13
Construction Loads .................................................................................................... 13
Lifting Loads .............................................................................................................. 13
SERVICEABILITY ..................................................................................................... 13
Acceptable Deflections .............................................................................................. 13
Slenderness Ratios for Steelwork .............................................................................. 15
DESIGN OF INDIVIDUAL ELEMENTS ...................................................................... 15
Earthworks ................................................................................................................ 15
Foundations............................................................................................................... 15
General ..................................................................................................................... 15
Footings .................................................................................................................... 15
Holding Down Bolts ................................................................................................... 16
Shear Keys ................................................................................................................ 16
Piers / Piles ............................................................................................................... 16
Raft Slabs .................................................................................................................. 16
Machine foundations.................................................................................................. 17
Tank Bases ............................................................................................................... 17
Concrete Structures ................................................................................................... 17
General ..................................................................................................................... 17
Materials.................................................................................................................... 18
Concrete cover for reinforcement ............................................................................... 18
Slabs on Grade.......................................................................................................... 19
Earth Retaining Structures ......................................................................................... 19
Rev. 0
Page 2 of 27
MP75/CVL/015
Rev. 0
Page 3 of 27
1.0
INTRODUCTION
This design criteria defines the general and technical requirements for the structural design
of buildings, structures and foundations for the Project No. D15002 (450-550 MW
Combined Cycle Power Plant and 8 MIGD SWRO Plant at the DUBAL Jebel Ali Site, Dubai,
UAE).
All design shall be in accordance with this Design Criteria, the Specifications and the
Standards and References set out in Section 2 and shall comply with the owners Safety
Guidelines. Alternative documents shall only be adopted with the owners approval.
2.0
2.1
ASCE 37-02
AISC 360-05
AISC 341-05
ACI 318M-08
ACI 530-08
AA ADM 2010
AISI S100-07
North American Specification for the Design of ColdFormed Steel Structural Members, American Iron and
Steel Institute
BS4449:2005
MP75/CVL/015
Rev. 0
Page 4 of 27
BS 5395-1:2010
BS EN 1990:2002
EN 1991-1-4:2005
EN 1991-3:2006
EN 1992-1-1:2004
EN 1992-3:2006
EN 1993-6:2007
EN 197-1:2011
EN 10080:2005
Refer to the technical specifications below for a list of relevant materials standards.
Alternative design codes may only be used with approval from the Company.
Any conflicts between approved codes shall be brought to the engineers attention for
resolution.
2.2
MP75/CVL/021
MP75/CVL/022
MP75/CVL/001
MP75/CVL/018
MP75/CVL/006
MP75/CVL/004
MP75/CVL/005
MP75/CVL/012
MP75/CVL/015
Rev. 0
Page 5 of 27
2.3
MP75/CVL/013
MP75/CVL/003
MP75/MEC/011
MP75/CVL/016
Specification
Fabrication
MP75/CVL/017
Civil Specification
Structural
Steelwork
Supply
and
References
Design of Structures and Foundations for Vibrating Machines by Arya, ONeill and
Pincus
2.4
3.0
SITE CONDITIONS
General site information and climatic data are included in Volume 2A, Section 10 Site
Data.
MP75/CVL/015
Rev. 0
Page 6 of 27
4.0
DESIGN RESPONSIBILITIES
4.1
General
The Contractor organizations design & lead engineers shall become familiar with the
functions and operating conditions of the plant such as the movement of materials and
liquids, rotating masses, out of balance forces, temperature changes, impact forces,
spillage loads, and build up of scale.
The design engineer shall ascertain, in conjunction with the lead engineer and in
consultation with the process, mechanical, and electrical engineers, the loads created by
plant, equipment, operational conditions, and stacked materials during construction for
each facility.
All design input shall be authorised by the lead engineer prior to application.
Structures supporting plant and equipment should be designed with consideration for the
proposed function and the economical fabrication and erection of the structures.
Constructability and access for maintenance shall be considered. The bracing at ground
level should be kept to a minimum so that easy access is provided for maintenance and
operations.
All calculations and drawings shall be documented in SI units and the English language.
4.2
Pre-Assembly
Prefabricated, shop welded and pre-assembled steelwork is an option as opposed to field
bolted steelwork. Similarly, precast concrete is an option as opposed to in-situ reinforced
concrete. The design engineer shall co-ordinate with the lead engineer in determining
where prefabrication and pre-casting is to be adopted.
The sequence of construction, installation of mechanical equipment and road transport and
lifting limitations shall be considered in the design process and these should be agreed with
the Pre-Assembly and Construction teams prior to a final design being completed.
4.3
Calculations
All design calculations shall be completed on A4 size project calculation sheets in
accordance with project procedures. All other design data shall be on A4 sized sheets,
reducing A3s etc. as necessary.
The basis and assumptions for the design together with all basic data and design
information and sources of unusual formulae shall be recorded with the calculations. The
calculations shall include a general arrangement of the facility and any sketches prepared.
Calculations together with the data and sketches shall be consecutively numbered, given a
title incorporating the specific facility number for the area, signed, dated and provided with a
project standard cover sheet. The cover sheet shall incorporate the title of the facility and
contain a brief index to the calculations. Each set of calculations shall be logged in to a
master index kept by the lead engineer so that it can be presented to any authority or its
delegate for approval.
All calculations and drawings shall be independently checked.
The following minimum requirements shall be satisfied.
MP75/CVL/015
Rev. 0
Page 7 of 27
A detailed introduction explaining the circumstances and basis for design and
the path chosen.
Copies of all inputs such as general arrangements, vendor data, geotech info,
data sheets, faxes , emails etc. Wherever possible these should be scanned
or copied as part of the calculations and not just referenced.
Ensure all electronic calculations and any other engineering package output is self
explanatory and easily followed without needing the software for interpretation.
5.0
Add an appendix for hard copy attachments, make the calculation a stand-alone
document where ever possible by attaching the nal IFC drawings to the
calculations.
Ensure there is a HOLDS list; all HOLDS should be cleared prior to nal check and
approval.
DESIGN DATA
For general design data related to temperature, humidity, rainfall and tide heights, refer to
Specification Site Conditions.
Buildings and other structures are generally occupancy category II in accordance with the
IBC Table 1604.5. Facilities shall be occupancy category IV where listed as an essential
facility in Table 1604.5.
6.0
DESIGN LOADS
6.1
General
The loads used in the design shall be in accordance with the loads given in this criteria, the
specific loadings as established for each item of equipment, and ASCE 7-05 Minimum
Design Loads for Buildings and Other Structures. The minimum or maximum dead loads
shall be combined in conjunction with other loads, so as to produce the most severe
combinations of load imposed on the structure.
MP75/CVL/015
Rev. 0
Page 8 of 27
The layout and design criteria for all equipment supported on the structure shall be
obtained in writing from the mechanical engineer before design commences.
The design engineer, in consultation with the lead engineer, shall determine the loads
imposed by electrical cables and services pipes.
6.2
Dead Loads
Dead loads shall be determined using ASCE 7-05.
Dead load shall be considered in two categories:
Superimposed dead loads shall be considered as the weight of all materials forming loads
on the structure that are not structural elements and which are likely to vary or be removed
during operation or construction of the structure.
Superimposed loads may include:
Piping contents.
The design engineer shall assess the possibility of the removal of these dead loads, which
will result in the most severe combination of stresses in the structure.
6.3
6.3.1.
Live Loads
Facilities and Buildings
Except where specific equipment loads produce more severe loads, minimum floor vertical
live loads shall be as the following table:
Area
Uniformly
Distributed Load
Concentrated Load
(kN)
(kPa)
Offices (excl. file rooms, etc.)
3.0
2.7
5.0
4.5
4.8
(100 psf)
4.5
2.5
2.0
2.5
2.0
MP75/CVL/015
Rev. 0
Page 9 of 27
Area
Uniformly
Distributed Load
Concentrated Load
(kN)
(kPa)
Conveyor gallery walkway for
truss design
1.2 kN/m
10.0
5.0
4.5
10.0
0.6 to 1.0
IBC
1607.11.2.1
4.5
These loads are to be verified for the specific area and facility. The structural members are
to be designed for the load pattern (either uniformly distributed or concentrated), which has
the most adverse effect on the supporting member. Generally the concentrated loads in the
above table will be applied to short members that support only a small area of floor.
Stair treads shall be designed for a concentrated vertical load of 1.34 kN (300 lb) in
accordance with the IBC.
Handrails shall be designed for a load of 0.36 kN/m (25 lb/ft) applied in any direction to the
top rail and also 0.89 kN (200 lb) concentrated load applied in any direction (not applied at
the same time).
6.3.2.
Retaining Walls
All retaining walls shall be designed for the actual surcharges applied.
Surcharge loads shall not be less than the following:
6.3.3.
6.4
6.4.1.
Equipment loads
General
Layout and design criteria for the support of equipment items, together with Certified Seller
drawings, shall be provided by the relevant discipline engineer. Equipment reactions shall
MP75/CVL/015
Rev. 0
Page 10 of 27
be supplied by the Seller and shall indicate all possible loading combinations, dynamic
effects and allowable deflections of supporting structures.
6.4.2.
3.0*
Rotating machinery
2.0*
Mobile equipment
1.2
Fork lifts
1.6
1.35
2.0
1.1
* These values shall be used for preliminary design only. Actual certified dynamic load
values nominated by the equipment Seller shall be used in the final design.
6.4.3.
Vibration Loads
Certified Seller drawings giving design parameters and operating frequencies shall be
obtained from the manufacturer for each piece of equipment. The dynamic effect on the
immediate supports and on the main structure shall be evaluated using un-factored actual
masses.
Areas subject to dynamic loading shall be checked for dynamic response against limits for
workers by ISO 2631-1:1997, Mechanical vibration and shock- Evaluation of human
exposure to whole-body vibration.
Wherever possible, vibrating equipment shall be isolated from the main structural framing.
However, where such equipment is supported on structural members, the following table
provides a guideline for the desired relationship between the frequency of the vibrating
loads and the frequency of the supporting members:
Length of Beam
Type of Supports
5m or less
Directly connected to
column
1.5
Greater than 5m
Directly connected to
column
2.0
5m or less
1.5
Greater than 5m
2.0
The natural frequency of bracing adjacent to the equipment shall also be checked. The
desired relationship between the natural frequency fn and the forcing frequency ff of the
brace shall be as follows: f n/ff is less than 0.75 or greater than 1.5.
MP75/CVL/015
Rev. 0
Page 11 of 27
The design engineer shall consider the effects of fatigue in the design of supporting
members and their connections. Fatigue shall be checked in accordance with EN 1993 and
shall be based on the relevant number of cycles applicable to the beam or to the detail
being designed and shall take into account the fabrication details of the beam and its
components.
6.5
Wind Loads
The basic wind speed for the site is 45 m/sec. The basic wind speed is the 3-second gust
speed at 10 m height in exposure category C with a 50 year return period.
The site exposure category for all wind directions shall be taken as exposure D. The design
wind speed is to be adjusted for the site exposure category and the building height above
ground in accordance with the procedures in ASCE 7-05.
The importance factor by ASCE 7-05 Table 6.1 shall be 1.0 for occupancy category II
facilities and 1.15 to occupancy category IV facilities.
The topographic factor and wind directionality factor in ASCE 7-05 shall be taken as 1.0.
Wind forces shall be determined in accordance with ASCE 7-05. Drag coefficients may also
be determined in accordance with EN 1991-1-4.
The operating wind speed VO shall be taken as 20 m/sec. This is the wind speed applicable
during shutdown of the plant and also during erection procedures.
The serviceability wind speed VS for serviceability deflection checks shall be based on a
10 year return period. It shall be taken as 0.9 x 45 = 40.5 m/sec.
6.6
Earthquake Loads
Seismic Loads - Structures and foundations shall be designed to withstand a seismic load
in accordance with the seismic provisions of the IBC 2009 standard and relevant clauses of
the ASCE 7 standard, based on the parameters as obtained from Seismic design Code for
Dubai by Dubai Municipality.
6.7
Temperature Effects
Structures shall be designed to accommodate movements due to environmental and
operational thermal expansion and contraction. Any operational temperature effects on
structures shall be assessed. The designer shall provide installation temperature
positioning tolerances for bearings and expansion joints. Bearings shall be designed for a
minimum installation tolerance of +/- 25mm in addition to the thermal movement
allowances.
Concrete shall be detailed with expansion joints as required to accommodate thermal
expansion.
Design steelwork installation temperature shall be between 25oC and 45oC. The steel
temperatures used to calculate contraction or expansion movements from an installation
position shall be:
Locations exposed to
direct sunlight
Other Locations
65
50
MP75/CVL/015
Rev. 0
Page 12 of 27
6.8
Combined Loads
6.8.1.
Loading Combinations
Loading combinations and factors shall be generally as defined in BS EN 1990 and BS EN
1991, BS EN 1992, or BS EN 1993 whichever applicable. In addition, loading combination
including seismic loads shall be generally as defined in IBC.
Live load shall include loading by cranes.
The imposed load shall include for dynamic effects where appropriate. The imposed and
wind loads shall be combined with the dead load and with each other in such a way as to
give the worst possible stresses at any location. In addition thermal effects shall be
considered where significant, acting in conjunction with the combined load cases.
Load cases need not be combined arbitrarily without regard for practical possibilities e.g. an
outdoor crane need not be capable of carrying its maximum operating load and maximum
wind load simultaneously, since it would not be operating whilst subject to the maximum
wind loading.
6.8.2.
Construction Loads
Consideration shall be given to the construction sequence in order to ensure that a
structure is able to carry the design loads which act before completion of the structure and,
also, that exceptional loads resulting from the construction sequence are catered for. This
consideration shall include dead, wind and thermal loads together with suitable imposed
loads, as appropriate. 2.5 kPa DL construction load for platforms shall be used, and
operating wind load shall be used because of the temporary nature of the loads.
6.8.3.
Lifting Loads
Consideration shall be given to the loads induced during lifting and placement.
7.0
SERVICEABILITY
7.1
Acceptable Deflections
The following table shall be used as a guide to determine acceptable deflections. Unless
noted otherwise, deflection is for the serviceability limit state load combination.
Element
Floor beam
Refer ISO 2631-1:1997, Mechanical vibration and shock Evaluation of human exposure to whole-body vibration
MP75/CVL/015
Rev. 0
Page 13 of 27
Element
Lateral deflections to be
based on the top or bottom
flange mobilization, as
applicable.
Lateral
deflection
of
supports at level of crane
rail (per EN 1991-3)
Lesser of 10 mm and Hc
500
Height
150
Height
250
Roof beam
Conveyor trusses
Span Vertical
300
Span Lateral
300
Relative horizontal
deflection between floors
Pipe Racks
MP75/CVL/015
Rev. 0
Page 14 of 27
7.2
100
180
180
250
8.0
8.1
Earthworks
Compaction standards shall be expressed as a percentage of the materials Modified
Proctor maximum dry density (MDD) at its optimum moisture content.
The required degree of compaction shall be as follows:
95% for a minimum depth of 300 mm immediately under concrete slabs and
footings placed on fill or the in-situ subgrade
Embankments composed of engineered fill and cuts in existing site material shall be to a
slope of 1 vertical to 2 horizontal unless proven by calculations otherwise.
8.2
8.2.1.
Foundations
General
Foundations shall be designed in accordance with the Geotechnical Report for the specific
facility.
Where over excavation has occurred backfill shall be either mass concrete or selected
graded granular material from an approved source in accordance with Specification
Earthworks, Structural Excavation and Backfill and shall be compacted in layers of 150
mm maximum compacted thickness to the required standard of compaction.
8.2.2.
Footings
Foundations shall be designed for the applicable load combinations.
Maximum total settlements, differential settlements and interaction between foundations
and structures shall be considered during design.
In checking uplift stability, only the soil directly above the footing shall be taken into account
unless proved otherwise.
MP75/CVL/015
Rev. 0
Page 15 of 27
300mm
300mm
The minimum height from top of concrete to paving high point shall generally be:
8.2.3.
150mm
150mm
8.2.4.
20mm dia.
16mm dia.
Shear Keys
Shear keys shall be used where the applied ultimate shear load to the baseplate exceeds
75 kN.
Shear keys shall be single or cruciform plates in preference to an open H section. They
shall be full penetration butt welded to the baseplate unless otherwise approved.
8.2.5.
Piers / Piles
The design parameters for piers shall be in accordance with the Geotechnical Report for
the specific facility.
8.2.6.
Raft Slabs
Raft slabs shall be designed in accordance with the Geotechnical Report for the specific
facility.
MP75/CVL/015
Rev. 0
Page 16 of 27
8.2.7.
Machine foundations
A finite element analysis shall be used to verify that the natural frequency of the foundation
is sufficiently removed from the forcing frequency of the equipment. The dynamic response
of the foundation shall be calculated and checked against agreed acceptability criteria.
References for machine foundations include:
8.2.8.
Design of Structures and Foundations for Vibrating Machines by Arya, ONeill and
Pincus
Tank Bases
Flat bottomed, ground supported tanks shall generally be supported on an annular ring of
concrete under the tank shell. Where additional uplift resistance is required or increased
axial bearing capacity is required, an inverted tee shaped ring foundation shall be used. A
full raft slab under the tank shall be used where required for stability.
Tank foundation loads shall be derived from an API 650 analysis of the tank. Working loads
from the API 650 analysis shall be factored to derive limit state load combinations for
foundation design.
8.3
8.3.1.
Concrete Structures
General
Concrete design shall be in accordance with ACI 318 or BS EN 1992: Euro code 2.
Site soils are generally corrosive. Concrete surfaces below ground shall receive surface
protection as per specification Concrete Works.
Concrete surfaces above ground shall receive surface protection where noted in
specification Painting and Protective Coatings.
MP75/CVL/015
Rev. 0
Page 17 of 27
8.3.2.
Materials
Concrete strength grade designations as per EN 1992 and corresponding usage, shall be
as follows:
Application
Strength
Grade
Designation
Maximum
Aggregate
Size
Characteristic
Compressive Strength
fck at 28 days MPa
C40/50
20
40
C40/50
20
40
Piles
C40/50
20
40
Silo walls
C40/50
20
40
Blinding
C12/15
20
12
Marine facilities
C50/60
20
50
Miscellaneous Concrete
e.g. Drainage Structures, Road
Signage and Fencing Footings
C25/30
20
25
C40/50
10
40
C20/25
10
20
75
Without membrane
75
Tops of footings
75
Formed
75
Bored piers
100
Precast footings
50
Precast piles
50
Rev. 0
Page 18 of 27
Formed
50
50
40
Slabs on Grade
Slab design, including joint selection and spacing, shall be guided by reference Guide to
Industrial Floors and Pavements by Cement Concrete and Aggregates Australia or
equivalent. Joint detailing is to be approved by the lead engineer. The design engineer shall
take account of any loading, both during construction and plant operations, from mobile
equipment, cranes and scaffolding.
As a minimum, provide a 150mm thick slab reinforced with A252 (8 mm bars at 200 mm
centres) throughout to top face.
8.3.5.
8.3.6.
MP75/CVL/015
Rev. 0
Page 19 of 27
8.3.7.
8.3.8.
8.3.9.
Crack Control
Minimum reinforcement shall be to EN 1992-1-1, Section 7.3.2. Flexural reinforcement shall
also not be less than ACI 318, Section 10.5.
Control of cracking shall be to EN 1992-1-1, Section 7.3.3 for a crack width of 0.30 mm. For
structures in seawater and over seawater (as determined by the astronomical high tide
contour), the crack widths shall be calculated and shall not exceed 0.15 mm. The quasipermanent load to EN 1990 shall be used in determining the crack widths.
For liquid retaining structures, crack control shall be achieved by applying Section 7.3.3 of
EN 1992-3 for a crack width of 0.10 mm.
8.4
8.4.1.
Steelwork
General
Steelwork design shall be to the limit state design method in accordance with the IBC and
AISC 360 and AISC 341 where required or in accordance with BS EN 1993.
Where floor plate is adequately welded to its support beam, it can be considered as
restraining the top flange of the beam. Floor grating fixed by any method shall not be
considered as restraining the top flange of its supporting beam.
3D welded steel frames shall not be used. 2D welded steel frames are acceptable, subject
to transportation size limits.
MP75/CVL/015
Rev. 0
Page 20 of 27
8.4.2.
8.4.3.
Bolting
Unless otherwise shown, structural bolts shall be M20 bolts to ASTM A325M or
EN 14399-3 Grade 8.8. Unless noted otherwise, all bolts shall be snug tight. Slip-critical
connections and tensioned bearing connections shall be designated on the drawings.
All bolts shall be hot dip galvanized. All bolts shall be painted following installation of nuts
and approval of installed bolt tensioning. The paint system shall be in accordance with
specification Painting and Protective Coatings.
Bolts in slip-critical connections shall be fully tensioned to exclude slip under serviceability
loads.
Bolts in tensioned bearing connections shall be fully tensioned but will permit the bolts
slipping into bearing mode under serviceability loads.
Fully tensioned ASTM A325 bolts shall be tensioned to AISC 360. Fully tensioned
EN 14399-3 bolts shall be tensioned to EN1090-2. Bolts shall be tensioned using the part
turn method.
Bolts subject to frequent load reversal from vibrating equipment shall be slip critical. Bolts
subject to cyclic or vibrating loads but without load reversal shall be tensioned bearing
connections or slip critical connections.
Capacities of bolts in shear bearing mode shall be based on the assumption that threads
are in the shear plane.
Bolts shall be a minimum size of M20, connected through cleats of 10mm minimum
thickness UNO. For purlins and girts and similar minor connections smaller bolts to
ASTM 307 (or Grade 4.6 to ISO 4016) and 8mm thick cleats may be used, except where
the purlin and girt manufacturer recommends high strength bolts and/or thicker cleats.
8.4.4.
Welding
Manual welding, semi-automatic and automatic welding shall be in accordance with
AWS D1.1 (and AWS D1.8 where required) or in accordance with EN ISO 3834. Electrodes
shall have a minimum ultimate tensile strength of 480 MPa and a minimum yield strength of
355 MPa.
Welds across the tension flange of members subjected to dynamic loads are not permitted,
unless approved by the lead engineer.
The minimum fillet weld size to be used is 6 mm. Where intermittent welds of a greater size
are specified, the remaining length shall be seal welded using a 3mm fillet weld where
specified. Butt welds shall be full penetration unless otherwise approved by the lead
engineer.
Details that require site welding shall only be acceptable with the lead engineers approval.
8.4.5.
Bracing
Vertical bracing shall generally be tube sections. Vertical braces are often long, heavily
loaded members and the fabrication effort required on the end connection is outweighed by
MP75/CVL/015
Rev. 0
Page 21 of 27
the structural efficiency of the tube section. Horizontal floor bracing shall generally be angle
sections. Open H section bracing is typically not used.
The flexural stiffness of tube bracing end connections shall be considered in determining
the effective length of compression tube braces.
8.4.6.
Corrosion Protection
Corrosion protection is required for all steelwork as per specification Painting and
Protective Coatings .
The steelwork shall incorporate the following minimum requirements:
8.4.7.
The minimum thickness of structural hollow sections shall be 4.8 mm and shall be
sealed unless galvanised.
Arrangements of steel that prevent access for inspection and maintenance shall not
be used, for example back-to-back angle members
Flooring
The minimum clear head height between top of floor and underside of ceiling beams for all
buildings, structures and conveyor gantries shall be 2200mm.
Unless noted otherwise, floor grating shall be hot dipped galvanised and fabricated from
32mm x 5mm bars at 40mm centres with 6mm square twisted cross bars at 100mm
centres. Load bars shall preferably be at right angles to the direction of predominant
pedestrian travel. All edges, ends and penetrations shall be fully banded.
The grating shall be fixed to the support members by hot galvanised bolts and proprietary
bent clip fasteners spaced at a maximum of 1000 mm intervals at all supports, but with a
minimum of four clips per panel. An alternative fixing system may be used subject to
approval. Where approved, floor grating may be welded to the supporting steelwork.
The standard floor plate thickness is 6 mm.
Floor plate shall have a raised angular pattern and shall be used selectively to prevent
spillage flowing to lower levels and shall be fully seal welded or sealed by another approval
method. Plate shall be welded to support beams or an alternative fixing system may be
used subject to approval, however it may not be sufficient to provide lateral restraint.
8.4.8.
900 mm
The clear nominal width between handrails for maintenance walkways and stairs in
conveyor gantries shall be 750mm.
MP75/CVL/015
Rev. 0
Page 22 of 27
Where possible, at the end of stairs, grating shall be aligned such that the load bars are
perpendicular to the direction of the stair.
For stairs up to 1200 wide, grating treads shall be fabricated from 32mm x 5mm load bars
at 30mm c/c with 6mm square twisted cross bars at 100mm c/c or approved alternative.
The stair treads shall be bolted to the stair stringers. Stair treads shall be T6 Webgrate
treads or an approved alternative and nosing shall be non-slip, coloured and removable.
The geometry of stair flights and handrails is detailed on the standard drawings and shall
conform to the IBC. The loading on stairs and handrails is detailed in Section 6.3 of this
document.
8.4.9.
8.4.10. Ladders
Rung ladders shall have:
20 mm square ladder rungs turned on edge where advised by the lead engineer.
MP75/CVL/015
Rev. 0
Page 23 of 27
1. Supporting Columns
Total of:
(a) Adjustment off centreline available from the design details, and
(b) Column height to beam rail divided by 500 or 25 mm, whichever is less.
2. Runway Beams
Total of:
(a) Rail head divided by 4, and
(b) Beam sweep allowance of beam span divided by 1000 or 3 mm, whichever is greater.
The horizontal actions arising from above eccentricities shall by analysed by the Twin
Beam Analogy assumption calculated by deriving horizontal forces acting at the centre of
gravity of the upper and lower beam flanges.
Horizontal loads derived from dynamic actions shall be applied at top of rail level and the
resulting horizontal design action on the beam also analysed by the Twin Beam Analogy
Method outlined above.
To allow for the above vertical and horizontal eccentric effects the following shall be
adopted to derive total stresses in the beam top and bottom flanges:
a)
Basic Case: Stresses due to vertical and lateral loads with no allowance for vertical
and lateral load eccentricity.
b)
c)
Page 24 of 27
8.5
Cladding
Cladding shall be in accordance with Cladding Specification.
8.6
Concrete Masonry
Concrete masonry (i.e. blockwork) shall be designed in accordance with ACI 530 Building
Code Requirements for Masonry Structures.
Infill blockwork shall typically cantilever from the base and shall not incorporate metal ties to
the surrounding structure. Metal ties are not rated for seismic loads nor capable of
sustaining high seismic deflections.
Walls shall be detailed in accordance with the standard drawings.
9.0
DESIGN OF FACILITIES
9.1
9.2
Pipe Racks
In consultation with the piping engineer, the design engineer shall determine the magnitude
and application of the loads listed below.
A pipe stress analysis shall be completed and all forces shall be provided before any
structural design on pipe racks proceeds. Seismic loads shall be confirmed by the structural
engineer.
MP75/CVL/015
Rev. 0
Page 25 of 27
Pipe rack lateral deflections shall be limited as required by the piping engineer.
9.2.1.
Vertical Loads
The design engineer shall obtain information relating to the process fluid and the likelihood
of scale formation from the lead engineer.
The vertical loads shall include the weight of pipes, fittings, valves, insulation and the fluid
contents of piping, as well as loads due to scaling and sanding. In determining the weight of
insulation, a density of 200 kg/m3 shall be adopted. A minimum vertical load (including self
weight of pipes) of 2.5 kPa shall be used for each level of pipe rack.
The procedure for hydro-testing and the resultant loads shall be evaluated to determine the
worst load case acting on supports.
9.2.2.
Transverse Loads
Transverse loads include those from thermal expansion and the transverse component of
wind load.
In determining wind loads, the projected height per level of pipe rack used shall be obtained
from the following:
Width of pipe rack B
Metres
Metres
B<4
1.2
4 <= B < 6
1.5
6 <= B <= 10
2.0
A drag coefficient Cd of 1.3 shall be adopted. Wind on structural steel is included in the
above.
For congested pipe racks, loads shall be explicitly calculated for all pipes (with due
allowance for future expansions) but shall not be less than calculated using the above
simplified method unless approved by the lead engineer.
9.2.3.
Longitudinal Loads
Longitudinal loads include those from thermal expansion and the longitudinal component of
wind load.
Thermal forces are those forces caused by temperature changes during operations and
maintenance conditions over the life of the plant. Thermal forces shall be considered for the
following conditions:
Sliding friction forces due to the thermal expansion and contraction of the piping and
equipment.
Horizontal loads due to thermal expansion shall be a minimum of 15% of the vertical pipe
loads and shall be applied to each transverse frame and the longitudinal steel immediately
adjacent to the frame on each side. Where anchor loads are higher they shall be adopted
for design. A minimum longitudinal load of 10% of vertical pipe loads shall be accumulated
at braced bays and carried down to the foundations.
MP75/CVL/015
Rev. 0
Page 26 of 27
Longitudinal thermal forces shall be considered as uniformly distributed loads over the
entire span of the beam applied to the top flange of the pipe support beam.
9.2.4.
Longitudinal Beams
All longitudinal beams connecting pipe racks shall be designed for a minimum 10% of the
vertical load on the transverse beams with a minimum of 10 kN.
Horizontal load shall be a minimum of 15% of the vertical load from pipe off-takes but shall
not be less than 3 kN. Loads from monorails and platforms etc. shall be considered to act
simultaneously with these loads.
9.2.5.
9.2.6.
9.2.7.
Cable Trays
Loadings from cable trays shall be determined in consultation with instrument and electrical
engineers. As a minimum, the following loads shall be used:
300 wide tray
60 kg/m
90 kg/m
120 kg/m
180 kg/m
MP75/CVL/015
Rev. 0
Page 27 of 27