TENDER NO.

G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH


ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES

Document Title : CT / VT calculations for 11kV switchgear for


ADWEA contract no G1408
TABLE OF CONTENTS
SECTION

TITLE

PAGE NO

1.0

OBJECTIVE ...................................................................................................... 3

2.0

REFERENCES .................................................................................................. 3

3.0

SCOPE .............................................................................................................. 3

4.0

CT SIZING CALCULATIONS............................................................................ 3
4.1
4.1.1
4.1.2
4.1.3
4.1.4
4.2
4.2.1
4.2.2
4.2.3
4.2.4
4.3
4.3.1
4.3.2
4.4
4.4.1
4.4.2
4.5
4.5.1
4.5.2
4.6
4.6.1
4.6.2
4.7
4.7.1
4.7.2

33/11.55kV, 15MVA Transformer Incomer Feeder........................................................ 3


CT's for Metering and Transducers .................................................................................. 3
CT's for Differential Protection & REF protection.............................................................. 4
CT for Standby Earth Fault(SBEF) protection................................................................... 7
CT's for OverCurrent and Earth Fault protection ............................................................ 10
33/11.55kV, 20MVA Transformer Incomer Feeder...................................................... 13
CT's for metering and Transducers................................................................................. 13
CT's for Differential Protection & REF protection............................................................ 14
CT for Standby Earth Fault(SBEF) protection................................................................. 17
CT's for Overcurrent and Earth fault protection .............................................................. 19
33/11.55kV, 15MVA Transformer Bus section Feeder ............................................... 22
CT's for Metering and Protection..................................................................................... 22
CT's for Transducers....................................................................................................... 24
33/11.55kV, 20MVA Transformer Bus section Feeder ............................................... 25
CT's for Metering and Protection..................................................................................... 25
CT's for Transducers....................................................................................................... 26
Outgoing 11/0.433kV, 500kVA Transformer Feeder................................................... 27
CT's for Metering and Protection..................................................................................... 27
CT's for Transducers....................................................................................................... 29
Outgoing 11kV, 5MVAr Capacitor Feeder ................................................................... 30
CT's for Metering and Protection..................................................................................... 30
CT's for Transducers....................................................................................................... 33
11kV Outgoing Feeder .................................................................................................. 34
CT's for Metering and Protection..................................................................................... 34
CT's for Transducers ....................................................................................................... 37

5.0

VT SIZING CALCULATIONS.......................................................................... 38

6.0

CONCLUSION ................................................................................................ 39

7.0

SUMMARY OF CURRENT TRANSFORMERS(Annexure-1).......................... 39

8.0

SUMMARY OF VOLTAGE TRANSFORMERS(Annexure-2).......................... 39

9.0

Relavent pages of Catalogues for Burden datas(Annexure-3) ................... 39

NOTE
Refer DTS no 0012 dated 15.11.2003 for Relay Catalogues.

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 2 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES

Document Title : CT / VT calculations for 11kV switchgear for


ADWEA contract no G1408
1.0

OBJECTIVE
To establish Current transformer(CT) and Voltage transformer parameters at 11 kV
level for all the 5 new substations.

2.0

REFERENCES
a) Bay control unit REF542 Plus catalogue
b) 11kV switchgear vendor (ABB FJH) Single line diagram no. N611844/1 to
N611844/8
c) Ducab cable catalogue
d) ESI standard 48-3 and Clients/Consultant Recommendations
e) Relay catalogues

3.0

SCOPE
To establish the requirements of CT/VT parameters such as CT/VT ratio, VA burden,
knee point voltage, accuracy class and magnetising current for CTs on the 11 kV
switchgear at all the sub-stations.

4.0

CT SIZING CALCULATIONS

4.1

33/11.55kV, 15MVA Transformer Incomer Feeder

4.1.1

CTs for Metering and Transducers


CT Ratio:
800-900 / 1A
Type of Metering:
It is proposed to use Bay Control Unit(BCU) type REF542 Plus.
Transformer full load current on secondary side ( considering tap setting at 15% )
= 15000/(3*11.55*0.85)
= 882.12 Amps
Hence it is proposed to provide 800-900 / 1A CT for metering.
Total burden of bay control unit = 0.1 VA (Refer REF542 Plus catalogue)
Maximum burden of Current Transducer
=
2 VA (Actual is 0.2VA)
Maximum burden of Power Transducer
=
2 VA
Maximum burden of Power factor Transducer
=
2 VA
The transducers are located in LDC cubicle.
Minimum length of cable
= 40 meters(As per equipment layout)
between CT and transducers

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 3 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Size of cable
Resistance of cable per
km at 20 deg C

= 4 sqmm
= 4.61 Ohms (as per Ducab cable catalogue)

Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 40 / 1000
(Lead & Return conductors) = 0.42
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.42 x 12
= 0.42 VA
Total burden = Burden of BCU+Burden of transducers+Burden due to lead resistance
= 0.1 + 6 + 0.42 = 6.52 VA
Considering 25% future margin
Total burden required

=1.25 x 6.52 = 8.15 VA

Hence a standard burden rating of 15 VA is chosen for a Tap of 800A and 30VA
chosen for a Tap of 900A.
The CT Accuracy Class selected is CL. 0.5S as per the specification requirements.
The instrument security factor (ISF) selected is less than or equal to Five(5) as per
the specification requirements.
Abstract
Therefore a CT of CL. 0.5,15VA is proposed for 800-900/1A and CL. 0.5,30VA is
proposed for 800-900/1A.The CTs are with a factor of safety less than or equal to 5.

4.1.2

CTs for Differential Protection and REF Protection:


CT Ratio:
900/1
Type of relay: RET 316*4 (ABB make)
Knee Point Voltage for Calculation for Differential Protection:
Fault current rating of 11 kV switchgear

= 31.5 kA

As per ESI Standard 48-3 enclosed the formulae for calculating Knee Point Voltage is
VK = If * N * (Rct+Rl)
Where If = fault current
N = Turns Ratio
Rct = CT secondary resistance
Rl = Lead resistance
Maximum fault current carrying capacity of 11 kV switchgear is 31.5 kA ,which can be
considered for knee point calculation.

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 4 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
If = 31500 Amps
N = 1/900
Rct = 7 (As per Manufacturers Recommendations)
The differential relay is mounted on 33kV relay panel which is located in control room.
Minimum length of cable
= 40 meters(As per equipment layout)
between CT and relay
Size of cable
= 4 sqmm
Resistance of cable per
= 4.61 Ohms (as per Ducab cable catalogue)
km at 20 deg C
Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 40 / 1000
(Lead & Return conductors) = 0.42
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.42 x 12
= 0.42 VA
Therefore, substituting the above values in the formula for Vk,
VK = 31500* (1/900) * (7 + 0.42 )
VK = 259.7V
VK > 400V
Therefore a CT of 900/1A, CL. X, VK > 400V is proposed. Imag shall be 30mA @
Vk/2
Recommendations from Consultant/Client for Differential Core requirement :
Further, to avoid mal-operation on energization of power transformer and in
connection with fault current that passes through power transformer, the rated
secondary voltage has to satisfy the following conditions:
Condition-1
The core may not saturate for current lower than 30 times the Power
Transformer rated current at connected burden. This ensures stability also
with heavy DC saturation.
Vk 30 * Int * (Rct + Rl + Rr / Ir2)
Where,
Int

Main CT secondary current corresponding to rated primary


current of power transformer

Rct

CT secondary resistance

Rl

Lead resistance

Rr

Relay burden

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 5 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Ir

Nominal relay current

Full load current of the transformer = (15000 / 1.732 * 11) = 787 Amps.
Vk 30 * (787/900) * (7+0.42 + 0.1 / 12)
Vk 187V
The knee point voltage proposed by us is 400V.
Hence this condition is Verified.
Condition-2
The core may not saturate for current lower than 4 times the maximum
through fault current at connected burden.
Vk 4 * Ift * (Rct + Rl + Rr / Ir2)
Where,
Ift

Maximum secondary side through fault current

Rct

CT secondary resistance

Rl

Lead resistance

Rr

Relay burden

Ir

Nominal relay current

Full load current of the transformer = (15000 / 1.732 * 11) = 787 Amps.
Impedance of transformer = 10%
Through fault current = 787 / 0.1 = 7870 Amps
Secondary side through fault current = 7870 / 900 = 8.75 Amps.
Hence Vk 4 * (7870/900) * (7+ 0.42 + 0.1 / 12)
Vk 263 V
The knee point voltage proposed by us is 400V.
Hence this condition is Verified.
Abstract
Therefore a CT of Vk > 400V is proposed for 900/1A.Imag shall be 30mA @ Vk/2
REF Protection Core Knee Point Calculations
CT Ratio:
900/1
Type of relay: SPAJ 115C (ABB make)
Fault current rating of 11 kV switchgear
= 31.5 kA
The REF relay is mounted on 33kV relay panel, which is located in control room.
The knee-point voltage Vk should be 2 times higher than the stabilising voltage Vs
required in through fault conditions:
Vk

2 x Vs =

Doc-No:G1408-AA-2030-J-0-101
Rev - A

2 x Ikmax x (Rct + Rl) / n


Page 6 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Where,
Vs

stabilising voltage

Ikmax

the maximum through fault current

According to ESI Standard 48, the voltage set on the relay is chosen such that the
stability of the protection during a through fault being taken as 16 times of the rated
transformer current.
Ikmax

16 x Transformer rated secondary current = 16 x 882.12 = 14114 amp

Rct

Internal resistance of the current transformer

7 ohms

Rl

total lead resistance

0.42 ohms

turns ratio of the current transformer

900

Substituting the above values in the equation the stabilising voltage,


Vs

16 x 882.12 x (7 + 0.42) / 900

116.36 Volts

Hence, Vk

2 x Vs

Vk

2 x 116.36 V =

232.72 V

The knee point voltage proposed by us is 400V.


Hence this condition is Verified.
Abstract
Since the CT Requirement of the REF and Differential Core is the same, we propose
to use a common core for both. Therefore a CT of Vk > 400V is proposed for 900/1A.
Imag shall be 30mA @ Vk/2

4.1.3

CT for Standby Earth Fault (SBEF) Protection:


CT Ratio:
800-900/1(As calculated in 4.1.1 above)
This CT is located on the transformer neutral.
Type of relay: REJ 521 (ABB make)
Fault current rating of 11kV switchgear = 31.5kA
The SBEF relay is mounted on 33kV relay panel which is located in control room.
Burden of relay = 0.1VA (As per relay catalogue)
Minimum length of cable
= 50 meters(As per equipment layout)
between CT and relay
Size of cable
= 4 sqmm
Resistance of cable per
= 4.61 Ohms (as per Ducab cable catalogue)
km at 20 deg C
Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 7 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 50 / 1000
(Lead & Return conductors) = 0.5244
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.5244 x 12
= 0.5244 VA
= Burden of the relay + Burden due to lead
resistance
= 0.1 + 0.5244

Total burden

= 0.6244 VA
Considering 25% future margin
Total burden required

=1.25 x 0.6244 = 0.78 VA

Hence a standard burden rating of 10 VA is chosen for a Tap of 800A and a burden
of 15 VA is chosen for a Tap of 900A.
The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.
For a Tap of 800A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

800A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

3Ohm (Assumed)

12 x 3

Rct

Doc-No:G1408-AA-2030-J-0-101
Rev - A

= 10 VA

Page 8 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES

Pb

3 VA

Total connected burden

Pr + PL

0.1 + 0.5244 =

0.6244 VA

10 + 3
Koalf

20 x
0.6244 + 3

=
Iscc / Ipn =
=

71
31500 / 800
40

Koalf > Iscc / Ipn


Hence the selected CT with parameters 800 900 / 1, 5P20, 10VA is adequate.
For a Tap of 900A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

900A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

4Ohm (As per Manufacturers recommendations)

12 x 4

4 VA

Total connected burden

Pr + PL

0.1 + 0.5244 =

Rct

Pb

Doc-No:G1408-AA-2030-J-0-101
Rev - A

= 15 VA

0.6244 VA
Page 9 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
15 + 4
Koalf

20 x
0.6244 + 4

=
Iscc / Ipn =
=

82.17
31500 / 900
35

Koalf > Iscc / Ipn


Hence the selected CT with parameters 800 900 / 1, 5P20, 15VA is adequate
Abstract
Therefore a CT of CL. 5P20,10VA is proposed for 800-900/1A and CL. 5P20,15VA is
proposed for 800-900/1A.

4.1.4

CTs for Overcurrent and Earth Fault Protection:


CT Ratio:
800-900/1
Type of relay: SPAJ 140C (ABB make)
Fault current rating of 11kV switchgear = 31.5kA
The relay is mounted on 11kV switchgear.
Burden of relay = 0.1VA(As per relay catalogue)
Minimum length of cable
= 5 meters
between CT and relay
Size of cable
= 2.5 sqmm
Resistance of cable per
= 7.41 Ohms (as per Ducab cable catalogue)
km at 20 deg C
Resistance of cable at
= 7.41(1+0.00393 (55-20) ) =
8.43 ohm/km
55 deg C, considering
temperature correction factor
Total resistance
= 2 x 8.43 x 5 / 1000
(Lead & Return conductors) = 0.0843
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.0843 x 12
Total burden

= 0.0843 VA
= Burden of the relay + Burden due to lead
resistance
= 0.1 + 0.0843
= 0.1843 VA

Considering 25% future margin


Total burden required

=1.25 x 0.1843 = 0.23 VA

Hence a standard burden rating of 10 VA is chosen for a Tap of 800A and a burden
of 15 VA is chosen for a Tap of 900A .
Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 10 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.
For a Tap of 800A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

800A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

3Ohm (Assumed)

12 x 3

3VA

Total connected burden

Pr + PL

0.1 + 0.0843 =

Rct

Pb

= 10 VA

0.1843 VA

15 + 3
Koalf

20 x
0.1843 + 3

=
Iscc / Ipn =
=

113
31500 / 800
40

Koalf > Iscc / Ipn


Hence the selected CT with parameters 800 900 / 1, 5P20, 10VA is adequate.

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 11 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
For a Tap of 900A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

900A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
=
Knalf x
Koalf
Pb + Pi
Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

12 x 4

4 VA

Total connected burden

Pr + PL

0.1 + 0.0843 =

Rct

Pb

= 15 VA

0.1843 VA

15 + 4
Koalf

20 x
0.1843 + 4

=
Iscc / Ipn =
=

90.81
31500 / 900
35

Koalf > Iscc / Ipn


Hence the selected CT with parameters 800 900 / 1, 5P20, 15VA is adequate.
Abstract
Therefore a CT of CL. 5P20,10VA is proposed for 800-900/1A and CL. 5P20,15VA is
proposed for 800-900/1A.

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 12 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES

4.2

33/11.55kV, 20MVA Transformer Incomer Feeder

4.2.1

CTs for Metering and Transducers


CT Ratio:
900-1200/1A
Type of Metering:
It is proposed to use Bay Control Unit(BCU) type REF542 Plus for the purpose of
metering.
Transformer full load current on secondary side ( considering tap setting at 15% )
= 20000/(3*11.55*0.85)
= 1176.16 Amps
Hence it is proposed to provide 900-1200/1A CT for metering.
Total burden of bay control unit = 0.1 VA (Refer REF542 Plus catalogue)
Maximum burden of Current Transducer
=
2 VA (Actual is 0.2VA)
Maximum burden of Power Transducer
=
2 VA
Maximum burden of Power factor Transducer
=
2 VA
The transducers are located in LDC cubicle.
Minimum length of cable
= 60 meters(As per equipment layout)
between CT and Transducer
Size of cable
= 4 sqmm
Resistance of cable per
km at 20 deg C

= 4.61 Ohms (as per Ducab cable catalogue)

Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.422 ohm/km
Total resistance
= 2 x 5.422 x 60 / 1000
(Lead & Return conductors) = 0.63
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.63 x 12
= 0.63 VA
Total burden = Burden of BCU+Burden of transducers+Burden due to lead resistance
= 0.1 + 6 + 0.63 = 6.73 VA
Considering 25% future margin
Total burden required

=1.25 x 6.73 = 8.41 VA

Hence burden of 10VA is chosen for 900A Tap and 15VA is chosen for 1200A Tap.
The instrument security factor (ISF) selected is less than or equal to 5, as per the
specification requirements.

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 13 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Abstract
Therefore a CT of CL. 0.5,10VA is proposed for 900-1200/1A and CL. 0.5,15VA is
proposed for 900-1200/1A.The CTs are with a factor of safety less than or equal to 5.

4.2.2

CTs for Differential Protection and REF Protection:


CT Ratio:
Ratio is considered as 1200/1(As calculated in 4.2.1 above)
Type of relay: RET 316*4 (ABB make)
Knee Point Voltage for Calculation for Differential Protection:
Fault current rating of 11 kV switchgear

= 31.5 kA

As per ESI Standard 48-3 enclosed the formulae for calculating Knee Point Voltage is
VK = If * N * (Rct+Rl)
Where If = fault current
N = Turns Ratio
Rct = CT secondary resistance
Rl = Lead resistance
Maximum fault current carrying capacity of 11 kV switchgear is 31.5 kA which can be
considered for knee point calculation.
If = 31500 Amps
N = 1/1200
Rct = 12 (As per manufacturers recommendations)
The differential relay is mounted on 33kV relay panel which is located in control room.
Minimum length of cable
between CT and relay
Size of cable
Resistance of cable per
km at 20 deg C

= 50 meters(As per equipment layout)


= 4 sqmm
= 4.61 Ohms (as per Ducab cable catalogue)

Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 50 / 1000
(Lead & Return conductors) = 0.5244
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.5244 x 12
= 0.5244 VA
Therefore, substituting the above values in the formula for Vk,
Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 14 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
VK = 31500* (1/1200) * (12 + 0.5244 )
VK = 329V
VK > 400V
Therefore a CT of 1200/1A, CL. X, VK > 400V is proposed. Imag shall be 30mA @
Vk/2
Recommendations from Consultant/Client for Differential Core requirement :
Further, to avoid mal-operation on energization of power transformer and in
connection with fault current that passes through power transformer, the rated
secondary voltage has to satisfy the following conditions:
Condition-1
The core may not saturate for current lower than 30 times the Power
Transformer rated current at connected burden. This ensures stability also
with heavy DC saturation.
Vk 30 * Int * (Rct + Rl + Rr / Ir2)
Where,
Int

Main CT secondary current corresponding to rated primary


current of power transformer

Rct

CT secondary resistance

Rl

Lead resistance

Rr

Relay burden

Ir

Nominal relay current

Full load current of the transformer = (20000 / 1.732 * 11) = 1050Amps.


Vk 30 * (1050/1200) * (10.5+0.5244 + 0.1 / 12)
Vk 292V
The knee point voltage proposed by us is 400V.
Hence this condition is Verified.
Condition-2
The core may not saturate for current lower than 4 times the maximum
through fault current at connected burden.
Vk 4 * Ift * (Rct + Rl + Rr / Ir2)
Where,
Ift

Maximum secondary side through fault current

Rct

CT secondary resistance

Rl

Lead resistance

Rr

Relay burden

Ir

Nominal relay current

Full load current of the transformer = (20000 / 1.732 * 11) = 1050 Amps.
Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 15 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Impedance of transformer = 10%
Through fault current = 1050 / 0.1 = 10500 Amps
Secondary side through fault current = 10500 / 1200 = 8.75 Amps.
Hence Vk 4 * (10500/1200) * (10.5+ 0.5244 + 0.1 / 12)
Vk 389 V
The knee point voltage proposed by us is 400V.
Hence this condition is Verified.
Abstract
Therefore a CT of Vk > 400V is proposed for 1200/1A.Imag shall be 30mA @ Vk/2
REF Protection Core Knee Point Calculations
CT Ratio:
1200/1
Type of relay: SPAJ 115C (ABB make)
Fault current rating of 11 kV switchgear
= 31.5 kA
The REF relay is mounted on 33kV relay panel, which is located in control room.
The knee-point voltage Vk should be 2 times higher than the stabilising voltage Vs
required in through fault conditions:
Vk

2 x Vs =

2 x Ikmax x (Rct + Rl) / n

Vs

stabilising voltage

Ikmax

the maximum through fault current

Where,

According to ESI Standard 48, the voltage set on the relay is chosen such that the
stability of the protection during a through fault being taken as 16 times of the rated
transformer current.
Ikmax

16 x Transformer rated secondary current = 16 x 1050 = 16796 amp

Rct

Internal resistance of the current transformer

10.5 ohms

Rl

total lead resistance

0.524 ohms

turns ratio of the current transformer

1200

Substituting the above values in the equation the stabilising voltage,


Vs

16 x 1050 x (10.5 + 0.5244) / 1200

154 Volts

Hence, Vk

2 x Vs

Vk

2 x 154 V

308V

The knee point voltage proposed by us is 400V.


Hence this condition is Verified.
Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 16 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Abstract
Since the CT Requirement of the REF and Differential Core is the same, we propose
to use a common core for both. Therefore a CT of Vk > 400V is proposed for
1200/1A.Imag shall be 30mA @ Vk/2 .

4.2.3

CT for Standby Earth Fault(SBEF) Protection:


CT Ratio:
Ratio is considered as 900-1200/1(As calculated in 4.2.1 above)
Type of relay: REJ 521 (ABB make)
The CT is mounted on the transformer neutral.
Fault current rating of 11kV switchgear = 31.5kA
The SBEF relay is mounted on 33kV relay panel which is located in control room.
Burden of relay = 0.1VA(As per relay catalogue)
Minimum length of cable
= 50 meters(As per equipment layout)
between CT and relay
Size of cable
= 4 sqmm
Resistance of cable per
= 4.61 Ohms (as per Ducab cable catalogue)
km at 20 deg C
Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 50 / 1000
(Lead & Return conductors) = 0.5244
Total burden
= Burden of the relay + Burden due to lead
resistance
= 0.1 + 0.5244
= 0.6244 VA
Considering 25% future margin
Total burden required

=1.25 x 0.6244 = 0.78 VA

Hence burden rating of 10 VA is chosen for 900A Tap and 15VA is chosen for 1200A.
The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.
For a Tap of 900A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

Doc-No:G1408-AA-2030-J-0-101
Rev - A

CT primary nominal current

900A
Page 17 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf

Knalf x
Pb + Pi

Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

3Ohm(Assumed)

12 x 3

3 VA

Total connected burden

Pr + PL

0.1 + 0.5244 =

Rct

Pb

= 10VA

0.6244 VA

10 + 3
Koalf

20 x
0.6244 + 3

=
Iscc / Ipn =
=

71
31500 / 900
35

Koalf > Iscc / Ipn


Hence the selected CT with parameters 900 1200 / 1, 5P20, 10VA is adequate.
For a Tap of 1200A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

Doc-No:G1408-AA-2030-J-0-101
Rev - A

1200A
31.5kA

Page 18 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

5(As confirmed by manufacturer)

12 x 5

5 VA

Total connected burden

Pr + PL

0.1 + 0.5244 =

Rct

Pb

= 15 VA

0.6244 VA

15 + 5
Koalf

20 x
0.6244 + 5

=
Iscc / Ipn =
=

71.11
31500 / 1200
26.25

Koalf > Iscc / Ipn


Hence the selected CT with parameters 900 1200 / 1, 5P20, 15VA is adequate.
Abstract
Therefore a CT of CL. 5P20,10VA is proposed for 900-1200/1A and CL. 5P20,15VA
is proposed for 900-1200/1A.
The same is as per the specification.

4.2.4

CTs for Overcurrent and Earth Fault Protection:


CT Ratio:
900-1200/1(As calculated in 4.2.1 above)
Type of relay: SPAJ 140C (ABB make)
Fault current rating of 11kV switchgear = 31.5kA
The relay is mounted on 11kV switchgear.

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 19 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Burden of relay = 0.1VA(As per relay catalogue)
Minimum length of cable
= 5 meters
between CT and relay
Size of cable
= 2.5 sqmm
Resistance of cable per
= 7.41 Ohms (as per Ducab cable catalogue)
km at 20 deg C
Resistance of cable at
= 7.41(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor

8.43 ohm/km

Total resistance
= 2 x 8.43 x 5 / 1000
(Lead & Return conductors) = 0.0843
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.0843 x 12
= 0.0843 VA
= Burden of the relay + Burden due to lead
resistance
= 0.1 + 0.0843

Total burden

= 0.1843 VA
Considering 25% future margin
Total burden required

=1.25 x 0.1843 = 0.23 VA

Hence burden rating of 10 VA is chosen for 900A Tap and 15VA is chosen for 1200A.
The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.
For a Tap of 900A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

900A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf

Knalf x
Pb + Pi

Where,
Knalf

20

Pn

Nominal CT burden

Doc-No:G1408-AA-2030-J-0-101
Rev - A

= 10VA
Page 20 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Pi

Rct

Pb

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

3Ohm(Assumed)

12 x 3

3 VA

Total connected burden

Pr + PL

0.1 + 0.0843

0.1843 VA
10 + 3

Koalf

20 x
0.1843+ 3

=
Iscc / Ipn =
=

82
31500 / 900
35

Koalf > Iscc / Ipn


Hence the selected CT with parameters 900 1200 / 1, 5P20, 10VA is adequate.
For a Tap of 1200A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

1200A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

Doc-No:G1408-AA-2030-J-0-101
Rev - A

= 15 VA

Page 21 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES

Rct

Pb

I2 * Rct

5(As confirmed by manufacturer)

12 x 5

5 VA

Total connected burden

Pr + PL

0.1 + 0.0843

0.1843 VA
15 + 5

Koalf

20 x
0.1843 + 5

=
Iscc / Ipn =
=

77.15
31500 / 1200
26.25

Koalf > Iscc / Ipn


Hence the selected CT with parameters 900 1200 / 1, 5P20, 15VA is adequate.
Abstract :
Therefore a CT of CL. 5P20, 10VA is proposed for 900-1200/1A and CL. 5P20,15VA
is proposed for 900-1200/1A.

4.3

33/11.55kV, 15MVA Transformer Bus-section Feeder

4.3.1

CTs for Metering and Protection


CT Ratio:
1600 /1A
Type of Metering and Protection:
It is proposed to use Bay Control Unit(BCU) type REF542 Plus for the same
Total burden of bay control unit = 0.1 VA(Refer REF542 Plus catalogue)
Minimum length of cable
= 5 meters
between CT and BCU
Size of cable
= 2.5 sqmm
Resistance of cable per
km at 20 deg C

= 7.41 Ohms (as per Ducab cable catalogue)

Resistance of cable at
= 7.41(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 8.43 ohm/km
Total resistance
= 2 x 8.43 x 5 / 1000
(Lead & Return conductors) = 0.0843
Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 22 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.0843 x 12
= 0.0843 VA
Total burden

= Total burden of the BCU + Burden due to lead


resistance
= 0.1 + 0.0843 = 0.1843 VA

Considering 25% future margin


Total burden required

=1.25 x 0.1843 = 0.23 VA

Hence burden rating of 15 VA is chosen.


The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.
Therefore a CT of 1600/1A, CL. 5P20, 15VA is proposed.
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

1600A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

8Ohm(As confirmed by the manufacturer)

12 x 8

8 VA

Total connected burden

Pr + PL

0.1 +0.0843

Rct

Pb

Doc-No:G1408-AA-2030-J-0-101
Rev - A

= 15 VA

Page 23 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
=

0.1843 VA
15 + 8

Koalf

20 x
0.1843 + 8

=
Iscc / Ipn =
=

56.2
31500 / 1600
19.68

Koalf > Iscc / Ipn


Abstract
Therefore a CT of CL. 5P20,15VA is proposed with for 1600/1A

4.3.2

CTs for Transducers


CT Ratio:
1600 /1A CT
Type of Metering:
We propose to use Transducers for the same
Maximum burden of current transducer = 2 VA (Actual Burden is 0.2VA only)
The transducers are located in LDC cubicle.
Minimum length of cable
= 40 meters
between CT and transducer
Size of cable
= 4 sqmm
Resistance of cable per
= 4.61 Ohms (as per Ducab cable catalogue)
km at 20 deg C
Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 40 / 1000
(Lead & Return conductors) = 0.419
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.419 x 12
= 0.419 VA
Total burden

= Total burden of the transducer + Burden due to lead


resistance
= 2 + 0.419 = 2.419 VA

Considering 25% future margin


Total burden required

=1.25 x 2.419 = 3 VA

Hence burden rating of 15 VA is chosen.


Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 24 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
The CT Accuracy Class selected is CL. 0.5 as per the specification requirements.
The instrument security factor (ISF) selected is less than or equal to Five(5) as per
the specification requirements.
Abstract
Therefore a CT of 1600/1A, CL. 0.5FS5, 15VA is proposed with factor of safety less
than or equal to 5.

4.4

33/11.55kV, 20MVA Transformer Bus-section Feeder

4.4.1

CTs for Metering and Protection


CT Ratio:
2500 /1A
Type of Metering and Protection:
It is proposed to use Bay Control Unit(BCU) type REF542
It is proposed to provide 2500/1A CT for metering and protection.
Total burden of bay control unit = 0.1 VA(Refer REF542 Plus catalogue)
Minimum length of cable
between CT and BCU
Size of cable
Resistance of cable per
km at 20 deg C

= 5 meters
= 2.5 sqmm
= 7.41 Ohms (as per Ducab cable catalogue)

Resistance of cable at
= 7.41(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 8.43 ohm/km
Total resistance
= 2 x 8.43 x 5 / 1000
(Lead & Return conductors) = 0.08429
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.0843 x 12
Total burden

= 0.0843 VA
= Total burden of the BCU + Burden due to lead
resistance
= 0.1 + 0.0843
= 0.1843 VA

Considering 25% future margin


Total burden required

=1.25 x 0.1843 = 0.23 VA

Hence burden rating of 15 VA is chosen.


The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.
Therefore a CT of 2500/1A, CL. 5P20, 15VA is proposed.
Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 25 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

2500A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

12 x 10

10 VA

Total connected burden

Pr + PL

0.1 +0.0843

Pb

= 15 VA

0.1843 VA

15 + 10
Koalf

20 x
0.1843 + 10

=
Iscc / Ipn =
=

49
31500 / 2500
12.6

Koalf > Iscc / Ipn


Abstract
Therefore a CT of CL. 5P20,15VA is proposed with for 2500/1A
4.4.2

CTs for Transducers


CT Ratio:
2500 /1A CT
Type of Metering:
We propose to use Transducers for the same

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 26 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Maximum burden of current transducer = 2 VA (Actual is 0.2VA )
The transducers are located in LDC cubicle.
Minimum length of cable
= 40 meters
between CT and transducer
Size of cable
= 4 sqmm
Resistance of cable per
km at 20 deg C

= 4.61 Ohms (as per Ducab cable catalogue)

Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 40 / 1000
(Lead & Return conductors) = 0.419
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.419 x 12
= 0.419 VA
Total burden

= Total burden of the transducer + Burden due to lead


resistance
= 2 + 0.419 = 2.419 VA

Considering 25% future margin


Total burden required

=1.25 x 2.419 = 3 VA

Hence burden rating of 15 VA is chosen.


The CT Accuracy Class selected is CL. 0.5 as per the specification requirements.
The instrument security factor (ISF) selected is less than Five(5) as per the
specification requirements.
Abstract
Therefore a CT of 2500/1A, CL. 0.5FS5, 15VA is proposed with factor of safety less
than or equal to 5.

4.5

Outgoing 11/0.433kV, 500kVA Transformer Feeder

4.5.1

CTs for Metering and Protection


CT Ratio:
30 /1A
Type of Metering and Protection:
It is proposed to use Bay Control Unit(BCU) type REF542

Transformer full load current on primary side = 500/(3*11)


= 26.24 Amps
Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 27 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Hence 30/1A CT is selected for metering and protection as per the specification
requirements.
Total burden of bay control unit = 0.1 VA(Refer REF542 Plus catalogue)
Minimum length of cable
between CT and BCU
Size of cable

= 5 meters

Resistance of cable per


km at 20 deg C

= 7.41 Ohms (as per Ducab cable catalogue)

= 2.5 sqmm

Resistance of cable at
= 7.41(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 8.43 ohm/km
Total resistance
= 2 x 8.43 x 5 / 1000
(Lead & Return conductors) = 0.0843
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.0843 x 12 = 0.0843 VA
= Total burden of the BCU + Burden due to lead
resistance
= 0.1 + 0.0843

Total burden

= 0.1843 VA
Considering 25% future margin
Total burden required

=1.25 x 0.1843 = 0.23 VA

Hence burden rating of 6 VA is chosen.


The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.
Therefore a CT of 30/1A, CL. 5P20, 6VA is proposed.
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

30A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 28 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

0.1(As confirmed by manufacturer)

12 x 0.1

0.1 VA

Total connected burden

Pr + PL

0.1 +0.0843

Rct

Pb

= 6 VA

0.1843 VA

6+ 0.1
Koalf

20 x
0.1843 + 0.1

430

Transformer Short Circuit


Transformer,

current

is limited by the 5% impedence of the

Hence,
Iscc

500/(3*110.05)

530 Amps

Iscc / Ipn =
=

530 / 30X 0.05


17

Koalf > Iscc / Ipn


Thus from the above calculations its also evident that,the actual short Circuit
withstand of the CT is 430 x 30 =12.9kA
Note: As the ratio of CT for auxiliary transformer is very low i.e 30 / 1A as per
the specification requirement, the best CT size realized to be accommodated
will be 30/1A, 5P20, 6VA with 31.5kA for 1sec short circuit level. Due to
limitation on CT dimension imposed by low CT ratio and CT short circuit
withstand capacity restricted to 31.5kA for 1 sec., We request you kind approval
for the same.
Abstract
Therefore a CT of CL. 5P20,6VA is proposed with for 30/1A
4.5.2

CTs for Transducers


CT Ratio:
30 /1A CT

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 29 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Type of Metering:
We propose to use Transducers for the same
Maximum burden of current transducer = 2 VA (Actual is 0.2VA )
The transducers are located in LDC cubicle.
Minimum length of cable
= 40 meters
between CT and transducer
Size of cable
= 4 sqmm
Resistance of cable per
= 4.61 Ohms (as per Ducab cable catalogue)
km at 20 deg C
Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 40 / 1000
(Lead & Return conductors) = 0.419
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.419 x 12
Total burden

= 0.419 VA
= Total burden of the transducer + Burden due to lead
resistance
= 2 + 0.419 = 2.419 VA

Considering 25% future margin


Total burden required

=1.25 x 2.419 = 3 VA

Hence burden rating of 7.5 VA is chosen.


The CT Accuracy Class selected is CL. 0.5 as per the specification requirements.
The instrument security factor (ISF) selected is less than or equal to Five(5) as per
the specification requirements.
Abstract
Therefore a CT of 30/1A, CL. 0.5FS5, 7.5VA is proposed with factor of safety less
than or equal to 5.

4.6

Outgoing 11kV, 5MVAr Capacitor Feeder

4.6.1

CTs for Metering and Protection


CT Ratio:
300-600 / 1A
Type of Metering and Protection:
It is proposed to use Bay Control Unit(BCU) type REF542

Capacitor full load current


Doc-No:G1408-AA-2030-J-0-101
Rev - A

MVAr / ( 3 * kV * sin )
Page 30 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
=

5000 / (3 * 11 * 0.6) =

437.38 Amps

Hence it is proposed to provide 300-600 / 1A CT for metering and protection.


Total burden of bay control unit = 0.1 VA (Refer REF542 Plus catalogue)
Minimum length of cable
between CT and BCU
Size of cable

= 5 meters

Resistance of cable per


km at 20 deg C

= 7.41 Ohms (as per Ducab cable catalogue)

= 2.5 sqmm

Resistance of cable at
= 7.41(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 8.43 ohm/km
Total resistance
= 2 x 8.43 x 5 / 1000
(Lead & Return conductors) = 0.0843
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.0843 x 12
= 0.0843 VA
Total burden

= Total burden of the BCU + Burden due to lead


resistance
= 0.1 + 0.0843
= 0.1843 VA

Considering 25% future margin


Total burden required

= 1.25 x 0.1843 = 0.23 VA

Hence burden range of 7.5VA is proposed for 300A Tap and 15VA is proposed for
600A Tap.
The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.
For a Tap of 300A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

Doc-No:G1408-AA-2030-J-0-101
Rev - A

300A
31.5kA

Page 31 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

1.5Ohm (Assumed)

12 x 1.5

1.5 VA

Total connected burden

Pr + PL

0.1 + 0.08429

Rct

Pb

= 7.5 VA

0.1843 VA

7.5 + 1.5
Koalf

20 x
0.1843 + 1.5

=
Iscc / Ipn =
=

109
31500 / 300
10.5

Koalf > Iscc / Ipn


Hence the selected CT with parameters 300-600 / 1, 5P20, 7.5VA is adequate.
For a Tap of 600A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

600A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 32 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Pn + Pi
Koalf

Knalf x
Pb + Pi

Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

3 Ohm

12 x 3

3VA

Total connected burden

Pr + PL

0.1 + 0.08429

Rct

Pb

= 15 VA

0.1843 VA

15 + 3
Koalf

20 x
0.1843 + 3

=
Iscc / Ipn =
=

113
31500 / 600
52.5

Koalf > Iscc / Ipn


Hence the selected CT with parameters 300-600 / 1, 5P20, 15VA is adequate
Abstract
Therefore a CT of CL. 5P20,7.5VA is proposed for 300-600/1A and CL. 5P20,15VA is
proposed for 300-600/1A.
The same is as per the specification.
4.6.2

CTs for Transducers


CT Ratio:
300 600 /1A
Type of Measurement:
We Propose to use Transducers form the same
Maximum burden of Current transducer = 2 VA (Actual is 0.2VA)
Maximum burden of Power factor transducer = 2 VA
Maximum burden of MVAr transducer = 2 VA

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 33 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Total burden of transducers = 6VA
The transducers are located in LDC cubicle.
Minimum length of cable
= 40 meters
between CT and transducer
Size of cable
= 4 sqmm
Resistance of cable per
km at 20 deg C

= 4.61 Ohms (as per Ducab cable catalogue)

Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 40 / 1000
(Lead & Return conductors) = 0.419
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.419 x 12
= 0.419 VA
Total burden

= Total burden of transducers + Burden due to lead


resistance
= 6 + 0.419 = 6.419 VA

Considering 25% future margin


Total burden required

=1.25 x 6.419 = 8 VA

Hence burden range of 7.5VA is proposed for 300A Tap and 15VA is proposed for
600A Tap.
The CT Accuracy Class selected is CL. 0.5 as per the specification requirements.
The instrument security factor (ISF) selected is equal to or less than Five(5) as per
the specification requirements.
Abstract
Therefore a CT of CL. 0.5,7.5VA is proposed for 300-600/1A and CL. 0.5,15VA is
proposed for 300-600/1A.The CTs are with a factor of safety less than or equal to 5.

4.7

11kV Outgoing Feeder

4.7.1

CTs for Metering and Protection


CT Ratio:
300-600 / 1A
Type of Metering and Protection:
It is proposed to use Bay Control Unit(BCU) type REF542
Total burden of bay control unit = 0.1 VA (Refer REF542 Plus catalogue)

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 34 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES

Minimum length of cable


between CT and BCU
Size of cable

= 5 meters

Resistance of cable per


km at 20 deg C

= 7.41 Ohms (as per Ducab cable catalogue)

= 2.5 sqmm

Resistance of cable at
= 7.41(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 8.43 ohm/km
Total resistance
= 2 x 8.43 x 5 / 1000
(Lead & Return conductors) = 0.0843
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.0843 x 12
= 0.0843 VA
Total burden

= Total burden of the BCU + Burden due to lead


resistance
= 0.1 + 0.0843
= 0.1843 VA

Considering 25% future margin


Total burden required

= 1.25 x 0.1843 = 0.23 VA

Hence burden range of 7.5VA is proposed for 300A Tap and 15VA is proposed
for 600A Tap.
The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.
For a Tap of 300A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

300A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Knalf

Doc-No:G1408-AA-2030-J-0-101
Rev - A

20
Page 35 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

I2 * Rct

1.5Ohm (Assumed)

12 x 1.5

1.5 VA

Total connected burden

Pr + PL

0.1 + 0.08429

Rct

Pb

= 7.5 VA

0.1843 VA

7.5 + 1.5
Koalf

20 x
0.1843 + 1.5

=
Iscc / Ipn =
=

109
31500 / 300
10.5

Koalf > Iscc / Ipn


Hence the selected CT with parameters 300-600 / 1, 5P20, 7.5VA is adequate.
For a Tap of 600A
To ensure correct operation of the connected relay in case of faults, the CT must be
able to transform the maximum symmetrical short circuit current without saturation.
To satisfy the above, following condition to be checked:
Koalf
Where,

Iscc / Ipn
Ipn

CT primary nominal current

Iscc

max. symmetrical short circuit current =

Koalf

Operating accuracy limiting factor

600A
31.5kA

The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting
factor (Knalf), the nominal CT burden (Pn), the internal CT burden (Pi) and the total
connected burden (Pb).
Pn + Pi
Koalf
=
Knalf x
Pb + Pi
Where,
Knalf

20

Pn

Nominal CT burden

Pi

Internal CT burden

V*I

(I * Rct) * I

Doc-No:G1408-AA-2030-J-0-101
Rev - A

= 15 VA

Page 36 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES

Rct

Pb

I2 * Rct

3 Ohm

12 x 3

3VA

Total connected burden

Pr + PL

0.1 + 0.08429

0.1843 VA

15 + 3
Koalf

20 x
0.1843 + 3

=
Iscc / Ipn =
=

113
31500 / 600
52.5

Koalf > Iscc / Ipn


Hence the selected CT with parameters 300-600 / 1, 5P20, 15VA is adequate
Abstract
Therefore a CT of CL. 5P20,7.5VA is proposed for 300-600/1A and CL. 5P20,15VA is
proposed for 300-600/1A.
4.7.2

CTs for Transducers


CT Ratio:
300 600 /1A
Type of Metering:
It is proposed to use Transducers.
Maximum burden of current transducer = 2 VA (Actual Burden is 0.2 only)
The transducers are located in LDC cubicle.
Minimum length of cable
= 40 meters
between CT and transducer
Size of cable
= 4 sqmm
Resistance of cable per
km at 20 deg C

= 4.61 Ohms (as per Ducab cable catalogue)

Resistance of cable at
= 4.61(1+0.00393 (55-20) )
55 deg C, considering
temperature correction factor
= 5.244 ohm/km
Total resistance
= 2 x 5.244 x 40 / 1000
(Lead & Return conductors) = 0.419
Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 37 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
Burden due to lead resistance = Total resistance x (CT secondary current)2
= 0.419 x 12
= 0.419 VA
Total burden

= Total burden of the transducer + Burden due to lead


resistance
= 2 + 0.419 = 2.419 VA

Considering 25% future margin


Total burden required

=1.25 x 2.419 = 3 VA

Hence burden range of 7.5VA is proposed for 300A Tap and 15VA is proposed for
600A Tap.
Abstract
Therefore a CT of CL. 0.5,7.5VA is proposed for 300-600/1A and CL. 0.5,15VA is
proposed for 300-600/1A.The CTs are with a factor of safety less than or equal to 5.
5.0

VT SIZING CALCULATIONS
The VTs considered are as follows:
Line VT
The devices connected on winding 1 of line VTs are BCU and Voltage Transducer
for line feeder.
The burden of the same are as given below:

BCU:
Voltage Transducers:

0.25VA
5VA max.

Total

2VA Maximum Considered


5VA Maximum Considered

7VA max.

The devices connected on winding 2 of line VTs Synchronising devices for line
feeder. As per the manufacturer the maximum burden for the same is 15VA.
Hence the VT considered for line is of following parameters.
11kV/3 / 110V/3 / 110V/3,

Winding 1
Winding 2

30VA , 0.5S
30VA , 3P

Bus VT
The devices connected on winding 1 of Bus VTs are BCU, Voltage Transducer and
Load shedding relay.
The burden of the same are as given below,

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 38 of 39

TENDER NO. G1408 FIVE (5) NEW 33/11KV PRIMARY SUBSTATIONS WITH
ASSOCIATED 33KV OVERHEAD LINES & 33KV CABLE LINES
BCU:
Voltage Transducers:
Load Shedding relay:

0.25VA
5VA max.
0.1VA max.

Total

2VA Maximum Considered


5VA Maximum Considered
2VA Maximum Considered
9VA max.

The devices connected on winding 2 of line VTs Synchronising devices for Bus
feeder. As per the manufacturer the maximum burden for the same is 15VA.
Hence the VT considered for BUS VT is of following parameters .
11kV/3 / 110V/3 / 110V/3,

6.0

Winding 1
Winding 2

30VA , 0.5S
30VA , 3P

CONCLUSION
The CT/VT parameters recommended are as calculated above. All the values at the
Usage Tap are Confirmed by the Manufacturer..

7.0

SUMMARY OF CURRENT TRANSFORMERS


The summary of the Current Transformers for all the Sub-stations is given in Annexure 1.

8.0

SUMMARY OF VOLTAGE TRANSFORMERS


The summary of the Voltage Transformers for all the Sub-stations is given in Annexure 2.

9.0

Relevant pages of Relay Catalogues


The same is made available in Annexure 3.

Doc-No:G1408-AA-2030-J-0-101
Rev - A

Page 39 of 39