Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Kevwords;
Cast-Resin, Dry Type Transformer,
Hottest Spot Temperature Allowance, Industry Standards,
Loading, Heat Transfer, Thermal Testing.
INTRODUCTION
After the demise of askarel insulated transformers
containing polychlorinated biphenols (PCB'S) in the
1 9 7 0 ' s , several alternative products appeared. One
alternative was a dry type transformer with solid cast
windings of epoxy resin. The development and commercial
application of this unit began in Europe and this
transformer design began to be widely accepted in the
United States in the 1 9 8 0 ' s .
The solid cast and/or
resin-encapsulatedtransformer was incorporated into the
first IEEE standard [ l ] in 1989. Various terminology is
used to describe this type unit and it will be referred
to as the "cast-resin''transformer in this paper.
One of the problems faced by the IEEE Working
Group which developed the new standard was the correct
value of the hottest spot temperature allowance to be
used for the cast-resin transformer. The hottest spot
temperature allowance is defined as the designated
difference between the hottest spot temperature and the
observable insulation temperature [2].
ANSI/IEEE
Standard 1 states that the value is arbitrary, difficult
to determine, and depends on many factors, such as size
185
-150
In
--
_-
30
30
TEST P R O G M
Test Transformer
A prototype cast-resin transformer rated 2000 kVA,
three phase, 60 hertz, high voltage of 4160 volts delta
connected, and a 480 volt Y connected Low voltage was
constructed with embedded thermocouples to determine the
hottest spot temperature rises of the high voltage and
low voltage windings under various loading conditions.
Fans were installed on the unit to evaluate the hottest
spot temperature rises under forced cooled conditions.
HV
LV
in
Figure 1 .
593
Test Procedure
Figure 2.
Figure 3 .
594
Table 4
THERMAL TEST RESULTS
FOR LOW VOLTAGE WINDING'
Table 2
THERMAL TEST RUNS
q-z
CORE
EXC. %
TAP
POS.
0
0
0
0
0
0
0
0
0
0
0
0
0
0
100
100
100
115
100
1.000
1.000
1.406
1.000
1.000
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
HIGH
HIGH
HIGH
LOW
LOW
LOW
LOW
LOW
y
M
B
.
COOL.
HS .
RISE
C
AA
AA
AA
AA
AA
FA
FA
FA
FA
FA
AA
AA
AA
FA
AA
AA
AA
AA
FA
27.1
28.9
24.5
24.8
28.4
26.9
25.4
25.3
24.4
27.8
25.9
25.2
28.6
27.0
31.0
28.3
30.9
33.3
34.9
91.7
77.4
54.5
117.7
99.7
95.8
84.5
78.1
44.4
11 1 2 2 . 9
91.2
12
86.6
14
1 5 105.6
90.8
16
113.1
97.4
20 1 4 6 . 6
22 1 2 6 . 9
108.1
CTR.
61.6
42.9
66.2
47.2
78.3
70.4
83.5
77.1
66.7
57.3
37.4
96.6
82.4
78.3
94.7
71.1
92.1
78.9
116.2
97.1
81.3
52.0
34.1
88.8
75.6
71.8
89.0
64.2
86.6
74.6
110.3
91.2
75.3
II
1.17
1.16
11.6
17.8
1.19
1.24
1.27
1.36
1.19
1.27
1.11
1.11
1.12
1.28
1.23
1.23
1.26
1.31
1.33
Summarv of Results
Table 3
THERMAL TEST RESULTS
FOR HIGH VOLTAGE WINDING'
RUN
NO.
AVG. RISE
HS.
RISE
LEG
'
1
2
3
4
5
7
8
9
10
11
12
14
15
16
18
19
20
22
23
94.2
80.9
54.8
126.0
103.2
106.4
93.1
84.4
46.8
138.9
95.3
84.5
104.6
89.4
75.4
63.3
41.9
98.7
79.9
74.6
66.8
63.4
35.3
99.3
75.8
66.2
83.6
66.3
82.7
68.1
-12.2
83.7
84.8
i
.vA'SHJ.RTC
3 LEG
CTR.
77.5
66.0
43.5
102.7
82.2
75.9
70.2
65.2
36.3
103.5
78.2
70.5
87.5
69.7
18.8
17.6
12.9
27.3
23.3
31.8
26.3
21.0
11.5
39.6
19.5
18.3
21.0
23.1
16.7
14.9
11.3
23.3
21.0
30.5
22.9
19.2
10.5
35.4
17.1
14.0
17.1
19.7
11.22
1.23
1.26
1.23
1.26
1.40
1.33
1.29
1.29
1.34
TEST 12
LOW TA?
TEST 1 1
HIGH TAP
-e-
110,
1.22
1.20
1.20
1.28
117.2
85.2
86.8
LOCATION
TEST 7
FA
* *
"-1
12
10
14
BUCKING
RUN
16
18
20
DIFFERENCE
18
91.2
89.4
84.1
84.2
84.3
89.0
90.9
113.1
112.4
105.5
104.2
103.2
102.9
103.8
103.1
14.8
12.2
82.4
92.1
9.7
__
21.9
23.0
21.4
20.0
18.9
--
22DE
TURN NO.
OPPOSITE
LEAD SIDE
-8-
-46-
97.1
~
""I
C
Table 7
COMPARISON OF TEST RESULTS WITH STANDARDS
JIND COOL
RUNI
HS
IRATIO
ITEST
lac
I
0
10
15
20
25
30
35
H V A A
40
LV
LV
596
FA
AA
FA
54.8
80.9
94.2
95.3
103.2
126.0
1.26
1.23
1.22
1.22
1.26
1.23
11.3
14.9
16.7
17.1
21.0
23.3
IEEE
___
IEC
30
30
30
30
30
5
5
10
10
10
15
10.5
19.2
22.9
30.5
35.4
__
__
30
30
30
30
5
5
5
15
18.5
21.0
30.4
30
30
30
30
10
10-15
15
10
QISCUSSI~
The test program showed that the ratio of hottest
spot temperature rise to average temperature rise at
different loads only varied slightly. This agreed with
the conclusions of Whitman [ll] for ventilated dry type
transformers. The tested ratios for the 2000 kVA unit
were higher than the ratios reported by Outer [ 1 4 ] for
400 and 600 kVA units indicating that the ratio of
hottest spot temperature rise to average temperature
rise probably varies with size of unit. The test data
indicated that the hottest spot temperature allowance
used in the IEC standard is too low resulting in
permissible average temperature rises which are too
high. This is also confirmed by the data of Stewart and
Whitman [ 8 ] for ventilated dry type units. The hottest
spot temperature increment was found to increase with
increasing hottest spot temperature rise and not the
constant 30 '2 allowance used in the IEEE standard. The
constant 30 C allowance appears conservative up to
about 115 'C average temperature rise for the cast-resin
design tested. Hottest spot temperature allowances used
in product standards should be conservative and probably
based on the largest unit covered by the product
standard. Future standards revisions should consider
a constant ratio of hottest spot temperature rise to
average temperature rise.
Another difference in IEEE and IEC standards
involves the method for performing temperature rise
INSULATION HOT. SPOT PERMISSIBLE
PERMISSIBLE
tests.
The IEEE test code 1181 requires that
SYSTEM
AVERAGE
AVERAGE
RISE
temperature rise tests be performed on the tap position
l'EMPERA:URE
IN
TEMP. RISE
TEMP. RISE
which gives the maximum winding temperature rise which
CLASS, c 40 'c AMB PER TEST DATA* PER STMDARDS
would usually be the low tap. IEC 726 [3] specifies
that the temperature rise test be performed on the rated
AA
FA
IEEE[l] IEC[3]
tap. On low tap the unit would run hotter than tested.
For three phase transformers there is a difference
65
51.6
48.5
-60
105
between average temperature rises of the three legs with
80
63.5
59.7
-75
120
the center leg usually but not always the hottest. The
_90
71.4
67.2
60
130
IEEE Task Force on Dry Type Thermal Tests has suggested
__
150
110
87.3
82.1
80
that the average temperature rise be calculated for each
-100
85.8
155
115
91.3
leg individually and the highest value used to determine
140
111.1 104.5
-125
180
if guarantees are met. The test program confirmed that
_
_
185
145
115.1
108.2 1 1 5
this was the correct approach.
Confirmation of hottest spot temperature rise i s
one performance characteristic for which no standard
test method exists. Consideration should be given to
add this measurement to the IEEE Standards as a design
test requirement using prototype transformers to qualify
a design family. A standard recommended test procedure
should also be developed. The test program indicated
that the loading back test method gave higher IOW
voltage winding hottest spot temperature rises than
expected from the short circuit test method. Core loss
raises the temperature of the low voltage winding nonuniformly. The top portion of the winding nearest the
core increased the most contributing to the higher
hottest spot temperature. A similar effect could occur
in the high voltage winding although the effect is
thought to be less. Additional investigation is needed
to develop correction factors for hottest spot
temperature rise for the short circuit test method.
Due to questions raised in the IEEE Working Groups
of the Transformers Committee the author decided that
this data and initial analysis should be made available
to the industry at the present time.
Additional
mathematical analysis is needed to fully explain the
effect of various physical parameters such as size upon
the hottest spot temperature increment. Analysis of dry
TIME CONSTANT, MINUTES
TEST
type transformer heat transfer appears to have been
neglected as evidenced by the lack of published papers.
HV
LV
The data obtained should assist in future product
standards and loading guide revisions. The test data
LEAD WINDING
reported is for only one transformer design from one
manufacturer.
Data and analysis from other
110
133
RUN 1 START UP
212
manufacturers is needed because there are several castINCREASE FROM 75%
89
129
194
resin transformer designs available.
The test
TO 114% LOAD
experience reported should assist other manufacturers in
planning similar thermal test programs.
CONCLUSIONS
1.
ACKNOWLEDGEMENT
REFERENCES
The work described in this paper was financed by
the General Electric Company. Many General Electric
personnel contributed to the manufacture and testing of
the transformer described in the paper. R. E. Gearhart
provided valuable technical honsultation to the author.
The assistance of the General Electric Medium
Transformer Operation Test Department at Rome, Georgia
is gratefully acknowledged.
BIOGRAPHY
Linden W. Pierce (M'70) was
born in AthenB, Texas on
January 4, 1941. He received
the B. S . degree in Mechanical
Engineering fromThe University
of Texas, Austin in 1963,
completed the GE Advanced
Course in Engineering in 1966,
and received the M. S. Degree
in Mechanical Engineering from
the University of Tennessee,
Knoxville in 1973.
In 1963 he joined the
General Electric Company and
since 1965 has worked for the Transformer Department at
Rome, Georgia with various positions in transformer
design, development, and program management. He is
currently Senior Engineer, Product Technology. He holds
eight patents.
Mr. Pierce is a member of the IEEE Power
Engineering, Magnetics, Dielectrics and Electrical
Insulation, and Industry Applications Societies, and
CIGRE.
He is a member of the IEEE Transformers
Committee, Chairman of the Working Group on Development
of the Loading Guide for Cast-Resin Transformers, and
Chairman of the Task Force on Revision of the Test Code
for Performing Temperature Rise Tests on Dry Type
Transformers. He is a Registered Professional Engineer
in the State of Georgia.
598