Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
A domain of expertise
With a complete range of equipment and a leading expertise in
DC traction power substations, Scheron SA is a world leader
and major partner for electrification of DC traction networks.
Covering all activities from calculation, network design and
engineering, up to the production of the DC Systems, Scheron
SA can offer customers and partners tailor made solutions
based on a modular concept and standard products.
Our equipment is developed on world leading technology
and proven worldwide design and acceptance. In-house
technology covers all key devices applied in the DC Systems
(Rectifiers, DC HSCB, Disconnect Switches, Protection Relays,
Measuring Amplifiers, etc.).
Main features
Rated current up to 2400 A (main circuit)
Rated voltage up to 900 VDC
Metal enclosed switchgear compartment equipped with high-speed
circuit-breaker
New features:
Description
The metal enclosed compartmented DC switchgear type SECUB-2 integrates three separated compartments for high and low
voltage equipment:
Service
Test
Disconnected
Removed
It is possible to see the physical state of the HSCB (opened or closed) as well as the drawer position (service, test or disconnected)
through a window located on the front door. A counter showing the number of HSCB operations is also visible through this window.
The drawer also contains a measuring shunt. The isolated amplifiers for current (MIU10) and voltage (VM10) measurement as well
as the line test components are mounted on a retractable plate located below the drawer.
With the plate removed, the power cable connection compartment is easily accessible inside the cubicle. This feature makes the
installation against the wall possible.
This compartment is separated from the busbar compartment thanks to isolating shutters.
Rear high voltage busbar compartment
The busbar rear compartment is composed of two main parts:
Unit
Cubicle type
SECUB-2 UR15
SECUB-2 UR26
INe
[A]
1500 A
2600 A
Rated voltage
UNe
[VDC]
900
900
Unm
[VDC]
1800
1800
Nominal voltage
Un
[VDC]
600/750
600/750
Ua
[kV]
INss/Nss
[A]
2400
2400/4000*
[kA]
12/18
100/150
IP30
[C]
[kg]
[mm]
-5 ... +40
330
350
450x1400x2200
*4000 A: option.
**IP32 / IP42: option.
Designed according to standard specifications EN50123 and IEC61992.
Composition
Unique feature:
Key components of the switchgear are designed and manufactured by Scheron and are fully compatible.
SEPCOS
Protection relay
SWS18.20
Disconnecting Switch
SEPCOS
Touch-screen display
VM10
Isolated amplifier for
Voltage Measurement
UR26.81S
High-speed circuit breaker
4
MIU10
Isolated amplifier for
Current Measurement
Main dimensions
450
1. Circuit-breaker
breaker drawer
325
100
2. Withdrawable
1400
1075
3. Low-voltage
compartment
(protection and
control circuits)
10
circuit)
5. Shunt (current)
amplifier
11
2200
6. Current measuring
7. Voltage measuring
amplifier
12
8. Busbar
1430
compartment
9. Output cable
11. Disconnecting
Switch (option)
MAIN BUSBAR
MAIN BUSBAR
MAIN BUSBAR
1. Line feeder
2. Line feeder with
SEPCOS
MIU10
VM10
SEPCOS
I>
I
MIU10
4. Rectifier breaker
SEPCOS
I>
Line Test
Line Test
I>
Line Test
isolating switch
I
MIU10
VM10
VM10
bypass
MAIN BUSBAR
MAIN BUSBAR
BY-PASS BUSBAR
SEPCOS
SEPCOS
I>
Line Test
I>
I
MIU10
I
MIU10
M
U
VM10
RC Filter
Combined with
base-load resistor
MIU 10 / VM 10/12
Isolated amplifiers for current
and voltage measurement
SWS / SWG
Bipolar off-load motorized
disconnecting switch with
optional earthing connection
IPT
Optional interphase coil
for connection with
coupled rectifier transformers
Side view of Rectifier+AIS cubicle (right side)
Technical data:
Rated service current
Rated power
Rated voltage
Rated insulation voltage
Nominal voltage
Power frequency withstand voltage
Output signal
Connection scheme
Protection degree (basic)
Ambient temperature range
Typical weight (without disconnector)
Dimensions (WxDxH)
Cooling
Symbol
INe
P
UNe
Unm
Un
Ua
Unit
[A]
[W]
[VDC]
[VDC]
[VDC]
[kV]
[C]
[kg]
[mm]
Up to 1600 A
Up to 1200 kW
900
1800
600/750
6.9 kV, 50 Hz, 1min
6 or 12 pulses
1 or 2 Graetz bridges in parallel
IP20
-5 ... +40
950
1600x1400x2200
Natural Air
7
Standards
The SECUB-2 has been successfully type tested at IPH laboratory in Berlin.
According to standards:
IEC61992-2:2006
EN50123-2:2003
Approved type test reports available.
Main features related to SECUB-2 breaker cubicle
SG820794BEN_C00-09.14
Scheron SA
Rue du Pr-Bouvier 25
1217 Meyrin - Geneva
CH-Switzerland
900 VDC
1800 VDC
2600 A
100/150 kA
31.5 ms
f, e, d
This document is not contractual and contains information corresponding to the level of technology at the date of printing. Scheron reserves the right to modify and/or improve the product, whose
characteristics are described in these documents, as required by new technology at any time. It is the purchasers responsibility to inform himself, no matter what the circumstances, of the products
maintenance conditions and requirements. Scheron reserves all rights, especially those arising from our General Delivery Conditions.
Copyright 2007 Scheron SA