FIRE PUMPS
Item
Provision
FSS No:
6.7
Notes
Definitions
Certification
QCD
Approved
1.0
Fire pumps must be provided for all buildings and structures where Application
fire fighting systems are required and installed to ensure adequate
flows of water at the minimum required pressures are maintained
for the duration of the fire fighting operations.
2.0
3.0
All equipment comprising the fire pump set including but not
limited to pump, motor, engine, controller, pressure relief valves,
suction valves, discharge valves, check valves, pipe supports and
hangar, etc., must be listed for their intended use by a 3rd party
certification body acceptable to the QCD.
All equipment associated with pump installations must be
submitted for QCD approval.
Current acceptable 3rd party certifiers are:
Underwriters Laboratories, (UL)
FM Global
LPCB
Page 1 of 2
23-Jun-09
FIRE PUMPS
Item
Provision
FSS No:
6.7
Notes
VdS
Other 3rd party certifiers not listed above may be submitted for
consideration. Complete credentials and accreditation in English
must be included in any submission for review by the QCD.
4.0
5.0
A listed approved flow meter must be provided for each fire pump
installation. The flow meter must be installed in accordance with
the manufacturer's recommendations and within the listing
limitations.
Flow meter
7.0
Fire pumps must be enclosed in their own dedicated pump room. Fire pump room
The fire pumps' room enclosure must have a 2 hour fire resistance
rating.
8.0
Ventilation
9.0
Safe direct access from outside the building must be provided for
the fire pump room. The location of the fire pump room must be
agreed with the QCD at DC1 stage.
Access
Pumps
performance
curves