Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Why Earthing:
Earthing system of generating station shall meet the following requirement.
To ensure low impedance earth fault current return path for operation
fault.
Earthing conductors
& connections should withstand the earth fault current for the duration
of the fault.
Neutral
earthed
through
grounding
transformer
c) 6.6 kV system : Neutral earthed through resistor.
d) 415V system : Neutral solidly grounded
Short circuit current and fault clearing time are playing an important
NIHARIKA
TECHNOLOGIES
Page 7
750mm respectively.
Minimum earth coverage of 300mm shall be provided between earth
conductor and the bottom of trench / foundation / underground pipes
at crossings. Earthing conductors crossing the road can be installed in
pipes. Wherever earthing conductor crosses or runs at less than
300mm distance along metallic structures such as gas, water, steam
NIHARIKA
TECHNOLOGIES
Page 7
=
Where
S - Cross section area in sq. mm.
NIHARIKA
TECHNOLOGIES
Page 7
K=
)---------(IS3043, Cl.12.2.2.1)
Taking values of 20, Qc, B as per IS 3043, Table 5 for steel conductors.
20 = Electrical resistivity of conductor material at 20C (ohm-mm).(138 x
10-6)
Qc = Volumetric heat capacity of conductor material (J/C mm3) (3.8 x 103).
B = Reciprocal of temperature co-efficient of resistivity at 0C for the
conductor(C) (202).
i = Initial temperature of conductor (C) (50C).
f = Final temperature of conductor (C) (500C) (as per IS 3043, Table
6A).
K = 79.14
S
NIHARIKA
TECHNOLOGIES
Page 7
The average soil resistivity of the main plant & auxiliary building is 12 ohm-m
andfor switchyard area is 6 ohm meter. Considering 4.8mm(0.12mm/year)
for loss of material for mild steel conductor due to corrosion, theminimum
rod diameter required is 30.17mm. Therefore rod diameter of 32mm
isselected for main plant and auxiliary building.
For conductors embedded in concrete and those exposed for inside Main
Plant,Switchyard & Auxiliary Building earth grid, the size adopted will be
equal to orhigherthan 505.43 sq.mm. Since owners specification calls for
providing 75x12mm,the same size is recommended.
Rod / Pipe Electrodes
32mm diameter, 3000mm long, galvanized steel rod will be provided for
directdriven rod. For test pits with electrodes, the electrodes will be 36mm
diameterheavy-duty type (Class-C) GI pipe with perforations. Electrodes
installed in thetest pits will have disconnecting facilities.
Equipment Grounding Leads
The size of the grounding leads depends upon the type of equipment
andstructure to be grounded and are provided generally as per IS 30431987 andalso with the view to minimize the number of sizes.
The grounding conductor sizes have been calculated as per following
formula:
(IS3043, Cl.12.2.2.1)
Where
S - Cross section area in sq. mm
NIHARIKA
TECHNOLOGIES
Page 7
K=
)(IS3043, Cl.12.2.2.1)
NIHARIKA
TECHNOLOGIES
Page 7
of fault current through the earth. The closer a person is to the ground rod or
grounded device, the greater the concentration of current and the higher the
voltage. The current flow creates a voltage drop as it flows through the
earth's surface and a person standing with their feet apart bridges a portion
of this drop thus creating a parallel path for current flow as seen in the these
two illustrations in Figure
The wider apart a person's legs are, the larger the voltage difference across
the body. Protection from the step potential hazard should be to stay in the
zone of equipotential while working. Simply being alert to this hazard is the
best defense. For this reason, unqualified personnel standing on the ground
are
cautioned
to
stay
clear
of
structures.
This means that a person standing near the point where fault current enters
the earth may have a large potential difference from foot-to-foot. The
potential difference over the same span will be less and less as the span is
moved away from either the fault current entry point or the fault current
return point at the source.
Touch Potential
Touch potential is a problem similar to step potential see Figure 4. It
involves a fault current flow in the earth establishing a potential difference
NIHARIKA
TECHNOLOGIES
Page 7
between the earth contact point and some nearby conductive structure or
hardware.
Protection for step and touch potential is the use of switch operating
platforms and ground grids. The worker must remain upon a local conductive
mat as the highest voltage gradient has been moved to the mat's edges. Sub
stations on Site have a ground grid located under the rocks, but if an
individual is located outside this area and while standing on the earth,
touches a ground or a grounded object, a difference in potential may exist
during a ground fault.
Touch and Step Potential Criteria:
For average 50kg body weight, the allowable step and touch voltage as per
Eq.29 & 32 of IEEE-80 isAllowable Step voltage,
Estep 50 (V) = (1000 + 6Cs x s) x 0.116 / (ts)(As per IEEE 80, Clause 8.3)
Allowable Touch voltage, Etouch 50 (V) = (1000 + 1.5Cs x s) x 0.116 / (ts)
Where,
NIHARIKA
TECHNOLOGIES
Page 7
Cs =
Cs =
= 0.7749
NIHARIKA
TECHNOLOGIES
Page 7
R2 =
[ln(
)-1+
-1)2]
Where,
Rg is Grid resistance in Ohms
R1 is Ground resistance of grid conductors in Ohms
R2 is Ground resistance of grid rod bed in Ohms
NIHARIKA
TECHNOLOGIES
Page 7
Page 7
Where:
Ta = DC offset time constant; [Ta = X/ (R) = 1 / (100) = 0.003 s]
Df = decrement factor
Sf = current division factor; 0.7
If = rms value of symmetrical ground fault current;
IG = maximum grid current in A
To verify the suitability of the design parameters, it is necessary to compare
GPR
with
thetolerable
voltage
(Etouch50);
therefore
further
design
K=
Where:
K = reflection factor between different material resistivities
= resistivity of the earth beneath the surface material in ohm-m
s= surface layer soil resistivity in ohm-m
Reflection factor (K) and thickness of the surface layer (hs) can be used to
determineSurface layer derating factor (Cs) using graphical analysis referred
to IEEE std 80-2000.
ETAP Calculation Method
Grounding calculation is carried out by using computer program ETAP Power
station 11.1.0from Operation Technology, Inc. which follows to the IEEE 80-
NIHARIKA
TECHNOLOGIES
Page 7
for
Square
Rectangular,
Triangular,
L-Shaped,
or
T-
Shapedground grids.
The Ground Grid Systems module calculates the following:
The maximum allowable current for specified conductors, warnings are
issued if thespecified conductor is rated lower than the fault current
level.
The step and Touch potentials for any rectangular / triangular / Lshaped / T-shapedConfiguration of a ground grid, with or without
ground rods (IEEE std 80 and IEEE std665).
The tolerable Step and Mesh potentials and compares them with
actual, calculatedStep and Mesh potentials (IEEE std 80 and IEEE std
665).
Graphic profiles for the absolute Step and Touch voltages, as well as
the tables of thevoltages at various locations (Finite Element Method).
The optimum number of parallel ground conductors and the rods for a
rectangular /triangular / L-shaped / T-shaped ground grid. The cost of
conductors / rods and thesafety of personal in the vicinity of the
substation
/ generating station
during a
groundfault
are both
NIHARIKA
TECHNOLOGIES
Page 7
NIHARIKA
TECHNOLOGIES
Page 7