CT Details for 33kV Switchgear

Substation Jabel Hafeet

J
A
B
E
L

CT Data

Description
Cable Feeder
Main Protection ( Pilot Wire Diff Prot)

CT No.

Core

CT Ratio

VA

Accuracy

T1

Core 1

600-400/1A

Core 2
Core 3
Core 4

600-1200/1A 15VA - 30VA


600-1200/1A 15VA - 30VA
2000/1A
15VA

Core 1

300-600/1A

Core 2
Core 3
Core 4

300-600/1A
300-600/1A
2000/1A

15VA - 30VA
15VA - 30VA
15VA

5P20
0.5FS5
5P20

Core 2
Core 1
Core 1

2000/1A
2000/1A
2000/1A

15VA
15VA
15VA

5P20
0.5FS5
5P20

Protection ( O/C+E/F)
Transducers+Bay Control Unit
BusBar Protection

Vk
375V @ 600A
250V @ 400A

RCT
Ie
2.4Ohms@ 600A
For 3 Feeder ( Sanya
50mA
1.6Ohms @ 400A
Grid Stn) +3 Spares

250V @ 300A
250V @ 600A

1.5Ohms@ 300A
60mA
3Ohms @ 600A

5P20
0.5FS5
5P20

Transformer feeder ( 15MVA,33/11kV)

H
A
H
E
E
T

Transformer Differential Protection

T1

Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection
Bus Section
Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection

T2

Note - Details of pilot wire protection will be provided in line with remote end data on receipt from Client

4/11/2004

CT Calculationas for 33kV Switchgear.xls

CT Details for 33kV Switchgear

Substation Remlat Al Raee


CT Data

Description

R
E
M
L
A
T
A
L
R
A
E
E

Cable Feeder
Main Protection ( Pilot Wire Diff Prot)

CT No.

Core

T1

Core 1

CT Ratio

VA

Accuracy

Core 2
Core 3
Core 4

600-1200/1A 15VA - 30VA


600-1200/1A 15VA - 30VA
2000/1A
15VA

T1

Core 1

600-1200/1A

T1

Core 2
Core 3
Core 4
Core 1

600-1200/1A 15VA - 30VA


600-1200/1A 15VA - 30VA
2000/1A
15VA
600-1200/1A 15VA - 30VA

Transformer Differential Protection

T1

Core 1

300-600/1A

Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection

T2

Core 1
Core 2
Core 1

300-600/1A
300-600/1A
2000/1A

15VA - 30VA
15VA - 30VA
15VA

5P20
0.5FS5
5P20

Core 1
Core 2
Core 1

2000/1A
2000/1A
2000/1A

15VA
15VA
15VA

5P20
0.5FS5
5P20

Protection ( O/C+E/F)
Transducers+Bay Control Unit
BusBar Protection

Vk

RCT

Ie
For 2 Feeders ( Al
Dhama Grid Stn )

Later
5P20
0.5FS5
5P20

OHL feeder

Main Protection ( Distance Prot)

Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection
SEF Protection ( Core Balance CT )

1068V @ 600A
990V @ 1200A

250V @ 300A
250V @ 600A

3Ohms @ 600A
6Ohms @1200A

60mA

5P20
Cl-0.5
5P20
5P20

Transformer feeder ( 15MVA,33/11kV)

Bus Section
Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection

T3

T2
T3

1.5Ohms@ 300A
60mA
3Ohms @ 600A

Note - Details of pilot wire protection will be provided in line with remote end data on receipt from Client

4/11/2004

CT Calculationas for 33kV Switchgear.xls

CT Details for 33kV Switchgear

Substation Falaj Al Haza


CT Data

Description

F
A
L
A
J
A
L
H
A
Z
A

Cable Feeder

CT No.

Core

CT Ratio

VA

Accuracy

Main Protection ( Pilot Wire Diff Prot)

T1

Core 1

600-300/1A

Main Protection ( Pilot Wire Diff Prot)

T1

Core 1

Protection ( O/C+E/F)
Transducers+Bay Control Unit
BusBar Protection

T2
T3

Core 1
Core 2
Core 1

600-1200/1A 15VA - 30VA


600-1200/1A 15VA - 30VA
2000/1A
15VA

Transformer Differential Protection

T1

Core 1

300-600/1A

Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection

T2

Core 1
Core 2
Core 1

300-600/1A
300-600/1A
2000/1A

15VA - 30VA
15VA - 30VA
15VA

5P20
0.5FS5
5P20

Core 1
Core 2
Core 1

2000/1A
2000/1A
2000/1A

15VA
15VA
15VA

5P20
0.5FS5
5P20

Vk
X

300V for 300A

Later

RCT

Ie

For 1 Feeder ( Zakher


3Ohms for 300A 30mA Grid Stn New Swgr) + 2
Spares
For 2 Feeder ( Zakher
Grid Stn Old Swgr) + 1
Spares

5P20
0.5FS5
5P20

Transformer feeder ( 15MVA,33/11kV)

Bus Section
Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection

T3

T2
T3

250V @ 300A
250V @ 600A

1.5Ohms@ 300A
60mA
3Ohms @ 600A

Note - Details of pilot wire protection will be provided in line with remote end data on receipt from Client

4/11/2004

CT Calculationas for 33kV Switchgear.xls

CT Details for 33kV Switchgear

Substation Al Ameria
CT Data

Description
Cable Feeder

A
L
A
M
E
R
I
A

CT No.

Core

CT Ratio

VA

Accuracy

Vk

Main Protection ( Pilot Wire Diff Prot)

T1

Core 1

Later

Main Protection ( Pilot Wire Diff Prot)

T1

Core 1

Later

Protection ( O/C+E/F)
Transducers+Bay Control Unit
BusBar Protection

T2
T3

Core 1
Core 2
Core 1

600-1200/1A 15VA - 30VA


600-1200/1A 15VA - 30VA
2000/1A
15VA

Transformer Differential Protection

T1

Core 1

300-600/1A

Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection

T2

Core 1
Core 2
Core 1

300-600/1A
300-600/1A
2000/1A

15VA - 30VA
15VA - 30VA
15VA

5P20
0.5FS5
5P20

Core 1
Core 2
Core 1

2000/1A
2000/1A
2000/1A

15VA
15VA
15VA

5P20
0.5FS5
5P20

RCT

Ie
For 2 Feeders ( Al
Dhama Grid Stn) + 1
Spare
For 2 Feeders ( Power
House Grid Stn) +
1Spare

5P20
0.5FS5
5P20

Transformer feeder ( 15MVA,33/11kV)

Bus Section
Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection

T3

T2
T3

250V @ 300A
250V @ 600A

1.5Ohms@ 300A
60mA
3Ohms @ 600A

Note - Details of pilot wire protection will be provided in line with remote end data on receipt from Client

4/11/2004

CT Calculationas for 33kV Switchgear.xls

CT Details for 33kV Switchgear

Substation New City Centre


CT Data

Description

N
E
W
C
I
T
Y
C
E
N
T
R
E

Cable Feeder

CT No.

Core

CT Ratio
600-400/1A

VA

Accuracy

Vk

700V for 600A


470V for 400A

Main Protection ( Pilot Wire Diff Prot)

T1

Core 1

Main Protection ( Pilot Wire Diff Prot)

T1

Core 1

Protection ( O/C+E/F)
Transducers+Bay Control Unit
BusBar Protection

T2
T3

Core 1
Core 2
Core 1

600-1200/1A 15VA - 30VA


600-1200/1A 15VA - 30VA
2000/1A
15VA

Transformer Differential Protection

T1

Core 1

400-600/1A

Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection

T2

Core 1
Core 2
Core 1

400-600/1A
400-600/1A
2000/1A

15VA - 30VA
15VA - 30VA
15VA

5P20
0.5FS5
5P20

Core 1
Core 2
Core 1

2000/1A
2000/1A
2000/1A

15VA
15VA
15VA

5P20
0.5FS5
5P20

RCT
Ie
Remarks
For 2 Feeders ( City
3.8Ohms for 600A
50mA Centre Grid Stn) &
2.5Ohms for 400A
Spare Feeder
For 3 Feeders ( Power

Later
House Grid Stn)
5P20
0.5FS5
5P20

Transformer feeder ( 20MVA,33/11kV)

Bus Section
Protection ( O/C+E/F)
Bay Control Unit
BusBar Protection

T3

T2
T3

250V @ 400A
250V @ 600A

1.5Ohms@ 400A
50mA
3Ohms @ 600A

Note - Details of pilot wire protection will be provided in line with remote end data on receipt from Client

4/11/2004

CT Calculationas for 33kV Switchgear.xls