SECTION C
PART 2
PROJECT SPECIFICATION
3.1.5
ALUMINUM SCREEN
Provide screens fabricated from cast aluminum elements. Pattern shall be as
indicated on drawings and approved by Engineer. Screen panels shall be operable
where indiacted. Hardware shall be able to sustain load of panels without failure.
__________________________________________________________________________________________
Construction of Two Health Care Centers at Al Karaana and Al Ghuwairiya (Package 1)
BA 12/13 C 007 G
C2/PS/102
August 2012
TECHNICAL SUBMISSION
SECTION C
PART 2
PROJECT SPECIFICATION
3.1.6
SKYLIGHT
Skylight comprising double glazing with aluminium framing with PVDF finish.
Aluminium Members: provide thermal break aluminium members of the alloy and
temper recommended by the manufacturer to satisfy requirements for strength,
corrosion resistance and application of finish indicated. Comply with requirements
of ASTM B 221M for extrusions, ASTM B 209M for aluminium sheet or plate, and
ASTM B 211M for aluminium bars, rods and wire:
Principal framing members: provide extruded aluminium members of 6063-T5
alloy and temper with a minimum thickness of 3 mm.
Trim members: provide extruded aluminium glazing caps and other
miscellaneous non-supporting trim members of 6063-T5 alloy and temper with
minimum thickness of 1.5 mm.
Formed metal members shall be sheet aluminium of 6061-T6 alloy and temper
with a minimum thickness of 3 mm for structural members and 1.5 mm for
closures and trim.
Provide aluminium skylight with a U-value maximum of 1.8 W/m2 K at 24 km/h
exterior wind velocity and a condensation resistance factor (CRF) of 45 when tested
according to AAMA 1503.1.
Gaskets and Joint Fillers: provide manufacturer's standard permanent-type framing
system gaskets and joint fillers for sliding joints, compression joint translation, or
non-moving joints depending on joint movement and sealing requirements.
Provide shop drawings of fully assembled skylight, showing adjacent aluminium
rain water gutters sloping to roof, all fixing, waterproofing and integration of
gutters with skylight curb details.
3.5.2
3.5.2.11. STEEL DOOR FRAMES to the general requirements of BS 1245, but to nonstandard sizes and profiles, constructed from not less than 1.2 mm thick galvanized
steel sheet, finished with factory applied corrosion inhibiting protective coating and
supplied complete with transoms, rubber silencers and glazing beads, as shown on
the Drawings.