Quiz # 4
Open Book
1. The first course of an aboveground storage tank is fabricated of 7/8 material, the tank
has been in-service for 14 years. Current thickness measurements reveal the general
condition of the shell plate to be corroded to an average thickness of .643. The
calculated minimum required design thickness is .402. What is the remaining life
expectancy of this tank based on the first course information?
a)
b)
c)
d)
2. What is the maximum permissible weld reinforcement for a vertical joint in plate
thickness 1.25?
a) 3/16th inch
b) 1/8th inch
c) 1/4th inch
d) 3/32nd inch
3. A repair organization has a WPS, which states it is qualified for P-8 to P-8 material
welded, with either E308, E309, or E316 electrodes (SMAW process). The PQR
supporting this WPS states the weld test coupons were SA-240 Type 304L material,
welded with E308 electrodes. Is the WPS properly qualified for the base material listed?
a) No SA-240 Type 304L is not P-8 Material
b) Yes - SA-240 Type 304L is P-8 Material
c) No E308 electrodes may not be used to weld SA-240 Type 304L material
d) Yes the WPS is qualified because the type of electrode is not an essential variable
4. During the filling of a new aboveground storage tank for initial testing, leakage was
observed in a horizontal seam. Repairs are to be completed with the test water in the tank.
The tank is 61 feet high and the leak is discovered 29 feet below the top of the tank.
Where must the water level be during the repair?
a) The water level shall be not more than 31 feet from the bottom of the tank
b) The water level shall be not less than 26 feet from the top of the tank
c) The water level shall be at the maximum design liquid level
d) The water shall be removed from the tank
5. An NPS 12 nozzle is to be installed in an existing 96 feet diameter AST. The shell course
thickness is .625 and the reinforcement plate thickness is .75. What minimum size of
nozzle-to-reinforcing plate fillet weld is required to comply with API-650?
a)
b)
c)
d)
.3125
.4375
.5625
.6250
2007
(610) 594-9036
Annually
Every five years
Monthly
Periodically
5. All tanks shall be given a visual external inspection, by an Authorized Inspector, at what
frequency?
a) Inspection conducted at least every 20 years or at the quarter corrosion rate of the
bottom whichever is less
b) Inspection conducted at least every 5 years or at the quarter corrosion rate of the
bottom whichever is less
c) Inspection conducted at least every 5 years or at the quarter corrosion rate of the shell
whichever is less
d) Inspection conducted at least every 20 years or at the quarter corrosion rate of the
shell whichever is less