Sei sulla pagina 1di 8

Calculation of Pump (Suction Head Case)

HSD

Fluid
Suction Side
LINE SIZE
Suction Line Length
Fluid Density

Specific Gravity
Atm Pressure
hatm
Atm Head
Vap Pressure
hvap
Vap Press Head
helev
Elevation Head
Velocity
hv
Velocity Head
Friction
str.run+fittings+strainer+1/2 of velocity head
hf
Friction Head
hatm-hvap+helev-hf
NPSHA
=
NPSHA(@ suction head case when pumps are at ground.
-31.05
RESULT
-26.4

16
4083.6
850
52.99
0.85
14.70
39.95
7.1
19.30
6.56
5.8
0.52

in
ft
kg/m3
lb/ft3

58.26

ft

psia
ft of oil
psia
ft of oil
ft
ft/sec
ft

ft of oil
ft of water

NPSHA CALCULATION OF HSD Pump Feed PUMP


NPSHA = Absolute press + Elevation - Friction losses- Vapour press
2
Pressure Drop Due to Friction2f(L/D)(V /gc)

Flow
Specific Gravity
Density
Viscosity
Total Length equivalent
Diameter of Pipe
Area of Pipe

Velocity
Reynold's No.
Friction Factor
P
P

BBLS/DAY
Tons/day
lb/ft3
lb/ft-sec
ft
in
ft
ft2
m2
m3/sec
m/sec
ft/sec
Dimensionless
f
lb/ft2
lb/in2 a

Suction line
28-inch Pipe
124276.666666667
16792.8
0.85
53.04
0.048
4083.6
16
1.3
1.40
0.13
0.2287
1.8
5.8
8512
0.008
Selected formula from Mccabe
2799.880
19.44

Strainer drop
Friction Loss
Head loss

0.26

Total Elevation

2m
6.56 ft

Case)

Strainer drop
Friction Loss
Head loss

1.9 psi
19.44 psi
52.841 ft

(half of velocity head)

psia

5.16 ft
(from Manual cal)

CASE-1
LINE SIZE
Suction Line Length
Fluid Density

Specific Gravity
Atm Pressure
Atm Head
Vap Pressure
Vap Press Head
Elevation Head
Velocity
Velocity Head
Friction
str.run+fittings+strainer+1/2 of ve
Friction Head
NPSHA
=
NPSHA
RESULT
CASE-2
LINE SIZE
Suction Line Length
Fluid Density

Specific Gravity
Atm Pressure
Atm Head
Vap Pressure
Vap Press Head
Elevation Head
Velocity
Velocity Head
Friction
str.run+fittings+strainer+1/2 of ve
Friction Head
NPSHA
=
NPSHA
RESULT
CASE-3
Suction Side
LINE SIZE
Suction Line Length
Fluid Density

Specific Gravity
Atm Pressure
Atm Head
Vap Pressure
Vap Press Head
Elevation Head
Velocity
Velocity Head
Friction
str.run+fittings+strainer+1/2 of ve
Friction Head
NPSHA
=
NPSHA(@ suction head case when pumps ar
RESULT

CASE-1

20 in
1361.2 ft
850 kg/m3
52.99 lb/ft3
0.85
14.70 psia
hatm
39.95 ft of oil
7.1 psia
hvap
19.30 ft of oil
helev
6.56 ft
3.7 ft/sec
hv
0.21 ft
tr.run+fittings+strainer+1/2 of velocity head
hf
23.65 ft
hatm-hvap+helev-hf
3.56 ft of oil
3.0 ft of water
CASE-2
24 in
4083.6 ft
850 kg/m3
52.99 lb/ft3
0.85
14.70 psia
hatm
39.95 ft of oil
7.1 psia
hvap
19.30 ft of oil
helev
6.56 ft
2.6 ft/sec
hv
0.10 ft
tr.run+fittings+strainer+1/2 of velocity head
hf
12.97 ft
hatm-hvap+helev-hf
14.24 ft of oil
12.1 ft of water
CASE-3
16
4083.6
850
52.99

hatm
hvap
helev

0.85
14.70
39.95
7.1
19.30
6.56
5.8
0.52

hv
tr.run+fittings+strainer+1/2 of velocity head
hf
58.26
hatm-hvap+helev-hf
on head case when pumps ar -31.05 ft of oil
-26.4 ft of water

Byco Oil Pakistan Ltd


Mouza Kund, Hub

DATA SHEET FOR


MOTOR DRIVEN COOLING
WATER PUMP

DATA SHEET NO.BOPL-CWP-DS-01


SHEET NO.
1 OF 1
DATE 16/01/2014
Rev.
01
PREPARED BY OHS
CHECKED BY
MS
APPROVED BY RZ

1 COOLING WATER PUMP


2 Items
Units Requirement
Offer
3 Tag Number
21G-103 A/B
4 Quantity Required
No.
2
5 VENDOR INFORMATION
6 Type
CENTRIFUGAL/Motor Driven
7 Make
Any wellknown OEM
8 Model
VTA
9 OPERATING CONDITION
10 Ambient Temperature
C
0-45
11 Fluid
cooling water/Sea Water
12 Fluid Temperature
C
25-40 0C
13 Humidity
%
20-100
14 Fluid pH Range
pH
7-9
15 Fluid Specific Density
kg/m3 995 (Approx)
16 Total Suspended Solids
mg/L
17 PERFORMANCE
18 Flow rate
m3/hr 600
19 Discharge Pressure
psig 74 psig
20 Pump Curve
VTC
21 Approximate NSPHa
ft
10
22 NPSHr
ft
VTA
23 Hydraulic Power Required
KW
85
24 Mounting
VTC
25 Priming
VTC
26 MOTOR SPECIFICATION
27 Volts/Frequency/Phase
415/50/3
28 Type
IP-55
29 Condensation Heater
Required
30 DIMENSIONS
31 Suction Size
inch
12" (VTC)
32 Suction Connection
FLANGE
33 Discharge Size
inch
12" (VTC)
34 Discharge Connection
FLANGE (VTC)
35 Overall Height
mm
VTA
36 Overall Width
mm
VTA
37 Overall Length
mm
VTA
38 Impeller / Diaphragm
mm VTA
39 MATERIALS
40 Body
Casing in Bronze
41 Shaft
Stainless Steel
42 Impeller / Diaphragm
Ni.Al.Br
43 WEIGHTS
44 Total Weight (dry)
kg
VTA
45 OPERATIONAL NOISE
46 Sound Power Level
dba
< 85
Note:
1 Pump shall be able to withstand a closed valve / no flow head.
2 Pump and all the associated auxilliaries to fully comply with API-610 11th Edition.
3 Adequate pump motor as per power requirement to be supplied by vendor

4
5
6
7

Pump efficiency shall not be less than 75%


All relevant documents, drawing and O&M manual should be provided alongwith pump.
VTA = Vendor to advice
VTC = Vendor to confirm