Sei sulla pagina 1di 5

Marble River

Relay Settings Basis


For The

MARBLE RIVER WIND PROJECT

May 21, 2012

Prepared For

MARBLE RIVER, LLC


Revision
0
1
2

Date
3/29/12
4/16/12
5/21/12

By
JK
JK
JK

Approved By
LAM
RJ
JK

Marble River Settings Basis

1. INTRODUCTION

The Marble River collector substation is being constructed for the Horizon Wind Energy
Marble River Wind Farm which consists of 73 wind turbine generators (WTGs) each with a
nominal rating of 3.0MW for a total generation capacity of 219MW. TRC is providing
protective relay settings for the collector substation. Guidance for the protective relay
settings, substation control and automation, as well as arc flash studies are provided by
POWER Engineers, Inc. This document provides the criteria used by TRC to complete the
relay settings.

Figure 1: System Overview Diagram

05/21/12

Rev. 2

Marble River Settings Basis

2.

CRITICAL NOTES AND ASSUMPTIONS

2.1

POWER Engineers supplied a settings guide, Marble River Protective Relaying


Functional Descriptions Revision 0, which was used where applicable in the
completion of the collection system relay settings. This document is located in the
Appendix for reference.

2.2

All impedance and short circuit contribution information in the supplied short circuit
model used for calculating relay settings is based on Horizon/EDPR information supplied
to the date of this document. All calculations for the system short circuit model are
located in the Appendix for reference.

2.3

Proper coordination of protective devices may not have been achieved to be able to
protect collector substation equipment. These instances are documented in the settings
calculations.

2.4

All protective equipment for T2 and the 230kV system are located in the point of
interconnection station operated by NYPA, Patnode Substation, and are excluded from
this document. Overcurrent protection is provided by the following relays to the 34.5kV
collector substation: 87TBP/T2, 87TP/T2 & 87TS/T2.

2.5

Capacitor Banks C1-C3 have been removed from the design of the collector substation
and therefore no documentation of protective devices is provided.

3.

PROTECTION OVERVIEW

3.1

The following table lists the protective devices covered by this document. The name,
model, brief description, and protective functions are provided. Refer to relay
calculations section for more detailed information.

Relay
50/62BF/T2MR

Relay Type
SEL-351S

Relay Description
34.5kV Main Breaker Failure

Protective
Elements
50FD

Element Function
Breaker failure fault
detector

05/21/12

Rev. 2

Marble River Settings Basis

87B/34.5

SEL-587Z

34.5kV Bus Differential

62BF

Breaker failure timer

27

230kV UV Trip

87

High impedance bus


differential

50/51/F1-F8

SEL351S

Collector Overcurrent

50FD

Breaker failure fault


detector

62BF

Breaker failure timer

59

Over voltage

81U/O

U/O Frequency

67P

Phase DTOC

51P

Phase TOC

51G

Gnd TOC

50P

Phase IOC

50G

Gnd IOC

51G-2

Gnd high set TOC

50GDT

Gnd Definite TOC

Table 1: Protective Device Overview

3.2

The following table lists the lock out relays covered by this document. The name and
description of operation are provided.

Lockout Relay
86BF/T2MR

Function
T2MR Breaker

Tripped By

Trips

50/62BF/T2MR

Failure Lockout

05/21/12

Blocks

F1

F1

F2

F2

F3

F3

F4

F4

F5

F5

F6

F6

F7

F7

F8

F8

2102-TC1

2102-TC1

2102-TC2

2102-TC2

2114-TC1

2114-TC1

2114-TC2

2114-TC2

Comments

Rev. 2

Marble River Settings Basis

86B/34.5

34.5kV Bus

87B/34.5

F1

F1

Trip by feeder

Differential

50/51/F1

F2

F2

breaker is for BF

Lockout

50/51/F2

F3

F3

function only.

50/51/F3

F4

F4

50/51/F4

F5

F5

50/51/F5

F6

F6

50/51/F6

F7

F7

50/51/F7

F8

F8

50/51/F8

T2MR

T2MR

SHORT 587Z

Table 2: Lock Out Relay Overview

3.3

The following table summarizes the primary and backup protection elements by zone of
protection.

Zone of
Protection
34.5kV Bus

Primary Protection

Back Up Protection

Relay

Relay

Trips

(Element)
87B/34.5

86B/34.5

(87)

(Element)
87TBP/T2

Trips
86TBP/T2

(51H)

Comments

All back up equipment is


located in NYPA Patnode
Control Building.

87TP/T2

86TP/T2

(51H, 51L,

Back up protection lock out

51LN)

relay will isolate T2.

87TS/T2

86TS/T2

(51H, 51L,
51LN,
51N)
F1

50/51F1

F1

87TP/T2

86TP/T2

(67P, 51P,

(51L,

located in NYPA Patnode

51G, 50P,

51LN)

Control Building.

50G, 51G2, 50GDT)

05/21/12

All back up equipment is

Back up protection lock out


87TS/T2

86TS/T2

relay will isolate T2.