ETE-300

Data Sheet - N00388

Digital Process Unit

ETE300 is a multivariable electrical meter able to measure the


following variables U; I; P; Q; S; ; power factor; frequency;
active and reactive energy; current and power demand, Total
Harmonic Distortion (THD), Harmonics and capture Voltage
and Current Oscilography.
The Oscilography register the waveforms of 3 Currents and 3
Voltages. Its resolution could be configured to 128, 64 or 32
points per mains cycle. The ETE300 save 50, 100 or 200 cycles
depend of the resolution configured. It can save up to 6
Oscilography in a circular memory (7th Oscilography will
overwrite the first). It could be triggered by: RMS values (Sags
or Swells), dV/dt or dI/dt surges, Digital Inputs or Modbus
Command. Oscilography is saved in a non volatile memory.
Non volatile memory can save the following data: month, day,
hour, minute and the measure variables previously configured
(with capacity to save 12 measure variables every 15 minutes,
of the last 48 days). The data are periodically save overwriting
the first data. The user can configure the variables that want to
save and the interval of measures. This information can be
rescued through IBIS_BE_cnf software.

Event Log of Sag, Swell and Digital Inputs actuation. Its


possible to obtain the amplitude and the period of Sag and
Swell events with milliseconds resolution.

Measure three-phase balanced or unbalanced load, with or


without neutral wire..
Galvanic isolation between input, output and auxiliary power
supply.

RX TX RX TX
31 32 33 34 35 36 37 38 39 40 41

CL

-0.2

Page 1/4
December 2008

GND +A

B GND +A

RS485_1

RS485_2

Input

Input
Voltage
Current
Analog
Inputs

Three serial interface, with two Modbus and one DNP3.


12 bit ADC with six independent channel, operating with 256
point per cycle of sample rate.

Digital
Inputs
Signal Limits

Four Digital Output that could can be controlled by Serial


Interfaces (Modbus and DNP3)

Consumption

Four Analog Input, for 0.20mADC or 4...20mADC signal


transmission through the serial
Ps: The signals must be insulated, if its not use a galvanic
insulator.

Auxiliary power supply AC or DC.

Protection: IP30 (Housing) e IP20 (terminal connection)..

Din Rail Mounting

Error limit of 0,2%

ANEEL 505 Standard. Specification

DI3 DI4 GND

DIGITAL
INPUT

GND +A

45 46 47 48 49 50 51 52 53 54 55 56 57

AI1 AI2 AI3

RS485_3

AI4 GND

DO1

ANALOG
INPUT

DO2

DO3

DO4

DIGITAL
OUTPUT

TECHNICAL DATA (NBR 8145)

Four Digital Inputs that could triggered an Oscilography,


generate a Log of Events or be monitored by Serial.

DI1 DI2

STATUS

TX RX
42 43 44

Nominal
Frequency
Overload
Auxiliary Power
Supply

Output

Phase
Line
80V
140V
150V
260V
300V
520V
1A , 5A
04 Inputs 0...20mA ou 4...20mA
Input Impedance: 150
12 bits ADC
Response Time: < 100ms
Error Limit: 0,2%
04 TTL Input 5V 1mA
Response Time: <1ms
U = 10120%
I = 5...150%
Voltage Input: 2mA.
Current Input: 0,2VA.
50 or 60 Hz 10%
Permanently: 1,5 x U ; 2 x I
Short time: 4 x U/1s;50 x I/1s
maximum: 250A /1s
85 265Vac/90300Vdc
Power consumption ~ 5VA

Digital Output

Open Collector Output


Maximum Voltage. 24Vcc
Maximum Current. 20mA

Serial Interface

02 RS485 with Modbus/RTU Protocol


(RS485_1 e RS485_3)
01 DNP3 (RS485_2)

ETE-300

Data Sheet - N00388

Digital Process Unit

Page 2/4
December 2008

Influence Magnitudes
Error Limit
EL=0,2%
(Optional)

Reference
Conditions

Climatic condition

Voltage
Current
Active Power
Reactive Power
Apparent Power
Power Factor
Frequency
Active Energy (Direct
and reverse flux)
Reactive Energy

(Value EL)
(Value EL)
(Value EL)
(Value EL)
(Value EL)
0,01
0,05 Hz
(W Error EL of
reading)
(VAR Error + EL of
reading)

Input:

I = 5%...100% ;
U = 10%...100%
fnom 2%
Specified Values
cos = 1 (Active Power)
sin = 1 (reactive
power)
25C 2K

Frequency:
Aux. Power Supply:
Power Factor:
Temperature:
Thermal Stability:

20 minutes.

Additional Errors
Additional error above 1,2I
or 1,2U
Linearity deviation
Temperature
Auxiliary power supply
External magnetic fields

0,2%
0,2% (included in error limit)
0,2%/10 K; rated temperature
25C
0,05% within the tolerance
range admissible for the power
supply voltage
0,5% for field intensity of
0,4 kA/m

Electric Tests
Test voltage

2,5kV/1 min - 60Hz between power


supply and remaining circuit
0,5kV min -60Hz between RS485 and
Pulse output

Construction and Mounting


Housing
Mounting
Electrical
Connection
Protection
Weight

Aluminum
DIN Rail Mounting .
Voltage, Current and Auxiliary power Supply
using ring shaped cable shoes.
Digital Input, Digital Output, RS485 and Analog
Input terminals for pin shaped cable shoes.
IP 30 (Housing)
IP 20 (Terminal Connections)
~ 1,0 kg

Operating temperature
Functioning temperature
Transport and storage
temperature
Relative humidity

-20...+60C
-25...+70C
-40...+80C
75% of annual mean with small
condensation
(others upon request)

Mechanical Tests
Impact
Vibration

Acceleration 30g during 11ms


Acceleration 2g frequency 5..150Hz

ETE-300

Data Sheet - N00388

Digital Process Unit

Page 3/4
December 2008

105,0

Dimensional Drawing
Dimensions in mm

11

13

14

12

182,0

95,2

Additional Information
The following items contain tips and cautions to be observed by the
user for a good functional performance, as well as the maintenance
of the instrument and the safety of the installations

Cautions
Be sure that the voltage and current to be connected to the
instrument are compatible.
Loosen all connections from the instrument before removing it from
the installation.

Mounting Instructions
Observe the ambient temperature range. At the place of installation,
values for vibration, dust, dirt and humidity, which must remain
between the limits, established by the protection class of the housing
and the climatic group, specified in this data sheet, have to be
observed.
For mounting on DIN rail, use the snap-in device on the rear of the
instrument.
The connections can be made with pin for shaped cable shoes, for
the input signals in Voltage and Current and for the Auxiliary
Power; RS485 and digital outputs terminals type pin

Instructions for Use


When connections have been made, switch on the power supply and
check the functioning of the instrument

.
.

ETE-300

Digital Process Unit

Data Sheet - N00388


Page 4/4
December 2008

ABB Ltda - ATLV/EI Electrical Instrumentation


Av. Dos Autonomistas, 1496 - 06020-902 - Osasco - SP