Sei sulla pagina 1di 12

0

Original Issue of test protocol

09/10/2011

ISSUE

DESCRIPTION

DATE

CUSTOMER

AREVA TD

SEC REFERENCE NO.

AREVA REFERENCE NO.


DATE

SIGNATURE DOCUMENT TITLE

TEST PROCEDURE FOR ACCS

PAGES

SIZE
A4 (297 x 420 mm)

ISSUE

10

ACCS TEST PROCEDURE

LOCATION : SEP RIYADH

INDEX
Test Result

Reference

Test Objective
Failed

Date Failed

Passed

PAGE-1

Hardware component identification : C264

PAGE-2

Validate HMI (LCD Screen)

PAGE-3

Validate Control and Indication

PAGE-4

Test General Cases

PAGE-5

Test Case-1 ( BS-1 & BS-2 are in open position).

PAGE-6

Test Case-2 (BS-1 in open position &BS-2 in close position).

PAGE-7

Test Case-3 ( BS-1 in close position & BS-2 in open position).

PAGE-8

Test Case-4 ( BS-1&BS-2 are in close position ).

PAGE-9

Test Case-5 (Irrespective of Bus Sectionaliser Status ).

PAGE-10

Test Case-6 (Irrespective of Bus Sectionaliser Status ).

ACCS TEST PROCEDURE

Date
Passed

TEST PROCEDURE

PAGE 1/10

IED:

C264

APPLICATION:

ACCS

Test Objective

Hardware component identification : C264

ISSUE:

Initial conditions

Test Tools

Test conditions

Referenced Documents

As Follows

C264 Technical Manual

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Note down the serial number of C264.

=> Identify and note down the number of I/O Cards.

=> Check that each DI Card contains 16 Input channels

=> Check that each DO Card contains 10 Output channels

=> Check the presence of 17 LED indicattion lamps.

=> Check for Copper (RJ45) & Fiber Optic (ST) Ports available.

=> Check the Auxilliary power supply of C264

=> Check the Wetting voltage of Digital Input Board of C264

=> Check the front port access.

10

=>

11

=>

12

=>

13

=>

14

=>

15

=>

Comments :

Software Version :
Database version :
Automation Version :
Other Version :

Attached Documents :

Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark

TEST PROCEDURE
IED:

C264

APPLICATION:

ACCS

Test Objective

Validate HMI (LCD Screen)

PAGE 2/10

ISSUE:

Initial conditions

Test Tools

Panel Powered on

Test conditions

Referenced Documents

As Follows

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Details of Firmware and database.

=> Status (Healthy or Faulty) of DI, DO & AI cards.

=> Status (High/Low) of all DI & DO Channels

=> Reading of Analog Value (If Any)

=> Check the SLD on LHMI

=> Check the arrangement of equipments on LHMI

=>

10

=>

11

=>

12

=>

13

=>

14

=>

15

=>

=> Check the navigation buttons on front panel of C264

Navigate through the pages on LCD and find display of the following.

Comments :

Software Version :
Database version :
Automation Version :
Other Version :

Attached Documents :

Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark

TEST PROCEDURE
IED:

C264

APPLICATION:

ACCS

Test Objective

Validate control and Indication

PAGE 3/10

ISSUE:

Initial conditions

Test Tools

Panel is powered on

Test conditions

Referenced Documents

As Follows

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Download a valid database and check the LED Corresponds to "OPERATIONAL" Glows

=> When the C264 Auxilliary supply connected, check the LED Corresponds to "POWER" Glows

=> Check when the ACCS is IN SERVICE, corresponding Lamp Glows

=> Check when the ACCS is OUT OF SERVICE, corresponding Lamp Glows

=> Check when the Capacitor Connected to Bus-A is in Discharging mode, corresponding Lamp Glows

=> Check when the Capacitor Connected to Bus-B is in Discharging mode, corresponding Lamp Glows

=> Check when the Capacitor Connected to Bus-C is in Discharging mode, corresponding Lamp Glows

10

11

=>

12

=>

13

=>

14

=>

15

=>

Comments :

Software Version :
Database version :
Automation Version :
Other Version :

Attached Documents :

Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark

TEST PROCEDURE
IED:

C264

APPLICATION:

ACCS

Test Objective

To test ACCS Logic(General Test)

PAGE 4/10

ISSUE:

Initial conditions

Test Tools

C264 is powered up and connected with Simulators

Digital Simulator kit, Analog Simulation Kit

Test conditions

Referenced Documents

As Follows

ACCS Functional & Logic Description

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Check all the status information are in healthy condition

=> Check the ACCS is IN SERVICE.

=> Check the CB of the Capacitor bank once Switched OFF shall not Switch ON within 10 Minutes.

=> Check the Operation of ACCS IN/OUT or ON/OFF function works correctly.

=> Validate the reading of GT-1 Reactive power is correct

=> Validate the reading of GT-2 Reactive power is correct

=> Validate the reading of GT-3 Reactive power is correct

=> Validate the reading of Bus-A Voltage is correct

=> Validate the reading of Bus-B Voltage is correct

10

=> Validate the reading of Bus-C Voltage is correct

11

] bank trip command issued from ACCS

12

=>

13

=>

14

=>

15

=>

=> Check when the Capacitor Bank is Overloaded, (ie: Overlaod DI signal received) the respective capacitor

Comments :

Software Version :
Database version :
Automation Version :
Other Version :

Attached Documents :

Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark

TEST PROCEDURE
IED:

C264

APPLICATION:

ACCS

Test Objective

To test ACCS Logic (Test case-1)

PAGE 5/10

ISSUE:

Initial conditions

Test Tools

C264 is powered up and connected with Simulators

Digital Simulator kit, Analog Simulation Kit

Test conditions

Referenced Documents

BS-1 & BS-2 are in open position

ACCS Functional & Logic Description

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Check all the status information are in healthy condition

=> Check the ACCS is IN SERVICE.

=> Inject the Reactive Power of Transformer-1 (HV Side) above set value (MVAr-1) for t1 time duration

=> Check the Capacitor -1 is switched ON automatically

=> Inject the Reactive Power of Transformer-1 (HV Side) below set value (MVAr-2) for t2 time duration

=> Check the Capacitor -1 is switched OFF automatically

=> Inject the Reactive Power of Transformer-2 (HV Side) above set value (MVAr-1) for t1 time duration

=> Check the Capacitor -2 is switched ON automatically

=> Inject the Reactive Power of Transformer-2(HV Side) below set value (MVAr-2) for t2 time duration

10

=> Check the Capacitor -2 is switched OFF automatically

11

=> Inject the Reactive Power of Transformer-3 (HV Side) above set value (MVAr-1) for t1 time duration

12

=> Check the Capacitor -3 is switched ON automatically

13

=> Inject the Reactive Power of Transformer-3 (HV Side) below set value (MVAr-2) for t2 time duration

14

=> Check the Capacitor -3 is switched OFF automatically

15

=>

Comments :

Software Version :
Database version :
Automation Version :
Other Version :

Attached Documents :

Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark

TEST PROCEDURE
IED:

C264

APPLICATION:

ACCS

Test Objective

To test ACCS Logic (Test case-2)

PAGE 6/10

ISSUE:

Initial conditions

Test Tools

C264 is powered up and connected with Simulators

Digital Simulator kit, Analog Simulation Kit

Test conditions

Referenced Documents

BS-1 in open position &BS-2 in close position

ACCS Functional & Logic Description

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Check all the status information are in healthy condition

=> Check the ACCS is IN SERVICE.

=> Inject the Reactive Power of Transformer-1 (HV Side) above set value (MVAr-1) for t1 time duration

=> Check the Capacitor -1 is switched ON automatically

=> Inject the Reactive Power of Transformer-1 (HV Side) below set value (MVAr-2) for t2 time duration

=> Check the Capacitor -1 is switched OFF automatically

] for t3 time duration

] t4 time duration

10

11

] t5 time duration

12

13

] t6 time duration

14

=> Check the Capacitor -3 is switched OFF automatically

15

=>

=> Inject the Reactive Power of Transformer-2 & Transformer-3 combinely to come above set value (MVAr-3)

=> Check the Capacitor -2 is switched ON automatically


=> Inject the Reactive Power of Transformer-2&Transformer-3 combinely to come below set value (MVAr-4) for

=> Check the Capacitor -2 is switched OFF automatically


=> Inject the Reactive Power of Transformer-2&Transformer-3 combinely to come above set value (MVAr-5) for

=> Check the Capacitor -3 is switched ON automatically


=> Inject the Reactive Power of Transformer-2&Transformer-3 combinely to come below set value (MVAr-6) for

Comments :

Software Version :
Database version :
Automation Version :
Other Version :
Notes:

System Allows to Switch ON the Capacitor Bank

Attached Documents :

10 Minutes After Swich OFF


Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark

TEST PROCEDURE
IED:

C264

APPLICATION:

ACCS

Test Objective

To test ACCS Logic (Test case-3)

PAGE 7/10

ISSUE:

Initial conditions

Test Tools

C264 is powered up and connected with Simulators

Digital Simulator kit, Analog Simulation Kit

Test conditions

Referenced Documents

BS-1 in close position & BS-2 in open position

ACCS Functional & Logic Description

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Check all the status information are in healthy condition

=> Check the ACCS is IN SERVICE.

] for t3 time duration

] t4 time duration

] for t5 time duration

] t6 time duration

10

=> Check the Capacitor -2 is switched OFF automatically

11

=> Inject the Reactive Power of Transformer-3 above set value (MVAr-1) for t1 time duration

12

=> Check the Capacitor -3 is switched ON automatically

13

=> Inject the Reactive Power of Transformer-3 below set value (MVAr-2) for t2 time duration

14

=> Check the Capacitor -3 is switched OFF automatically

15

=>

=> Inject the Reactive Power of Transformer-1 & Transformer-2 combinely to come above set value (MVAr-3)

=> Check the Capacitor -1 is switched ON automatically


=> Inject the Reactive Power of Transformer-1&Transformer-2 combinely to come below set value (MVAr-4) for

=> Check the Capacitor -1 is switched OFF automatically


=> Inject the Reactive Power of Transformer-1 & Transformer-2 combinely to come above set value (MVAr-5)

=> Check the Capacitor -2 is switched ON automatically


=> Inject the Reactive Power of Transformer-1&Transformer-2 combinely to come below set value (MVAr-6) for

Comments :

Software Version :
Database version :
Automation Version :
Other Version :
Notes:

System Allows to Switch ON the Capacitor Bank

Attached Documents :

10 Minutes After Swich OFF


Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark

TEST PROCEDURE
IED:

C264

APPLICATION:

ACCS

Test Objective

To test ACCS Logic (Test case-4)

PAGE 8/10

ISSUE:

Initial conditions

Test Tools

C264 is powered up and connected with Simulators

Digital Simulator kit, Analog Simulation Kit

Test conditions

Referenced Documents

BS-1&BS-2 are in close position

ACCS Functional & Logic Description

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Check all the status information are in healthy condition

=> Check the ACCS is IN SERVICE.

] value (MVAr-3) for t3 time duration

] value (MVAr-4) for t4 time duration

] value (MVAr-5) for t5 time duration

] value (MVAr-6) for t6 time duration

10

11

] value (MVAr-7) for t7 time duration

12

13

] value (MVAr-8) for t8 time duration

14

=> Check the Capacitor -3 is switched OFF automatically

15

=>

=> Inject the Reactive Power of Transformer-1, Transformer-2& Transformer-3 combinely to come above set

=> Check the Capacitor -1 is switched ON automatically


=> Inject the Reactive Power of Transformer-1, Transformer-2 & Transformer-3 combinely to come below set

=> Check the Capacitor -1 is switched OFF automatically


=> Inject the Reactive Power of Transformer-1 , Transformer-2 & Transformer-3 combinely to come above set

=> Check the Capacitor -2 is switched ON automatically


=> Inject the Reactive Power of Transformer-1 , Transformer-2 & Transformer-3 combinely to come below set

=> Check the Capacitor -2 is switched OFF automatically


=> Inject the Reactive Power of Transformer-1 , Transformer-2 & Transformer-3 combinely to come above set

=> Check the Capacitor -3 is switched ON automatically


=> Inject the Reactive Power of Transformer-1 , Transformer-2 & Transformer-3 combinely to come below set

Comments :

Software Version :
Database version :
Automation Version :
Other Version :
Notes:

System Allows to Switch ON the Capacitor Bank

Attached Documents :

10 Minutes After Swich OFF


Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark

TEST PROCEDURE
IED:

C264

APPLICATION:

ACCS

Test Objective

To test ACCS Logic (Test case-5)

PAGE 9/10

ISSUE:

Initial conditions

Test Tools

C264 is powered up and connected with Simulators

Digital Simulator kit, Analog Simulation Kit

Test conditions

Referenced Documents

Irresctive of Bus Sectionalizer (BS) Status. Capacitor Banks are ON

ACCS Functional & Logic Description

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Check all the status information are in healthy condition

=> Check the ACCS is IN SERVICE.

=> Inject the Voltage to Bus Section-A (13.8kV Side) above set value (V-1) for t9 time duration

=> Check the Capacitor -1 is switched OFF automatically

=> Check if the Over Voltage Switch OFF Condition Supersedes Conditions of CASE-1 to CASE-4

=> Inject the Voltage to Bus Section-B (13.8kV Side) above set value (V-1) for t9 time duration

=> Check the Capacitor -2 is switched OFF automatically

=> Check if the Over Voltage Switch OFF Condition Supersedes Conditions of CASE-1 to CASE-4

=> Inject the Voltage to Bus Section-C (13.8kV Side) above set value (V-1) for t9 time duration

10

=> Check the Capacitor -3 is switched OFF automatically

11

=> Check if the Over Voltage Switch OFF Condition Supersedes Conditions of CASE-1 to CASE-4

12

=>

13

=>

14

=>

15

=>

Comments :

Software Version :
Database version :
Automation Version :
Other Version :
Notes:

System Allows to Switch ON the Capacitor Bank

Attached Documents :

10 Minutes After Swich OFF


Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark

TEST PROCEDURE
IED:

C264

APPLICATION:

ACCS

Test Objective

To test ACCS Logic (Test case-6)

PAGE 10/10

ISSUE:

Initial conditions

Test Tools

C264 is powered up and connected with Simulators

Digital Simulator kit, Analog Simulation Kit

Test conditions

Referenced Documents

Irresctive of Bus Sectionalizer (BS) Status. Capacitor Banks are OFF

ACCS Functional & Logic Description

Pa
ss
ed

Actions

N
o
Te t
st
ed
Fa
ile
d

Result:

=> Check all the status information are in healthy condition

=> Check the ACCS is IN SERVICE.

=> Inject the Voltage to Bus Section-A (13.8kV Side) below set value (V-2) for t-10 time duration

=> Check the Capacitor -1 is switched ON automatically

=> Inject the Voltage to Bus Section-B (13.8kV Side) below set value (V-2) for t-10 time duration

=> Check the Capacitor -2 is switched ON automatically

=> Inject the Voltage to Bus Section-C (13.8kV Side) below set value (V-2) for t-10 time duration

=> Check the Capacitor -3 is switched ON automatically

=> Check if the Under Voltage Switch ON Condition Supersedes Conditions of CASE-1 to CASE-4

10

=>

11

=>

12

=>

13

=>

14

=>

15

=>

Comments :

Software Version :
Database version :
Automation Version :
Other Version :
Notes:

System Allows to Switch ON the Capacitor Bank

Attached Documents :

10 Minutes After Swich OFF


Overall Decision :
: Passed

TESTED BY

WITNESSED BY

Name / Visa

Name / Visa

Date :

Date :

: Not Completed
: Failed
ACCS TEST PROCEDURE

Remark