ULTRASONIC FLOW METER

SX15004459A0IDS120EN

DATA SHEET

SHEET
CUSTOMER'S REF.:

REV.

DATE

DESCRIPTION

BY

of

CHK'D

APPR.

WARTSILA

13/02/2015

ISSUE FOR APPROVAL

MA.M

ST.L

CA.A

TITLE :

17/04/2015

GENERAL REVISION

MA.M

ST.L

CA.A

ARUN PLN

24/04/2015

REVISED WHERE INDICATED

MA.M

ST.L

CA.A

LOCATION :
INDONESIA
P&ID No. Ref. :
GENERAL

SX15004459A0PDG001EN
FT300

2 Quantity

3 Service

ULTRASONIC FLOW METERS (FISCAL METERING, PAY)

10"/DN250/ANSI 300 RF

5 End Connections
6 Body Rating

ANSI300

7 Nominal Flow Range (m/h)

65 6500

(Qmin Qmax)

< 0.5% of the value measured


< 0.2% with high pressure calibration

8 Accuracy

0.1%

9 Repeatability

1 : 100

10 Rangeability
11 Materials:

ACCORDING TO AGA 9 and ISO17089

10" sch. STD (40)

4 Line Size

METER

<C>

1 Tag No.

Body

12 Design Pressure/Temperature
13 Flanges

LOW TEMPERATURE CARBON STEEL


22 Barg / 0C to + 70C
LOW TEMPERATURE CARBON STEEL

14 Pickoff Type
15 Local Display

INCLUDED LCD DISPLAY

16 Flow Direction

UNIDIRECTIONAL
NATURAL GAS

17 Fluid
18 Flow Rate Process Min.|Max

420Nm/h

46.000 Nm/h

19 Flow rate ultr.meter Min|Max

990 Nm/h

46.000 Nm/h

@Pmax=15BarG

20 Flow rate ultr.meter Min|Max

675 Nm/h

46.000 Nm/h

@Pmin=10BarG

21 Normal Flow (Stm/h)

FLUID DATA

22 Pressure Min/ Op/ Max (Bar g)

38.400 Nm/h
10 / - / 15

23 Back Pressure (Bar)


24 Temperature Min/Op/Max (C)
25 Molecular Weight

17,59

26 Viscosity Range (Cp)

0,011

27 Percent Solids & Type

NOT SPECIFIED

28 Type

4 PATH MINIMUM

29 Material

TRANSDUCER

19 / - / 66

TITANIUM

30 Function
31 Retractable
32 Protection

YES, UNDER PRESSURE


intrinsically safe ia

33 Model number
34 Housing
35 Power Supply / Consumption

ELECTRONIC

36 Flow Range

II 1/2G Ex de ib [ia] IIC T4, IP67

38 Output Signals

RS485; 2 X HF PULSE TRANSM

40 High Pressure Calibration

YES
YES

45 Code
CONSTRUCTION

46 Welding/Inspection Code
47 Inspection Authority
48 Manufacturer

Notes:

YES

42 At Op. Pressure

44 No. Points

N3 M20x1,5 ELECTR. CONNECTIONS

YES (STATIC)

41 Atmospheric

43 Pressure Value

PRESSURE TAP ON METERING BODY (1/4" NPT-F)

YES

37 Explosion Proof Protection

39 Dry Calibration (Atmospheric)

CALIBRATION
REQUIRED

ALUMINUM
12 ... 28,8 VDC / < 1 W

13BarG
N7 CALIBRATION POINTS AND N3 CONTROL POINTS
ASME
N/A
N/A
SICK

49 Meter Model No.

FLOWSIC600

50 PF Internal Code

PFR15004459S501

(1) ACCEPTANCE TEST CERTIFICATE TO EN 10204 / 3.1B CE MARKING, ACCORDING AGA 9 REPORT
(2) ATEX CERTIFICATE (94/9/EC)
(3) HYDROTEST CERTIFICATE INCLUDED
(4) PAINTING SPECIFICATION ACCORDING TO MANUFACTURER STANDARD
(5) HP CALIBRATION TEST WITH FINAL CUSTOMER AND/OR INSPECTOR ATTENDANCE IF REQUIRED

Accessories:

(1) N1 RETRACTION TOOL FOR REMOVING THE TRANSDUCERS UNDER OPERATING PRESSURE

Spare Parts:

(1) KIT FOR COMMISSIONING

Third part (5)

Status: Approved

Confidential

Document id: DBAD561283 - Page 5 (14)

DOCUMENT No.

FLOW COMPUTER

SX15004459A0IDS120EN

DATA SHEET
CUSTOMER'S REF.:

REV.

DATE

WARTSILA

17/04/2015

TITLE :

24/04/2015

SHEET

BY

of
CHK'D

APPR.

GENERAL REVISION

MA.M

ST.L

CA.A.

REVISED WHERE SHOWN <C>

MA.M

ST.L

CA.A.

DESCRIPTION

ARUN PLN
LOCATION :
INDONESIA
P&ID No. Ref :
P&ID Tag

FQY300

Service

ELECTRONIC MEASURER & CONVERTER OF NATURAL GAS VOLUME

Measuring System

ULTRASONIC FLOW METER (CUSTODY TRANSFER)

Channel

GENERAL

Quantity

Fluid

NATURAL GAS

Flow rate

0 - 38.400 Nm/h

Pressure (Min/Op/Max)

10 BarG / - / 15 BarG

Temperature (Min/Op/Max)

19C / - / 66C

Molecolar weight

18,11

Power supply

1836 Vdc (2A Max)


Reference condition (+25C 0,1% FS); Resolution 4A (250 ppm); 0,01%/C

Output accurancy (analog outboard)


Station configuration

See SX1504459A0LDG001EN

Redundant configuration

NO

OUTPUT
SIGNAL

COMMUNICATION

Frequency (Turbine/Ultrasonic)

2 Ch HF (10KHz max) and/or LF (2Hz max)

Analog signal 420mA Temperature

1 (HART protocol)

Analog signal 420mA Pressure

1 (HART protocol)

NO

Frequency (Densimeter)
Congestion Management Filters

Analog or Digital input for alarm Congestion Management Filters

Digital signal

3 DI UPS management system

Digital signal

8 CONFIGURABLE (Alarms/Volumes) and 2 SPDT fixed function

Analog output 420mA

6 CONFIGURABLE (Optional)

Serial link

STD. SERIAL RS485

Serial link function


Serial link number

Printer, Ultrasonic meter, PLC (Modbus protocol)

<C>

Etherneth Link
Etherneth Link number
Weight

OTHERS

TECHNICAL DATA

INPUT SIGNAL

Name Line

N2: for ultrasonic meter communication and gas chromatograph (provision)


N1 Ethernet TCP/IP / Modbus over TCP for PLC communication
1
3,5kg

Dimension

213mm x 232mm x 128,4mm

Mounting / Installation
Ex Execution

19" rack mounting supported

Index of Protection
Display

For use in safe area only


IP20
LCD with keyboard 4 keys (TFT graphic 1/4 VGA size monochrome)

Log

Up to 6 Log available

Printer

External or Virtual

Blade Failure Available


Memory

N/A
Memory card 1GB

Gas compressibility factor calculation Z


Type of execution
Manufact.
Model

According AGA 8 detail, AGA 8 gross 1, AGA 8 gross 2, AGA NX 19 Mod, ISO 12213-3 MGERG

Instruments have Eex_d execution


P. FIORENTINI
FLOWEB - CODE 3480411

Notes:
1) Intentionally blank

<C>

<C>

2) In case of gas chromatograph connection, this shall be through serial link RS485
3) Floweb will be panel installation with all accessory
4) Metrological approval: NMi: EN 12405-1: 2005 - MID-Nmi n T10113 O4.04.2008
5) Gas mass flow or corrected volume calculations according to AGA 9 standards
6) Compressibility calculated according to According AGA 8 detail, AGA 8 gross 1, AGA 8 gross 2, AGA NX 19 Mod, ISO 12213-3 MGERG
7) Calorific value directly from gas chromatograph (PROVISION)