Sei sulla pagina 1di 51

Circuit

breakers

Product

Section

1
Page

DPN MCBs, 1 - 40A

10

DPN RCBOs, 6 - 40A

11

C60H MCBs, 1 - 63A

12

C60H Vigis, 1 - 63A

14

C60H RCBOs, 6 - 45A

15

C120 MCBs, 10 - 125A

16

C120 Vigis, 10 - 125A

20

DPN/C60/C120 auxiliaries

24

DPN/C60/C120 accessories

29

NG125 MCBs, 10 - 125A

32

NG125 Vigi's, 10 - 125A

41

NG125 auxiliaries

46

NG125 accessories

50

P25M, 0.16 - 25A

52

RMG RCCBs, 16 - 100A

55

RMG RCCBs auxiliaries

56

RMG RCCBs accessories

57

Circuit breaker
Selection guide

Circuit breaker
Selection guide

DPN MCBs/RCBOs
DPN MCBs/RCBOs are available up to 40A, with a single phase
breaking capacity of 6kA. Both phase and neutral conductors are
encapsulated in a compact (18/36mm) unit making it ideal for
special applications where the neutral must be disconnected but
space is a constraint.

C60 MCBs/RCBOs
Forming the core part of the Merlin Gerin MCB offer, C60 MCBs
are available up to 63A, B, C or D curve with a breaking capacity
of 15kA. Accepting cables as large as 35mm2, C60 provides a
single or three phase compact solution for a wide range of
commercial or heavy industrial applications.
They may be connected to Isobar 4 pan assemblies or hard wired.

C120 MCBs/RCBOs

New

Providing a partial replacement for the NC100 range, C120


provides current ratings up to 125A with a breaking capacity of
15kA. Single or three phase versions are available which can be
used in conjunction with a wide range of clip on vigi (RCD)
devices. The flexibility of this new range is further enhanced by the
ability to use a common range of accessories on DPN, C60 and
now C120.

NG125 MCBs/RCBOs
The revolutionary new NG125 provides current rating up to 125A,
with breaking capacities of 25, 36 or 50kA, (50kA for motor
applications only). Suitable for use as an outgoer to final circuits
being fed from panel applications.
NG125 includes standard features such as:
Integral padlocking facility
Tripped indication

New

Interchangeable connection system


Rotary handles

DPN
Miniature circuit breakers
Ratings 4 to 40A, breaking capacity 6kA
Applications
Protection and control of circuits against overloads and short circuits where
switching of the neutral is required.

DPN type B

19271

For use in applications with general load


characteristics.
2 pole switching in single pole width. Phase only
protected.
Tripping characteristics: BS EN 60898 type B
magnetic setting between 3 and 5 In.

Rating
(A)
4
6
10
16
20
25
32
40

Part
No.
19249
19250
19252
19254
19255
19256
19257
19258

Width in 18mm
SP ways
1
1
1
1
1
1
1
1

DPN type C

For use in applications with moderate inrush


currents.
2 pole switching in single pole width. Phase only
protected.
Tripping characteristics: BS EN 60898 type C
magnetic setting between 3 and 10 In.

Rating
(A)
1
2
4
6
10
16
20
25
32
40

Part
No.
19260
19261
19263
19264
19266
19268
19269
19270
19271
19272

Width in 18mm
SP ways
1
1
1
1
1
1
1
1
1
1

Installation

Symmetrical DIN rail.

Technical data

Current rating: 1 to 40A at 300C.


Voltage rating: 240V ac.
Breaking capacity: BS EN 60898, 6kA.
Operating cycles: Mechanical: 20,000,
Electrical:
20A, 20,000,
25A, 15,000,
32A, 10,000,
40A, 6,000.
Positive contact indication: in accordance with
BS 7671.
Width: 18mm.
Weight: 120g.
Cable capacity: 16mm2.
Tightening torque: 2.5Nm.

Accessories:
Earth leakage DPNN:
Technical data:

10

see page 29.


see page 11.
see page 169.

DPN RCBO
Combined MCB/RCD
Application
Protection against the effects of earth leakage, overload and short circuit currents.

2 pole switching of phase & neutral. Phase


protected against overloads and short circuits.
Commercial, industrial and domestic electrical
distribution systems.
Note: must not be used as the sole means of
providing protection against direct contact (BS7671).

Technical data

19668

AC
Class
Type

Width
Sens.
in
(mA)
18mm
SP ways
N + 1P 2
30
N

1P

Rat.
(A)

Part No.

6
10
16
20
25
32
40

19661
19663
19665
19666
19667
19668
19669

Nominal voltage: 110/240V.


Breaking capacity: 6000A Ics to BS EN 60898,
and earth leakage tested to BS EN 61009.
Tripping characteristics: C curve: the magnetic
release operates between 5 and 10 x In.
Positive contact indication of the phase
conductor: in accordance with the IEE Wiring
Regulations BS7671.
Sensitivity: (non-adjustable) 30mA:
unwanted tripping: The DPN rcbo incorporates a
filtering device, preventing the risks of unwanted
tripping due to transient voltages (lightning, line
disturbances on other equipment and transient
currents from high capacitive circuits).
Visual indication of trip due to earth faults.
Cable capacities: Tunnel terminals up to 16mm2.
Weight: 190g.
Installation: Panel mounting on symmetrical DIN
rail in multi-service type boards and standard
enclosures.
Padlocking in the ON/OFF position by using
part no. MGLA or 20718.

Dimensions (mm)
RCBO

N 2

1 protected pole + neutral

70

5
36

45

81

44
Type
No. of MCBs
Comb busbar
1P+N
13
1P+N
24
(bag of 2)
25mm2 insulated
connector (bag of 4)

Comb busbars

Part no.

Comb busbars enable several circuit breakers to be


supplied with power.
The supply to the comb busbar can be connected:
Directly across the circuit breaker terminals by a
16mm2 cable,
OR
via 25mm2 connectors. Suitable for use with DPN
MCBs and DPN vigi or combinations of both.

14880
14890
14885

432
max.24 MCBs

Characteristics

235

max.13 MCBs

DPN comb busbar 100A/240V IEC664

Current rating at 400C:


100A with a central connector,
125A with two supply points.

Clip-on markers

27

Markers can be installed:


On the front face (max. 6 markers)
Or above the downstream terminals (max. 4
markers). See page 31.

10
15

11

C60H
Miniature circuit breakers
Ratings 1 to 63A, breaking capacity 15kA
Installation

Symmetrical DIN rail.


Direct panel mounting.
Isobar 4 pan assemblies.

Technical data

1, 2, 3 and 4 pole Type B Miniature circuit breakers

Current ratings: 1 to 63A at 300C to BS EN60898.


Voltage ratings: 240 - 440V ac.
Breaking capacity: BS EN 60898: 10kA,
BS EN 60947-2: 15kA.
See page 174 for further information on breaking
capacities and dc ratings.
Operating cycles (O-C): on load 20,000.
Operating temperature: -300C to +700C.
Positive contact indication: in accordance
with BS7671.
Width:
Pole
18mm SP ways
1
1
2
2
3
3
4
4
Dimensions: see page 155.
Weight:
Pole
Grams
1
110
2
220
3
340
4
450
Accessories:
see page 29.
Add on earth leakage: see page 14.
Technical data:
see page 168.
Note: 2 and 4 pole C60H MCBs are suitable for
installation in Isobar 4 pan assemblies with NKIT.

1, 2, 3 and 4 pole Type C Miniature circuit breakers

1, 2 and 3 pole Type D Miniature circuit breakers

12

C60H
Miniature circuit breakers
Ratings 1 to 63A, breaking capacity 15kA
C60HB type B (3 - 5In)
Applications
Protection and control of circuits against overloads
and short circuits.
In applications with general load characteristics.
Tripping characteristics: BS EN 60898 type B:
magnetic setting between 3 and 5 In.
Cable capacity:
2
1 - 25A = 25mm .
2
32 - 63A = 35mm .
Tightening torque:
25A = 2.5Nm.
32 - 63A = 3.5Nm.

C60HC type C (5 - 10In)


Applications
Protection and control of circuits against overloads
and short circuits.
In applications with moderate inrush currents,
such as certain lighting systems.
Tripping characteristics: BS EN 60898 type C:
magnetic setting between 5 and 10 In.
Cable capacity:
2
1 - 25A = 25mm .
2
32 - 63A = 35mm .
Tightening torque:
25A = 2.5Nm.
32 - 63A = 3.5Nm.

C60HD type D (10 - 14In)


Applications
Protection and control of circuits against overloads
and short circuits.
In applications with high inrush currents, such as
transformers, motors, certain lighting systems etc.
Tripping characteristics: BS EN 60898 type D:
magnetic setting between 10 and 14 In.
Cable capacity:
2
1 - 25A = 25mm .
2
32 - 63A = 35mm .
Tightening torque:
25A = 2.5Nm.
32 - 63A = 3.5Nm.

C60HB miniature circuit breaker Part Nos


Ratings
(A)
1
2
4
6
10
16
20
25
32
40
50
63

1P
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB

2P
101
102
104
106
110
116
120
125
132
140
150
163

C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB

3P
201
202
204
206
210
216
220
225
232
240
250
263

C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB

4P
301
302
304
306
310
316
320
325
332
340
350
363

C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB

401
402
404
406
410
416
420
425
432
440
450
463

C60HC miniature circuit breaker Part Nos


Ratings
(A)
1
2
4
6
10
16
20
25
32
40
50
63

1P
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC

2P
101
102
104
106
110
116
120
125
132
140
150
163

C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC

3P
201
202
204
206
210
216
220
225
232
240
250
263

C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC

4P
301
302
304
306
310
316
320
325
332
340
350
363

24876
24877
24878
24879
24880
24881
24882
24883
24884

C60HD miniature circuit breakers Part Nos


Ratings
(A)
1
2
4
6
10
16
20
25
32
40
50
63

1P
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD

2P
101
102
104
106
110
116
120
125
132
140
150
163

C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD

3P
201
202
204
206
210
216
220
225
232
240
250
263

C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD

301
302
304
306
310
316
320
325
332
340
350
363

13

Vigi C60
Add on residual current device for use with C60 MCBs only
Applications
Clipped onto the side of any C60 MCB, add on Vigis
provide a high level of protection against earth fault in
addition to overload and short circuit protection
provided by the MCB alone.

Effectively creating an RCBO to BS EN 61009, C60


MCBs with add on Vigi's can be used with any
Isobar 4 distribution board pan assemblies as well as
a wide range of DIN enclosures.

Vigi

MCB

RCBO

Vigi modules - 2 pole for assembly with 1 or 2 pole MCBs


Part No.
MGV
MGV
MGV
MGV

25
63
63
63

010
030
100
300

Ratings
(A)
25
63
63
63

2
2
2
2

Sensitivity
(mA)
10
30
100
300

Ratings
Sensitivity
(A)
(mA)
MGV 63 030 4
63
30
MGV 63 300 4
63
300
Terminal screw shields available for Vigi RCDs.
See C60 accessories on page 29.

Standards Approval: BS EN 61008 (BS EN 61009 when fitted to MCB).


2 pole = 110/240V 50/60Hz,
4 pole = 240/415V 50/60Hz.

Cable capacity:

2 pole = 25mm2,
4 pole = 35mm2.

Note: Must not be used as the sole means of protection against direct contact with
live parts (BS 7671).
Dimensions: see page 155.

14

2 4

7
T

Width in
18mm SP ways
4
4

Specification:
Operating voltage:

Width in
18mm SP ways
2
2
2
2

Vigi modules - 4 pole for assembly with 3 or 4 pole MCBs


Part No.

2 4 68

C60H RCBO (18mm)


Combined MCB/RCD
Applications
Protection and control circuits against overloads, short circuits and earth
leakage faults in commercial and industrial electrical distribution systems.

The C60H RCBO provides:

C60HC32R30

Protection against indirect contact.


Complimentary protection against direct contact
(BS 7671).
Protection for the installation against insulation
faults.
Finger safe terminals.
Reverse polarity protection.
Loss of neutral protection.
Operating voltage: 50V to 253V.
Current ratings: 6A to 45A.
Tripping characteristics: BS EN 61009 (type C)
magnetic setting between 5 to 10In.
Breaking capacity: BS EN 60898 10,000A.
Class 3 current limiting overcurrent protection.
Positive contact indication in accordance with
BS 7671.
Lockable in ON or OFF position.
Trip free mechanism.
Compatible with C60 auxiliaries and accessories
e.g. alarm contact, shunt trip.
Dimensions: see page 133.

Installation

Isobar 4 distribution board pan assemblies and


standard enclosures.

Part No.
C60HC6R30

Ratings
(A)
6A 30mA

Curve
type
C

Class
AC

C60HC10R30

10A 30mA

AC

C60HC16R30

16A 30mA

AC

C60HC20R30

20A 30mA

AC

C60HC32R30

32A 30mA

AC

C60HC45R30

45A 30mA

AC

C60HC6R100

6A 100mA

AC

C60HC10R100

10A 100mA

AC

C60HC16R100

16A 100mA

AC

C60HC20R100

20A 100mA

AC

C60HC32R100

32A 100mA

AC

C60HC45R100

45A 100mA

AC

C60HC6RA10

6A 10mA

C60HC10RA10

10A 10mA

C60HC16RA10

16A 10mA

C60HC20RA10

20A 10mA

C60HC32RA10

32A 10mA

C60HC45RA10

45A 10mA

C60HC6RA30

6A 30mA

C60HC10RA30

10A 30mA

C60HC16RA30

16A 30mA

C60HC20RA30

20A 30mA

C60HC32RA30

32A 30mA

C60HC45RA30

45A 30mA

15

C120H circuit breakers


B, C and D curves
BS EN 60898 - BS EN 60947.2: 15kA
Applications
C120 MCBs provide high levels of current capacity,
while maintaining a breaking capacity of 15kA.
Available with a wide range of add on earth leakage
and control accessories, C120H provides a physical
replacement for the previous NC100 range of devices
with B, C, and D type characteristics and 1 to 4 poles.
Protection of cables against overloads and short
circuits in final distribution.
Manual control and isolation.
Earth leakage protection when combined with a
Vigi to BS EN 61009.
Remote tripping, indication, by adding auxiliaries
common to the entire C60/C120 range.
See page 27.

New

1, 2, 3 and 4 pole Miniature circuit breakers

Technical data

Current rating: 10 to 125A.


Maximum voltage rating Ue: 440V ac.
Insulation voltage Ui: 500V.
Impulse withstand voltage Uimp: 6kV.
Complies with: BS EN 60898 and
BS EN 60947-2.
Breaking capacity: BS EN 60898.
Type
Voltage
Breaking
(V)
capacity Icn (A)
1, 2, 3, and 4P
230 - 400
15000
Breaking capacity: BS EN 60947-2.
Type
Voltage
Breaking
(V)
capacity Icu (A)
1P
130
30000
230 - 240
15000
400 - 415
45000
2, 3 and 4P
230 - 240
30000
400 - 415
15000
440
10000
(1) Breaking capacity under 1 pole with IT isolated
neutral system (case of double fault).

Service breaking capacity: Ics = 50% Icu.


Positive break indication.
Fast closing ensures simultaneous closing of
poles.
Electrical durability:
63A: 10,000 cycles (O-C).
80 - 125A: 5,000 cycles (O-C).
Limitation class: 3
Mechanical durability: 20,000 cycles (O-C).
Weight:
Pole
Grams
1
205
2
410
3
615
4
820

16

Connection:
Flexible cables: 1.5 to 35mm2.
Rigid cables: 1 to 50mm2.
Terminals ensure:
Degree of protection IP2X.
Clamping of wide cross section cables.
Automatic guiding of cable into the correct
position.
Markers:
4 marker clips next to the upstream terminal.
Label holder on handle (2, 3 and 4 pole).
Degree of pollution: 3.
Degree of protection:
Open or surface mounted device: IP2X.
In a Pragma or Prisma enclosure: IP4X. (IPXXD).

B curve

Magnetic trip units operate between 3 and 5 In.


Protection of electric heating.
Protection of networks supplied by generators.

C curve

Magnetic trip units operate between 5 and 10 In.


Protection of lighting circuits.

D curve

Magnetic trip units operate between 10 and 14 In.


Protection of circuits that supply high inrush
current loads: transformers, motors, etc.

Note: This product is not suitable for use with


Isobar 4 pan assemblies.

C120H circuit breakers

New

B curve
BS EN60898 - BS EN 60947.2: 15kA
B curve C120H
1P
1

2
18404

2P
1

18415

3P
1

18426

4P

18437

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18394
18395
18396
18397
18398
18399
18400
18401
18402
18403
18404

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18405
18406
18407
18408
18409
18410
18411
18412
18413
18414
18415

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18416
18417
18418
18419
18420
18421
18422
18423
18424
18425
18426

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18427
18428
18429
18430
18431
18432
18433
18434
18435
18436
18437

Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3
3
3

Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6
6
6
17

C120H circuit breakers

New

C curve
BS EN60898 - BS EN 60947.2: 15kA
C curve C120H
1P
1

2
18448

2P
1

18459

3P
1

18470

4P

18481
18

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18438
18439
18440
18441
18442
18443
18444
18445
18446
18447
18448

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18449
18450
18451
18452
18453
18454
18455
18456
18457
18458
18459

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18460
18461
18462
18463
18464
18465
18466
18467
18468
18469
18470

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18471
18472
18473
18474
18475
18476
18477
18478
18479
18480
18481

Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3
3
3

Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6
6
6

C120H circuit breakers

New

D curve
BS EN60898 - BS EN 60947.2: 15kA
D curve C120H
1P
1

2
18492

2P
1

18503

3P
1

18514

4P

18525

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18482
18483
18484
18485
18486
18487
18488
18489
18490
18491
18492

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18493
18494
18495
18496
18497
18498
18499
18500
18501
18502
18503

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18504
18505
18506
18507
18508
18509
18510
18511
18512
18513
18514

Rating (A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18515
18516
18517
18518
18519
18520
18521
18522
18523
18524
18525

Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3
3
3

Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6
6
6
19

Vigi C120 modules

New

Add on residual current devices for use with C120 MCBs


Standard and si type, BS EN 61009-IEC 60947.2 appendix B
Common function

Common technical data

The protection of electrical installations against


earth faults.
The protection of persons against indirect contact:
medium sensitivities (300, 500, 1000 mA).
Supplementary protection of persons against
accidental direct contact: high sensitivity (30 mA).
The C120 residual current device complies with
BS EN 61009. It is equipped with a locating device
that ensures the correct rating and number of poles.
The technical data of C120 circuit breakers when
combined with Vigi modules remain unchanged and
the circuit breakers remain compatible with indication
or control auxiliaries.

Trip sensitivity

AC class
Tripped by sinusoidal AC currents whether they
are quickly applied or rise slowly.

A class
A
class: ensures tripping with a DC
component current. Tripped by sinusoidal AC
currents as well as by pulsed DC currents
whether they are quickly applied or rise slowly.

Trip type
Instantaneous
Provides a trip upon reaching threshold (no intentional
time delay).

Selective s

Technical data for standard type

AC class: standard, 5060 Hz.


8/20 ms impulse withstand:
Instantaneous: 250A,
Selective: 3kA.
Impulse withstand:
Instantaneous: 3kA,
Selective: 5kA.
Remote tripping: possible using an MX or MN
release on circuit-breaker.
Connection: Identical to C120 circuit-breakers:
Flexible cables: 1.5 to 35mm2,
Rigid cables: 1 to 50mm2.
Width of C120 residual current device + Vigi
module: (in number of 18mm SP ways)

2P
6.5 (3+3.5)

Provides discrimination with down stream device by


introducing an intentional time delay. Down stream
device must be instantaneous with a sensitivity of 1/2
the upstream device.

SI

Provides continuity of supply on circuits with a


disturbed supply network. Used where there is a high
risk of nuisance tripping due to:
Lightning strikes.
IT earthing systems.
Switched electronic ballasts.
Desensitised by:
Harmonics or high frequencies.
DC components.

The Vigi C120 module incorporates the residual


current relay and toroid in a case. Its earth
leakage module is electro-mechanical. It functions
without an auxiliary power supply source and thus
has a very wide operating range.
Protected against nuisance tripping due to
transient overvoltages (lightning stroke,
switchgear switching on the network, etc.).
Breaking and making capacity upon short-circuit
is equal to the breaking capacity of the circuit
breaker.
Instantaneous or selective s trip units.
Reinforced electromagnetic compatibility.

4P
11 (6+5)

3P
500

4P
580

Weight (g):

2P
325

3P
9.5 (4.5+5)

Fault indication by means of a red strip on the


resetting handle.
Resetting the Vigi module, at user's
convenience:
Either using the circuit-breaker handle,
Or independently of the circuit-breaker.

Combination of earth leakage modules


with circuit breakers

C120 residual current device

20

C120 circuit breaker

Vigi C120 module

C120 circuit breakers

New

Add on residual current devices for use with C120 MCBs


AC class, BS EN 61009
Class AC, C120 Vigi module
2P
1

3
T

Voltage
(V)

Sens.
(mA)

Part No.

230415

30
300
300 s
500
1000 s

18563
18564
18544
18565
18545

Voltage
(V)

Sens.
(mA)

Part No.

230415

30
300
300 s
500
1000 s

18566
18567
18546
18568
18547

Voltage
(V)

Sens.
(mA)

Part No.

230415

30
300
300 s
500
1000 s

18569
18570
18548
18571
18549

Width in
18mm SP
ways
3.5
3.5
3.5
3.5
3.5

2 4

18563

3P
1

5
T

Width in
18mm SP
ways
5
5
5
5
5

24 6

18546

4P
1

7
T

Width in
18mm SP
ways
5
5
5
5
5

2 4 68

18549

21

C120 circuit breakers

New

Add on residual current devices for use with C120 MCBs


A class, BS EN 61009
Class A, C120 Vigi module
2P
1

3
T

Voltage
(V)

Sens.
(mA)

Part No.

230415

30
300
300 s
500
500 s
1000 s

18572
18573
18581
18574
18582
18583

Voltage
(V)

Sens.
(mA)

Part No.

230415

30
300
300 s
500
500 s
1000 s

18575
18576
18584
18577
18585
18586

Voltage
(V)

Sens.
(mA)

Part No.

230415

30
300
300 s
500
500 s
1000 s

18578
18579
18587
18580
18588
18589

2 4

Width in
18mm SP
ways
3.5
3.5
3.5
3.5
3.5
3.5

18572

3P
1

5
T

2 4 6

Width in
18mm SP
ways
5
5
5
5
5
5

18584

4P
1

7
T

2 4 68

18589

22

Width in
18mm SP
ways
5
5
5
5
5
5

C120 circuit breakers

New

Vigi modules
si type, BS EN 61009
Class si C120 Vigi module
2P
1

3
T

Voltage
(V)

Sens.
(mA)

Part No.

230415

30
300
300 s
500
1000 s

18591
18592
18556
18593
18557

Voltage
(V)

Sens.
(mA)

Part No.

230415

30
300
300 s
500
1000 s

18594
18595
18558
18596
18559

Voltage
(V)

Sens.
(mA)

Part No.

230415

30
300
300 s
500
1000 s

18597
18598
18560
18599
18561

Width in
18mm SP
ways
3.5
3.5
3.5
3.5
3.5

2 4

18591

3P
1

5
T

Width in
18mm SP
ways
5
5
5
5
5

2 4 6

18558

4P
1

7
T

Width in
18mm SP
ways
5
5
5
5
5

2 4 68

18561

23

Electrical auxiliaries
For DPN, C60 and C120 MCBs
Applications
For the remote control and status indication of DPN, C60 or C120 MCBs.

They are mounted to the left of the circuit-breaker


within a maximum width of 54mm.
Fixed using clips (no tools) onto the left side of
the circuit-breaker.
Compatible with Vigi modules (fitted to the right
side).
A maximum of 3 indication auxiliaries on the same
circuit-breaker.
A maximum of 2 changeover auxiliaries
(OF+SD/OF) on the same circuit-breaker.
A maximum of 2 tripping auxiliaries (MX + OF or
MN) on the same circuit-breaker.
A maximum of 1 tripping auxiliary (MN s or MNx
or MSU) on the same circuit-breaker.

Auxiliary combination

OF+SD/OF
auxiliary
contact

24

OF
auxiliary
contact

SD
fault indication
switch

Mx + OF, MN, MN s
MNx or MSU
auxiliary

Circuit
breaker

Electrical auxiliaries
For DPN, C60 and C120
MX + OF (shunt release and auxiliary contact)

U>

26946

New

14 12

Control
voltage
(V AC)
220...415
48...130
24
12
Disconnects

Part No.

Width in
18mm SP
(V DC)
ways
110...130 26946
1
48
26947
1
24
26948
1
12
26949
1
the MCB when a voltage is applied.

C2 C1

MSU (voltage threshold release)


1P + N
U>>

Control
voltage
(V AC)
220...240

Part No.

26979

Width in
18mm SP
ways
2

380...415

26980

Control
voltage
(V AC)
220...240
48

Part No.

Control
voltage
(V AC)
220...240

Part No.

26969

Width in
18mm SP
ways
2

380...415

26971

N L
26979

3P + N

U>>

N L1

L2 L3

MN (under voltage release)


Instantaneous
U<

Width in
18mm SP
(V DC)
ways
26960
1
26961
1
48
26962
1
220...240 Delayed s
26963
2
Disconnects the MCB when a voltage is removed.

D1 D2
26963

New

MNx release for opening PB


Ph + N

U<

26969

E1 E2

Ph to Ph

U<

E1 E2

L1 L2

25

Electrical auxiliaries
For DPN, C60 and C120
SD fault indicating switch
Part No.

26927

Width in
18mm SP
ways
0.5

Contact rating

94 92

91

26927

(V)
240V ac
415V ac
24V dc
48V dc
125V dc

(A)
6A
3A
6A
2A
1A

(V)
240V ac
415V ac
24V dc
48V dc
125V dc

(A)
6A
3A
6A
2A
1A

OF auxiliary contact
Part No.

26924

Width in
18mm SP
ways
0.5

Contact rating

14 12

11

26924

OF + SD/OF selector switch


Part No.
voltage
26929

26929

26

24 22
92 94

21
91

Width in
18mm SP
ways
0.5

TM remote control

New

For C60 and C120


Applications
The TM unit provides remote control of C60 and C120 circuit breakers via an
electrical signal. For security or energy management, TM can be used to control
lighting motors or heating.

OF+SD/OF
auxiliary
contact

OF
auxiliary
contact

SD
fault
indication
switch

MN s , MNx or MSU
auxiliary

MX + OF or MN
auxiliary

TM
remote control

Tm modules allow:

Technical data

Remote control of C60/C120 circuit breakers (with


or without a Vigi module)via a latched order.
Circuit breaker resetting after tripping, while
respecting safety rules and regulations in force.
A disconnection selector switch placed on the
front panel is used to:
Disconnect the remote control,
Lock the remote controlled circuit-breaker in the
"open"position (7 mm padlock not supplied).
A mechanical indicator shows the "open" or
"closed"status of the Tm remote control.
Reclosing after a fault:
Must be carried out in manual mode,locally after
search and clearance of the fault.
To enable manual and local resetting, an SD
auxiliary switch (cat.no.26927),cabled in series in
the control line of the Tm to module, prevent
automatic remote reclosing,
Remote reclosing is possible provided regulations
are complied with:resetting takes place by
opening the control circuit for more than 1.5 s.

Circuit
breaker

Control voltage (Uc): 230 V AC (-15 %+10 %)


Frequency: 50 60 Hz.
Consumption:
Inrush: -TmC60:28 VA, -TmC120:35 VA.
Holding: 2 VA.
Insensitive to brownouts: 0.45 s.
Undervoltage behaviour:
>0.45 s,mechanical opening of poles,
Reclosing 2 s after power is restored.
Number of cycles (O-C)at 40C:
Tm +C60:20 000,
Tm +C120 (63 A):10 000,
Tm +C120 (80 125 A): 5 000.
Opening time by Tm: 0.5 s
Closing time by Tm: 2 s

Connection

Using tunnel terminals:


1 x 6mm2 cable,
2 x 1.5mm2 or 2.5mm2 cables.

Weight

1-2P: 300g.
3-4P: 310g.

27

TM remote controls

New

For C60 and C120

A1
MX
auto

MN

Possible
Voltage
combinations (V)

Part No.

C60 1-2P
C120 1-2P

18310
18312

230
230

Width in
18mm SP
ways
3.5
3.5

230V ~
SD
OF

A2
18310

A1
MX
auto

MN

230V ~
SD
OF

A2

18311

28

Possible
Voltage
combinations (V)

Part No.

C60 3-4P
C120 3-4P

18311
18313

230
230

Width in
18mm SP
ways
3.5
3.5

Accessories
For C60 and C120
Padlocking facility
Breaker
C60
C120

Quantity
Bag of 5
Bag of 2

Part No.
MGLA
27145

Breaker
C60

Quantity
Sealable bag of 2

Part No.
26981

Breaker
C60 Vigi

Quantity
Sealable bag of 10

Part No.
26982

Breaker
C120

Quantity
Sealable and
dividable bag of 2

Part No.
18527

Breaker
C60

Pole
1
2
3
4

Part No.
26975
26976
26975
26976 + 26978

Breaker
C120

Pole
1
2
3
4

Part No.
18526
2 x 18526
3 x 18526
4 x 18526

Breaker
C60/C120

Quantity
Bag of 4

Part No.
19091

Breaker
C60/C120

Quantity
Bag of 1

Part No.
27060

26970

Screw shield

Screw shield

18527

Screw shield

Terminal shield

Terminal shield

18526

Insulated sub distribution terminal

Aluminium cable terminal

27060
29

Accessories
For C60 and C120
Screw connection
Breaker
C60/C120

Quantity
Bag of 8

Part No.
27053

Breaker
C60/C120

Quantity
Bag of 2

Part No.
18528

Breaker
C60/C120

Quantity
Bag of 10

Part No.
27001

Breaker
C60/C120

Width
9mm

Part No.
27062

Rear connection terminal with 1P terminal shield

18528

Inter-pole barrier

Spacer

27062

Marker strips
Breaker
C60/C120

See page 31

Label holder
Breaker
C120

Quantity
Bag of 10
replacements

Part No.
27150

Pole
2
3
4

Part No.
26483
26484
26485

Replacement wire cover for vigibloc


Breaker
C60
Bag of 5
replacements
26483

30

Marking accessories

New

C60 and C120


Applications
These clip on markers allow circuit breakers or residual current circuit breakers to
be marked.

Marking

C60: 6 identification markers for the protected


outgoer, on front face.
DPN, C60 and C120: 4 markers for the
terminals.

Packing

Box of 250 markers.

Markers

27017

27003

Number
0
1
2
3
4
5
6
7
8
9

Part No.
27017
27029
27030
27031
27032
27033
27034
27035
27036
27037

Letter
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z

Part No.
27003
27004
27005
27006
27007
27008
27009
27010
27011
27012
27013
27014
27015
27016
27017
27018
27019
27020
27021
27022
27023
27024
27025
27026
27027
27028

Marker
+
Blank

Part No.
27038
27039
27040

Miscellaneous

31

NG125 circuit breakers

New

Selection
Circuit breakers
Standard

Number
of poles

Rating
(A)

Type

Curves

Magnetic
threshold
In

BS EN 60947-2

1, 2

1080

NG125N

3, 4

10125

NG125N

3, 4

80125

NG125N

3, 4

80125

NG125N

12

1, 2, 3, 4

1080

NG125H

2, 3

1.680

NG125LMA

MA

12

Rating

Type

Breaking capacity at 415V


(kA)
16
25
36
50

Trip free switch disconnector


Standard

Number
of poles
3, 4

BS EN 60947-3

80, 100, 125 NG125NA

Earth leakage modules for trip free circuit breakers and switch disconnectors
Standard

BS EN 60947-2

Number
of poles
2, 3, 4

Rating
In at 400C
(A)
63

Vigi
type

Sensitivity
(mA)
Instantaneous
Vigi NG125 30
300

300
1000

125

Vigi NG125 30

300-500-1000

125

Vigi NG125 30
300

300-500-1000

(1) Only in 3P and 4P.


Note: This product is not suitable for use with Isobar 4 pan assemblies.

32

Selective s

Instantaneous
or selective

Instantaneous
or selective s
or delayed 150ms
300-500-1000-3000
with fault threshold
indication (1)
300-500-1000-3000
with fault threshold
indication
300-500-1000-3000
with fault threshold
indication

NG125 circuit breakers

New

Selection

Choice of circuit-breakers
Type
Impulse voltage Uimp (kV)
Insulation voltage Ui (V)
Maximum voltage rating Ue (V)
Number of poles
Breaking
Icu
AC 110130V
capacity
220240V
(kA)
380415V
IEC 947.2
440V
500V
DC 60V
125V
250V
500V
Ics
AC
DC
Tripping
B curve
40C
curves
C curve
40C
/ratings (A)
D curve
40C

NG125N
8
690
500
1
50
25
6

25

75% Icu
100% Icu

MA curve
Fast closing
Positive break indication
Auxiliaries
Degree of pollution 3

40C

1080

2, 3, 4

50
25
20
10

25 (2P)
25 (4P)

75% Icu
100% Icu
80125
10125
80125

NG125H
8
690
500
1
70
36
9

36

75% Icu
100% Icu
1080

2, 3, 4

70
36
30
12

36 (2P)
36 (4P)

NG125LMA
8
690
500

2, 3

100

50

40

15

1080

1.680

18668

33

NG125 switch disconnectors

New

BS EN 60947-3

Applications
The NG125NA is a trip-free switch-disconnector for on-load opening and closing.

This modular device has the same


auxiliary functions and accessories as
the NG125 circuit breaker.

Vigi NG125 module for earth leakage protection.


OF + SD auxiliary contact.
MX or MN releases.
Various connection types (80, 100 and 125A
ratings).
Rotary handle.This modular device has the same
auxiliary.

Common technical data

Ratings: 63125A.
maximum voltage rating Ue: 500V AC.
Performance as in BS EN 60947.3.
Short-time withstand current (50 ms) Icw:
1.5 kA.
Maximum making capacity: see co-ordination
tables.
Maximum insulation voltage Ui: 690V.
Impulse voltage Uimp: 8 kV
Electrical durability:
Voltage
Category
63/80A
100/125 A
500V AC
AC22B
1500
1000
440V AC
AC22B
1500
1000
415V AC
AC22A-AC23B 1500
1000
125V DC
DC22A
1500
1000
(2P series)
250V DC
DC22A
1500
1000
(4P series)
Isolation with positive contact indication.
Built-in padlocking facility.
Weight (g):
Type
3P
4P
720
960

Compatible with Pragma or Prisma G or P


modular enclosures.
connection: tunnel terminals for flexible and rigid
copper cables up to 70 mm2.

3P
1

Maximum
rating
(A)
63
80
100
125

Part No.

Maximum
rating
(A)
63
80
100
125

Part No.

18889
18890
18891
18892

Width in
18mm SP
ways
4.5
4.5
4.5
4.5

4P

34

18893
18894
18895
18896

Width in
18mm SP
ways
6
6
6
6

NG125N circuit breakers

New

B curve
BS EN 60947-2: 25kA
Applications
This circuit-breaker is specially designed for functions requiring a high breaking
capacity (up to 25 kA): modular enclosure incomer, main incomer in sub-distribution
switchboards, outgoer, protection of loads directly supplied by a power switchboard.

Common technical data


Rating: 10125A.
Reference temperature: 40C.
Uimp: 8kV.
Ui: 690V
Maximum voltage rating: 500V AC.
Breaking capacity: as in BS EN 60947-2:
Type
Voltage
Breaking capacity
(V AC)
(A)
1P
220240
25000
1P
380415
6000 (1)
2, 3, 4P
380415
25000
(1) 1-pole breaking capacity in the IT isolated neutral
system (double fault).

Isolation with positive contact indication.


3-position toggle: open-tripped-closed.
Built-in padlocking facility on 3P and 4P.
Fault display on front face by:
Fault indicator,
Position of toggle: tripped.
Test button to check proper operation of the
tripping mechanism.
Fast closing.
Electrical durability: 10,000 cycles at In.
Tropicalisation as in IEC 68.1: treatment 2
(relative humidity: 95% at 55C).

B curve NG125N
3P
1

Weight (g):
Type
1P
240

2P
480

3P
720

4P
960

Compatible with the Pragma F24 and Prisma


G/GX enclosures and the Prisma P cabinets.
Degree of protection: IP20B (IP40D for the part
outside the enclosure).
Connection:
63 A ratings: tunnel terminals for 1.5 to 50mm2
copper cables,
80 to 125 A ratings: tunnel terminals for
16 to 70mm2 copper cables,
Aluminium cables, copper cables with lug or
busbar (see connection accessories),
On 3P and 4P: upstream voltage connection on
each pole, by 6.35mm Fast-on lugs, for auxiliary
circuit supply.

B curve

The magnetic trip units operate at 4 In 20%.

C curve

The magnetic trip units operate at 8 In 20%.

D curve

The magnetic trip units operate at 12 In 20%.

Rating
(A)

Part No.

80
100
125

18663
18664
18665

Rating
(A)

Part No.

80
100
125

18666
18667
18668

Width in
18mm SP
ways
4.5
4.5
4.5

18664
2

4P
7

Width in
18mm SP
ways
6
6
6

18668
2

35

NG125N circuit breakers

New

C curve
BS EN 60947-2: 25kA
C curve NG125N
1P
1

18610
2

Rating
(A)

Part No.

10
16
20
25
32
40
50
63
80

18610
18611
18612
18613
18614
18615
18616
18617
18618

Rating
(A)

Part No.

10
16
20
25
32
40
50
63
80

18621
18622
18623
18624
18625
18626
18627
18628
18629

Rating
(A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18632
18633
18634
18635
18636
18637
18638
18639
18640
18642
18644

Rating
(A)

Part No.

10
16
20
25
32
40
50
63
80
100
125

18649
18650
18651
18652
18653
18654
18655
18656
18658
18660
18662

Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

2P
1

18621
2

Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3

3P
1

18632
2

Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

4P
1

18662
2

36

Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6
6
6

NG125N circuit breakers

New

D curve
BS EN 60947-2: 25kA
D curve NG125N
3P
1

Rating
(A)

Part No.

80
100
125

18669
18670
18671

Rating
(A)

Part No.

80
100
125

18672
18673
18674

Width in
18mm SP
ways
4.5
4.5
4.5

18669
2

4P

18674

Width in
18mm SP
ways
6
6
6

37

NG125H circuit breakers

New

C curves
BS EN 60947-2: 36kA
Applications
This circuit-breaker is specially designed for functions requiring a high breaking
capacity (up to 36 kA): main incomer in sub-distribution switchboards; outgoer,
protection of loads directly supplied by a power switchboard.

Common technical data


Rating: 1080A.
Reference temperature: 40C.
Uimp: 8kV.
Ui: 690V.
Maximum voltage rating: 500V AC.
Breaking capacity: as in BS EN 60947-2:
Type
Voltage
Breaking capacity
(V) AC
(A)
1P
220240
36000
1P
380415
9000 (1)
2, 3, 4P
380415
36000
(1) 1-pole breaking capacity in IT isolated neutral
systems (double fault).

Isolation with positive break indication.


3-position toggle: open-tripped-closed.
Built-in padlocking facility on 3P and 4P.
Fault display on front face by:
Fault indicator,
Position of toggle: tripped.
Test button to check proper operation of the
tripping mechanism.
Fast closing.

Electrical durability: 10,000 cycles at In.


Tropicalisation as in IEC 68.1: treatment 2
(relative humidity: 95% at 55C).
Weight (g):
Type
1P
2P
3P
4P
240
480
720
960

Compatible with Pragma F24 and Prisma G/GX


enclosures and Prisma P cabinets.
Degree of protection: IP20B (IP40D for the part
outside the enclosure).
Connection:
63 A ratings: tunnel terminals for 1.5 to 50mm2
copper cables,
80 A rating: tunnel terminals for 16 to 70mm2
copper cables,
Connection of aluminium cables, copper cables
with lug or busbar for 3P and 4P (see connection
accessories),
Upstream voltage connection on each pole, by
6.35mm Fast-on lugs, for auxiliary circuit supply.

C curve

The magnetic trip units operate at 8 In 20%.

1P
1

18705
2

Rating
(A)

Part No.

10
16
20
25
32
40
50
63
80

18705
18706
18707
18708
18709
18710
18711
18712
18713

Rating
(A)

Part No.

10
16
20
25
32
40
50
63
80

18714
18715
18716
18717
18718
18719
18720
18721
18722

Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

2P
1

18714
2

38

Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3

NG125H circuit breakers

New

C curve
BS EN 60947-2: 36kA
3P

18723

Rating
(A)

Part No.

10
16
20
25
32
40
50
63
80

18723
18724
18725
18726
18727
18728
18729
18730
18731

Rating
(A)

Part No.

10
16
20
25
32
40
50
63
80

18732
18733
18734
18735
18736
18737
18738
18739
18740

Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

4P

18732

Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6

39

NG125 circuit breakers

New

MA curve (magnetic only)


BS EN 60947-2: 50kA
Applications
The NG125LMA circuit-breakers are designed to protect motor supply circuits
(cables and starters) against short-circuit current. These devices can be used in
conjunction with Telemecanique overload relays to achieve total motor protection.

Common technical data


Trip units: 1.680A.
Reference temperature: 40C.
Uimp: 8kV.
Ui: 690V.
Maximum voltage rating: 500V AC.
Breaking capacity: as in BS EN 60947-2:
Type
Voltage
Breaking capacity
(V)
AC (A)
2, 3P
380415
50000

Isolation with positive contact indication.


3-position toggle: open-tripped-closed.
Built-in padlocking facility on 3P.
Fault display on front face by:
Fault indicator,
Position of toggle: tripped.
Test button to check proper operation of the
tripping mechanism.
Fast closing.

Electrical durability: 10,000 cycles at In.


Tropicalisation as in IEC 68.1: treatment 2
(relative humidity: 95% at 55C).
Weight (g):
Type
2P
3P
480
720

Compatible with Pragma and Prisma G/GX


enclosures and Prisma P cabinets.
Degree of protection: IP20B (IP40D for the part
outside the enclosure).
Connection:
Trip units up to MA63: tunnel terminals for 1.5 to
50mm2 copper cables,
MA80 trip units: tunnel terminals for 16 to 70mm2
copper cables,
On 3P, upstream voltage connection on each
pole, by 6.35mm Fast-on lugs, for auxiliary circuit
supply.

MA curve

The magnetic trip units operate at 12 In 20%.

2P
1

18868
2

Trip unit
(A)

Magn. I

Part No.

MA4
MA6.3
MA10
MA12.5
MA16
MA25
MA40
MA63
MA80

50
75
120
150
190
300
480
750
960

18868
18869
18870
18871
18872
18873
18874
18875
18876

Trip unit
(A)

Magn. I

Part No.

MA4
MA6.3
MA10
MA12.5
MA16
MA25
MA40
MA63
MA80

50
75
120
150
190
300
480
750
960

18879
18880
18881
18882
18883
18884
18885
18886
18887

Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3

3P

40

Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

NG125 Vigi

New

Selection

18668

19049

Vigi module A class


Adjustable

Non adjustable

300, 500, 1000 mA


instantaneous, selective s
300, 500, 1000, 3000 mA
instantaneous, selective, delayed
30 mA
300 mA
300 mA selective s
1000 mA selective s

10 - 63A
Page

Pole
3P, 4P

Page
45

3P, 4P

45

3P, 4P

45

43
45
45
45

3P, 4P
4P

2P,
2P,
2P,
2P,

3P,
3P,
3P,
3P,

4P
4P
4P
4P

Vigi module AC class

10 - 63A

Non adjustable

Pole
2P, 3P, 4P
2P, 3P, 4P

30 mA
300 mA

80 - 125A

Pole

43
45

Page
42
44

Vigi module si class

80 - 125A

Adjustable

Pole
3P, 4P

Page
45

3P, 4P

43

Non adjustable

300, 500, 1000, 3000 mA


instantaneous, selective, delayed
30 mA

41

NG125 high sensitivity Vigi

New

30mA instantaneous, BS EN 61008


(AC class)
Applications
Combined with an NG125 MCB, vigi units provide protection against indirect and
supplementary protection against contact with live parts.

Technical data

In the presence of equipment containing rectifying


devices (diodes, thyristors, triacs), use an A class
residual current circuit breaker, to guarantee
tripping on detection of a DC component of earth
fault.
Incorporates in a single case:
The residual current relay,
The toroid.
Connection to the circuit breaker by rigid links
(compact size) insulated by a shield
(supplied) (degree of protection IP40D).
Earth fault display on the front face of the Vigi
module by reset handle.
Voltage rating: 230415 VAC.
Frequency: 50/60Hz.
Uimp: 8kV.
Ui: 690V.
Protection against nuisance tripping due to
transient overvoltages (lightning, switchgear
switching on the network, etc.).

Tripping by direct mechanical action on the circuit


breaker.
Rated current: 63A or 125A with locating
device:
63A for < 63A circuit breakers,
125A for 80, 100 and 125A circuit breakers.
Auxiliaries that can be plugged onto Vigi
125A:
Remote tripping by MXV shunt trip,
Remote indication of earth fault trip by SDV
auxiliary switch.
Weight (g) of Vigi only:
Type
2P
3P
4P
5 mod.
250

9 mod.

410
450
11 mod.

750
800

Connection:
63 A ratings: tunnel terminals for 1.5 to 50mm2
copper cables,
80 to 125 A ratings: tunnel terminals for 16 to
70mm2 copper cables,
Aluminium cables, copper cables with lug (see
connection accessories).

Class AC ~
2P
1

Sensitivity
(mA)

I Max.
(A)

Part No.

30

63

19000

Sensitivity
(mA)

I Max.
(A)

Part No.

30

63

19002

Sensitivity
(mA)

I Max.
(A)

Part No.

30

63

19004

Width in
18mm SP
ways
2.5

2 4

3P
1

5
T

Width in
18mm SP
ways
4.5

2 4 6

4P
1

7
T

2 4 68

42

Width in
18mm SP
ways
4.5

NG125 high sensitivity Vigi

New

30mA instantaneous, BS EN 61008


(A class)
Class A
2P
1

I Max.
(A)

Sensitivity
(mA)

Part No.

63
125

30
30

19010
19008 (1)

I Max.
(A)

Sensitivity
(mA)

Part No.

63
125

30
30

19013
19039

I Max.
(A)

Sensitivity
(mA)

Part No.

63
125

30
30

19015
19041

I Max.
(A)

Sensitivity
(mA)

Part No.

125

30

19100

I Max.
(A)

Sensitivity
(mA)

Part No.

125

30

19101

Width in
18mm SP
ways
2.5
2.5

2 4

19010

(1) Voltage rating: 110...220V AC.

3P
1

5
T

Width in
18mm SP
ways
4.5
5.5

2 4 6

4P
1

7
T

Width in
18mm SP
ways
4.5
5.5

2 4 68

Class A

si type

3P
1

5
T

Width in
18mm SP
ways
5.5

2 46

4P
1

6
T

Width in
18mm SP
ways
5.5

2 4 68

43

NG125 sensitivity Vigi

New

Instantaneous, selective, time delayed (300 - 3000mA)


BS EN 61008 (AC class)

In the presence of equipment containing rectifying


devices (diodes, thyristors, triacs), use an A class
residual current circuit breaker to guarantee
tripping on detection of a DC component.
Incorporates in a single case:
The residual current relay,
The toroid.
Connection to the circuit-breaker by rigid links
(compact size) insulated by a shield (supplied).
Earth fault display:
On the front face of the Vigi by reset handle.
Protection against nuisance tripping due to
transient overvoltages (lightning, switchgear
switching on the network, etc.).
Rated current: 63 or 125A with locating device:
63 A: for 63 A circuit-breakers,
125 A: for 80 - 100 - 125A circuit breakers.
Frequency: 50/60Hz.

Specific technical data of the adjustable


vigi

In sensitivity adjustable by index: 300, 500,


1000, 3000mA
Adjustable tripping time:
Instantaneous,
Selective: 60ms,
Delayed: 150ms.
Leakage current indication on 3P and 4P
3003000 I/S/D :
On the front face by LED,
Remotely, by 250V - 1A (low level) volt free NO
contact, connected by 2 x 1.5 mm 2 plate
terminal,
Threshold setting by potentiometer from 10 to
50% of In.
Disconnection essential for dielectric testing by
built-in pushbutton.
Auxiliaries plugged onto 125A and 63A Vigi I/S/D.
Remote tripping by MXV shunt trip,
Remote indication of earth fault trip by SDV
auxiliary switch.
Weight (g) of Vigi only:
Type
2P
3P
4P
5 mod.
250

9 mod.

410
450
11 mod.

750
800

Class AC ~
2P
1

I Max.
(A)

Sensitivity
(mA)

Part No.

63

300

19001

I Max.
(A)

Sensitivity
(mA)

Part No.

63

300

19003

I Max.
(A)

Sensitivity
(mA)

Part No.

63

300

19005

Width in
18mm SP
ways
2.5

2 4

3P
1

5
T

Width in
18mm SP
ways
4.5

2 4 6

4P
1

7
T

2 4 68

44

Width in
18mm SP
ways
4.5

NG125 medium sensitivity Vigi

New

Instantaneous, selective, delayed (300 - 3000mA)


BS EN 61008 (A class)
Class A
2P
1

I Max.
(A)

Sensitivity
(mA)

Part No.

63

2 4

300
300
300 s
1000 s
(1) Voltage rating: 110...220V AC.

19012
19009 (1)
19030
19031

I Max.
(A)

Sensitivity
(mA)

Part No.

63

300
300 s
1000 s
3003000
3003000
3001000
3003000
3003000

19014
19032
19033
19036
19053 (2)
19044
19047
19055 (2)

Width in
18mm SP
ways
2.5
2.5
2.5
2.5

19049

3P
1

2 4 6

125

I/S/D
I/S/D
I/S
I/S/D
I/S/D

Width in
18mm SP
ways
4.5
4.5
4.5
5.5
5.5
5.5
5.5
5.5

(2) Voltage rating: 440/415V AC, without early warning function.


4P

I Max.
(A)

7
T

63

300
300 s
1000 s
3003000 I/S/D
3003000 I/S/D
125
300
3001000 I/S
3003000 I/S/D
3003000 I/S/D
(2) Voltage rating: 440/415V AC,

2 4 68

Class A
3P

Part No.

Width in
18mm SP
ways
19016
4.5
19034
4.5
19035
4.5
19037
5.5
19054 (2)
5.5
19042
5.5
19046
5.5
19049
5.5
19056 (2)
5.5
without early warning function.

si type

Sensitivity
(mA)

I Max.
(A)

Sensitivity
(mA)

Part No.

125

3003000 I/S/R

19106

I Max.
(A)

Sensitivity
(mA)

Part No.

125

3003000 I/S/R

19107

Width in
18mm SP
ways
5.5

2 4 6

4P
1

7
T

Width in
18mm SP
ways
5.5

2 4 68

45

NG125 and NG125 Vigi

New

Electrical auxiliaries
Applications
MX+OF, MXV shunt trip

OF+SD, OF+OF, SDV auxiliary contacts

Trips the circuit breaker or vigi (MXV) when a voltage


is applied.

MN, MN undervoltage release

Remotely indicates:
The "open" or "closed" position (OF).
a fault on the circuit-breaker (SD) or Vigi module
(SDV).

Trips the circuit breaker when the voltage is


disconnected.

Early warning

Delayed MN s undervoltage release

Provides delayed tripping of the circuit breaker to


which it is attached.

Common technical data

Complies with standard:


BS EN 60947-5-1 (MX + OF, OF + SD, OF + OF
and SDV),
BS EN 6094712 (MN, MN s , MX and MXV).
Electrical durability: 10,000 cycles (AC 15):
Ui: class 2 insulation : 690V,
Uimp: 8kV,
Degree of pollution: 3.

This function is performed by light indication and


fault free contact.
Built in adjustable Vigi modules, 300 to 3000mA,
of the I/S/R/ type from 230 to 415V AC.
Connection: plate terminal for:
1 or 2 flexible or rigid 2.5mm2 cables,
2 x 2.5mm2 uninsulated cable ends,
2 x 1.5mm2 insulated cable ends,
2 x 1.5mm2 fork lugs.

NG125 with residual current circuit breaker


or device

Technical data for circuit breaker


auxiliaries
OF+OF

Auxiliary contact.

OF+SD

Fault indicating switch.

MX+OF

Shunt releases.
Tripping: on energisation.
Equipped with a contact allowing self breaking.

MN

Undervoltage release.
Tripping and opening of the associated circuit
breaker: if supply voltage drops between 70 and
35%.
Reclosing: forbidden if supply voltage is not
restored (e.g.: emergency breaking by
pushbutton).

MN s

46

delayed undervoltage release


Allows a 0,25 second time delay on brownout or
voltage drop.

Technical data for Vigi module


auxiliaries

Can be added to:


All types of 125A Vigi module,
63 A 3003 000 I/S/D Vigi module SDV.
Fault indicating switch.

MXV

Shunt releases.
Tripping: on energisation
Equipped with a contact allowing self breaking.
Impulse withstand: 6kV
High impedance input: use an ACTp if leakage
current is greater than 1mA.

MNx

Undervoltage release unaffected by power cuts.

NG125 and NG125 Vigi

New

Electrical auxiliaries
Auxiliaries for circuit breaker
OF + OF
11

12 14

21

Voltage
(V AC)

Part No.

220-240 (6A)

19071

Voltage
(V AC)

Part No.

220-240 (6A)

19072

Voltage
(V AC)

Part No.

240 (6A)

19073

Width in
18mm SP
ways
0.5

22 24

19071

Fault indicating switch


11 12 14
OF + SD

95

Width in
18mm SP
ways
0.5

98 96

19072

OF+OF or OF+SD
11

12 14

Width in
18mm SP
ways
0.5

21 22 24
95 98 96
19073

Shunt trip
MX + OF

Voltage
(V AC)

(V DC)

Part No.

230-415

110-130

19064

Width in
18mm SP
ways
1

48-130
24

48
24

19065
19066

1
1

U>

14 12 C2 C1
19064

47

NG125 and NG125 Vigi

New

Electrical auxiliaries
Undervoltage release
MN

Voltage
(V AC)

Part No.
(V DC)

U>

220-240
48
48
D1

19067
19069
19070

Width in
18mm SP
ways
1
1
1

D2

19067

Undervoltage release with 0.5s time delay


MN s

Voltage
(V AC)

Part No.

230-240

19068

Voltage
(V AC)

Part No.

NO 250 (0.1 - 2A)


NC 250 (0.1 - 2A)

19058
19059

Voltage
(V AC)

Part No.

110-240

19060

U>

D1

Width in
18mm SP
ways
2

D2

19068

Auxiliary contacts for Vigi module


SDV

11

12 13

Width in
18mm SP
ways
-

14

19058

MXV

Width in
18mm SP
ways
-

U>

M1
19060

48

M2

Note: High impedance output (use an ACTP Cat. No. 15919, if the leakage current of the control device is
greater than 1mA).

Distribloc
125A splitters
Applications
Distribloc is a fully insulated four pole modular splitters.
Connection by screw terminals or spring terminals.

Technical data

Connection

Rated insulation voltage: 690V.


Permissible peak current: Ipk = 20kA.
Complies with the low voltage switchgear
standard: BS EN 60947-7-1.
Rated current at 40C: 125A.
Installation:
Clipped onto a symmetrical rail,
Fits onto a row next to other modular device:
- 45 mm nose.
- 12 mod. of 9mm.
Can be screwed onto a plain or mounting grid,
Cannot be installed in flush mounting Pragma
C12 and Pragma D18 enclosures.

Incomer:
Tunnel terminal for 35mm2 flexible or rigid cables,
Optional factory-built link for NG125 (catalogue
number: 07054).
Outgoer in spring terminals:
Minimum cross-section: 1mm2,
Simplifies rebalancing of phases and extensions,
Unaffected by temperature variations,
Spring contact pressure automatically adapted to
conductor cross-section,
A single cable without metal end per spring:
- by flexible cables: 2 x 10mm2 + 3 x 6mm2 +
7 x 4 mm2,
- by rigid cables: 2 x 16mm2 + 3 x 6mm2 +
7 x 4mm2,
Outgoer in screw terminals: 1x16mm2 or 25mm2
flexible or rigid cables.

Distribloc
Type

Part No.

Distribloc 125A
Set of 4 125A
flexible links

07105

Width in
18mm SP
ways
6

07054

Distribloc 125

49

NG125 and NG125 Vigi

New

Accessories
Applications
The following NG125 accessories can be used to increase flexibility and simplify
installation.

Rotary handle

Screw shield

Insulated sub-distribution terminal

Prevents contact with device terminal screws.


Protection against direct contact:
IP40D: on the front face,
IP20B: at connection level.
Optional sealing terminal shield for circuit breaker.

Installation: mounted upstream and downstream


of the circuit breaker/vigi.
Phase-to-phase insulation voltage Ui = 1000V.
Protection against direct contact: IP40D.
Class II in metal or plastic enclosures (up to
440V).
Optional sealing terminal shield for residual
current device.
Installation: mounted upstream of the circuit
breaker and downstream of the Vigi module.
Phase-to-phase insulation voltage Ui = 1000V.
Protection against direct contact: IP40D.
Class II in metal or plastic enclosures (up to
440V).
Optional sealing.

Tunnel terminals for copper cables

Cable cross-section:
For 63 A ratings:
- flexible cable: 1 to 35mm2,
- rigid cable: 1.5 to 50mm2.
For 80-100-125 A ratings:
- flexible cable: 10 to 50mm2,
- rigid cable: 16 to 70mm2.
Tightening torque and tool type:
For 63 A ratings: 3.5 Nm with 6.5 mm flat
screwdriver or PZ n 2 (Pozidrive recessed head
screw),
For 80-100-125 A ratings: 6 Nm with 4 mm Allen
wrench (hexagon socket screw).
Degree of protection: IP20B.

Cable cross-section for all ratings (circuit


breaker only):
Flexible cable: 1 to 10mm2,
Rigid cable: 1.5 to 16mm2,
With ends: up to 4mm2 inclusive.
Tightening torque and tool type: 2 Nm with
5.5mm flat screwdriver or PZ N 1 (Pozidrive
recessed head screw).
Phase-to-phase insulation voltage: Ui = 1000V.

Matching terminals for 70mm2


aluminium cables

Cable cross-section for 80,100 and 125A ratings:


2570mm2.
Tightening torque and tool type: 6Nm with 4mm
Allen wrench (hexagon socket screw).

Screws and nuts


for lug and bar connection

Installation: upstream or downstream.


Connection of 80, 100 and 125A ratings:
copper lug:
- flexible cable up to 35mm2,
- rigid cable up to 50mm2,
Bars: 16x3mm, 15x4mm
Lugs with small eyelet hole.
Tightening torque and tool type: 6Nm with Allen
4mm wrench (M6 screw).
Phase-to-phase insulation voltage: Ui = 1000V.

Cable lugs

Extended rotary handle

Comb busbar

Installation: front.
Utilisation: circuit breaker control from outside
the enclosure.
Retains isolation/padlocking in the O position (3
padlocks).
IP55.
3 positions.
Door interlocking: opening possible in O position
only direct rotary handle.

Padlocking accessory

50

Copper cable sub-distribution terminals

Terminal shield

Holes for 3 cables:


16mm2 rigid cables,
10mm2 flexible cables.

Enables padlocking (in l or O position) of 1P


or 2P NG125 circuit-breakers:
In l position of 3P or 4P NG125 circuit-breakers
Note: the 3P/4P NG125 circuit-breakers are
factory-designed for padlocking in the O position
(isolated).
Padlock: 5 to 8 mm (not supplied).

Connection of 80, 100 and 125A ratings:


Flexible copper cable: 50mm2,
Rigid copper cable: 70mm2.

Utilisation: for NG125 circuit-breaker up to 63A.


direct supply by circuit-breaker terminal (50mm2
max. rigid cable).
Tooth shield available for unused teeth.
Length (dividable): 16 modules of 27mm,
i.e. 48 modules of 9mm.
125 A max. upstream.
Insulation voltage: 690V.
Uimp: 8kV.
Degree of protection when used with toothshield ends: IPxxB.

NG125 and NG125 Vigi

New

Accessories
Screw shield for circuit breaker
Bag of 10

19087

Type
1P
2P
3P
4P

Part No.
19084
19085
19086
19087

Type
1P
2P
3P
4P

Part No.
19080
19081
19082
19083

Terminal shield for circuit breaker


The set

19080

Terminal shield for residual current device (Set of)


63A

19076

125A

Type
2P
3P
3P adjustable
4P
4P adjustable
3P
4P

Part No.
19074
19075
19077
19076
19078
19077
19078

Type
Standard, black
Red handle
yellow background

Part No.
19088
19089

Type
Bag of 4

Part No.
19090

Type
bag of 4

Part No.
19091

Rotary handle

19088

Padlocking accessory

19090

Insulated sub-distribution terminal

19091

Screws and nuts for lug or bar connection


Part No.
19093

19093

Cable lugs
Type
4 supplied

Part No.
19094

4 supplied

19095

Type
1P
2P
3P
4P
Tooth-shield end (set of 20)

Part No.
14811
14812
14813
14814
14818

Matching terminal for aluminium cable


19094

Comb busbar

14813

51

P25M Motor protection circuit breaker


Ratings: 0.1 to 25A
BS EN 60947-2
Installation

Symmetrical DIN rail.

Technical data

P25M circuit breaker

Phase failure sensitive.


Temperature compensation: -20 to +400C in
enclosure.
Current ratings (In): 0.1 0 25A.
Voltage ratings (Ue): 690 V ac.
Breaking capacity: BS EN 60947-2.

Voltage (V)
230,240
400,415
440
500
Icu Ics Icu Ics Icu Ics Icu
in
in
in
in
in
in
in
Rating kA
%
kA
%
kA
%
kA
(A)
0.16
to
self protected
1.6
2.5
4
6.3
50 100 50
10
15 100 10
14
15 50
8
50
6
18
15 50
8
50
6
23
50 100 15 40
6
50
4
25
50 100 15 40
6
50
4

Ics
in
%

690
Icu
in
kA

Ics
in
%

100
100
75
75
75
75

3
3
3
3
3
3
3
3

75
75
75
75
75
75
75
75

Operating cycles: 100,000 AC3.


Positive contact indication in accordance with
BS7671.
Width: 2.5 SP ways (45mm).
Weight (g):
Cable capacity: min 2 x 1mm2 rigid,
max. 2 x 6mm2 flexible.
Approvals: CEBEC, DEMKO, NEMKO,
SEMKO, F1.
Accessories: see page 54.
Technical data: see page 178.

Rating
In (A)
0.16
0.25
0.40
0.63
1.0
1.6
2.5
4.0
6.3
10
14
18
23
25

Settings

Part No.

0.1 - 0.16
0.16 - 0.25
0.25 - 0.40
0.40 - 0.63
0.63 - 1.0
1.0 - 1.6
1.6 - 2.5
2.5 - 4.0
4.0 - 6.3
6.0 - 10
9.0 - 14
13 - 18
17 - 23
20 - 25

21100
21101
21102
21103
21104
21105
21106
21107
21108
21109
21110
21111
21112
21113

Limiter block
Increases the breaking capacity to 100kA up to 415V.
Individual mounting (upstream) or on the terminal
block part no. 21144 .

21115

52

Connection: tunnel terminal for flexible cable up


to 25mm2.
Dimensions: see page 134.

Width in Rating Part


18mm
(A)
No.
SP ways
2.5
63
21115

P25M Motor protection circuit breaker


Auxiliaries
Auxiliary combination
P
O+F F+F
2
/
/
5
F+F O+F
M

P
O+F
MX
2
/
SD
/
5
F+F
MN
M

Remote indication:

Position:
O+F contact indicates ON or OFF position of the
P25M,
F+F contact double contact for ON position.
Position + alarm indicator: with red flag trip
indicator:
F+SD.O - ON position + OFF fault indication,
O+SD.O - OFF position + OFF fault indication,
F+SD.F - ON position + ON fault indication,
O+SD.F - OFF position + ON fault indication.

Width in 18mm
SP ways
0.5
Contact position O+F
0.5
Contact position F+F

43 31

33

44

34

21117
21116

Technical data
Voltage
Ue

Position (OF)

Fault (SD)

V AC
24
48
130
240
415
440
V DC
24
48
60
110
220

(A)

(A)
1.5
1
0.5
0.3

44

21118

6
4.5
3.3
2.2
1.5
DC 13
6
5
3
1.3
0.5

DC 13
1
0.3
0.15

Connection by terminal clamp:


Min.: rigid cables 2 x 1 mm2,
Max.: flexible cables 2 x 2.5 mm2,
Flexible cable with cable end 2 x 1.5 mm2.

MX shunt trip release: trips the P25M when


energised.
MN undervoltage release: trips the P25M when
the voltage supply drops (between 35% and 75%)
and prevents reclosing until the supply voltage
is restored.
Power consumption of releases:
AC
DC
(V.A)
(W)

MX
Pick up
14
10
Hold
5
1.6
MN
Hold
3.5
1.1
Connection by terminal clamp
Min.: rigid cables 2 x 1 mm2
Max.: flexible cables up to 2 x 2.5 mm2
Flexible cable with cable end 2 x 1.5 mm2

21116

Width in 18mm
SP ways
0.5
Position+alarm
contact F+SD.F
0.5
Position+alarm
contact O+SD.F
0.5
Position+alarm
contact F+SD.O
0.5
Position+alarm
contact O+SD.O
95 53

95 51

96 54

96 52

Part No.

21118
21119
21120
21121

21121

97 53

97 51

98 54

98 52

21118

Remote tripping

32

21117

21120

21127

43

Part No.

21119

Width
Voltage
18mm
(V)
SP ways
MX shunt trip release
1
220.240
380.415

Width
Voltage
18mm
(V)
SP ways
MN under voltage release
1
220.240
380.415

Frequency Part No.


(Hz)

50
50

21127
21128

Frequency Part No.


(Hz)

50
50

21129
21130

53

P25M Motor protection circuit breaker


Accessories
P25M insulated enclosure
(Surface mounting). Can incorporate 1 x P25M with 1 x
auxiliary contact and 1 x shunt or UVR release with
earth and neutral terminals.
Degree of protection: IP55.
Double insulation.
Sealable cover.
Indicator lamp can be installed on the front to
indicate the ON or OFF position.
4 knock outs for cable gland 16mm.

Dimensions: see page 134.


Part No.
21133

Enclosure
Neon indicator light 220.240V
21133

Neon indicator light 380.440V

green
red
green
red

21140
21142
21141
21143

Comb busbars P25M


3 Poles 63A
Power supply for several P25M up to 63A. Comb busbar
versions 2 or 4 outlets and the possibility of combining
comb busbar Auxiliary contacts can be installed
between the P25Ms.
Comb busbar
For 2 P25M units
For 4 P25M units

21146

Part No.
21145
21146

21145

Terminal block
For supply of busbars with cables up to 25mm2 (can
be installed with limiter block).
End cover (bag of 5 pcs)
Terminal block

Part No.
21148
21144

21144

Insulated connector
To supply comb busbars or P25M directly with cables
up to 25mm2.

Insulated connector

21147
54

Part no.
21147

RMG residual current devices


Ratings: 16 to 100A
Sensitivities: 10 to 300mA, time delayed
Application
Type RMG residual current devices provide the functions of isolation, switching and
earth leakage protection of electrical circuits. They have a residual current operated
electro-mechanical release which operates without any auxiliary source of supply to
open a circuit automatically in the case of an earth leakage fault between phase and
earth greater than or equal to a threshold of 10, 30, 100, or 300mA.

Type RMG RCD - two pole 240V


Rating
(A)
16
25
RMG 80 030 2

40

Specifications

63

RCD: BS EN 61008.

Technical data

Positive contact indication in accordance with


BS 7671.
Unwanted tripping
All RMG rcd's incorporate a filtering device preventing
the risks of unwanted tripping due to transient voltages
(lightning, line disturbances on other equipment...) and
transient currents (from high capacitive circuits.)

Electrical data

Current ratings: 16A to 100A.


Voltage ratings: 2 pole: 110/240V AC,
4 pole: 240/415V AC.
Cable capacities
16A-80A: tunnel terminals for cables up to 35mm2.
100A: clamp terminals for cables up to 50mm2.
Number of operating cycles: (on load) 20,000
cycles (O-C).
Operating temperature: -5 to +40C.
Identification system: All RMG RCD's can accept
up to a total of 4 marking accessories on each of
their poles. The following symbols are available:
Blank, 1-9, +, -, and A-Z. See page 31.

80

100

80
time delayed
100
time delayed
100
time delayed

Installation
On symmetrical DIN rail.
Panel mounting.
Note: RMG residual current devices must be used with
circuit breakers to provide circuit protection of overload
and short circuit faults.
Dimensions: see page 155.

3 phase 3 wire 415V applications


(No neutral present) Auxiliary test resistor required
(Installed externally as indicated)
30mA
2700
4 watt
100mA
820
4 watt
300 mA
270
4 watt
Note: Resistors are not available from Merlin Gerin.

Part No.
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG

16 010 2
25 010 2
25 030 2
40 030 2
40 300 2
63 030 2
63 100 2
63 300 2
80 030 2
80 100 2
80 300 2
100 030 2
100 100 2
100 300 2

23111 (50-70mS)
300
23116 (50-70mS)
100
RMG 1001002S

Type RMG RCD - four pole 415V


Rating
(A)
25
40
63

63
time delayed
80
100
100
time delayed

Width in 18mm SP ways:


2P RMG all ratings: 2.
4P RMG all ratings: 4.

Sensitivity
(mA)
10
10
30
30
300
30
100
300
30
100
300
30
100
300
100

Sensitivity
(mA)
30
300
30
300
30
100
300
300

Part No.
RMG
RMG
RMG
RMG
RMG
RMG
RMG

25
25
40
40
63
63
63

030
300
030
300
030
100
300

4
4
4
4
4
4
4

23146 (50-70mS)
16261
23213

30
300
300

23227

Class A RCD
Rating
(A)
25A 30mA
40A 30mA
63A 30mA

No. of
poles
2
2
2

23249
23253
23258

40A 30mA
63A 30mA

4
4

23303
23308

Y B

Part No.

or

FEED

LOAD

LOAD

FEED

Y B

Accessories
Padlocking
Padlock with 2 keys
Spare key for MGPL

20719
MGPL
MGPLSK

55

Electrical auxiliaries for


2 and 4 pole RMGs
Arrangement of auxiliaries
O
F

O
F

O
F

Auxiliary
switch OF

Undervoltage
trip module MN

Shunt trip
module MX

Auxiliary
switch OF.S

RCD

Shunt trip release (MX)

Enables remote tripping.


Is equipped with a cut-off switch in series with the
coil.
Includes one auxiliary changeover switch (OF).
Red flag trip indicator.
Mounted on the LHS of the OFS.
Cable capacity 2.5mm2.

MX
or
MN

MX
or
MN

MX
or
MN

O
F
S

R
M
G

O
F
S

R
M
G

O
F
S

R
M
G

Notes: both 2P and 4P RMG type residual current


devices can be fitted with the above combinations of
electrical auxiliaries.

No. of
Coil
Consumption
18mm
volt
pickup W or VA
SP ways
1
130dc
10
1
240ac
50
1
415ac
120
1
48-60dc
22
1
48-130ac
200
1
24ac/dc
120
(Also requires OFS 26923)

Part
No.

No. of
Coil
Consumption
18mm
volt
pickup W or VA
SP ways
1
220/240AC 4.1
1
48AC
4.3
1
48DC
2
(Also requires OFS 26923)

Part
No.

No. of
18mm
SP ways
0.5
0.5
Contact ratings (A):
3A at 415V ac
1A at 125V dc
6A at 24V dc
6A at 240V ac
2A at 48V dc

Part
No.

26946
26946
26946
26947
26947
26948

26946

Undervoltage release (MN)

Enables the RCD to be tripped either when the


auxiliary supply voltage drops or by the opening
operation of a normally closed remote pushbutton.
Prevents the rcd from being switched 'ON' again if
the undervoltage release supply is not present.
Red flag trip indicator.
Mounted on the LHS of the OFS.
Cable capacity 2.5mm2.

26960
26961
26962

26960

Auxiliary switch (OFS/OF)

26923

26924

56

A changeover switch which acts as an indicating


or control device to monitor the ON or OFF
positions of an RCD.
The OFS also acts as an adaptor mounted on the
LHS of rcd, between the rcd and any other auxiliaries (additional OF, MX, MN, mounted on LHS of
OFS).
Test function.
Cable capacity 2.5mm2.

OFS
OF

26923
26924

Metal
All insulated

Accessories and enclosures


RMG type residual current devices
Terminal shields.

Two-piece: completely covers terminals (cannot


be fitted to 100A 2 pole unit).
One-piece: completely covers terminals.
Padlocking attachment (not shown).
Padlock (not shown).

Description
Two piece unit for use with 2P
RMG RCD's (except 100A unit)
Two piece unit for use with 4P
RMG RCD's
One piece unit for use with 2P
RMG RCD's (IP30 enclosure)
One piece unit for use with 4P
RMG RCD's (IP30 enclosure)
Padlocking attachment
Padlock with 2 keys
Spare key for MGPL

Part No.
26976
26978
13392
13394
20719
MGPL
MGPLSK

26978

Sealable terminal screw shield

Enables total isolation of the terminal screws.


2P and 4P RMG RCD's only.

Description
For use with 2P and 4P
RMG RCD's (bag of 8 shields)

Part No.
26981

26981

Enclosures
(See page 118 for full range)

G9 enclosure IP30

Made from folded steel, epoxy powder coated.


Degree of protection: IP30.
It consists of:
A back plate with DIN rail,
A cover screwed to the back plate having 25mm
knockouts top and bottom.
Dimensions: see page 156.
For 4P RMG RCDs use 14599.
For 2P RMG RCDs use 99560.

Capacity in
18mm SP ways
4
5
2*-3
*Blanking plate supplied.

Part No.
14599
14603
99560

14599

Mini opale
Impact resistant, all-insulated enclosure self
extinguishing to 650C.
Degree of protection: IP30.
It consists of:
An insulated back plate with integral DlN-rail.
A cover screwed to the back plate,
Four-hole terminal bar (also available separately (Poles) part No. 14901).

Capacity in
18mm SP ways
2
4
6
8

Part No.
13392
13394
13396
13398

13394

Weatherproof mini pragma

10504

Weatherproof enclosures are all-insulated and


made of a high impact resistant thermoplastic
material which is self-extinguishing.
Degree of protection: IP65.
They consist of:
A symmetrical mounting rail with two height
settings.
Cable entry from the top or bottom.
Screwed cover with hinged transparent window.
Optional terminal rails which simply clip into
position - see page 128.

Capacity in
18mm SP ways
1-4
4-8
8-12
Dimensions: see page 163.
Accessories: see page 128.

Part No.
10504
10508
10512

57

Potrebbero piacerti anche