DC 1010 / 1020
1030 / 1040
DIGITAL CONTROLLER
PRODUCT MANUAL
51-52-25-113
06/02
Before using this manual, please check to ensure the Model number, input type
Range and output match your requirements.
1.
1.1
Display
1.2
1.3
PV
SP
LED Indicators
OUT1
OUT2
AT
PRO
AL1
AL2
MAN
Keys
SET
A/M
:Auto/Manual key
2.
Auto Tuning
2.1
2.2
2.3
ATVL = auto tuning offset, the off set value when entered will be calculated
and subtracted from the SP.
(It prevents over-shooting during auto tuning)
SP-ATVL = Auto-tuning value, ATVL = Auto tuning offset
Ex.) SP = 200C, ATVL = 5, Auto tuning point is at 195C
* ATVL means auto-tuning point (195C) in the above example.
2.4
3.
Error Information
Open circuit sensor input 1
RAM failed
Interface failed
Auto tuning failed
4.
Operating Flow
4.1
Level 1
Display PV
PV
Display SP
SP
SET
Output
Press SET key
for 5 sec
Percentage
SET
Auto Tuning
Status
SET
Alarm 1 Set
SET
Alarm 2 Set
SET
Alarm 3 Set
4.1.1
) or DOWN
key again to go to the next digit, repeat the above procedure until the
required has been selected. Press the SET key to enter the desired value.
4.1.2
The SET key also has the function of changing MODEs. If SET key is
pressed, the display shows the next MODE.
4.1.3
Press SET key for 5 sec. The display goes to level 2, press the SET key
again to return to level 1.
4.1.4
If any key is not pressed for 1 minute the display will return to level 1.
4.1.5
4.1.6
4.2
Level 2
Main Control
Range: 0~200%
Proportional Band
ON/OFF at P=0
Main Control
Integral Time
Main Control
Derivative Time
Main Control
Dead-band Time
Main Control
Range: 0~USPL
SET
SET
SET
SET
Auto Tuning off-set
SET
Main Control
Proportional Cycle
Main Control
Hysterisis
Range: 0~1000
Sub Control
Same as P1
SET
SET
Proportional band
SET
Sub Control
Same as I1
Integral Time
SET
Sub Control
Same as D1
Derivative Time
SET
Sub Control
Same as CYT1
Proportional Cycle
SET
Sub Control
Same as HYS1
Hysterisis
SET
Main Control
Gap (Output 1)
OFF early to SP
Sub Control
Gap (Output 2)
ON early to SP
SET
SET
Function Lock
SET
Return to
P1
4.3
Level 3
When LCK=0000, press the SET key and SHIFT key for 5 seconds to enter level 3.
Main Control
Input Selection
Main Control
Range: LSPL~USPL
Main Control
Same as ANL1
SET
SET
Analog Span set
SET
Decimal point
Sub Control
Range: LSPL~USPL
Sub Control
Same as ANL2
SET
SET
SET
SET
Analog Span set
SET
Alarm mode of AL1
Range: 00~19
Refer to 6.1 Alarm Function Selection on P.15
SET
Time set of Alarm 1
SET
Alarm mode of AL2
Range: 00~19
Same as ALT 1
Range: 00~19
Same as ALT 1
Hysterisis of Alarm
Range: 0~1000
SET
SET
SET
SET
SET
Main Control
Calibration
Main Control
Calibration high
Sub control
Same as CL01
SET
SET
Calibration low
SET
Sub Control
Same as CH01
Calibration high
SET
Transmitter control
Same as CL01
Calibration low
SET
Transmitter control
Same as CH01
Calibration high
SET
Timer for
0=No wait
0= a contact, 1= b contact
ID number
Communication ID number
SET
SET
SET
(please skip this step)
SET
Baud rate
Compensate SP
Range: -1000~1000
Compensate PV
Range: LSPL~USPL
Unit of PV & SP
Range: C, F, A (analog)
Soft filter
Range: 0.05~1.00
SET
SET
SET
SET
SET
Control action
Frequency
SET
SET
* Check if the frequency is right. If not, change it, please.
SET
Return to INP1
4.4
4.4.1
Functions of LCK
Let the display go to LCK in level 2, and set 1111 in LCK, then press
SET key and SHIFT key (
PV
SP
Status of SET .1
Status definition
Status of SET .2
0= lock (skip)
Status of SET .3
1= open (display)
Status of SET .4
4.4.3
Functions of SETs
SET
1.1
1.2
1.3
1.4
2.1
2.2
Function
OUTL
AT
AL1
AL2
AL3
ANL1, ANH1, DP
SET
5.1
5.2
5.3
5.4
6.1
6.2
Function
CL02, CH02
CL03, CH03
Rucy, WAIT, HYSM
IDNO, BAUD
SVOS
PVOS
2.3
2.4
3.1
3.2
3.3
3.4
4.1
LSPL, USPL
ANL2, ANH2
ALD1
ALT1
ALD2
ALT2
ALD3
6.3
6.4
7.1
7.2
7.3
7.4
UNIT
SOFT
CASC
OUD
OPAD
Hz
4.2
4.3
4.4
ALT3
HYSA
CL01, CH01
SET
8.1
8.2
8.3
9.3
9.4
0.3
Function
Remarks
0= No Repeat
1= Program Repeat
0= No Power Failure
1= With Power Failure
0= Start from 0
1= Start from PV
TRS SP
Program Use
TRS PV
0= No Remote SP
1= Remote SP
* Caution: Please dont operate SET8.4, otherwise the process of the controller will
be in confusion.
4.5
Program Level
Level 1
SET
Set program pattern
Range: 0~2
SET
SET
Program segment display
Range: (1-0)~(2-8)
SET
SET
SET
Set point for Seg.6
SET
Set time for Seg.6
SET
Set output for Seg.6
SET
Set point for Seg.7
SET
Set time for Seg.7
SET
Set output for Seg.7
SET
Set point for Seg.8
SET
Set time for Seg.8
SET
SET
Set point for Seg.4
Return to Normal(PV,SP)
SET
Set time for Seg.4
SET
Set output for Seg.4
SET
10
4.5.1
4.5.2
4.5.3
Terminologies
Pattern
Step
RAMP status
SOAK status
Operating
1) Key functions (No changing parameters)
(START)
(WAIT)
+SET (JUMP)
: To jump segment
11
12
5.
Input
5.1
R
S
B
E
N
W
PLII
U
L
CODE
RANGE
HEX
0.0~200.0C/0.0~392.0F
01H
0.0~400.0C/0.0~752.0F
02H
0.0~600.0C/0.0~1112.0F
03H
0.0~800.0C/0.0~1472.0F
04H
0.0~1000.0C/0.0~1832.0F
05H
0.0~1200.0C/0.0~2192.0F
06H
0.0~200.0C/0.0~392.0F
07H
0.0~400.0C/0.0~752.0F
08H
0.0~600.0C/0.0~1112.0F
09H
0.0~800.0C/0.0~1472.0F
0AH
0.0~1000.0C/0.0~1832.0F
0BH
0.0~1200.0C/0.0~2192.0F
0CH
0.0~1600.0C/0.0~2912.0F
0DH
0.0~1769.0C/0.0~3216.0F
0EH
0.0~1600.0C/0.0~2912.0F
0FH
0.0~1769.0C/0.0~3216.0F
10H
0.0~1820.0C/0.0~3308.0F
11H
0.0~800.0C/0.0~1472.0F
12H
0.0~1000.0C/0.0~1832.0F
13H
0.0~1200.0C/0.0~2192.0F
14H
0.0~1300.0C/0.0~2372.0F
15H
-199.9~400.0C/-199.9~752.0F
16H
-199.9~200.0C/-199.9~392.0F
17H
0.0~350.0C/0.0~662.0F
18H
0.0~2000.0C/0.0~3632.0F
19H
0.0~2320.0C/0.0~2372.0F
1AH
0.0~1300.0C/0.0~2372.0F
1BH
0.0~1390.0C/0.0~2534.0F
1CH
-199.9~600.0C/-199.9~999.9F
1DH
-199.9~200.0C/-199.9~392.0F
1EH
0.0~400.0C/0.0~752.0F
1FH
0.0~400.0C/0.0~752.0F
20H
0.0~800.0C/0.0~1472.0F
21H
TYPE
CODE
RANGE
HEX
-199.9~600.0C/-199.9~999.9F
22H
-199.9~400.0C/-199.9~752.0F
23H
-199.9~200.0C/-199.9~392.0F
24H
0.0~200.0C/0.0~392.0F
25H
0.0~400.0C/0.0~752.0F
26H
0.0~600.0C/0.0~1112.0F
27H
-199.9~600.0C/-199.9~999.9F
28H
-199.9~400.0C/-199.9~752.0F
29H
-199.9~200.0C/-199.9~392.0F
2AH
0.0~200.0C/0.0~392.0F
2BH
0.0~400.0C/0.0~752.0F
2CH
0.0~600.0C/0.0~1112.0F
2DH
-199.9~600.0C/-199.9~999.9F
2EH
-199.9~400.0C/-199.9~752.0F
2FH
-199.9~200.0C/-199.9~392.0F
30H
0.0~200.0C/0.0~392.0F
31H
0.0~400.0C/0.0~752.0F
32H
0.0~600.0C/0.0~1112.0F
33H
AN1
-10~10mV/-1999~9999
34H
AN2
0~10mV/-1999~9999
35H
AN3
0~20mV/-1999~9999
36H
AN4
0~50mV/-1999~9999
37H
AN5
10~50mV/-1999~9999
38H
JIS
Pt100
DIN
Pt100
JIS
Pt50
14
6.
6.1
Alarm
Alarm function selection
CODE
/
DESCRIPTION
Hold-On
None
Deviation high limit alarm
Yes
No
Yes
No
Yes
No
No
Yes
No
No
Yes
* Note : Hold-On means the alarm does not work at the first time.
15
6.2
6.1.1
CODE 00/10
: None
6.1.2
CODE 01
6.2.3
CODE 11
6.2.4
CODE02
6.2.5
CODE12
6.2.6
CODE03
6.2.7
CODE13
6.2.8
CODE04/14
: Band alarm
6.2.9
CODE05
16
6.2.10
CODE15
6.2.11
CODE06
6.2.12
CODE16
6.2.13
CODE07
6.2.14
CODE17
ALD 1~3,
set 07
ii) AL1~3,
iii) ALT1~3,
if
set 0
= flicker alarm
set 99.59
= alarm continued
set others
= on delay time
6.2.15
CODE08
: System Error- ON
17
6.2.16
CODE18
: System Error-OFF
6.2.17
CODE19
: on delay timer
when PV=alarm SP, it keeps a certain period (set time)
before alarm action (Range: 00H00M~99H59M)
18
7.
7.1
DC1010
7.2
DC1030
7.3
DC1020/1040
19
8.
8.1
SET 1
SET 0
8.1.1
INP2
OUTY
8.1.2
Output mode
OUTY = 0, Single output
OUTY = 1, Double output
OUTY = 2, Non
OUTY = 3, Motor Postion Control
OUTY = 4, Single phase SCR (Single phase control)
OUTY = 5, Three phase SCR (Three phase control)
20
8.2
8.2.1
RAMP
i)
PV
SP
8.2.2
SOAK
i)
ALD1/ALD2 = 19
PV
SP
Example)
SP = 100C, RAMP = 10.00 C/minute
Time(minute) = 10 minute AL1 = 00.10
PV = 25C
C
If PV
Time on
SV(100 C)
100 C
PV=25 C
21
8.3
Remote SP
8.3.1
8.3.2
8.3.3
8.4
8.4.1
8.4.2
8.4.3
8.5
Function SET A
PV
SP
If SET A.1 = 1 set, AL1 relay reversed
If SET A.2 = 1 set, AL2 relay reversed
8.6
Function SET 8
8.6.1
SET 8.1 = 0
Non
SET 8.1 = 1
Program Repeat
SET 8.2 = 0
SET 8.2 = 1
SET 8.3 = 0
SET 8.3 = 1
PV start
SET 8.4 = 0
Non
SET 8.4 = 1
8.6.2
8.6.3
8.6.4
22
8.7
Function SET 9
8.7.1
SET 9.1 = 0
Non
SET 9.1 = 1
PV/SP switching
* This is for the single display set (refer to SET 8.4)
8.7.2
8.7.3
8.7.4
SET 9.2 = 0
Non
SET 9.2 = 1
: No display RAMP
Program mod el
SET 9.3 = 0
Non
SET 9.3 = 1
Transmission SP
SET 9.4 = 0
Non
SET 9.4 = 1
Transmission PV
8.8
Function SET 0
8.8.1
SET 0.1 = 0
Non
SET 0.1 = 1
SET 0.2 = 0
Non
SET 0.2 = 1
SET 0.3 = 0
Non
SET 0.3 = 1
Remote SP
SET 0.4 = 0
SET 0.4 = 1
8.8.2
8.8.3
8.8.4
8.9
Cycle Time
(i)
mA
(ii)
Phase control(SCR)
(i)
SSR
(ii)
Relay output.
23
DC1030/1040, DC1030P/1040P
-. Data Change:
OUTY = 4
CYT = 0
CL01 = 0, CH01 = 5000 if used for resistance load
CL01 = 0, CH01 = 4000 if used for inductor load
FAST
FUSE
CONTROLLER
K2
G1
G2
SCR
Module
K1
G1
G2
K1
K2
24
PROT
Short
DC1040/DC1040P
-. Data Change :
OUTY = 5
CYT = 0
CL01 = 0, CH01 = 5000 only if used for resistance load
T
CONTROLLER
G1
FAST
FUSE
K2
K1
G1
K2
G2
K3
G3
DIODE/SCR
Module
G2
K2
G3
K3
25
PROT
Short
3 LOAD
DC1030/1040
DC1030P/1040P
-. Data Change:
OUTY = 0
CYT1 = 1
FAST
FUSE
CONTROLLER
G1
G1
SCR
Module
G2
G2
TIME CHART:
ON
OFF
26
PROT
Short
DC1040/1040P
-. Data Change:
OUTY = 0
CYT1 = 1
CONTROLLER
RG 1
FAST
FUSE
SCR
Module
RG 1
RG 2
TG 1
TG 1
RG 2
TG 2
TG 2
Short
TIME CHART:
OFF
ON
CYCLE TIME = 200 mSEC.
27
PROT
WE CAN SUPPLY
HEATER SINK
DC1020/1030/1040
DC1020P/1030P/1040P
-. Data Change:
OUTY = 3
CYT1 = 1~100 sec. (Normally, set 5 sec.)
RUCY = 5~200 sec.
MOTOR VALVE
COM
CONTROLLER
R
CLOSE
OUT2
Relay
CLOSE
OPEN
OPEN
COM
28
OUT1
Relay
DC1030/1040
DC1030P/1040P
-. Data Change:
OUTY = 4
CLO1=0 CHO1=5000 if use for resistance load
CLO1=0 CHO1=4000 if use for inductor load
FAST
FUSE
CONTROLLER
G1
T2
TRIAC
Module
K1
G1
G2
T1
K2
PROT
Short
V
1/2W
100[
0.1uf/630V
AC
29